Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will...

40
Catalog 278 Canadian Edition Commercial Unitary Rooftop Units 71/2 to 25 tons Models GCS16-953 . Thru GCS16-3003 Cooling With Gas Heat

Transcript of Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will...

Page 1: Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will operate satisfactori ly down to 45 F (7.2 C) outdoor air temperature without additional

Catalog 278 Canadian Edition

Commercial Unitary Rooftop Units

71/2 to 25 tons

Models GCS16-953 . Thru GCS16-3003

Cooling With Gas Heat

Page 2: Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will operate satisfactori ly down to 45 F (7.2 C) outdoor air temperature without additional

* ARI standard conditions

GCS16-1353 Model

------­Horizontal (side) Supply and Return Air Installation

Typical Applications

Horizontal (side) Supply and Return Air Installation with OAD16 Outdoor Air Dampers.

with RMF16 Roof Mounting Frame and EMDH16M Economizer Dampers.

Down-Flo Supply and Return Air Installation with RMF16 Roof Mounting Frame.

Down-Flo Supply and Return Air Installation with RMF16 Roof Mounting Frame, REMD16M Economizer Dampers

and RTD11 Ceiling Diffuser.

Page 2 I Catalog 278

"McQuay" is a registered trademark of SnyderGeneral Corporation.

©1994 SnyderGeneral Corporation, Minneapolis, Minnesota.

"Bulletin illustrations cover the general appearance of SnyderGeneral Corporation products at the time of publication and we reserve the right to make changes in design and construction at any time without notice."

(5/94)

Page 3: Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will operate satisfactori ly down to 45 F (7.2 C) outdoor air temperature without additional

Application- GCS16 series all season DX cooling and gas fired heating units are designed for bottom (down-flo) or side (horizon­tal) handling of supply and return air. A separate roof mounting frame mates to the unit base and when flashed into the roof permits weatherproof duct connections and entry into the conditioned area in down-flo applications. The units can also be installed at grade level with horizontal (side) duct connections. A choice of RTD11 step-down or FD11 flush ceiling diffusers are available for combination ceiling supply and return air distribution systems. Optional economizer dampers provide "free cooling" by using outdoor air in lieu of mechanical refrigeration. Thermostat and system controls are not furnished and must be ordered extra. Available as options are W973 control system, electro-mechanical or D300 thermostat control systems. Units are shipped factory as­sembled, piped and wired. Each unit is factory test operated insuring unit dependability. Approvals- The design of the units with the roof mounting frame is C.G.A. certified as combination heating-cooling units for outdoor installation. GCS16-953 & 1353 models have been rated in accordance with ARI Standard 210/240-89. GCS16-953 & 1353 units have been sound rated in accordance with ARI Standard 270-84. GCS16-1603, 1853, 2553 & 2753 units have been rated in accordance with ARI Stan­dard 360-86. GCS16-3003 units have been tested in accordance with test conditions included in ARI Standard 360-86. Units and compo­nents within are bonded for grounding to meet safety standards for servicing required by C.G.A. and Canadian Electrical Codes. Equipment Warranty- Heat exchanger has a limited warranty for a full ten years. Compressors have a limited warranty for a full five years. All other components have a limited warranty for one year. Refer to Limited Warranty included with unit for details. Weather Resistant Cabinet-Rugged cabinet is constructed of heavy gauge galvanized steel. Cabinet is subject to a five station metal wash process resulting in a perfect bonding surface for a paint finish of powder enamel, electrostatically bonded to the metal. Large remov­able cabinet panels allow service access. GCS16-1853-2553-2753-3003 filter access panel is hinged and equipped with quarter turn fasteners. Base section and cabinet panels exposed to conditioned air are lined with thick fiberglass insulation. Electrical inlets are provided in cabinet base and condenser section cabinet panel for wiring entry. Control box with factory installed controls is conveniently located for service access. A low voltage terminal strip is provided in the control box for ease of field wiring connections. Lifting brackets are furnished for ease of handling and rigging. Evaporator coil condensate drain connection extends outside of cabinet for ease of connection. Rugged Tubular Heat Exchanger - Tubular heat exchanger is constructed of aluminized steel for superior resistance to corrosion and oxidation. Curving design allows complete exposure of heating surfaces to supply air stream. Round surfaces create minimum air resistance and allows air to wipe all surfaces for excellent heat transfer. Internal baffles prolong flue gas passage resulting in maximum heat transfer. Compact design reduces space requirement in unit cabinet. Removable cabinet panels allow service access. Heat exchanger has been laboratory life cycle tested. Heating System -Aluminized steel inshot burners provide efficient, trouble free operation and are unaffected by adverse wind or atmo­spheric conditions. Burner venturi mixes air and gas in correct propor­tion for proper combustion. Burners can be removed individually for service. Equipped with direct spark ignition. Spark is intermittent and occurs only when required. Electronic flame sensor controls assure safe and reliable operation. Should loss of flame occur, flame sensor controls will initiate 3 to 5 attempts at re-ignition before locking out unit operation. Redundant automatic dual gas valve has manual shut­off, pressure regulation and provides two stage operation. Induced draft blower prepurges heat exchanger and safely vents flue products. Centrifugal switch proves blower operation before allowing gas valve to open. Induced draft blower only operates during heating cycle. Flame rollout switch protects against loss of combustion air due to flue vent or intake air blockage. Peep hole with cover is furnished in cabinet access panel for flame viewing. Fan and Limit Controls- Factory installed and accurately located. Fan time delay allows blower operation to continue approximately 90 seconds after burner shut-off. Dual limit controls (primary and secondary) have fixed temperature setting and protect heating system from abnormal operating conditions. Refrigeration System- Factory sealed refrigerant system consists of multiple compressors, condenser coil and direct drive fan(s), evaporator coil and belt drive blower, expansion valves, high capacity driers, thermometer wells, high pressure switches and loss of charge switches Refrigerant lines are connected with a full operating charge of refrigerant. GCS16-2553,-2753 & -3003 have liquid and suction line service valves. Factory installed freezestat prevents evaporator coil freeze-up during low ambient operation.lndependent refrigerant circuits provide staging control to fit varying cooling loads.

Copper Tube Evaporator and Condenser Enhanced Fin Coils- Extra large surface area and circuiting of coils provide maximum cooling efficiency, excellent heat transfer and low air resistance. Coils are constructed of precisely spaced ripple-edged aluminum fins fitted to durable copper tubes. Fins are equipped with collars that grip tubing for maximum contact area. Flared shoulder tubing connections and silver soldering provide tight, leakproof joints. Long life cop­per tubing is easy to field service. Coil is thoroughly factory tested under high pressure to insure leakproof construction. The evaporator coil is face split with separate circuits. Each circuit has separate expan­sion valve, compressor and refrigerant charge.

Dependable Compressors- Rugged and reliable compressors are hermetically sealed, suction cooled and overload protected. GCS16-953, -1353,-1603 (2nd stage only) and -1853 units have inter­nal pressure relief valve. Compressors are internally protected from excessive current and temperature. Crankcase heaters are fur­nished on all compressors. GCS16-953 thru -1603 and GCS16-2553 thru -3003 units have two compressors and GCS16-1853 unit has three. Compressor monitor (non-adjustable) prevents compressor operation when outdoor temperature is below 40°F (4°C). In addition, the compressors are installed on resilient rubber mounts in the unit. assuring quiet and vibration free operation .

Powerful Supply Air Blower- Belt drive centrifugal blower delivers large air volume efficiently and with minimum power consumption. Blower wheel is heavy duty, with forward curved blades and double inlet. Wheel is statically and dynamically balanced to eliminate vibration and designed to give maximum air delivery. Bearings are heavy duty, self aligning, permanently sealed and lubricated. Design of motor mounting base permits quick and simple motor change­over, belt tension adjustment or belt changing. Adjustable motor pulley allows for variable speed adjustments. Motor is overload protected. See specifications table for motors and drives available.

Condenser Fan(s)- GCS16-953 models are equipped with a single fan. GCS16-1353thru -3003 have two. Direct drive fan(s) draw large air volumes uniformly through condenser coil and discharges it vertical­ly. Fan orifice design and low fan tip speed keeps operating sound lev­el at a minimum. Uniform air flow through the coil results in high re­frigerant cooling capacity. Fan motor is permanently lubricated and overload protected. Motor is resiliently mounted. Corrosion resis­tant PVC coated steel wire fan guard(s) are furnished.

Air Filters -Disposable frame type two inch (51 mm) thick commercial grade filters are furnished as standard. Filters are readily accessible for service. See dimension drawing. Filter rack is designed to accept one inch (25 mm) thick cleanable filters.

(Must Be Ordered Extra)

Low Ambient Control Kit (Optional)- System will operate satisfactori­ly down to 45°F (7.2°C) outdoor air temperature without additional controls. If air conditioning operation is required at low ambients, a field installed low ambient kit can be added, enabling the unit to operate down to 30°F (-1 °C). Kits must be ordered extra. See Optional Accessories tables.

Timed-Off Control (Optional)- Timed-off control available for field in­stallation. Prevents compressor short-cycling. Automatic reset control will shut the compressor off and hold it off for 5 minutes. Kit (85J14) includes two LB-50709BA controls and must be ordered extra. Furnished as stan­dard on GCS16-1853 thru -3003 units.

Cold Weather Kit {Optional)- Electric heater (86J16) is available to automatically control the minimum temperature in the gas burner com­partment. Heater is C.G.A. certified to allow cold weather operation of unit down to - 60°F (- 50°C) when outdoor temperature is below - 40° F ( 40°C).

RMF16 Roof Mounting Frame (Optional)- Sturdy mounting frame mates to the single package unit and provides an automatic weather sealed rooftop installation. Shipped knocked down for ease of shipping and handling, it is easily field assembled. A nailer strip is secured to the frame sides to facilitate flashing. Approved by National Roofing Contractors Association.

Catalog 278 I Page 3

Page 4: Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will operate satisfactori ly down to 45 F (7.2 C) outdoor air temperature without additional

(Must Be Ordered Extra)

REMD16M Economizer Dampers (Optional)- Economizer consists of: mechanically linked recirculated air dampers and outdoor air dampers, damper motor and controls. Economizers are shipped factory wired and only require plug-in connection. Formed low leakage (less than 3% ) dampers rotate smoothly in nylon bearings. Outdoor air dampers are equipped with stainless steel seals for minimum air leakage. The posi­tioning of the dampers is accomplished with a 24 volt fully modulating spring return damper motor with adjustable minimum damper position switch. Damper motor is controlled by the room thermostat, mixed air controller and solid-state adjustable outdoor air enthalpy control. The enthalpy control allows for 0 to 100% outdoor air (first stage of cooling) to be used for "free cooling" when outdoor humidity and temperature are acceptable. Additionally, an integrated economizer cycle can be accomplished by allowing the outside air dampers to remain open, continuing to admit outside air, and cycling the compressors to provide dehumidification and additional cooling, as needed. The integrated economizer cycle uses only the amount of mechanical cooling necessary. Two cleanable polyurethane media frame filters are furnished for extra air filtering and bird screen protection.

REMD16M-95, 135 & 160 are available for down-flo applications only. Economizer cabinet is constructed of heavy gauge galvanized steel with a powder enamel paint finish electrostatically bonded to the metal and completely insulated with thick fiberglass insulation. Economizer cabinet field installs on the unit cabinet. Provisions have been made in the economizer cabinet for easy field installation of optional GED16 gravity exhaust dampers. See dimension drawings.

REMD16M-185 & -300 are available for down-flo or horizontal applica­tions. Field installed damper assembly slides in cavity provided in unit cabinet. Outdoor air hood field installs over outdoor air damp­ers external to the unit. Gravity exhaust dampers are also furnished forfield installation. See dimension drawings. Horizontal applications require Optional Horizontal Supply and Return Air Kit for duct connec­tion to unit. See Optional Accessories tables. PED16 Power Exhaust Fans (Optionalfor GCS16-1853, -2553, -2753 & -3003 Units Only)- Fans field install on REMD16M-185 & -300 economizers in down-flo applications and must be ordered extra. Fans provide pressure relief and are interlocked to run when return air dampers are closed and supply air blowers are operating. Motors are overload protected. See dimension drawing. EMDH16M Horizontal Economizer Dampers (Optional for GCS16-953, 1353 & 1603 Units Only)-The EMDH 16M horizontal economizer cabi­net section contains recirculated air dampers, outdoor air dampers, damper motor and controls. Economizer section field installs on the unit cabinet. Outdoor air hood is shipped separately and is field installed. Economizer is factory assembled and wired and only requires field plug-in connection. Cabinet is constructed of heavy gauge galva­nized steel with a powdered enamel paint finish electrostatically bonded to the metal. Completely insulated with thick fiberglass insula­tion. Recirculated damper section of cabinet has flanged air openings for ease of duct connection. Formed low leakage (less than 3%) dampers rotate smoothly in nylon bearings. Outdoor air damper blades are equipped with stainless steel seals for minimum air leak­age. The positioning of the dampers is accomplished with a 24 volt fully modulating spring return damper motor with adjustable minimum damper positioner. Damper motor is controlled by the room thermo­stat, mixed air controller and solid-state adjustable outdoor air enthalpy control. The enthalpy control allows for 0 to 100% outdoor air (first stage of cooling) to be used for "free cooling" when outdoor humidity and temperature are acceptable. Additionally, an integrated econo­mizer cycle can be accomplished by allowing the outside air dampers to remain open, continuing to admit outside air, and cycling the com­pressors to provide dehumidification and additional cooling as needed. The integrated economizer cycle uses only the amount of mechanical cooling necessary. Two cleanable polyurethane media frame filters are furnished for extra air filtering and bird screen protection. See dimension drawing. Provisions have been made in the economizer cabinetforeasyfield installation of optional GED16gravityexhaust dampers. Requires Optional Horizontal Supply and Return Air Kit for duct connection to unit. See Optional Accessories tables. GED16 Gravity Exhaust Dampers (Optional)- Optional for use with REMD16M and EMDH16M-95, 135 & 160 economizer damper sections and must be ordered extra. Furnished as standard with REMD16M-185 & -300 Openings are provided in the economizer cabinet for easy field installation. See dimension drawing. Two exhaust dampers are furnished for installation on the economizer section. Rain hoods are also furnished for field installation on 95/135/160 model. Neoprene coated fiberglass dampers prevent blow-back and outdoor air infiltration during off cycle. Bird screen is provided. Exhaust dampers are field installed on the return air duct adjacent to the unit in horizontal applica­tions with REMD16M-185 & -300.

Page 4 I Catalog 278

Differential Enthalpy Control (Optional) -A solid-state return air enthalpy sensor is available to be used with the outdoor air enthalpy control to determine which air has the lowest enthalpy. The air with the lowest enthalpy will be selected. Return air enthalpy sensor (85J15) field installs in the return air section and must be ordered extra.

OAD16 Outdoor Air Damper Section (Optional)- Damper section with factory installed and linked dampers field installs external to the unit cabinet and must be ordered extra. Interchangeable unit cabinet panel with opening for installation is furnished with damper for down-flo air applications. Two-piece cabinet allows access to controls. See unit dimension drawing for location. Damper section field installs in return air duct for horizontal supply and return air applica­tions. A cleanable polyurethane media frame type airfilter is furnished and factory installed. Dampers allow a fixed amount of outdoor air into the system and can be adjusted for air quantities up to 25%. Damper section is available for manual or automatic operation. Manually operated dampers may be adjusted and locked in place for the amount of air desired. Automatic operation is available with the addition of a spring return 3 position damper actuator. Actuator only requires plug-in connection for operation. Automatic OAD16 damper kit (84J56) must be ordered extra.

Horizontal Supply and Return Air Kit (Optional)- Provides horizon­tal supply and return air duct connection to the side of the unit. Kit contains duct connection flanges for field installation on the supply and return air openings, screws for installing, two filler panels for sup­ply and return air openings in the unit base not being used and a filter access panel to replace the existing cabinet panel above the return air opening. Kit must be ordered extra. See Optional Accessories tables.

Propane Conversion Kits (Optional)- For propane models, a field conversion kit is required for changeover from natural gas. Kit is not furnished and must be ordered extra. See Optional Accessories tables.

Bottom Power Entry Kit (Optional for GCS16-953 & 1353)- Field in­stalled kit BPE16-95/135/160 (85J06) is provided for bottom power en­try into the unit within the confines of the roof mounting frame. Bottom power entry is furnished with GCS16-1603 thru -3003 units. Kit contains wiring junction box with cover 6" x 8" x 10" (152mm x 203mm x 254mm), 78" (2.0m) length of armored cable and necessary installing hardware. Galvanized steel junction box with prepunched mounting holes and electrical knockouts installs on electrical inlet openings located in the unit base. Kit must be ordered ext>a. See basic unit dimension drawing.

RTD11 Combination Ceiling Supply and Return Diffuser Assembly (Optional) -Step-down mount diffuser extends slightly below ceiling level and discharges conditioned air out through grilles on all four sides. Aluminum grilles are fitted with double deflection louvers for precise directional control of air flow. Return air enters through the large center grille. Assembly also includes insulated diffuser box with flanges for ease of duct connection, hanging rings for suspending and interior transition to insure low static and even air flow on all four sides. Transition is sealed internally to prevent recirculation. Diffuser assembly is completely factory assembled. Diffuser readily adapts toT-bar ceiling grids and plaster ceilings. Must be ordered extra, see Optional Accessories tables.

FD11 Combination Ceiling Supply and Return Diffuser Assembly (Optionai)-Fiush mount diffuser installs almostflush with the ceil­ing level and discharges conditioned air out through fixed blade lou­vers on all four sides. Fixed blade louvers insure that air flow will be evenly distributed. Return air enters through large center grille. As­sembly also includes insulated diffuser box with flanges for ease of duct connections, support hanger eyelets at the top corners for se­cure installation and interior transition to insure low static and even air flow on all four sides. Transition is sealed internally to prevent recirculation. Diffuser assembly is completely factory assembled. Diffuser readily adapts toT-bar ceiling grids and plaster ceilings. Must be ordered extra, see Optional Accessories tables.

SRT16 Supply and Return Transitions (Optional) - Transitions field install in the roof mounting frame and provide segregated and simple duct connections to supply and return diffuser. Completely insulated gal­vanized steel transitions have flanges for ease of duct connection. Duct from the transitions to the diffuser is not furnished and must be provided by installer. Transitions are completely factory assembled and easily field installed in the roof mounting frame with minimum costs and labor requirements. Must be ordered extra, see Optional Accessories tables. - SRT16-95 used with the RMF16-95 with GCS16-953. - SRT16-135 used with the RMF16-135/160 with GCS16-1353. - SRT16-160 used with the RMF16-135/160 with GCS16-1603. - SRT16-185 used with the RMF16-185 with GCS16-1853. - SRT16-300 used with the RMF16-300 with GCS16-2553,

GCS16-2753 & GCS16-3003 units.

Page 5: Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will operate satisfactori ly down to 45 F (7.2 C) outdoor air temperature without additional

Electro-Mechanical Thermostat and Controls System (Optional) -Two stage heat and two stage cool thermostat (86J40)with dual tem­perature selector levers. Uses subbase (86J42) with manual system switch (Off-Heat-Auto-Cool) and fan switch (Auto-On) or non-switch­ing subbase (86J41). SP11 Remote Status Panel (86J44)or SSP11 Re­mote Switching Status Panel (86J45) is available for observing and controlling unit operation from the conditioned area. A SSP11 Relay Kit (86J46) is required for switching functions ofthe Switching Status Panel. Kit must be ordered extra and field installed. For nite operation the following are available. Single stage heating thermostat (86J53) and non-switching subbase (86J41). For applications without the economizer a Nite Kit (86J54), containing a plug-in relay, is required to override the operation of day thermostat. Two time clocks are available for the system. Automatic 7 day time clock programs a weekly schedule. Any day or days can be omitted. Each day of the week is clearly separated from every other day. Day and nite periods are distinctly marked. When the settings have been made the clock will turn the system on and off. Spaced in 2 hour increments and equipped with battery back-up in case of power outage. 24 hour nite setback time clock automatically programs the system to keep condi­tioned area at a more conservative temperature level (nite setback thermostat setting) during a period of vacancy. Spaced in 15 minute increments and equipped with battery back-up in case of power out­age. See Price Book for time clock selection and catalog numbers. Also available is a Warm Up Kit (86J58) which holds the economizer outdoor air dampers closed during nite heat operation and morning warm up. Cycle Control (85J14) is required with GCS16-953, -1353, & -1603 units. Furnished on GCS16-1853, -2553, -2753 & -3003 units. Control with plug-in connections provides a timed-on and timed-off function to prevent compressor short cycling. See Flow Chart on page 6. W973 Control System (Optional)- Logic Panel (86J66) controls the operation of the economizer dampers and the stages of cooling and heating in response to a signal from the thermostat. To maintain stable temperatures the logic panel balances the conditioned space thermostat demand against the system output. System output is measured by a discharge sensor (furnished with the logic panel) lo­cated in the discharge air duct of the unit. The combined demand and output signals from the sensor determines economizer damper posi­tion and number of cooling or heating stages energized. The logic panel field installs in the unit or in a remote panel located within the conditioned space. W973 Plug-In Relay (furnished with the logic pan­el) is required to adapt the control system to the unit. Two thermo­stats are available for the system. Dual set point room thermostat (86J67) or transmitter (86J68) with a choice of remote sensors. Both have separate heating-cooling locking set points concealed under the cover and do not have indicating thermometer. The room thermostat has integral sensor and installs in the conditioned space. The trans­mitter installs outside the conditioned space with a Room Tempera­ture Sensor (86J63) in the conditioned area or a Return Air Tempera­ture Sensor (86J65) in the return air duct of the unit. Thermostat and transmitter are furnished with a wiring wall plate. Also available is a switching subbase (86J69) with system selector switch (Heat-Auto­Cool-Off) and fan switch (Auto-On). SP11 Remote Status Panel (86J44) or SSP11 Remote Switching Status Panel (86J45) is available for observing and controlling unit operation from the conditioned area. Two time clocks are available for the system. Automatic 7 day time clock programs a weekly schedule. Any day or days can be omitted. Each day of the week is clearly separated from every other day. Day and nite periods are distinctly marked. When the settings have been made the clock will turn the system on and off. Spaced in 2 hour increments and equipped with battery back-up in case of power outage. 24 hour nite setback time clock automatically programs the system to keep the conditioned area at a more conservative tempera­ture level (nite set back thermostat setting) during a period of vacan­cy. Spaced in 15 minute increments and equipped with battery back­up in case of power outage. See Price Book for time clock selection and catalog numbers. Also available is a Warm Up Kit (86J58) which holds the economizer outdoor air dampers closed during nite heat operation and warm up. See Flow Chart on page 6.

T7300 Thermostat and Control System (Optional) - T7300 program­mable thermostat (86J61) has internal or optional remote temperature sensing, touch sensitive keyboard, automatic switching from heat to cool, oF or oc temperature readout, no anticipator, droop/no droop selection, indicator LED's, hour/day programming, override capabilities, time readout, stage status indicators, operational mode readout and battery back-up. Switching subbase (86J62) features selectable output staging up to two heat and two cool, indicator LED's, manual system switch (Heat­Off-Auto-Cool) and fan switch (Auto-On). The subbase also features an auxiliary relay output which controls economizer operation during oc­cupied and unoccupied periods. Also available is a Room Temperature Sensor (86J63) or Room Temperature Sensor (86J64) with 3-hour over­ride and setpoint adjustment for installation in the conditioned area and a Return Air Temperature Sensor (86J65) for installation in the return air duct of the unit. SP11 Status Panel (86J44) is available for checking unit operation from within the conditioned area. See Flow Chart on page 7.

SP11 Remote Status Panel (Optional)-The operation of the unit can be checked at a glance on the Remote Status Panel (86J44) conve­niently located within the conditioned area. Signal lights on the panel indicate "Cool Mode", "Heat Mode", "Compressor 1", "Compressor 2", "No Heat" and "Filter". The Cool Mode signal light is green when lit and indicates economizer damper operation or DX cooling opera­tion for units without the economizer. Heat Mode light is green and reflects heating operation. Compressor 1 and Compressor 2 lights are green when operating and will turn red if there is an operational malfunction. The No Heat and Filter lights will show red and indicate a requirement for service. The following field installed controls are re­quired for use with the status panel and must be ordered extra. Filter Switch Kit (86J47) is required for operation of the filter light. Status Panel Readout Relay Kit is required to interface status panel with unit operation. See flowcharts for kit selection. SSP11 Remote Switching Status Panel (Optional}- The operation of the unit can be controlled and observed on the Switching Status Panel (86J45) conveniently located within the conditioned area. Sig­nal lights on the panel indicate "Cool Mode", "Heat Mode", "Com­pressor 1 ","Compressor 2", "No Heat" and "Filter". The Cool Mode signal light is green when lit and indicates economizer damper opera­tion or DX cooling operation for units without the economizer. Heat Mode light is green and reflects heating operation. Compressor 1 and Compressor 2 lights are green when operating and will turn red if there is an operational malfunction. The No Heat and Filter lights will show red and indicates a requirement for service. Additionally, panel is equipped with a system selector switch (OfF- Heat-Auto- Cool -Emergency Heat) (Heat Pump Only), fan switch (Auto- On) and after hours timer. Fan switch provides a choice of intermittent (Auto) or continuous (On) blower operation. Manually operated after hours timer (0 to 12 hours) overrides night setback controls providing nor­mal operation forti me period set. A momentary push button switch is used to initiate the timer period. The following field installed controls are required for use with the status panel and must be ordered extra. Filter Switch Kit (86J47) is required for operation of the filter light. Status Panel Readout Relay Kit is required to interface status panel with unit operation. See flowcharts for kit selection.

Catalog 278 I Page 5

Page 6: Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will operate satisfactori ly down to 45 F (7.2 C) outdoor air temperature without additional

<J PJ

"" <1> (J)

()

a PJ 0 co 1\)

"' 00

:-JID-

I "'"" r MECHANICAL THERMOSTAT

86J40 \ 2 Heat- 2 Cool

y...

1 wmwG" >-PANEL KIT

86J66 \ 2 Heat 2 Cool

NON SWITCHING SUBBASE

86J41

SWITCHING SUBBASE 86J42

W973 PLUG-IN RELAY

(Furnished)

OPTIONAL ELECTRO-MECHANICAL THERMOSTAT CONTROL SYSTEM NO NO

SSP11 RELAY ....

KIT -+ 86J46 '

T 7 DAY

FILTER TIME -SWITCH CLOCK NO

SSP11 KIT

- SWITCHING 86J47 ~ .. ,. STATUS

+ PANEL 86J45 REQUIRED NON NITE KIT ,, ,, CYCLE CONTROL

SWITCHING (less WARM STATUS PANEL SUBBASE Economizer)

GCS 16-953-953 - -,. - -1353-1603 ~ UP KIT READOUT 86J41 86J54 '

,, 86J58 ,, RELAY KIT • 85J14 SP11 (see below) r------ STATUS t-- With Economizer ,, Furnished on GCS16-1853,

~ PANEL I , NITE -2553,-2753 & 3003 Units 86J44 .. - THERMOSTAT

24 HOUR 1 Heat j 86J53 TIME 1--

~ STATUS PANEL READOUT RELAY KIT I CLOCK

GCS16-953 thru -1603 86J48

~ GCS16-1853 thru -3003 86J51

NO

OPTIONAL W973 CONTROL SYSTEM

ROOM NO THERMOSTAT

NO NO NO

86J67

"

DISCHARGE ROOM if SWITCHING " SP11 , ,,

i-- ... TEMPERATURE .... ... SUBBASE ... ... STATUS .... ... 7 DAY .... ... WARM SENSOR SENSOR - - - TIME UP KIT r-(Furnished) 86J69 PANEL

86J63 ~ 86J44 "' CLOCK " 86J58

'~ ,, REMOTE

SETPOINT

~ ~ 24 HOUR

TRANSMITTER ,, TIME -

86J68 CLOCK SSP11 FILTER STATUS PANEL __., SWITCHING ~~ SWITCH ____. READOUT

STATUS KIT RELAY KIT , PANEL 86J45 86J47 (see below)

RETURN AIR TEMPERATURE I STATUS PANEL READOUT RELAY KIT I

SENSOR GCS16-953 thru -1603 86J48 86J65 GCS16-1853 thru -3003 86J51

Page 7: Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will operate satisfactori ly down to 45 F (7.2 C) outdoor air temperature without additional

NO

OPTIONAL T7300 CONTROL SYSTEM

ROOM TEMPERATURE

SENSOR 86J63

ROOM TEMPERATURE

SENSOR W/OVERRIDE

86J64

RETURN AIR TEMPERATURE

SENSOR 86J65

NO

1 STATUS PANEL 86J44

FILTER SWITCH

KIT 86J47

STATUS PANEL READOUT RELAY KIT GCS16-953 thru -1603 86J48 GCS16-1853thru-3003 86J51

STOP

Page 8: Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will operate satisfactori ly down to 45 F (7.2 C) outdoor air temperature without additional

-

9.0

9.3

8.6

6 lbs. 4 oz. (2.83 kg)

5 lbs. 14 oz. (2.66 kg)

12 X 12 (305 X 305)

2 (1492)

208/230/460v or 575v-3ph

740-1010

7.75 (0.72)

3/8 (9.5) -3

14 (551)

15.67 ( 1.46)

3/8 (9.5)- 2

20 (787)

24 (610)- 4

5300 (2500)

3/4 (560)

660

126,000 (36.9)

98,000 (28.7)

200,000 (58.6)

160,000 (46.9)

80%

126,000 (36.9)

98,000 (28.7)

175,000 (51.3)

142,600 (41.8)

81.5%

3/4 (19)

3/4 (19)

7 (1.7)

11 (2.7)

1 (25.4)

(4) 16 X 20 X 2 (406 X 508 X 51)

i<Sound Rating Number in accordance with ARI Standard 270. *Rated in accordance with ARI Standard 210/240; 95°F (35°F) outdoor air temperature and 80°F (27"C) db/67"F (19°C) wb entering evaporator air. **For Propane units a field conversion kit is required and must be ordered extra. See Optional Accessories table. ***Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. NOTE- High Altitude Derate- For high altitude installation (2,000 to 4,500 feet) (610 to 1372 m) above sea level, units must be derated 10%.

Page 9: Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will operate satisfactori ly down to 45 F (7.2 C) outdoor air temperature without additional

*Sound Rating Number in accordance with ARI Standard 270.

9.0

8.6

8.8

7 lbs. 4 oz. (3.29 kg)

7 lbs. 4 oz. (3.29 kg)

15 X 15 (381 X 381)

2 (1492)

208/230/460v or 575v-3ph

730-950

3 (2238)

208/230/460v or 575v-3ph

730-950

9.46 (0.88)

3/8 (9.5)- 4

20 (787)

(2) 20 (508) 5

6400 (3020)Total

(2) 1/3 (224)

875 Total

170,000 (49.8)

132,500 (38.8)

270,000 (79.1)

216,000 (63.3)

80%

170,000 (49.8)

132,500 (38.8)

1{8.50

1{8.8

10

7 lbs. 12 oz. (3.52 kg)

3 (2238)

208/230/460v or 575v-3ph

730-950

3/8 (9.5) -3

12 (472)

3/8 (9.5) -2

20 (787)

7700 (3635)Total

(2) 1/2 (224)

1050 Total

132,500 (38.8)

270,000 (79.1)

216,000 (63.3)

80%

170,000 (49.8)

132,500 (38.8)

236,250 (69.2)

192,500 (56.4)

81.5%

3/4 (19)

635 X 25)

*Rated in accordance with ARI Standard 210/240 or "i\:360; 95'F (35'F) outdoor air temperature and 80'F (27'C) db/67'F (19'C) wb entering evaporator air. **For Propane units a field conversion kit is required and must be ordered extra. See Optional Accessories table. ***Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. NOTE- High Altitude Derate- For high altitude installation (2,000 to 4,500 feet) (610 to 1372 m) above sea level, units must be derated 10%.

Catalog 278 I Page 9

Page 10: Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will operate satisfactori ly down to 45 F (7.2 C) outdoor air temperature without additional

20,300

8.8

9.6

kg)

7 lbs. 9 oz. (3.43 kg)

7 lbs. 9 oz. (3.43 kg)

3 (2238)

208/230/460v or 575v-3ph

610- 780

208/230/460v or 575v-3ph

770-980

3/8 (9.5) -3

13 (512)

3/8 (9.5)- 2

20 (787)

12,000 Total

(2) 1 (746)

2200 Total

159,900 (46.9)

330,000 (96.7)

264,000 (77.4)

80%

189,600 (55.6)

235,000 (68.9) 330,000 (96.7)

188,000 (55.1) 264,000 (77.4)

80% 80%

3/4 (19)

3/4 (19)

11 (2.7)

1 (25.4)

24 X 24 X 2 (610 X 610 X 51)

pressure. **For Propane units a field conversion kit is required and must be ordered extra. See Optional Accessories table. ***Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. NOTE- High Altitude Derate- For high altitude installation (2,000 to 4,500 feet) (610 to 1372 m) above sea level, units must be derated 10%.

Page 1 0 I Catalog 278

Page 11: Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will operate satisfactori ly down to 45 F (7.2 C) outdoor air temperature without additional

•9.8

10.4

18 lbs. 8 oz. (8.39 kg)

18 lbs. 8 oz. (8.39 kg)

20 X 18 (508 X 457)

5 (3730)

208/230v/460v-3ph or 575v-3ph

660-840

7.5 (5595)

208/230v/460v-3ph or 575v-3ph

750-905

21.0 (1.95)

3/8 (9.5) -3

13 (512)

48.5 (4.51)

3/8 (9.5)- 2

20 (787)

14,000 (6605) Total

(2) 1 (746)

2100 Total

145,000 (42.5) 290,000

116,000 (34.0) 232,000 (68.0)

235,000 (68.9) 470,000 (137.7)

188,000 (55.1) 376,000 (110.2)

80% 80%

164,000 (48.1) 328,000 (96.1)

131,200 (38.4) 262,400 (76.9)

235,000 (68.9) 470,000 (137.7)

188,000 (55.1) 376,000 (110.2)

80% 80%

3/4 (19) 1 (25.4)

3/4 (19) 1 (25.4)

7 (1.7)

11 (2.7)

(2) 1 (25.4)

pressure. **For Propane units a field conversion kit is required and must be ordered extra. See Optional Accessories table. ***Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. •208,000 Btuh (60.9 kW) and 9.6 EER at 208 volts. NOTE- High Altitude Derate- For high altitude installation (2,000 to 4,500 feet) (610 to 1372 m) above sea level, units must be derated 10%.

Catalog 278 I Page 11

Page 12: Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will operate satisfactori ly down to 45 F (7.2 C) outdoor air temperature without additional

t9.1

0 oz. (9.07 kg)

20 lbs. 0 oz. (9.07 kg)

8 (508 X 457)

7.5 (5595)

208/230v/460v-3ph or 575v-3ph 208/230v/460v-3ph or 575v-3ph

660-840 610-780

7.5 (5595) 10 (7460)

208/230v/460v-3ph or 575v-3ph 208/230v/460v-3ph or 575v-3ph

770-980

21.0 (1.95)

3/8 (9.5)- 3

13 (512)

48.5 (4.51)

3/8 (9.5)- 3

16 (630)

(2) 26 (660) - 4

14,500 (6845) Total

(2) 1 (746)

2200 (Total)

290,000 (85.0)

232,000 (68.0)

470,000 (137.7)

376,000 (110.2)

11 (2.7)

(2) 1 (25.4)

are 1

*Rated in accordance with ARI Standard 360; 95°F (35°F) outdoor air temperature and 80°F (2JCC) db/67°F (19°C) wb entering evaporator air; minimum external duct static pressure.

**For Propane units a field conversion kit is required and must be ordered extra. See Optional Accessories table. ***Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. •238,000 Btuh (69.7 kW) and 8.9 EER at 208 volts. NOTE- High Altitude Derate- For high altitude installation (2,000 to 4,500 feet) (610 to 1372 m) above sea level, units must be derated 10%.

Page 12 I Catalog 278

Page 13: Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will operate satisfactori ly down to 45 F (7.2 C) outdoor air temperature without additional

(Must Be Ordered Extra)

(Must Be Ordered Extra)

Catalog 278 I Page 13

Page 14: Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will operate satisfactori ly down to 45 F (7.2 C) outdoor air temperature without additional

Model No.

14.8/14.1 (28.9)

130/130 (260.0)

3.7

7.3

2

1492

7.5

41.0

50

44.0

~nit~o;/J~~~fact8r .88 "' ~': i -~ ' " '\ '' ' ''' '', '

*Refer to Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. NOTE- Extremes of operating range are plus and minus 10% of line voltage.

2

17.3/17.3 (34.6)

150/150 (300.0)

2.1/2.1 (4.2)

5.1/5.1 (10.2)

3

2238

10.6

58.0

60

54.0

.88 .88

2

460v

9.6/9.6 (19.2)

73/73 (146.0)

1.2/1.2 (2.4)

2.7/2.7 (5.4)

3

1492 2238

3.4 4.8

20.4 26.8

35 35

28.0 29.0

.88 .88

2

575v

7.0/7.0 (14.0)

50/50 (100.0)

1.0/1.0 (2.0)

2.3/2.3 (4.6)

3

1492 2238

3.3 3.9

16.2 23.4

30 30

22.0 22.0

.88 .88

*Refer to Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. NOTE- Extremes of operating range are plus and minus 10% of line voltage.

Page 14 I Catalog 278

7.7(7.1 (14.8)

64/64 (128.0)

1.9

3.7

2

1492

3.4

20.4

25

23.0

.88

208/230v

27.1/17.9 (45.0)

183/150 (323.0)

3.0/3.0 (6.0)

6.2/6.2 (12.4)

3

2238

10.6

58.0

90

69.0

.88

460v

14.2/10.0 (24.2)

91/73 (164)

1.5/1.5 (3.0)

3.4/3.4 (6.8)

3

2238

4.8

26.8

45

36.0

.88

6.4/5.8 (12.2)

52/52 (104.0)

1.6

3.4

2

1492

2.7

16.2

20

19.0

.88

575v

11.2/8.6 (19.8)

73/50 (123.0)

1.2/1.2 (2.4)

2.9/2.9 (5.8)

3

2238

3.9

23.4

35

28.0

.88

Page 15: Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will operate satisfactori ly down to 45 F (7.2 C) outdoor air temperature without additional

ModeiNo .. · GCS16~1853

460v

9.6/9.6/9.6 (28.8)

575v

7.7fi.7/7.7 (23.1)

208/230v

31.0/31.0 (62.0)

GCS16·2553

460v

16.8/16.8 (33.6)

575v

12.3/12.3 (24.6)

124/124 (372.0)

62/62/62 (186.0)

50/50/50 (150.0)

205/205 (410.0)

104/104 (208.0)

78.4/78.4 (156.8)

9.6 4.8 3.0 9.6 4.8 4.0

24.0 12.0 8.9 46.0 23.0 16.8

3 5 3 5 3 5 5 7-1/2 5 7-1/2 5 7-1/2

3730 2238 3730 2238 3730 3730 5595 3730 5595 3730 5595

16.7 4.8 7.6 3.9 6.1 16.7 24.2 7.6 11.0 6.1 9.0

91.0 26.8 45.6 23.4 36.6 105.0 152.0 45.6 66.0 36.6 54.0

(2)- 1/4 (187) (3)- 1/4 (187)

2.8 1.4 1.2 4.2 2.2 2.1

6.5 3.3 2.8 8.7 3.9 3.9

110 50 50 35 40 125 125 60 70 50 50

110 50 50 35 40 125 125 60 70 50 50

95.0 45.0 50.0 35.0 35.0 101.0 108.0 53.0 56.0 40.0 43.0

92.0 43.0 48.0 34.0 34.0 97.0 104.0 51.0 54.0 38.0 41.0

.84 .84 .84 .84 .84 .84 .88 .88 .88 .88 .88 .88

.84 .84 .84 .84 .84 .84 .88 .88 .88 .88 .88 .88

*Refer to Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. NOTE- Extremes of operating range are plus and minus 10% of line voltage.

460v 575v

37.1/37.1 (74.2)

17.8/17.8 (35.6)

15.7/15.7 (31.4)

46.5/46.5 (93.0)

22.2/22.2 (44.4)

18.5/18.5 (37.0)

239.0/239.0 (478.0)

120.0/120.0 (240.0)

111.0/111.0 (222.0)

269.0/269.0 (538.0)

135.0/135.0 (270.0)

92.0/92.0 (184.0)

9.6 4.8 4.0 9.6 4.8 4.0

46.0 23.0 16.0 46.0 23.0 18.0

5 7-1/2 5 7-1/2 5 7-1/2 7-1/2 10 7-1/2 10 7-1/2 10

5595 3730 5595 3730 5595 5595 7460 5595 7460 5595 7460

24.2 7.6 11.0 6.1 9.0 24.2 30.8 11.0 14.0 9.0 11.0

152.0 45.6 66.0 36.6 54.0 152.0 193.0 66.0 84.0 54.0 66.0

(3)- 1/4 (187) (3) -1/4 (187)

4.2 2.2 2.1 4.2 2.2 2.1

8.7 3.9 3.9 8.7 3.9 4.2

150 70 70 60 60 175 175 90 90 70 70

150 70 70 60 60 175 175 90 90 70 70

122.0 55.0 58.0 48.0 51.0 143.0 150.0 68.0 71.0 57.0 59.0

118.0 53.0 56.0 46.0 49.0 139.0 146.0 66.0 69.0 55.0 57.0

*Refer to Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. NOTE- Extremes of operating range are plus and minus 10% of line voltage.

Catalog 278 I Page 15

Page 16: Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will operate satisfactori ly down to 45 F (7.2 C) outdoor air temperature without additional

W973 CONTROL SYSTEM A - Three wire power (See Electrical Data Table) r-----, r-----, B - Seven wire low voltage- DC only OPTIONAL OPTIONAL I

- Five wire low voltage- DC only- with SSP11 I THERMOSTAT I I REMOTE I OR I I TEMPERATURE I

Switching Status Panel TRANSMITTER ~ SENSOR - Seven wire low voltage- DC only- with switching subbase L TI...J ~ L-Jj_...J

C - Two wire low voltage- AC only- with switching subbase C D - Two wire low voltage- DC only E - Nine wire low voltage- AC only F - Two wire low voltage- AC only G - Two wire low voltage- AC only H - Thirteen wire low voltage- AC only J - Two wire low voltage- DC only

AC- Alternating current DC- Direct current

NOTE- Run separate harnesses for AC and DC. AC voltage interferes with DC signals.

-Field wiring not furnished-NOTE- All wiring must conform to CEC and local electrical codes.

r OPTIONAL I I REMOTE SWITCHING I L ~TATU~~E.!:_ ...J

r DiScoNNECT "1 I SWITCH I L~yother~...J

ELECTRO-MECHANICAL THERMOSTAT CONTROL SYSTEM

SINGLE PACKAGE

UNIT

r-----, I T~;:~0~s~~T I

c ft r DiscoNNECT.., I SWITCH I L~yother~...J

A - Three wire power (See Electrical Data Table)

B - Six wire low voltage

r OPTIONAL I I REMOTE SWITCHING I L ~TATUS P~E.!:_ ...J

r-----, I T~::~ooNs~~T I

" 1C rp

roPTIONAL"'l I REMOTE I t.:>TAT~~~':..J

Page 16 I Catalog 278

r o1scoNNECT-, I SWITCH I L~yot~~...J

roPTIONAL"'l I REMOTE I t.:>TATUS~~':..J

SINGLE PACKAGE

UNIT

- Five wire low voltage- with SSP11

Switching Status Panel

C - Nine wire low voltage

D - Two wire low voltage

E - Two wire low voltage

F - Sixteen wire low voltage

-Field wiring not furnished-

NOTE- All wiring must conform to CEC and local electrical codes.

T7300 THERMOSTAT CONTROL SYSTEM

SINGLE PACKAGE

UNIT

A - Three wire power (See Electrical Data Table)

B - Nine wire low voltage

C - Two wire low voltage (T7300 only)

- Seven wire low voltage (T7300 Room Sensor with override)

D - Nine wire low voltage

-Field wiring not furnished-

NOTE- All wiring must conform to CEC and local electrical codes.

Page 17: Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will operate satisfactori ly down to 45 F (7.2 C) outdoor air temperature without additional

NOTE- To determine Sensible Capacity, Leaving Wet and Dry Bulb temperatures not shown in the tables, see Miscellaneous Engineering Data section, page 39.

GCS16-953 COOLING CAPACITY (With One Compressor Only Operating)

NOTE- All values are gross capacities and do not include evaporator coil blower motor heat deduction.

NOTE- All values are gross capacities and do not include evaporator coil blower motor heat deduction.

Catalog 278 I Paga 17

Page 18: Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will operate satisfactori ly down to 45 F (7.2 C) outdoor air temperature without additional

NOTE- To determine Sensible Capacity, Leaving Wet and Dry Bulb temperatures not shown in the tables, see Miscellaneous Engineering Data section, page 39.

GCS16-1603 COOliNG CAPACITY (With One Compressor Only Operating) Outdoor Air Temoerature Enterina Condenser Coil

En~ering T~!:' .· . li.ot. a.l Sensible Total Sensible Total Sensible Wet Bulb Volume · · C r Comp. To Total C r Comp. To Total Comp. To Total Temper- C 00 1~9 Motor Ratio {S/'rJ C 00 1~9 Motor Ratio {S/TI CCa~poalci~,tgy Motor '---'-R:;;a;=ti:..::o,..t;:;.S:.,IT::...!)'--. .;

ature apactty Watts Drv Bulb apactty Watts Dry_ Bulb Watts ' Drv Bulb . · .. ·· .·. mmm Input 75"F 80"F 85~ Input f-7-5....,"F.:;.:..8,_0".:::F=r=85_" __ F+--...----..,.--! Input f-7-5-"F:::r'-180t...:"=o::F;::8=-5-"F-4. ... ·. . l/s .cfm k/W Btuh 24"C 27oc 29ocl!k/WI Btuh 24oc 2;7"C 29oC k/W Btuh 24"C 27"C 29"C

6i:i"F . 28.3 96 700 6830 .68 .79 .90 27.2 92 700 7250 .69 .81 .92 26.0 88 600 7640 .70 .83 .94 • {17.2~C) 29.4 100 500 6980 .71 .83 .94 28.2 96 300 7400 .72 .84 .96 27.0 92 000 7810 .73 .87 .98

.. . • : 2735: 5:800 30.3 103 300 7080 .73 .86 .98 28.9 98 800 7520 .74 .88 1.00 27.6 94 300 7930 .76 .90 1.00

67.;F 1980 ~ 29.7 101 300 7010 .55 .66 .76 28.5 97 300 7440 .55 .67 .77 27.3 93 200 7870 .56 .68 .79 l.l9,4"Cl 2360 ~ 30.8 105 200 7160 .56 .68 .79 29.6 101 000 7610 .57 .69 .81 28.3 96 600 8020 .58 .70 .83

2735 5800 31.7 108200 7280 .57 .70 .83 30.4103900 7720 .58 .72 .84 29.1 99200 8160 .59 .73 .87

-),',,, c,

E~t~ri~g ·. :. WetB.J.tlb·· •Temper· .;.'l'!ture

41.8 43.4 44.5 43.4 45.6 46.8 46.1 47.8 49.0

142 600 148 000 151 800 150 100 155 600 159 800 157,400 163,000 167,200

12 310 .70 .83 12 550 .73 .87 12 730 .76 .90 12 650 .56 .68 12 880 .58 .70 13 070 .59 .73 12,950 .43 .54 13,200 .43 .56 13,390 .44 .58

.94 39.8 136 000 13 010 .72

.97 41.3 141 000 13 250 .75 1.00 42.4 144 700 13 450 .77 .79 42.0 143 400 13 380 .57 .83 43.5 148 600 13 640 .58· .87 44.7 152 500 13 840 .60 .65 44.1 150,600 13 740 .43 .68 45.6 155,800 13,990 .44 .71 46.8 159,600 14,180 .45

NOTE- All values are gross capacities and do not include evaporator coil blower motor heat deduction.

14 800 59.8 204 200 14 960 59.4 202,600 14,910 61.4 209,600 15,110 63.0 215,100 15,270

NOTE- All values are gross capacities and do not include evaporator coil blower motor heat deduction.

Page 18 I Catalog 278

.84 .96 37.9 129 300 13 660 .73 .87 .99

.89 .99 39.2 133 800 13 920 .76 .91 1.00

.92 1.00 40.4 137 800 14 130 .79 .95 1.00

.69 .81 40.0 136 500 14 080 .58 .71 .83

.72 .85 41.4 141 300 14 340 .59 .74 .87

.75 .89 42.5 145 000 14 550 .61 .77 .91

.55 .66 42.1 143,700 14,480 .44 .56 .68

.57 .69 43.5 148,400 14,740 .44 .58 .71

.59 .72 44.6 152,100 14,960 .45 .60 .74

16 860 .73 .91 1.00 17 170 .78 .97 1.00 17470 .82 1.00 1.00

52.2 178 100 17 840 .59 .74 .93 53.5 182 400 18 130 .61 .79 .98 53.4 182,200 18,110 .42 .55 .67 55.3 188,600 18,490 .42 .57 .71 56.7 193,500 18,780 .43 :59 .75

Page 19: Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will operate satisfactori ly down to 45 F (7.2 C) outdoor air temperature without additional

NOTE- To determine Sensible Capacity, Leaving Wet and Dry Bulb temperatures not shown in the tables, see Miscellaneous Engineering Data section, page 39.

85°F (29°C)

Total Comp. Cooling

Cap;:tcity Motor Watts

Of k/W Btuh

Input goc

33.3 110 000 7350 .74 .86 31.0 105 700 8040 .61 .75 .88 35.5 .2 116 800 7500 .79 .94 32.9 112 300 8200 .65 .80 .97 37.2 5.8 122 000 7610 .84 1.00 34.3 117 000 8320 .70 .86 1.00 35.3 34.1 116 300 7500 .60 .71 32.8 112 000 8200 .47 .60 .72 37.6 128 400 36.2 123 600 7640 .62 .77 34.9 119 000 8370 .50 .63 .79 39.2 133 900 37.8 128 900 7750 .66 .83 36.3 123 800 8490 .52 .67 .85 37.3 127,300 36.0 122,800 7630 .48 .58 34.6 118,200 8350 .35 .49 .59 39.6 135,100 38.2 130,400 7770 .50 .62 36.8 125,500 8530 .36 .50 .63 41.2 140,700 39.7 135,600 7880 .52 .66 38.2 130,200 8660 .37 .52 .68

NOTE- All values are gross capacities and do not include evaporator coil blower motor heat deduction.

GCS16-2553 TOTAL COOLING CAPACITY (With Both Compressors Operating)

Catalog 278 I Page 19

Page 20: Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will operate satisfactori ly down to 45 F (7.2 C) outdoor air temperature without additional

NOTE- To determine Sensible Capacity, Leaving Wet and Dry Bulb temperatures not shown in the tables, see Miscellaneous Engineering Data section, page 39.

GCS16-953 BLOWER PERFORMANCE

955 1000 1050 1100 1195 - - - - - - - -- - - - - - - - - - -- - - -- 810 905 (0.63) (0.78) (0.85) (0.93) (1.04) (1.16) (1.45)

1.00 1.20 1.30 1.40 1.55 1.70 970 1015 1060 1105 - - - - ---- - -- - - -- -- - - - - - - - - - -- 840 930

(0.75) (0.90) (0.97) (1.04) (1.16) (1.27)

1.05 1.15 1.35 1.45 1.60 1.70 1.85 995 1035 1075 1115 - - -- ---- - - - - - - - -- - - - ---- 830 870 955

(0.78) (0.86) (1.00) (1.08) (1.19) (1.27) (1.38)

1.20 1.30 1.55 1.65 1.80 1.90 860 905 980 1020 1060 1095 - -- - - - - - ---- ---- - - - - ----

(0.90) (0.97) (1.16) (1.23) (1.34) (1.42)

1.20 1.40 1.50 1.75 1.90 2.00 905 940 1010 1050 1085 ---- ---- ---- - - -- - -- - ---- - - - - - -- -

(0.90) (1.04) (1.12) (1.31) (1.42) (1.49)

1.40 1.60 1.75 2.00 945 980 1045 -- - - - - - - - - - - ---- ---- - -- - ---- ---- - - -- ---- ----

(1.04) (1.19) (1.31) (1.49)

1.65 1.85 2.00 985 1015 ---- ----

(1.23) (1.38) (1.49)

1.90 - - - - - - -- -- - - -- - - - - - - - - - -

Accessory Air Resistance data.

Page 20 I Catalog 278

Page 21: Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will operate satisfactori ly down to 45 F (7.2 C) outdoor air temperature without additional

GCS16-1353 BLOWER PERFORMANCE

---- ---- 672 707 772 802 831 860 887 940 985 (0.85) (0.93) (1.10) (1.19) (1.30) (1.40) (1.49) (1.72) (1.94)

1.27 1.39 1.64 1.78 1.93 2.06 2.20 2.46 2.76 690 725 790 820 850 878 905 950 994

(0.95) (1.04) (1.22) (1.33) (1.44) (1.54) (1.64) {1.84) (2.06)

1.18 1.43 1.54 1.81 1.95 2.09 2.24 2.38 2.66 2.96 715 746 809 838 866 895 920 968 1013

(0.88) (1.07) (1.15) (1.35) (1.45) (1.56) (1.67) (1.78) (1.98) {2.21)

1.35

(1.01)

1.52

(1.13)

1.70

(1.27)

1.93

(1.44)

2.16

(1.61)

2.41

1.59

736

760

785

807

830

860

1.50

(1.12)

1.79

(1.34)

2.00

(1.49)

2.22

(1.66)

2.46

(1.84)

2.75

768

790

815

835

860

887

1.73

(1.29)

1.93

(1.44)

2.15

(1.60)

2.37

(1.60)

2.66

(2.06)

2.89

828

850

872

892

915

2.00

(1.49)

2.29

856

878

2.13

(1.59)

2.36

(1.71) (1.76)

2.44 2.59

885

905

900 923 {1.82) (1.93)

2.66

(1.98)

2.92

(2.18)

918 2.82

{2.10) 940

2.28

(1.70)

2.50

913

930

2.43

(1.81)

2.63

(1.87) (1.96)

2.71 2.84

938

955

948 974 {2.02) (2.12)

2.93

{2.19)

GCS16-1603 BLOWER PERFORMANCE

2.56

(1.91)

2.77

(2.07)

3.00

(2.24)

984 2.86

{2.13)

750 780 840 870 900 930 955 1010 1045 (1.25) (1.32) (1.53) (1.62) (1.72) (1.83) (2.07) (2.28) (2.34)

1.83 1.99 2.24 2.39 2.51 2.67 2.83 3.12 3.39 770 805 860 890 915 945 970 1025 1060

(1.19) (1.41) (1.48 (1.67) (1.78) (1.87) (1.99) (2.11) (2.33) (2.53)

1.78 2.13 2.17 2.45 2.60 2.75 2.89 3.06 3.38 3.62 795 825 880 910 935 960 990 1040 1075

(1.33) (1.59) (1.62) (1.83) (1.94) (2.05) (2.16) (2.39) (2.66) (2.70)

2.00 2.27 2.43 2.70 2.85 3.01 3.26 3.33 3.63 3.87 820 850 905 930 955 980 1010 1055 1090

(1.49) (1.69) (1.81) (2.01) (2.13) (2.25) (2.43) (2.48) {2.71) (2.89)

2.26 2.53 2.68 2.96 3.11 3.27 3.41 3.58 3.94 4.16 845 875 925 950 975 1000 1025 1075 1110

(1.69) (1.89) (2.00) (2.21) {2.32) (2.44) (2.54) {2.67) (2.94) (3.10)

2.50 2.80 2.95 3.25 3.42 3.56 3.75 3.88 4.23 4.46 870 900 950 975 1000 1025 1045 1095 1125

(1.87) (2.09) (2.20) (2.42) (2.55) (2.66) (2.80) {2.89) (3.16) (3.33}

2.79 3.07 3.24 3.55 3.70 3.87 4.09 4.22 4.53 4.81 895 920 970 995 1020 1045 1070 1110 1145

(2.08) (2.29) (2.42) (2.65) (2.76) {2.89) (3.05) (3.15) (3.38) {3.59)

3.08 3.39 3.58 3.88 4.05 4.22 4.37 4.57 4.89 5.16 920 950 995 1020 1045 1065 1090 1130 1165

(2.30) (2.53) (2.67) {2.89) (3.02) (3.15) (3.26) (3.41) (3.65} (3.85)

3.38 3.73 3.90 4.25 4.42 4.57 4.76 4.93 5.25 5.59 945 980 1185

(4.17)

e un1 1 NOTE- Data in shaded area requires field furnished motor and drive.

Catalog 278 I Page 21

Page 22: Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will operate satisfactori ly down to 45 F (7.2 C) outdoor air temperature without additional

GCS16-1853-235 BlOWER PERFORMANCE

Air STATIC PRESSURE EXTERNAL TO UNIT -'-Inches Water Gauge (Pal

Volume .20 (5()J .40 {751 .50 (125) .7() t175) .. 80 1200) ,90(225) 1.00(250} 1.1.0 (275) 1;30 (325} cfm BHP BHP BHP BHP BHP BHP BHP BHP BHP IL/s) RPM RPM RPM RPM .· RPM (kW} RPM RPM RPM RPM

·tkW) (kWl (kW) lkWl {kWl (kWl {kW) !kW)

5000 1.50 1.75 1.80 2.30 2.45 2.65 2.75 2.95 3.15

(2360) 520 580 610 ' 670 690 715 745 770 820

(1.12) (1.31) (1.34) (1.72) (1.83) (1.98} (2.05) (2.20} (2.35}

5200 1.60 1.90 2.00 2.45 2.60 2.75 2.90 3.20 3.35

(24~5)' 540 590 620 680 705 725 755 780 830

.... ·... .· (1.19} (1.42} (1.49} (1.83} (1.94} (2.05} (2.16} (2.39} (2.50}

I. 5400 1.70 2.00 2.25 2.65 2.75 2.85 3.05 3.30 3.50

I (.2550) 550 605 635 690 710 735 760 790 840

..... (1.27) (1.49} (1.68} (1.98} (2.05) (2.13} (2.28} (2.46} (2.61}

5600 1.80 2.25 2.30 2.85 2.90 3.10 3.20 3.40 3.65

(2645} ... 565 615 645 700 720 745 770 800 850 (1.34} (1.68) (1.72} (2.13} (2.16} (2.31} (2.39} (2.54) (2.72)

5800 .•. 2.10 2.40 260 3.00 3.10 3.25 3.40 3.55 3.75

(2735) 580 625 660 710 730 760 780 810 855

(1.57) (1.79} (1.94} (2.24) (2.31} (2.42} (2.54} (2.65} (2.80)

6000 .. 2.30 2.65 2.80 3.20 3.35 3.45 3.60 3.75 4.05

I·· (2~30) 600 650 670 720 745 770 795 820 870 (1.72} (1.98) (2.09) (2.39) (2.50) (2.57) {2.69) {2.80) (3.02) .

6200 2.45 2.85 3.05 3.40 3.50 3.65 3.85 3.95 4.30

610 660 685 730 755 780 805 830 875 (2925} (1.83) (2.13) (2.28) (2.54) (2.61) (2.72) (2.87f (2.95) {3.21) · ..... 64oo · 2.70 3.15 3.30 3.60 3.70 3.95 4.00 4.15 4.45

• (3020) . 625 675 695 740 765 790 815 840 885 (2.01) (2.35) (2.46) (2.69) (2.76} {2.95) (2.98) (3.10) (3.32)

66oo··· 2.95 3.45 3.55 3.75 3.95 4.10 4.25 4.40 4.70

r.(3'lt5l, 640 690 705 755 775 805 825 850 895

.. ·, · .. (2.20) (2.57) (2.65) (2.80) {2.95) (3.06) (3.17) (3.28) (3.51)

• 6800. 3.10 3.65 3.75 4.00 4.20 4.35 4.45 4.65 4.95

655 700 720 765 790 815 835 860 905 ; (;3210[. (2.31) (2.72) (2.80} (2.98} (3.13) (3.25) (3.32) (3.47) (3.69)

·{~~~gl .... 3.50 3.85 4.00 4.35 4.45 4.65 4.75 4.95 670 710 730 780 800 825 845 870 -- - - ----

(2.61) (2.87) (2.98) (3.25) (3.32) (3.47) (3.54) (3.69)

~ ,' '',' ' ' ' 3.60 3.90 ·"' 4.15 4.60 4.75 4.90 noo '<34ool.

685 735 755 790 815 835 - - - - - - - - - - - - -- - - - - - - - - - -.. · .... {2.69) (2.91) (3.10) (3.43) (3.54) (3.66) . ... .. '· ',. 3.80 4.15 4.35 4.65 4.85 5.00 I 7400 700 750 760 805 825 850 --- - --- - - - - - ---- --- - ----

(3490) (2.83) (3.10) (3.25) {3.47) (3.62) {3.73)

I t600 4.00 4.30 4.45 4.80 5.00 710 760 770 815 835 - - -- --- - ---- - - - - - - - - - -- - -- - - - - --

•• (3.585) (2.98} {3.21) (3.32) (3.58) (3.73}

NOTE- All data 1s measured external to the un1t w1th dry coil and w1th the a1r filters rn place. See Page 26 for Accessory A1r Resistance data. NOTE- Data in shaded area denotes optional5 hp (3730W) drive kit.

Page 22 I Catalog 278

1,5G 13751

RPM BHP

lkWI

3.45 865

(2.57}

3.55 875

(2.65)

3.75 885

(2.80)

3.95 890

(2.95)

4.05 900

(3.02)

4.25 910

{3.17)

4.75 915

{3.54)

4.90 930

(3.66)

--- - - - - -

- - - - - - --

---- ----

- --- - - - -

- - - - - - --

---- -- - -

Page 23: Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will operate satisfactori ly down to 45 F (7.2 C) outdoor air temperature without additional

(1.31)

1.90

(1.42)

2.00

(1.49)

2.20

(1.64)

2.35

(1.75)

2.55

(1.90)

2.75

(2.05)

3.15

(2.35)

3.20

(2.39)

3.60

GCS16-1853-330 BLOWER PERFORMANCE

620 650 (1.45) (1.57)

2.15 2.35 640 665

(1.60) (1.75)

2.35 2.45 655 680

(1.75) (1.83)

2.50 2.70 670 700

(1.87) (2.01)

2.70 2.85 690 710

(2.01) (2.13)

2.95 3.15 705 725

(2.20) (2.35)

720

730

3.75 3.85 750 770

(2.80) (2.87)

3.95 4.00 760 780

(2.95) (2.98)

4.10 4.20 775

(3.05} (3.13)

4.25 4.45 810

(3.17) (3.32}

4.40 4.65 815

705

715

730

740

755

770

(1.90)

2.75

(2.05)

2.90

(2.16)

3.10

(2.31)

3.25

(2.42)

3.50

(2.61)

3.65

(2.72)

3.85

(2.87)

725 (2.01)

2.85 740

(2.13)

2.95 755

(2.20)

3.15 765

(2.35)

3.40 775

(2.54)

3.55 790

{2.65)

3.75 800

(2.80}

4.05 810

(3.02)

750

765

775

785

795

810

820

835

(2.13)

2.95

(2.20)

. 3.15

(2.35)

3.30

(2.46)

3.60

(2.69)

3.75

(2.80)

4.00

(2.98)

4.15

(3.10)

4. 1 0 4.30 4.45 805 825 845

(3.06) (3.21) (3.32)

4.45 4.55 4.75 820 840 860

(3.32) (3.39) (3.54)

830 850 (3.47)

4.80

(3.58)

4.75 4.90 845 865

(3.54) (3.66)

4.90 850

4.95 870

(3.69)

775

785

759

810

820

830

845

865

880

(2.24)

3.10

(2.31)

3.25

(2.42)

3.50

(2.61)

3.65

(2.72)

3.90

(2.91)

4.10

(3.06}

795 (2.46)

3.35 810

(2.50)

3.45 815

(2.57)

3.60 830

(2.69)

3.80 840

(2.83)

4.00 850

(2.98)

4.20 865

(3.13)

840

850

860

870

880

(2.57)

3.55

(2.65)

3.

{2.76)

3.80

(2.83)

4.10

{3.06)

4.35 890

(3.25)

4.50 900

(3,36}

4.30 4.45 .4.75 875 910

{3.21) (3.32) (3.54)

4.55

(3.39)

4.95

(3.69)

4.70 885

(3.51}

880 (2.72)

3.80 890

(2.83)

4.00 900

910

(2.98)

4.10

(3.06)

4.30

(3.21)

4.80 930

(3.58)

4.95 940

(3.69!

Catalog 278 I Page 23

Page 24: Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will operate satisfactori ly down to 45 F (7.2 C) outdoor air temperature without additional

-u

"' :0 (D

1\) ... 0 !!l.

"' 0 co 1\) ..., ())

Page 25: Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will operate satisfactori ly down to 45 F (7.2 C) outdoor air temperature without additional

0 !!t "' 0

<0 1\)

"' (X)

-u

"' <0 (I)

1\) 01

Page 26: Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will operate satisfactori ly down to 45 F (7.2 C) outdoor air temperature without additional

ACCESSORY AIR RESISTANCE . · ..

'· ... ")"Qtal R.e$is.taru:e.,..;.; inches water gaug~ t~a) • ··.• .·· . .. ..

Unit AirVolurne ... ·. 1.. . .• ·· .. ··•.·· ••·•··.·.· RTQ11 Step.~Down Diffuser Model . Wet .. ··REMD"tSM· EMDH16M. . · ..... · . . FD11

No. .. ·. · Evaporator Down-ft()' . • 1 Jioriz.()rital ·· 2 .Ends ·. · · ···. 1 Side ... AI~ ~n;ds .Flush

cfrn L/s ·. ··~n:···. • Economizer• Economizer • 0 · · .·. · .2 E;nds. .· & Stdes . · .. ..Diffuser

........... ·····•··· : • p.en. •.·· Open • · Open

• . .. ·. ·.·· .. .··· ··.:· ...•... .... . •. ... ... .. .

2400 1185 .12 (30} .03 (7} .03 (7} .21 (52} .18 (45} .15 (37} .14 (35}

2600 1225 .13 (32} .04 (10} .04 (10} .24 (60} .21 (52} .18 (45} .17 (42}

2800 1320 .14 (35} .04 (10} .04 (10} .27 (67} .24 (60} .21 (52} .20 (50}

GCS16-953 3000 1415 .16 (40} .05 (12} .05 (12} .32 (80} .29 (72} .25 (62} .25 (62}

3200 1510 .18 (45} .05 (12} .05 (12} .41 (102} .37 (92} .32 (80} .31 (77}

3400 1605 .19 (47} .06 (15} .06 (15} .50 (124} .45 (112} .39 (97} .37 (92}

3600 1700 .21 (52} .06 (15} .06 (15} .61 (152} .54 (134} .48 (119} .44 (109}

·•. .· .

3800 1795 .23 (57} .07 (17} .07 (17} .73 (182} .63 (157} .57 (142} .51 (127}

3600 1700 .12 (30} .03 (7} .03 (7} .36 (90} .28 (70} .23 (57} .15 (37}

3800 1795 .13 (32} .04 (10} .04 (10} .40 (99} .32 (80} .26 (65} .18 (45}

4000 1890 .14 (35} .04 (10} .04 (10} .44 (109} .36 (90} .29 (72} .21 (52}

. 4200 1980 .15 (37} .05 (12} .05 (12} .49 (122} .40 (99} .33 (82} .24 (60}

GCS16-1353 4400 2075 .16 (40} .05 (12} .05 (12} .54 (134} .44 (109} .37 (92} .27 (67}

4600 2170 .17 (42} .06 (15} .06 (15} .60(149} .49 (122} .42 (104} .31 (77}

•· 4800 2265 .18 (45} .07 (17} .07 (17} .65 (162} .53 (132} .46 (114} .35 (87}

5000 2360 .19 (47} .09 (22} .09 (22} .69 (172} .58 (144} .50 (124} .39 (97}

. ·· ... · ... 5200 2455 .20 (50} .10 (25} .10 (25} .75 (186} .62(154} .54 (134} .43 (107} :: 4200 1980 .10 (25} .06 (15} .06 (15} .22 (55} .19 (47} .16 (40} .10 (25}

4400 2075 .11 (27} .07 (17} .07 (17} .28 (70} .24 (60} .20 (50} .12 (30} ..

4600 2170 .12 (30} .07 (17} .07 (17} .34 (85} .29 (72} .24 (60} .15 (37}

4800 2265 .13 (32} .08 (20} .08 (20} .40 (99} .34 (85} .29 (72} .19 (47}

GCSl6.160;3 5000 2360 .14 (35} .08 (20} .08 (20} .46(114} .39 (97} .34 (85} .23 (57}

\ 5200 2455 .15 (37} .09 (22} .09 (22} .52 (129} .44 (109} .39 (97} .27 (67}

5400 2550 .16 (40} .10 (25} .10 (25} .58 (144} .49 (122} .43 (107} .31 (77} ·. .

5600 2645 .17 (42} .12 (30} .12 (30} .64 (159} .54 (134} .47 (117} .35 (87}

... .· 5800 2735 .18 (45} .13 (32} .13 (32} .70 (174} .59 (147} .51 (127} .39 (97}

•• 5000 2360 .07 (17} .11 (27} - - - - .51 (127} .44 (109} .39 (97} .27 (67}

. · .. 5200 2455 .08 (20} .12 (30} - --- .56 (139} .48(119} .42 (104} .30 (75}

.•· 5400 2550 .09 (22} .13 (32} - - - - .61 (152} .52 (129} .45(112} .33 (82}

i 5600 2645 .10 (25} .14 (35} - - - - .66 (164} .56 (139} .48(119} .36 (90}

5800 2735 .11 (27} .15 (37} - - -- .71 (177} .59 (147} .51 (127} .39 (97}

6000 2830 .12 (30} .16 (40} - - - - .76 (189} .63 (157} .55 (137} .42 (104}

GCS16-1853 6200 2925 .13 (32} .17 (42} - - - - .80 (199} .68 (169} .59 (147} .46 (114}

·.· 6400 3020 .14 (35} .18 (45} - - -- .86 (214} .72 (179} .63 (157} .50 (124}

. 6600 3115 .15 (37} .20 (50} - - - - .92 (229} .77 (191} .67 (167} .54 (134}

6800 3210 .16 (40} .22 (55} - - - - .99 (246} .83 (206} .72(174} .58 (144}

. 7000 3305 .17 (42} .23 (57} - - -- 1.03 (256} .87 (216} .76 (189} .62 (154}

7200 3400 .18 (45} .24 (60} ---- 1.09 (271} .92 (229} .80 (199} .66 (164}

7400 3490 .19 (47} .25 (62} -- - - 1.15 (286} .97 (241} .84 (209} .70 (174}

.. 7600 3585 .20 (50} .26 (65} - - - - 1.20 (301} 1.02 (254} .88 (219} .74 (184} . 6000 2830 .06 (15} .01 (2} ---- .36 (90} .31 (77} .27 (67} .29 (72}

6500 3065 .07 (17} .02 (5} -- - - .42 (104} .36 (90} .31 (77} .34 (85}

7000 3305 .08 (20} .02 (5} - -- - .49 (122} .41 (102} .36 (90} .40 (99}

GCS16~2553 7500 3540 .09 (22} .04 (10} ---- .51 (127} .46 (114} .41 (102} .45 (112}

GCS16-2753 8000 3775 .10 (25} .06 (15} - - - - .59 (147} .49 (122} .43 (107} .50 (124} GCS16-3003 8500 4010 .11 (27} .08 (20} - -- - .69 (172} .58 (144} .50 (124} .57 (142}

9000 4245 .12 (30} .10 (25} - - - - .79 (196} .67 (167} .58 (144} .66 (164}

9500 4485 .13 (32} .12 (30} ---- .89 (221} .75 (186} .65 (162} .74 (184}

10,000 4720 .15 (37} .14 (35} - - - - 1.00 (249} .84 (209} .73 (182} .81 (201}

Page 26 I Catalog 278

Page 27: Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will operate satisfactori ly down to 45 F (7.2 C) outdoor air temperature without additional

PED16-185 & PED16-300 POWER EXHAUST FANS PERFORMANCE

Air Volume Exhausted Return Air System Modell'llo. Static Press.ure

cfm L/s Inches Water Gauge (Pa}

4200 1980 0 (0)

3800 1795 .05 (12)

3500 1650 .10 (25)

3200 1510 .15 (37)

2700 1275 .20 (50)

2200 1040 .25 (62)

6300 2970 0 (0)

5750 2715 .05 (12)

5200 2455 .10 (25)

4625 2180 .15 (37)

4050 1910 .20 (50)

CEILING DIFFUSER AIR THROW DATA

1595 30-37 9-11 28-34 9-10

1770 34-41 10-12 31-38 9-12

2075 34-42 10-13 32-40 10-12

2335 38-47 12-14 36-45 11 -14

2595 43-52 13-16 40-50 12-15

1980 39-46 12-14 40-48 12-15

2360 41-50 12-15 43-52 13-16

2735 43-52 13-16 45-54 14-16

2830 45-55 14-17 48-55 15-17

3190 47-56 14-17 50-58 15-18

7500 3540 49-58 15-18 55-66 17-20

8000 3775 39-44 12-13 53-62 16-19

GCS16-2553 GCS16~2753 9000 4245 47-56 14-17 55-64 17-20 GCS16-300.3

10,000 4720 49-58 15-18 57-67 17-20

*Throw is the horizontal or vertical distance an airstream travels on leaving the outlet or diffuser before the maximum velocity is reduced to 50 ft. (15 m) per minute. Four sides open.

Catalog 278 I Page 27

Page 28: Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will operate satisfactori ly down to 45 F (7.2 C) outdoor air temperature without additional

Prepared for the guidance of architects, consulting engineers and mechanical contractors.

General- Furnish and install a single package combination air to air OX mechanical cooling system and gas fired heating system, com­plete with automatic controls. The single package unit shall be a standard product of a firm regularly engaged in the manufacture of heating-cooling equipment. The manufacturer shall have parts and service available throughout Canada.

The installed weight shall not be more than . ....... lbs.(kg). Entire unit shall have a width of not more than ........ inches (mm), a depth of not more than . ....... inches (mm) and an overall height of not more than ........ inches (mm). The equipment shall be shipped completely factory assembled, precharged, piped and wired internally ready for field connections. In addition, manufacturer shall test operate system at the factory before shipment.

Air Distribution - Equipment shall be capable of bottom or side (horizontal) handling of conditioned air. All air distribution ducts shall be fiberglass or ........ ga. galvanized steel insulated with ....... . inch (mm) thick . ....... lb./ft. 3 (kgjm3) density fiberglass or equivalent.

Approvals -All electrical components shall have U.L. Listing. All wiring shall be in compliance with CEC.

Equipment Warranty- Heat exchangers have a limited warranty for a full ten years. Compressors have a limited warranty for a full five years. All other components have a limited warranty for one year. Refer to Limited Warranty certificate included with the unit for details.

Cooling System - The total certified cooling capacity shall not be less than ........ Btuh (kW) with an evaporator air volume of ........ cfm (L/s), an entering wet bulb air temperature of . ...... . oF (° C), an entering dry bulb air temperature of . ....... oF (° C) and a condenser entering temperature of . ....... oF (° C). The compressor power input shall not exceed . ....... kw at these conditions.

The coils shall be non-ferrous construction with aluminum fins mechanically bonded to durable copper tubes. Coils shall be pressure leak tested. Coil face area shall be not less than ........ sq. ft. (m2) (evaporator) and ........ sq. ft. (m2) (condenser).

Multiple compressors shall be resiliently mounted, have overload protection, compressor monitor and crankcase heater. GCS16-953, -1353, -1603 (2nd stage only) and -1853 units shall have internal pressure relief. The refrigeration system shall have suction and liquid line service gauge ports, high pressure switches, loss of charge switches, thermometer well, driers, freezestat and full refrigerant charge. GCS 16-2553, -2753 & -3003 shall have suction and liquid line service valves. Control option available shall consist of low ambient control and timed-off control. Shall be rated in accordance with ARI Standard 210/240-89 or 360-86.

Heating System - The heating capacity output shall be ....... . Btuh (kW) with a gas input of . ....... Btuh (kW).

Tubular heat exchanger and inshot type gas burners shall be constructed of aluminized steel. Controls shall consist of direct spark ignition, electronic flame sensor controls, flame rollout switch, limit controls and automatic redundant dual gas valve with staging control and centrifugal switch on induced draft blower. Unit shall be available for use with propane as an option. Complete service access shall be provided for controls and wiring. Shall be C.G.A. design certified for outdoor installation.

Cabinet- Shall be galvanized steel with a powdered enamel paint finish electrostatically bonded to the metal. Cabinet panels where conditioned air is handled shall be fully insulated to prevent sweating and minimize sound. Openings shall be provided for power connection entry. Shall have peep hole with cover for flame viewing of burners. Evaporator coil condensate drain extended outside cabinet shall be provided. Lifting brackets shall be provided for rigging.

Service Access- All components, wiring and inspection areas shall be completely accessible through removable panels.

Supply Air Blowers- Centrifugal supply air blower shall have perma­nently lubricated ball bearings and adjustable belt drive. Motor mount base shall permit ease of motor changeover and belt tension adjustment. Blower wheel shall be statically and dynamically balanced. Blower shall be capable of delivering ........ cfm (l/s) at an external static pressure of . ....... inches water gauge (Pa) requiring ....... . bhp (W) and ........ rpm.

Page 28 I Catalog 278

Condenser Fan(s)- Direct drive propeller type condenserfan(s) shall discharge vertically and be direct driven by a . ....... hp (W) motor. Fan motor shall be permanently lubricated and inherently protected. Fan(s) shall have a safety guard.

Air Filters - Disposable filters furnished shall have not less than ....... . sq. ft. (m2) of free area.

Roof Mounting Frame- Furnish and install a steel roof mounting frame for bottom discharge and return air duct connection. It shall mate to the bottom perimeter of the equipment. When flashed into the roof it shall make a unit mounting curb and provide weatherproof duct connection and entry into the conditioned area. Flashing shall be the responsibility of a roofing contractor. Frame shall be approved by National Roofing Contractors Association.

Economizer Damper Section- Furnish and install complete with recir­culated air dampers, outside air dampers, air filters, damper actuator and controls. Low leakage dampers shall ride in nylon bearings. The economizer section shall provide for the introduction of 100% outdoor airfor minimum ventilation and free cooling. REMD16M-185 & -300 shall include gravity exhaust air dampers. Integrated economizer cycle shall allow compressors to cycle for dehumidification and additional cooling, as needed, with 100% outdoor air intake. Damper actuator shall be 24 volt, fully modulating spring return. ·controls shall include fixed 55° F (13°C) mixed air controller, damper actuator, adjustable outdoor air minimum position switch and solid-state adjustable outdoor air enthalpy control. Cabinet shall be galvanized steel with a powdered enamel paint finish electrostatically bonded to the metal. Control option shall consist of differential enthalpy control (return air sensor).

Gravity Exhaust Dampers - Optional pressure operated dampers shall be available for field installation in economizer damper section. Neoprene coated fiberglass dampers shall prevent blow-back and outdoor air infiltration during off cycle. Shall be equipped with rain­hoods and bird screen. Shall be furnished with REMD16M-185 & -300.

Power Exhaust Fans- Shall be available for GCS 16-1853-2553-2753 & -3003with REMD16M economizer installed in the down-flo position only. Direct drive propeller type fans shall exhaust air through exhaust dampers. Motors shall be overload protected. Fans shall install in­between the unit and exhaust dampers.

Outdoor Air Damper Section- Optional outdoor dampers shall be available to provide outdoor air requirements of up to 25%. Shall be available for manual or automatic operation. Damper section field installs external to the unit. Shall be equipped with filter for extra air filtering and bird screen protection.

Horizontal Supply & Return Air Kit- Optional kit shall provide necessary cabinet parts to field convert unit for side (horizontal) supply and return air duct connections.

Bottom Power Entry Kit- Optional kit for GCS16-953 & 1353 shall provide bottom power entry to the unit within the confines of the roof mounting frame. Shall be furnished with GCS16-1603-1853-2553-2753 & -3003 units.

Ceiling Diffusers-Furnish and install a (flush or step-down) optional combination ceiling supply and return air diffuser. It shall be capable of not less than . ....... ft. (m) radius of effective throw. Supply and return transitions shall be available, for field installation in the roof mounting frame, to provide duct connection to the diffuser.

Control Systems- Shall provide a selection of thermostats and related controls to automatically operate the mechanical equipment through the heating or cooling and ventilating cycles as required.

Remote Status Panel- Shall be available for installation within the conditioned area to observe equipment operation. The panel shall include signal lights for Cool Mode, Heat Mode, Compressor 1, Compressor 2, No Heat and Filter.

Remote Switching Status Panel- Shall be available for installation within the conditioned area to contra/and observe equipment opera­tion. The panel shall include signa/lights for Cool Mode, Heat Mode, Compressor 1, Compressor 2, No Heat and Filter. System selector switch and fan switch shall provide operational mode and blower operation. After hours timer switch shall override night setback controls and provide normal operation for time period set.

Page 29: Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will operate satisfactori ly down to 45 F (7.2 C) outdoor air temperature without additional

GCS16-953, -1353, -1603 & -1853 (-235 Size Shown) CORNER WEIGHTS -lbs. (kg) CENTER OF GRAVITY- in (mm)

'Model No: ' ',,

Q.GS16c953 GCSHH353 GGS16'-1603 GCSl6Cl853

INDUCED DRAFT BLOWER

FLUE/VENT OUTLET

lbs.

236 255 285 419

AA BB l(g lbs. kg

107 283 128 116 345 156 129 394 179 190 552 250

GCS16-1603 & 1853 DISCONNECT SWITCH

(not furnished)

cc lbS. kg lbs;

194 880 162 287 130 213 353 160 256 435 197 329

DO kg Model No.

73 GCS16-953 97 .GCS16-1353 116 GCS16-1.603 149 GCS16-1853

v

EE FF in. mm in.

28-1/2 724 40 32-3/4 832 40 31-5/8 803 42-3/8

38 965 50

ELECTRICAL INLETS (GCS16-953 & 1353)

14------ R ------t.,._,, BOTTOM POWER ENTRY KIT

(Optional GCS16·953 8r 13s;il (Furnished GCS16-1603 8r 1853)

mm

1016 1016 1076 1270

oo~------~~----~~~~~~~~

1i' CONDENSER COIL FANS (Single Fan On GCS16-963)

FLUE/VENT OUTLET

TOP VIEW

BACK VIEW With HORIZONTAL SUPPLY & RETURN AIR OPENINGS

T:J-u HEAT SECTION END VIEW

r·• ·:'A• . .cB, c D . E

TOP VIEW BASE SECTION

14-------- B---------1.,..""11 ~~~~~=r=======:~O~====~

ELECTRICAL INLETS (GCS16-1853)

COMPRESSORS (2) GCS16-1853 has 3 compressors)

CONDENSER SECTION END VIEW

F G H J K

"'-FLUE/VENT OUTLET

L •PJI~~~N~: ,'•inc:' •mm· :iin; · 'Rlffi in. mm in. mm in. mm, in: •• mm in: mm in. mm in. mm in. mm in. mm GG$167953 · 39 991 88-1/2 2248 48 1219 16'112 419 30-3/8 772 5-5/8 142 32-1/8 816 19-7/16 494 24-5/8 625 33 838 1-5/8 41

GCS16c1353 46 1168 94 2388 60 1524 24 610 30-3/8 772 4-7/16 113 39-1/8 994 25-1/4 641 31-5/8 803 33 838 2 51 acsJa:,JE?Q3, 46 1168 102 2591 60 1524 24 610 38 965 4-7/16 113 39-1/8 994 25-1/4 641 31-5/8 803 41 1041 2 51 GCS1~1853 51-1/2 1308 116 2946 68 1727 24-1/2 622 44 1118 5-5/8 143 41-1/2 1054 25-3/4 654 32-3/4 832 50-1/8 1273 2 51

>;c: >: ',·:11 :''·,M·' ,, N p Q ''• R s '\, •,r ·,. u V, W. X y

~-""I m, ~ in,, lmm in. mm m. mm in. mm iri. rom in. tmm in. mm ;in. mm in •. , mm m. mm in,.: mm 9-3/4 248 25-1/16 637 22-1/8 562 64-7/8 1648 53-1/2 1359 2-3/4 70 2-3/8 60 2-7/8 73 4-3/16 106 3-1/16 78 1-1/2 38 3-1/16 78

14 356 31-3/16 792 28-1/2 724 64 1626 53-1/2 1359 2-3/4 70 2-3/8 60 2-7/8 73 4-3/16 106 3-1/16 78 1-1/2 38 3-1/16 78

GG$1~i~ft 14 356 31-3/16 792 28-1/2 724 72 1829 25-1/2 648 2-3/4 70 2-3/8 60 2-7/8 73 4-3/16 106 3-1/16 78 1-1/2 38 3-1/16 78 GCS1a;ttS531115-1/2 394 33-1/2 851 33 838 81-1/2 2070 36 914 4-1/4 108 4 102 4 102 7-1/4 184 5 127 3 76 4-1/16 103

Catalog 278 I Page 29

Page 30: Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will operate satisfactori ly down to 45 F (7.2 C) outdoor air temperature without additional

211 532 241 755 342 659

240 639 290 893 405 739 335

257 684 310 957 434 792 359

INDUCED DRAFT BLOWER BOTTOM POWER ENTRY (Furnished) (-470 Model DISCONNECT SWITCH

Has Two) (Not Furnished)

~ ~~ I cc I CONDENSER COIL

L_

\--=--=

-B~~~~ L_l~J)-j~

1111111111 CENTEA OF/ HEAT GRAVITY

EXCHANGE ------­llllllllil CEVAPORATOB._COIL ,-,,-rr-1111111111 I FILTERS'

uuuuu J_- _j~=lL-=-

5 (127)

IAAI~I--- ~ CONDENSER FANS (2)

CONDENSER COIL

2 (51)

TOP VIEW

FILTER ACCESS (Hinged)

CONDENSER COIL INTAKE

AIR

1 51-1/2

~~~~==~~6~4-~1/~4~(1~6~32~)~~~~~~~~ __:["'

3 (76) HORIZONTAL

SUPPLY AIR OPENING

BACK VIEW

CONDENSER COIL AIR INTAKE (Both Sides)

WITH HORIZONTAL SUPPLY & RETURN AIR OPENING

57(1448) I 7-1/4f84) ~

ELECTRICAL INLETS (In Bottom Of Unit)

DOWNFLOW SUPPLY

AIR OPENING

20-1/2 (521) DOWNFLOW

RETURN AIR OPENING

TOP VIEW BASE SECTION

LIFTING LUGS

CONDENSATE DRAINS (2)

LOW HEAT FLUE/VENT OUTLET (1) (-235 & -470)

FRONT VIEW

HIGH HEAT FLUE/VENT OUTLET (2) (-4700nly)

C MBUSTION AIR;;

fool <if---- 85 (2159) ---"""~I

CONDENSER COIL EXHAUST AIR~

1- '0- 85 (2159) -0~~~'""'1 INDUCED

DRAFT BLOWER (-470Model

Has Two)

18-1/4 (464)

r -,

LJ_L r======-, L _J -.,

I HEAT \\ I EXCHANGER _); ---1 -- --:::.:::- - - /

~.--- / I ( < I \ '- ........, ---- ' I --.::::----'\. I \\

0 L--, -~}J ~======-~

j__ ~~===:;:J -l GAS INLET

4 (102) HEAT SECTION END VIEW

Paqe 30 I Cataloq 278

1 51-1/2 (1308)

r 51-1/2 (1308)

COMPRESSORS (2)

CONDENSER SECTION END VIEW

Page 31: Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will operate satisfactori ly down to 45 F (7.2 C) outdoor air temperature without additional

FLUE/VENT OUTLET

FlUE/VENT OUTLET

GCS16-953, -1353 & -1603 UNITS WITH REMD16M ECONOMIZER DAMPER SECTION AND RMF16 ROOF MOUNTING FRAME

CORNER WEIGHTS

256 116

415 188 459 208 353 160

CENTER OF GRAVITY

(Field Installed)

TOP VIEW

CONDENSER COIL EXHAUST AIR

r~" ~ c ~, 8 (756) )}

l OUTDOOR AIR DAMPERS

I

I OPTIONAL A ECONOMIZER

_j DAMPERS D (Field Installed)

1-1/2 (38)

RMF16 ROOF Ill 14 (356)

MOUNTING FRAME .. 0 _i (Field Installed Both Sides)

BACK VIEW CONDENSER SECTION END VIEW

827

1168 94 2388 60 1524 34-9/16 878 32-9/16 827

1168 102 2591 60 1524 34-9/16 878 40-9/16 1030

r:~t~lnn ?7R I D~no ~1

Page 32: Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will operate satisfactori ly down to 45 F (7.2 C) outdoor air temperature without additional

INDUCED DRAFT

BLOWER

FLUE/VENT OUTLET

GCS16-953, -1353 & -1603 UNITS WITH EMDH16 HORIZONTAL ECONOMIZER DAMPER SECTION

CONDENSER COIL INTAKE

AIR

CORNER WEIGHTS

® 1.:-1 -----:-::2::----.L-....,~::.=-:~~ ® CENTER OF GRAVITY

FLUE/VENT OUTLET-....,_

F

I

I I

: f I SUPPLY 1 : AIR I

I ,-, I v·f-· . __ .-.. J

SUPPLY AIR PLENUM

(Not Furnished by Lennox)

TOP VIEW

OPTIONAL HORIZONTAL ECONOMIZER

CONDENSER COIL FANS (Single Fan On GCS16-963j

DAMPERS (Field Installed)

!""',.._ _______ B -------..-j

CONDENSER COIL EXHAUST AIR\

r (1289) A ...._ ____ 50-3/4 ----··i··~----~--

SUPPLY 1f

FILTER ACCESS

RETURN AIR OPENING (On EMDH16M)

BACK VIEW

2 2

51 19-1/4 489 51 19-1/4 489

l AIR

r\------------FILTERl ~ r- 25-3/4-

)...... (654)

' A

~~~J 1-1/2 (38)

OPTIONAL GED COMPRESSORS

GRAVITY EXHAUST DAMPERS DAMPER (Field Installed) MOTOR END VIEW

31-1/2 800 34-3/4 32-9/16 827 39-1/2 1003 34-3/8 883 40-9/16 1030

Page 33: Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will operate satisfactori ly down to 45 F (7.2 C) outdoor air temperature without additional

I

-GCS16-1853, -2553, -2753 & -3003 UNIT

WITH REMD16M ECONOMIZER DAMPER SECTION AND RMF16 ROOF MOUNTING FRAME

(DOWN-FLOW APPLICATION)

CENTER OF GRAVITY- in. (mm)

~-----t- EE ----Joi CONDENSER FANS (2)

I

LIFTING LUGS

" \

k---c-------~~•

OPTIONAL ECONOMIZER

DAMPERS (Field Installed)

TOP VIEW

A

0

0

FILTER ACCESS (Hinged)

OPTIONAL ECONOMIZER

DAMPERS (Field Installed)

<"0'

"

I 1'

FILTERS

-- --- -~--It RMF16ROOF MOUNTING FRAME

BACK VIEW GRAVITY EXHAUST DAMPERS

(Furnished With REMD16M) Net Face Area: -185-4.3 sq. ft. (0.40 m2)

-300 - 5.6 sq. ft. (0.52 m2)

CONDENSER

COIL "' EXHAUST AIR 1,..~1--""""'=---- B --~---c~~>~

26-1/2 --, Y\: (673) t.:.I

OPTIONAL PED16 POWER EXHAUST FANS (PED16-185 has two fans)

IPED16-300 has three fans)

CONDENSER SECTION END VIEW

Ca!aloa 278 I Paae 33

Page 34: Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will operate satisfactori ly down to 45 F (7.2 C) outdoor air temperature without additional

SUPPLY AIR PLENUM

(Not Furnished)

1+--- c ----1

OPTIONAL ECONOMIZER

DAMPERS (Field Installed)

0 I I

I RETURN I AIR l-_""'...-........ ...._ __ _

TOP VIEW

LIFTING LUGS

FILTER ACCESS (Hinged)

RETURN AIR OPENING (On Unit)

BACK VIEW

GCS16-1853, -2553, -2753 & -3003 UNIT WITH REMD16M ECONOMIZER DAMPER SECTION

(HORIZONTAL APPLICATION)

CORNER WEIGHTS - lbs. (kg)

256 544 247 742 256 544 247 742 288 647 293 871 308 690 313 929

337 769 337 769 395 856 421 913

~ CENTER OF GRAVITY- in. (mm) CONDENSER

FANS (2)

GRAVITY EXHAUST DAMPERS

(Furnished With REMD16M) Net Face Area: -185-4.3 sq. ft. (0.40 m2)

-300- 5.6 sq. ft. (0.52 m2)

2330 :t3¢~~~~~'7;5~ 91-3/4 2330

~esij~3oo3 91-1/4 2318

CONDENSER COIL

EXHAUST AIR ~ 26-1/2 .. 1 'b (673)

41-3/4 1060 41-3/4 1060 42-7/8 1089

1---- c ---+4

GRAVITY EXHAUST DAMPERS (Furnished with REMD16M)

(Field Installed in Return Air Duct)

RECIRCULATED AIR DAMPERS

349 349 388 414

CONDENSER SECTION END VIEW

Page 35: Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will operate satisfactori ly down to 45 F (7.2 C) outdoor air temperature without additional

RMF16 SERIES ROOF MOUNTING FRAME WITH DOUBLE DUCT OPENING

~ ~-•r------------------A Frame ~~1-13/16 1-13/161 .. ,

1-13/16 B Opening .. , j

-.--

"' "' c E ·=

c f! .,

LL Q,

0

D

l 1-13/16

SUPPLY AIRI OPENING

F

f-- E--f- G

1-13/16 A

5/8~rLt_ L

[~' RETURNAIR t l__ NAILER

STRIP (Furnished)

~~"-f -J";"k-SECTION A-A

~ A

SUPPORT ANGLES / (furnished)

1

r I ~~~~I~-- ~NAI:R~~:.;J-J -Y- . .1~ ~--'- ~--~---. (Furnished)

l__ -'"1'--_..;.N;;.;O;;.;T.;;E-..;R.;.;o..;;o.;..fd;;,;e;.;;c;.;.k;.;.m;;;;a.:..y,;,;,be;;..;;,;om.;.;;.;.itt;.;;e,;,;,d..;.w..;.it..;h..;.in..;t;.;.he;;..c;;.;o..;.n..;.fin..;.e;.;;s..;o.;..ff;.;.ra;;;;m..;.e;.;. . .I.I • .L

RMF16-95 ROOF MOUNTING FRAME WITH SRT16-95 SUPPLY AND RETURN AIR TRANSITIONS FOR FD11-95 & RTD11-95 CEILING DIFFUSERS

SRT16-95 SRT16-95 1-13/16 A A SUPPLY RETURN -J I- l_ _j

TRANSITION SUPPORT ANGLES (Furnished with Roof Mounting Frame)

,_ "i;:'FI.""fi•:""l,.:f--~:--~:--~:--~:--;:--;:--~:--~:--~:::8:::~::~1::~::8~0=i=F-;~a-e:: mn-i::~-g~~~~~~~~~~~~~~~,..:i~"/16 TRANSITION TRANSITION

518 --j ~

46-5/8 II~, I" I·

NAILER STRIP I (Furnished) 0

", l__

NAILER STRIP

urnished)

NOTE-Roof deck may be omitted within the confines of frame. -12k-SECTIONA-A

RMF16-135/160, -185 & -300 ROOF MOUNTING FRAMES WITH SRT16 SUPPLY AND RETURN AIR TRANSITIONS FOR FD11 & RTD11 CEILING DIFFUSERS

1-13/161·, _. ~-•r------------------- AB Frame ~~1-13/16 ,.., Opening

1-1 :ij16 I ~

SRT16 SRT16 SUPPLY RETURN

TRANSITIOi TRANSITION

., "' c E '2

~ ~ .. ., ~ Q,

.._ 0 c SUPPLY RETURN

D AIR AIR

l ~PENING OPENING

1+- F- --~· 181+- F -f-Joo

-1-1 3/16

~

1-13/16 A A

5/8~ l_

I 1

I r _j

l__ NAILER STRIP

(Furnished)

-l'7k-SECTION A-A

~ ' INSULATION : (Furnished)'

', ' ' ''' ...,_.

TRANSITION SUPPORT ANGLES (Furnished with Roof Mounting Frame) ~

INSULATION :~ -. ---·----~ -.:r---· • ~ (Furnished~ } \ I

~ ' ' ' ( NAILER STRIP :• ... (Furnished) •

NOTE-Roof deck may be omitted within the confines of frame.

Page 36: Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will operate satisfactori ly down to 45 F (7.2 C) outdoor air temperature without additional

TYPICAL FLASHING DETAIL FOR RMF16 ROOF MOUNTING FRAME

ROOF MOUNTING FRAME SPECIFICATIONS Roof Mounting frame is rigid enough to be spanned over its entire

length or cantilevered if supported on both sides of center of gravity.

Roof Mounting Frame RMF16-95 thru -300

Mountingframe.wt. (lblft} (kg/m) of length 5.5 (8.2)

Mounting frame design strength .{psi) (kPa) 20,000 (137,900)

*Includes both so des of frame.

RIGID INSULATION (Field Supplied)

OAD16 OUTDOOR AIR DAMPER SECTION

11~ (38)

~ A

B .. I 0

0

BACK VIEW

·.·· .· . .·.

:: Model No;

····· ·.·

In; mill

1-1 12

~) t F

01 D

0

c

AIR • FLOW

AIR.FLOW

J 14-1• -E-----'"'1 7/8 (22)

SIDE VIEW

CANT STRIP (Field Supplied}

24 610 21 533 18-1/2 470 17-1/8 435 17-1/8 435 3/4 19 5/8 16

oAI)tt)-.185 · .. · .·· ..... · 33 838 30 762 28-3/8 594 27 686 22-1/4 565 3/4 19 5/8 16

33 838 30 762 34-5/8 879 33-1/4 845 34-1/4 870 1/2 13 1/2 13

GCS16 UNIT WITH OAD16 OUTDOOR AIR DAMPER SECTION DOWN-FLO SUPPLY AND RETURN AIR

BACK VIEW

0AD16-300

NOTE - For Horizontal (side) Supply and Return Air OAD16 Field Installs on Return Air Duct.

OAD16 OUTDOOR AIR DAMPERS

OAD16 OUTDOOR AIR DAMPERS

8-5/16 (211)- GCS16-953 15-15/16 (405)- GCS16-1353 & 1603

10 (254)- GCS16-1853 5 (127)- GCS16-2553, 2753 & 3003

27

33-1/4 845 24-1/4

0 _J-~

r .,

: ~:-J

I I ._)\,_

END VIEW

565

616

Page 37: Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will operate satisfactori ly down to 45 F (7.2 C) outdoor air temperature without additional

COMBINATION CEILING SUPPLY AND RETURN DIFFUSERS RTD11-95 STEP-DOWN CEILING DIFFUSER

914 4-13/16 122 18 457 45-5/8 1159 47-5/8 1210

1219 4-13/16 122 24 610 57-5/8 1464 59-5/8 1521

FD11-95 FLUSH CEILING DIFFUSER

20 (508) DUCT SIZE

FD11-135, FD11-185 & FD11-275 FLUSH CEILING DIFFUSER

Catalog 278 I Page 37

Page 38: Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will operate satisfactori ly down to 45 F (7.2 C) outdoor air temperature without additional

Page 38 I Catalog 278

GCS16 BASIC UNIT

NOTE - Top Clearance Unobstructed.

NOTE - Entire perimeter of unit requires support when elevated above mounting surface.

GCS16 UNIT WITH REMD16M ECONOMIZER DAMPER SECTION OR OAD16 OUTDOOR AIR DAMPER

NOTE - Top Clearance Unobstructed.

GCS16 UNIT WITH EMDH16M HORIZONTAL ECONOMIZER

NOTE - Top Clearance Unobstructed.

Page 39: Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will operate satisfactori ly down to 45 F (7.2 C) outdoor air temperature without additional

To determine sensible capacity, leaving wet bulb and dry bulb temperature not shown in the rating tables use the methods below.

Leaving Wet Bulb (Imperial Units) 1. cfm x 4.5 = lbs. of air per hour

2. Btuh cooling capacity = Btu's per lb. of air lbs. of air per hour

3. Refer to enthalpy table below for entering wet bulb to determine Btu per lb. of air.

4. Subtract the result of #2 from #3 for Btu per lb. of air. 5. Match the result of #4 on the enthalpy table to obtain the leaving wet

bulb required.

Example: 1. 4500 cfm x 4.5 = 20,250 lbs. of air per hour

2. 120,000 Btuh cooling capacity = 5.93 Btu per lb. of air 20,250 lbs. of air per hour

3. Entering wet bulb of 67°F = 31.62 Btu per lb. 4. Subtract 5.93 from 31.62 = 25.69 Btu per lb. 5. From enthalpy table 25.69 Btu per lb. equals 58.8 leaving wet bulb.

Leaving Dry Bulb (Imperial Units) Leaving dry bulb = entering dry bulb _ Sensible heat capacity (Btuh)

1.08 x cfm Sensible capacity = SIT x total capacity

To determine sensible capacities at dry bulb temperatures not shown in the cooling unit tables, apply the following correction factor.

Dry bulb temperatures higher than table figure: Add 900 Btuh per 1000 cfm/°F

Dry bulb temperatures lower than table figure: Subtract 900 Btuh per 1000 cfm/ 0 F.

Example: From table@ 4500 cfm- 80°F dry bulb- 67°F wet bulb­.75 SIT ratio - 120,000 Btuh total cooling capacity

What is sensible capacity and leaving dry bulb for 78°F dry bulb@ 67°F wet bulb?

Sensible capacity@ 80°F dry bulb/67°F wet bulb = .75 SIT x 120,000 Btuh = 90,000 Btuh

Sensible capacity@ 78°F dry bulb/67°F wet bulb

90,000 Btuh _ 900 Btuh x 4500 cfm x 2°F 1,000 cfm

= 90,000 Btuh - 8,100 Btuh = 81,900 Btuh

Leaving dry bulb 78°F _ -:-::::::-81...:.,9_0--,0=-=Bt::::u_h-:-1.08 x 4,500 cfm

78°F 16.85°F = 61.15°F

Enthalpy Table (Imperial Units) - *Btu of Moist Air at Saturation Per Pound of Dry Air (hs) ~~~~~~~~~~~~~--~~~~~

*Specify enthalpy of dry air assigned a value of zero at 0°F.

Cataloq 278 I Paae 39

Page 40: Catalog 278 Canadian Edition - Daikin Applied...Low Ambient Control Kit (Optional)-System will operate satisfactori ly down to 45 F (7.2 C) outdoor air temperature without additional

To determine sensible capacity, leaving wet bulb and dry bulb temperature not shown in the rating tables use the methods below.

Leaving Wet Bulb (Metric Units) 1. Cooling capacity kilowatts (kW) x 3600 = kilojoules per hour (kJihr) 2. Litres per second (Lis) x 4.68 = kilograms of air per hour (kglhr) 3. Enthalpy (hs) = kJihr _,_ kglhr = kJikg of dry air 4. Refer to enthalpy table below for entering wet bulb to determine kJikg

of air. 5. Subtract the result of #3 from #4 for kJikg of air. 6. Match the result of #5 on the enthalpy table to obtain the leaving wet

bulb required.

Example: Cooling unit capacity 35.16 kW and 2124 Lis Temperature condition, entering wet bulb 19.4°C 1. Cooling capacity 35.16 kW x 3600 = 126,600 kJihr 2. 2124 Lis x 4.68 = 9940 kglhr of air 3. hs = 126,600 kJihr _,_ 9940 kglhr = 12.74 kJikg of air 4. Entering wet bulb of 19.4°C = 55.54 kJikg (from enthalpy table) 5. Subtract 12.74 from 55.54 = 42.80 kJikg 6. From enthalpy table 42.80 kJikg equals 15.2°C leaving wet bulb

Leaving Dry Bulb (Metric Units) Leaving dry bulb = entering dry bulb _ Sensible heat capacity (Watts)

1.21 x Lis Sensible capacity = SIT x total capacity

To determine sensible capacities at dry bulb temperatures not shown in the cooling unit tables, apply the following correction factor.

Dry bulb temperatures higher than table figure: Add 1.0 kW per 1000 Lis per oc

Dry bulb temperatures lower than table figure: Subtract 1.0 kW per 1000 Lis per oc

Example: Cooling unit capacity 35.16 kW and 2124 Lis, SIT ratio = 0.75 Temperature conditions, entering DB 25.6°C, entering WB 19.4°C

Sensible heat capacity (from cooling unit tables) at 26.JDC dry bulb and 19.4°C wet bulb = 0.75 SIT ratio x 35.16 kW = 26.37 kW

Sensible heat capacityy at 25.6°C dry bulb, 19.4°C wet bulb

26.37 kW _ 1.0 kW x 2124 Lis x (26.7 - 25.6°C)

1000 Lis 26.37 kW - 2.34 kW 24.03 kW = 24,030 W

Leaving dry bulb = 25.6°C 24,030 W 1.21 x 2124 Lis

= 25.6°C - 9.35°C = 16.25°C

Enthalpy Table (Metric Units) - *kJ of Moist Air at Saturation Per kg of Dry Air (hs)

WET BULB TENTHS. Of' DEGREES (•C) (oC) .0 .1 .2 .3 .4 .5 .6 .7

5 18.64 18.84 19.04 19.24 19.44 19.64 19.84 20.04

6 20.64 20.85 21.05 21.26 21.47 21.68 21.88 22.09

7 22.71 22.93 23.14 23.35 23.57 23.78 23.99 24.21

8 24.85 25.07 25.29 25.51 25.74 25.96 26.18 26.40

9 27.06 27.29 27.52 27.74 27.97 28.20 28.43 28.66

10 29.34 29.58 29.81 30.05 30.29 30.53 30.76 31.00

11 31.71 31.96 32.20 32.45 32.70 32.95 33.19 33.44

12 .· 34.18 34.43 34.69 34.94 35.20 35.45 35.70 35.96

13 36.71 36.98 37.24 37.51 37.77 38.04 38.30 38.57

14 39.37 39.64 39.91 40.19 40.46 40.73 41.00 41.27

1!). 42.09 42.38 42.66 42.95 43.23 43.53 43.81 44.09

16 ·•. 44.95 45.25 45.54 45.84 46.13 46.43 46.72 47.02

17 47.90 48.21 48.52 48.83 49.14 49.45 49.75 50.06

18 .. 51.00 51.32 51.64 51.96 52.28 52.61 52.93 53.25

19 54.21 54.54 54.88 55.21 55.54 55.88 56.21 56.54

20 57.53 57.88 58.23 58.58 58.93 59.28 59.62 59.97

21 61.02 61.38 61.75 62.11 62.47 62.84 63.20 63.56

22 64.65 65.03 65.41 65.79 66.17 66.55 66.92 67.30

23 68.44 68.83 69.23 69.62 70.01 70.41 70.80 71.19

24 72.37 72.78 73.19 73.61 74.02 74.43 74.84 75.25

.· 25 76.49 76.92 77.35 77.77 78.20 78.63 79.06 79.49

26 80.77 81.22 81.67 82.11 82.56 83.01 83.46 83.91

27 85.24 85.71 86.17 86.64 87.10 87.57 88.04 88.50

28 89.90 90.38 90.87 91.35 91.84 92.32 92.80 93.29

29 94.74 95.26 95.78 96.30 96.82 89.34 97.85 98.37

*Specify enthalpy of dry air assigned a value of zero at O'C

SnyderGeneral 13600 Industrial Park Blvd., P.O Box 1551, Minneapolis, MN 55440 (612) 553-5330

G) Printed on recycled paper containing at least 10% post-consumer recycled material.

.8 .9 20.24 20.44

22.30 22.50

24.42 24.64

26.62 26.84

28.88 29.11

31.24 31.47

33.69 33.93

36.21 36.47

38.83 39.10

41.55 41.82

44.38 44.66

47.31 47.61 50.37 50.68

53.57 53.89

56.87 57.21

60.32 60.67

63.92 64.29

67.68 68.06

71.58 71.98

75.67 76.08

79.91 80.34

84.35 84.80

88.97 89.43

93.77 94.26

98.89 99.41