  • Insulation monitoring

    Catalogue

    Vigilohm

    2006

    423E0000_Guilding.fm Page 4 Lundi, 24. juillet 2006 9:35 09

  • 0The Guiding System, the new way to create your electrical installations

    A comprehensive offer of products with consistent design

    The Guiding System is first and foremost a Merlin Gerin product offer covering all electrical distribution needs. However, what makes all the difference is that these products have been designed to operate togheter: mechanical and electrical compatibility, interoperability, modularity, communication.Thus the electrical installation is both optimised and more efficient: better continuity of supply, enhanced safety for people and equipment, guaranteed upgradeability, effective monitoring and control.

    Tools to simplify design and implementation

    With the Guiding System, you have a comprehensive range of tools - the Guiding Tools - that will help you increase your product knowledge and product utilisation. Of course this is in compliance with current standards and procedures.These tools include technical booklets and guides, design aid software, training courses, etc. and are regularly updated.

    For a genuine partnership with you

    Because each electrical installation is unique, there is no standard solution. With the Guiding System, the variety of combinations allows for genuine customisation solutions. You can create and implement electrical installations to meet your creative requirements and design knowledge. You and Merlin Gerins Guiding System form a genuine partnership.

    For more details on the Guiding System,consult www.merlin-gerin.com

  • 0A consistent design of offers from Medium Voltage to Low Voltage

    All Merlin Gerin offers are designed according to electrical, mechanical and communication consistency rules.The products express this consistency by their overall design and shared ergonomics.

    Electrical consistency:

    Each product complies with or enhances system performance at co-ordination level: breaking capacity, Isc, temperature rise, etc. for more safety, continuity of supply (discrimination) or economic optimisation (cascading).The leading edge technologies employed in Merlin Gerins Guiding System ensure high performance levels in discrimination and cascading of protection devices, electrodynamic withstand of switches and current distributors, heat loss of devices, distribution blocks and enclosures.Likewise, inter-product ElectroMagnetic Compatibilty (EMC) is guaranteed.Discrimination guarantees co-ordination between the operating characteristics of serial-connected circuit-breakers. Should a

    fault occurs downstream, only the circuit-breaker placed immediately upstream from the fault will trip.

    Mechanical consistency:

    Each product adopts dimensional standards simplifying and optimising its use within the system.It shares the same accessories and auxiliaries and complies with global ergonomic choices (utilisation mode, operating mode, setting and configuration devices, tools, etc.) making its installation and operation within the system a simpler process.

    Direct connection of the Canalis KT busbar trunking on the Masterpact 3200 A circuit breaker.

    Communication consistency:

    Each product complies with global choices in terms of communication protocols (Modbus, Ethernet, etc.) for simplified integration in the management, supervision and monitoring systems.

    Thanks to the use of standard Web technologies, you can offer your customers intelligent Merlin Gerin switchboards allowing easy access to information: follow-up of currents, voltages, powers, consumption history, etc.

    Guiding Tools for more efficient design and implementation of your installations.

    180E1000_Ver3.1.fm Page 1 Lundi, 24. juillet 2006 11:25 11

    1

  • 0

    SM6Medium voltage switchboard system from 1 to 36 kV

    SepamProtection relays

    MasterpactProtection switchgear from 100 to 6300 A

    TrihalMV/LV dry cast resin transformer from 160 to 5000 kVA

    EvolisMV vacuum switchgear and components from 1 to 24 kV.

    The Technical guide

    These technical guides help you comply with installation standards and rules i.e.:The electrical installation guide, the protection guide, the switchboard implementation guide, the technical booklets and the co-ordination tables all form genuine reference tools for the design of high-performance electrical installations.For example, the LV protection co-ordination guide - discrimination and cascading - optimises choice of protection and connection devices while also increasing markedly continuity of supply in the installations.

    CAD software and tools

    The CAD software and tools enhance productivity and safety.They help you create your installations by simplifying product choice through easy browsing in the Guiding System offers.Last but not least, they optimise use of our products while also complying with standards and proper procedures.

    180E1000_Ver3.1.fm Page 2 Lundi, 24. juillet 2006 11:25 11

    2

  • 0

    CompactProtection switchgear system from 100 to 630 A

    Multi 9

    Modular protection switchgear system up to 125 A

    Prisma Plus

    Functional system for electrical distribution switchboards up to 3200 A

    Pragma CanalisEnclosures for distribution switchboards up to 160 A

    Prefabricated Busbar Trunking from 25 to 4000 A

    PowerLogicPowermanagement

    Training

    Training allows you to acquire the Merlin Gerin expertise (installation design, work with power on, etc.) for increased efficiency and a guarantee of improved customer service.The training catalogue includes beginners courses in electrical distribution, knowledge of MV and LV switchgear, operation and maintenance of installations, design of LV installations to give but a few examples.

    merlin-gerin.com

    This international site allows you to access all the Merlin Gerin products in just 2 clicks via comprehensive range data-sheets, with direct links to:b complete library: technical documents, catalogs, FAQs, brochuresb selection guides from the e-catalogb product discovery sites and their Flash animations.You will also find illustrated overviews, news to which you can subscribe, the list of country contacts

    180E1000_Ver3.1.fm Page 3 Lundi, 24. juillet 2006 11:25 11

    3

  • 4423E2000.PM6 16

  • 5insulation monitoring

    monitoring

    Vigilohm

    page

    1/ presentation 62/ functions and 17characteristics

    3/ installation and 45connection

    4/ catalogue numbers 55

    423E1000.PM6 24/07/06, 9:275

  • 6continuity of supplyContinuity of supply is a need that mustalways be satisfied by electrical installations,along with the protection of life and property.The IT system provides the best guaranteein terms of continuity of supply. Even when afirst insulation fault is present, the installationcan continue to supply power withoutendangering human life. The first fault musthowever be detected and repaired before asecond fault occurs.

    IO31

    6_12

    3D

    B100

    664principle

    Insulation monitoring is provided on ITsystems to detect and indicate insulationfaults as soon as they occur.The basic function is carried out by anInsulation Monitoring Device (IMD), alsoreferred to in certain documentation as apermanent or continuous insulation monitor(PIM or CIM respectively). The monitoringdevice injects a DC or low-frequencyAC voltage between the installation andearth. The insulation resistance is determinedfrom the resulting current. This technique canbe used on all types of installations: AC, DC,rectified, mixed AC/DC, etc.

    measuring, indicating andlocating insulation faultsVigilohm System, with or without acommunication bus, fulfils the followingbasic functions:c measurement of insulation level on alltypes of installationsc manual or automatic locating of insulationfaults.

    Vigilohm System with acommunication busThe communication bus adds the followingpossibilities:c measurement of the insulation resistanceand earth leakage capacitance of eachcircuitc centralisation of fault locatingmeasurements on the IMD display unitsc communication with a supervisor(transmission of measurements andreception of settings).

    Vigilohm: presentationinsulation monitoring and associated functions

    423E1010.PM6 24/07/06, 9:276

  • 7Vigilohm System with acommunication bus

    DB1

    0066

    2

    DB1

    0095

    5

    Vigilohm System without acommunication bus

    XASXAS XLI300 XTU300

    XML308/316 XM300c

    XD301 XD312XRM XL308 / 316XD308c

    vigilohm systemXAS

    d faut

    MERLIN GERINvigilohm systemXLI300

    d faut

    MERLIN GERINvigilohm systemXTU300

    d faut

    MERLIN GERIN

    test

    vigilohm systemXL316

    MERLIN GERIN

    1

    9

    2

    10

    3

    11

    4

    12

    5

    13

    6

    14

    7

    15

    8

    16

    test/reset

    GO

    MERLIN GERIN

    S1

    S2

    P O

    MERLIN GERIN

    S1

    S2

    test

    vigilohm systemXM300c

    MERLIN GERIN

    valeur d'isolement040 KTEST MENU

    vigilohm systemXML316

    MERLIN GERIN

    1

    9

    2

    10

    3

    11

    4

    12

    5

    13

    6

    14

    7

    15

    8

    16

    test

    valeur d'isolement040 KTEST MENU

    vigirex - vigidixMERLIN GERIN

    vigirex - vigidixMERLIN GERIN

    vigirex - vigidixMERLIN GERIN

    XD301vigilohm system

    MERLIN GERIN

    test

    resetM

    M

    50507

    vigilohm systemMERLIN GERIN

    test

    reset

    1 2 3

    4 5 6

    7 8 9

    10 11 12

    XD312

    M

    M

    50536

    vigilohm systemXD308c

    MERLIN GERIN

    test reset

    test

    1 2 3 4 5 6 7 8 on

    vigidixRM 10N

    MERLIN GERIN

    on P12P50P100

    supervision and event logging

    interfaces

    supervisor printer

    insulation monitoring

    insulation fault detection and locating

    sensors

    Vigilohm: presentationVigilohm System with or without a communication bus

    423E1010.PM6 24/07/06, 9:287

  • 8Vigilohm System without acommunication busThis solution offers:c automatic fault detection;c accurate measurements of the insulationlevel for all types of installations.

    vigilohm TR 22A

    MERLIN GERIN

    test

    K

    TR22A

    E188

    12insulation monitoringInsulation monitoring devices inject a DC orlow-frequency AC voltage between theinstallation and earth. The insulationresistance is determined by measuring theresulting leakage current.c Vigilohm EM9 devices use an indicatorlight to signal the presence of an insulationfault within the installation. They aremodular devices (Multi 9 format) designedfor small installations or sub-systemsisolated from earth;c the TR22A and TR22AH (for hospitals)devices detect insulation faults and, inaddition, continuously indicate the value ofthe insulation resistance on a digital display;c the XM200 is part of the Vigilohm Systemrange and can be associated with automaticfault locating devices.

    DB1

    0065

    0

    SM21

    MERLIN GERINvigilhomSM21

    50761

    1414131312121111101099

    AL. REL.OK

    11 22 33 44 55 66 77

    88

    test

    AL. REL.0,5

    1,0

    1,5

    2,0 3,0

    5,0

    7,5

    10

    off on

    M0,25

    0,5

    0,751,0 1,25

    1,5

    1,75

    2,0 SpSa

    E271

    12

    E271

    36off-line insulationmonitoringThe failure of a motor to start can haveserious consequences. This is especiallytrue in the following applications:c safety equipment (fire pumps, smokeextractors, etc.);c production (glass works, cement plants,etc.);c manufacturing processes (rolling mills, etc.).Motors often fail to start due to insulationproblems caused by the humidity thataccumulates in the microscopic cracks of theinsulation during periods when the motor isnot running. The SM21 device monitors theinsulation of critical motors while they areoff-line. Insulation faults give rise to analarm or motor starting lock-out.

    Vigilohm: presentationVigilohm System without a communication bus

    423E1020.PM6 24/07/06, 9:288

  • 9XRMvig id ix

    RM 10N

    MERLIN GERIN

    on P12P50P100

    test

    vigilohm systemXM100

    MERLIN GERIN

    valeur d'isolement040 KTEST MENU

    XM300C

    Vigilohm: presentationVigilohm System without a communication bus

    Automatic fault locating

    Manual fault locating

    vigilohm systemMERLIN GERIN

    test

    reset

    1 2 3

    4 5 6

    7 8 9

    10 11 12

    XD312

    M

    M

    50536

    test

    vigilohm systemXM200

    MERLIN GERIN

    menu ok test

    R C Sp Sa

    S

    vigidixRM 10N

    MERLIN GERIN

    on P12P50

    P100

    XM200

    XD312

    XRM

    fault locatingOnce detected, an insulation fault must belocated and eliminated in order to guaranteemaximum continuity of supply.Manual fault locatingThe fault is located by testing different pointsin the installation, one after another, using aVigilohm System XRM mobile receiver and acurrent probe. The receiver captures thelow-frequency fault locating signal.Two cases may be encountered:c the installation is equipped with an XM200or XM300C insulation monitoring device(Vigilohm System).In this case, the manual system is used tofine-tune the results of the automaticlocating systemc the installation (relatively small or anisolated sub-system) is equipped with aninsulation monitoring device for DC injection.In this case, a Vigilohm XGR portablegenerator is used together with an XRMreceiver.

    E271

    10D

    B100

    950

    DB1

    1093

    5

    Automatic locating:For easy locating of insulation faults, theVigilohm System makes it possible tocombine the XM200 insulation monitoringdevice with:c XD301/XD312 fault detectors to monitorthe different circuits of the installation;c XRM receivers for mobile fault locating.

    XGR

    XRM

    vigidix

    RM 10N

    MERLIN GERIN

    on P12P50P100

    423E1020.PM6 24/07/06, 9:289

  • 10

    Vigilohm: presentationVigilohm System with a communication bus

    Vigilohm System with acommunication busThe communication bus adds the followingpossibilities:c communication with a supervisor(transmission of measurements andreception of settings)c measure the insulation resistance andearth leakage capacitance of each circuitc centralisation of the locator measurementson the insulation monitoring device displays.

    DB1

    0095

    6

    communication featuresIn addition to displaying the insulation valuesit measures for the installation as a whole, aninsulation monitoring device can also providea centralised display for informationconcerning specific circuits. It receives thisinformation from communicating insulationfault locators and detectors distributedthroughout the installation. All this informationmay also be transmitted to a remotesupervisory system.These communication features satisfy theoperating requirements of modern electricalinstallations. All information concerning theinsulation can be transmitted via acommunication bus for display on acentralised insulation monitoring device or toa supervision system for centralisedprocessing and management.

    prevention of insulationfaultsPrevention is the best way to ensure thecontinuity of supply of electrical installations.It may be applied in two ways:c the insulation monitoring device signals adrop in the insulation resistance below anon-critical prevention threshold determinedby the user;c the measurements are transmitted to asupervisor, which can then process them topredict insulation faults on ageing cables.These indications can be used to schedulepreventive maintenance.

    centralisation on a supervisor

    centralisation on an IMD

    local display

    measurements

    E170

    57E1

    7059

    preventive level

    fault level

    fault prevention

    insulation monitoring and associated functions

    XAS XLI200/XLI300 XTU300

    XML308/316 XM300c

    XD301 XD312 XRM XL308 / 316XD308c

    vigilohm systemXAS

    dfaut

    MERLIN GERINvigilohm systemXLI300

    dfaut

    MERLIN GERINvigilohm systemXTU300

    dfaut

    MERLIN GERIN

    test

    vigilohm systemXL316

    MERLIN GERIN

    1

    9

    2

    10

    3

    11

    4

    12

    5

    13

    6

    14

    7

    15

    8

    16

    test/reset

    GO

    MERLIN GERIN

    S1

    S2

    P O

    MERLIN GERIN

    S1

    S2

    test

    vigilohm systemXM300c

    MERLIN GERIN

    valeur d'isolement040 KTEST MENU

    vigilohm systemXML316

    MERLIN GERIN

    1

    9

    2

    10

    3

    11

    4

    12

    5

    13

    6

    14

    7

    15

    8

    16

    test

    valeur d'isolement040 KTEST MENU

    vigirex - vigidixMERLIN GERIN

    vigirex - vigidixMERLIN GERIN

    vigirex - vigidixMERLIN GERIN

    XD301vigilohm system

    MERLIN GERIN

    test

    resetM

    M

    50507

    vigilohm systemMERLIN GERIN

    test

    reset

    1 2 3

    4 5 6

    7 8 9

    10 11 12

    XD312

    M

    M

    50536

    vigilohm systemXD308c

    MERLIN GERIN

    test reset

    test

    1 2 3 4 5 6 7 8 on

    vigidixRM 10N

    MERLIN GERIN

    on P12P50P100

    supervision and event logging

    interfaces

    supervisor printer

    insulation monitoring

    insulation fault detection and locating

    sensors

    423E1030.PM6 24/07/06, 9:2810

  • 11

    Other functionsc measurement of the true insulationresistancec measurement of the earth leakagecapacitancec indication of transient faultsc prevention alarm when the insulationresistance falls below a non-criticalthreshold determined by the user;c remote interrogation and display, from theinsulation monitoring device, of faultsdetected by the fault locatorsc setting of alarm thresholds from asupervisorc ...The system evolves with the needs of theinstallation. New devices can be added atany time to adapt to installationmodifications or provide higher levels ofmonitoring.

    insensitivity to electricaldisturbancesThe Vigilohm System offers bothmeasurement accuracy and insensitivity toelectrical disturbances. Designed to operateon modern installations, it is not affected bythe harmonics generated by loads such asvariable speed drives, UPSs and switch-mode power supplies.

    easier operation ofIT systemsAn installation implementing the IT system,i.e. isolated from earth or connected to earththrough a sufficiently high impedance, givestop priority to continuity of supply.Today, the operation of such installationscan be greatly facilitated by the use ofdevices that offer functions going far beyondthe simple fault signalling imposed bystandards.

    ... with Vigilohm SystemVigilohm System is a range of Merlin Gerinproducts meeting the needs of IT systems interms of performance, practical operationand continuity of supply.This range features modular design. It ismade up of Insulation Monitoring Devices(IMDs) and fault detection and locatingdevices. Some of these devices makeindependent measurements of the insulationresistance on each circuit.In addition, the Vigilohm System cancommunicate with a supervisor or PLC.

    principle and functionsThe basic device is the InsulationMonitoring Device (IMD). It injects a low-frequency AC voltage between earth and theinstallation. Based on a measurement of theresulting current, the Vigilohm Systemaccurately determines the true insulationresistance of the installation and its earthcoupling capacitance. This technique can beused on all types of installations: AC, DC,rectified, mixed, etc.Fault locating is the main functionassociated with insulation monitoring.Toroids placed on the various circuitscapture a signal proportional to the currentinjected by the insulation monitoring device.This signal is transmitted to fault detectionand locating devices which automaticallyidentify any faulty circuit.Distributed measurements of theinsulation resistance and the earth leakagecapacitance are possible on each circuit viathe toroids used for fault locating.Centralisation on a supervisor. Via acommunication bus using JBUS protocol,the Vigilohm System can forward allmeasurements, information and events to asupervisor. In this way, the supervisormaintains full knowledge on the insulationstatus of the overall installation and theindividually monitored circuits. Thesupervisor (or PLC) can be connected to aprinter to log all events occurring on theinstallation, complete with location andtimestamp.Adaptation to variable installationconfigurations. The system automaticallyexcludes all but one insulation monitoringdevice connected to the same set ofbusbars.

    Vigilohm: presentationVigilohm System:general information

    XM200

    test

    vigilohm systemXM200

    MERLIN GERIN

    menu ok test

    R C Sp Sa

    S

    vigilohm systemMERLIN GERIN

    test

    reset

    XD312

    M

    M

    50536

    XD312

    1 2 3

    4 5 6

    7 8 9

    10 11 12

    From automatic fault locating with local display ...

    E201

    23

    E201

    22

    ... to distributed measurements with centralised display

    supervisorXM300c

    test

    vigilohm systemXM300c

    MERLIN GERIN

    valeur d'isolement1,5 KTEST MENU

    XLI300

    vigilohm systemXLI300

    dfaut

    MERLIN GERIN

    XL316

    test

    vigilohm systemXL308c

    MERLIN GERIN

    test/reset

    1

    9

    2

    10

    3

    11

    4

    12

    5

    13

    6

    14

    7

    15

    8

    16

    valeur d'isolement1,5 K

    insulation resistance

    1.5 KTEST MENU

    insulationresistance1.5 K

    423E1030.PM6 24/07/06, 9:2811

  • 12

    2 locating and measurement devices

    XRM XD301/302 XD308C XL308/316receiver detector detector locator

    1 level of performance

    manual fault locating cautomatic fault locating c v vwith local displayautomatic fault locating c vwith centralised displaydistributed measurements cwith local displaydistributed measurements cwith centralised display

    3 insulation monitoring device

    XM200 c cXM300c v v c cXML308/316 v v v c

    4 XAS, XLI200, XLI300, XTU300

    interfaces c cc device providing only the required functionv device offering additional possibilities or higher performance.

    what devices make up thesystem?c XM200 and XM300C insulation monitoringdevices inject a signal that is used by thedetection and locating devices;c XL308 and XL316 locators, connected to 8or 16 toroids, measure the insulationresistance of each circuit (distributedmeasurements) and, in the event of a fault,automatically identify the faulty circuit.They can transmit this information to asupervisor;c XML308 and XML316 monitoring-locatingdevices combine the monitoring and locatingfunctions in a single unit;c the XD308C communicating insulationfault detector automatically identifies thefaulty circuit and transmits this information toa supervisor;c XD301 and XD312 non-communicatinginsulation fault detectors automaticallyidentify the faulty circuit;c the XRM mobile receiver can be used tofine-tune the automatic locating results byidentifying the faulty circuit at the finaldistribution level;c XLI200, XLI300 and XTU300 interfacesmake communication possible between theVigilohm System and a supervisor;c the XAS interface is used to supply powerto the communication bus.

    Vigilohm: presentationVigilohm System:choosing the system architecture

    how to choose the rightsystem?The right system can be chosen in foursteps, described in detail below:1. define the required level of locating andmeasurement performance.2. select the corresponding locating andmeasurement devices.3. select the insulation monitoring devicescompatible with the locating andmeasurement devices.4. check whether or not an interface isrequired.Note: connect the insulation monitoringdevice to a PHT1000 subassembly if theinstallation voltage U is:c 760 < U < 1700 V AC (neutral distributed);c 440 < U < 1000 V AC (neutral notdistributed);c 550 < U < 1200 V DC (DC or rectifiedvoltage). 1 level of locating and measurementperformanceAccording to your need, select one of thefive possibilities listed in part 1 of the table.The choice depends on:c the required performance of the locatingsystem to be associated with the faultdetection function;c the need for independent insulationmeasurements on each circuit.The five possibilities are (in increasing orderof performance):v manual fault locatingThe fault is located using a mobile receiverconnected to a current probe placed atdifferent points in the installation one afteranother. This type of system isrecommended as an enhancement to theautomatic system in order to determine thefaulty portion of a circuit on which aninsulation fault has been detected.

    v automatic fault locating with localdisplayThe faulty circuit is identified and indicatedon the front face of the fault detector.A contact is provided for remote indications,v automatic fault locating withcentralised displayThe faulty circuit is identified and indicatedon the front face of the fault detector. Theinformation is also transmitted to asupervisor or a PLC,v distributed measurements with localdisplayThe devices measure the insulationresistance on each circuit independently.These measurements can be read on thefront face of the device.Faults are located and displayed locally. Acontact is provided for remote indications,v distributed measurements withcentralised displayThe insulation measurement for each circuitand the indication of the faulty circuit aredisplayed on the front of the device andtransmitted to a supervisor or PLC. 2 selection of the locating andmeasurement devicesOn the line selected in part 1, select the faultlocating or distributed measurement devicein part 2 of the table. 3 selection of the insulation monitoringdeviceSimilarly, determine the insulation monitoringdevices, in part 3 of the table, that arecompatible with the selected locating andmeasurement devices. 4 necessity of an interfaceFor the column selected in part 2 of thetable, part 4 indicates whether or not aninterface is required. If required, theinterface will be selected according to theinstallation and the devices making up thesystem. See the page entitled "choosing thecommunication interface".

    423E1040.PM6 24/07/06, 9:2812

  • 13

    interface

    vigilohm system XAS

    MERLIN GERIN

    dfaut

    test

    vigilohm systemXM300c

    MERLIN GERIN

    valeur d'isolement040 KTEST MENU

    XM300c

    XD312XRM

    XL308/316

    test

    vigilohm systemXL316

    MERLIN GERIN

    1

    9

    2

    10

    3

    11

    4

    12

    5

    13

    6

    14

    7

    15

    8

    16

    test/reset

    MERLIN GERIN

    test

    reset

    XD312

    RM 10N

    MERLIN GERIN

    P12P50

    P100

    Vigilohm: presentationVigilohm System:choosing the fault locating system

    The Vigilohm System offers four faultlocating performance levels.level 1: automatic fault detection andlocating.level 2: automatic fault detection andlocating with transmission to a supervisor.

    level 3: automatic fault detection, locatingand measurement.level 4: automatic fault detection, locatingand measurement with transmission to asupervisor.

    Manual fault locating with the XRM mobilereceiver is generally used to fine-tune theautomatic locating results.

    XM200

    XD312

    test

    vigilohm systemXM200

    MERLIN GERIN

    menu ok test

    R C Sp Sa

    S

    XRM

    RM 10N

    MERLIN GERIN

    P12P50

    P100

    vigilohm systemMERLIN GERIN

    test

    reset

    1 2 3

    4 5 6

    7 8 9

    10 11 12

    XD312

    M

    M

    50536

    E245

    48

    E245

    47

    test

    vigilohm systemXM300c

    MERLIN GERIN

    valeur d'isolement040 KTEST MENU

    IMDinterface

    vigilohm system XAS

    MERLIN GERIN

    dfaut

    supervisor

    printer

    XD308c XD308c

    vigilohm system XD308c

    MERLIN GERIN

    test reset

    test

    1 2 3 4 5 6 7 8 on

    vigilohm system XD308c

    MERLIN GERIN

    test reset

    test

    1 2 3 4 5 6 7 8 on

    XD312

    MERLIN GERIN

    test

    reset

    XD312

    XRM

    RM 10N

    MERLIN GERIN

    P12P50

    P100

    level 1: automatic fault detection and locating

    test

    vigilohm systemXL308c

    MERLIN GERIN

    1

    9

    2

    10

    3

    11

    4

    12

    5

    13

    6

    14

    7

    15

    8

    16

    test/reset

    XL308/316

    interface

    vigilohm system XAS

    MERLIN GERIN

    dfaut

    XD308c

    XD312

    supervisor

    printer

    RM 10N

    MERLIN GERIN

    P12P50

    P100

    XD308c

    MERLIN GERIN

    MERLIN GERIN

    test

    reset

    XD312

    vigilohm systemXML316

    MERLIN GERIN

    1

    9

    2

    10

    3

    11

    4

    12

    5

    13

    6

    14

    7

    15

    8

    16

    test

    valeur d'isolement040 KTEST MENU

    XML308/316

    XRM

    level 4: automatic fault detection, locating and measurement with transmissionto a supervisor.

    level 3: automatic fault detection, locating andmeasurement

    E245

    49

    E245

    50

    level 2: automatic fault detection and locating with transmission to a supervisor.

    423E1040.PM6 24/07/06, 9:2813

  • 14

    four interfacesThe Vigilohm System offers four interfaces:c the XLI200 interface, for the transmissionof information from the insulation monitoringdevice and XD308C detectors to asupervisor or PLC via JBUS. In this way,a PC can access information concerningthe presence of faults and the identificationof the faulty circuit. This interface cannot beused with XL308/316 or XML308/316devices and connects only to the XM300Cand XD308C (the XLI200 cannot be usedwith XML monitoring-locating devices or withXL locating devices).c the XLI300 interface, for the transmissionof measurements and measurementparameters from the XM300C and XD308Cdevices to a supervisor. This interface isused on single busbar installations. The

    IMD associated only one XML308/316 IMD with at least IMD with a leastwith XD308C device 1 locator 1 locatorcommunicating + 1 set of busbars + several setsdetectors, whatever the of busbars withinstallation configuration bus coupling

    without supervision ---- ---- XAS XTU300with supervision XLI200 XLI300 XLI300 XTU300

    Vigilohm: presentationVigilohm System:choosing a communication interface

    the power of acommunicating systemThe power of the Vigilohm System lies in thecapacity it offers for communication betweenall its devices, thereby ensuring insulationmonitoring and complementary functionssuch as automatic locating of faults or theanticipation of their occurrence.In addition, the Vigilohm System is capableof communicating with a supervisor or aPLC, i.e. it can both transmit data to andreceive data from such units.The transfer of information takes place:c via the internal Vigilohm System bus forcommunication between the devices;c via the external JBUS for communicationwith a supervisor or PLC.In both cases, the use of an internal orexternal bus requires a communicationinterface.

    One set of busbars with supervisor

    Several sets of busbars with bus coupling and with or without supervisor

    E207

    91E2

    0792

    interface selection table

    exclusion of other insulation monitoringdevices found on the same installation ismanaged automatically;c the XTU300 interface, for communicationbetween the Vigilohm System and asupervisor, like the XLI300 interface. Thisinterface is required for installations withmultiple busbars and bus coupler circuitbreakers. It manages the exclusion of otherinsulation monitoring devices found on thesame installation and the link between thelocators and their corresponding insulationmonitoring devices;c the XAS interface, indispensable for theoperation of the communication bus in theabsence of one of the three other interfaces.

    One set of busbars without supervisor

    application of the measurement voltageinternal Vigilohm System busJBUS bus

    MV/LV

    XM300c

    supervisoror

    PLC

    XTU300

    MV/LV

    XML308

    XL308

    MV/LV XASMV/LV

    XML308 XM300c

    XL308

    DB1

    0095

    7E2

    0790

    A

    MV/LV

    XLI300

    MV/LV

    XML308 XM300c

    supervisoror

    PLC

    XL308

    XLI200XM300C

    XD308C

    XM300C

    XD308C

    MT/BTMT/BT

    supervisoror

    PLC

    423E1110.PM6 24/07/06, 9:2814

  • 15

    Vigilohm: presentationVigilohm System:two examples of installations

    automatic fault locatingwith or without supervisionThe following examples cover two typicalinstallation configurations with insulationmonitoring and fault locating systems.Example 1:c automatic fault locating with localdisplay.The use of an XM200 insulation monitoringdevice together with XD301 and XD312detectors represents the typical caseproviding basic detection and automaticlocating of insulation faults on the mainfeeders as well as on certain secondaryfeeders.Fault locating can be fine-tuned using anXRM mobile receiver and a current probe todetermine the exact location of the fault onthe faulty circuit.The auto-exclusion of other XM200 insulationmonitoring devices is controlled by the circuitbreaker position indication contacts.

    Example 2:c measurement and automatic faultlocating with local and centraliseddisplay, for an installation with more thanone set of busbars and a bus couplingcircuit breaker.The measurement of the insulationresistance on the main feeders is provided inaddition to fault detection with automaticlocating (XL308/316 and XML308/316).The secondary feeders are monitored simplyby an XD312/301 detector or by an XD308Cdetector that communicates detected faults tothe supervisor (via the XTU300 interface).The architecture of the installation (severalsources and sets of busbars) makes itnecessary to use an XTU300 interface tohandle the exclusion of other insulationmonitoring devices and the link between thelocators and their corresponding insulationmonitoring devices.

    E207

    86E2

    0788

    application of the measurement voltageinternal Vigilohm System busJBUS bus

    MV/LV

    XD312

    XD301 XD301

    MV/LV

    XM200

    XRM

    XM200

    XRM

    XML316

    MV/LV MV/LVG

    XD312

    XL308

    supervisoror

    PLC

    XTU300

    XM300cXML308

    XD308c

    423E1110.PM6 24/07/06, 9:2815

  • 16

    423E2000.PM6 24/07/06, 9:2816

  • 17

    Vigilohm

    2/ functionsand characteristics

    page

    choosing an insulation monitoring devicefor different types of installations 18and associated functions 20

    Vigilhom SystemXM300C insulation monitoring 22deviceXL308 and XL316 insulation 24fault locatorsXML308 and XML 316 monitoring- 26locating devicesXD308C communicating automatic 28insulation fault detectorXLI200, XLI300, XTU300, XAS 29communication interfacesXM200 insulation monitoring 30deviceXD301 and XD312 automatic 32insulation fault detectorsXRM mobile fault locating receiver 33and current probes

    VigilohmTR22A and TR22AH insulation 34monitoring devicesEM9 and EM9B insulation 35monitoring devicesEM9BV insulation monitoring device 36EM9T insulation monitoring device 37TR5A insulation monitoring device 38SM21 insulation monitoring device 39mobile fault locating kitXGR + XRM + probes 40

    toroids 41auxiliaries 43

    insulation monitoring

    423E2000.PM6 24/07/06, 9:2817

  • 18

    Vigilohm: functions and characteristicschoosing an insulation monitoring devicefor different types of installations

    device XM200 XM300C

    Continuity of supply is the requirement that most oftenleads designers to chose the IT system for an electricalinstallation.This requirement may apply to the entire installation(e.g. chemical process plant, steel plant, etc.).Such an installation requires continuous monitoring ofthe insulation level.

    installation characteristics (1)

    440 to1000 V AC* (1)500 to1200 V DC**withPHT 1000subassembly

    iiiii 440 V AC (1)iiiii 500 V DC

    iiiii 440 V AC (1)iiiii 500 V DC

    E273

    41E2

    7336

    E273

    43

    E274

    27MV/LV

    IMD

    PHT 1000

    MV/LVL1L2L3N

    IMDP1

    MV/LVL1L2L3N

    IMD

    L+L-

    The requirement for continuity of supply may apply toonly a part of an installation, for example a single shopor plant, or a circuit subject to special conditions(safety lighting).In this case, it is recommended to use the IT systemfor this part of the installation, whatever the systemused for general distribution.

    In many cases, the use of direct current corresponds toa need for continuity of supply. The use of an ITsystem and insulation monitoring is thereforeconsistent with this choice.

    The use of motors in industrial processes creates a furtherneed for insulation monitoring. By checking the insulationwith power off, the presence of insulation faults can bedetermined before starting motors (fire pumps, smokeextractors, etc.). It is also possible to prevent motor startingautomatically if the insulation resistance is below a certainthreshold.

    iiiii 440 V AC iiiii 440 V AC

    iiiii 500 V DC iiiii 500 V DC500 to1200 V DC**withPHT 1000subassembly

    500 V TR5A500 to 1200 V

    (1) Phase-to-phase voltage with IMD connected to one phase. Multiply these values by e if IMD is connected to neutral.(2) Installation without frequency converter.

    E273

    44E2

    7345

    E273

    37

    E273

    38

    E273

    39

    E273

    46 L1L2L3

    IMD

    M

    PHT 1000 IMD

    +

    MV/LV TN or TTL1L2L3

    machinetool orrobot

    control/monitoring

    IMD LV/LV

    IT

    MV/LV

    IMD

    TN or TT

    LV/LV IT L1L2L3N

    L1L2L3N

    PHT 1000

    IMD

    +

    IMD

    +

    IMD

    044147 044148

    off-line insulation monitoring

    IT system for DC installations

    IT system for part of an installation

    IT system for the entire installation

    423E2010.PM6 24/07/06, 9:2818

  • 19

    TR22A TR22AH EM9 EM9B EM9T TR5A SM21

    iiiii 1 000 V AC(1)with P1subassembly

    iiiii 440 V AC (1)(2)

    iiiii 440 V AC (1)(2)

    iiiii 440 V AC (1)iiiii 500 V DC

    440 to1000 V AC* (1)500 to1200 V DC**withPHT 1000subassembly

    iiiii 440 V AC iiiii 440 V AC iiiii 440 V AC iiiii 440 V AC

    iiiii 220 V AC

    iiiii 420 V DC

    iiiii 690 V AC

    iiiii 440 V AC

    iiiii 500 V DC500 to1200 V DC**withPHT 1000subassembly

    XML308/316

    044149 041850 042580 042582 017422 051346042578043274

    042581

    042580

    EM9BV

    iiiii 440 V AC

    423E2010.PM6 24/07/06, 9:2819

  • 20

    Vigilohm: functions and characteristicschoosing an insulation monitoring deviceand associated functions

    i 690 V AC

    MV/LV

    MV/LV

    HV/MV

    LV/LVMV/LV

    external BUS

    device

    injected signal

    voltage (1) 440 to 1000 V AC

    i 400 V AC

    with rectifiers 440 to 1000 V AC

    i 440 V AC

    for hospitals i 440 V AC

    installation characteristics

    high insulation level i 440 V AC

    low insulation level i 440 V ACi 220 V AC

    24 to 420 V DC

    i 500 V DC

    500 to 1200 V DC

    communication functions

    measurement display

    prevention indication

    insulation fault indication

    manual

    automatic

    automatic + fault measurement

    via JBUS communication bus (and interfaces)

    DC installation

    fault locating

    communication with supervisor

    control andmonitoringof machines

    (1) Phase-to-phase voltage with IMD connected to onephase. Multiply these values by e if IMD is connected toneutral.(2) With PHT 1000 subassembly.

    XM200

    2.5 Hz

    XM300C

    2.5 Hz

    M

    (2)

    (2)

    (2)

    (4) (4)

    (6) (7)

    (8)

    +

    -

    k

    044147 044148

    E273

    28E2

    7329

    E273

    30E2

    7331

    E273

    32E2

    7333

    E273

    35

    IT system for part of an installation

    insulation resistance measurement

    (3) With P1 subassembly.(4) With XRM mobile receiver.(5) With XRM mobile receiver + XGR signal generator

    IT system for the entire installation

    off-line monitoring (LV motors)

    423E2020.PM6 24/07/06, 9:2820

  • 21

    TR22A

    DC

    TR22AH

    DC

    EM9

    DC

    EM9B

    DC

    EM9T

    DC

    TR5A

    NONE

    SM21

    DC

    XML308/3162.5 Hz

    (3)

    (5) (5) (5) (5) (5) (5)(4)

    (7)

    (8)

    (2)

    (2)

    (2)

    042582042580042578043274041850 017422 051346044149

    EM9BV

    DC

    (5)

    0425

    81

    042580

    (6) With XD301/312 detector.(7) With XD301/312 detector or communicating XD308Cdetector.(8) With XL308/316 locator.(9) Remote test possible.

    (9)

    423E2020.PM6 24/07/06, 9:2821

  • 22

    basic function: overallinsulation monitoringThe XM300C provides overall insulationmonitoring of electrical installations byinjecting a low-frequency AC voltagebetween the installation and earth.

    main functionsc measurement:v insulation resistance,v earth leakage capacitance;c indications:v satisfactory insulation resistance (greenlight on bargraph),v drop in insulation resistance: below prevention threshold (orange lighton bargraph and relay actuated), below fault threshold (red light on bargraphand two relays actuated, including one witha failsafe feature),v transient faults (orange light);c display:v measurements,v events detected by any XL308/316locators connected.All this data is accessible locally on the LCDscreen of the insulating monitoring deviceand remotely via the Vigilohm System bus.

    additional functions withother devicesLocating of faulty circuitsThis function is obtained by using theXM300C together with:c XL308 and XL316 locators connected to 8or 16 toroids. They are linked to theXM300C by the Vigilohm System bus;c XD308C communicating detectors. Theyare linked to the XM300C by the VigilohmSystem bus, and connected to the toroidsplaced on the circuits to be monitored;c XD301 and XD312 detectors connected tothe toroids placed on the circuits to bemonitored;c an XRM mobile receiver and a currentprobe to fine-tune the automatic locatingresults.All these devices can be combined on agiven installation.Distributed measurementsThis function is provided by combining anXM300C monitoring device (or anXML308/316 monitoring-locating device)with XL308 or XL316 locators.These locators measure the insulationresistance and the earth leakagecapacitance of each of the circuits.They have a fault alarm threshold that canbe set to a different levels for each channel.

    Vigilohm: functions and characteristicscommunicating Vigilohm SystemXM300C insulation monitoring device

    communicationCommunication with the supervision system.The XLI300 and XTU300 interfaces allowmonitoring devices + locators+ communicating detectors to exchangeinformation with a supervision system viaJBUS protocol.The XLI300 and XTU300 interfaces connectto the Vigilohm System bus and allowtimestamping of insulation monitoringevents.

    configuration managementOn installations with a number of insulationmonitoring devices installed to covervariable configurations, only one device at atime can be allowed to inject a voltagebetween earth and the installationdownstream of the incoming circuit breaker.For this reason, the system must managethe exclusion of other connected insulationmonitoring devices. In addition, each locatormust identify the monitoring device fromwhich it is to capture the signal.The exclusion of monitoring devices andtheir identification by the locators is handledin one of the following manners:c by the XTU300 interface for multiplebusbar installations;c by the XLI300 interface for single busbarinstallations.In both cases, the circuit breaker positionindication contacts are wired to the all-or-nothing inputs of the XM300C orXML308/316.If only XD308C detectors are associatedwith the XM300C, monitoring deviceexclusion is handled by the XLI200 interface.

    standardsThe XM300C insulation monitoring devicecomplies with the following standards:c IEC 364, parts 4 and 5;c class CPI/XA of UTE C 63-080.It is implemented in accordance withstandard NF C 15-100 paragraph 413.4;c IEC 61557-8.

    installation and connectionc horizontal flush mounting on the front faceof a cubicle or enclosure;c easy mounting in Prisma enclosures usingthe corresponding mounting plates and frontplates that come with the appropriatecut-outs;c the devices are interconnected by shieldedcables (double 0.75 mm2 twisted pairs).The resistance between the two most distantpoints must not exceed 12 .The coupling capacitance between pairsmust not exceed 250 nF;c if no XTU300 or XLI300 interface isincluded, operation of the Vigilohm Systembus will require an XAS interface.

    0441

    48D

    B100

    958

    insulation monitoring

    insulationfault detection and locating

    sensors

    interfaces

    XML308/316 XM300c

    vig ilo h m system

    X A S

    d f a u t

    MERLIN GERINvig ilo h m system

    X L I 3 0 0

    d f a u t

    MERLIN GERINvig ilo h m system

    X T U 3 0 0

    d f a u t

    MERLIN GERIN

    test

    v ig ilo h m system

    X L 3 1 6

    MERLIN GERIN

    1

    9

    2

    1 0

    3

    1 1

    4

    1 2

    5

    1 3

    6

    1 4

    7

    1 5

    8

    1 6

    test/reset

    G O

    MERLIN GERIN

    S1

    S2

    P O

    MERLIN GERIN

    S1

    S2

    test

    v ig ilo h m system

    X M 3 0 0 c

    MERLIN GERIN

    valeur d'isolement040 KTEST MENU

    vig ilo h m system

    X M L 3 1 6

    MERLIN GERIN

    1

    9

    2

    1 0

    3

    1 1

    4

    1 2

    5

    1 3

    6

    1 4

    7

    1 5

    8

    1 6

    test

    valeur d'isolement040 KTEST MENU

    v i g i r e x - v i g i d i x

    MERLIN GERIN

    v i g i r e x - v i g i d i x

    MERLIN GERIN

    v i g i r e x - v i g i d i x

    MERLIN GERIN

    X D 3 0 1

    v ig ilo h m s y s te m

    MERLIN GERIN

    t e s t

    r e s e t

    M

    M

    5 0 5 0 7

    v ig ilo h m s y s te m

    MERLIN GERIN

    t e s t

    r e s e t

    1 2 3

    4 5 6

    7 8 9

    1 0 1 1 1 2

    X D 3 1 2

    M

    M

    5 0 5 3 6

    vig ilo h m system

    X D 3 0 8 c

    MERLIN GERIN

    testreset

    test

    1 2 3 4 5 67 8

    on

    v i g i d i x

    R M 1 0 N

    MERLIN GERIN

    o nP 1 2

    P 5 0

    P 1 0 0

    423E2030.PM6 24/07/06, 9:2822

  • 23

    1. display indicating:c the value of the overall insulationresistance R;c other information as selected via functionkeys.2. red self-test light, indicating internalXM300C faults.3. light indicating that a transient fault hasoccurred.4. 5 lights indicating the insulation level.5. instruction manual stored in a drawer onthe front face6. sealable cover ensuring tamperproofsettings.7. function keys for:c accessing earth coupling capacitancereadingsc setting thresholds;c accessing three last values of transientinsulation faults;c remote access to faults detected by XL308or XL316 detectors;c choice of language.

    E195

    27

    XM300C

    MERLIN GERIN

    i

    test

    1 7 6 2 4 5 3

    (1) The upper limit is extended to the second value by adding a PHT1000 subassembly.(2) Failsafe feature: a failsafe relay operates in the event of an accidental interruption of auxiliary power or a fault.(3) This contact is an auxiliary switch mounted on the circuit breaker and used to indicate its operating status.

    type of installation to be monitoredAC or mixed phase-to phase voltageAC/DC IT systems with XM300C connected to neutral < 760 or 1700 V AC (1)

    with XM300C connected to phase < 440 or 1000 V AC (1)frequency 45-400 Hzsize of installation 0 to 30 km of cable

    DC or rectified line voltage < 500 or 1200 V DC (1)IT systemselectrical characteristicsohmmeter digitalrange for insulation resistance readings 0.1 to 999 ksignalling number of thresholds 2 (sealable settings)

    threshold settings 1st threshold (prevent.) 1 to 299 k2nd threshold (fault) 0.2 to 99.9 k

    dielectric strength 2500 Vauxiliary supply voltage 50/60 Hz 115/127 V AC

    220/240 V AC380/415 V AC500/525 V AC

    auxiliary supply voltage tolerances - 15 % to + 10 %maximum device consumption 30 VAmeasurement voltage 6 Vmeasurement current 5 mA max50 Hz/DC impedance 22 kdevice test self-test and manual testfailsafe feature (2) as standardchangeover output contact quantity 3 (1 failsafe)breaking capacity of output AC 400 V p. f. = 0.7 3 Acontacts

    230 V p. f. = 0.7 5 ADC 220 V L/R = 1 ms 0.45 A 120 V L/R = 1 ms 0.65 A 48 V L/R = 1 ms 2.5 A 24 V L/R = 1 ms 10 A

    circuit breaker position indication contacts (3): voltage supplied 24 V(voltage and current supplied by XAS max. current supplied 10 mA (short-circuit)XLI or XTU interfaces)connection cross-sections rigid conductors 1 to 1.5 mm2

    flexible conductors 0.75 to 1.5 mm2

    mechanical characteristicsweight 3.5 kgsheet-metal case (horizontal mounting) disconnectable screw terminal blockdegree of protection flush mounting IP 30other characteristicsinterfacing possible with supervisormulti-language display English/Frenchtamperproof settings protected by access code or sealable covertemperature range operating - 5 C to + 55 C

    storage - 25 C to + 70 C

    auxiliariesCardew surge limiter: page 43.ZX limiting impedance to create animpedance-earthed neutral: page 44.PHT1000 subassembly if the device is tobe used on 1000-1700 V installations:page 44.

    restrictions for useThe XM300C operates by injecting low-frequency signals (2.5 Hz). It should not beused for circuits that include variable speeddrives if this equipment continuouslygenerates a signal with a similar frequency( 5 Hz).

    423E2030.PM6 24/07/06, 9:2823

  • 24

    Vigilohm: functions and characteristicscommunicating Vigilohm SystemXL308 and XL316 insulation fault locators

    basic function: localinsulation fault monitoringUsed together with an XM300C or XML308/316 monitoring device, XL308 and XL316locators monitor the insulation of 8 or 16individual circuits and automatically locateany faults.

    main functionsccccc measurement:v insulation resistance of each monitoredcircuit,v earth leakage capacitance of eachmonitored circuit;ccccc indications:v satisfactory insulation resistance (greenlight),v drop in insulation resistance below faultthreshold (red light and two relays actuated,including one with a failsafe feature). Thefault threshold is adjustable for each of the 8or 16 channels corresponding to themonitored circuits,v transient faults on each of the monitoredcircuits;c display:v faulty circuits are indicated by thecorresponding LEDs (8 or 16 depending onthe model),v a flashing LED indicates a transient faulton the corresponding circuit.

    DB1

    0095

    9

    communicationFaults detected by XL308/316 locators canbe displayed on the insulation monitoringdevice associated with the locator.The information transmitted to the insulationmonitoring device can be transmitted to asupervisor via an XLI300 or XTU300interface connect to the Vigilohm Systembus.

    standardsXL308 and XL316 locators comply with thefollowing standards:c IEC 364, parts 4 and 5;c class DLD/M of UTE C 63-080;They are implemented in accordance withstandard NF C 15-100 paragraph 413.4;c IEC 61557-8.

    toroidsXL308 and XL316 locators operate with typeA and OA toroids.

    installation and connectionc horizontal flush mounting on the front faceof a cubicle or enclosure;c easy mounting in Prisma enclosures usingthe corresponding mounting plates and frontplates that come with the appropriatecut-outs;c the devices are interconnected by shieldedcables (double 0.75 mm2 twisted pairs).The resistance between the two most distantpoints must not exceed 12 .The coupling capacitance between pairsmust not exceed 250 nF;c connection of toroids using twisted,shielded cable (1 pair);c if no XTU300 or XLI300 interface isincluded, operation of the Vigilohm Systembus will require an XAS interface.

    XD301 XD312 XL308 / 316XD308cXRM

    vig ilo h m system

    X A S

    d f a u t

    MERLIN GERINvig ilo h m system

    X L I 3 0 0

    d f a u t

    MERLIN GERINvig ilo h m system

    X T U 3 0 0

    d f a u t

    MERLIN GERIN

    test

    v ig ilo h m system

    X L 3 1 6

    MERLIN GERIN

    1

    9

    2

    1 0

    3

    1 1

    4

    1 2

    5

    1 3

    6

    1 4

    7

    1 5

    8

    1 6

    test/reset

    G O

    MERLIN GERIN

    S1

    S2

    P O

    MERLIN GERIN

    S1

    S2

    test

    v ig ilo h m system

    X M 3 0 0 c

    MERLIN GERIN

    valeur d'isolement040 KTEST MENU

    vig ilo h m system

    X M L 3 1 6

    MERLIN GERIN

    1

    9

    2

    1 0

    3

    1 1

    4

    1 2

    5

    1 3

    6

    1 4

    7

    1 5

    8

    1 6

    test

    valeur d'isolement040 KTEST MENU

    v i g i r e x - v i g i d i x

    MERLIN GERIN

    v i g i r e x - v i g i d i x

    MERLIN GERIN

    v i g i r e x - v i g i d i x

    MERLIN GERIN

    X D 3 0 1

    v ig ilo h m s y s te m

    MERLIN GERIN

    t e s t

    r e s e t

    M

    M

    5 0 5 0 7

    v ig ilo h m s y s te m

    MERLIN GERIN

    t e s t

    r e s e t

    1 2 3

    4 5 6

    7 8 9

    1 0 1 1 1 2

    X D 3 1 2

    M

    M

    5 0 5 3 6

    vig iloh m system

    X D 3 0 8 c

    MERLIN GERIN

    testreset

    test

    1 2 3 4 5 67 8

    on

    v i g i d i x

    R M 1 0 N

    MERLIN GERIN

    o nP 1 2

    P 5 0

    P 1 0 0

    interfaces

    insulation monitoring

    sensors

    insulationfault detection and locating

    0441

    45

    423E2040.PM6 24/07/06, 9:2824

  • 25

    breaking capacity ofoutput contacts

    (1) The upper limit is extended to the second value by adding a PTH1000 subassembly.The same voltage limits apply to both the XL308 and the XL316.

    i

    XL316

    MERLINGERIN

    test/reset

    F/!

    1 2 3 4 5 6 7 8

    9 10 11

    12 13 14 15 16

    +-

    1 9 7 8 5 6 4 32

    DB1

    0095

    4

    1. display indicating measured insulationresistance and earth coupling capacitancevalue.2. light indicating measurement units fordisplayed value (k, F, etc.).3. red self-test light, indicating device faults.4. yellow light indicating that a transient faulthas occurred.5. 2 lights indicating the insulation level:c green light: normal;c red light: insulation resistance below faultthreshold on one of the circuits.6. instruction manual stored in a drawer onthe front face7. function keys for:c accessing earth leakage capacitancereadings;c setting thresholds;c accessing three last values of transientinsulation faults.8. sealable cover ensuring tamperproofsettings.9. lights indicating faulty circuits.

    connection cross-sections

    locator XL308 XL316electrical characteristicsohmmeter digitalrange for insulation resistance readings 0.1 to 999 ksignalling 8 lights (1 per channel) 16 lights (1 per channel)signalling threshold and 1setting range (per channel) fault threshold 0.2 to 99.9 kpolling time 15 seconds per channeldevice test self-test and manual testdielectric strength 2500 Vauxiliary supply voltage 50/60 Hz 115/127 V AC

    220/240 V AC380/415 V AC500/525 V AC

    auxiliary supply voltage tolerances - 15 % to + 10 %maximum device consumption 30 VAindicator and output relay local or from insulation monitoring deviceoutput relays 2 (1 failsafe)

    AC 400 V p.f. = 0.7 3 A 230 V p.f. = 0.7 5 ADC 220 V L/R = 1 ms 0.45 A 120 V L/R = 1 ms 0.65 A 48 V L/R = 1 ms 2.5 A 24 V L/R = 1 ms 10 A

    link with insulation monitoring device via 4-wire communication busrigid conductors 1 to 1.5 mm2flexible conductors 0.75 to 1.5 mm2

    mechanical characteristicsweight 3.5 kgsheet-metal case horizontal mounting

    disconnectable screw terminal blockother characteristicstypes of toroid to be used A and OA (XC compatible)temperature range operating - 5 C to + 55 C

    storage - 20 C to + 70 C

    423E2040.PM6 24/07/06, 9:2825

  • 26

    Vigilohm: functions and characteristicscommunicating Vigilohm SystemXML308 and XML316 monitoring-locating devices

    basic function: overall andindividual circuit insulationmonitoringXML308 and XML316 monitoring-locatingdevices combine the functions of:c the XM300C insulation monitoring device;c XL308 or XL316 insulation fault locators.They monitor the insulation of:v the overall installation by injection of a low-frequency AC voltage between theinstallation and earth,v 8 or 16 individual circuits via detectiontoroids.

    main functionsccccc measurement:v insulation resistance of the overallinstallation and each monitored circuit,v earth leakage capacitance of the overallinstallation and each monitored circuit;c indications:v satisfactory insulation resistance (greenlight),v drop in insulation resistance: for the overall installation, belowprevention threshold (orange light and relayactuated), for the overall installation and eachmonitored circuit, below adjustable faultthreshold (red light and two relays actuated,including one with a failsafe feature),v transient faults on the overall installation(orange light), with storage in memory of thethree last values,v faulty circuit by 8 or 16 indicator lights (1 for each circuit);c display:v measurements,v events detected by any XL308/316locators connected.All this data is accessible locally on the LCDscreen of the insulating monitoring deviceand remotely via the Vigilohm System bus.

    additional functions withother devicesIt is possible to monitor more than 8 or 16circuits by adding any of the followingdevices:c XL308 or XL316 locators that measure theinsulation resistance on each additionalcircuit;c XD308C communicating detectors thatautomatically detect the faulty circuit andcommunicate via an XLI300 or XTU300interface;c XD301 and XD312 detectors thatautomatically detect the faulty circuit andprovide local indications.The communicating detectors and locatorsare connected to the XML308/316 via theVigilohm System bus.

    communicationCommunication with the supervision system.The XLI300 and XTU300 interfaces allowmonitoring devices + locators+ communicating detectors to exchangeinformation with a supervision system viaJBUS protocol.The XLI300 and XTU300 interfaces connectto the Vigilohm System bus and allowtimestamping of insulation monitoring events.

    configuration managementOn installations with a number of insulationmonitoring devices installed to cover variableconfigurations, only one device at a time canbe allowed to inject a voltage between earthand the installation downstream of theincoming circuit breaker. For this reason, thesystem must manage the exclusion of otherconnected insulation monitoring devices. Inaddition, each locator must identify themonitoring device from which it is to capturethe signal.The exclusion of monitoring devices and theiridentification by the locators is handled in oneof the following manners:c by the XTU300 interface for multiple busbarinstallations with bus coupling;c by the XLI300 interface for single busbarinstallations.In both cases, the circuit breaker positionindication contacts are wired to the all-or-nothing inputs of the XM300C orXML308/316.

    standardsThe XML308 and XML316 devices complywith the following standards:c IEC 364, parts 4 and 5;c class CPI/XA and DLD/M of UTE C 63-080.They are implemented in accordance withstandard NF C 15-100 paragraph 413.4;c IEC 61557-8.

    toroidsThe XML308 and XML316 devices operatewith type A and OA toroids. They are alsocompatible with type XS toroids.

    installation and connectionc horizontal flush mounting on the front faceof a cubicle or enclosurec easy mounting in Prisma enclosures usingthe corresponding mounting plates and frontplates that come with the appropriate cut-outs;c the devices are interconnected by shieldedcables (double 0.75 mm2 twisted pairs). Theresistance between the two most distantpoints must not exceed 12 .The coupling capacitance between pairs mustnot exceed 250 nF;c connection of toroids using twisted, shieldedcable (1 pair);c if no XTU300 or XLI300 interface isincluded, operation of the Vigilohm Systembus will require an XAS interface.

    DB1

    0095

    804

    4149

    insulation monitoring

    insulationfault detection and locating

    sensors

    interfaces

    XML308/316 XM300c

    vig ilo h m system

    X A S

    d f a u t

    MERLIN GERINvig ilo h m system

    X L I 3 0 0

    d f a u t

    MERLIN GERINvig ilo h m system

    X T U 3 0 0

    d f a u t

    MERLIN GERIN

    test

    v ig ilo h m system

    X L 3 1 6

    MERLIN GERIN

    1

    9

    2

    1 0

    3

    1 1

    4

    1 2

    5

    1 3

    6

    1 4

    7

    1 5

    8

    1 6

    test/reset

    G O

    MERLIN GERIN

    S1

    S2

    P O

    MERLIN GERIN

    S1

    S2

    test

    v ig ilo h m system

    X M 3 0 0 c

    MERLIN GERIN

    valeur d'isolement040 KTEST MENU

    vig ilo h m system

    X M L 3 1 6

    MERLIN GERIN

    1

    9

    2

    1 0

    3

    1 1

    4

    1 2

    5

    1 3

    6

    1 4

    7

    1 5

    8

    1 6

    test

    valeur d'isolement040 KTEST MENU

    v i g i r e x - v i g i d i x

    MERLIN GERIN

    v i g i r e x - v i g i d i x

    MERLIN GERIN

    v i g i r e x - v i g i d i x

    MERLIN GERIN

    X D 3 0 1

    v ig ilo h m s y s te m

    MERLIN GERIN

    t e s t

    r e s e t

    M

    M

    5 0 5 0 7

    v ig ilo h m s y s te m

    MERLIN GERIN

    t e s t

    r e s e t

    1 2 3

    4 5 6

    7 8 9

    1 0 1 1 1 2

    X D 3 1 2

    M

    M

    5 0 5 3 6

    vig ilo hm system

    X D 3 0 8 c

    MERLIN GERIN

    testreset

    test

    1 2 3 4 5 67 8

    on

    v i g i d i x

    R M 1 0 N

    MERLIN GERIN

    o nP 1 2

    P 5 0

    P 1 0 0

    423E2050.PM6 24/07/06, 9:2826

  • 27

    test

    XML316

    MERLIN GERIN

    i1 2 3 4 5 6 7 89 10 11 12 13 14 15 16

    9 8 10 71 2 3 6 4 5

    E195

    02

    (1) The upper limit is extended to the second value by adding a PHT1000 subassembly.(2) Failsafe feature: a failsafe relay operates in the event of an accidental interruption of auxiliary power or a fault.(3) This contact is an auxiliary switch mounted on the circuit breaker and used to indicate its operating status.

    1. display indicating measurementsconcerning the overall installation or eachmonitored circuit, and informationconcerning the device settings;2. red self-test light, indicating device faults.3. light indicating that a transient fault hasoccurred.4. 5 lights indicating the insulation level.5. instruction manual stored in a drawer onthe front face6. sealable cover ensuring tamperproofsettings.7. function keys for:c accessing earth coupling capacitancereadings;c setting thresholds;c accessing three last values of transientinsulation faults;c reading measurements made on individualcircuits by the internal locator;c remote access to faults detected by XL308or XL316 detectors;c choice of language.8. two indicator lights continuously displaythe insulation level of the overall installation.9. 8 or 16 indicating lights indicate faultycircuits.10. light indicating that a transient fault hasoccurred.

    type of installation to be monitoredAC or mixed phase-to phase voltageAC/DC IT systems with XML308/316 connected to neutral < 760 or 1700 V AC (1)

    with XML308/316 connected to phase < 440 or 1000 V AC (1)frequency 45-400 Hzsize of installation 0 to 30 km of cable

    DC or rectified line voltage < 500 or 1200 V DC (1)IT systemselectrical characteristicsohmmeter digitalrange for insulation resistance readings 0.1 to 999 ksignalling for overall instal. number of thresholds 2 (sealable settings)

    for each circuit number of thresholds 1 (sealable settings)threshold settings for overall instal. 1st threshold (preven.) 1 to 299 k

    instal. and circuits 2nd threshold (fault) 0.2 to 99.9 knumber of toroids that can be connected XML308 8(1 per channel) XML316 16polling time 15 s. per channeldielectric strength 2500 Vauxiliary supply voltage 50/60 Hz 115/127 V AC

    220/240 V AC380/415 V AC500/525 V AC

    auxiliary supply voltage tolerances -15 % to +10 %maximum device consumption 30 VAmeasurement voltage 6 Vmeasurement current 5 mA max.50 Hz/DC impedance 22 kdevice test self-test and manual testfailsafe feature (2) as standardchangeover output contact quantity 3 (1 failsafe)breaking capacity of AC 400 V p.f. = 0.7 3 Aoutput contacts

    230 V p.f. = 0.7 5 ADC 220 V L/R = 1 ms 0.45 A 120 V L/R = 1 ms 0.65 A 48 V L/R = 1 ms 2.5 A 24 V L/R = 1 ms 10 A

    circuit breaker position indication contacts (3): voltage supplied 24 V(voltage and current supplied by XAS, max. current supplied 10 mA (short-circuit)CLI or XTU interfaces)connection cross-sections rigid conductors 1 to 1.5 mm2

    flexible conductors 0.75 to 1.5 mm2

    mechanical characteristicsweight 4.5 kgsheet-metal case (horizontal mounting) disconnectable screw terminal blockdegree of protection flush mounting IP 30other characteristicstypes of toroid to be used A, OA (XS compatible)interfacing possible with supervisormulti-language display English/Frenchtamperproof settings protected by access code or sealable covertemperature range operating - 5 C to + 55 C

    storage - 20 C to + 70 C

    restrictions for useThe XML308/316 operates by injecting low-frequency signals (2.5 Hz). It should not beused for circuits that include variable speeddrives if this equipment continuouslygenerates a signal with a similar frequency( 5 Hz).

    auxiliariesCardew surge limiter: page 43.ZX limiting impedance to create animpedance-earthed neutral: page 44.PHT1000 subassembly if the device is to beused on 1000-1700 V installations: page 44.

    423E2050.PM6 24/07/06, 9:2827

  • 28

    Vigilohm: functions and characteristicscommunicating Vigilohm SystemXD308C communicating automatic insulation fault detector

    test

    XD308C

    MERLIN GERIN

    reset

    1 2 3 4 5 6 7 8

    1 4 5 3 2 6

    1. lights indicating the faulty circuit.2. power on3. general fault indicator light.4. test button for indicator lights.5. device internal fault indication (self-test)6. self-test fault indicator light.

    basic function: localinsulation fault detectionThe XD308C provides 3 functions:c detection of insulation faults;c automatic locating of the faulty circuit,identified by the number of the illuminatedindicating light;c communication of this information to anXLI200 or XLI300 or XTU300 interface fortransmission to a supervisor or PLC.

    operationc XD308C insulation fault detectors are fixedreceivers connected to XM300C or XML308/316 insulation monitoring devices via theVigilohm System communication bus;c the XD308C detector, with 8 channelsconnected to a maximum of 12 toroidsinstalled on different circuits of theinstallation, includes the following featureson its front face:v 8 fault indicator lights corresponding to the8 channels,v 1 general fault indicator light signalling thata fault has occurred,v 1 light indicating the operating status ofthe device,v 2 pushbuttons (self-test and reset).

    E195

    04

    electrical characteristicstype of installation to be monitored low voltage AC 45-400 Hz / DCoperating threshold 2.5 mA at 2.5 Hz (1)polling time 20 s per channelfault indications 8 indicator lightsoperating tests localfunctions tested indicator lights and electronicsclearing of memorised faults local reset on front face

    or remote reset from supervisorauxiliary supply voltage 50/60 Hz 115/127 V AC

    220/240 V AC380/415 V AC500/525 V AC

    auxiliary supply voltage tolerances - 15 % to + 10 %consumption 6 VAdielectric strength 2500 Vconnection with insulation monitoring device via 4-wire Vigilohm System busmechanical characteristicsweight 0.6 kgmetal case with insulated front vertical mountingdegree of protection flush mounting IP 30other characteristicstemperature range storage - 25 C to + 70 C

    operating - 5 C to + 55 Ctypes of toroid to be used A (N and O compatible)(1) The operating threshold of the XD308C detectors is not adjustable. These devices are designed to detect low-impedancefaults. The detection threshold varies between 100 and 2 k depending on the characteristics of the installation.

    0441

    43

    installation and connectionc live parts in a disconnectable metal case;c vertical mounting on front plate;c tunnel terminals for 1.5 mm2 wires;c the devices are interconnected byshielded cables (double 0.75 mm2 twistedpairs). The resistance between the two mostdistant points must not exceed 12 .The coupling capacitance between pairsmust not exceed 250 nF;c if no XTU300 or XLI300 interface isincluded, operation of the Vigilohm Systembus will require an XAS interface.

    toroidsXD308C insulation fault detectors operatewith type A and OA toroids. They are alsocompatible with the older type N and Otoroids.

    DB1

    0095

    9

    XD301 XD312 XL308 / 316XD308cXRM

    vig ilo h m system

    X A S

    d f a u t

    MERLIN GERINvig ilo h m system

    X L I 3 0 0

    d f a u t

    MERLIN GERINvig ilo h m system

    X T U 3 0 0

    d f a u t

    MERLIN GERIN

    test

    v ig ilo h m system

    X L 3 1 6

    MERLIN GERIN

    1

    9

    2

    1 0

    3

    1 1

    4

    1 2

    5

    1 3

    6

    1 4

    7

    1 5

    8

    1 6

    test/reset

    G O

    MERLIN GERIN

    S1

    S2

    P O

    MERLIN GERIN

    S1

    S2

    test

    v ig ilo h m system

    X M 3 0 0 c

    MERLIN GERIN

    valeur d'isolement040 KTEST MENU

    vig ilo h m system

    X M L 3 1 6

    MERLIN GERIN

    1

    9

    2

    1 0

    3

    1 1

    4

    1 2

    5

    1 3

    6

    1 4

    7

    1 5

    8

    1 6

    test

    valeur d'isolement040 KTEST MENU

    v i g i r e x - v i g i d i x

    MERLIN GERIN

    v i g i r e x - v i g i d i x

    MERLIN GERIN

    v i g i r e x - v i g i d i x

    MERLIN GERIN

    X D 3 0 1

    v ig ilo h m s y s te m

    MERLIN GERIN

    t e s t

    r e s e t

    M

    M

    5 0 5 0 7

    v ig ilo h m s y s te m

    MERLIN GERIN

    t e s t

    r e s e t

    1 2 3

    4 5 6

    7 8 9

    1 0 1 1 1 2

    X D 3 1 2

    M

    M

    5 0 5 3 6

    vig iloh m system

    X D 3 0 8 c

    MERLIN GERIN

    testreset

    test

    1 2 3 4 5 67 8

    on

    v i g i d i x

    R M 1 0 N

    MERLIN GERIN

    o nP 1 2

    P 5 0

    P 1 0 0

    423E2060.PM6 24/07/06, 9:2828

  • 29

    Vigilohm: functions and characteristicscommunicating Vigilohm SystemXLI200, XLI300, XTU300 and XAS communication interfaces

    useWhen two or more communicating devices(XM300C, XML308/316, XL308/316 orXD308C) are used or when communicationwith a supervisor is required, it is necessaryto connect one (and only one) interface tothe communication bus.If no XTU300 or XLI300 interface isincluded, operation of the Vigilohm Systembus will require an XAS interface.

    functionsThe interface allows communicationbetween the Vigilohm System and asupervisor or PLC using a JBUS typeprotocol (except X25).It transmits the information provided by theVigilohm System:c prevention and fault alarms from XM300Cor XML308/316 monitoring devices (onlyXM300C for XLI200);c fault alarms from XML308/316 orXM308/316 locators (except XLI200);c insulation resistance and capacitancemeasurements;c threshold settings;c fault alarms and faulty circuit identificationfrom XD308C detectors.The interface also allows the thresholds tobe set form the supervisor.

    0441

    46

    device XLI200 XLI300 XTU300 XASfunctioninterface between the Vigilohm System bus and a supervisor or PLC c c cpower supply to Vigilohm System bus c c c coperates with monitoring device XM300C c c c c

    mon.-loc. device XML308/316 c c clocator XL308/316 c c cdetector XD301/312

    XD308C c c c cmaximum configuration monitoring device XM300C and/or XML308/316 4 (1) 4 4 4

    locator XL308/316 8 8detector XD308C 16 8 8 8

    electrical characteristicsauxiliary supply voltage 50/60 Hz 220/240 V AC 115/127 V AC 115/127 V AC 115/127 V AC

    380/415 V AC 220/240 V AC 220/240 V AC 220/240 V AC380/415 V AC 380/415 V AC 380/415 V AC500/525 V AC 500/525 V AC 500/525 V AC

    consumption 30 VA c c c cdielectric strength 2500 V c c c cmechanical characteristicsweight gross 2.228 kg 2.228 kg 2.228 kg

    net 1.864 kg 1.864 kg 1.864 kgmetal case with insulated front c c c cdegree of protection IP30degree of protection of front IP40other characteristicsinterfacing possible with supervisor c c cJBUS connector Sub D 9-pin (not supplied) c c ccommunication with other devices via 4-wire data bus c c c ctemperature range storage - 25 C to + 70 C

    operation - 5 C to + 55 Cinstallationvertical mounting on front plate c c c cconnectionVigilohm System bus 1.5 mm2 tunnel terminals c c c cexternal bus RS485 sub D9 female connector c c ccommunicationspeed (bauds) adjustable 300... 19200 300... 19200 300... 19200

    per fault 9600 9600 9600data length (bits) 8 8 8parity none none nonestart bits 1 1 1stop bits 1 1 1(1) only XM300C.

    423E2060.PM6 24/07/06, 9:2829

  • 30

    Vigilohm: functions and characteristicsVigilohm SystemXM200 insulation monitoring device

    standardsThe XM200 insulation monitoring devicecomplies with the following standards:c IEC 364, parts 4 and 5;c class CPI/XA of UTE C 63-080.It is implemented in accordance withstandard NF C 15-100 paragraph 413.4;c IEC 61557-8.

    operating voltagec AC IT systems up to:v 440 V with neutral not distributed,v 760 V with neutral distributed;c DC systems up to 500 V.The XM200 cannot be adapted toinstallations with higher voltages byconnecting it to a PHT1000 subassembly.For higher voltage, use an XM300C.

    installationc horizontal flush mounting on the front faceof a cubicle or enclosure;c easy mounting in Prisma enclosures usingthe corresponding mounting plates and frontplates that come with the appropriatecut-outs.

    auxiliariesCardew surge limiter: page 43.ZX impedance: page 44.

    restrictions for useThe XM200 operates by injecting low-frequency signals (2.5 Hz). It should not beused for circuits that include variable speeddrives if this equipment continuouslygenerates a signal with a similar frequency( 10 Hz).

    basic function: overallinsulation monitoringThe XM200 provides overall insulationmonitoring of electrical installations byinjecting a low-frequency AC voltagebetween the installation and earth.

    main functionsc measurement:v insulation resistance,v earth leakage capacitance;c indications:v satisfactory insulation resistance (greenlight),v drop in insulation resistance: below prevention threshold (orange lightand failsafe relay actuated), below fault threshold (red light and relayactuated),v transient faults (orange light);c display:v measurements accessible locally on thedisplay unit of the device,v value of the last transient fault.

    additional functions withother devicesIdentification of faulty circuitsThis function is obtained by using theXM200 together with XD301/XD312automatic insulation fault detectors.In addition, an XRM mobile receiver and acurrent probe can be used to determine theexact location of the fault on the faultycircuit.

    E245

    54 insuation monitoring

    insulation faultdetection and locating

    sensors

    XD301vigilohm system

    MERLIN GERIN

    test

    resetM

    M

    50507

    vigilohm systemMERLIN GERIN

    test

    reset

    1 2 3

    4 5 6

    7 8 9

    10 11 12

    XD312

    M

    M

    50536

    vigidixRM 10N

    MERLIN GERIN

    on P12P50

    P100

    test

    vigilohm systemXM200

    MERLIN GERIN

    menu ok test

    R C Sp Sa

    S

    XM200

    vigirex - vigidixMERLIN GERIN

    vigirex - vigidixMERLIN GERIN

    vigirex - vigidixMERLIN GERIN

    GO

    MERLIN GERIN

    S1

    S2

    P O

    MERLIN GERIN

    S1

    S2

    0441

    47

    423E2070.PM6 24/07/06, 9:2830

  • 31

    test

    XM200

    MERLIN GERIN

    testokmenu

    R C Sp Sa O

    i

    k k k k SF

    1 6 4 5 32

    1. display indicating:c the value of the overall insulationresistance R;c other information as selected via functionkeys.2. red self-test light, indicating internalXM200 faults.3. light indicating that a transient fault hasoccurred.4. 3 lights indicating the insulation level.5. sealable cover ensuring tamperproofsettings.6. function keys for:c accessing earth coupling capacitancereadings;c setting thresholds;c displaying the value of the last transientinsulation fault;c setting time delays.

    E190

    51 type of installation to be monitoredAC or mixed phase-to phase voltageAC/DC IT systems with XM200 connected to neutral < 760 V AC

    with XM200 connected to phase < 440 V ACfrequency 45-400 Hzsize of installation 0 to 30 km of cable

    DC or rectified line voltage < 500 V DCIT systems

    electrical characteristicsohmmeter digitalrange for insulation resistance readings 0.1 to 999 ksignalling number of thresholds 2 (sealable settings)

    threshold settings 1st threshold (prevent) 10 to 100 k2nd threshold (fault) 0.1 to 20 k

    time delay for signalling 3 settings 0 s,15 s, 30 sdielectric strength 2500 Vauxiliary supply voltage 50/60 Hz 115/127 V AC

    220/240 V AC380/415 V AC500/525 V AC

    auxiliary supply voltage tolerances - 15 % to +10 %maximum device consumption 30 VAmeasurement voltage variable 25 V max.measurement current 3 mA max.50 Hz/DC impedance 33 kdevice test self-test and manual testfailsafe feature (1) as standardoutput contacts changeover quantity 2 (1 failsafe)breaking capacity of AC 400 V p.f. = 0.7 3 Aoutput contacts 230 V p.f. = 0.7 5 A

    DC 220 V L/R = 1 ms 0.45 A120 V L/R = 1 ms 0.65 A48 V L/R = 1 ms 2.5 A24 V L/R = 1 ms 10 A

    connection cross-sections rigid conductors 1 to 1.5 mm2flexible conductors 0.75 to 1.5 mm2

    mechanical characteristicsweight 2.5 kgsheet-metal case (horizontal mounting) disconnectable screw terminal blockdegree of protection flush mounting IP 30other characteristicstamperproof settings behind sealable covertemperature range operating - 5 C to + 55 C

    storage - 25 C to + 70 Cfault locating with other devicesautomatic detectors XD301/312manual mobile receiver XRM + probes(1) Failsafe feature: a failsafe relay operates in the event of an accidental interruption of auxiliary power or a fault.

    423E2070.PM6 24/07/06, 9:2831

  • 32

    insulation fault detectors XD301 XD312electrical characteristicstype of installation to be monitored low voltage AC 45-400 Hz / DCoperating threshold 2.5 mA at 2.5 Hz (1)polling time 20 s 20 s per channelfault indications 1 indicator light 12 channel indicator

    lights (+ 1 general)local tests for indicator lights and output relayclearing of indications reset button on devicelatching of transient fault indications on/off via selectoroutput relay number of contacts 1 failsafe

    AC 400 V p.f. = 0.7 3 A 230 V p.f. = 0.7 5 ADC 220 V L/R = 1 ms 0.45 A 120 V L/R = 1 ms 0.65 A 48 V L/R = 1 ms 2.5 A 24 V L/R = 1 ms 10 A

    auxiliary 50/60 Hz 115/127 V ACsupply voltage 220/240 V AC

    380/415 V AC500/525 V AC

    auxiliary supply voltage tolerances - 15 % to + 10 %consumption 6 VAdielectric strength 2500 Vconnection with insulation monitoring device nonemechanical characteristicsweight 0.3 kg 0.6 kgplastic case horizontal mountingdegree of protection flush/surface mounting IP 30 / IP 20other characteristicstemperature range storage - 25 C to + 70 C

    operating - 5 C to + 55 Ctypes of toroid to be used A, OA (N and O compatible)toroid for direct connection to case 30 and 50 mm none

    type A toroid(1) The operating threshold of the XD301/312 detectors is not adjustable. These devices are designed to detect low-impedancefaults. The detection threshold varies between 100 and 2 k depending on the characteristics of the installation.

    Vigilohm: functions and characteristicsVigilohm System:XD301 and XD312 automatic insulation fault detectors

    basic functionlocal fault detectionXD301 and XD312 insulation fault detectorshave two functions:c fault detection (with respect to the faultthreshold);c automatic locating of the faulty circuit.

    operationc XD301 and XD312 insulation faultdetectors are fixed receivers used with (butnot connected to) XM300C, XML308/316and XM200 insulation monitoring devices.Via measurement toroids, they detect andautomatically locate insulation faultsc the XD312 detector, with 12 channelsconnected to a maximum of 12 toroidsinstalled on different circuits of theinstallation, includes the following featureson its front face:v 12 fault indicator lights corresponding tothe 12 channels,v a selector to enable or disable latching oftransient fault indications until reset;c detector XD301 is a single-channelversion designed for use with onemeasurement toroid.

    installation and connectionc live parts in an insulated case with asealable transparent cover. Width equal to 8(XD301) or 12 (XD312) 9 mm widthmodules;c horizontal flush or surface mounting onDIN rail;c tunnel terminals for 1.5 mm2 wires.

    toroidsXD301 and XD312 insulation fault detectorsoperate with type A and OA toroids. Theyare also compatible with the older type Nand O toroids.

    breaking capacityof output contacts

    MERLIN GERIN

    XD312

    test

    reset

    1 2 3

    4 5 6

    7 8 9

    10 11 12

    1 23 4 5 6

    E195

    00

    1. lights indicating the faulty circuit.2. selector to enable or disable transientfault indication latching3. sealable cover.4. general fault indicator light.5. test button for indicator lights and outputrelay.6. reset button (to clear fault indications).

    0441

    44

    423E2080.PM6 24/07/06, 9:2832

  • 33

    Vigilohm: functions and characteristicsXRM mobile fault locating receiverand current probes

    operationThe XRM mobile receiver, used with acurrent probe, is mainly intended as anenhancement to automatic fault locatingsystems. It can be placed at various pointsalong a faulty circuit, capturing the signalemitted by an XM300C, XML308/316 orXM200 insulation monitoring device todetermine the exact location of the fault.Three current probes are available, theXM15, XP50 and XP100.The set of live conductors to be tested musthave a maximum diameter of 12, 50and 100 mm respectively.

    displayThe XRM receiver displays a numberfrom 0 to 19, corresponding to the insulationlevel:c 0: no fault;c 19: solid fault (no insulation).

    E245

    55

    DB1

    0095

    9

    insulation monitoring

    insulation faultdetection and locating

    sensors

    XD30 XD31 XRM

    X D 3 0 1

    v ig ilo h m s y s te m

    MERLIN GERIN

    t e s t

    r e s e t

    M

    M

    5 0 5 0 7

    v ig ilo h m s y s te m

    MERLIN GERIN

    t e s t

    r e s e t

    1 2 3

    4 5 6

    7 8 9

    1 0 1 1 1 2

    X D 3 1 2

    M

    M

    5 0 5 3 6

    G O

    MERLIN GERIN

    S1

    S2

    P O

    MERLIN GERIN

    S1

    S2

    vig ilo h m system

    X M200

    MERLIN GERIN

    menu ok test

    R C SpS

    test

    v i g i r e x - v i g i d i x

    MERLIN GERIN

    v i g i r e x - v i g i d i x

    MERLIN GERIN

    v i g i r e x - v i g i d i x

    MERLIN GERIN

    v i g i d i x

    R M 1 0 N

    MERLIN GERIN

    o nP 1 2

    P 5 0

    P 1 0 0

    XD301 XD312 XL308 / 316XD308cXRM

    vig ilo h m system

    X A S

    d f a u t

    MERLIN GERINvig ilo h m system

    X L I 3 0 0

    d f a u t

    MERLIN GERINvig ilo h m system

    X T U 3 0 0

    d f a u t

    MERLIN GERIN

    test

    v ig ilo h m system

    X L 3 1 6

    MERLIN GERIN

    1

    9

    2

    1 0

    3

    1 1

    4

    1 2

    5

    1 3

    6

    1 4

    7

    1 5

    8

    1 6

    test/reset

    G O

    MERLIN GERIN

    S1

    S2

    P O

    MERLIN GERIN

    S1

    S2

    test

    v ig ilo h m system

    X M 3 0 0 c

    MERLIN GERIN

    valeur d'isolement040 KTEST MENU

    vig ilo h m system

    X M L 3 1 6

    MERLIN GERIN

    1

    9

    2

    1 0

    3

    1 1

    4

    1 2

    5

    1 3

    6

    1 4

    7

    1 5

    8

    1 6

    test

    valeur d'isolement040 KTEST MENU

    v i g i r e x - v i g i d i x

    MERLIN GERIN

    v i g i r e x - v i g i d i x

    MERLIN GERIN

    v i g i r e x - v i g i d i x

    MERLIN GERIN

    X D 3 0 1

    v ig ilo h m s y s te m

    MERLIN GERIN

    t e s t

    r e s e t

    M

    M

    5 0 5 0 7

    v ig ilo h m s y s te m

    MERLIN GERIN

    t e s t

    r e s e t

    1 2 3

    4 5 6

    7 8 9

    1 0 1 1 1 2

    X D 3 1 2

    M

    M

    5 0 5 3 6

    vig iloh m system

    X D 3 0 8 c

    MERLIN GERIN

    testreset

    test

    1 2 3 4 5 67 8

    on

    v i g i d i x

    R M 1 0 N

    MERLIN GERIN

    o nP 1 2

    P 5 0

    P 1 0 0

    interfaces

    insulation monitoring

    sensors

    insulationfault detection and locating

    0513

    50

    XRM receiver

    PB10

    0471

    XP15, XP50 and XP100 current probes.

    Note: the photographs are for information purposes only.There are two types of probes that function in the sameway but are different in shape and colour.

    DB1

    0107

    0

    423E2080.PM6 24/07/06, 9:2833

  • 34

    Vigilohm: functions and characteristicsVigilohm TR22A and TR22AH insulation monitoring devices

    (1) For the TR22A, the upper limit is extended to this value by adding a P1 subassembly. This is not possible for the TR22AH.(2) Failsafe: the relay is disactivated either on occurrence of a fault or if the auxiliary supply voltage accidentally fails.(3) Locating signal changeover switch: this device identifies the faulty feeder during locating by opening each feeder in turn.When the faulty feeder is opened, the alarm sounds.(4) Suitable for use in all climates:c damp heat, equipment not operating (IEC 60068-2-30)c damp heat, equipment operating (IEC 60068-2-56)c salt mist (IEC 60068-2-52).

    type of installation to be monitoredLV AC IT systems phase-to-phase voltage

    with TR22A/AH connected to neutral i 760 V (i 1700 V (1))with TR22A/AH connected to phase i 440 V (i 1000 V (1))frequency 20 to 1000 Hzlimited in size IT subsystem

    electrical characteristicsohmmeter type digital

    reading range 0 to 511 kfault signalling number thresholds 1 (sealable)

    threshold setting TR22A 0.7 to 100 kTR22AH 1 to 251 k

    response time 3 sdevice test operation yes

    thresholds yesfailsafe feature (2) yesoutput changeover quantity 1contact breaking capacity AC 400 V p.f. = 0.7 5 A

    DC 230 V L/R = 1 ms 0.45 A 120 V L/R = 1 ms 0.65 A 48 V L/R = 1 ms 2.5 A 24 V L/R = 1 ms 10 A

    impedance 100 kmaximum current injected 240 Amaximum consumption 5 VAauxiliary supply voltage 50/60 Hz 115/127 V AC

    220/240 V AC380/415 V AC440/480 V AC500/525 V AC

    auxiliary supply voltage tolerances - 15 % to + 10 %locating signal changeover switch (3) yesfront insulation class 2mechanical characteristicsweight 0.8 kgmetal case disconnectable mounting verticalwith insulated frontdegree of protection flush mounted IP 40

    surface mounted IP 40other characteristicstemper