CALIFORNIA 2010 - IAPMO Group California Plumbing Code/Chapter 05.pdf · 507.3 Indoor Opening Size...
Transcript of CALIFORNIA 2010 - IAPMO Group California Plumbing Code/Chapter 05.pdf · 507.3 Indoor Opening Size...
Adopting Agency BSC SFM HCD DSA OSHPD CSA DPH AGR DWR CA
1 2 1/AC AC SS SS/CC 1 2 3 4
Adopt Entire Chapter X X X X X X XAdopt Entire Chapter asamended (amended sectionslisted below)
X X X
Adopt only those sectionsthat are listed belowChapter/Section508.2 X X X
692010 CALIFORNIA PLUMBING CODE
CALIFORNIA PLUMBING CODE – MATRIX ADOPTIONTABLECHAPTER 5 -WATER HEATERS
70 2010 CALIFORNIA PLUMBING CODE
Part I
501.0 General.The regulations of this chapter shall govern the construction,location, and installation of fuel-burning and other waterheaters heating potable water, together with chimneys, vents,and their connectors. The minimum capacity for water heatersshall be in accordance with the first hour rating listed in Table5-1. Design, construction, and workmanship shall be in con-formity with accepted engineering practices, manufacturer’sinstallation instructions, and applicable standards and shallbe of such character as to secure the results sought to be ob-tained by this code. No water heater shall be hereinafter in-stalled that does not comply in all respects with the type andmodel of each size thereof approved by theAuthority HavingJurisdiction.A list of accepted gas appliance standards are in-cluded in Table 14-1.
502.0 Definitions.502.1 Appliance Categorized Vent Diameter/Area. Theminimum vent area/diameter permissible for Category I ap-pliances to maintain a nonpositive vent static pressure whentested in accordance with nationally recognized standards.[NFPA 54:3.3.7]502.2 Chimney (See also Gas Vent, and Venting System).One (1) or more passageways, vertical or nearly so, for con-veying flue or vent gases to the outside atmosphere. [NFPA54:3.3.17]502.3 Chimney, Factory-Built. A chimney composed oflisted factory-built components assembled in accordance withthe terms of listing to form the completed chimney. [NFPA54:3.3.17.2]502.4 Chimney, Masonry. A field-constructed chimney ofsolid masonry units, bricks, stones, listed masonry chimneyunits, or reinforced portland cement concrete, lined with suit-able chimney flue liners. [NFPA 54:3.3.17.3]502.5 Chimney, Metal. A field-constructed chimney ofmetal. [NFPA 54:3.3.17.4]502.6 Combustible Material. As pertaining to materials ad-jacent to or in contact with heat-producing appliances, ventconnectors, gas vents, chimneys, steam and hot water pipes,and warm air ducts, shall mean materials made of or surfaced
with wood, compressed paper, plant fibers, or other materialsthat are capable of being ignited and burned. Such materialshall be considered combustible even though flame-proofed,fire-retardant treated, or plastered. [NFPA 54:3.3.65.1]502.7 Direct-Vent Appliances. Appliances that are con-structed and installed so that air for combustion is derived di-rectly from the outside atmosphere and all flue gases aredischarged to the outside atmosphere. [NFPA 54:3.3.6.3]502.8 Flue Collar. That portion of an appliance designed forthe attachment of a draft hood, vent connector, or venting sys-tem. [NFPA 54:3.3.45]502.9 Gas Vent, Type B. Avent for venting-listed gas appli-ances with draft hoods and other Category I appliances listedfor use with Type B gas vents. [NFPA 54:3.3.105.2.2]502.10 Gas Vent, Type L. A vent for venting applianceslisted for use with Type L vents and appliances listed for usewith Type B gas vents. [NFPA 54:3.3.105.2.4]502.11 Indirect-Fired Water Heater. A water heater con-sisting of a storage tank equipped with an internal or externalheat exchanger used to transfer heat from an external sourceto heat potable water. The storage tank either contains heatedpotable water or water supplied from an external source, suchas a boiler.502.12 Vent. A passageway used to convey flue gases fromthe gas utilization appliances or their vent connectors to theoutside atmosphere. [NFPA 54:3.3.103]502.13 Vent Connector. The pipe or duct that connects afuel-gas-burning appliance to a vent or chimney. [NFPA54:3.3.106]502.14 Venting System.Acontinuous open passageway fromthe flue collar or draft hood of a gas-burning appliance to theoutside atmosphere for the purpose of removing flue or ventgases. [NFPA 54:3.3.96.6]502.15 Water Heater. An appliance for supplying hot waterfor domestic or commercial purposes. [NFPA 54:3.3.55.7]
503.0 Permits.It shall be unlawful for any person to install, remove, or re-place or cause to be installed, removed, or replaced any waterheater without first obtaining a permit from the AuthorityHaving Jurisdiction to do so.
712010 CALIFORNIA PLUMBING CODE
CHAPTER 5WATER HEATERS
TABLE 5-11
FIRST HOUR RATING
Note:1 The first hour rating is found on the “Energy Guide” label.2 Non-storage and solar water heaters shall be sized to meet the appropriate first hour rating as shown in the table.
Number of Bathrooms 1 to 1.5 2 to 2.5 3 to 3.5
Number of Bedrooms 1 2 3 2 3 4 5 3 4 5 6
First Hour Rating,2 Gallons 42 54 54 54 67 67 80 67 80 80 80
504.0 Inspection.504.1 Inspection of Chimneys or Vents. This inspectionshall be made after all chimneys, vents, or parts thereof, au-thorized by the permit, have been installed and before anysuch vent or part thereof has been covered or concealed.504.2 Final Water Heater Inspection. This inspection shallbe made after all work authorized by the permit has been in-stalled. TheAuthority Having Jurisdiction will make such in-spection as deemed necessary to be assured that the work hasbeen installed in accordance with the intent of this code. Noappliance or part thereof shall be covered or concealed untilthe same has been inspected and approved by the AuthorityHaving Jurisdiction.
505.0 Water Heater Requirements.505.1 Location. Water heater installations in bedrooms andbathrooms shall comply with one of the following [NFPA54:10.28.1]:(1) Fuel-burning water heaters may be installed in a closet
located in the bedroom or bathroom provided the closetis equipped with a listed, gasketed door assembly and alisted self-closing device. The self-closing door assemblyshall meet the requirements of Section 505.1.1. The doorassembly shall be installed with a threshold and bottomdoor seal and shall meet the requirements of Section505.1.2. All combustion air for such installations shallbe obtained from the outdoors in accordance with Sec-tion 507.4. The closet shall be for the exclusive use ofthe water heater.
(2) Water heater shall be of the direct vent type. [NFPA54:10.28.1(2)]505.1.1 Self-Closing Doors. Self-closing doors shallswing easily and freely and shall be equipped with a self-closing device to cause the door to close and latch eachtime it is opened. The closing mechanism shall not havea hold-open feature. [NFPA 80:6.1.4.2]505.1.2 Gasketing. Gasketing on gasketed doors orframes shall be furnished only in accordance with thepublished listings of the door, frame, or gasketing mate-rial manufacturer. [NFPA 80:6.4.8]Exception: Where acceptable to the Authority HavingJurisdiction, gasketing of non-combustible or limited-combustible material (See NFPA220, Standard on Typesof Building Construction) shall be permitted to be ap-plied to the frame, provided closing and latching of thedoor are not inhibited.
505.2 Water heaters of other than the direct-vent type shallbe located as close as practical to the chimney or gas vent.[NFPA 54:9.28.1.2]505.3 Clearance.
505.3.1 The clearances shall not be such as to interferewith combustion air, draft hood clearance and relief, andaccessibility for servicing. Listed water heaters shall beinstalled in accordance with their listings and the manu-facturer’s instructions. [NFPA 54:10.28.2.1]
505.3.2 Unlisted water heaters shall be installed with aclearance of twelve (12) inches (300 mm) on all sidesand rear. Combustible floors under unlisted water heatersshall be protected in an approved manner. [NFPA54:10.28.2.2]
505.4 Pressure-Limiting Devices. A water heater installa-tion shall be provided with overpressure protection by meansof an approved, listed device, installed in accordance with theterms of its listing and the manufacturer's instructions. [NFPA54:10.28.3]505.5 Temperature-Limiting Devices. A water heater in-stallation or a hot water storage vessel installation shall beprovided with over temperature protection by means of an ap-proved, listed device installed in accordance with the terms ofits listing and the manufacturer's instructions. [NFPA54:10.28.4]505.6 Temperature, Pressure, and VacuumRelief Devices.The installation of temperature, pressure, and vacuum reliefdevices or combinations thereof, and automatic gas shutoffdevices, shall be installed in accordance with the terms oftheir listings and the manufacturer’s instructions. A shutoffvalve shall not be placed between the relief valve and thewater heater or on discharge pipes between such valves andthe atmosphere. The hourly Btu discharge capacity or therated steam relief capacity of the device shall be not less thanthe input rating of the water heater. [NFPA 54:10.28.5]
506.0 Oil-Burning and OtherWater Heaters.506.1Water heaters deriving heat from fuels or types of energyother than gas shall be constructed and installed in accordancewith approved standards. Vents or chimneys for such appli-ances shall be approved types. An adequate supply of air forcombustion and for adequate ventilation of heater rooms orcompartments shall be provided. Each such appliance shall beinstalled in a location approved by the Authority Having Ju-risdiction and local and state fire-prevention agencies.506.2 Storage-type water heaters and hot water boilers de-riving heat from fuels or types of energy other than gas, shallbe provided with, in addition to the primary temperature con-trols, an over temperature safety protection device con-structed, listed, and installed in accordance with nationallyrecognized applicable standards for such devices and a com-bination temperature and pressure-relief valve.506.3 Oil-fired water heaters shall be installed in accordancewith NFPA 31, Standard for the Installation of Oil-BurningEquipment.506.4 Indirect-Fired Water Heaters.
506.4.1 Indirect-fired water heaters shall conform to ap-plicable sections of the ASME Boiler and Pressure Ves-sel Code, or to one (1) of the other applicable standardsshown in Table 14-1. Each water heater shall bear a labelin accordance withASME requirements, or an approvedtesting agency, certifying and attesting that such an ap-pliance has been tested, inspected and meets the require-ments of the applicable standards or code.
72 2010 CALIFORNIA PLUMBING CODE
WATER HEATERS
506.4.2 Indirect-fired water heater that incorporate a sin-gle-wall heat exchanger shall meet all of the followingrequirements:
(1) Connected to a low-pressure hot water boiler lim-ited to a maximum of thirty (30) psig by an approvedsafety or relief valve.
(2) Heater transfer medium is either potable water orcontains fluids having a toxicity rating or Class of 1.
(3) Bear a label with the word “Caution,” followed bythe following statements:
(a) The heat-transfer medium must be water orother nontoxic fluid having a toxic rating orClass of 1 as listed in Clinical Toxicology ofCommercial Products, 5th edition.
(b) The pressure of the heat-transfer medium mustbe limited to a maximum of thirty (30) psig(207 kPa) by an approved safety or relief valve.
Note: The word “Caution” and the statementsin letters having an uppercase height of not lessthan 0.120 of an inch (3.0 mm). The verticalspacing between lines of type shall be not lessthan 0.046 of an inch (1.2 mm). Lowercase let-ters shall be compatible with the uppercase let-ter size specification.
507.0 Air for Combustion and Ventilation.
507.1 General.
507.1.1 Air for combustion, ventilation, and dilution offlue gases for gas utilization appliances installed in build-ings shall be obtained by application of one (1) of themethods covered in Sections 507.2.1 through 507.7. Gasutilization appliances of other than natural draft and Cat-egory I vented appliances shall be provided with com-bustion, ventilation, and dilution air in accordance withthe appliance manufacturer's instructions. Where infil-tration does not provide the necessary air, outdoor airshall be introduced in accordance with methods coveredin Sections 507.4 through 507.7. [NFPA 54:9.3.1.1]
Exceptions:
(1) This provision shall not apply to direct-vent appli-ances.
(2) Type 1 clothes dryers that are provided with make-up air in accordance with section NFPA 54:10.4.3.
507.1.1.1 Clothes Dryer. A device used to dry wetlaundry by means of heat derived from the combus-tion of fuel gases. [NFPA 54:3.3.18]
507.1.1.2 Clothes Dryer, Type 1. Primarily used infamily living environment. May or may not be coin-operated for public use. [NFPA 54:3.3.18.1]
507.1.1.3 Exhausting to the Outdoors. Type 1 andType 2 clothes dryers shall be exhausted to the out-side air. [NFPA 54:10.4.2]
507.1.1.4 Provisions for Make-Up Air. Make-upair shall be provided for Type 1 clothes dryers in ac-cordance with the manufacturer’s installation in-structions. [NFPA 54:10.4.3.1]
507.1.2 Gas appliances of other than natural draft designand other than Category I vented appliances shall be pro-vided with combustion, ventilation, and dilution air inaccordance with the appliance manufacturer's instruc-tions. [NFPA 54:9.3.1.2]
507.1.3 Where used, a draft hood or a barometric draftregulator shall be installed in the same room or enclo-sure as the appliance served so as to prevent any differ-ence in pressure between the hood or regulator and thecombustion air supply. [NFPA 54:9.3.1.4]
507.1.4 Makeup air requirements for the operation of ex-haust fans, kitchen ventilation systems, clothes dryers,and fireplaces shall be considered in determining the ad-equacy of a space to provide combustion air require-ments. [NFPA 54:9.3.1.5]
507.2 Indoor Combustion Air. The required volume of in-door air shall be determined in accordance with Sections507.2.1 or 507.2.2 except that where the air infiltration rate isknown to be less than 0.40 ACH, Section 507.2.2 shall beused. The total required volume shall be the sum of the re-quired volume calculated for all appliances located within thespace. Rooms communicating directly with the space inwhich the appliances are installed through openings not fur-nished with doors, and through combustion air openings sizedand located in accordance with Section 507.3 are considereda part of the required volume. [NFPA 54:9.3.2]
507.2.1 Standard Method. The required volume shallbe not less than fifty (50) cubic feet per 1,000 Btu/hour(4.8 m3/kW). [NFPA 54:9.3.2.1]
507.2.2 Known Air Infiltration Rate Method. Wherethe air infiltration rate of a structure is known, the mini-mum required volume shall be determined as follows[NFPA 54:9.3.2.2]:
(1) For appliances having other than fan-assisted, com-bustion systems: calculate using Equation 5-1 butnot less than thirty-five (35) cubic feet per 1,000Btu/hour (3.4 m3/kW). [NFPA 54:9.3.2.2(1)]
(2) For fan-assisted combustion system appliances, cal-culate using Equation 5-2 but not less than twenty-five (25) cubic feet per 1,000 Btu/hour (2.4 m3/kW).[NFPA 54: 9.3.2.2(2)]
(3) For purposes of this calculation, an infiltration rategreater than 0.60 ACH shall not be used in the equa-tions. [NFPA 54:9.3.2.2(3)]
Equation 5-1:
Required volume other > ( 21 ft3 /ACH) x ( Iother/1,000Btu/h)
Equation 5-2:
Required volume fan > ( 15 ft3 /ACH) x ( Ifan/1,000Btu/h)
Where:
Iother = All appliances other than fan-assisted input inBtu/hour
Ifan = Fan-assisted appliance input in Btu/hour
ACH = Air change per hour (Percent of volume of spaceexchanged per hour, expressed as a decimal)
732010 CALIFORNIA PLUMBING CODE
WATER HEATERS
507.3 Indoor Opening Size and Location. Openings usedto connect indoor spaces shall be sized and located in accor-dance with the following [NFPA 54:9.3.2.3]:
(1) Combining spaces on the same story. Each opening shallhave a free area of not less than one (1) square inch/1,000 Btu/h (2,200 mm2/kW) of the total input rating ofall gas utilization appliances in the space, but not lessthan one-hundred (100) square inches (0.06 m2). One (1)opening shall commence within twelve (12) inches (300mm) of the top, and one (1) opening shall commencewithin twelve (12) inches (300 mm) of the bottom of theenclosure [see Figure 5-7]. The dimension of air open-ings shall be not less than three (3) inches (80 mm).[NFPA 54:9.3.2.3(1)]
(2) Combining spaces in different stories. The volumes ofspaces in different stories shall be considered as com-municating spaces where such spaces are connected byone (1) or more openings in doors or floors having a totalfree area of not less than two (2) square inches/1,000Btu/h (4,400 mm2/kW) of total input rating of all gas uti-lization appliances. [NFPA 54:9.3.2.3(2)]
507.4 Outdoor Combustion Air. Outdoor combustion airshall be provided through opening(s) to the outdoors in ac-cordance with methods Sections 507.4.1 or 507.4.2. The di-mension of air openings shall be not less than three (3) inches(80 mm). [NFPA 54:9.3.3]
507.4.1 Two Permanent Openings Method. Two (2)permanent openings, one (1) commencing within twelve(12) inches (300 mm) of the top and one (1) commenc-ing within twelve (12) inches (300 mm) of the bottom ofthe enclosure shall be provided. The openings shall com-municate directly, or by ducts, with the outdoors orspaces that freely communicate with the outdoors as fol-lows [NFPA 54:9.3.3.1]:
(1) Where directly communicating with the outdoors orwhere communicating to the outdoors through ver-tical ducts, each opening shall have a free area of notless than one (1) square inch/4000 Btu/h (550mm2/kW) of total input rating of all appliances inthe enclosure. [See Figures 5-8 and 5-9.] [NFPA54:9.3.3.1(1)]
(2) Where communicating with the outdoors throughhorizontal ducts, each opening shall have a free areaof not less than one (1) square inch/2,000 Btu/h(1,100 mm2/kW) of total input rating of all appli-ances in the enclosure. [See Figure 5-10] [NFPA54:9.3.3.1(2)]
507.4.2 One Permanent Opening Method. One (1) per-manent opening, commencing within twelve (12) inches(300 mm) of the top of the enclosure, shall be provided.The appliance shall have clearances of not less than one(1) inch (25 mm) from the sides and back and six (6)inches (160 mm) from the front of the appliance. Theopening shall directly communicate with the outdoors orshall communicate through a vertical or horizontal duct tothe outdoors or spaces that freely communicate with the
outdoors [see Figure 5-11] and shall have a minimum freearea of the following [NFPA 54:9.3.3.2]:
(1) One (1) square inch/3,000 Btu/h (700 mm2/kW) ofthe total input rating of all appliances located in theenclosure, and [NFPA 54:9.3.3.2(1)]
(2) Not less than the sum of the areas of all vent con-nectors in the space. [NFPA 54:9.3.3.2(2)]
507.5 Combination Indoor and Outdoor Combustion Air.The use of a combination of indoor and outdoor combustionair shall be in accordance with Sections 507.5.1, 507.5.2 and507.5.3 [see example calculation in NFPA 54 Annex J andthis chapter – Part II] [NFPA 54:9.3.4].
507.5.1 Indoor Openings. Where used, openings con-necting the interior spaces shall comply with Section507.3. [NFPA 54:9.3.4(1)]
507.5.2 Outdoor openings shall be located in accordancewith Sections 507.4.1 or 507.4.2. [NFPA 54:9.3.4(2)]
507.5.3 Outdoor Openings Size. The outdoor openingssize shall be calculated in accordance with the following[NFPA 54:9.3.4(3)]:
(1) The ratio of interior spaces shall be the available vol-ume of communicating spaces divided by the re-quired volume.
(2) The outdoor size reduction factor shall be one (1)minus the ratio of interior spaces.
(3) The minimum size of outdoor openings shall be thefull size of outdoor openings calculated in accor-dance with Sections 507.4.1 or 507.4.2, multipliedby the reduction factor. The dimension of air open-ings shall be not less than three (3) inches (80 mm).[NFPA 54:9.3.4(3)(c)]
507.6 Engineered Installations. Engineered combustion airinstallations shall provide an adequate supply of combustion,ventilation, and dilution air and shall be approved by the Au-thority Having Jurisdiction. [NFPA 54:9.3.5]
507.7 Mechanical Combustion Air Supply. Where com-bustion air is provided by a mechanical air supply system, thecombustion air shall be supplied from outdoors at the mini-mum rate of 0.35 cubic feet/min per 1,000 Btu/h (0.034m3/min per kW) for appliances located within the space.[NFPA 54:9.3.6]
507.7.1 Where exhaust fans are installed, additional airshall be provided to replace the exhausted air. [NFPA54:9.3.6.1]
507.7.2 Each of the appliances served shall be inter-locked to the mechanical air supply system to preventmain burner operation where the mechanical air supplysystem is not in operation. [NFPA 54:9.3.6.2]
507.7.3 Where combustion air is provided by the build-ing's mechanical ventilation system, the system shall pro-vide the specified combustion air rate in addition to therequired ventilation air. [NFPA 54:9.3.6.3]
507.8 Louvers, Grilles and Screens.
(A) Louvers and Grilles. The required size of openings forcombustion, ventilation, and dilution air shall be based
74 2010 CALIFORNIA PLUMBING CODE
WATER HEATERS
<on the net free area of each opening. Where the free areathrough a design of louver or grille is known, it shall beused in calculating the size opening required to providethe free area specified. Where the design and free areaare not known, it shall be assumed that wood louvers willhave 25 percent free area and metal louvers and grilleswill have 75 percent free area. Nonmotorized louvers andgrilles shall be fixed in the open position. [NFPA54:9.3.7.1]
(B) Minimum Screen Mesh Size. Screens shall be not lessthan one-fourth (1⁄4) inch mesh. [NFPA 54:9.3.7.2]
(C) Motorized louvers shall be interlocked with the appli-ance so they are proven in the full open position prior tomain burner ignition and during main burner operation.Means shall be provided to prevent the main burner fromigniting should the louver fail to open during burner start-up and to shut down the main burner if the louvers closeduring burner operation. [NFPA 54:9.3.7.3]
507.9 Combustion Air Ducts. Combustion air ducts shallcomply with the following:(1) Ducts shall be of galvanized steel or a material having
equivalent corrosion resistance, strength, and rigidity.[NFPA 54:9.3.8.1]Exception:Within dwelling units, unobstructed stud andjoist spaces shall not be prohibited from conveying com-bustion air, provided that not more than one (1) fireblockis removed.
(2) Ducts shall terminate in an unobstructed space, allowingfree movement of combustion air to the appliances.[NFPA 54:9.3.8.2]
(3) Ducts shall serve a single space. [NFPA 54:9.3.8.3](4) Ducts shall not service both upper and lower combustion
air openings where both such openings are used. The sep-aration between ducts serving upper and lower combus-tion air openings shall be maintained to the source ofcombustion air. [NFPA 54:9.3.8.4]
(5) Ducts shall not be screened where terminating in an atticspace. [NFPA 54:9.3.8.5]
(6) Intakes for combustion air ducts located exterior to thebuilding shall have the lowest side of the combustion airintake openings located at least twelve (12) inches (300mm) vertically from the adjoining finished grade level.
(7) Horizontal upper combustion air ducts shall not slopedownward toward the source of combustion air. [NFPA54:9.3.8.6]
(8) The remaining space surrounding a chimney liner, gasvent, special gas vent, or plastic piping installed within amasonry chimney flue, metal or factory-built chimney,shall not be used to supply combustion air [NFPA54:9.3.8.7], unless it is listed and shown in the manufac-turer's installation instructions.
508.0 OtherWater Heater Installation Requirements.508.1 The Authority Having Jurisdiction shall have the au-thority to require the use of an approved dielectric insulator
on the water piping connections of water heaters and relatedwater heating appliances.508.2 Protection from Seismic Damage.Water heaters shallbe anchored or strapped to resist horizontal displacement dueto earthquake motion. Strapping shall be at points within theupper one third (1⁄3) and lower one-third (1⁄3) of its vertical di-mensions. At the lower point, a minimum distance of four (4)inches (102 mm) shall be maintained above the controls withthe strapping.Note: [HCD 1 & HCD 2] Reference Health and Safety CodeSection 19211(a) which addresses new, replacement, and ex-isting water heaters.Note: The applicable subsection of Health and Safety CodeSection 19211(a) which addresses new, replacement, and ex-isting water heaters is repeated here for clarity and reads asfollows:
Section 19211(a) Notwithstanding Section 19100, all newand replacement water heaters, and all existing residentialwater heaters shall be braced, anchored, or strapped to resistfalling or horizontal displacement due to earthquake motion.At a minimum, any water heater shall be secured in accor-dance with the California Plumbing Code, or modificationsmade thereto by a city, county, or city and county pursuant toSection 17958.5.508.3Awater heater supported from the ground shall rest onlevel concrete or other approved base extending not less thanthree (3) inches (76 mm) above the adjoining ground level.508.4When a water heater is located in an attic, attic-ceilingassembly, floor-ceiling assembly, or floor-subfloor assemblywhere damage results from a leaking water heater, a water-tight pan of corrosion-resistant materials shall be installed be-neath the water heater with not less than three-quarters (3⁄4) ofan inch (20 mm) diameter drain to an approved location.508.5 Relief Valve Discharge. Discharge from a relief valveinto a water heater pan shall be prohibited.508.6Added or ConvertedAppliances.When an additionalor replacement appliance is installed or an appliance is con-verted to gas from another fuel, the location in which the ap-pliance is to be operated shall be checked to verify thefollowing [NFPA 54:9.1.2]:
508.6.1 Air for combustion and ventilation is providedwhere required, in accordance with the provisions of Sec-tion 507.0. Where existing facilities are not adequate,they shall be upgraded to Section 507.0 specifications.[NFPA 54:9.1.2(1)]508.6.2 The installation components and appliances meetthe clearances to combustible material provisions ofNFPA54:9.2.2. It shall be determined that the installationand operation of the additional or replacement appliancedoes not render the remaining appliance unsafe for con-tinued operation. [NFPA 54:9.1.2(2)](The following reference was extracted from NFPA 54,National Fuel Gas Code).9.2.2 Clearance to Combustible Materials. Appliancesand their vent connectors shall be installed with clear-ances from combustible material so their operation will
752010 CALIFORNIA PLUMBING CODE
WATER HEATERS
not create a hazard to persons or property. Minimumclearances between combustible walls and the back andsides of various conventional types of appliances andtheir vent connectors are specified in Chapters 10 and12. (Reference can also be made to NFPA 211, Standardfor Chimneys, Fireplaces, Vents, and Solid Fuel-BurningAppliances.)508.6.3 The venting system is constructed and sized inaccordance with the provisions of this chapter. Where theexisting venting system is not adequate, it shall be up-graded to comply with this chapter. [NFPA 54:9.1.2(3)]
508.7 Types of Gases. It shall be determined whether the gas-utilization appliance has been designed for use with the gas towhich it will be connected. No attempt shall be made to con-vert the appliance from the gas specified on the rating platefor use with a different gas without consulting the installationinstructions, the serving gas supplier, or the appliance manu-facturer for complete instructions. [NFPA 54:9.1.3]508.8 Safety Shutoff Devices for Unlisted LP-Gas Appli-ance Used Indoors. Unlisted gas utilization appliances foruse with undiluted liquefied petroleum gases and installed in-doors shall be equipped with safety shutoff devices of thecomplete shutoff type. [NFPA 54:9.1.4]508.9 Use of Air or Oxygen Under Pressure.Where air oroxygen under pressure is used in connection with the gas sup-ply, effective means such as a back-pressure regulator and re-lief valve shall be provided to prevent air or oxygen frompassing back into the gas piping. Where oxygen is used, in-stallation shall be in accordance with NFPA 51, Standard forthe Design and Installation of Oxygen-Fuel Gas Systems forWelding, Cutting, and Allied Processes. [NFPA 54:9.1.5]508.10 Protection of GasAppliances from Fumes or GasesOther than Products of Combustion. Non-direct vent-typegas appliances installed in beauty shops, barbershops, or otherfacilities where chemicals that generate corrosive or flam-mable products such as aerosol sprays are routinely used shallbe located in an equipment room separate or partitioned offfrom other areas with provisions for combustion and dilutionair from outdoors. Direct vent appliances shall be installed inaccordance with the appliance manufacturer's installation in-structions. [NFPA 54:9.1.6.2]508.11 Process Air. In addition to air needed for combustionin commercial or industrial processes, process air shall be pro-vided as required for cooling of equipment or material, con-trolling dew point, heating, drying, oxidation, dilution, safetyexhaust, odor control, air for compressors, and for comfortand proper working conditions for personnel. [NFPA54:9.1.7]508.12 Building Structural Members.
508.12.1 Structural members of a building shall not passthrough gas utilization appliances having an operatingtemperature exceeding 500°F (260°C). [NFPA54:9.1.8.1]508.12.2 Structural members passing through gas uti-lization appliances having an operating temperature of500°F (260°C) or less shall be of noncombustible mate-rial. Building columns, girders, beams, or trusses shall
not be installed within appliances, unless insulation andventilation are provided to avoid deterioration in strengthand linear expansion of the building structure in either avertical or a horizontal direction. [NFPA 54:9.1.8.2]508.12.3Gas utilization appliances shall be furnished ei-ther with load-distributing bases or with a sufficient num-ber of supports to prevent damage to either the buildingstructure or appliance. [NFPA 54:9.1.8.3]508.12.4 At the locations selected for installation of thegas utilization appliance, the dynamic and static load-carrying capacities of the building structure shall bechecked to determine whether they are adequate to carrythe additional loads. The appliance shall be supportedand shall be connected to the piping so as not to exertundue stress on the connections. [NFPA 54:9.1.8.4]
508.13 Flammable Vapors. Gas appliances shall not be in-stalled in areas where the open use, handling, or dispensing offlammable liquids occurs, unless the design, operation, or in-stallation reduces the potential of ignition of the flammablevapors. Gas utilization appliances installed in compliancewith Sections 508.14, 508.15, or 508.16 shall be consideredto comply with the intent of this provision. [NFPA 54:9.1.9]508.14 Installation in Residential Garages.(1) Gas utilization appliances in residential garages and in
adjacent spaces that open to the garage and are not partof the living space of a dwelling unit shall be installedso that burners and burner-ignition devices are locatednot less than eighteen (18) inches (450 mm) above thefloor unless listed as flammable vapor ignition resistant.[NFPA 54:9.1.10.1]
(2) Such appliances shall be located or protected so it is notsubject to physical damage by a moving vehicle. [NFPA54:9.1.10.2]
(3) When appliances are installed in a separate enclosedspace having access only from outside of the garage,such appliances shall be permitted to be installed at floorlevel, providing the required combustion air is takenfrom the exterior of the garage. [NFPA 54:9.1.10.3]
508.15 Installation in Commercial Garages.508.15.1 Parking Structures.Gas utilization appliancesinstalled in enclosed, basement, and underground park-ing structures shall be installed in accordance withNFPA 88A, Standard for Parking Structures. [NFPA54:9.1.11.1]508.15.2 Repair Garages.Gas utilization appliances in-stalled in repair garages shall be installed in a detachedbuilding or room, separated from repair areas by wallsor partitions, floors, or floor-ceiling assemblies that areconstructed so as to prohibit the transmission of vaporsand having a fire-resistance rating of not less than one(1) hour, and that have no openings in the wall separat-ing the repair area within eight (8) feet (2.5 m) of thefloor. Wall penetrations shall be fire-stopped. Air forcombustion purposes shall be obtained from outside thebuilding. The heating room shall not be used for the stor-age of combustible materials. [NFPA 54:9.1.11.2]
76 2010 CALIFORNIA PLUMBING CODE
WATER HEATERS
Exceptions:(1) Overhead heaters where installed not less than eight
(8) ft (2.5 m) above the floor shall be permitted.(2) Heating appliances for vehicle repair areas where
there is no dispensing or transferring of Class I orClass II flammable or combustible liquids or lique-fied petroleum gas shall be installed in accordancewith NFPA 30A, Code for Motor Fuel DispensingFacilities and Repair Garages. [NFPA 54:9.1.11.2]
508.16 Installation inAircraft Hangars. Heaters in aircrafthangars shall be installed in accordance with NFPA409, Stan-dard on Aircraft Hangars. [NFPA 54:9.1.12]508.17 GasAppliance Physical Protection.Where it is nec-essary to locate gas utilization appliances close to a passage-way traveled by vehicles or equipment, guardrails or bumperplates shall be installed to protect the appliance from dam-age. [NFPA 54:9.1.13]508.18 Venting of Flue Gases.Gas utilization appliances shallbe vented in accordance with the provisions of this chapter andNFPA 54, National Fuel Gas Code, Chapter 12. [NFPA54:9.1.14]508.19 Extra Device or Attachment. No device or attach-ment shall be installed on any gas utilization appliance thatcould in any way impair the combustion of gas. [NFPA54:9.1.15]508.20 Adequate Capacity of Piping.When additional gasutilization appliances are being connected to a gas piping sys-tem, the existing piping shall be checked to determine if ithas adequate capacity (See Section 1209.4.3). Where inade-quate, the existing system shall be enlarged as necessary, orseparate gas piping of adequate capacity shall be run from thepoint of delivery to the appliance. [NFPA 54:9.1.16]508.21 Avoiding Strain on Gas Piping. Gas utilization ap-pliances shall be supported and so connected to the piping asnot to exert undue strain on the connections. [NFPA54:9.1.17]508.22 GasAppliance Pressure Regulators.Where the gassupply pressure exceeds that at which the gas utilization ap-pliance is designed to operate or varies beyond the designpressure limits of the appliance, a gas appliance pressure reg-ulator shall be installed. [NFPA 54:9.1.18]508.23 Venting of Gas Appliance Pressure Regulators.Venting of gas appliance pressure regulators shall complywith the following requirements [NFPA 54:9.1.19]:
508.23.1Gas appliance pressure regulators requiring ac-cess to the atmosphere for successful operation shall beequipped with vent piping leading outdoors or, if the reg-ulator vent is an integral part of the appliance, into thecombustion chamber adjacent to a continuous pilot, un-less constructed or equipped with a vent limiting meansto limit the escape of gas from the vent opening in theevent of diaphragm failure. [NFPA 54:9.1.19(1)]508.23.2 Vent limiting means shall be employed on listedgas appliance pressure regulators only. [NFPA54:9.1.19(2)]508.23.3 In the case of vents leading outdoors, meansshall be employed to prevent water from entering this
piping and also to prevent blockage of vents by insectsand foreign matter. [NFPA 54:9.1.19(3)]508.23.4 Under no circumstances shall a regulator bevented to the gas utilization appliance flue or exhaustsystem. [NFPA 54:9.1.19(4)]508.23.5 In the case of vents entering the combustionchamber, the vent shall be located so the escaping gaswill be readily ignited by the pilot and the heat liberatedthereby will not adversely affect the normal operation ofthe safety shutoff system. The terminus of the vent shallbe securely held in a fixed position relative to the pilot.For manufactured gas, the need for a flame arrester in thevent piping shall be determined. [NFPA 54:9.1.19(5)]508.23.6 Vent lines from a gas appliance pressure regu-lator and bleed lines from a diaphragm-type valve shallnot be connected to a common manifold terminating in acombustion chamber. Vent lines shall not terminate inpositive-pressure-type combustion chambers. [NFPA54:9.1.19(6)]
508.24 Bleed Lines for Diaphragm-Type Valves. Bleedlines shall comply with the following requirements [NFPA54:9.1.20]:
508.24.1 Diaphragm-type valves shall be equipped toconvey bleed gas to the outside atmosphere or into thecombustion chamber adjacent to a continuous pilot.[NFPA 54:9.1.20(1)]508.24.2 In the case of bleed lines leading outdoors,means shall be employed to prevent water from enteringthis piping and also to prevent blockage of vents by in-sects and foreign matter. [NFPA 54:9.1.20(2)]508.24.3Bleed lines shall not terminate in the gas utilizationappliance flue or exhaust system. [NFPA54:9.1.20(3)]508.24.4 In the case of bleed lines entering the combus-tion chamber, the bleed line shall be located so the bleedgas will be readily ignited by the pilot and the heat lib-erated thereby will not adversely affect the normal oper-ation of the safety shutoff system. The terminus of thebleed line shall be securely held in a fixed position rela-tive to the pilot. For manufactured gas, the need for aflame arrester in the bleed line piping shall be deter-mined. [NFPA 54:9.1.20(4)]508.24.5 Bleed lines from a diaphragm-type valve andvent lines from a gas appliance pressure regulator shallnot be connected to a common manifold terminating in acombustion chamber. Bleed lines shall not terminate inpositive-pressure-type combustion chambers. [NFPA54:9.1.20(5)]
508.25 Combination ofAppliances.Any combination of gasutilization appliances, attachments, or devices used togetherin any manner shall comply with the standards that apply tothe individual appliance. [NFPA 54:9.1.21]508.26 Installation Instructions. The installing agency shallconform with the appliance manufacturer's recommendations
772010 CALIFORNIA PLUMBING CODE
WATER HEATERS
in completing an installation. The installing agency shall leavethe manufacturer's installation, operating, and maintenance in-structions in a location on the premises where they will be read-ily available for reference and guidance for the AuthorityHaving Jurisdiction, service personnel, and the owner or oper-ator. [NFPA54:9.1.22]508.27 Protection of Outdoor Appliances. Gas utilizationappliances not listed for outdoor installation but installed out-doors shall be provided with protection to the degree that theenvironment requires. Appliances listed for outdoor installa-tion shall be permitted to be installed without protection inaccordance with the provisions of its listing (See NFPA54:9.2.1). [NFPA 54:9.1.23]
(The following references were extracted from NFPA 54,National Fuel Gas Code.)9.2 Accessibility and Clearance.9.2.1 Accessibility for Service. Gas utilization appliancesshall be located with respect to building construction andother equipment so as to permit access to the gas utiliza-tion appliance. Sufficient clearance shall be maintained topermit cleaning of heating surfaces; the replacement offilters, blowers, motors, burners, controls, and vent con-nections; the lubrication of moving parts where neces-sary; the adjustment and cleaning of burners and pilots;and the proper functioning of explosion vents, if provided.For attic installation, the passageway and servicing areaadjacent to the appliance shall be floored.
509.0 Appliances on Roofs.509.1 General.(1) Gas utilization appliances on roofs shall be designed or
enclosed so as to withstand climactic conditions in thearea in which they are installed. Where enclosures areprovided, each enclosure shall permit easy entry andmovement, shall be of reasonable height, and shall havenot less than a thirty (30) inch (760 mm) clearance be-tween the entire service access panel(s) of the applianceand the wall of the enclosure. [NFPA 54:9.4.1.1]
(2) Roofs on which an appliance is to be installed shall be ca-pable of supporting the additional load or shall be rein-forced to support the additional load. [NFPA 54:9.4.1.2]
(3) All access locks, screws, and bolts shall be of corrosion-resistant material. [NFPA 54:9.4.1.3]
509.2 Installation of Appliances on Roofs.(1) Gas utilization appliances shall be installed in accordance
with its listing and the manufacturer's installation in-structions. [NFPA 54:9.4.2.1]
(2) Appliances shall be installed on a well-drained surfaceof the roof. Not less than six (6) feet (1.8 m) of clearanceshall be available between any part of the appliance andthe edge of a roof or similar hazard, or rigidly fixed rails,guards, parapets, or other building structures not less thanforty-two (42) inches (1.1 m) in height shall be providedon the exposed side. [NFPA 54:9.4.2.2]
(3) Appliances requiring an external source of electricalpower for its operation shall be provided with (1) a read-ily accessible electrical disconnecting means within sightof the appliance that will completely de-energize the ap-pliance, and (2) a 120-VAC grounding-type receptacleoutlet on the roof adjacent to the appliance. The recepta-cle outlet shall be on the supply side of the disconnectswitch. [NFPA 54:9.4.2.3]
(4) Where water stands on the roof of the appliance or in thepassageways to the appliance, or where the roof is of a de-sign having a water seal, a suitable platform, walkway, orboth shall be provided above the waterline. Such platformsor walkways shall be located adjacent to the appliance andcontrol panels so that the appliance can be safely servicedwhere water stands on the roof. [NFPA 54:9.4.2.4]
509.3 Access to Appliances on Roofs.509.3.1 Gas utilization appliances located on roofs orother elevated locations shall be accessible. [NFPA54:9.4.3.1]509.3.2 Buildings exceeding fifteen (15) feet (4.6 m) inheight shall have an inside means of access to the roof,unless other means acceptable to the Authority HavingJurisdiction are used. [NFPA 54:9.4.3.2]509.3.3 The inside means of access shall be a permanent,or fold-away inside stairway or ladder, terminating in anenclosure, scuttle, or trap door. Such scuttles or trap doorsshall be not less than twenty-two (22) inches x twenty-four (24) inches (560 mm x 610 mm) in size, shall openeasily and safely under all conditions, especially snow;and shall be constructed so as to permit access from theroof side unless deliberately locked on the inside.
Not less than six (6) feet (1.8 m) of clearance shallbe available between the access opening and the edge ofthe roof or similar hazard, or rigidly fixed rails or guardsnot less than forty-two (42) inches (1.1 m) in height shallbe provided on the exposed side.Where parapets or otherbuilding structures are utilized in lieu of guards or rails,they shall be not less than forty-two (42) inches (1.1 m)in height. [NFPA 54:9.4.3.3]509.3.4 Permanent lighting shall be provided at the roofaccess. The switch for such lighting shall be located in-side the building near the access means leading to theroof. [NFPA 54:9.4.3.4]
509.4 Appliances in Attics.509.4.1 Attic Access. An attic in which an appliance isinstalled shall be accessible through an opening and pas-sageway not less than as large as the largest component ofthe appliance, and not less than twenty-two (22) inches xthirty (30) inches (560 mm x 760 mm). [NFPA 54:9.5.1]509.4.2Where the height of the passageway is less thansix (6) feet (1.8 m), the distance from the passageway ac-cess to the appliance shall not exceed twenty (20) feet(6.1 m) measured along the centerline of the passageway.[NFPA 54:9.5.1.1]
78 2010 CALIFORNIA PLUMBING CODE
WATER HEATERS
509.4.3 The passageway shall be unobstructed and shallhave solid flooring not less than twenty-four (24) inches(610 mm) wide from the entrance opening to the appli-ance. [NFPA 54:9.5.1.2]509.4.4 Work Platform. A level working platform notless than thirty (30) inches (760 mm) by thirty (30)inches (760 mm) shall be provided in front of the serviceside of the appliance. [NFPA 54:9.5.2]509.4.5 Lighting and Convenience Outlet. A perma-nent 120-volt receptacle outlet and a lighting fixture shallbe installed near the appliance. The switch controllingthe lighting fixture shall be located at the entrance to thepassageway. [NFPA 54:9.5.3]
510.0 Venting of Appliances.510.1 General. This section recognizes that the choice ofventing materials and the methods of installation of ventingsystems are dependent on the operating characteristics of theappliance. [NFPA 54:12.2.1]
510.1.1 Categories.The operating characteristics of ventedgas utilization appliances can be categorizedwith respect to(1) positive or negative pressure within the venting system,and (2) whether or not the appliance generates flue or ventgases that can condense in the venting system. See NFPA54, National Fuel Gas Code, Section 3.3 for the definitionof these vented appliance categories. [NFPA54:12.2.2]510.1.2 Installation. Listed vents shall be installed in ac-cordance with Chapter 5 and the manufacturer’s instal-lation instructions. [NFPA 54:12.2.3]510.1.3 Appliance vents shall not discharge into anyspace enclosed by screens having openings less than one-fourth (1⁄4) inch (6.4 mm) mesh.
510.2 Specification for Venting.510.2.1 Connection to Venting Systems. Except as per-mitted in Sections 510.2.2 through 510.2.6, gas utiliza-tion appliances shall be connected to venting systems.[NFPA 54:12.3.1]510.2.2 Appliances Not Required to Be Vented. Thefollowing appliances shall not be required to be vented[NFPA 54:12.3.2]:
510.2.2.1 Listed ranges. [NFPA 54:12.3.2(1)]510.2.2.2 Built-in domestic cooking units listed andmarked for optional venting. [NFPA 54:12.3.2(2)]510.2.2.3 Listed hot plates and listed laundry stoves.[NFPA 54:12.3.2(3)]510.2.2.4 Listed Type 1 clothes dryers shall be ex-hausted to the outside air. [NFPA 54:12.3.2(4)]510.2.2.5Asingle listed booster-type (automatic in-stantaneous) water heater, when designed and usedsolely for the sanitizing rinse requirements of a dish-washing machine, provided that the appliance is in-stalled with the draft hood in place and unaltered if
a draft hood is required, in a commercial kitchenhaving a mechanical exhaust system; where installedin this manner, the draft hood outlet shall be not lessthan thirty-six (36) inches (910 mm) vertically andsix (6) inches (150 mm) horizontally from any sur-face other than the appliance. [NFPA 54:12.3.2(5)]510.2.2.6 Listed refrigerators. [NFPA 54:12.3.2(6)]510.2.2.7 Counter appliances. [NFPA 54:12.3.2(7)]510.2.2.8 Direct gas-fired makeup air heaters.[NFPA 54:12.3.2(9)]510.2.2.9Other appliances listed for unvented use andnot provided with flue collars. [NFPA54:12.3.2(10)]510.2.2.10 Specialized appliance of limited inputsuch as laboratory burners or gas lights. [NFPA54:12.3.2(11)]
Where appliances in Sections 510.2.2.5 through510.2.2.10 are installed so the aggregate input ratingexceeds 20 Btu/h/ft.3 (207W/m3) of room or space inwhich it is installed, one (1) or more shall be pro-vided with venting systems or other approved meansfor removing the vent gases to the outside atmos-phere so the aggregate input rating of the remainingunvented appliance does not exceed 20 Btu/h/ft.3(207W/m3). Where the calculation includes the vol-ume of an adjacent room or space, the room or spacein which the appliance is installed shall be directlyconnected to the adjacent room or space by a door-way, archway, or other opening of comparable sizethat cannot be closed. [NFPA 54:12.3.2]
510.2.3 Ventilating Hoods. Ventilating hoods and ex-haust systems shall be permitted to be used to vent gasutilization appliances installed in commercial applica-tions (See Section 510.3.5) and to vent industrial appli-ances, particularly where the process itself requires fumedisposal. [NFPA 54:12.3.3]510.2.4 Well-Ventilated Spaces. The operation of in-dustrial appliances such that its flue gases are dischargeddirectly into a large and well-ventilated space shall bepermitted. [NFPA 54:12.3.4]510.2.5 Direct-Vent Appliances. Listed direct-vent gasutilization appliances shall be considered properly ventedwhere installed in accordance with the terms of its listing,the manufacturer's instructions, and Section 510.8.3 of thiscode. [NFPA54:12.3.5]510.2.6Appliances with Integral Vents.Gas utilizationappliances incorporating integral venting means shall beconsidered properly vented where installed in accordancewith its listing, the manufacturer's instructions, and Sec-tions 510.8.1 and 510.8.2 of this code. [NFPA54:12.3.6]
510.3 Design and Construction.510.3.1Minimum Safe Performance.Aventing systemshall be designed and constructed so as to develop a pos-itive flow adequate to remove flue or vent gases to theoutside atmosphere. [NFPA 54:12.1]
792010 CALIFORNIA PLUMBING CODE
WATER HEATERS
510.3.2Appliance Draft Requirements.Aventing sys-tem shall satisfy the draft requirements of the appliancein accordance with the manufacturer's instructions.[NFPA 54:12.4.1]510.3.3 Design and Construction. Gas utilization ap-pliances required to be vented shall be connected to aventing system designed and installed in accordance withthe provisions of Sections 510.4 through 510.15 of thiscode. [NFPA 54:12.4.2]510.3.4 Mechanical Draft Systems.
510.3.4.1 Mechanical draft systems shall be listedand shall be installed in accordance with the terms oftheir listing and both the appliance and the mechan-ical draft system manufacturer’s instructions. [NFPA54:12.4.3.1]510.3.4.2 Gas utilization appliances requiring vent-ing shall be permitted to be vented by means of me-chanical draft systems of either forced or induceddraft design. [NFPA 54:12.4.3.2]Exception: Incinerators.510.3.4.3 Forced draft systems and portions of in-duced draft systems under positive pressure duringoperation shall be designed and installed so as to pre-vent leakage of flue or vent gases into a building.[NFPA 54:12.4.3.3]510.3.4.4Vent connectors serving appliances ventedby natural draft shall not be connected into any por-tion of mechanical draft systems operating underpositive pressure. [NFPA 54:12.4.3.4]510.3.4.5 Where a mechanical draft system is em-ployed, provision shall be made to prevent the flowof gas to the main burners when the draft system isnot performing so as to satisfy the operating re-quirements of the appliance for safe performance.[NFPA 54:12.4.3.5]510.3.4.6 The exit terminals of mechanical draft sys-tems shall be not less than seven (7) feet (2.1 m)above finished grade where located adjacent to pub-lic walkways and shall be located as specified inSections 510.8.1 and 510.8.2 of this code. [NFPA54:12.4.3.6]
510.3.5 Ventilating Hoods and Exhaust Systems.510.3.5.1 Ventilating hoods and exhaust systemsshall be permitted to be used to vent gas utilizationappliances installed in commercial applications.[NFPA 54:12.4.4.1]510.3.5.2Where automatically operated appliances,other than commercial cooking appliances, arevented through a ventilating hood or exhaust systemequipped with a damper or with a power means ofexhaust, provisions shall be made to allow the flowof gas to the main burners only when the damper isopen to a position to properly vent the appliance andwhen the power means of exhaust is in operation.[NFPA 54:12.4.4.2]
510.3.6 Circulating Air Ducts and Furnace Plenums.Venting systems shall not extend into or pass through anyfabricated air duct or furnace plenum. [NFPA 54-09:12.4.5.1]
510.4 Type of Venting System to Be Used.510.4.1 The type of venting system to be used shall be inaccordance with Table 5-2. [NFPA 54:12.5.1]510.4.2 Plastic Piping. Plastic piping used for ventingappliances listed for use with such venting materials shallbe approved. [NFPA 54:12.5.2]510.4.3 Plastic Vent Joints. Plastic pipe and fittings usedto vent appliances shall be installed in accordance withthe appliance manufacturer’s installation instructions.Where primer is required, it shall be of a contrastingcolor. [NFPA 54-09:12.5.3]510.4.4 Special Gas Vent. Special gas vent shall belisted and installed in accordance with the terms of thespecial gas vent listing and the manufacturer's instruc-tions. [NFPA 54:12.5.3]
510.5 Masonry, Metal, and Factory-Built Chimneys.510.5.1 Listing or Construction.
510.5.1.1 Factory-built chimneys shall be installed inaccordance with their listing and the manufacturer’sinstructions. Factory-built chimneys used to vent ap-pliances that operate at positive vent pressure shall belisted for such application. [NFPA 54:12.6.1.1]510.5.1.2Metal chimneys shall be built and installedin accordance with NFPA 211, Standard for Chim-neys, Fireplaces, Vents, and Solid Fuel-Burning Ap-pliances. [NFPA 54:12.6.1.2]510.5.1.3 Masonry chimneys shall be built and in-stalled in accordance with NFPA 211, Standard forChimneys, Fireplaces, Vents, and Solid Fuel-Burn-ing Appliances, and lined with approved clay fluelining, a listed chimney lining system, or other ap-proved material that will resist corrosion, erosion,softening, or cracking from vent gases at tempera-tures up to 1,800°F (982°C). [NFPA 54:12.6.1.3]Exception: Masonry chimney flues lined with achimney lining system specifically listed for usewith listed gas appliances with draft hoods, Cate-gory I appliances, and other gas appliances listedfor use with Type B vents shall be permitted. Theliner shall be installed in accordance with the linermanufacturer's instructions and the terms of the list-ing. A permanent identifying label shall be attachedat the point where the connection is to be made tothe liner. The label shall read: "This chimney lineris for appliances that burn gas only. Do not connectto solid- or liquid-fuel-burning appliances or incin-erators." [NFPA 54:12.6.1.3]
510.5.2 Termination.510.5.2.1 A chimney for a residential-type or low-heat gas utilization appliance shall extend at leastthree (3) feet (0.9 m) above the highest point whereit passes through the roof of a building and at leasttwo (2) feet (0.6 m) exceeding any portion of a
80 2010 CALIFORNIA PLUMBING CODE
WATER HEATERS
building within a horizontal distance of ten (10) feet(3.0 m). [See Figure 5-1.] [NFPA 54:12.6.2.1]
510.5.2.2 A chimney for a medium-heat applianceshall extend at least ten (10) feet (3.0 m) exceedingany portion of any building within twenty-five (25)feet (7.6 m). [NFPA 54:12.6.2.2]
510.5.2.3 A chimney shall extend at least five (5)feet (1.5 m) above the highest connected appliancedraft hood outlet or flue collar. [NFPA 54:12.6.2.3]
510.5.2.4 Decorative shrouds shall not be installed atthe termination of factory-built chimneys exceptwhere such shrouds are listed and labeled for usewith the specific factory-built chimney system andare installed in accordance with manufacturer’s in-stallation instructions. [NFPA 54:12.6.2.4]
510.5.3 Size of Chimneys. The effective area of a chim-ney venting system serving listed gas appliances withdraft hoods, Category I appliances, and other applianceslisted for use with Type B vents shall be in accordancewith one of the following methods [NFPA 54:12.6.3.1]:
(1) This chapter and NFPA 54: Chapter 13. [NFPA54:12.6.3.1(1)]
(2) For sizing an individual chimney venting system fora single appliance with a draft hood, the effectiveareas of the vent connector and chimney flue shallbe not less than the area of the appliance flue collaror draft hood outlet or exceeding seven (7) times thedraft hood outlet area. [NFPA 54:12.6.3.1(2)]
(3) For sizing a chimney venting system connected totwo (2) appliances with draft hoods, the effective areaof the chimney flue shall be not less than the area ofthe larger draft hood outlet plus 50 percent of the areaof the smaller draft hood outlet, or exceeding seven(7) times the smallest draft hood outlet area. [NFPA54:12.6.3.1(3)]
(4) Other approved engineering methods. [NFPA54:12.6.3.1(5)]
(5) Chimney venting systems using mechanical draftshall be sized in accordance with approved engi-neering methods. [NFPA 54:12.6.3.1(4)]
510.5.4 Inspection of Chimneys.
(A) Before replacing an existing appliance or connectinga vent connector to a chimney, the chimney pas-sageway shall be examined to ascertain that it isclear and free of obstructions and shall be cleaned ifpreviously used for venting solid- or liquid-fuel-burning appliances or fireplaces. [NFPA 54:12.6.4.1]
(B) Chimneys shall be lined in accordance with NFPA 211,Standard for Chimneys, Fireplaces, Vents, and Solid-Fuel Burning Appliances. [NFPA 54-09:12.6.4.2]
Exception: Existing chimneys shall be permitted tohave their use continued where an appliance is re-placed by an appliance of similar type, input rating,and efficiency, where the chimney complies with510.5.4, and the sizing of the chimney is in accor-dance with 510.5.3.
812010 CALIFORNIA PLUMBING CODE
WATER HEATERS
FIGURE 5-1 TYPICAL TERMINATION LOCATIONS FOR
CHIMNEYS AND SINGLE-WALL METAL PIPES SERVING
RESIDENTIAL-TYPE AND LOW-HEAT APPLIANCE
[NFPA 54: FIGURE 12.6.2.1]
(C) Cleanouts shall be examined to determine that theywill remain tightly closed when not in use. [NFPA54:12.6.4.3]
(D) When inspection reveals that an existing chimney isnot safe for the intended application, it shall be re-paired, rebuilt, lined, relined, or replaced with a ventor chimney to conform to NFPA 211, Standard forChimneys, Fireplaces, Vents, and Solid-Fuel-Burn-ing Appliances, and shall be suitable for the appli-ances to be attached. [NFPA 54:12.6.4.4]
510.5.5 Chimney Serving Appliances Burning Other
Fuels.
510.5.5.1 Gas utilization appliances shall not be con-nected to a chimney flue serving a separate appliancedesigned to burn solid fuel. [NFPA 54:12.6.5.1]
510.5.5.2 Where one (1) chimney serves gas uti-lization appliances and liquid fuel-burning appli-ances, the appliance shall be connected throughseparate openings or shall be connected through asingle opening where joined by a suitable fitting lo-cated as close as practical to the chimney. Wheretwo (2) or more openings are provided into one (1)chimney flue, they shall be at different levels. Wherethe gas utilization appliance is automatically con-trolled, it shall be equipped with a safety shutoff de-vice. [NFPA 54:12.6.5.2]
82 2010 CALIFORNIA PLUMBING CODE
WATER HEATERS
ROOF PITCH HEIGHTS
ROOF PITCH H(minimum) ft. m
Flat to 6⁄12 1.0 0.30
Over 6⁄12 to 7⁄12 1.25 0.38
Over 7⁄12 to 8⁄12 1.5 0.46
Over 8⁄12 to 9⁄12 2.0 0.61
Over 9⁄12 to 10⁄12 2.5 0.76
Over 10⁄12 to 11⁄12 3.25 0.99
Over 11⁄12 to 12⁄12 4.0 1.22
Over 12⁄12 to 14⁄12 5.0 1.52
Over 14⁄12 to 16⁄12 6.0 1.83
Over 16⁄12 to 18⁄12 7.0 2.13
Over 18⁄12 to 20⁄12 7.5 2.27
Over 20⁄12 to 21⁄12 8.0 2.44
FIGURE 5-2 GAS VENT TERMINATION LOCATIONS FOR
LISTED CAPS 12 INCH (300 MM) OR LESS IN SIZE NOT LESS
THAN 8 FEET (2.4 m) FROM A VERTICAL WALL
[NFPA 54: FIGURE 12.7.2 AND TABLE 12.7.2]
APPLIANCES TYPE OF VENTING SYSTEM
Listed Category I appliances Type B gas vent (510.6)
Listed appliances equipped withdraft hood
Chimney (510.5)
Appliances listed for Type B gasvent
Single-wall metal pipe (510.7)Listed chimney lining systemfor gas venting (510.5.1.3)Special gas vent listed for thisappliance (510.4.4)
Listed vented wall furnaces Type B-W gas vent (510.6,510.6.2.2)
Category II appliances
Category III appliances
Category IV appliances
As specified or furnished bymanufacturers of listed appli-ance (510.4.2, 510.4.4)
Incinerators, outdoors Single-wall metal pipe (510.7,510.7.3)
Incinerators, indoors
Appliances that can be convertedto use of solid fuel
Unlisted combination gas- andoil-burning appliances
Combination gas- and solid-fuel-burning appliances
Appliances listed for use withchimneys only
Unlisted appliances
Chimney (510.5)
Listed combination gas- andoil-burning appliances
Type L vent (510.6) or chimney(510.5)
Decorative appliance in ventedfireplace
Chimney [UMC 907.2(3)]
Gas-fired toilets Single-wall metal pipe (510.7,NFPA 54:10.25.3)
Direct-vent appliances See 510.2.5
Appliances with integral vent See 510.2.6
TABLE 5-2
TYPE OF VENTING SYSTEM TO BE USED
[NFPA 54: Table 12.5.1]
FIGURE 5-3 PLAN VIEW OF PRACTICAL SEPARATION
METHOD FOR MULTISTORY GAS VENTING.
[NFPA 54: FIGURE 12.7.4.2]
510.5.5.3 A listed combination gas- and solid-fuel-burning appliance connected to a single chimneyflue shall be equipped with a manual reset device toshut off gas to the main burner in the event of sus-tained backdraft or flue gas spillage. The chimneyflue shall be sized to properly vent the appliance.[NFPA 54:12.6.5.3]510.5.5.4Asingle chimney flue serving a listed com-bination gas- and oil-burning appliance shall be sizedto properly vent the appliance. [NFPA54:12.6.5.4]
510.5.6 Support of Chimneys. Portions of chimneysshall be supported for the design and weight of the ma-terials employed. Listed factory-built chimneys shall besupported and spaced in accordance with their listingsand the manufacturer’s instructions. [NFPA 54:12.6.6]510.5.7 Cleanouts.Where a chimney that formerly car-ried flue products from liquid- or solid-fuel-burning ap-pliances is used with an appliance using fuel gas, anaccessible cleanout shall be provided. The cleanout shallhave a tight-fitting cover and be installed so its upper edgeis at least six (6) inches (150 mm) below the lower edgeof the lowest chimney inlet opening. [NFPA 54:12.6.7]510.5.8 Space Surrounding Lining or Vent.
510.5.8.1 The remaining space surrounding a chim-ney liner, gas vent, special gas vent, or plastic pipinginstalled within a masonry chimney flue shall not beused to vent another appliance. [NFPA 54:12.6.8.1]Exception: The insertion of another liner or ventwithin the chimney as provided in this code and theliner or vent manufacturer's instructions.510.5.8.2 The remaining space surrounding a chim-ney liner, gas vent, special gas vent, or plastic pipinginstalled within a masonry chimney flue shall not beused to supply combustion air. [NFPA 54:12.6.8.2]Exception: Direct-vent gas-fired appliances de-signed for installation in a solid-fuel-burning fire-place where installed in accordance with the listingand the manufacturer’s instruction.
510.6 Gas Vents.510.6.1 A gas vent passing through a roof shall extendthrough the entire roof flashing, roof jack, or roof thim-ble and be terminated with a listed termination cap.[NFPA 54:12.7.2(6)]
510.6.1.1 Type B or Type L vents shall extend in agenerally vertical direction with offsets not exceed-ing 45 degrees, except that a vent system having notmore than one 60 degree offset shall be permitted.Any angle greater than 45 degrees from the verticalis considered horizontal. The total horizontal dis-tance of a vent plus the horizontal vent connectorserving draft-hood-equipped appliances shall not ex-ceed 75 percent of the vertical height of the vent.[NFPA 54:12.7.3.2]
Exception: Systems designed and sized as providedin this chapter or in accordance with other approvedengineering methods.510.6.1.2 Screws, rivets and other fasteners shall notpenetrate the inner wall of double wall gas vents.
510.6.2 A gas vent shall terminate in accordance withone of the following [NFPA 54:12.7.2(1)]:(1) Above the roof surface with a listed cap or listed
roof assembly. Gas vents twelve (12) inches (300mm) in size or smaller with listed caps shall be per-mitted to be terminated in accordance with Figure5-2, provided they are at least eight (8) feet (2.4 m)from a vertical wall or similar obstruction. Other gasvents shall terminate not less than two (2) feet (0.6m) above the highest point where they pass throughthe roof and at least two (2) feet (0.6 m) exceedingany portion of a building within ten (10) feet (3.1m). [NFPA 54:12.7.2(1)(a) and (b)]
(2) Industrial gas utilization appliances as provided inSection 510.2.4. [NFPA 54:12.7.2(1)(c)]
(3) Direct-vent systems as provided in Section 510.2.5.[NFPA 54:12.7.2(1)(d)]
(4) Appliances with integral vents as provided in Sec-tion 510.2.6. [NFPA 54:12.7.2(1)(e)]
(5) Mechanical draft systems as provided in Section510.3.4. [NFPA 54:12.7.2(1)(f)]
(6) Ventilating hoods and exhaust systems as providedin Section 510.3.5. [NFPA 54: 12.7.2(1)(g)]510.6.2.1 A Type B or a Type L gas vent shall ter-minate at least five (5) feet (1.5 m) in vertical heightabove the highest connected appliance draft hood orflue collar. [NFPA 54:12.7.2(2)]510.6.2.2 A Type B-W gas vent shall terminate atleast twelve (12) feet (3.7 m) in vertical height abovethe bottom of the wall furnace. [NFPA54:12.7.2(3)]510.6.2.3 A gas vent extending through an exteriorwall shall not terminate adjacent to the wall or beloweaves or parapets, except as provided in Sections510.2.5 and 510.3.4. [NFPA 54:12.7.2(4)]510.6.2.4 Decorative shrouds shall not be installed atthe termination of gas vents except where suchshrouds are listed for use with the specific gas ventingsystem and are installed in accordance with manufac-turer’s installation instructions. [NFPA54:12.7.2(5)]510.6.2.5 Gas vents shall extend through the roofflashing, roof jack, or roof thimble and terminatewith a listed cap or listed roof assembly. [NFPA54:12.7.2(6)]510.6.2.6Agas vent shall terminate at least three (3)feet (0.9 m) above a forced air inlet located withinten (10) feet (3.0 m). [NFPA 54:12.7.2(7)]
510.6.3 Size of Gas Vents. Venting systems shall besized and constructed in accordance with NFPA 54, Na-tional Fuel Gas Code, Chapter 13 or other approved en-gineering methods and the gas vent and gas appliancemanufacturer’s instructions. [NFPA 54:12.7.3]
832010 CALIFORNIA PLUMBING CODE
WATER HEATERS
510.6.3.1 Category I Appliances. The sizing of nat-ural draft venting systems serving one (1) or morelisted appliances equipped with a draft hood or appli-ances listed for use with Type B gas vent, installed ina single story of a building, shall be in accordancewithone of the following methods [NFPA54:12.7.3.1]:(1) The provisions of this chapter. [NFPA
54:12.7.3.1(1)](2) Vents serving fan-assisted combustion system
appliances, or combinations of fan-assistedcombustion systems and draft hood-equippedappliances, shall be sized in accordance withthis chapter or other approved engineeringmethods. [NFPA 54:12.7.3.1(2)]
(3) For sizing an individual gas vent for a single,draft-hood-equipped appliance, the effectivearea of the vent connector and the gas vent shallbe at least the area of the appliance draft hoodoutlet or exceeding seven (7) times the drafthood outlet area. [NFPA 54:12.7.3.1(3)]
(4) For sizing a gas vent connected to two (2) ap-pliances with draft hoods, the effective area ofthe vent shall be at least the area of the largerdraft hood outlet plus 50 percent of the area ofthe smaller draft hood outlet or exceeding seven(7) times the smaller draft hood outlet area.[NFPA 54:12.7.3.1(4)]
(5) Approved engineering practices. [NFPA54:12.7.3.1(5)]
510.6.3.2 Category II, Category III, and CategoryIVAppliances. The sizing of gas vents for CategoryII, Category III, and Category IV gas utilization ap-pliances shall be in accordance with the equipmentmanufacturer's instructions. [NFPA 54:12.7.3.3]510.6.3.3 Sizing. Chimney venting systems usingmechanical draft shall be sized in accordance withapproved engineering methods. [NFPA54:12.7.3.4]
510.6.4 Gas Vents Serving Appliances on More ThanOne Floor.
510.6.4.1 A common gas vent shall be permitted inmultistory installations to vent Category I gas uti-lization appliances located on more than one (1)floor level, provided the venting system is designedand installed in accordance with approved engi-neering methods.
For the purpose of this section, crawl spaces,basements, and attics shall be considered as floorlevels. [NFPA 54:12.7.4.1]510.6.4.2Gas utilization appliances connected to thecommon vent shall be located in rooms separatedfrom a habitable space. Each of these rooms shallhave provisions for an adequate supply of combus-tion, ventilation, and dilution air that is not suppliedfrom a habitable space (See Figure 5-3). [NFPA54:12.7.4.2]
The size of the connectors and common seg-ments of multistory venting systems for gas utiliza-tion appliances listed for use with Type B double-wallgas vent shall be in accordance with Table 5-14, pro-vided [NFPA 54:12.7.4.3]:(1) The available total height (H) for each segment
of a multistory venting system is the verticaldistance between the level of the highest drafthood outlet or flue collar on that floor and thecenterline of the next highest interconnectiontee (See Figure G.1(K)). [NFPA54:12.7.4.3(1)]
(2) The size of the connector for a segment is de-termined from its gas utilization appliance heatinput and available connector rise, and shall notbe smaller than the draft hood outlet or flue col-lar size. [NFPA 54:12.7.4.3(2)]
(3) The size of the common vertical vent segment,and of the interconnection tee at the base of thatsegment, shall be based on the total gas uti-lization appliance heat input entering that seg-ment and its available total height. [NFPA54:12.7.4.3(3)]
510.6.5 Support of Gas Vents. Gas vents shall be sup-ported and spaced in accordance with their listings andthe manufacturer’s instructions. [NFPA 54:12.7.5]510.6.6 Marking. In those localities where solid and liq-uid fuels are used extensively, gas vents shall be perma-nently identified by a label attached to the wall or ceilingat a point where the vent connector enters the gas vent.The label shall read: "This gas vent is for appliances thatburn gas. Do not connect to solid- or liquid-fuel-burningappliances or incinerators." The Authority Having Juris-diction shall determine whether its area constitutes sucha locality. [NFPA 54:12.7.6]
510.7 Single-Wall Metal Pipe.510.7.1 Construction. Single-wall metal pipe shall beconstructed of galvanized sheet steel not less than 0.0304inch (0.7 mm) thick or of other approved, noncom-bustible, corrosion-resistant material. [NFPA 54:12.8.1]510.7.2 Cold Climate. Uninsulated single-wall metalpipe shall not be used outdoors in cold climates for vent-ing gas utilization appliances. For venting appliances inregions where the 99 percent winter design temperatureis below 32°F (0°C). [NFPA 54:12.8.2]510.7.3 Termination. The termination of single-wallmetal pipe shall comply with the following requirements[NFPA 54:12.8.3]:
510.7.3.1 Single-wall metal pipe shall terminate atleast five (5) feet (1.5 m) in vertical height above thehighest connected appliance draft hood outlet or fluecollar. [NFPA 54:12.8.3(1)]510.7.3.2 Single-wall metal pipe shall extend at leasttwo (2) feet (0.6 m) above the highest point where itpasses through the roof of a building and at least (2)feet (0.6 m) exceeding any portion of a buildingwithin a horizontal distance of ten (10) feet (3.1 m)(See Figure 5-1). [NFPA 54:12.8.3(2)]
84 2010 CALIFORNIA PLUMBING CODE
WATER HEATERS
510.7.3.3 An approved cap or roof assembly shall beattached to the terminus of a single-wall metal pipe.[Also see Section 510.7.4.4.] [NFPA 54:12.8.3(3)]
510.7.4 Installation with Appliances Permitted by
510.4.1.
510.7.4.1 Prohibited Use. Single-wall metal pipe
shall not be used as a vent in dwellings and resi-
dential occupancies. [NFPA 54-09:12.8.4.1]
510.7.4.2 Single-wall metal pipe shall be used only
for runs directly from the space in which the gas uti-
lization appliance is located through the roof or ex-
terior wall to the outer air. A pipe passing through a
roof shall extend without interruption through the
roof flashing, roof jacket, or roof thimble. [NFPA
54:12.8.4.1]
510.7.4.3 Single-wall metal pipe shall not originate
in any unoccupied attic or concealed space and shall
not pass through any attic, inside wall, concealed
space, or floor. For the installation of a single-wall
metal pipe through an exterior combustible wall, see
Section 510.7.4.6. [NFPA 54:12.8.4.2]
510.7.4.4 Single-wall metal pipe used for venting an
incinerator shall be exposed and readily examinable
for its full length and shall have suitable clearances
maintained. [NFPA 54:12.8.4.3]
510.7.4.5 Minimum clearances from single-wall
metal pipe to combustible material shall be in ac-
cordance with Table 5-3. Reduced clearances from
single-wall metal pipe to combustible material shall
be as specified for vent connectors in Table 5-4.
[NFPA 54:12.8.4.4]
510.7.4.6 Single-wall metal pipe shall not pass
through a combustible exterior wall unless guarded at
the point of passage by a ventilated metal thimble not
smaller than the following [NFPA 54:12.11.14.2]:
(1) For listed appliances equipped with draft hoodsand appliances listed for use with Type B gasvents, the thimble shall be at a minimum four
(4) inches (100 mm) larger in diameter than themetal pipe. Where there is a run of at least six(6) feet (1.8 m) of metal pipe in the opening be-tween the draft hood outlet and the thimble, thethimble shall be a minimum two (2) inches (50mm) larger in diameter than the metal pipe.
(2) For unlisted appliances having draft hoods, the
thimble shall be a minimum six (6) inches (150
mm) larger in diameter than the metal pipe.
(3) For residential and low-heat appliances, the
thimble shall be a minimum twelve (12) inches
(300 mm) larger in diameter than the metal
pipe.
Exception: In lieu of thimble protection, com-
bustible material in the wall shall be removed a
sufficient distance from the metal pipe to provide
the specified clearance from such metal pipe to
combustible material. Any material used to close
up such opening shall be noncombustible.
510.7.4.7 Where a single-wall metal pipe passes
through a roof constructed of combustible material,
a noncombustible, nonventilating thimble shall be
used at the point of passage. The thimble shall ex-
tend not less than eighteen (18) inches (460 mm)
above and six (6) inches (150 mm) below the roof
with the annular space open at the bottom and closed
only at the top. The thimble shall be sized in accor-
dance with Section 510.7.4.6. [NFPA 54:12.8.4.5]
510.7.5 Size of Single-Wall Metal Pipe. Single-wall
metal piping shall comply with the following require-
ments [NFPA 54:12.8.5]:
510.7.5.1 A venting system of a single-wall metal
pipe shall be sized in accordance with one of the fol-
lowing methods and the gas appliance manufac-
turer's instructions [NFPA 54:12.8.5(1)]:
(1) For a draft-hood-equipped appliance, in accor-
dance with this chapter. [NFPA 54:12.8.5(1)(a)]
852010 CALIFORNIA PLUMBING CODE
WATER HEATERS
TABLE 5-3
CLEARANCE FOR CONNECTORS [NFPA 54: TABLE 12.8.4.4]
For SI units, 1 in.= 25.4 mm.
Note: These clearances shall apply unless the listing of an appliance or connector specifies clearances, in which case the listed clearances shall apply.
MINIMUM DISTANCE FROM COMBUSTIBLE MATERIAL
APPLIANCE LISTED TYPE B GAS
VENT MATERIAL
LISTED TYPE L VENT
MATERIAL
SINGLE-WALL
METAL PIPE
FACTORY-BUILT
CHIMNEY SECTIONS
Listed appliances with draft hoods and appliances listed
for use with Type B gas vents
As listed As listed 6 in. As listed
Residential boilers and furnaces with listed gas conver-
sion burner and with draft hood
6 in. 6 in. 9 in. As listed
Residential appliances listed for use with Type L vents Not permitted As listed 9 in. As listed
Listed gas-fired toilets Not permitted As listed As listed As listed
Unlisted residential appliances with draft hood Not permitted 6 in. 9 in. As listed
Residential and low-heat appliances other than those
above
Not permitted 9 in. 18 in. As listed
Medium-heat appliances Not permitted Not permitted 36 in. As listed
86 2010 CALIFORNIA PLUMBING CODE
WATER HEATERS
WHERE THE REQUIRED CLEARANCE WITH NO PROTECTION FROM APPLIANCE, VENT CONNECTOR, OR SINGLE-WALL METAL PIPE IS:
36 in. 18 in. 12 in. 9 in. 6 in.
ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (in.)
TYPE OF PROTECTION APPLIED
TO AND COVERING SURFACES
OF COMBUSTIBLE MATERIAL
WITHIN THE DISTANCE SPECI-
FIED AS THE REQUIRED CLEAR-
ANCE WITH NO PROTECTION
[SEE FIGURES 5-4 THROUGH 5-6]
USE COLUMN 1 FOR CLEARANCE ABOVE APPLIANCE OR HORIZONTAL CONNECTOR.
COLUMN 2 FOR CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE
ABOVE
COLUMN 1
SIDES AND
REAR
COLUMN 2
ABOVE
COLUMN 1
SIDES AND
REAR
COLUMN 2
ABOVE
COLUMN 1
SIDES AND
REAR
COLUMN 2
ABOVE
COLUMN 1
SIDES AND
REAR
COLUMN 2
ABOVE
COLUMN 1
SIDES AND
REAR
COLUMN 2
(1) 31⁄2 in. thick masonry
wall without ventilated
air space
-- 24 -- 12 -- 9 -- 6 -- 5
(2) 1⁄2 in. insulation boardover 1 in. glass fiber ormineral wool batts
24 18 12 9 9 6 6 5 4 3
(3) 0.024 sheet metal over 1in. glass fiber or mineralwool batts reinforced withwire on rear face withventilated air space
18 12 9 6 6 4 5 3 3 3
(4) 31⁄2 in. thick masonry wallwith ventilated air space
-- 12 -- 6 -- 6 -- 6 -- 6
(5) 0.024 sheet metal withventilated air space
18 12 9 6 6 4 5 3 3 2
(6) 1⁄2 in. thick insulationboard with ventilated airspace
18 12 9 6 6 4 5 3 3 3
(7) 0.024 sheet metal withventilated air space over0.024 sheet metal withventilated air space
18 12 9 6 6 4 5 3 3 3
(8) 1 in. glass fiber or mineralwool batts sandwichedbetween two sheets 0.024sheet metal with venti-lated air space
18 12 9 6 6 4 5 3 3 3
TABLE 5-4
REDUCTION OF CLEARANCES WITH SPECIFIED FORMS OF PROTECTION [NFPA 54: TABLE 10.2.3(b)]
For SI units, 1 in. = 25.4 mm.Notes:1 Reduction of clearances from combustible materials shall not interfere with combustion air, draft hood clearance and relief, and accessibility of servicing.2 Clearances shall be measured from the outer surface of the combustible material to the nearest point on the surface of the appliance, disregarding any in-
tervening protection applied to the combustible material.3 Spacers and ties shall be of noncombustible material. No spacer or tie shall be used directly opposite the appliance or connector.4 Where clearance reduction systems use a ventilated air space, adequate provision for air circulation shall be provided as described. [See Figure 5-5 and
Figure 5-6.]5 There shall be at least one (1) in. (25 mm) between clearance reduction systems and combustible walls and ceilings for reduction systems using a venti-
lated air space.6 Where a wall protector is mounted on a single flat wall away from corners, it shall have a minimum one (1) inch (25 mm) air gap. To provide adequate air
circulation, the bottom and top edges, or only the side and top edges, or edges shall be left open.7 Mineral wool batts (blanket or board) shall have a minimum density of eight (8) lb/ft.3 (128 kg/m3) and a minimum melting point of 1500°F (816°C).8 Insulation material used as part of a clearance reduction system shall have a thermal conductivity of 1.0 Btu in./ft2/h-°F (0.144 W/m-K) or less.9 There shall be at least (1) inch (25 mm) between the appliance and the protector. In no case shall the clearance between the appliance and the combustible
surface be reduced below that allowed in this table.10 Clearances and thicknesses are minimum; larger clearances and thicknesses are acceptable.11 Listed single-wall connectors shall be installed in accordance with the terms of their listing and the manufacturer’s instructions.
(2) For a venting system for a single appliance witha draft hood, the areas of the connector and thepipe each shall be at least the area of the appli-ance flue collar or draft hood outlet, whicheveris smaller. The vent area shall not exceed seven(7) times the draft hood outlet area. [NFPA54:12.8.5(1)(b)]
(3) Other approved engineering methods. [NFPA54:12.8.5(1)(c)]
510.7.5.2Where a single-wall metal pipe is used andhas a shape other than round, it shall have an equiv-alent effective area equal to the effective area of theround pipe for which it is substituted, and the inter-nal dimension of the pipe shall be at least two (2)inches (50 mm). [NFPA 54:12.8.5(2)]510.7.5.3 The vent cap or a roof assembly shall havea venting capacity at least that of the pipe to whichit is attached. [NFPA 54:12.8.5(3)]
510.7.6 Support of Single-Wall Metal Pipe. Portionsof single-wall metal pipe shall be supported for the de-sign and weight of the material employed. [NFPA54:12.8.6]510.7.7 Marking. Single-wall metal pipe shall complywith the marking provisions of Section 510.6.6. [NFPA54:12.8.7]
510.8 Through-the-Wall Vent Termination (See Fig-ure 5-12).
510.8.1Amechanical draft venting system shall terminateat least three (3) feet (0.9 m) above any forced air inlet lo-cated within ten (10) feet (3.1 m). [NFPA 54:12.9.1]Exceptions:(1) This provision shall not apply to the combustion air
intake of a direct-vent appliance.
872010 CALIFORNIA PLUMBING CODE
WATER HEATERS
Notes:
A – Equals the clearance with no protection specified in Tables 5-3 and 5-4and in the sections applying to various types of appliances.
B – Equals the reduced clearance permitted in accordance with Table 5-3.The protection applied to the construction using combustible material shallextend far enough in each direction to make C equal to A.
FIGURE 5-4 EXTENT OF PROTECTION NECESSARYTOREDUCE CLEARANCES FROM GAS APPLIANCES ORVENT
CONNECTORS [NFPA 54: FIGURE 10.3.2.2(1)]
Masonry walls can be attached to combustible walls using wall ties. Spac-ers should not be used directly behind appliance or connector.
FIGURE 5-5WALL PROTECTION REDUCTION SYSTEM.
[NFPA 54:FIGURE 10.3.2.2(2)]
FIGURE 5-6 MASONRY CLEARANCE REDUCTION SYSTEM.[NFPA 54: FIGURE 10.3.2.2(3)]
(2) This provision shall not apply to the separation ofthe integral outdoor air inlet and flue gas dischargeof listed outdoor appliances.
510.8.2Amechanical draft venting system of other thandirect-vent type shall terminate at least four (4) feet (1.2m) below, four (4) feet (1.2 m) horizontally from, or one(1) foot (300 mm) above any door, operable window, orgravity air inlet into any building. The bottom of the ventterminal shall be located at least twelve (12) inches (300mm) above finished grade. [NFPA 54:12.9.2]510.8.3The vent terminal of a direct-vent appliancewith aninput of 10,000 Btu/h (3 kW) or less shall be located at least(6) inches (150 mm) from any air opening into a building,and such an appliance with an input over 10,000 Btu/h (3kW) but not over 50,000 Btu/h (14.7 kW) shall be installedwith a nine (9) inch (230 mm) vent termination clearance,and an appliance with an input over 50,000 Btu/h (14.7kW) shall have at least a twelve (12) inch (300 mm) venttermination clearance. The bottom of the vent terminal andthe air intake shall be located at least twelve (12) inches(300 mm) above finished grade. [NFPA54:12.9.3]510.8.4 Through-the-wall vents for Category II and Cat-egory IV appliances and noncategorized condensing ap-pliances shall not terminate over public walkways orover an area where condensate or vapor could create anuisance or hazard or could be detrimental to the opera-tion of regulators, relief valves, or other equipment.Where local experience indicates that condensate is aproblem with Category I and Category III appliances,this provision shall also apply.
Drains for condensate shall be installed in accor-dance with the manufacturer’s installation instructions.[NFPA 54-09:12.9.4]510.8.5Where vents, including those for direct-vent ap-pliances or combustion air intake pipes, penetrate outsidewalls of buildings, the annular spaces around such pene-trations shall be permanently sealed using approved ma-terials to prevent entry of combustion products into thebuilding. [NFPA 54-09:12.9.5]
510.9 Condensation Drain.510.9.1 Provision shall be made to collect and disposeof condensate from venting systems serving Category IIand Category IV gas utilization appliances and noncate-gorized condensing appliances in accordance with Sec-tion 510.8.4. [NFPA 54:12.10.1]510.9.2Where local experience indicates that condensa-tion is a problem, provision shall be made to drain offand dispose of condensate from venting systems servingCategory I and Category III gas utilization appliances inaccordance with Section 510.8.4. [NFPA 54:12.10.2]
510.10 Vent Connectors for Category I Gas UtilizationAp-pliances.
510.10.1Where Required.Avent connector shall be usedto connect gas utilization appliances to a gas vent, chim-ney, or single-wall metal pipe, except where the gas vent,chimney, or single-wall metal pipe is directly connectedto the appliance. [NFPA 54:12.11.1]
510.10.2 Materials.510.10.2.1 A vent connector shall be made of non-combustible, corrosion resistant material capable ofwithstanding the vent gas temperature produced by thegas utilization appliance and of sufficient thickness towithstand physical damage. [NFPA54:12.11.2.1]510.10.2.2 Where the vent connector used for gasutilization appliances having a draft hood or a Cat-egory I appliance is located in or passes through anunconditioned area, that portion of the vent connec-tor shall be listed Type B, Type L, or listed vent ma-terial having equivalent insulation qualities. [NFPA54:12.11.2.2]Exception: Single-wall metal pipe located withinthe exterior walls of the building and located in areashaving a local 99 percent winter design temperatureof 5°F (-15°C) or higher.510.10.2.3 Where the vent connector used for gasutilization appliances having a draft hood or a Cat-egory I appliance is located in or passes through at-tics and crawl spaces, that portion of the ventconnector shall be listed Type B, Type L, or listedvent material having equivalent insulation qualities.[NFPA 54:12.11.2.3]510.10.2.4 Vent connectors for residential-type ap-pliances shall comply with the following [NFPA54:12.11.2.4]:(1) Vent connectors for listed gas appliances hav-
ing draft hoods and for appliances having drafthoods and equipped with listed conversionburners that are not installed in attics, crawlspaces, or other unconditioned areas shall beone of the following [NFPA 54:12.11.2.4(1)]:(a) Type B or Type L vent material.(b) Galvanized sheet steel at least 0.018 inches
(0.46 mm) thick.(c) Aluminum (1100 or 3003 alloy or equiva-
lent) sheet at least 0.027 inches (0.69 mm)thick.
(d) Stainless steel sheet at least 0.012 inches(0.31 mm) thick.
(e) Smooth interior wall metal pipe having re-sistance to heat and corrosion equal to orexceeding that of b, c, or d above.
(f) A listed vent connector.(2) Vent connectors shall not be covered with insu-
lation.Exception: Listed insulated vent connectorsshall be installed in accordance with the manu-facturer’s installation instructions. [NFPA54:12.11.2.4(2)]
510.10.2.5Avent connector for non-residential low-heat appliance shall be a factory-built chimney sec-tion or steel pipe having resistance to heat andcorrosion equivalent to that for the appropriate gal-vanized pipe as specified in Table 5-5. Factory-built
88 2010 CALIFORNIA PLUMBING CODE
WATER HEATERS
chimney sections shall be joined together in accor-dance with the chimney manufacturer's instructions.[NFPA 54:12.11.2.5]
510.10.2.6 Vent connectors for medium-heat appli-ances and commercial and industrial incineratorsshall be constructed of factory-built, medium-heatchimney sections or steel of a thickness at least thatspecified in Table 5-6 and shall comply with the fol-lowing [NFPA 54:12.11.2.6]:(1) A steel vent connector for appliances with a
vent gas temperature exceeding 1,000°F(538°C) measured at the entrance to the con-nector shall be lined with medium-duty firebrick (ASTM C 64, Specification for Refracto-ries for Incinerators and Boilers, Type F) or theequivalent.
(2) The lining shall be at least two and one-half(21⁄2) inches (64 mm) thick for a vent connectorhaving a diameter or greatest cross-sectional di-mension of eighteen (18) inches (460 mm) orless.
(3) The lining shall be at least four and one-half(41⁄2) inches (110 mm) thick laid on the four andone-half (41⁄2) inch (110 mm) bed for a ventconnector having a diameter or cross-sectionaldimension exceeding eighteen (18) inches (460mm).
(4) Factory-built chimney sections, if employed,shall be joined together in accordance with thechimney manufacturer's instructions.
510.10.3 Size of Vent Connector.510.10.3.1 A vent connector for gas utilization ap-pliances with a single draft hood or for a Category Ifan-assisted combustion system appliance shall besized and installed in accordance with this chapteror other approved engineering methods. [NFPA54:12.11.3.1]510.10.3.2 For a single appliance having more thanone (1) draft hood outlet or flue collar, the manifoldshall be constructed according to the instructions ofthe appliance manufacturer. Where there are no in-structions, the manifold shall be designed and con-structed in accordance with approved engineeringpractices. As an alternate method, the effective areaof the manifold shall equal the combined area of theflue collars or draft hood outlets, and the vent con-nectors shall have a minimum one (1) foot (0.3 m)rise. [NFPA 54:12.11.3.2]510.10.3.3 Where two (2) or more gas appliancesare connected to a common vent or chimney, eachvent connector shall be sized in accordance with thischapter or other approved engineering methods.[NFPA 54:12.11.3.3] As an alternative method ap-plicable only when the appliances are draft-hood-equipped, each vent connector shall have aneffective area at least the area of the draft hood out-let of the appliance to which it is connected. [NFPA54:12.11.3.4]510.10.3.4 Where two (2) or more gas appliancesare vented through a common vent connector or ventmanifold, the common vent connector or vent man-ifold shall be located at the highest level consistentwith available head-room and clearance to com-bustible material and shall be sized in accordancewith this chapter or other approved engineeringmethods. [NFPA 54:12.11.3.5]
As an alternate method applicable only wherethere are two (2) draft-hood-equipped appliances,the effective area of the common vent connector orvent manifold and junction fittings shall be at leastthe area of the larger vent connector plus 50 percentof the areas of smaller flue collar outlets. [NFPA54:12.11.3.6]510.10.3.5Where the size of a vent connector is in-creased to overcome installation limitations and ob-tain connector capacity equal to the appliance input,the size increase shall be made at the appliance drafthood outlet. [NFPA 54:12.11.3.7]
510.10.4 Two orMoreAppliances Connected to a Sin-gle Vent.
510.10.4.1Where two (2) or more openings are pro-vided into one (1) chimney flue or vent, the openingsshall either be at different levels, or the connectorsshall be attached to the vertical portion of the chim-ney or vent at an angle of 45 degrees or less relativeto the vertical. [NFPA 54-09:12.11.4.1]
892010 CALIFORNIA PLUMBING CODE
WATER HEATERS
TABLE 5-6MINIMUMTHICKNESS FOR STEEL VENT CONNECTORS FOR
MEDIUM-HEAT APPLIANCES AND COMMERCIAL ANDINDUSTRIAL INCINERATORS[NFPA 54:TABLE 12.11.2.6]
For SI units, 1 in. = 25.4 mm; 1 in.2 = 645 mm2.
DIAMETER OF CONNECTOR(in.)
MINIMUMTHICKNESS(in.)*
Less than 6 0.0196 to less than 10 0.02310 to 12 inclusive 0.02914 to 16 inclusive 0.034
Over 16 0.056
TABLE 5-5MINIMUMTHICKNESS FOR GALVANIZED STEEL VENT
CONNECTOR FOR LOW-HEAT APPLIANCES[NFPA 54:TABLE 12.11.2.5]
* For SI units, 1 in. = 25.4 mm; 1 in.2 = 645 mm2.
VENT CONNECTOR SIZE
DIAMETER (in.) AREA (in.2)MINIMUM
THICKNESS (in.)
Up to 14 Up to 154 0.053Over 14 to 16 154 to 201 0.067Over 16 to 18 201 to 254 0.093Over 18 Exceeding 254 0.123
510.10.4.2 Where two (2) or more vent connectorsenter a common gas vent, chimney flue, or single-wall metal pipe, the smaller connector shall enter atthe highest level consistent with the available head-room or clearance to combustible material. [NFPA54:12.11.4.1]510.10.4.3Vent connectors serving Category I appli-ances shall not be connected to any portion of a me-chanical draft system operating under positive staticpressure, such as those serving Category III or Cate-gory IV appliances. [NFPA 54:12.11.4.2]
510.10.5 Clearance.Minimum clearances from vent con-nectors to combustible material shall be in accordancewith Table 5-3. [NFPA 54:12.11.5]Exception: The clearance between a vent connector andcombustible material shall be permitted to be reducedwhere the combustible material is protected as specifiedfor vent connectors in Table 5-4.510.10.6 Avoid Unnecessary Bends. A vent connectorshall be installed so as to avoid turns or other constructionfeatures that create excessive resistance to flow of ventgases. [NFPA 54:12.11.6]510.10.7 Joints. Joints between sections of connector pip-ing and connections to flue collars or draft hood outletsshall be fastened in accordance with one of the followingmethods [NFPA 54:12.11.7]:(1) By sheet metal screws.(2) Vent connectors of listed vent material shall be as-
sembled and connected to flue collars or draft hoodoutlets in accordance with themanufacturer’s instruc-tions.
(3) Other approved means.510.10.8 Slope. A vent connector shall be installed with-out any dips or sags and shall slope upward toward thevent or chimney not less than one-quarter (1⁄4) inch/foot(20 mm/m). [NFPA 54:12.11.8]Exception:Vent connectors attached to a mechanical draftsystem installed in accordance with the appliance and draftsystem manufacturer’s instructions.510.10.9 Length of Vent Connector.
510.10.9.1 A vent connector shall be as short aspractical and the gas utilization appliance locatedas close as practical to the chimney or vent. [NFPA54:12.11.9.1]510.10.9.2 The maximum horizontal length of a sin-gle-wall connector shall be 75 percent of the heightof the chimney or vent except for engineered sys-tems. [NFPA 54-09:12.11.9.2]510.10.9.3 The maximum horizontal length of aType B double-wall connector shall be 100 percentof the height of the chimney or vent, except for en-gineered systems. The maximum length of an indi-vidual connector for a chimney or vent systemserving multiple appliances, from the appliance out-let to the junction with the common vent or anotherconnector, shall be 100 percent of the height of thechimney or vent. [NFPA 54:12.11.9.3]
510.10.10 Support.Avent connector shall be supportedfor the design and weight of the material employed tomaintain clearances and prevent physical damage andseparation of joints. [NFPA 54:12.11.10]510.10.11 Chimney Connection.Where entering a fluein a masonry or metal chimney, the vent connector shallbe installed above the extreme bottom to avoid stoppage.Where a thimble or slip joint is used to facilitate removalof the connector, the connector shall be firmly attachedto or inserted into the thimble or slip joint to prevent theconnector from falling out. Means shall be employed toprevent the connector from entering so far as to restrictthe space between its end and the opposite wall of thechimney flue. [NFPA 54:12.11.11]510.10.12 Inspection. The entire length of a vent con-nector shall be readily accessible for inspection, clean-ing, and replacement. [NFPA 54:12.11.12]510.10.13 Fireplaces.Avent connector shall not be con-nected to a chimney flue serving a fireplace unless thefireplace flue opening is permanently sealed. [NFPA54:12.11.13]510.10.14 Passage through Ceilings, Floors, orWalls.
510.10.14.1Avent connector shall not pass throughany ceiling, floor, or fire-resistance-rated wall.A sin-gle-wall metal pipe connector shall not pass throughany interior wall.Exception:Vent connectors made of listed Type B orType L vent material and serving listed applianceswith draft hoods and other appliances listed for usewith Type B gas vents that pass through walls or par-titions constructed of combustible material shall beinstalled with not less than the listed clearance tocombustible material.510.10.14.2 Vent connectors for medium-heat ap-pliances shall not pass through walls or partitionsconstructed of combustible material. [NFPA54:12.11.14.3]
510.11 Vent Connectors for Category II, Category III, andCategory IV Gas Utilization Appliances (See Section510.4). [NFPA 54:12.12]510.12 Draft Hoods and Draft Controls.
510.12.1 Appliances Requiring Draft Hoods. Ventedgas utilization appliances shall be installed with drafthoods. [NFPA 54:12.13.1]Exception: Dual oven-type combination ranges; incin-erators; direct-vent appliances; fan-assisted combustionsystem appliances; appliances requiring chimney draftfor operation; single firebox boilers equipped with con-version burners with inputs exceeding 400,000 Btu/h(117 kW); appliances equipped with blast, power, orpressure burners that are not listed for use with drafthoods; and appliances designed for forced venting.510.12.2 Installation. A draft hood supplied with orforming a part of listed vented gas utilization appliances
90 2010 CALIFORNIA PLUMBING CODE
WATER HEATERS
shall be installed without alteration, exactly as furnished
and specified by the appliance manufacturer. [NFPA
54:12.13.2]
If a draft hood is not supplied by the appliance man-ufacturer where one (1) is required, a draft hood shall beinstalled, be of a listed or approved type, and, in the ab-sence of other instructions, be of the same size as the ap-pliance flue collar. Where a draft hood is required with aconversion burner, it shall be of a listed or approved type.[NFPA 54: 12.13.2.1]
Where it is determined that a draft hood of specialdesign is needed or preferable for a particular installa-tion, the installation shall be in accordance with the rec-ommendations of the appliance manufacturer and shallbe approved by the Authority Having Jurisdiction.[NFPA 54:12.13.2.2]
510.12.3 Draft-Control Devices. Where a draft-controldevice is part of the gas utilization appliance or is sup-plied by the appliance manufacturer, it shall be installedin accordance with the manufacturer's instructions. In theabsence of manufacturer's instructions, the device shallbe attached to the flue collar of the appliance or as nearto the appliance as practical. [NFPA 54:12.13.3]
510.12.4 Additional Devices. Gas utilization appliances(except incinerators) requiring controlled chimney draftshall be permitted to be equipped with a listed double-acting barometric draft regulator installed and adjustedin accordance with the manufacturer’s instructions.[NFPA 54:12.13.4]
510.12.5 Location. Draft hoods and barometric draft reg-ulators shall be installed in the same room or enclosureas the appliance in such a manner as to prevent any dif-ference in pressure between the hood or regulator and thecombustion air supply. [NFPA 54:12.13.5]
510.12.6 Positioning. Draft hoods and draft regulatorsshall be installed in the position for which they were de-signed with reference to the horizontal and verticalplanes and shall be located so that the relief opening isnot obstructed by any part of the appliance or adjacentconstruction. The appliance and its draft hood shall belocated so that the relief opening is accessible for check-ing vent operation. [NFPA 54:12.13.6]
510.12.7 Clearance. A draft hood shall be located so thatits relief opening is at least six (6) inches (150 mm) fromany surface except that of the appliance it serves and theventing system to which the draft hood is connected.Where a greater or lesser clearance is indicated on theappliance label, the clearance shall not be less than thatspecified on the label. Such clearances shall not be re-duced. [NFPA 54:12.13.7]
510.13 Manually Operated Dampers. A manually operateddamper shall not be placed in any appliance vent connector.Fixed baffles shall not be classified as manually operateddampers. [NFPA 54:12.14]
510.14 Automatically Operated Vent Dampers. An auto-matically operated vent damper shall be of a listed type.[NFPA 54:12.15]
510.15 Obstructions. Devices that retard the flow of ventgases shall not be installed in a vent connector, chimney, orvent. The following shall not be considered as obstructions[NFPA 54:12.16]:
(1) Draft regulators and safety controls specifically listed forinstallation in venting systems and installed in accor-dance with the terms of their listing.
(2) Approved draft regulators and safety controls designedand installed in accordance with approved engineeringmethods.
(3) Listed heat reclaimers and automatically operated ventdampers installed in accordance with the terms of theirlisting.
(4) Vent dampers serving listed appliances installed in ac-cordance with this chapter or other approved engineeringmethods.
(5) Approved economizers, heat reclaimers, and recupera-tors installed in venting systems of appliances not re-quired to be equipped with draft hoods, provided the gasutilization appliance manufacturer's instructions coverthe installation of such a device in the venting systemand performance in accordance with Sections 510.3.1and 510.3.2 is obtained.
511.0 Sizing of Category I Venting Systems.
511.1 These venting tables shall not be used where obstruc-tions (see Section 510.15) are installed in the venting system.The installation of vents serving listed appliances with ventdampers shall be in accordance with the appliance manufac-turer’s instructions or in accordance with the following[NFPA 54:13.1.1]:
(1) The maximum capacity of the vent system shall be de-termined using the NAT Max column.
(2) The minimum capacity shall be determined as though theappliance were a fan-assisted appliance, using the FANMin column to determine the minimum capacity of thevent system. Where the corresponding “FAN Min” is“NA” the vent configuration shall not be permitted andan alternative venting configuration shall be utilized.
511.1.1 Where the vent size determined from the tables
is smaller than the appliance draft hood outlet or flue col-
lar, the use of the smaller size shall be permitted provided
that the installation complies with the following require-
ments [NFPA 54:13.1.2]:
(1) The total vent height (H) is at least ten (10) feet (3
m).
(2) Vents for appliance draft hood outlets or flue collars
twelve (12) inches (300 mm) in diameter or smaller
are not reduced more than one (1) table size.
(3) Vents for appliance draft hood outlets or flue collars
exceeding twelve (12) inches (300 mm) in diameter
are not reduced more than two (2) table sizes.
(4) The maximum capacity listed in the tables for a fan-as-sisted appliance is reduced by 10 percent (0.90 maxi-mum table capacity).
912010 CALIFORNIA PLUMBING CODE
WATER HEATERS
(5) The draft hood outlet exceeds four (4) inches (100mm) in diameter. Do not connect a three (3) inch (80mm) diameter vent to a four (4) inch (100 mm) diam-eter draft hood outlet. This provision shall not apply tofan-assisted appliances.
511.1.2 Elbows. Single-appliance venting configurationswith zero (0) lateral lengths in Tables 5-8, 5-9, and 5-12shall have no elbows in the venting system. Single-ap-pliance venting with lateral lengths, include allowancefor two (2) 90 degree elbows. For each additional elbowup to and including 45 degrees, the maximum capacitylisted in the venting tables shall be reduced by 5 percent.For each additional elbow exceeding 45 degrees up toand including 90 degrees, the maximum capacity listedin the venting tables shall be reduced by 10 percent.[NFPA 54:13.1.3]
Where multiple offsets occur in a vent, the total lat-eral length of all offsets combined shall not exceed thatspecified in Tables 5–8 through 5–12. [NFPA 54-09:13.1.3]511.1.3 Zero (0) lateral (L) shall apply only to a straightvertical vent attached to a top outlet draft hood or fluecollar. [NFPA 54:13.1.4]511.1.4 Sea level input ratings shall be used when deter-mining maximum capacity for high-altitude installation.Actual input (derated for altitude) shall be used for de-termining minimum capacity for high-altitude installa-tion. [NFPA 54:13.1.5]511.1.5 For appliances with more than one (1) input rate,the minimum vent capacity (FANMin) determined fromthe tables shall be less than the lowest appliance inputrating, and the maximum vent capacity (FAN Max/NATMax) determined from the tables shall exceed the high-est appliance rating input. [NFPA 54:13.1.6]511.1.6 Listed corrugated metallic chimney liner systemsin masonry chimneys shall be sized by using Tables 5-8or 5-9 for Type B vents with the maximum capacity re-duced by 20 percent (0.80 maximum capacity) and theminimum capacity as shown in Tables 5-8 or 5-9.
Corrugated metallic liner systems installed withbends or offsets shall have their maximum capacity fur-ther reduced in accordance with Section 511.1.2. The 20percent reduction for corrugated metallic chimney linersystems includes an allowance for one (1) long radius 90degree turn at the bottom of the liner. [NFPA 54:13.1.7]511.1.7 Connection to Chimney Liners. Connectionsbetween chimney liners and listed double-wall connec-tors shall be made with listed adapters designed for suchpurposes. [NFPA 54:13.1.8]511.1.8 Vertical Vent Upsizing 7 x Rule.Where the ver-tical vent has a larger diameter than the vent connector,the vertical vent diameter shall be used to determine theminimum vent capacity, and the connector diameter shallbe used to determine the maximum vent capacity. The
flow area of the vertical vent shall not exceed seven (7)times the flow area of the listed appliance categorizedvent area, flue collar area, or draft hood outlet area unlessdesigned in accordance with approved engineering meth-ods. [NFPA 54:13.1.9]511.1.9 Draft Hood Conversion Accessories. Drafthood conversion accessories for use with masonry chim-neys venting listed Category I fan-assisted appliancesshall be listed and installed in accordance with the listedaccessory manufacturer’s installation instructions.[NFPA 54:13.1.10]511.1.10 Tables 5-8 through 5-12 shall be used for chim-neys and vents not exposed to the outdoors below theroof line. AType B vent or listed chimney lining systempassing through an unused masonry chimney flue shallnot be considered to be exposed to the outdoors. A TypeB vent passing through an unventilated enclosure orchase insulated to a value of at least R8 shall not be con-sidered to be exposed to the outdoors. Table 5-10 in com-bination with Table 5-13 shall be used for clay-tile-linedexterior masonry chimneys, provided the following aremet [NFPA 54:13.1.11]:(1) The vent connector is Type B double wall.(2) The vent connector length is limited to one and one-
half (11⁄2) feet for each inch (18 mm/mm) of ventconnector diameter.
(3) The appliance is draft-hood-equipped.(4) The input rating is less than the maximum capacity
given in Table 5-10.(5) For a water heater, the outdoor design temperature
shall be not less than 5°F (-15°C).(6) For a space-heating appliance, the input rating ex-
ceeds the minimum capacity given by Table 5-13.511.1.11 Corrugated vent connectors shall not be smallerthan the listed appliance categorized vent diameter, fluecollar diameter, or draft hood outlet diameter. [NFPA54:13.1.12]511.1.12 Vent connectors shall not be upsized more thantwo (2) sizes exceeding the listed appliance categorizedvent diameter, flue collar diameter, or draft hood outletdiameter. [NFPA 54:13.1.13]511.1.13 In a single run of vent or vent connector, morethan one (1) diameter and type shall be permitted to beused, provided that the sizes and types are permitted bythe tables. [NFPA 54:13.1.14]511.1.14 Interpolation shall be permitted in calculatingcapacities for vent dimensions that fall between table en-tries (See Part II-Example G.1.3). [NFPA 54:13.1.15]511.1.15 Extrapolation beyond the table entries shall notbe permitted. [NFPA 54:13.1.16]511.1.16 For vent heights lower than six (6) feet and ex-ceeding vent heights shown in the tables, engineeringmethods shall be used to calculate vent capacities. [NFPA54:13.1.17]
92 2010 CALIFORNIA PLUMBING CODE
WATER HEATERS
511.2 Additional Requirements to Multiple ApplianceVent Table 5-14 through Table 5-22.
511.2.1 Obstructions and Vent Damper. These ventingtables shall not be used where obstructions (See Section510.15) are installed in the venting system. The installa-tion of vents serving listed appliances with vent dampersshall be in accordance with the appliance manufacturer’sinstructions or in accordance with the following [NFPA54:13.2.1]:(1) The maximum capacity of the vent connector shall
be determined using the NAT Max column.(2) The maximum capacity of the vertical vent or chim-
ney shall be determined using the FAN + NAT col-umn when the second appliance is a fan-assistedappliance, or the NAT + NAT column when the sec-ond appliance is equipped with a draft hood.
(3) The minimum capacity shall be determined as if theappliance were a fan-assisted appliance.(a) The minimum capacity of the vent connector
shall be determined using the FANMin column.(b) The FAN + FAN column shall be used when the
second appliance is a fan-assisted appliance,and the FAN + NAT column shall be used whenthe second appliance is equipped with a drafthood, to determine whether the vertical vent orchimney configuration is not permitted (NA).Where the vent configuration is NA, the ventconfiguration shall not be permitted and an al-ternative venting configuration shall be utilized.
511.2.2 The vent connector horizontal length shall beeighteen (18) inches/inch (18 mm/mm) of connector di-ameter as shown in Table 5-7. [NFPA 54:13.2.2]511.2.3 The vent connector shall be routed to the ventutilizing the shortest possible route. Connectors withlonger horizontal lengths than those listed in Table 5-7are permitted under the following conditions [NFPA54:13.2.3]:(A) The maximum capacity (FANMax or NATMax) of
the vent connector shall be reduced 10 percent foreach additional multiple of the length listed in Table5-7. For example, the length listed for a four (4) inch(100 mm) connector shall not exceed six (6) feet (1.8m). With a connector length exceeding six (6) feet(1.8 m) but not exceeding twelve (12) feet (3.7 m),the maximum capacity must be reduced by 10 per-cent (0.90 maximum vent connector capacity). Witha connector length exceeding twelve (12) feet (3.7m) but not exceeding eighteen (18) feet (5.5 m), themaximum capacity must be reduced by 20 percent(0.80 maximum vent capacity) [NFPA54:13.2.3(1)].
(B) For a connector serving a fan-assisted appliance, theminimum capacity (FANMin) of the connector shallbe determined by referring to the corresponding sin-gle appliance table. For Type B double-wall con-nectors, Table 5-8 shall be used. For single-wallconnectors, Table 5-9 shall be used. The height (H)and lateral (L) shall be measured according to the
procedures for a single appliance vent, as if the otherappliances were not present. [NFPA 54:13.2.3(2)]
511.2.4Where the vent connectors are combined prior toentering the vertical portion of the common vent to forma common vent manifold, the size of the common ventmanifold and the common vent shall be determined byapplying a 10 percent reduction (.90 x maximum com-mon vent capacity) to the Common Vent Capacity partof the common vent tables. The length of the commonvent connector manifold (LM) shall not exceed eighteen(18) inches/inch (18 mm/mm) of common vent connec-tor manifold diameter (D) (See Part II-Figure G.1(k)).[NFPA 54:13.2.4]511.2.5 Vent Offset.Where the common vertical vent isoffset, the maximum capacity of the common vent shallbe reduced in accordance with Section 511.2.6, and thehorizontal length of the common vent offset shall not ex-ceed eighteen (18) inches/inch (18 mm/mm) of commonvent diameter. Where multiple offsets occur in a com-mon vent, the total horizontal length of offsets combinedshall not exceed eighteen (18) inches/inch (18 mm/mm)of common vent diameter. [NFPA 54:13.2.5]511.2.6 For each elbow up to and including 45 degrees inthe common vent, the maximum common vent capacitylisted in the venting tables shall be reduced by 5 percent.For each elbow exceeding 45 degrees up to and includ-ing 90 degrees, the maximum common vent capacitylisted in the venting tables shall be reduced by 10 per-cent. [NFPA 54:13.2.6]511.2.7 Common Vent Minimum Size. The cross-sec-tional area of the common vent shall be equal to or ex-ceeding the cross-sectional area of the largest connector.[NFPA 54:13.2.8]
932010 CALIFORNIA PLUMBING CODE
WATER HEATERS
CONNECTOR DIAMETER
MAXIMUM (in.)
CONNECTOR HORIZONTAL
LENGTH (ft.)
3 41⁄24 65 71⁄26 97 101⁄28 129 131⁄210 1512 1814 2116 2418 2720 3022 3324 36
TABLE 5-7VENT CONNECTOR MAXIMUM LENGTH
[NFPA 54:TABLE 13.2.2]
For SI units, 1 in. = 25.4 mm; 1 ft. = 0.305 m.
511.2.8 Tee andWye Fittings. Tee and wye fittings con-nected to a common gas vent shall be considered as partof the common gas vent and constructed of materialsconsistent with that of the common gas vent. [NFPA 54-09:13.2.9]511.2.9At the point where tee or wye fittings connect toa common vent, the opening size of the fitting shall beequal to the size of the common vent. Such fittings shallnot be prohibited from having reduced size openings atthe point of connection of appliance vent connectors.[NFPA 54:13.2.10]511.2.10 Sea level input ratings shall be used when de-termining maximum capacity for high-altitude installa-tion. Actual input (derated for altitude) shall be used fordetermining minimum capacity for high-altitude instal-lation. [NFPA 54:13.2.11]511.2.11 The connector rise (R) for each appliance con-nector shall be measured from the draft hood outlet orflue collar to the centerline where the vent gas streamscome together. [NFPA 54:13.2.12]511.2.12 For multiple units of gas utilization applianceslocated on one (1) floor, available total height (H) shallbe measured from the highest draft hood outlet or fluecollar up to the level of the outlet of the common vent.[NFPA 54:13.2.13]511.2.13 For multistory installations, available totalheight (H) for each segment of the system shall be thevertical distance between the highest draft hood outlet orflue collar entering that segment and the centerline of thenext higher interconnection tee (See Part II-FigureG.1(m)). [NFPA 54:13.2.14]511.2.14 The size of the lowest connector and of the ver-tical vent leading to the lowest interconnection of a mul-tistory system shall be in accordance with Tables 5-8 or5-9 for available total height (H) up to the lowest inter-connection (See Part II-Figure G.1(n)). [NFPA54:13.2.15]511.2.15Where used in multistory systems, vertical com-mon vents shall be Type B double-wall and shall be in-stalled with a listed vent cap. [NFPA 54:13.2.16]511.2.16 Offsets in multistory common vent systemsshall be limited to a single offset in each system, and sys-tems with an offset shall comply with all of the follow-ing [NFPA 54:13.2.17]:(1) The offset angle shall not exceed 45 degrees from
vertical.(2) The horizontal length of the offset shall not exceed
eighteen (18) inches for each inch (180 mm/mm) ofcommon vent diameter of the segment in which theoffset is located.
(3) For the segment of the common vertical vent con-taining the offset, the common vent capacity listed inthe common venting tables shall be reduced by 20percent (0.80 x maximum common vent capacity).
(4) A multistory common vent shall not be reduced insize above the offset.
511.2.17 Where two (2) or more appliances are con-nected to a vertical vent or chimney, the flow area of thelargest section of vertical vent or chimney shall not ex-ceed seven (7) times the smallest listed appliance cate-gorized vent areas, flue collar area, or draft hood outletarea unless designed in accordance with approved engi-neering methods. [NFPA 54:13.2.18]511.2.18 For appliances with more than one (1) inputrate, the minimum vent connector capacity (FAN Min)determined from the tables shall be less than the lowestappliance input rating, and the maximum vent connectorcapacity (FAN Max or NAT Max) determined from thetable shall exceed the highest appliance input rating.[NFPA 54:13.2.19]511.2.19 Listed corrugated metallic chimney liner sys-tems in masonry chimneys shall be sized by using Tables5-14 or 5-15 for Type B vents, with the maximum ca-pacity reduced by 20 percent (0.80 maximum capacity)and the minimum capacity as shown in Tables 5-14 or 5-15. Corrugated metallic liner systems installed withbends or offsets shall have their maximum capacity fur-ther reduced in accordance with Sections 511.2.5 and511.2.6. The 20 percent reduction for corrugated metal-lic chimney liner systems includes an allowance for one(1) long radius 90 degree turn at the bottom of the liner.[NFPA 54:13.2.20]511.2.20 Tables 5-14 and 5-15 shall be used for chim-neys and vents not exposed to the outdoors below theroof line. AType B vent passing through an unventilatedenclosure or chase insulated to a value of not less than R8shall not be considered to be exposed to the outdoors. Ta-bles 5-19 and 5-20 shall be used for clay-tile-lined exte-rior masonry chimneys, provided all of the followingconditions are met [NFPA 54:13.2.22]:(1) Vent connector is Type B double-wall.(2) One (1) appliance is draft-hood-equipped.(3) The combined appliance input rating is less than the
maximum capacity given by Table 5-19 (for NAT +NAT) or Table 5-21 (for FAN + NAT).
(4) The input rating of each space-heating appliance ex-ceeds the minimum input rating given by Table 5-20(for NAT + NAT) or Table 5-22 (for FAN + NAT).
(5) The vent connector sizing is in accordance withTable 5-16.
511.2.21 Vent connectors shall not be increased morethan two (2) sizes exceeding the listed appliance catego-rized vent diameter, flue collar diameter, or draft hoodoutlet diameter. Vent connectors for draft-hood-equippedappliances shall not be smaller than the draft hood outletdiameter. Where vent connector sizes determined fromthe tables for fan-assisted appliances are smaller than theflue collar diameter, the use of the smaller sizes shall bepermitted provided that the installation complies with allof the following conditions [NFPA 54:13.2.24]:(1) Vent connectors for fan-assisted appliance flue col-
lars twelve (12) inches (300 mm) in diameter or
94 2010 CALIFORNIA PLUMBING CODE
WATER HEATERS
smaller are not reduced by more than one (1) tablesize [e.g., twelve (12) inches to ten (10) inches (300mm to 250 mm) is a one (1) size reduction] andthose exceeding twelve (12) inches (300 mm) in di-ameter are not reduced exceeding two (2) table sizes[e.g., twenty-four (24) inch to twenty (20) inch (610mm to 510 mm) is a two (2) size reduction].
(2) Fan-assisted appliances are common vented with adraft-hood-equipped appliance.
(3) The vent connector has a smooth interior wall.511.2.22 Combinations of pipe sizes, single-wall, anddouble-wall metal pipe shall be allowed within any con-nector run or within the common vent, provided ALL ofthe appropriate tables permit ALL of the desired sizesand types of pipe, as if they were used for the entirelength of the subject connector or vent. Where single-wall and Type B double-wall metal pipes are used forvent connectors within the same venting system, thecommon vent must be sized using Tables 5-15 or 5-17 asappropriate. [NFPA 54:13.2.25]511.2.23Where a table permits more than one (1) diam-eter of pipe to be used for a connector or vent, all the per-mitted sizes shall be permitted to be used. [NFPA54:13.2.26]511.2.24 Interpolation shall be permitted in calculatingcapacities for vent dimensions that fall between table en-tries (See Part II Annex G.1.3). [NFPA 54:13.2.27]511.2.25 Extrapolation beyond the table entries shall notbe permitted. [NFPA 54:13.2.28]511.2.26 For vent heights lower than six (6) feet and ex-ceeding vent heights shown in the tables, engineeringmethods shall be used to calculate vent capacities. [NFPA54:13.2.29]
512.0 Direct-Vent Appliances.Listed direct-vent gas utilization appliances shall be consid-ered properly vented where installed in accordance with theterms of its listing, the manufacturer’s instructions, and Sec-tion 510.8.3. [NFPA 54:12.3.5]
952010 CALIFORNIA PLUMBING CODE
WATER HEATERS
FIGURE 5-7 ALL COMBUSTION AIR FROM ADJACENT INDOORSPACESTHROUGH INDOOR COMBUSTION AIR OPENINGS.
[NFPA 54: FIGURE A.9.3.2.3(1)]
96 2010 CALIFORNIA PLUMBING CODE
WATER HEATERS
FIGURE 5-8 ALL COMBUSTION AIR FROM OUTDOORS.INLET AIR FROMVENTILATED CRAWL SPACE AND
OUTLET AIRTOVENTILATED ATTIC.[NFPA 54: FIGURE A.9.3.3.1(a)]
FIGURE 5-10 ALL COMBUSTION AIR FROMOUTDOORSTHROUGH HORIZONTAL DUCTS.
[NFPA 54: FIGURE A.9.3.3.1(2)]
FIGURE 5-9 ALL COMBUSTION AIR FROMOUTDOORSTHROUGHVENTILATED ATTIC.
[NFPA 54: FIGURE A.9.3.3.1(1)(b)]
FIGURE 5-11 ALL COMBUSTION AIR FROM OUTDOORSTHROUGH SINGLE COMBUSTION AIR OPENING.
[NFPA 54: FIGURE A.9.3.3.2]
972010 CALIFORNIA PLUMBING CODE
WATER HEATERS
FIGURE 5-12 EXITTERMINALS OF MECHANICAL DRAFT ANDDIRECT-VENTVENTING SYSTEMS. [NFPA 54: FIGURE A.12.9]
FIGURE 5-13 RANGE OFWINTER DESIGNTEMPERATURES USED IN ANALYZINGEXTERIOR MASONRY CHIMNEYS INTHE UNITED STATES. [NFPA 54: FIGURE G.2.4]
98 2010 CALIFORNIA PLUMBING CODE
WATER HEATERS
TABLE 5-8TYPE B DOUBLE-WALL GASVENT [NFPA 54:TABLE 13.1(a)]
NUMBER OF APPLIANCES: SINGLE
APPLIANCETYPE: CATEGORY I
APPLIANCEVENT CONNECTION: CONNECTED DIRECTLYTOVENT
VENT DIAMETER – D (inch)
3 4 5 6 7
APPLIANCE INPUT RATING INTHOUSANDS OF BTU PER HOUR
HEIGHTH(ft)
LATERALL(ft)
FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT
Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max
6 0246
0132125
78514946
46363432
0183036
152979491
86676461
0273947
251157153149
141105103100
0325059
375232227223
205157153149
0446678
524321316310
285217211205
8 0258
0122328
84575349
50403835
0163239
16510910398
94757166
0254251
276178171164
155120115109
0285364
415263255247
235180173165
0427084
583365356347
320247237227
10 02510
0122330
88615751
53424036
0173241
175118113104
100817770
0234154
295194187176
166129124115
0265267
447289280267
255195188175
0406888
631402392376
345273263245
15 0251015
011222935
9469655953
5848454137
015304048
191136130121112
11293878276
020395161
327226219206195
187150142135128
022496476
502339330315301
285225217208198
038648498
716475463445429
390316300288275
20 025101520
01021283448
977571645852
615148444035
01429384655
202149143133124116
11910096898478
01838505969
349250242229217206
202166160150142134
02047627384
540377367351337322
307249241228217206
033628194107
776531519499481464
430346337321308295
30 02510152030
0921273356NA
1008177706458NA
64565450NANANA
0132837445373
213166160150141132113
1281121081029690NA
0143648576688
374283275262249237214
220185176171163154NA
01845597080104
587432421405389374346
336280273261249237219
027587790102131
853613600580560542507
475394385371357343321
50 02510152030
08202659NANA
10186827670NANA
6761NANANANANA
0112735425069
216183177168158149131
134122119114NANANA
0143545546384
397320312299287275250
232206200190180169NA
0154356667699
633497487471455440410
363314308298288278259
02255738597123
932715702681662642605
518445438426413401376
100 0251015203050
NANANANANANANANA
NANANANANANANANA
NANANANANANANANA
01026334047NANA
218194189182174166NANA
NANANANANANANANA
0123343505978NA
407354347335321311290NA
NANANANANANANANA
0134053627192147
665566557542528513483428
400375369361353344NANA
01852688090115180
997831820801782763726651
560510504493482471449405
For SI units, 1 in. = 25.4 mm, 1 ft. = 0.305 m, 1,000 Btu/hr = 0.293 kW, 1 in.2 = 645 mm2.
992010 CALIFORNIA PLUMBING CODE
WATER HEATERS
NUMBER OF APPLIANCES: SINGLE
APPLIANCETYPE: CATEGORY I
APPLIANCEVENT CONNECTION: CONNECTED DIRECTLYTOVENT
VENT DIAMETER – D ( inch)
8 9 10 12 14
APPLIANCE INPUT RATING INTHOUSANDS OF BTU PER HOUR
HEIGHTH(ft)
LATERALL(ft)
FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT
Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max
6 0246
0537993
698425419413
370285279273
06393110
897543536530
470370362354
075110128
1,121675668661
570455445435
0103147171
1,645982975967
850650640630
0138191219
2,2671,3461,3381,330
1,170890880870
8 0258
0508399
780483473463
415322313303
06099117
1,006619607596
537418407396
071115137
1,261770758746
660515503490
098154180
1,8581,1241,1101,097
970745733720
0130199231
2,5711,5431,5281,514
1,3201,0201,0101,000
10 02510
04881104
847533522504
450355346330
05795122
1,096684671651
585457446427
068112142
1,377852839817
720560547525
093149187
2,0361,2441,2291,204
1,060850829795
0124192238
2,8251,7131,6961,669
1,4501,1301,1051,080
15 0251015
0457699115
970633620600580
525414403386373
05390116134
1,263815800777755
682544529507491
063105135155
1,5961,0191,003977953
840675660635610
086140177202
2,3801,4951,4761,4461,418
1,240985967936905
0114182227257
3,3232,0622,0412,0091,976
1,7201,3501,3271,2891,250
20 025101520
0417395111125
1,057711697675654634
575470460443427410
05086112129145
1,384917902877853830
752612599576557537
059101130150167
1,7561,1501,1331,1051,0781,052
930755738710688665
081135172195217
2,6371,6941,6741,6411,6091,578
1,3501,1001,0791,0451,018990
0107174220248273
3,7012,3432,3202,2822,2452,210
1,9001,5201,4981,4601,4251,390
30 02510152030
0336991105119149
1,173826811788765743702
650535524507490473444
04282107124139171
1,5481,0721,0551,0281,002977929
855700688668648628594
05496125143160195
1,9771,3511,3321,3011,2721,2431,189
1,060865851829807784745
074127164187207246
3,0042,0041,9811,9441,9081,8731,807
1,5501,3101,2891,2541,2201,1851,130
098164209237260305
4,2522,7862,7592,7162,6742,6332,555
2,1701,8001,7751,7331,6921,6501,585
50 02510152030
0266586100113141
1,297975960935911888844
708615605589572556522
03377101117131161
1,7301,2761,2591,2301,2031,1761,125
952813798773747722670
04190118136151183
2,2311,6201,6001,5671,5361,5051,446
1,1951,010996972948924876
066118154177195232
3,4412,4312,4062,3662,3272,2882,214
1,8251,5131,4951,4661,4371,4081,349
086151196222244287
4,9343,4093,3803,3323,2853,2393,150
2,5502,1252,1022,0642,0261,9871,910
100 0251015203050
021608093105131197
1,4111,1551,1411,1181,0951,0731,029944
770700692679666653627575
0257194109122149217
1,9081,5361,5191,4921,4651,4381,3871,288
1,040935926910895880849787
03082108126141170241
2,4911,9751,9551,9231,8921,8611,8021,688
1,3101,1701,1591,1421,1241,1071,0711,000
044107142163181215292
3,9253,0273,0022,9612,9202,8802,8032,657
2,0501,8201,8031,7751,7471,7191,6631,550
072136180206226265350
5,7294,3134,2824,2314,1824,1334,0373,856
2,9502,5502,5312,5002,4692,4382,3752,250
TABLE 5-8TYPE B DOUBLE-WALL GASVENT [NFPA 54:TABLE 13.1(a)] (continued)
For SI units, 1 in. = 25.4 mm, 1 ft. = 0.305 m, 1,000 Btu/hr = 0.293 kW, 1 in.2 = 645 mm2.
100 2010 CALIFORNIA PLUMBING CODE
WATER HEATERS
NUMBER OF APPLIANCES: SINGLE
APPLIANCETYPE: CATEGORY I
APPLIANCEVENT CONNECTION: CONNECTED DIRECTLYTOVENT
VENT DIAMETER – D (inch)
16 18 20 22 24
APPLIANCE INPUT RATING INTHOUSANDS OF BTU PER HOUR
HeightH(ft)
LateralL(ft)
FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT
Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max
6 0246
0178242276
2,9831,7691,7611,753
1,5301,1701,1601,150
0225300341
3,8022,2502,2422,235
1,9601,4801,4751,470
0296390437
4,7212,7822,7742,767
2,4301,8501,8351,820
0360469523
5,7373,3773,3703,363
2,9502,2202,2152,210
0426555618
6,8534,0304,0234,017
3,5202,6702,6602,650
8 0258
0168251289
3,3992,0302,0132,000
1,7401,3401,3301,320
0212311354
4,3332,5842,5632,552
2,2201,7001,6851,670
0278398450
5,3873,1963,1803,163
2,7502,1102,0902,070
0336476537
6,5553,8823,8633,850
3,3602,5602,5452,530
0401562630
7,8384,6344,6124,602
4,0103,0503,0403,030
10 02510
0161243298
3,7422,2562,2382,209
1,9251,4801,4611,430
0202300364
4,7822,8682,8492,818
2,4501,8901,8711,840
0264382459
5,9553,5563,5363,504
3,0502,3402,3182,280
0319458546
7,2544,3224,3014,268
3,7102,8402,8182,780
0378540641
8,6825,1535,1325,099
4,4503,3903,3713,340
15 0251015
0147229283318
4,4232,7192,6962,6592,623
2,2701,7701,7481,7121,675
0186283346385
5,6783,4673,4423,4023,363
2,9002,2602,2352,1932,150
0239355432479
7,0994,3044,2784,2344,192
3,6202,8002,7772,7392,700
0290426510564
8,6655,2325,2045,1595,115
4,4103,4103,3853,3433,300
0346501599665
10,3936,2516,2226,1756,129
5,3004,0804,0574,0193,980
20 025101520
0139219273306335
4,9483,0973,0713,0292,9882,948
2,5202,0001,9781,9401,9101,880
0175270334372404
6,3763,9553,9263,8803,8353,791
3,2502,5702,5442,5002,4652,430
0220337413459495
7,9884,9164,8854,8354,7864,737
4,0603,2003,1743,1303,0903,050
0269403489541585
9,7855,9835,9505,8965,8445,792
4,9803,9103,8803,8303,7953,760
0321475573631689
11,7537,1547,1197,0637,0076,953
6,0004,7004,6624,6004,5754,550
30 02510152030
0127206259292319369
5,7253,6963,6663,6173,5703,5233,433
2,9202,3802,3502,3002,2502,2002,130
0159252316354384440
7,4204,7344,7014,6474,5944,5424,442
3,7703,0503,0202,9702,9202,8702,785
0199312386431467540
9,3415,9005,8635,8035,7445,6865,574
4,7503,8103,7833,7393,6953,6503,565
0241373456507548635
11,4837,1947,1557,0907,0266,9646,842
5,8504,6504,6224,5744,5274,4804,375
0285439535590639739
13,8488,6178,5748,5058,4378,3708,239
7,0605,6005,5525,4715,3915,3105,225
50 02510152030
0113191243274300347
6,7114,5544,5204,4644,4094,3564,253
3,4402,8402,8132,7672,7212,6752,631
0141234295330361412
8,7745,8645,8265,7635,7015,6415,523
4,4603,6703,6393,5853,5343,4813,431
0171283355396433494
11,1297,3397,2957,2247,1557,0866,953
5,6354,6304,5974,5424,5114,4794,421
0209336419465506577
13,7678,9808,9338,8558,7798,7048,557
6,9405,6955,6545,5855,5465,5065,444
0251394491542586672
16,69410,78810,73710,65210,57010,48810,328
8,4306,8606,8186,7496,7106,6706,603
100 0251015203050
095172223252277319415
7,9145,8345,7975,7375,6785,6195,5055,289
4,0503,5003,4753,4343,3923,3513,2673,100
0120208268304330378486
10,4857,5917,5487,4787,4097,3417,2096,956
5,3004,6004,5664,5094,4514,3944,2794,050
0138245318358387446572
13,4549,5779,5289,4479,3679,2899,1368,841
6,7005,8005,7695,7175,6655,6135,5095,300
0169293374418452514659
16,81711,80311,74811,65811,56911,48211,31010,979
8,6007,2007,1627,1007,0376,9756,8506,600
0204341436487523592752
20,57814,26414,20414,10514,00713,91013,72013,354
10,3008,8008,7568,6838,6108,5378,3918,100
TABLE 5-8TYPE B DOUBLE-WALL GASVENT [NFPA 54: TABLE 13.1(a)] (continued)
For SI units, 1 in. = 25.4 mm, 1 ft. = 0.305 m, 1,000 Btu/hr = 0.293 kW, 1 in.2 = 645 mm2.
1012010 CALIFORNIA PLUMBING CODE
WATER HEATERS
NUMBER OF APPLIANCES: SINGLE
APPLIANCETYPE: CATEGORY I
APPLIANCEVENT CONNECTION: SINGLE-WALL METAL CONNECTOR
VENT DIAMETER – D (inch)
3 4 5 6 7
APPLIANCE INPUT RATING INTHOUSANDS OF BTU PER HOUR
HEIGHTH(ft)
LATERALL(ft)
FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT
Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max
6 0246
3839NANA
7751NANA
45363331
59607483
151969289
85666360
8585102114
249156152147
14010410299
126123146163
373231225220
204156152148
165159187207
522320313307
284213208203
8 0258
3739NANA
8356NANA
50393733
58597790
16410810295
93756964
8383107122
273176168161
154119114107
123121151175
412261252243
234179171163
161155193223
580363352342
319246235225
10 02510
373952NA
876156NA
53413934
57597697
174117111100
99807668
8282105132
293193185171
165128122112
120119148188
444287277261
254194186171
158153190237
628400388369
344272261241
15 0251015
363851NANA
936963NANA
57474439NA
56577595NA
190136128116NA
11193867972
8080102128158
325225216201186
186149140131124
116115144182220
499337326308290
283224217203192
153148182228272
713473459438418
388314298284269
20 025101520
353750NANANA
967468NANANA
60504741NANA
54567393NANA
200148140129NANA
11899948680NA
7878100125155186
346248239223208192
201165158146136126
114113141177216254
537375363344325306
306248239224210196
149144178222264309
772528514491469448
428344334316301285
30 02510152030
343749NANANANA
998074NANANANA
635652NANANANA
53557291115NANA
211164157144131NANA
12711110698NANANA
767698122151181NA
372281271255239223NA
219183173168157NANA
110109136171208246NA
584429417397377357NA
334279271257242228NA
144139171213255298389
849610595570547524477
472392382367349333305
50 02510152030
333648NANANANA
998480NANANANA
6661NANANANANA
51537089112NANA
213181174160148NANA
133121117NANANANA
737394118145176NA
394318308292275257NA
230205198186174NANA
105104131162199236315
629495482461441420376
361312305292280267NA
138133164203244285373
928712696671646622573
515443435420405389NA
100 0251015203050
NANANANANANANANA
NANANANANANANANA
NANANANANANANANA
49516785132NANANA
214192186175162NANANA
NANANANANANANANA
697090113138168231NA
403351342324310295264NA
NANANANANANANANA
10098125153188224301NA
659563551532511487448NA
395373366354343NANANA
131125156191230270355540
991828813789764739685584
555508501486473458NANA
TABLE 5-9TYPE B DOUBLE-WALL GASVENT [NFPA 54: TABLE 13.1(b)]
For SI units, 1 in. = 25.4 mm, 1 ft. = 0.305 m, 1,000 Btu/hr = 0.293 kW, 1 in.2 = 645 mm2.
102 2010 CALIFORNIA PLUMBING CODE
WATER HEATERS
NUMBER OF APPLIANCES: SINGLE
APPLIANCETYPE: CATEGORY I
APPLIANCEVENT CONNECTION: SINGLE-WALL METAL CONNECTOR
VENT DIAMETER – D (inch)
8 9 10 12
APPLIANCE INPUT RATING INTHOUSANDS OF BTU PER HOUR
HEIGHTH(ft)
LATERALL(ft)
FAN NAT FAN NAT FAN NAT FAN NAT
Min Max Max Min Max Max Min Max Max Min Max Max
6 0246
211201237263
695423416409
369284277271
267251295327
894541533526
469368360352
371347409449
1,118673664656
569453443433
537498584638
1,639979971962
849648638627
8 0258
206197245280
777482470458
414321311300
258246305344
1,002617604591
536417404392
360339418470
1,257768754740
658513500486
521486598665
1,8521,1201,1041,089
967743730715
10 02510
202193241296
844531518497
449354344325
253242299363
1,093681667643
584456443423
351332409492
1,373849834808
718559544520
507475584688
2,0311,2421,2241,194
1,057848825788
15 0251015
195187231284334
966631616592568
523413400381367
244232287349404
1,259812795768742
681543526501484
336319392470540
1,5911,015997966937
838673657628601
488457562664750
2,3741,4911,4691,4331,399
1,237983963928894
20 025101520
190182224277325374
1,053708692666640616
573468457437419400
238227279339393448
1,379914896866838810
750611596570549526
326309381457526592
1,7511,1461,1261,0921,0601,028
927754734702677651
473443547646730808
2,6311,6891,6651,6261,5871,550
1,3461,0981,0741,0371,005973
30 02510152030
184175215265312360461
1,168823806777750723670
647533521501481461426
229219269327379433541
1,5421,0691,0491,017985955895
852698684662638615574
312296366440507570704
1,9711,3461,3241,2871,2511,2161,147
1,056863846821794768720
454424524620702780937
2,9961,9991,9711,9271,8841,8411,759
1,5451,3081,2831,2431,2051,1661,101
50 02510152030
176168204253299345442
1,292971953923894866809
704613602583562543502
220209257313363415521
1,7241,2731,2521,2171,1831,1501,086
948811795765736708649
295280347418481544674
2,2231,6151,5911,5511,5121,4731,399
1,1891,007991963934906848
428401496589668741892
3,4322,4262,3962,3472,2992,2512,159
1,8181,5091,4901,4551,4211,3871,318
100 0251015203050
166158194238281325418617
1,4041,1521,1341,1041,0751,046988866
765698688672656639NANA
207196240293342391491711
1,9001,5321,5111,4771,4431,4101,3431,205
1,033933921902884864824NA
273259322389447507631895
2,4791,9701,9451,9051,8651,8251,7471,591
1,3001,1681,1531,1331,1101,0871,041NA
395371460547618690834
1,138
3,9123,0212,9902,9382,8882,8382,7392,547
2,0421,8171,7961,7631,7301,6961,6271,489
TABLE 5-9TYPE B DOUBLE-WALL GASVENT [NFPA 54:Table 13.1(b)] (continued)
For SI units, 1 in. = 25.4 mm, 1 ft. = 0.305 m, 1,000 Btu/hr = 0.293 kW, 1 in.2 = 645 mm2.
1032010 CALIFORNIA PLUMBING CODE
WATER HEATERS
NUMBER OF APPLIANCES: SINGLE
APPLIANCETYPE: CATEGORY I
APPLIANCEVENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR
TYPE B DOUBLE-WALL CONNECTOR DIAMETER – D (inch)TO BE USEDWITH CHIMNEY AREASWITHINTHE SIZE LIMITS AT BOTTOM
3 4 5 6 7
APPLIANCE INPUT RATING INTHOUSANDS OF BTU PER HOUR
HEIGHTH(ft)
LATERALL(ft)
FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT
Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max
6 25
NANA
NANA
2825
NANA
NANA
5249
NANA
NANA
8682
NANA
NANA
130117
NANA
NANA
180165
8 258
NANANA
NANANA
292624
NANANA
NANANA
555248
NANANA
NANANA
938883
NANANA
NANANA
145134127
NANANA
NANANA
198183175
10 2510
NANANA
NANANA
312825
NANANA
NANANA
615750
NANANA
NANANA
1039687
NANANA
NANANA
162148139
NANANA
NANANA
221204191
15 251015
NANANANA
NANANANA
353528NA
NANANANA
NANANANA
67625548
NANANANA
NANANANA
1141079789
NANANANA
NANANANA
179164153141
53NANANA
475NANANA
250231216201
20 25101520
NANANANANA
NANANANANA
3836NANANA
NANANANANA
NANANANANA
746860NANA
NANANANANA
NANANANANA
1241161079783
NANANANANA
NANANANANA
201184172159148
5180NANANA
522503NANANA
274254237220206
30 2510152030
NANANANANANA
NANANANANANA
41NANANANANA
NANANANANANA
NANANANANANA
827667NANANA
NANANANANANA
NANANANANANA
13712811510791NA
NANANANANANA
NANANANANANA
216198184171159NA
4775NANANANA
581561NANANANA
303281263243227188
50 2510152030
NANANANANANA
NANANANANANA
NANANANANANA
NANANANANANA
NANANANANANA
92NANANANANA
NANANANANANA
NANANANANANA
161151138127NANA
NANANANANANA
NANANANANANA
251230215199185NA
NANANANANANA
NANANANANANA
351323304282264NA
Minimuminternalarea of
chimney(in.2)
12 19 28 38 50
Maximuminternalarea of
chimney(in.2)
Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas.
For SI units, 1 in. = 25.4 mm, 1 ft. = 0.305 m, 1,000 Btu/hr = 0.293 kW, 1 in.2 = 645 mm2.
TABLE 5-10MASONRY CHIMNEY [NFPA 54-09:TABLE 13.1(c)]
104 2010 CALIFORNIA PLUMBING CODE
WATER HEATERS
For SI units, 1 in. = 25.4 mm, 1 ft. = 0.305 m, 1,000 Btu/hr = 0.293 kW, 1 in.2 = 645 mm2.
TABLE 5-10MASONRY CHIMNEY [NFPA 54-09: TABLE 13.1(c)] (continued)
NUMBER OF APPLIANCES: SINGLE
APPLIANCETYPE: CATEGORY I
APPLIANCEVENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR
TYPE B DOUBLE-WALL CONNECTOR DIAMETER – D (inch)TO BE USEDWITH CHIMNEY AREASWITHINTHE SIZE LIMITS AT BOTTOM
8 9 10 12
APPLIANCE INPUT RATING INTHOUSANDS OF BTU PER HOUR
HEIGHTH(ft)
LATERALL(ft)
FAN NAT FAN NAT FAN NAT FAN NAT
Min Max Max Min Max Max Min Max Max Min Max Max
6 25
NANA
NANA
247231
NANA
NANA
320298
NANA
NANA
401376
NANA
NANA
581561
8 258
NANANA
NANANA
266247239
84NANA
590NANA
350328318
100149173
728711695
446423410
139201231
1,0241,007990
651640623
10 2510
68NANA
519NANA
298277263
82124155
655638610
388365347
98146182
810791762
491466444
136196240
1,1441,1241,093
724712668
15 251015
6499126NA
613594565NA
336313296281
77118148171
779759727698
441416394375
92139173198
968946912880
562533567485
127186229259
1,3761,3521,3151,280
841828777742
20 25101520
6195122NANA
678658627NANA
375350332314296
73113143165186
867845811780750
491463440418397
87133167191214
1,0831,0591,022987955
627597566541513
121179221251277
1,5481,5231,4821,4431,406
953933879840807
30 2510152030
5790115NANANA
762741709NANANA
421393373353332288
68106135156176NA
985962927893860NA
558526500476450416
81125158181203249
1,2401,2161,1761,1391,1031,035
717683648621592555
111169210239264318
1,7931,7661,7211,6791,6381,560
1,1121,0941,025981940877
50 2510152030
5183NANANANA
840819NANANANA
477445424400376327
6198126146165NA
1,1061,0831,0471,010977NA
633596567539511468
72116147170190233
1,4131,3871,3471,3071,2691,196
812774733702669623
99155195222246295
2,0802,0522,0061,9611,9161,832
1,2431,2251,1471,0991,050984
Minimuminternalarea of
chimney(in.2)
63 78 95 132
Maximuminternalarea of
chimney(in.2)
Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas.
1052010 CALIFORNIA PLUMBING CODE
WATER HEATERS
For SI units, 1 in. = 25.4 mm, 1 ft. = 0.305 m, 1,000 Btu/hr = 0.293 kW, 1 in.2 = 645 mm2.
TABLE 5-11MASONRY CHIMNEY [NFPA 54-09: TABLE 13.1(d)]
NUMBER OF APPLIANCES: SINGLE
APPLIANCETYPE: CATEGORY I
APPLIANCEVENT CONNECTION: SINGLE-WALL METAL CONNECTOR
SINGLE-WALL METAL CONNECTOR DIAMETER – D (inch)TO BE USEDWITH CHIMNEY AREASWITHINTHE SIZE LIMITS AT BOTTOM
3 4 5 6 7
APPLIANCE INPUT RATING INTHOUSANDS OF BTU PER HOUR
HEIGHTH(ft)
LATERALL(ft)
FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT
Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max
6 25
NANA
NANA
2825
NANA
NANA
5248
NANA
NANA
8681
NANA
NANA
130116
NANA
NANA
180164
8 258
NANANA
NANANA
292623
NANANA
NANANA
555147
NANANA
NANANA
938782
NANANA
NANANA
145133126
NANANA
NANANA
197182174
10 2510
NANANA
NANANA
312824
NANANA
NANANA
615649
NANANA
NANANA
1029586
NANANA
NANANA
161147137
NANANA
NANANA
220203189
15 251015
NANANANA
NANANANA
353227NA
NANANANA
NANANANA
67615446
NANANANA
NANANANA
1131069687
NANANANA
NANANANA
178163151138
166NANANA
473NANANA
249230214198
20 25101520
NANANANANA
NANANANANA
3835NANANA
NANANANANA
NANANANANA
736759NANA
NANANANANA
NANANANANA
1231151059580
NANANANANA
NANANANANA
200183170156144
163NANANANA
520NANANANA
273252235217202
30 2510152030
NANANANANANA
NANANANANANA
41NANANANANA
NANANANANANA
NANANANANANA
817566NANANA
NANANANANANA
NANANANANANA
13612711310588NA
NANANANANANA
NANANANANANA
215196182168155NA
158NANANANANA
578NANANANANA
302279260240223182
50 2510152030
NANANANANANA
NANANANANANA
NANANANANANA
NANANANANANA
NANANANANANA
91NANANANANA
NANANANANANA
NANANANANANA
160149136124NANA
NANANANANANA
NANANANANANA
250228212195180NA
NANANANANANA
NANANANANANA
350321301278258NA
Minimuminternalarea of
chimney(in.2)
12 19 28 38 50
Maximuminternalarea of
chimney(in.2)
Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas.
106 2010 CALIFORNIA PLUMBING CODE
WATER HEATERS
For SI units, 1 in. = 25.4 mm, 1 ft. = 0.305 m, 1,000 Btu/hr = 0.293 kW, 1 in.2 = 645 mm2.
TABLE 5-11MASONRY CHIMNEY [NFPA 54-09:TABLE 13.1(d)] (continued)
NUMBER OF APPLIANCES: SINGLE
APPLIANCETYPE: CATEGORY I
APPLIANCEVENT CONNECTION: SINGLE-WALL METAL CONNECTOR
SINGLE-WALL METAL CONNECTOR DIAMETER – D (inch)TO BE USEDWITH CHIMNEY AREASWITHINTHE SIZE LIMITS AT BOTTOM
8 9 10 12
APPLIANCE INPUT RATING INTHOUSANDS OF BTU PER HOUR
HEIGHTH(ft)
LATERALL(ft)
FAN NAT FAN NAT FAN NAT FAN NAT
Min Max Max Min Max Max Min Max Max Min Max Max
6 25
NANA
NANA
247230
NANA
NANA
319297
NANA
NANA
400375
NANA
NANA
580560
8 258
NANANA
NANANA
265246237
NANANA
NANANA
349327317
382NANA
725NANA
445422408
549673747
1,0211,003985
650638621
10 2510
216NANA
518NANA
297276261
271334NA
654635NA
387364345
373459547
808789758
490465441
536657771
1,1421,1211,088
722710665
15 251015
211261NANA
611591NANA
335312294278
264325392452
776755722692
440414392372
362444531606
965942907873
560531504481
520637749841
1,3731,3481,3091,272
840825774738
20 25101520
206255312NANA
675655622NANA
374348330311292
258317382442NA
864842806773NA
490461437414392
252433517591663
1,0791,0551,016979944
625594562539510
508623733823911
1,5441,5181,4751,4341,394
950930875835800
30 2510152030
200245300NANANA
759737703NANANA
420391370349327281
249306370428NANA
982958920884NANA
556524496471445408
340417500572643NA
1,2371,2101,1681,1281,089NA
715680644615585544
489600708798883
1,055
1,7891,7601,7131,6681,6241,539
1,1101,0901,020975932865
50 2510152030
191NANANANANA
837NANANANANA
475442420395370318
238293355NANANA
1,1031,0781,038NANANA
631593562533504458
323398447546616NA
1,4081,3811,3371,2941,251NA
810770728695660610
463571674761844
1,009
2,0762,0441,9941,9451,8981,805
1,2401,2201,1401,0901,040970
Minimuminternalarea of
chimney(in.2)
63 78 95 132
Maximuminternalarea of
chimney(in.2)
Seven times the listed appliance categorized vent area, flue collar area, or draft hood outlet areas.
1072010 CALIFORNIA PLUMBING CODE
WATER HEATERS
TABLE 5-12SINGLE-WALL METAL PIPE ORTYPE B ASBESTOS CEMENTVENT [NFPA 54:TABLE 13.1(e)]
NUMBER OF APPLIANCES: SINGLE
APPLIANCETYPE: DRAFT HOOD-EQUIPPED
APPLIANCEVENT CONNECTION: CONNECTED DIRECTLYTO PIPE ORVENT
HEIGHTH(ft)
LATERALL(ft)
DIAMETER – D (inch)TO BE USEDWITH CHIMNEY AREASWITHINTHE SIZE LIMITS AT BOTTOM
3 4 5 6 7 8 10 12
APPLIANCE INPUT RATING INTHOUSANDS OF BTU PER HOUR
MAXIMUM APPLIANCE INPUT RATING INTHOUSANDS OF BTU PER HOUR
6 025
393128
705551
1169488
170141128
232194177
312260242
500415390
750620600
8 02510
42322924
76615649
1261029586
185154141131
252210194180
340284264250
542451430406
815680648625
10 0251015
45353227NA
8467615446
1381111049484
202168153143130
279233215200186
372311289274258
606505480455432
912760724700666
15 025101520
49393530NANA
9172675850NA
1511221101039382
223186170158144132
312260240223207195
420350325308291273
684570540514488466
1,040865825795760726
20 025101520
53423832NANA
10180746555NA
16313612311510491
252210192178163149
342286264246228214
470392364345326306
770641610571550525
1,190990945910870832
30 02510152030
5644NANANANANA
108847868NANANA
18314813712511399NA
276230210196177163NA
384320296274258240192
529441410388366344295
878730694656625596540
1,3701,1401,0801,0501,000960890
50 02510152030
NANANANANANANA
12095NANANANANA
210171159146NANANA
310260234221200185NA
443370342318292276222
590492474456407384330
980820780730705670605
1,5501,2901,2301,1901,1301,0801,010
For SI units, 1 in. = 25.4 mm, 1 ft. = 0.305 m, 1,000 Btu/hr = 0.293 kW, 1 in.2 = 645 mm2.
108 2010 CALIFORNIA PLUMBING CODE
WATER HEATERS
TABLE 5-13EXTERIOR MASONRY CHIMNEY [NFPA 54: TABLE 13.1(f)]
NUMBER OF APPLIANCES: SINGLE
APPLIANCETYPE: NAT
APPLIANCEVENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR
INTENDED USE: MINIMUM ALLOWABLE INPUT RATING OF SPACE-HEATING APPLIANCE INTHOUSANDS OF BTU PER HOUR
VENT HEIGHTH(ft)
INTERNAL AREA OF CHIMNEY (inch2)
12 19 28 38 50 63 78 113
681015203050
Local 99% winter design temperature: 37°F or greater000
NANANANA
0000
NANANA
0000
123NANA
0000
190NANA
0000
249NANA
0000
184393NA
00000
334NA
000000
579
681015203050
Local 99% winter design temperature: 27°F to 36°F000
NANANANA
0051NANANANA
688297NANANANA
116127141NANANANA
156167183233NANANA
180187201253307419NA
212214225274330445NA
266263265305362485763
681015203050
Local 99% winter design temperature: 17°F to 26°FNANANANANANANA
NANANANANANANA
NANANANANANANA
NANANANANANANA
NA197214NANANANA
215226245296352NANA
259264278331387507NA
349352358398457581NA
681015203050
Local 99% winter design temperature: 5°F to 16°FNANANANANANANA
NANANANANANANA
NANANANANANANA
NANANANANANANA
NANANANANANANA
NANA289NANANANA
NA312331393450NANA
416423430485547682972
681015203050
Local 99% winter design temperature: -10°F to 4°FNANANANANANANA
NANANANANANANA
NANANANANANANA
NANANANANANANA
NANANANANANANA
NANANANANANANA
NANANANANANANA
484494513586650805
1,003
Local 99% winter design temperature: -11°F or lowerNot recommended for any vent configurations
For SI units, 1 in. = 25.4 mm, 1 in.2 = 645 mm2, 1 ft. = 0.305 m, 1,000 Btu per hr = 0.293 kW, °C = (°F – 32)/1.8.Note: See Figure 5-13 for a map showing local 99 percent winter design temperatures in the United States.
1092010 CALIFORNIA PLUMBING CODE
WATER HEATERS
TABLE 5-14TYPE B DOUBLE-WALL VENT [NFPA 54: TABLE 13.2(a)]
NUMBER OF APPLIANCES: TWO OR MORE
APPLIANCETYPE: CATEGORY I
APPLIANCEVENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR
VENT CONNECTOR CAPACITY
VENTHEIGHT
H(ft)
CONNECTORRISE
R(ft)
TYPE B DOUBLE-WALL VENT AND CONNECTOR DIAMETER – D (inch)
3 4 5 6 7
APPLIANCE INPUT RATING LIMITS INTHOUSANDS OF BTU PER HOUR
FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT
Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max
6 123
222324
374144
263135
353738
667581
465562
464849
106121132
728696
586062
164183199
104124139
777982
225253275
142168189
8 123
222324
404447
273236
353637
728087
485764
495153
114128139
7690101
646667
176195210
109129145
848688
243269290
148175198
10 123
222324
434750
283337
343637
788692
505967
495152
123136146
7893104
656769
189206220
113134150
899194
257282303
154182205
15 123
212224
505355
303540
333536
8996102
536371
474951
142153163
8399111
646668
220235248
120142160
889193
298320339
163193218
20 123
212223
545760
313742
333435
99105110
566674
464850
157167176
87104116
626466
246259271
125149168
868991
334354371
171202228
30 123
202122
626466
333944
313334
113118123
597079
454748
181190198
93110124
606264
288299309
134158178
838588
391408423
182215242
50 123
192122
717375
364348
303233
133137141
647686
434546
216223229
101119134
575961
349358366
145172194
788183
477490502
197234263
100 123
181920
828384
374450
283031
158161163
667989
404244
262267272
104123138
535557
442447452
150178200
737578
611619627
204242272
For SI units, 1 in. = 25.4 mm, 1 in.2 = 645 mm2, 1 ft. = 0.305 m, 1000 Btu per hr = 0.293 kW.
COMMONVENT CAPACITY
VENTHEIGHT
H(ft)
TYPE B DOUBLE-WALL COMMONVENT DIAMETER – D (inch)
4 5 6 7
COMBINED APPLIANCE INPUT RATING INTHOUSANDS OF BTU PER HOUR
FAN+FAN
FAN+NAT
NAT+NAT
FAN+FAN
FAN+NAT
NAT+NAT
FAN+FAN
FAN+NAT
NAT+NAT
FAN+FAN
FAN+NAT
NAT+NAT
681015203050100
92101110125136152167175
819097112123138153163
65737991102118134NA
140155169195215244279311
116129141164183210244277
103114124144160185214NA
204224243283314361421489
161178194228255297353421
147163178206229266310NA
309339367427475547641751
248275299352394459547658
200223242280310360423479
110 2010 CALIFORNIA PLUMBING CODE
WATER HEATERS
TABLE 5-14TYPE B DOUBLE-WALL VENT [NFPA 54: TABLE 13.2(a)] (continued)
COMMONVENT CAPACITY
VENT HEIGHTH(ft)
TYPE B DOUBLE-WALL COMMONVENT DIAMETER – D (inch)
8 9 10
COMBINED APPLIANCE INPUT RATING INTHOUSANDS OF BTU PER HOUR
FAN+FAN
FAN+NAT
NAT+NAT
FAN+FAN
FAN+NAT
NAT+NAT
FAN+FAN
FAN+NAT
NAT+NAT
681015203050100
404444477556621720854
1,025
314348377444499585706873
260290315365405470550625
547602649753842979
1,1641,408
434480522612688808977
1,215
335378405465523605705800
672740800924
1,0351,2091,4511,784
520577627733826975
1,1881,502
410465495565640740860975
For SI units, 1 in. = 25.4 mm, 1 in.2 = 645 mm2, 1 ft. = 0.305 m, 1000 Btu per hr = 0.293 kW.
NUMBER OF APPLIANCES: TWO OR MORE
APPLIANCETYPE: CATEGORY I
APPLIANCEVENT CONNECTION: TYPE B DOUBLEWALL CONNECTOR
VENT CONNECTOR CAPACITY
VENTHEIGHT
H(ft)
CONNECTORRISE
R(ft)
TYPE B DOUBLE-WALL VENT AND CONNECTOR DIAMETER – D (inch)
8 9 10
APPLIANCE INPUT RATING LIMITS INTHOUSANDS OF BTU PER HOUR
FAN NAT FAN NAT FAN NAT
Min Max Max Min Max Max Min Max Max
6 123
929597
296333363
185220248
109112114
376424463
237282317
128131134
466526575
289345386
8 123
100103105
320356384
194230258
118121123
408454492
248294330
138141143
507564612
303358402
10 123
106109111
341374402
200238268
125128131
436479515
257305342
146149152
542596642
314372417
15 123
110112115
389419445
214253286
134137140
493532565
273323365
162165167
609658700
333394444
20 123
107110113
436463486
224265300
131134137
552587618
285339383
158161164
681725764
347414466
30 123
103105108
512535555
238282317
125129132
649679706
305360405
151155158
802840874
372439494
50 123
97100103
627645661
257306343
120123126
797820842
330392441
144148151
9841,0141,043
403478538
100 123
919497
810822834
266316355
112115118
1,0381,0541,069
341405455
135139142
1,2851,3061,327
417494555
1112010 CALIFORNIA PLUMBING CODE
WATER HEATERS
TABLE 5-14TYPE B DOUBLE-WALL VENT [NFPA 54: TABLE 13.2(a)] (continued)
NUMBER OF APPLIANCES: TWO OR MORE
APPLIANCETYPE: CATEGORY I
APPLIANCEVENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR
VENT CONNECTOR CAPACITY
VENTHEIGHT
H(ft)
CONNECTORRISE
R(ft)
TYPE B DOUBLE-WALL VENT AND CONNECTOR DIAMETER – D (inch)
12 14 16 18
APPLIANCE INPUT RATING LIMITS INTHOUSANDS OF BTU PER HOUR
FAN NAT FAN NAT FAN NAT FAN NAT
Min Max Max Min Max Max Min Max Max Min Max Max
6 246
174180NA
764897NA
496616NA
223230NA
1,0461,231NA
653827NA
281287NA
1,3711,617NA
8531,081NA
346352NA
1,7722,069NA
1,0801,370NA
8 246
186192198
822952
1,050
516644772
238244252
1,1261,3071,445
696884
1,072
298305313
1,4781,7191,902
9101,1501,390
365372380
1,9202,2112,434
1,1501,4601,770
10 246
196201207
870997
1,095
536664792
249256263
1,1951,3711,509
730924
1,118
311318325
1,5701,8041,989
9551,2051,455
379387395
2,0492,3322,556
1,2051,5351,865
15 246
214221228
9671,0851,181
568712856
272279286
1,3341,4991,632
7901,0061,222
336344351
1,7601,9782,157
1,0301,3201,610
408416424
2,3172,5792,796
1,3051,6652,025
20 246
223230237
1,0511,1621,253
596748900
291298307
1,4431,5971,726
8401,0641,288
357365373
1,9112,1162,287
1,0951,3951,695
430438450
2,5332,7782,984
1,3851,7652,145
30 246
216223231
1,2171,3161,400
632792952
286294303
1,6641,8021,920
9101,1601,410
367376384
2,1832,3662,524
1,1901,5101,830
461474485
2,8913,1103,299
1,5401,9202,340
50 246
206213221
1,4791,5611,631
689860
1,031
273281290
2,0232,1392,242
1,0071,2911,575
350359369
2,6592,8142,951
1,3151,6852,055
435447461
3,5483,7303,893
1,6652,1352,605
100 246
192200208
1,9231,9842,035
712888
1,064
254263272
2,6442,7312,811
1,0501,3461,642
326336346
3,4903,6063,714
1,3701,7602,150
402414426
4,7074,8424,968
1,7402,2202,700
For SI units, 1 in. = 25.4 mm, 1 in.2 = 645 mm2, 1 ft. = 0.305 m, 1000 Btu per hr = 0.293 kW.
COMMONVENT CAPACITY
VENTHEIGHT
H(ft)
TYPE B DOUBLE-WALL COMMONVENT DIAMETER – D (inch)
12 14 16 18
COMBINED APPLIANCE INPUT RATING INTHOUSANDS OF BTU PER HOUR
FAN+FAN
FAN+NAT
NAT+NAT
FAN+FAN
FAN+NAT
NAT+NAT
FAN+FAN
FAN+NAT
NAT+NAT
FAN+FAN
FAN+NAT
NAT+NAT
681015203050100
900994
1,0761,2471,4051,6582,0242,569
696773841986
1,1161,3271,6402,131
588652712825916
1,0251,2801,670
1,2841,4231,5421,7942,0062,3732,9113,732
9901,1031,2001,4101,5881,8922,3473,076
815912995
1,1581,2901,5251,8632,450
1,7351,9272,0932,4402,7223,2203,9645,125
1,3361,4911,6251,9102,1472,5583,1834,202
1,0651,1901,3001,5101,6901,9902,4303,200
2,2532,5072,7273,1843,5614,1975,1846,749
1,7321,9362,1132,4842,7983,3264,1495,509
1,3451,5101,6451,9102,1402,5203,0754,050
112 2010 CALIFORNIA PLUMBING CODE
WATER HEATERS
TABLE 5-14TYPE B DOUBLE-WALL VENT [NFPA 54: TABLE 13.2(a)] (continued)
NUMBER OF APPLIANCES: TWO OR MORE
APPLIANCETYPE: CATEGORY I
APPLIANCEVENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR
VENT CONNECTOR CAPACITY
VENTHEIGHT
H(ft)
CONNECTORRISE
R(ft)
TYPE B DOUBLE-WALL VENT AND CONNECTOR DIAMETER – D (inch)
20 22 24
APPLIANCE INPUT RATING LIMITS INTHOUSANDS OF BTU PER HOUR
FAN NAT FAN NAT FAN NAT
Min Max Max Min Max Max Min Max Max
6 246
NANANA
NANANA
NANANA
NANANA
NANANA
NANANA
NANANA
NANANA
NANANA
8 246
NA471478
NA2,7373,018
NA1,8002,180
NA560568
NA3,3193,665
NA2,1802,640
NA662669
NA3,9574,373
NA2,5903,130
10 246
NA486494
NA2,8873,169
NA1,8902,290
NA581589
NA3,5023,849
NA2,2802,760
NA686694
NA4,1754,593
NA2,7103,270
15 246
NA523533
NA3,1973,470
NA2,0602,510
NA624634
NA3,8814,216
NA2,4903,030
NA734743
NA4,6315,035
NA2,9603,600
20 246
NA554567
NA3,4473,708
NA2,1802,650
NA661671
NA4,1904,511
NA2,6303,190
NA772785
NA5,0055,392
NA3,1303,790
30 246
NA619632
NA3,8404,080
NA2,3652,875
NA728741
NA4,8614,976
NA2,8603,480
NA847860
NA5,6065,961
NA3,4104,150
50 246
NA580594
NA4,6014,808
NA2,6333,208
NA709724
NA5,5695,826
NA3,1853,885
NA851867
NA6,6336,943
NA3,7904,620
100 246
NA523539
NA5,9826,143
NA2,7503,350
NA639654
NA7,2547,453
NA3,3304,070
NA769786
NA8,6508,892
NA3,9504,810
COMMONVENT CAPACITY
VENT HEIGHTH(ft)
TYPE B DOUBLE-WALL COMMONVENT DIAMETER – D (inch)
20 22 24
COMBINED APPLIANCE INPUT RATING INTHOUSANDS OF BTU PER HOUR
FAN+FAN
FAN+NAT
NAT+NAT
FAN+FAN
FAN+NAT
NAT+NAT
FAN+FAN
FAN+NAT
NAT+NAT
681015203050100
2,8383,1623,4444,0264,5485,3036,5678,597
2,1802,4392,6653,1333,5524,1935,2406,986
1,6601,8602,0302,3602,6403,1103,8005,000
3,4883,8904,2414,9715,5736,5398,11610,681
2,6772,9983,2783,8624,3525,1576,4588,648
1,9702,2002,4002,7903,1203,6804,5005,920
4,2064,6955,1236,0166,7497,9409,83713,004
3,2263,6163,9574,6705,2616,2477,81310,499
2,3902,6802,9203,4003,8004,4805,4757,200
For SI units, 1 in. = 25.4 mm, 1 in.2 = 645 mm2, 1 ft. = 0.305 m, 1000 Btu per hr = 0.293 kW.
1132010 CALIFORNIA PLUMBING CODE
WATER HEATERS
NUMBER OF APPLIANCES: TWO OR MORE
APPLIANCETYPE: CATEGORY I
APPLIANCEVENT CONNECTION: SINGLE-WALL METAL CONNECTOR
VENT CONNECTOR CAPACITY
VENTHEIGHT
H(ft)
CONNECTORRISE
R(ft)
SINGLE-WALL METALVENT CONNECTOR DIAMETER – D (inch)
3 4 5 6 7
APPLIANCE INPUT RATING LIMITS INTHOUSANDS OF BTU PER HOUR
FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT
Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max
6 123
NANANA
NANANA
263134
NANANA
NANANA
465562
NANA121
NANA131
718595
NA168175
NA182198
102123138
207215222
223251273
140167188
8 123
NANANA
NANANA
273235
NANANA
NANANA
485764
NA125130
NA126138
7589100
NA184191
NA193208
106127144
226234241
240266287
145173197
10 123
NANANA
NANANA
283336
NA8489
NA8591
505967
119124129
121134144
7791102
182189197
186203217
110132148
240248257
253278299
150183203
15 123
NANANA
NANANA
293439
798387
8794100
526270
116121127
138150160
8197109
177185193
214230243
116138157
238246255
291314333
158189215
20 123
495255
565962
303640
788287
97103107
546472
115120125
152163172
84101113
175182190
238252264
120144164
233243252
325346363
165197223
30 123
475154
606264
313742
778185
110115119
576776
112117122
175185193
89106120
169177185
278290300
129152172
226236244
380397412
175208235
50 123
464952
697172
344045
757983
128132136
607282
109114119
207215221
96113123
162170178
336345353
137164186
217226235
460473486
188223252
100 123
454851
798081
344146
717579
150153157
617385
104110114
249255260
98115129
153160168
424428433
140167190
205212222
585593603
192228256
COMMONVENT CAPACITY
VENTHEIGHT
H(ft)
TYPE B DOUBLE-WALL COMMONVENT DIAMETER – D (inch)
4 5 6 7
COMBINED APPLIANCE INPUT RATING INTHOUSANDS OF BTU PER HOUR
FAN+FAN
FAN+NAT
NAT+NAT
FAN+FAN
FAN+NAT
NAT+NAT
FAN+FAN
FAN+NAT
NAT+NAT
FAN+FAN
FAN+NAT
NAT+NAT
681015203050100
NANANA121131145159166
788794108118132145153
6471768898113128NA
NANA163189208236268297
113126137159177202233263
99111120140156180208NA
200218237275305350406469
158173189221247286337398
144159174200223257296NA
304331357416463533622726
244269292343383446529633
196218236274302349410464
TABLE 5-15TYPE B DOUBLE-WALL VENT [NFPA 54:TABLE 13.2(b)]
For SI units, 1 in. = 25.4 mm, 1 in.2 = 645 mm2, 1 ft. = 0.305 m, 1000 Btu per hr = 0.293 kW.
114 2010 CALIFORNIA PLUMBING CODE
WATER HEATERS
NUMBER OF APPLIANCES: TWO OR MORE
APPLIANCETYPE: CATEGORY I
APPLIANCEVENT CONNECTION: SINGLE-WALL METAL CONNECTOR
VENT CONNECTOR CAPACITY
VENTHEIGHT
H(ft)
CONNECTORRISE
R(ft)
SINGLE-WALL METALVENT CONNECTOR DIAMETER – D (inch)
8 9 10
APPLIANCE INPUT RATING LIMITS INTHOUSANDS OF BTU PER HOUR
FAN NAT FAN NAT FAN NAT
Min Max Max Min Max Max Min Max Max
6 123
262271279
293331361
183219247
325334344
373422462
234281316
447458468
463524574
286344385
8 123
285293302
316353381
191228256
352360370
403450489
244292328
481492501
502560609
299355400
10 123
302311320
335369398
196235265
372381391
429473511
252302339
506517528
534589637
308368413
15 123
312321331
380411438
208248281
397407418
482522557
266317360
556568579
596646690
324387437
20 123
306317326
425453476
217259294
390400412
538574607
276331375
546558570
664709750
336403457
30 123
296307316
497521542
230274309
378389400
630662690
294349394
528541555
779819855
358425482
50 123
284294304
604623640
245293331
364376387
768793816
314375423
507520535
951983
1,013
384458518
100 123
269279289
774788801
249299339
345358368
9931,0111,027
321383431
476490506
1,2361,2591,280
393469527
COMMONVENT CAPACITY
VENTHEIGHT
H(ft)
TYPE B DOUBLE-WALL COMMONVENT DIAMETER – D (inch)
8 9 10
COMBINED APPLIANCE INPUT RATING INTHOUSANDS OF BTU PER HOUR
FAN+FAN
FAN+NAT
NAT+NAT
FAN+FAN
FAN+NAT
NAT+NAT
FAN+FAN
FAN+NAT
NAT+NAT
681015203050100
398436467544606703833999
310342369434487570686846
257285309357395459535606
541592638738824958
1,1391,378
429473512599673790954
1,185
332373398456512593689780
665730787905
1,0131,1831,4181,741
515569617718808952
1,1571,459
407460487553626723838948
TABLE 5-15TYPE B DOUBLE-WALL VENT [NFPA 54: TABLE 13.2(b)] (continued)
For SI units, 1 in. = 25.4 mm, 1 in.2 = 645 mm2, 1 ft. = 0.305 m, 1000 Btu per hr = 0.293 kW.
1152010 CALIFORNIA PLUMBING CODE
WATER HEATERS
NUMBER OF APPLIANCES: TWO OR MORE
APPLIANCETYPE: CATEGORY I
APPLIANCEVENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR
VENT CONNECTOR CAPACITY
VENTHEIGHT
H(ft)
CONNECTORRISE
R(ft)
TYPE B DOUBLE-WALL VENT CONNECTOR DIAMETER – D (inch)
3 4 5 6 7
APPLIANCE INPUT RATING LIMITS INTHOUSANDS OF BTU PER HOUR
FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT
Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max
6 123
242627
334349
212834
394142
627992
405261
525355
106133155
678597
656769
194230262
101124143
878991
274324369
141173203
8 123
242627
394752
222934
394042
728797
415362
555759
117140159
698698
717375
213246269
105127145
949799
304350383
148179206
10 123
242627
425055
222935
384041
8093105
425463
555758
130153170
7187100
747678
232261284
108129148
101103106
324366397
153184209
15 123
242526
485559
233135
383941
93105115
445564
545657
154174189
7489102
727476
277299319
114134153
100103105
384419448
164192215
20 123
242526
525863
243135
373940
102114123
465665
535557
172190204
7791104
717375
313335353
119138157
98101104
437467493
173199222
30 123
242526
546064
253236
373840
111122131
485866
525456
192208221
8295107
697274
357376392
127145163
9699101
504531554
187209233
50 123
232426
515964
253236
363739
116127135
516169
515355
209225237
89102115
677072
405421435
143161180
929598
582604624
213235260
100 123
232425
465359
243135
353738
108120130
506068
495153
208224237
92105118
656769
428444458
155174193
889294
640660679
237260285
COMMONVENT CAPACITY
VENTHEIGHT
H(ft)
MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (inch2)
12 19 28 38 50
COMBINED APPLIANCE INPUT RATING INTHOUSANDS OF BTU PER HOUR
FAN+FAN
FAN+NAT
NAT+NAT
FAN+FAN
FAN+NAT
NAT+NAT
FAN+FAN
FAN+NAT
NAT+NAT
FAN+FAN
FAN+NAT
NAT+NAT
FAN+FAN
FAN+NAT
NAT+NAT
681015203050100
NANANANANANANANA
748084NANANANANA
2528313641NANANA
NANANANANANANANA
119130138152NANANANA
4653566775NANANA
NANANANANANANANA
178193207233250270NANA
718290106122137NANA
NANANANANANANANA
257279299334368404NANA
103119131152172198NANA
NANANA523565615NANA
351384409467508564620NA
143163177212243278328348
TABLE 5-16MASONRY CHIMNEY [NFPA 54: TABLE 13.2(c)]
For SI units, 1 in. = 25.4 mm, 1 in.2 = 645 mm2, 1 ft. = 0.305 m, 1000 Btu per hr = 0.293 kW.
116 2010 CALIFORNIA PLUMBING CODE
WATER HEATERS
NUMBER OF APPLIANCES: TWO OR MORE
APPLIANCETYPE: CATEGORY I
APPLIANCEVENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR
VENT CONNECTOR CAPACITY
VENTHEIGHT
H(ft)
CONNECTORRISE
R(ft)
TYPE B DOUBLE-WALL VENT CONNECTOR DIAMETER – D (inch)
8 9 10
APPLIANCE INPUT RATING LIMITS INTHOUSANDS OF BTU PER HOUR
FAN NAT FAN NAT FAN NAT
Min Max Max Min Max Max Min Max Max
6 123
104107109
370436491
201232270
124127129
479562633
253300349
145148151
599694795
319378439
8 123
113116119
414473517
210240276
134137139
539615672
267311358
156160163
682776848
335394452
10 123
120123126
444498540
216247281
142145147
582652705
277321366
165168171
739825893
348407463
15 123
125128131
511558597
229260292
153156159
658718760
297339382
184187190
824900960
375432486
20 123
123126129
584625661
239270301
150153156
752805851
312354396
180184187
9431,0111,067
397452505
30 123
119122125
680715746
255287317
145149152
883928968
337378418
175179182
1,1151,1711,220
432484535
50 123
115118121
798827854
294326357
140143147
1,0491,0851,118
392433474
168172176
1,3341,3791,421
506558611
100 123
109113116
907933956
334368399
134138141
1,2221,2531,282
454497540
161165169
1,5891,6261,661
596651705
COMMONVENT CAPACITY
VENTHEIGHT
H(ft)
MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (inch2)
63 78 113
COMBINED APPLIANCE INPUT RATING INTHOUSANDS OF BTU PER HOUR
FAN+FAN
FAN+NAT
NAT+NAT
FAN+FAN
FAN+NAT
NAT+NAT
FAN+FAN
FAN+NAT
NAT+NAT
681015203050100
NANA606682742816879NA
458501538611668747831NA
188218236283325381461499
NA724776874955
1,0621,165NA
582636686781858969
1,089NA
246278302365419496606669
1,0411,1441,2261,3741,5131,7021,9052,053
853937
1,0101,1561,2861,4731,6921,921
NA408454546648749922
1,058
TABLE 5-16MASONRY CHIMNEY [NFPA 54: TABLE 13.2(c)] (continued)
For SI units, 1 in. = 25.4 mm, 1 in.2 = 645 mm2, 1 ft. = 0.305 m, 1000 Btu per hr = 0.293 kW.
1172010 CALIFORNIA PLUMBING CODE
WATER HEATERS
NUMBER OF APPLIANCES: TWO OR MORE
APPLIANCETYPE: CATEGORY I
APPLIANCEVENT CONNECTION: SINGLE-WALL METAL CONNECTOR
VENT CONNECTOR CAPACITY
VENTHEIGHT
H(ft)
CONNECTORRISE
R(ft)
SINGLE-WALL METALVENT CONNECTOR DIAMETER – D (inch)
3 4 5 6 7
APPLIANCE INPUT RATING LIMITS INTHOUSANDS OF BTU PER HOUR
FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT
Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max
6 123
NANANA
NANANA
212834
NANANA
NANANA
395261
NANA134
NANA153
668497
179186193
191227258
100123142
231239247
271321365
140172202
8 123
NANANA
NANANA
212834
NANANA
NANANA
405262
NA137143
NA139156
688598
195202210
208240264
103125145
250258266
298343376
146177205
10 123
NANANA
NANANA
222934
NANA97
NANA102
415362
130136143
151150166
708699
202210217
225255277
106128147
267276284
316358389
151181207
15 123
NANANA
NANANA
233034
NA9296
NA103112
435463
129135141
151170185
7388101
199207215
271295315
112132151
268277286
376411439
161189213
20 123
NANANA
NANANA
233035
879196
99111119
455564
128134140
167185199
7690103
197205213
303325343
117136154
265274282
425455481
169195219
30 123
NANANA
NANANA
243135
869195
108119127
475765
126132138
187203216
8093105
193201209
347366381
124142160
259269277
492518540
183205229
50 123
NANANA
NANANA
243135
858994
113123131
506068
124130136
204218231
87100112
188196205
392408422
139158176
252262271
567588607
208230255
100 123
NANANA
NANANA
233034
848893
104115124
495967
122127133
200215228
89102115
182190199
410425438
151169188
243253262
617636654
232254279
COMMONVENT CAPACITY
VENTHEIGHT
H(ft)
MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (inch2)
12 19 28 38 50
COMBINED APPLIANCE INPUT RATING INTHOUSANDS OF BTU PER HOUR
FAN+FAN
FAN+NAT
NAT+NAT
FAN+FAN
FAN+NAT
NAT+NAT
FAN+FAN
FAN+NAT
NAT+NAT
FAN+FAN
FAN+NAT
NAT+NAT
FAN+FAN
FAN+NAT
NAT+NAT
681015203050100
NANANANANANANANA
NANANANANANANANA
25283136NANANANA
NANANANANANANANA
118128136NANANANANA
4552566674NANANA
NANANANANANANANA
176190205230247NANANA
718189105120135NANA
NANANANANANANANA
255276295335362398NANA
102118129150170195NANA
NANANANANANANANA
348380405400503558612NA
142162175210240275325NA
TABLE 5-17MASONRY CHIMNEY [NFPA 54:TABLE 13.2(d)]
For SI units, 1 in. = 25.4 mm, 1 in.2 = 645 mm2, 1 ft. = 0.305 m, 1000 Btu per hr = 0.293 kW.
118 2010 CALIFORNIA PLUMBING CODE
WATER HEATERS
NUMBER OF APPLIANCES: TWO OR MORE
APPLIANCETYPE: CATEGORY I
APPLIANCEVENT CONNECTION: SINGLE-WALL METAL CONNECTOR
VENT CONNECTOR CAPACITY
VENTHEIGHT
H(ft)
CONNECTORRISE
R(ft)
SINGLE-WALL METALVENT CONNECTOR DIAMETER – D (inch)
8 9 10
APPLIANCE INPUT RATING LIMITS INTHOUSANDS OF BTU PER HOUR
FAN NAT FAN NAT FAN NAT
Min Max Max Min Max Max Min Max Max
6 123
292301309
366432491
200231269
362373381
474557634
252299348
499509519
594696793
316376437
8 123
313323332
407465509
207238274
387397407
530607663
263309356
529540551
672766838
331391450
10 123
333343352
434489530
213244279
410420430
571640694
273317363
558569580
727813880
343403459
15 123
349359368
502548586
225256289
445456466
646706755
291334378
623634646
808884945
366424479
20 123
345355365
569610644
235266298
439450461
734787831
306348391
614627639
921986
1,042
387443496
30 123
338348358
665699729
250282312
430442452
864908946
330372412
600613626
1,0891,1451,193
421473524
50 123
328339349
778806831
287320351
417429440
1,0221,0581,090
383425466
582596610
1,3021,3461,386
492545597
100 123
315326337
875899921
328361392
402415427
1,1811,2101,238
444488529
560575589
1,5371,5701,604
580634687
COMMONVENT CAPACITY
VENTHEIGHT
H(ft)
MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (inch2)
63 78 113
COMBINED APPLIANCE INPUT RATING INTHOUSANDS OF BTU PER HOUR
FAN+FAN
FAN+NAT
NAT+NAT
FAN+FAN
FAN+NAT
NAT+NAT
FAN+FAN
FAN+NAT
NAT+NAT
681015203050100
NANANA677765808NANA
455497532602661739821NA
187217234280321377456494
NANA771866947
1,0521,152NA
579633680772849957
1,076NA
245277300360415490600663
NA1,1361,2161,3591,4951,6821,8792,006
846928
1,0001,1391,2641,4471,6721,885
NA405450540640740910
1,046For SI units, 1 in. = 25.4 mm, 1 in.2 = 645 mm2, 1 ft. = 0.305 m, 1000 Btu per hr = 0.293 kW.
TABLE 5-17MASONRY CHIMNEY [NFPA 54: TABLE 13.2(d)] (continued)
1192010 CALIFORNIA PLUMBING CODE
WATER HEATERS
TABLE 5-18SINGLE-WALL METAL PIPE ORTYPE B ASBESTOS CEMENTVENT [NFPA 54: TABLE 13.2(e)]
NUMBER OF APPLIANCES: TWO OR MORE
APPLIANCETYPE: DRAFT HOOD-EQUIPMENT
APPLIANCEVENT CONNECTION: DIRECTTO PIPE ORVENT
VENT CONNECTOR CAPACITY
TOTALVENTHEIGHT
H(ft)
CONNECTORRISE
R(ft)
VENT CONNECTOR DIAMETER – D (inch)
3 4 5 6 7 8
APPLIANCE INPUT RATING INTHOUSANDS OF BTU PER HOUR
6-8 123
212834
405361
688698
102124147
146178204
205235275
15 123
233035
445664
7792102
117134155
179194216
240265298
30and up
123
253136
495868
8497107
129145164
190211232
270295321
COMMONVENT CAPACITY
TOTALVENTHEIGHT
H(ft)
COMMONVENT DIAMETER – D (inch)
4 5 6 7 8 10 12
COMBINED APPLIANCE INPUT RATING INTHOUSANDS OF BTU PER HOUR
681015203050
4855597180NANA
788995115129147NA
111128136168186215NA
155175190228260300360
205234250305340400490
320365395480550650810
NA505560690790940
1,190For SI units, 1 in. = 25.4 mm, 1 in.2 = 645 mm2, 1 ft. = 0.305 m, 1000 Btu per hr = 0.293 kW.
NUMBER OF APPLIANCES: TWO OR MORE
APPLIANCETYPE: NAT + NAT
APPLIANCEVENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR
INTENDED USE: COMBINED APPLIANCE MAXIMUM INPUT RATING INTHOUSANDS OF BTU PER HOUR
VENT HEIGHTH(ft)
INTERNAL AREA OF CHIMNEY (inch2)
12 19 28 38 50 63 78 113
681015203050100
252831NANANANANA
46535667NANANANA
718290106NANANANA
103119131152NANANANA
143163177212NANANANA
188218236283325NANANA
246278302365419496NANA
NA408454546648749922NA
TABLE 5-19EXTERIOR MASONRY CHIMNEY [NFPA 54:TABLE 13.2(f)]
For SI units, 1 in. = 25.4 mm, 1 in.2 = 645 mm2, 1 ft. = 0.305 m, 1000 Btu per hr = 0.293 kW.
120 2010 CALIFORNIA PLUMBING CODE
WATER HEATERS
NUMBER OF APPLIANCES: TWO OR MORE
APPLIANCETYPE: NAT + NAT
APPLIANCEVENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR
INTENDED USE: MINIMUM ALLOWABLE INPUT RATING OF SPACE-HEATING APPLIANCE INTHOUSANDS OF BTU PER HOUR
VENT HEIGHTH(ft)
INTERNAL AREA OF CHIMNEY (inch2)
12 19 28 38 50 63 78 113
Local 99% winter design temperature: 37°F or greater681015203050100
000NANANANANA
0000NANANANA
0000NANANANA
0000NANANANA
0000NANANANA
0000184393NANA
00000334NANA
NA00000579NA
Local 99% winter design temperature: 27°F to 36°F681015203050100
000NANANANANA
0051NANANANANA
6882NANANANANANA
NANANANANANANANA
NANANANANANANANA
180187210253307NANANA
212214225274330445NANA
NA263265305362485763NA
Local 99% winter design temperature: 17°F to 26°F681015203050100
NANANANANANANANA
NANANANANANANANA
NANANANANANANANA
NANANANANANANANA
NANANANANANANANA
NANANANANANANANA
NA264278331387NANANA
NA352358398457581862NA
Local 99% winter design temperature: 5°F to 16°F681015203050100
NANANANANANANANA
NANANANANANANANA
NANANANANANANANA
NANANANANANANANA
NANANANANANANANA
NANANANANANANANA
NANANANANANANANA
NANA430485547682NANA
Local 99% winter design temperature: 4°F or lowerNot recommended for any vent configurations
TABLE 5-20EXTERIOR MASONRY CHIMNEY [NFPA 54: TABLE 13.2(g)]
For SI units, 1 in. = 25.4 mm, 1 in.2 = 645 mm2, 1 ft. = 0.305 m, 1000 Btu per hr = 0.293 kW, °C = (°F - 32)/1.8.Note: See Figure G.2.4 for a map showing local 99 percent winter design temperatures in the United States.
1212010 CALIFORNIA PLUMBING CODE
WATER HEATERS
NUMBER OF APPLIANCES: TWO OR MORE
APPLIANCETYPE: FAN + NAT
APPLIANCEVENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR
INTENDED USE: COMBINED APPLIANCE MAXIMUM INPUT RATING INTHOUSANDS OF BTU PER HOUR
VENT HEIGHTH(ft)
INTERNAL AREA OF CHIMNEY (inch2)
12 19 28 38 50 63 78 113
681015203050100
748084NANANANANA
119130138152NANANANA
178193207233250NANANA
257279299334368404NANA
351384409467508564NANA
458501538611668747831NA
582636686781858969
1,089NA
853937
1,0101,1561,2861,4731,6921,921
TABLE 5-21EXTERIOR MASONRY CHIMNEY [NFPA 54: TABLE 13.2(h)]
For SI units, 1 in. = 25.4 mm, 1 in.2 = 645 mm2, 1 ft. = 0.305 m, 1000 Btu per hr = 0.293 kW.
122 2010 CALIFORNIA PLUMBING CODE
WATER HEATERS
NUMBER OF APPLIANCES: TWO OR MORE
APPLIANCETYPE: FAN + NAT
APPLIANCEVENT CONNECTION: TYPE B DOUBLE-WALL CONNECTOR
INTENDED USE: MINIMUM ALLOWABLE INPUT RATING OF SPACE-HEATING APPLIANCE INTHOUSANDS OF BTU PER HOUR
VENT HEIGHTH(ft)
INTERNAL AREA OF CHIMNEY (inch2)
12 19 28 38 50 63 78 113
Local 99% winter design temperature: 37°F or greater681015203050100
000NANANANANA
0000NANANANA
0000123NANANA
0000190334NANA
0000249398NANA
0000184393714NA
00000334707NA
0000005791,600
Local 99% winter design temperature: 27°F to 36°F681015203050100
000NANANANANA
0051111NANANANA
688297142187NANANA
116127141183230330NANA
156167183233284319NANA
180187210253307419672NA
212214225274330445705NA
2662632653053624857631,554
Local 99% winter design temperature: 17°F to 26°F681015203050100
052NANANANANANA
557490NANANANANA
99111125167212NANANA
141154169212258362NANA
182197214263316429NANA
215226245296352470723NA
259264278331387507766NA
3493523583984575818621,669
Local 99% winter design temperature: 5°F to 16°F681015203050100
NANANANANANANANA
7894111NANANANANA
121135149193NANANANA
166182198247293377NANA
214230250305360450NANA
252269289346408531797NA
301312331393450580853NA
4164234304855476829721,833
Local 99% winter design temperature: -10°F to 4°F681015203050100
NANANANANANANANA
NANANANANANANANA
145159175NANANANANA
196213231283333NANANA
249269292351408NANANA
296320339404468603NANA
349371397457528667955NA
4844945135866508051,003NA
Local 99% winter design temperature: -11°F or lowerNot recommended for any vent configurations
TABLE 5-22EXTERIOR MASONRY CHIMNEY [NFPA 54: TABLE 13.2(i)]
For SI units, 1 in. = 25.4 mm, 1 in.2 = 645 mm2, 1 ft. = 0.305 m, 1000 Btu per hr = 0.293 kW.Note: See Figure 5-13 for a map showing local 99 percent winter design temperatures in the United States.
PART II
This is originally from NFPA 54, which contains additionalreferences from the UPC.
Sizing of Venting Systems ServingAppliances Equipped withDraft Hoods, Category I Appliances, and Appliances Listedfor Use with Type B Vents
1232010 CALIFORNIA PLUMBING CODE
WATER HEATERS
G.1 Examples Using Single Appliance Venting Tables.See Figure G.1(a) through Figure G.1(n).
FIGURE G.1(a)TYPE B DOUBLE-WALLVENT SYSTEM SERVINGA SINGLE APPLIANCEWITH ATYPE B DOUBLE-WALLVENT.
FIGURE G.1(c) VENT SYSTEM SERVING A SINGLE APPLIANCEWITH A MASONRY CHIMNEY AND ATYPE B DOUBLE-WALL
VENT CONNECTOR.
FIGURE G.1(b) TYPE B DOUBLE-WALL VENT SYSTEMSERVING A SINGLE APPLIANCEWITH A SINGLE-WALL
METALVENT CONNECTOR.
FIGURE G.1(d) VENT SYSTEM SERVING A SINGLE APPLIANCEUSING A MASONRY CHIMNEY AND A SINGLE-WALL METAL
VENT CONNECTOR.
124 2010 CALIFORNIA PLUMBING CODE
WATER HEATERS
FIGURE G.1(e) ASBESTOS CEMENTTYPE B OR SINGLE-WALLMETALVENT SYSTEM SERVING A SINGLE DRAFT-HOOD-
EQUIPPED APPLIANCE
FIGURE G.1(g) VENT SYSTEM SERVINGTWO OR MOREAPPLIANCESWITHTYPE B DOUBLE-WALL VENT AND
SINGLE-WALL METALVENT CONNECTORS.
FIGURE G.1(f) VENT SYSTEM SERVINGTWO OR MOREAPPLIANCESWITHTYPE B DOUBLE-WALL VENT ANDTYPE B
DOUBLE-WALL VENT CONNECTORS
FIGURE G.1(h) MASONRY CHIMNEY SERVING TWO ORMORE APPLIANCESWITH TYPE B DOUBLE-WALL VENT
CONNECTORS.
1252010 CALIFORNIA PLUMBING CODE
WATER HEATERS
FIGURE G.1(i) MASONRY CHIMNEY SERVINGTWO OR MOREAPPLIANCESWITH SINGLE-WALL VENT CONNECTORS.
FIGURE G.1(k) USE OF MANIFOLDED COMMONVENT CONNECTOR.
FIGURE G.1(j) ASBESTOS CEMENTTYPE B OR SINGLE-WALLMETALVENT SYSTEM SERVINGTWO OR MORE DRAFT-
HOOD-EQUIPPED APPLIANCES.
FIGURE G.1(l) USE OF OFFSET COMMONVENT.
G.1.1 Example 1: Single Draft-Hood-Equipped Appli-ance. An installer has a 120,000-Btu/h input appliance witha five (5) inch diameter draft hood outlet that needs to bevented into a ten (10) foot high Type B vent system. Whatsize vent should be used assuming (1) a five (5) foot lateralsingle-wall metal vent connector is used with two (2) 90 de-gree elbows or (2) a five (5) foot lateral single-wall metal ventconnector is used with three (3) 90 degree elbows in the ventsystem? (See Figure G.1.1).
SolutionTable 5-9 should be used to solve this problem because sin-gle-wall metal vent connectors are being used with a Type Bvent, as follows:(1) Read down the first column in Table 5-9 until the row
associated with a ten (10) foot height and five (5) footlateral is found. Read across this row until a vent capac-ity exceeding 120,000 Btu/h is located in the shadedcolumns labeled NAT Max for draft-hood-equipped ap-pliances. In this case, a five (5) inch diameter vent has acapacity of 122,000 Btu/h and can be used for this ap-plication.
(2) If three (3) 90 degree elbows are used in the vent system,the maximum vent capacity listed in the tables must bereduced by 10 percent (See NFPA 54:13.1.3). This im-plies that the five (5) inch diameter vent has an adjustedcapacity of only 110,000 Btu/h. In this case, the vent sys-tem must be increased to six (6) inches in diameter. Seethe following calculations:
122,000 x 0.90 = 110,000 for five (5) inch ventFrom Table 5-10, select six (6) inch vent.186,000 x 0.90 = 167,000
This figure is exceeding the required 120,000.Therefore, use a six (6) inch vent and connector wherethree (3) elbows are used.
G.1.2. Example 2: Single Fan-Assisted Appliance. An in-staller has an 80,000 Btu/h input fan-assisted appliance thatmust be installed using ten (10) feet of lateral connector at-tached to a thirty (30) foot high Type B vent. Two (2) 90 de-gree elbows are needed for the installation. Can a single-wallmetal vent connector be used for this application? See FigureG.1.2.
SolutionTable 5-9 refers to the use of single-wall metal vent connec-tors with Type B vent. In the first column find the row associ-ated with a thirty (30) foot height and a ten (10) foot lateral.Read across this row, looking at the FAN Min and FAN Maxcolumns, to find that a three (3) inch diameter single-wall metalvent connector is not recommended. Moving to the next larger
126 2010 CALIFORNIA PLUMBING CODE
WATER HEATERS
FIGURE G.1(m) MULTISTORY GASVENT DESIGN PROCEDUREFOR EACH SEGMENT OF SYSTEM
FIGURE G.1(n) PRINCIPLES OF DESIGN OF MULTISTORYVENTS USINGVENT CONNECTOR AND COMMONVENT
DESIGNTABLES.
size single-wall connector (four (4) inch), we find that a four (4)inch diameter single-wall metal connector has a recommendedmaximum vent capacity of 144,000 Btu/h. The 80,000 Btu/hfan-assisted appliance is outside this range, so the conclusionis that a single-wall metal connector could be used to vent theappliance. Table 5-9 shows the acceptable range of vent ca-pacities for a four (4) inch vent with five (5) feet of lateral tobe between 72,000 Btu/h and 157,000 Btu/h.
If the appliance cannot be moved closer to the verticalvent, then a Type B vent could be used as the connector ma-terial. In this case, Table 5-8 shows that, for a thirty (30) foothigh vent with ten (10) feet of lateral, the acceptable range ofvent capacities for a four (4) inch diameter vent attached to afan-assisted appliance is between 37,000 Btu/h and 150,000Btu/h.
G.1.3. Example 3: Interpolating Between Table Values.Aninstaller has an 80,000 Btu/h input appliance with a four (4)inch diameter draft hood outlet that needs to be vented into atwelve (12) foot high Type B vent. The vent connector has a5-foot lateral length and is also Type B vent. Can this appli-ance be vented using a four (4) inch diameter vent?
SolutionTable 5-8 is used in the case of an all Type B Vent system.However, since there is no entry in Table 5-8 for a height oftwelve (12) feet, interpolation must be used. Read down thefour (4) inch diameter NATMax column to the row associatedwith a ten (10) foot height and five (5) foot lateral to find thecapacity value of 77,000 Btu/h. Read further down to the fif-teen (15) foot height, five (5) foot lateral row to find the ca-pacity value of 87,000 Btu/h. The difference between thefifteen (15) foot height capacity value and the ten (10) footheight capacity value is 10,000 Btu/h. The capacity for a ventsystem with a twelve (12) foot height is equal to the capacityfor a ten (10) foot height plus two-fifths (2⁄5) of the differencebetween the ten (10) foot and fifteen (15) foot height values,or 77,000 + 2⁄5 x 10,000 = 81,000 Btu/h. Therefore, a four (4)inch diameter vent can be used in the installation.
G.2 Examples Using Common Venting Tables.G.2.1 Example 4: Common Venting Two Draft-Hood-Equipped Appliances.A 35,000-Btu/h water heater is to becommon vented with a 150,000 Btu/h furnace, using a com-mon vent with a total height of thirty (30) feet. The connec-tor rise is two (2) feet for the water heater with a horizontallength of four (4) feet. The connector rise for the furnace isthree (3) feet with a horizontal length of eight (8) feet.Assumesingle-wall metal connectors will be used with Type B vent.What size connectors and combined vent should be used inthis installation?See Figure G.2.1.
1272010 CALIFORNIA PLUMBING CODE
WATER HEATERS
FIGURE G.1.1 SINGLE DRAFT HOOD-EQUIPPED APPLIANCE– EXAMPLE 1
FIGURE G.1.2 SINGLE FAN-ASSISTED APPLIANCE – EXAMPLE 2
FIGURE G.2.1 COMMONVENTINGTWODRAFT HOOD-EQUIPPEDAPPLIANCES – EXAMPLE 4
SolutionTable 5-15 should be used to size single-wall metal vent
connectors attached to Type B vertical vents. In the vent con-nector capacity portion of Table 5-15, find the row associatedwith a thirty (30) foot vent height. For a two (2) foot rise onthe vent connector for the water heater, read the shadedcolumns for draft-hood-equipped appliances to find that athree (3) inch diameter vent connector has a capacity of37,000 Btu/h. Therefore, a three (3) inch single-wall metalvent connector can be used with the water heater. For a draft-hood-equipped furnace with a three (3) foot rise, read acrossthe appropriate row to find that a five (5) inch diameter ventconnector has a maximum capacity of 120,000 Btu/h (whichis too small for the furnace), and a six (6) inch diameter ventconnector has a maximum vent capacity of 172,000 Btu/h.Therefore, a six (6) inch diameter vent connector should beused with the 150,000 Btu/h furnace. Since both vent con-nector horizontal lengths are less than the maximum lengthslisted in Table 5-8, the table values can be used without ad-justments.
In the common vent capacity portion of Table 5-15, findthe row associated with a thirty (30) foot vent height and readover to the NAT + NAT portion of the six (6) inch diametercolumn to find a maximum combined capacity of 257,000Btu/h. Since the two (2) appliances total only 185,000 Btu/h,a six (6) inch common vent can be used.
G.2.2 Example 5(a): Common Venting a Draft-Hood-EquippedWater Heater with a Fan-Assisted Furnace intoa Type B Vent. In this case, a 35,000-Btu/h input draft-hood-equipped water heater with a four (4) inch diameter draft hoodoutlet, two (2) feet of connector rise, and four (4) feet of hor-izontal length is to be common vented with a 100,000 Btu/hfan-assisted furnace with a four (4) inch diameter flue collar,three (3) feet of connector rise, and six (6) feet of horizontallength. The common vent consists of a thirty (30) foot heightof Type B vent.What are the recommended vent diameters foreach connector and the common vent? The installer would liketo use a single-wall metal vent connector. See Figure G.2.2.
Solution (See Table 5-15)Water Heater Vent Connector Diameter. Since the water
heater vent connector horizontal length of four (4) feet is lessthan the maximum value listed in Table 5-15, the ventingtable values can be used without adjustment. Using the VentConnector Capacity portion of Table 5-15, read down theTotal Vent Height (H) column to thirty (30) feet and readacross the two (2) feet Connector Rise (R) row to the firstBtu/h rating in the NAT Max column that is equal to or ex-ceeding the water heater input rating. The table shows that athree (3) inch vent connector has a maximum input rating of37,000 Btu/h. Although this rating is exceeding the waterheater input rating, a three (3) inch vent connector is prohib-ited by Section 511.1.1(5). A four (4) inch vent connector hasa maximum input rating of 67,000 Btu/h and is equal to thedraft hood outlet diameter. A four (4) inch vent connector is
128 2010 CALIFORNIA PLUMBING CODE
WATER HEATERS
NOMINALLINER SIZE(inch)
INSIDE DIMEN-SIONS OFLINER(inch)
INSIDE DIAMETER OREQUIVALENT DIAME-
TER(inch)
EQUIVALENTAREA(inch2)
4 x 8 21⁄2 x 61⁄2 4.0 12.25.0 19.66.0 28.37.0 38.3
8 x 8 63⁄4 x 63⁄4 7.4 42.78.0 50.3
8 x 12 61⁄2 x 101⁄2 9.0 63.610.0 78.5
12 x 12 93⁄4 x 93⁄4 10.4 83.311.0 95.0
12 x 16 91⁄2 x 131⁄2 11.8 107.512.0 113.014.0 153.9
16 x 16 131⁄4 x 131⁄4 14.5 162.915.0 176.7
16 x 20 13 x 17 16.2 206.118.0 254.4
20 x 20 163⁄4 x 163⁄4 18.2 260.220.0 314.1
20 x 24 161⁄2 x 201⁄2 20.1 314.222.0 380.1
24 x 24 201⁄4 x 201⁄4 22.1 380.124.0 452.3
24 x 28 201⁄4 x 241⁄4 24.1 456.228 x 28 241⁄4 x 241⁄4 26.4 543.3
27.0 572.530 x 30 251⁄2 x 251⁄2 27.9 607.030 x 36 251⁄2 x 311⁄2 30.9 749.9
33.0 855.336 x 36 311⁄2 x 311⁄2 34.4 929.4
36.0 1017.9
TABLE G.2.3MASONRY CHIMNEY LINER DIMENSIONSWITH CIRCULAR
EQUIVALENTS
For SI units, 1 in. = 25.4 mm, 1 in.2 = 645 mm2.Note:When liner sizes differ dimensionally from those shown in this table,equivalent diameters can be determined from published tables for squareand rectangular ducts of equivalent carrying capacity or by other engi-neering methods.
FIGURE G.2.2 COMMONVENTING A DRAFT HOOD-EQUIPPEDWATER HEATERWITH A FAN-ASSISTED FURNACE INTO ATYPE B DOUBLE-WALL COMMONVENT – EXAMPLE 5(a).
selected. Since the water heater is equipped with a draft hood,there are no minimum input rating restrictions.
Furnace Vent Connector Diameter. Using the Vent Con-nector Capacity portion of Table 5-15, read down the TotalVent Height (H) column to thirty (30) feet and across the three(3) foot Connector Rise (R) row. Since the furnace has a fan-assisted combustion system, find the first FAN Max columnwith a Btu/h rating exceeding the furnace input rating. Thefour (4) inch vent connector has a maximum input rating of119,000 Btu/h and a minimum input rating of 85,000 Btu/h.
The 100,000-Btu/h furnace in this example falls withinthis range, so a four (4) inch connector is adequate. Since thefurnace vent connector horizontal length of six (6) feet is lessthan the maximum value listed in Table 5-8, the venting tablevalues can be used without adjustment. If the furnace had aninput rating of 80,000 Btu/h, then a Type B vent connectorwould be needed in order to meet the minimum capacity limit(See Table 5-14).
Common Vent Diameter. The total input to the commonvent is 135,000 Btu/h. Using the CommonVent Capacity por-tion of Table 5-15, read down the Vent Height (H) column tothirty (30) feet and across this row to find the smallest vent di-ameter in the FAN + NAT column that has a Btu/h ratingequal to or exceeding 135,000 Btu/h. The four (4) inch com-mon vent has a capacity of 132,000 Btu/h and the five (5)inch common vent has a capacity of 202,000 Btu/h. There-fore, the five (5) inch common vent should be used in this ex-ample.Summary: In this example, the installer can use a four (4) inchdiameter, single-wall metal vent connector for the waterheater and a four (4) inch diameter, single-wall metal ventconnector for the furnace. The common vent should be a five(5) inch diameter Type B vent.
G.2.3 Example 5(b): Common Venting into an Interior Ma-sonry Chimney. In this case, the water heater and fan-assistedfurnace of Example 5(a) are to be common-vented into a clay-tile-lined masonry chimney with a thirty (30) foot height. Thechimney is not exposed to the outdoors below the roof line.The internal dimensions of the clay tile liner are nominallyeight (8) inches x twelve (12) inches.Assuming the same ventconnector heights, laterals, and materials found in example5(a), what are the recommended vent connector diameters,and is this an acceptable installation?
SolutionTable 5-17 is used to size common venting installations in-volving single-wall connectors into masonry chimneys.
Water Heater Vent Connector Diameter. Using Table 5-17, Vent Connector Capacity, read down the Vent Height (H)column to thirty (30) feet, and read across the two (2) footConnector Rise (R) row to the first Btu/h rating in the NATMax column that is equal to or exceeding the water heaterinput rating. The table shows that a three (3) inch vent con-
nector has a maximum input of only 31,000 Btu/h, while afour (4) inch vent connector has a maximum input of 57,000Btu/h. A four (4) inch vent connector must therefore be used.
Furnace Vent Connector Diameter. Using the Vent Con-nector Capacity portion of Table 5-17, read down the totalVent Height (H) column to thirty (30) feet and across the three(3) feet Connector Rise (R) row. Because the furnace has afan-assisted combustion system, find the first FAN Max col-umn with a Btu/h rating exceeding the furnace input rating.The four (4) inch vent connector has a maximum input ratingof 127,000 Btu/h and a minimum input rating of 95,000Btu/h. The 100,000 Btu/h furnace in this example falls withinthis range, so a four (4) inch connector is adequate.
Masonry Chimney. From Table G.2.3, the equivalent areafor a nominal liner size of eight (8) inches x twelve (12)inches is sixty-three and six-tenths (63.6) of a square inch.Using Table 5-17, Common Vent Capacity, read down theFAN + NAT column under the Minimum Internal Area ofChimney value of sixty-three (63) to the row for thirty (30)foot height to find a capacity value of 739,000 Btu/h. Thecombined input rating of the furnace and water heater,135,000 Btu/h, is less than the table value so this is an ac-ceptable installation.Section 511.1.8 requires the common vent area to not exceedseven (7) times the smallest listed appliance categorized ventarea, flue collar area, or draft hood outlet area. Both appli-ances in this installation have four (4) inch diameter outlets.From Table G.2.3, the equivalent area for an inside diameterof four (4) inches is twelve and two-tenths (12.2) of a squareinch. Seven (7) times twelve and two-tenths (12.2) equalseighty-five and four-tenths (85.4), which is exceeding sixty-three and six-tenths (63.6), so this configuration is accept-able.G.2.4 Example 5(c): Common Venting into an ExteriorMasonry Chimney. In this case, the water heater and fan-as-sisted furnace of Examples 5(a) and 5(b) are to be common-vented into an exterior masonry chimney. The chimneyheight, clay-tile-liner dimensions, and vent connector heightsand laterals are the same as in Example 5(b). This system isbeing installed in Charlotte, North Carolina. Does this exte-rior masonry chimney need to be relined? If so, what corru-gated metallic liner size is recommended? What ventconnector diameters are recommended? See Table G.2.3 andFigure 5-14.
SolutionAccording to 511.2.17, Type B vent connectors are re-
quired to be used with exterior masonry chimneys. Use Table5-21 and Table 5-22 to size FAN+NAT common venting in-stallations involving Type-B double-wall connectors into ex-terior masonry chimneys.
The local 99 percent winter design temperature needed touse Table 5-21 and Table 5-22 can be found in the ASHRAEHandbook – Fundamentals. For Charlotte, North carolina,this design temperature is 19°F (-7.22°C).
Chimney Liner Requirement.As in Example 5(b), use thesixty-three (63) square inch column of Table 5-21 to the thirty
1292010 CALIFORNIA PLUMBING CODE
WATER HEATERS
(30) foot height row to find that the combined appliance max-imum input is 747,000 Btu/h. The combined input rating ofthe appliance in this installation, 135,000 Btu/h, is less thanthe maximum value, so this criterion is satisfied. Table 5-22,at a 19°F (-7.22°C) design temperature, and at the same ventheight and internal area used earlier, shows that the minimumallowable input rating of a space-heating appliance is 470,000Btu/h. The furnace input rating of 100,000 Btu/h is less thanthis minimum value. So this criterion is not satisfied, and analternative venting design needs to be used, such as a Type Bvent shown in Example 5(a) or a listed chimney liner systemshown in the rest of the example.
According to Section 511.2.19, Table 5-9 or Tables 5-14or 5-15 are used for sizing corrugated metallic liners in ma-sonry chimneys, with the maximum common vent capacitiesreduced by 20 percent. This example will be continued as-suming Type B vent connectors.
Water Heater Vent Connector Diameter. Using Table 5-14 Connector Capacity, read down the total Vent Height (H)column to thirty (30) feet, and read across the two (2) footConnector Rise (R) row to the first Btu/hour rating in the NATMax column that is equal to or exceeding the water heaterinput rating. The table shows that a three (3) inch vent con-nector has a maximum capacity of 39,000 Btu/h. Althoughthis rating is exceeding the water heater input rating, a three(3) inch vent connector is prohibited by Section 511.1.6. Afour (4) inch vent connector has a maximum input rating of70,000 Btu/h and is equal to the draft hood outlet diameter. Afour (4) inch vent connector is selected.
Furnace Vent Connector Diameter. Using Table 5-14,Vent Connector Capacity, read down the total Vent Height (H)column to thirty (30) feet, and read across the three (3) footConnector Rise (R) row to the first Btu/h rating in the FANMAX column that is equal to or exceeding the furnace inputrating. The 100,000 Btu/h furnace in this example falls withinthis range, so a four (4) inch connector is adequate.
Chimney Liner Diameter. The total input to the commonvent is 135,000 Btu/h. Using the CommonVent Capacity por-tion of Table 5-14, read down the total Vent Height (H) col-umn to thirty (30) feet and across this row to find the smallestvent diameter in the FAN + NAT column that has a Btu/h rat-ing exceeding 135,000 Btu/h. The four (4) inch common venthas a capacity of 138,000 Btu/h. Reducing the maximum ca-pacity by 20 percent (See 13.2.19) results in a maximum ca-pacity for a four (4) inch corrugated liner of 110,000 Btu/h,less than the total input of 135,000 Btu/h. So a larger liner isneeded. The five (5) inch common vent capacity listed inTable 5-14 is 210,000 Btu/h, and after reducing by 20 percentis 168,000 Btu/h. Therefore, a five (5) inch corrugated metalliner should be used in this example.
Single Wall Connectors.Once it has been established thatrelining the chimney is necessary, Type B double-wall ventconnectors are not specifically required. This example couldbe redone using Table 5-15 for single-wall vent connectors.For this case, the vent connector and liner diameters would bethe same as found for Type B double-wall connectors.
The following is originally from NFPA54, National Fuel GasCode, which contains additional reference.
Example of Combination of Indoor and Outdoor Com-bustion and Ventilation Opening Design.
J.1 Example of Combination Indoor and Outdoor Com-bustion Air Opening. Determine the required combinationof indoor and outdoor combustion air opening sizes for thefollowing appliance installation example.
Example Installation:Afan-assisted furnace and a draft-hood-equipped water heater with the following inputs are lo-cated in a fifteen (15) foot x thirty (30) foot basement with aneight (8) foot ceiling. No additional indoor spaces can be usedto help meet the appliance combustion air needs.Fan-Assisted Furnace Input: 100,000 Btu/h
Draft-Hood-Equipped Water Heater Input: 40,000 Btu/h
Solution(1) Determine the total available room volume: Equipment
room volume:Fifteen (15) feet x thirty (30) feet with an eight (8) footceiling = thirty-six-hundred (3,600) cubic feet
(2) Determine the total required volume: The standard methodto determine combustion air will be used to calculate therequired volume.The combined input for the appliances located in thebasement is calculated as follows:100,000 Btu/h +40,000 Btu/h = 140,000 Btu/hThe Standard Method requires that the required volumebe determined based on fifty (50) cubic feet per 1,000Btu/hour.Using TableA.9.3.2.1, the required volume for a 140,000Btu/h water heater is seven-thousand (7,000) cubic feet.
Conclusion: Indoor volume is insufficient to supply com-bustion air since the total of thirty-six-hundred (3,600)cubic feet does not meet the required volume of seven-thousand (7,000) cubic feet. Therefore, additional com-bustion air must be provided from the outdoors.
(3) Determine ratio of the available volume to the requiredvolume:
(4) Determine the reduction factor to be used to reduce thefull outdoor air opening size to the minimum required basedon ratio of indoor spaces:
1.00 – 0.51 (from Step 3) = 0.49
130 2010 CALIFORNIA PLUMBING CODE
WATER HEATERS
3,600 ft.3 = 0.517,000 ft.3
(5) Determine the single outdoor combustion air openingsize as if combustion air is to come from outdoors. In thisexample, the combustion air opening directly communi-cates with the outdoors.
(6) Determine the minimum outdoor combustion air open-ing area:
Outdoor opening area = 0.49(from Step 4) x 47 in.2= 23 in.2
Section 507.3 requires the minimum dimension of the airopening shall be not less than three (3) inches.
1312010 CALIFORNIA PLUMBING CODE
WATER HEATERS
APPLIANCE INPUT (Btu/h) REQUIREDVOLUME (ft.3)5000 25010 000 50015 000 75020 000 100025 000 125030 000 150035 000 175040 000 200045 000 225050 000 250055 000 275060 000 300065 000 325070 000 350075 000 375080 000 400085 000 425090 000 450095 000 4750100 000 5000105 000 5250110 000 5500115 000 5750120 000 6000125 000 6250130 000 6500135 000 6750140 000 7000145 000 7250150 000 7500160 000 8000170 000 8500180 000 9000190 000 9500200 000 10 000210 000 10 500220 000 11 000230 000 11 500240 000 12 000250 000 12 500260 000 13 000270 000 13 500280 000 14 000290 000 14 500300 000 15 000
TABLE A.9.3.2.1STANDARD METHODVOLUME, ALL APPLIANCES
507.4.1 See Figure 5-8 • 507.4.1(1) See Figure 5-9 and Figure 5-10 •507.4.1(2) See Figure 5-11 • 507.4.2 See Figure 5-12
140,000 Btu/h = 47 in.23,000 Btu/in.2
132 2010 CALIFORNIA PLUMBING CODE