C C a a s s e e H H i i s s t t o o r r y y ECP Steel Piers Model PPB-350 Earth Contact Products, LLC. 15612 S. Keeler Terrace, Olathe, KS 66062 866.327.0007- FAX 913.393.0008 Leaning Grain Silo Restored with ECP Steel Piers Garrison, Iowa Project Summary Project: Johnson Farms Grain Silo Restoration Installing Contractor: Iowa Wall Sawing Independence, Iowa Engineer: Mark Schuchard, P.E. VJ Engineering, Coralville, Iowa Product Installed: ECP Model PPB-350 Steel Pier with 4” Sleeving to 25 feet Number of Placements: 18 Average Proof Test: 60,000 lb Ultimate Capacity: 86,000 lb Average Working Load: 48,000 lb Factor of Safeties: 1.3:1 Test Load to Working Load 1.8:1 Ultimate to Working Load Poor drainage caused softening of the soil underlying the foundation at one side of a 100 foot tall, 30 foot diameter grain silo. The total structural weight of the silo was estimated at 680,000 pounds and the silo has a grain capacity of 1,265 tons. The engineer estimated that the northwest portion of the foundation had settled four inches causing the silo to tilt. The engineer concluded that the settlement was the result of compromised support under the foundation as a result of moisture intrusion through a crack between the walls and slab. The subsequent freeze and thaw cycles over several years expanded the foundation crack allowing more water intrusion each year, which eventually permitted flow and erosion of the underlying soil. The moisture laden soil under the footing and void under the silo caused the failure of foundation support for a part of the structure. Maximum settlement exceeded four inches. The engineer recommended deep foundation piles to transfer the structural load from the failing soil under the footing to a suitable load bearing stratum below the surface. ECP Steel Piers were selected for rapid repair and restoration of lost elevation with the least disturbance to the weak soil adjacent to the silo foundation. The PPB-350 Steel Pier System uses 3-1/2 inch diameter pier pipe. For additional stability, and to increase the moment of inertia (stiffness) of the steel pier, 4 inch diameter pipe sleeves were installed over the pier pipe. The sleeve joints and the pipe joints were staggered to strengthen the coupled joints of the pier system. The Model PPB-350 ECP Steel Piers were installed on this site using vibration free hydraulics to achieve depths between 35 and 50 feet below grade where end bearing was encountered. Once end bearing resistance was found, a proof test was applied to each pier. Depending upon where the piers are mounted on the structure, proof test forces ranged from 56,000 to 66,000 pounds. All testing was performed prior to placing the ECP Steel Piers into service. Steel Piers Location Settled Grain Silo

Transcript of CaseHistory ECPSteelPiers … ·  · 2015-02-09CaseHistory ECPSteelPiers ... Leaning Grain Silo...

Page 1: CaseHistory ECPSteelPiers … ·  · 2015-02-09CaseHistory ECPSteelPiers ... Leaning Grain Silo Restored with ECP Steel Piers ... The moisture laden soil under the footing and void

CCaassee HHiissttoorryy EECCPP SStteeeell PPiieerrss™™

MMooddeell PPPPBB--335500

Earth Contact Products, LLC. 15612 S. Keeler Terrace, Olathe, KS 66062 866.327.0007- FAX 913.393.0008

Leaning Grain SiloRestored with

ECP Steel Piers™

Garrison, Iowa

Project Summary

Project: Johnson Farms Grain Silo Restoration

InstallingContractor:

Iowa Wall SawingIndependence, Iowa Engineer: Mark Schuchard, P.E.

VJ Engineering, Coralville, Iowa

Product Installed: ECP Model PPB-350 Steel Pier™ with 4” Sleeving to 25 feetNumber of Placements: 18 Average Proof Test: 60,000 lbUltimate Capacity: 86,000 lb Average Working Load: 48,000 lbFactor of Safeties: 1.3:1 Test Load to Working Load 1.8:1 Ultimate to Working Load

Poor drainage caused softening of the soil underlying the foundation atone side of a 100 foot tall, 30 foot diameter grain silo. The totalstructural weight of the silo was estimated at 680,000 pounds and thesilo has a grain capacity of 1,265 tons. The engineer estimated thatthe northwest portion of the foundation had settled four inches causingthe silo to tilt.

The engineer concluded that the settlement was the result of compromised support under thefoundation as a result of moisture intrusion through a crack between the walls and slab. Thesubsequent freeze and thaw cycles over several years expanded the foundation crack allowingmore water intrusion each year, which eventually permitted flow and erosion of the underlyingsoil. The moisture laden soil under the footing and void under the silo caused the failure offoundation support for a part of the structure. Maximum settlement exceeded four inches.

The engineer recommended deep foundation piles to transfer the structural load from the failingsoil under the footing to a suitable load bearing stratum below the surface. ECP Steel Piers™

were selected for rapid repair and restoration of lost elevation with the least disturbance to theweak soil adjacent to the silo foundation. The PPB-350 Steel Pier System uses 3-1/2 inchdiameter pier pipe. For additional stability, and to increase the moment of inertia (stiffness) of thesteel pier, 4 inch diameter pipe sleeves were installed over the pier pipe. The sleeve joints andthe pipe joints were staggered to strengthen the coupled joints of the pier system.

The Model PPB-350 ECP Steel Piers™ were installed on this site using vibration free hydraulics toachieve depths between 35 and 50 feet below grade where end bearing was encountered. Onceend bearing resistance wasfound, a proof test wasapplied to each pier.Depending upon where thepiers are mounted on thestructure, proof test forcesranged from 56,000 to66,000 pounds. All testingwas performed prior toplacing the ECP SteelPiers™ into service.

Steel Piers Location

Settled Grain Silo

Page 2: CaseHistory ECPSteelPiers … ·  · 2015-02-09CaseHistory ECPSteelPiers ... Leaning Grain Silo Restored with ECP Steel Piers ... The moisture laden soil under the footing and void

Earth Contact Products, LLC. 15612 S. Keeler Terrace, Olathe, KS 66062 866.327.0007- FAX 913.393.0008

Installation and Restoration Sequence

1. Prior to ECP Steel Pier™ installation, access for the pier bracketsand pipes were made. Most of the steel piers were installed onthe outside of the silo, but where there were obstructions outside;the piers were installed from the inside of the silo.

2. The PPB-350 Footing Brackets were installed and bolted in placewith the bracket bearing plates in contact with the undersides ofthe footings. The technician is shown installing the 3-1/2 inchdiameter pier pipe into the soil until suitable firm bearing wasencountered. Once the bedrock was reached at depths rangingfrom 35 to 50 feet, the technician installed 25 feet of 4 inchdiameter sleeve over the pier pipe to stiffen the pier shaft andstrengthen the coupled joints. Following the pipe and sleeveinstallation, each placement was proof tested to 60,000 pounds toverify the competency of the load bearing stratum.

3. Once all of the piers were installed and proof tested, hydraulicrams applied 48,000 pounds of force at each placementsimultaneously to recover the lost elevation. The load at eachplacement location was monitored by a pressure gauge.

4. Lifting the silo was accomplished by placing a 25 ton hydraulicram between the top of the pier pipe and a lifting assembly thatwas attached to each pier bracket.

5. The engineer specified a maximum recovery of 2-1/2 inches. Fullrecovery was restricted by external connections to the silo andother existing structural conditions.

6. Once the lost elevation was recovered, the bolts on the pier capswere tightened and the hydraulic lifting rams and lifting assembliesremoved. Afterwards, the void beneath the silo slab was injectedwith polyurethane foam to provide uniform support under the slabprior to filling the silo.

Disturbed soil in the area of work was replaced and concrete that wasremoved for access to the foundation was replaced. Drainagecorrections insured that the cause of the settlement was removed.

This successful project was completed on time and within budget byIowa Wall Sawing.

ECP Steel Piers™

“Designed and Engineered to Perform”

3

4

5

2

1

2-1/2”2-1/2”