PRIVATE COMMUNICATION NOT FOR PUBLICATION INDEXED CALIBRATION TESTS OF A490 BOLTS by G. H. STERLING, E. W. J. TROUP, E. CHESSON, JR. and J. W. FISHER AUGUST 1964 Fritz Eflgineering Laboratory Re'port 288.23

Transcript of CALIBRATION TESTS OF A490 HIGH~STRENGTH BOLTS

Page 1: CALIBRATION TESTS OF A490 HIGH~STRENGTH BOLTS

PRIVATE COMMUNICATIONNOT FOR PUBLICATION

INDEXED

CALIBRATION TESTSOF A490 HIGH~STRENGTHBOLTS

by

G. H. STERLING,

E. W. J. TROUP,

E. CHESSON, JR.and

J. W. FISHER

AUGUST 1964

Fritz Eflgineering Laboratory Re'port No~ 288.23

Page 2: CALIBRATION TESTS OF A490 HIGH~STRENGTH BOLTS

CALIBRATION TESTS

OF

A490 HIGH-STRENGTH BelTS

by

Gordon H. SterlingEmile W. J. Troup, A.M. AseE

"Eugene Chesson, Jrq, M. ASCEand

John WO Fisher, Me ASeE

A Report of an Investigation Conducted

by

The Departments of Civil EngineeringLEHIGH UNIVERSITY and the UNIVERSITY OF ILLINOIS

in cooperation with

, The Research Counci 1 on Riveted and Bolted Structural Joints

The American ~nstfttute of Steel Construction

The ~118nois Division of Highways(Project IHR-5)

The Pennsylvania Department of Highways

and

The Department of Commerce ~= Bureau of Public Roads

August 1964

Page 3: CALIBRATION TESTS OF A490 HIGH~STRENGTH BOLTS

=1-

CAL~BRAT~ON TESTS OF A490 H~GH-STRENGTH BOLTS*

by

Gordon H, Ster~ing(l) ~ Em! Ie W. J. uroup(2) A,M. ASCE,

Eugene Chesson 9 Jr, (3) M. ASCE, and

John W. Fisher(4) M. ASCE

SYNOPSijS

Over 100 calibration tests were conducted at Lehigh and Illinois

on 7/8 ino diameter ASTM A49Q hBgh=strength bolts from the same lotso Each

'laboratory staff used the~r own equipment and procedures o Data on bolt

tension, elongat!on, turns of nut D and genera] behavior were analyzed.

Comparison between bolt behavior when torqued in a commercial load cell and

in a solid steel block show a sign!fijcant difference between these two

conditionso The general characteristics of the A490 h~gh~strength bolt are

similar to those of the famij lijar A325 bo~tD but the physical properties of

the new bolt provide greater fastener strength and joint clamping o The

effects of different testing techniq~es and laboratories were inconsequential 0

.,'c This paper combines two unpublished reports: '9Calibration Tests of A490High-Strength Bolts'S by Eo Wo Jo Troup and Eo Chessorl v Jr tJ , University ofIllinois, SRS 280 j March 1964; and InTests of A490 B101ts p

lO by Gordon Ho Ster]ingand John W, Fisher» Lehigh University» Report NOQ 288Q 15, March 19640

1. Research Assistant p Fritz Engineering laboratoryp lehigh University,Bethlehem, Pao

2. Formerly Research Assistant» ijnijversity of ~llinoisD Urbana s ~ 11ino15030 Associate Professor of Civi 1 Engineerin99 University of ~11inois, Urbana,

111 i no i So

4. Research Assistant Professor~ Fritz Engineer~n9 laboratory, lehighUniversity, Bet~lehem, Pao

//

Page 4: CALIBRATION TESTS OF A490 HIGH~STRENGTH BOLTS

-2-

!NTRODUCTI ON

Scope and Purpose:

This investigation was approved by the Research Counci 1 on

Riveted and Bolted Structural Joints in March 19630 The primary purpose

was to provide data on the behavior of bolts with higher strength properties

than for A325 fasteners, Such information was necessary for possible

revision (in 1964) of the specifications of the Council~ Although the

ASTM A354 grade Be bolts has been permitted by the 1961 and 1963 editions

of the specifications of the American Institute of Steel Construction, it

was found that the A354 grade BD bolt offered greater strength at very small

additional cost and might prove more economical in structures~ The American

Society for Testing and Materials acknowledged the need for a structural

bolt comparable dimensionally to the ASTM A325 fastener but with material

properties similar to those of the ASTM A354 grade BD bolto This new bolt»

described in ASTM A490-64T 'OQuenched and Tempered Alloy Steel Bolts for

Structural Steel Joints lO (including nuts and plain hardened washers), was

approved by ASTM in 19640 Because acceptance by ASTM of the A490 bolt

specification was anticipated, it was necessary to obtain the information

required for revisions in the specifications of the Research Council (Which

approved revisions in March 1964 9 incorporating the A490 bolt) and of the

American Institute of Steel Construction, so that designers would be able to

use the new bolt.

A second purpose for this study was to determine whether different

testing procedures employed at various laboratories would contribute sig­

nificantly to experimental scattero This possible variable was checked by

having the University of Illinois and lehigh University conduct the testing

in duplicateG All bolts, nuts, and washers were supplied to lehigh

Page 5: CALIBRATION TESTS OF A490 HIGH~STRENGTH BOLTS

-3m:>

University by a well-known manufacturer in sufficient quantities from the same

lotso At lehigh the bolts were identified and selected at random so that

Ill~nois would receive half of each lot~ Each university supplied the

special equipment for the tests conducted in its laboratoryo

Acknowledgments

The tests reported herein were part of investijgat~ons resulting

from cooperative agreements between the Engineering Experiment Station of the

University of Illinois (Department of Civi 1 Eng~neering), Lehigh University

(Department of Civil Engineering), the Research Council on Riveted and

Bolted Structural Joints g the American ~nstitute of Steel Construction, the

ij l1inois Division of Highways, the Pennsylvania Department of Highwayst a~d

the Department of Commerce == Bureau of Public Roadso WQ Ho Munse, Professor

of Civi 1 Engineering at ~11inois and l. So Beedle, Research Professor of

Civil Engineering at Lehigh, were the general superv~sors of the testso The

tests at ~ 11inois were conducted by Emn le Troup» Research Assistant, working

directly with Eugene Chesson» Jro, Associate Professor of Civij 1 Engineering;

the tests at lehigh were conducted by Gordon Sterling~ Research Assistant,

working directly with John Wo Fisher, Research Ass~stant Professor of

Civil Engineering o

The program was planned in cooperation with Committee 15 of the

Research Counc i 1 on Riveted and Bolted Structural Jointso The members of the

Committee ( 1964) are as follows:

T. R. Higgins, Chairman W~ Ho Munse

l. So Beedle Eo J ° Ruble

Ro Bo Belford Ao Schwartz, J ro

Eo Chesson, J ro T. W. Sp i lman

Fo H~ Dill D~ lo Tar 1ton

Page 6: CALIBRATION TESTS OF A490 HIGH~STRENGTH BOLTS

G. s. Vincent

-4~

F. Eo Graves

E. L. Erickson

Acknowledgment and appreciation are also due the Bethlehem Steel

Company for supplying the test samples.

DESCR~PT~ON OF TESTS

Materials and Equipment

The tests were conducted on 7/8 in. A490 heavy hexagon head bolts

having lengths under head of 5-1/2 in. and 9-1/2 in. The 5-1/2 in. bolts

(designated lot LI) had 1-7/16 in. of rol]ed thread while the 9-1/2 in.

bolts (designated lot AS) had 1-3/8 ino of machine cut thread. At lehigh

gage holes were dri lIed in the centers of both ends of the ,bolts to accomo­

date extensometers for length measurements, and lot and bolt numbers were

stamped on the bolt heads. The threads of the nuts and of the 9~1/2 in.

bolts were well lubricated as received; the threads of ~he 5-1/2 in. bolts

were not so well lubricatedo ~n every test one hardened washer was used

under the heavy hexagon ASTM A194 grade 2H nuto The washers had rough mill

scale on both surfaces~

A representative sample of twenty bolts and nuts from the AB lot

was checked, and found acceptable, with NC2A go and no-go ring gages and

NC2B go and no-go plug gages o The II lot bolts were not checked in this

mannero

Skidmore-Wi lhelm model M cal~brators were used for the torque

tests. This device uses hydraulic pressure to determine load measurements.

These units were recalibrated at intervals during the testing program to

insure that vibrations from pneumatic torquing did not alter their accuracyo

Adaptors were used with bolts of both lengths to provide the proper grips

Page 7: CALIBRATION TESTS OF A490 HIGH~STRENGTH BOLTS

with minimum numbers of p~ies or parts in the assemblieso All tests of

5-1/2 ino bolts torqued in solid steel were conducted in 4 ina X 4 ino X 4 in.

blocks of A44Q steel~ each with a 15/16 ino d~ameter holeo Pneumatic impact

wrenches were used to tighten all the specimens in the torque testso

The lehigh bolt calibrat~ng equipment and the direct reading ex-

tensometer used in these tests are described and i l~~strated in Reference

5(5). At Illinois two different multiplying C-frame extensometers were used

for elongation measurementso A large extensometer w~th a 12-1/2 in. maximum

gage length was used for the 9-1/2 1no bolts and a smaller capacity extenso=·

meter was used for the shorter boltso Both extensometers were carefully

calftbrated with a super~micrometer before testing to d~termine accurately

the multiplication factors(6). The actual changes in bolt elongation were

multiplied approximately 4~1/2 times by these lever type extensometerso

In order to assure accurate e]ongat~on readings 9 each of the three

extensometers was equipped with a counter=balance which was posit~oned so

that the entire weight of the extensometer and of the counter~balancewas

carried by the fixed point on the frameo Thus the hi9h~y sensit~ve movable

point was influenced solely by the e]ongation of the bo~tv and consnstent 9

uniform seating of the movable point in the bottom gage hole was assuredo

50 John l. Rumpf and John WO Fisher; IDCa~ibration of A325 Bolts sn Journal of

the Structural Division$ ASCE p Volo 89~ Noo ST6 p ProCa paper 3731» DecQ1963, ppo 215~234Q

60 Eo Chesson, Jro J fUEquijpment for Research on Riveted and Bolted Joints»'oR!lEM Bul1etin p Noo 22 9 March 1964~ (Paris~ France) p PPQ 66-67Q

Page 8: CALIBRATION TESTS OF A490 HIGH~STRENGTH BOLTS

-6-

Test Variables

The type and number of tests conducted are shown in the following

table:

Length 5- 1/2 (L I) 9- 1/2 (AB)in. J andlot No.

Total 4-1/8 4-9/16 8.. 1/4 8-11/16Grip, in.

Thread 1/8 9/16 1/8 9/16length inGrip, in.

University I 11 i no i s Lehigh I'll i noi s Lehigh I 11 i noi s lehigh 111 i noi s lehigh

Direct 5 5 5 5 6 5 5 5Tension

Torqued 5 6 5 5 5 5 5 5Tens ion(Skidmore-Wi 1he 1m)

Torqued 5 5 5 '5 - - - -Tension(4 in. squaresol id steelblock)

It can be seen that the variables included total grip, thread length

in grip, and method of lo~din9o The grip was measured from tne underside of

the bolt head to the face of t~e nut in contact with the wash~ro The thread

1~n9th uhder the nut was measured from the beginning of the minimum root

diameter of the bolt thread (~tart of first full thread) to the face of the

nut, as shown in the diagram in Figure 1*

Page 9: CALIBRATION TESTS OF A490 HIGH~STRENGTH BOLTS

Direct Tension Tests:

The direct tension tests were conducted- in a 120 kip* Baldwin

hydraulic testing machine at Illinois and in a 300 kip Baldwin hydraulic

testing machine at lehigho The special holders with replaceable inserts

used at both universities to accommodate various bolt diameters were similar

to those pictured in Reference 50 The differences in test procedures are

covered briefly in the following descriptions:

(a) lehigh: The bolt was first loaded to the specified proof

load (55045 kips), with readings taken at 10 kip increments$ and then un­

loaded to check the ASTM requirements of maximum measured set of O~0005 in.

No bolts were rejected by this testo The bolt was then reloaded at a

constant crosshead speed of approximately O~Ol ino per min.» and elongation

readings were taken at 10 kip intervals until the inelast~c range was

reached~ At this point load readangs were taken for every 0.01 ino of

elongation in the bolt~

(b) ~11inois: ~n direct tension testing the bo]twas taken from

a 0.6 kip initial load up to proof load (S5Q45 k~ps) t with elongation read~n9s

recorded at 5 kip incrementso (The small initial ~oad was applijed to keep

the test assembly in good alignment whi le initial extensometer readings were

made) 0 The bolt was unloaded to O~6 kips and measured to detect any permanent

setQ The bolt was then taken directly to proof load, this tijme at a strain

rate of about 0005 ino per min~9 after which load and elongation readings

were taken at various points until the extensometer ran out of travel well

beyond the ultimate loado All bolts met the ASTM requirements for measured

set and ultimate loadQ In general p three elongation readings were taken at

* One kip equals 1000 pounds'(ki 10 pound)

Page 10: CALIBRATION TESTS OF A490 HIGH~STRENGTH BOLTS

-8-

each loading increment p and they usually fell within a dial range of 00001 in.

(or within O~0002 in, actual). The average of these three readings was then

converted to the actual change in elongation in incheso

Torqued Tension Tests -~ Calibrator

Specimens of the 9~1/2 ino and 5~1/2 ino bo~ts were torqued in the

commercial hydraulic calibratorso Special 7/16 ino thick IBwashers lU were

used as adaptors at the faces of the calibrators to obtain the longer grips

for both lengths of boltso After packing the calibrator to the required grip

with appropriate adaptors, the bolt and nut were instalied to a lifinger-tight"

position, The nut was then tightened with a hand wrench to 5 kips and then

to 10 kips (lOsnug80 position); elongation and nut rotation read~ngs were

taken at both loadso The nut was tightened from the 19SI1ugiO pos~tion to

fai lure with pneumatic impact wrenches in 30 degree increments (1/12 turn) at

~11inois and 45 degree increments (]/8 turn) at lehigh; ]oad and elon9at~on

data were taken at each intervalo The extensometers used in the direct

tension tests were also used in these tests and were mounted vertica!lyo

Torqued Tension Tests =- Sol~d Block

For these tests, the 5~1/2 ~no bouts were tightened in the solid

steel blockso The nut was brought to a nfinger=tight 'U posntion and then

tightened by ma"nua 1 wrench i n9 to the mean 1UsnugOC e longat ion determi ned in

the hydraulic ca]ibrator testso The nut was then torqued u~ti 1 fai lurep

Elongation measurements were taken at 30 degree increments at ij~l~nois and

45 degree increments at lehigh" The 7/16 ino thick ltiwashers 'o were again used

in the test set~up to obtain the longer 4-9/16 ina gripo The extensometers

were used in a vertical pos~tion for these tests~ alsoa

Page 11: CALIBRATION TESTS OF A490 HIGH~STRENGTH BOLTS

-9-

TEST RESULTS AND ANALYSIS

General

A comparison of the test data taken at the two universities is

shown in Tables 1 and 2 as well as in the figures which follow. A close

study of the data shows that there is excellent agreement in most cases.

The mean elongations at ultimate (maximum) load (line 5, Table 1)

for the direct tension tests are the only tabulated data where substantial

differences consistently occur. These differences, about 10 percent or less~

were caused by two factors. First, the strain rate, which was 0.05 in.

per min. at Illinois and approximately O~Ol inQ per minQ at lehigh, affected

the results. The second and more important factor was the instant at which

the extensometers were read for ultimate load. Since the maximum load

held for relatively long periods of bolt deformation (as can be seen in

Figures 1 and 3) this second factor was the more importanto

During the torqued tension tests conducted in the calibrator the

bolt tension (read to the nearest 002 kips) sometimes remained at the

ultimate load value for as much as 3/8 of a turno ~n these cases the value

of the elongation at ultimate load was determined as the mean of the

incremental valueso A comparison of these data taken at I 11inoi5 and lehigh

(line 7, Table 2) ShONS excellent agreementIJ

The only other data in which there are not!ceable differences are

those most subject to human erroro This is apparent in the I~verage turns

to snug from finger tight lU data (1 ines 10 and 18, Table 2) and HMean·

elongation after rupture18 data (line 7, Table 1» and lines 8 and 22,

Tab 1e 2) •

Page 12: CALIBRATION TESTS OF A490 HIGH~STRENGTH BOLTS

-10-

!n general, the results reported herein are in agreement with other

studies of A490 (and A354 BD) bolts(7) (8) .

Load-Elongation Relationships

Figures 1 through 4 show the average bolt tension - or bolt load-

elongation characteristics of the bolts testedQ The close agreement between

the data from the two universities indicate that, as would be expected, the

load-elongation characteristics of the bolts were not affected by the different

testing procedures used at the two laboratories.

Figure 1 shows that the inelastic deformation of the 5-1/2 in. bolts

occurred after the prescribed proof load was reached (as required by speci-

fication) whereas Figure. 2 shows that in torqued tension tests inelastic

deformation began slightly be~low proof load; this behavior under torque was

caused by the combined tensile and- shear stresses produced by tightening the

nut. These observations are a"ls:o:.:true for the 9~~/2 ino bolts (see Figures 3

and 4) 0

figures 5 and 6 summarize the load-deformat~on relationships for the

5-1/2 and 9-1/2 in~ bolts respectively. The effects of thread in grip and

method of loading are very evident~ ~n torqued tensnon tests the 5-1/2 in~

bolts achieved about 82 percent of the ult~mate load reached in direct tension

tests (Figure 5 and Table 2) Q For the longer bolts (7/8 ina by 9~1/2 ina) the

torqued tension ultimate load was about 88 percent of the direct tension

ultimate load (Figure 6 and Table 2) 0 These values compare well with the

70 Eo Chesson, JrQD and Wo Ho Munse, IOStudies of the Behavior of High-StrengthBolts and Bolted Joints,18 Bulletin Noo 469, Engineernng Experiment Station,lUniversity of ~11inois9 Urbana!) ~11inois9 19640

8Q Ro JQ Christopher and Jj) W. Fisher, 'OCalibration of Alloy Steel Boltsf)fRFritz Engineering Laboratory Report N90 288019 9 lehigh Unijversftty,Bethlehem, Pao, July 1964Q

Page 13: CALIBRATION TESTS OF A490 HIGH~STRENGTH BOLTS

~11-

commonly presented value of 85 percent~ the value of 82 percent mentioned

in Refo 7 for A354 BD bolts, and the 84 percent from the extens~ve tests of

Refo 9 with A325 boltso

~t is evadent from Figures 5 and 6 that an increase in the thread

in grip caused a decrease in the ultimate load in both the direct and torqued

tension testso !n addition j greater ducti l~ty~ or tota] elongation, was

observed in the bolts with 9/16 ino thread in gripo The l~ lot bolts with

1/8 ina thread in the grip reached an ultimate load ~ percent greater than

those with 9/16 ina thread in gripo For the longer AB lot bolts this increase

was about 8 percento For both ~engths of bolts the elongation at failure in

the direct tension tests was more than twice that in the torqued testso

Figure 7 shows the ]oad-e~ongation characterist~cs of the two bolt

lotso As was expected, the longer bolts deformed more than the shorter bolts

in reaching the same loado

load~Nut Rotation Relatijonshfips~

~f the torqued tension~elon9at8on character~st~cs of a given lot

of bolts with a given grijp are assumed to be independent of the device ~n

which the bolts are instat]ed, then elongation can be used to determine the

load or tensnon ~n a bolt torqued in a solid blockQ Thus D using the nut

rotation-elongation relationships p]otted on the uppe~ sectijon of Figure 8

and the load~elongation relationships plotted be]ow D the ]oad at any

increment of turn can be established for the bolts tested in the solid blocko

The loads at 1/2 turn from snug for the solid block tests are shown for both

90 Jo GQ Viner~ Eo Chesson D Jro, Ro lo Dineen and WO HQ Mun5e, DOA Study ofNuts for Use with High-Strength Bolts~V8 Structura~ Research SeriesNoo 212 9 Department of Cijvil Engineering, ijn~versity of ~ l1inoijs, Urbana j

~11inois9 ~arch ]960~

Page 14: CALIBRATION TESTS OF A490 HIGH~STRENGTH BOLTS

=12c=

~11inois and lehigh datao ~n a similar fashion t the load~rotation data for

the shorter grip 5-1/2 in. bolts can be obtained.

From Figure 8 it is readily apparent that the hydraulic calibrator

is nsofter" than the solid block; that is, a given nut rotation produced

in the calibrator a smaller bolt load (as measured by elongation) than was

produced in the solid block testo This observation is of specia~ importance

to fabricators, erectors, and inspectors of high-strength bolted steel

structures. An actual! multiple~ply structural jo~nt may be expected to

have a stiffness which lies somewhere between the extremes of a hydraulic

cylinder and a solid block p depending on the thoroughness with which the

steel has been drawn up during the snugging and assembly operations; the

number, thickness, and flatness of the plies; etco*

This important observation is shown more clearly in Figures 9 and

10 (which were obtained ~n the manner described for Figure 8). Load-rotation

curves are commonly used to determine proper tightening of structural boltso

There is a considerable scatter band of results, as would be expected in

this type of datao The reason for the smaller scatter in the so]id block

data is as fol1owso For the tests conducted in the hydraulic cal~brator

actual load-nut rotation data were takeno Thus, the variations in lndividual

bolts are reflected in the scatter bands associated with these tests~ How-

ever, in the solid block tests the only data that cou~d be taken were nut

rotation and elongation measurementso With the method described above, the

bolt tension at any specified elongation was determ~nedo Use of a mean

curve for load VS~ elongation, as in Figure 8 neglects the variations in

* Other examples 'of:th'i,~ phenomenon are given in a dijscussion to Ref~ 5by Eo Chesson~ Jr., ASCE~ 504 9 Vol. 90~ p. 317-319 9 Aug G 19640

Page 15: CALIBRATION TESTS OF A490 HIGH~STRENGTH BOLTS

-13-

individual boltso Thus the small scatter band associated with the solid

block tests is somewhat conservative.

However, in both Figures 9 and 10 it is clear that the solid

block deformed much less under the bolt forces than did the hydraulic

calibrator and that a given amount of nut rotation produced more bolt

elongation in the block than in the calibrator~ For example, the bolts

with 1/8 inothread in grip (Figure 9) reached proof load at 0.28 turns from

snug (mean va 1ue) i n the so 1i d block and 0 ~ 50 tu rns (mean va l/IJe) i n the

hydraulic calibrator9

The mean load-nut rotation curves from Figures 9 and 10 are

summarized in Figure 11. When almost 1/2· inG more threads are included in

the gripv slightly more turns of the nut are required to reach proof load.

The difference produced by th~s change of the thread in the grip is small

compared to the difference between a bolt tightened in a solid block and

one tightened in a hydraulic call1brator~

ijn the analysis of these data another observation can be made~

Despite a very broad scatter of results ~n the nut rotation-elongation data$

as plotted in Figure 8» it is obvious that a definite separation of the mean

curves obtained by the two universities existso The- major separation of these

mean curves occurs beyond 1/2 turn from snug» i ~e~ in the inelastic range

and near ultimate load and beyond, where this difference is not a matter of

concern~ None-the~less, in Figure 12» the mean curves of load vSo nut

rotation obtained in the hydraulic calibratnng devices of the respective

universities, show a definite trendo ijt appears that one calibrator is

"softer18 than the other\! Th~s difference (Fig. ]2) from calibrator to

calibrator is much smaller than the difference shown in Figures 10 and 11

from solid block to caliprator. However, the possible v~ri~bility in

Page 16: CALIBRATION TESTS OF A490 HIGH~STRENGTH BOLTS

.... 14-

different hydraulic calibrators should be kept in mind by userso When data

from the two universities obtained with the solid block tests were plotted

as was done ~n Figure 12 9 the two curves were almost identicalo

The bolt: tension.... nut rotation data for the 7/8, inQ by 9-1/2·, ino

bolts are summarized in the average curves of Figure 130 To insure proof

load in these longer bo~tsp it is necessary to apply more than a half turn

from snug Q These tests were made in a hydraulic calibrator that, as

mentioned above, may be thought to represent an upper limit on the fisoftness18

which might be expected in actual structural jointso ijt might also be

pointed out that tests made with experienced steel workers operating pneumatic

wrenches have shown that 18snugfO often wi] 1 be greater than the 10 kips used

herein as a reasonab~e base from which to calculate turnso These 9-1/2 ino

bolts are almost 11 diameters lon9~ or more than the 8 diameters length

limit which is included in the 1964 Counci 1 specif~cation revis~on as the

maximum length for which only 'ij~!2 turn from snug'B wil] be prescr!bed; bolts

eight diameters or 8 ino l()ng are req~ired to have H2/~ turn from snugo fO

~t might be noted that despite the small differences in behavior for

variations in the grip$ the average number of turns !2 fai lure from JOsnllg 'O

appeared to be only slight]y affected by the number of threads in the 9r~p;

this difference amounted to approximately one quarter turn more to fai lure

for the longer-thread~in~9ripboltso ijn this same connection D from Table 2

it can be seen that, for the tests performed in the solid block v the average

turns to failure were only about 6 percent less than for those similar tests

performed in the hydraulic calibratoro

Description of failures:

S~X thread stripping failures occurred in the twenty direct tension

tests on the l~ lot boltso Five of these occurred in bolts being tested with

Page 17: CALIBRATION TESTS OF A490 HIGH~STRENGTH BOLTS

-15-

1/8 ino thread in gripG Th~s would be expected because that conditijon gave

the higher bolt loado ~n all cases of thread stripping the nut and bolt

threads were so badly damaged that it was impossible to determine which

threads had fai led firsto The remaining l~ lot bolts tested in direct

tension, with 9/16 iOG thread in grip, failed on a jagged diagonal extending

over several threadso Those with 1/8 ino thread in grip failed on a level

plane through the thread at the juncture of the thread runout and bolt shanko

Al~ AB lot bolts tested in direct tension also fai led on a jagged

diagonal extending over several threadso Those tested with 1/8 ino thread

in grip had fai lure planes extending into the nut~bolt interthreading.

All l~ lot bolts tested in torqued tension broke near the nut

faceo The failure mode was generally a ntw!sting off~o through the f~rst

thread under the nuto Some fa~ lure surfaces extended over two threads and

showed ev~dence of longitudinal tear 9 ~~dicating that the fina] fai !ure

occurred in tens~onQ The difference ~~ thread ~ength in grip had little

effect on the appearance or texture of the fracture surface.

S~X of the AB lot bolts tested in torq~ed tension failed by thread

strippingo With these except~ons the faB lure, modes for the AB bolts in

torqued tension were the same as those described above for the l~ bo!ts.

These stripping fai lures deve]oped after the max~mum bolt load appeared to

have been reached; maximum loads recorded were similar to those obta!ned with

tensile failureso Measurements of the bolt and n~t diameters prior to testing

indicated that each thread form was near the extreme permitted for an ASA

Class 2 fit and thus a minimum thread engagement occurredo

Comparison with A325 Bolts

The A325 and A490 bolts compared in Figures 14 and 15 had the same

dimens~ons and their ultimate strengths were close to thelr respect~ve

Page 18: CALIBRATION TESTS OF A490 HIGH~STRENGTH BOLTS

-16,.

specified minimums. The AS lot A325 bolts shown in these Figures gave 105

percent of the minimum ultimate load specified for A325 bolts when tested

with 1/8 in. thread in gripo The H lot A325 bolts with 1/2 in. thread in

grip gave 106 percent of the specified minimum ultimate. The results of

these tests are given in Reference 5. As is shown in line 4 of Table 1 the

comparative values for the LI and AB lot A490 bolts were 109 percent and

102 percent respectively.

In Figure 14 it can be seen that the A325 and A490 bolts gave

substantially the same load-turns relationships up to the elastic limit

of the A325 bolts. At 1/2 turn beyond Iisnugli the A490 bolts gave about

20 percent greater load than the A325 bolts because of the relative mechanical

properties of the bolt steels.

Figure 15 compares the load-elongation characteristics of A490

bolts with those of A325 bolts» when tested in a hydraulic calibrator. The

longer bolts gave similar curves, with the A490 bolts going to a higher

plateauD Tests of shorter bolts show a quicker load drop-off beyond

ultimate load for the A490 bolts than for the A325 bolts. Simi Jar

comparisons were shown in Reference 7 for A325 with A354 BD bolts (which have

the same mechanical properties as A490 bolts), and in Reference 8 fGr A325

with A354 BD and A490 bolts.

Page 19: CALIBRATION TESTS OF A490 HIGH~STRENGTH BOLTS

-17-

CONCLUS~ONS

Conclusions of a general nature are presented below. Specific

values and relationships can be seen from the tables and figures.

10 Decreasing the amount of thread in grip increased the ultimate

strength of a bolt in both direct and torqued tensiono

20 The effect of loading method was quite pronounced. Bolts

teste~ in direct tension always gave higher (by approximately 20 percent)

ultimate loads than those from the same lot tested in torqued tension.

30 Bolts tested in torqued tension with 1/8 in. thread in grip

had less ducti lity and had from 1/4 to 3/8 fewer turns to fai lure than did

those tested with 9/16 ino thread in gripo

40 The load-nut rotation characteristics of bolts tested in a

solid steel block differed considerably from those of bQlts tested in the

hydraulic calibrator. The hydraulic calibrator deformed more under the bolt

forces than did the solid blocko ~n these tests the bolts torqued in the

sol id block reached proof load in just over 1/4 turn from 'Osnug 'O wh~ le those

in the calibrator required 1/2 turn or more from the same starting pointo

5~ There appears to be some small variation in IOsoftness fn or

flexib~ lity from one hydraul8c calibrator to another.

6. The 7/8 inc by 9-1/2 ino bo]ts had a tension approx~mately

equal to proof load when torqued to 2/3 turns from snug for both 1/8 ino and

9/16 ino thread in grip~ The 7/8 ina by 5-1/2 inu bolts had a bolt tension

of approximately proof load when torqued to 1/2 turn from snug f~r both

1/8 inQ and 9/16 in~ thread in gripe If the gripped materia! has more

IOstiffnessli than a hydraulic calibrator, proof load will be attained in

fewer turns.

Page 20: CALIBRATION TESTS OF A490 HIGH~STRENGTH BOLTS

-18-

70 The A490 bolts gave an increase of about 20 percent in

preload ever their A325 C0unterpatts when torqued to the specified values

of 1/2 turn for the short b01ts and 2/3 turn for the long bolts.

8. No significant differences caused by diffef~nt testing

procedures at the two universities ~ere netedo

Page 21: CALIBRATION TESTS OF A490 HIGH~STRENGTH BOLTS

1

2

3

4

5

6

7

8

9

10

TABLE 1

DIREeT TENS ION CAL IBRAT! ON

Lot Des I gnat ion LI AB

Bol t Length in. 5-1/2 9-1/2

Bolt Diameter in. 7/8 7/8

Thread Length In. 1-7/16 1-3/8

Spec i fled Proof Load kips 55.45 55.45

Specified Min. UI t. L~ad kips 69.30 69.30

~

Tes t i ng Agency .!.!:!:lJ:!Q..L 1§i.!§!!. .!.!:!:lJ:!Q..L 1§i.!§!!. .!.!:!:lJ:!Q..L LEH IGH .!.!:!:lJ:!Q..L LEH I GH

Nominal Grip In. 4.. 1/8 4-1/8 4-9/16· 4-9/16 8-1/4 8-1/4 8-11/16 8-11/16

Th read Leng th in Grip in. 1/8 1/8 9/16 9/16 1/8 1/8 9/16 9/16

No. of Spec imens Tes,ted 5 5 5 5 6 5 5 5

Mean Ul t imate Load kips 75.9 76.0 72.1 72.1 74.6 73.2 69.8 70.8

Standard Deviation kips 0.45 1.07 0.54 0.57 1.57 1.59 1.32 1.36

% Spec. Min. U1t. load 109 110 104 104 108 106 101 102

Mean Elong. at Ult. Load in .' 0.047 0.051 0.057 0.065 0.071 0.077 0.079 0.085

Mean Rupture Load kips 68 67 61 59 67 65 62 61

Mean Elong. after Rupture In. 0.13 0.14 0.23 0.24 0.15 0.12 0.19 0.18

Mean Elong. at Proof Load In. 0.0147 0.0154 0.,0160 0.0171 0.0280 0.0282 0.0297 0.0302

No. of Bol t T~ns ileFailures 2 3 4 5 5 5 5 5

No. of Stripping Failures 3 2 1 a 0 O. 0 0

TABLE 2 TORQUED TENSION CALIBRATION

1

2

3

4

5

6

7

8

9

10

11

12

13

14

IS

16

17

18

19

20

21

22

Lot Designation LI .AB

Bol t Length in. 5-1/2 9-1/2

Bolt Diameter in. 7/8 7/8

Type of Test Torqued in Skidmore-Wi lhe1m !orqued in Skidmore-Wi lhelm

Tes t i ng Agency .!.b!:.!l!Q!i 1§i.!§!!. ILLlNO IS LEH I GH ILL INO IS LEH IGH ILLINOIS .!£!!.!ill!Nomi na 1 Grip in. 4,:" 1/8 4 .. 1/8 4 ..9/16 4 ..9/16 8-1/4 8-1/4 8-11/16 8-11/16

Thread Length in Grip in. 1/8 1/8 9/16 9/16 1/8 1/8 9/16 9/16

No. of Spec imens Tes ted 5 5 5 5 5 6 5 5

Mean Load at 1/2 Turn from Snug kips 56.5 53.4 54.3 50.0 48.4 48.8 45.9 4].1

Mean Load at 2/3 Turn from Snug kips 62.0 60.2 59.1 55.8 58.5 58.9 54.4 51.7

Mean U1 t imate Load kips 62.3 61.1 60.1 58.4 65.4 65.4 60.1 61.8

Standard Dev iat ion kips 3.11 2.80 2.63 3.03 3.47 2.80 0.55 2.03

Mean Rupture Load kips 43 40 47 34 54 52 53 50

Mean Elong. at Ult. Load in. 0.025 0.026 0.037 0.036 0.057 0.055 0.060 0.058

Mean Elong. after Rupture in. 0.09 0.08 0.15 0.1.1 0.11 0.08 0.13 0.11

Mean Elong. at Proof Load in. 0.015 0.016 0.018 0.018 '0.028 0.028 0.033 0.031'

Avg. turns to snug fr~ finger tight 0.32 0.41 0.29 0.45 0.31 0.62 0.31 0.57

Avg. turns to Proof Load from snug 0.48 0.50 0.52 0.57 0.61 0.60 0.67 0.75

Avg. turns to fa i 1ure from snug 1.34 1.33 1. 61 1.65 1.45 1.43 1.59 1. 75

Rat ioTorqued Tension Ultimate 0.82 0.80 0.83 0.81 0.88 0.90 0.86 0.87Direct Tens ion U1 t imate

No. of stripping failures 0 0 0 0 0 2 0 0

Type of Test Torqued in Sol id Block

No. of, Spec i mens Tested 5 5 5 5

No. of Stripping Failures 3 0 1 0

Avg. turns to snug from finger tight 0.16 0.20 0.26 0.28

Avg. turns to Proof Load from snug 0.28 0.28 0.33 0.37

Mean Load at 1/2 turn from snug 62.0 62.0 58.5 57 ~5

Avg. turns to fa i 1ure from snug 1.26 1.40 1.50 1.44

Mean Elong. after Rupture in. 0.09 0.10 0.15 0.10

Page 22: CALIBRATION TESTS OF A490 HIGH~STRENGTH BOLTS

80

I .. .- ·i'a Thread· an Grip· Lehigho Illinois

st ll

r 16 Thread in Grip· Lehigh, 0 Illinois

~81 X 5 Y; Bolts·

+Fracture of Bolt

.16.14

++-+-

.12.10.08.06.04.02,0

20

60BOLTLOAD(ki ps)

40

BOLT ELONGATION (inches)

FIG. I DIRECT TENSION CALIBRATION - LI ;~ LOT A490 'BOLTS.

Page 23: CALIBRATION TESTS OF A490 HIGH~STRENGTH BOLTS

80

9 n •i'16 Thread in Grip • LehIgh

o Illinois

++Ys'Thread in Grip· Lehigh

o Illinois

"2Turn from Snug

.14

+

.12

~

.10

...~8 x 5 Y~ Bolts

-+-,+ Fracture of Bolt

.08

• 0 •00 0 0 0o 0 0'b •

---~ 0 ..D .••• • -- --0- __o 0 •

o

.06

oo

.04.02

20

o

'60. BOLT LProof

LOAD ILoad-

(kips)

40

BOLT ELONGATION (inches)

FIG. 2 TORQUED TENSION CALIBRATION - LI 'LOT A490 BOLTS.

Page 24: CALIBRATION TESTS OF A490 HIGH~STRENGTH BOLTS

.16.14.12

--~---~· Grip9 • Thread In

< 1a6 - • Lehigh

o Illinois

~81 x 9~2 Bolts

-+-,+ Fractu re of Bolt

.10

~8 Thread in Grip •. Lehighc Illinois

.08.06.04.02

¥P

o

Min. Tens iIe~-----_........--.. ...............

Strength

20

.80

60~BOLT e.r<!.ofLOAD Load--

(kips)

40

.BOLT ELONGATION (inches)

.'

FIG. 3 DIRECT TENSION. CALIBRATION -AB LOT A490 BOLTS.

Page 25: CALIBRATION TESTS OF A490 HIGH~STRENGTH BOLTS

80I II • •Ys Thread In Grip· LehIgh

c Illinois

2/3

Turn from Snug9" .~6 Thread in Grip· LehIgh

o Illinois

.16. 14

--1. ___

• +o

.12.10

7,11 x91~u Bolts'8' '2

.,..,.,. Fracture of Bolt

+0

.08..06.04.02

Proof[oad'--

20

o

60BOLTLOAD(kips)

.40

BOLT ELONGAT'ION (inches)

FIG. 4 TORQUED TEr\lSION CALIBR·ATION -AB LOT A490 BOLTS.

Page 26: CALIBRATION TESTS OF A490 HIGH~STRENGTH BOLTS

.14

~JlX5~11 So-Its8 2

.12.08

I ..

~~JTb16 '!

---I/.............. :

-............ ...............-............ -............

I_---.:.._._._"."_,<~" .._ ~_",,·_·.~."_~· ..d_. •.. ,_.._;" , " __ ••...• __ , __ , ,,, .. _,, __ : _ ".." ' '.. ' -- __ __ "-:., ' ' __-- --.. __.. ,,- __ __ '-.--~"__~~h= :~6} Th d ~ G· -ri d T .I/SI rea In riP, I\orque enSlon

Min.Tensi Ie..... - ----.- ----Strength

8 0 ~-,--.-..-~--_ -..-----',---_ ~ .._----" ..-.,,-,--.~~-:---~---,~~,-- ..,"_._.._--~~---- "..~., _----. ~-"'--- . .i'

2

o

60:.---....... ­

BOLTLOAD(kips)

'4

BOLT ELONGATION (inches)

FIG. 5 EFFECT OF LOADING METHOD ON LOAD-ELONGATION RELATIONSHIPS;L I LOT A490 SOLTS .

Page 27: CALIBRATION TESTS OF A490 HIGH~STRENGTH BOLTS

~"

8 } Thread in Grip,< 9~~ Torqued Tension

.16.14

- -----..... --

. I 2

----- ----- ~------

~n:J.Thread in Grip,I~ Direct Tension

~81 X 9 ~2n Bolts

~ 10.08.06

---- ----

.04.02

ProofLoad---

..Min. Tensi Ie

Strength

20

o

80

60BOLTLOAD(ki ps)

40

BOLT ELONGATION (inches)

FIG. 6 EFFECT OF LOADING METHOD ON LOAD-ELONGATION RELATIONSHIPS;AB LOT A490 BOLTS.

Page 28: CALIBRATION TESTS OF A490 HIGH~STRENGTH BOLTS

80 Direct Tension

.16.14.12.10

-Torqued Tension

.08

--- y~'x9~211 Bolts, ~8u Thread in Grip

---- 'la' x 5Y2' Bolts, Ys'Thread in Grip

.06.04~02o

~in.Tensile /' -- - ­

Strength"·-/

/ .

J:.rQ.ol_('/ --­Load

/IIII

20f- I/II

60BOLTLOAD(kips)

40

BOLT ELONGATION (inches)

FIG. 7 COMPARISON OF LOAD-ELONGATION RELATIONSHIPS OF LI LOTBOLTS WITH AB LOT BOLTS.

Page 29: CALIBRATION TESTS OF A490 HIGH~STRENGTH BOLTS

CJ

.10

Mean Load CurveFrom Fig.2 t 9~6 Thread in Grip

Proof Load

.08

~8 X 5 1/21

Bolts

g1~ Thread in Grip

#4-~---Torqued in Solid Block• -Lehigha-Illinois

o

.06

.04.02

Torqued inHydraulic Calibrator•• - Lehigh0- Illinois

o

20

60

01--&------'--1--1------1..---.........1-------'-----....,1...----

BOLTLOAD 40(kips)

. NUT ~4ROTATION

FROM 5/eSNUG

BOLT ELONGATION (inches)

FIG. 8 NUT ROTATION-ELONGATION CHARACTERISTICS OFLI LOT BOLTS; 9/16 INCH THREAD IN GRIP.

Page 30: CALIBRATION TESTS OF A490 HIGH~STRENGTH BOLTS

70

60

Torqued inHydraulicCalibrator

I Y2 (TURNS)

5400 (DEGREES)

- Proof Load

'--Torqued inSolid Steel

I

3600

~~ x 51/~' Bolts

~8' Thread in Grip

:;4270 0

~2

1800

o0 0

20 '

30

50

40

BOLTLOAD(ki ps)

I I-12 -1'4

-1800 -900

NUT ROTATION FROM SNUG

FIG. 9 TORQUED TENSION-NUT ROTATION RELATIONSHIPS OFLI. LOT A490, BOLTS; 1/8 INCH THREAD IN GRIP.

Page 31: CALIBRATION TESTS OF A490 HIGH~STRENGTH BOLTS

70

1~4 (TURNS)

6300 (DEGREES)

I3600

~8 x 5~21 Bolt,s

9,,~ Thread in Gri p

3l4

2700

o0°

20

30

60

Proof Load

.....- Torqued in50BOLT Hydraulic

CalibratorLOAD(kips)

Torqued in40 Solid Steel

-Y2 -~4

·-180° -90°

NUT ROTATION FROM SNUG

FIG. 10 TORQUED TENSION-NUT ROTATION RELATIONSHIPS OF LILOT A490 BOLTS, 9/16 INCH THREAD IN GRIP.

Page 32: CALIBRATION TESTS OF A490 HIGH~STRENGTH BOLTS

70

NUT ROTATION FROM SNUGFIG. II. EFFECT OF GRIPPED MATERIAL ON LOAD-ROTATION

RELATIONSHIPS -AVERAGE CURVES.

I

3600

'la' x 5 y~1 Bolts

-- Yal Thread in Grip9 "--~ ~6 It "It

Torqued in Sol id Block

Torqued in HydraulicCalibrator

20

o0°

30

50

40

60

BQLTLOAD(kips)

Calibrator

-Y2 ~Y4

-180° -900

Page 33: CALIBRATION TESTS OF A490 HIGH~STRENGTH BOLTS

BOLTLOAP(kips)

70

60

50

40

30

20

10

9/1~ T~read in Grip

~8.Thread in Grip

Lehigh-Illinois

Y~ x 5 ~2 Bolts

Torqued inHydraulic Calibrator

O-------"------.lL.------I....----.&o-----'---------o Y4 .1/2 3/4 ' I 1Y4 1'~2 (TURNS)

0° 90° 1800 2700 3600 4500 5400 (DEGREES)

NUT ROTATION FROM SNUG

FIG. 1·2 ·COMPARISON OF LOAD-NUT. ROTATION DATAFROM TWO UNIVERSITIES i SHOWING MEANCURVES.

Page 34: CALIBRATION TESTS OF A490 HIGH~STRENGTH BOLTS

70

BOLTLOAD(kips)

60

50

40

30

20

10

I/S Thread in Gri p

9/1~ Thread in Grip

7. II I n~8 x 9 V2 BoltsTorqued in Hydraulic Calibrator

O~---~....,.--_....a--_----a....__.....a--_---L_--..a-_-----.lL...-.-_--L.

o V4 1/2 3/4 I 1~4 I Y2 13/4 2 ( TURNS)

0 0. 900 1800 2700 3600 4500 5400 6300 7200 (DEGREES)

NUT ROTATION FROM SNUG

FIG. 13 LOAD-NUT ROTATION RELATI,ONSHIPS OF 7/8 INCH X

9-1/2 INCH A490 BOLTS i SHOWING MEAN CURVES.

Page 35: CALIBRATION TESTS OF A490 HIGH~STRENGTH BOLTS

70

II"60. /1 A49,O, L I Lot

A490 /prOOf-~r- -Load

I50'

IBOLTLOAD I I(k ips) ~1/2Turn

40 I

I IProof Load-----

-~1325 -I//

A325, 88 Lot~I

/

30 II

20 I --- Torqued in Solid Block

ITorqued in H:tdraulic Calibrator

- ~. ~

.-

10 'la' x5 Y21

Bolts

Yal Thread in Grip

O""'"---------------~_-----.a..--.----'------"------L-

o Y4 Y2 3/4 I I Y4 I Y2 I 3/4 (Turns)

900 .1800 2700 3600 450 0 540 0 6300 (Degrees)

NUT ROTATION FROM SNUGFIG. '14 COMPARISON OF LOAD-NUT ROTATION RELATIONSHIPS

OF A490 AND A325 BOLTS.

Page 36: CALIBRATION TESTS OF A490 HIGH~STRENGTH BOLTS

"'Proof Load t A325~2T';':;f;;' Snug -.~ - - - --

r L I Lot t A490 Bolts. :....... ~8 Thread' in Grip

----__: _ ',- _Proof Loa"~A49.2..__

~"""",,-- -'---....... 8 B Lot t A325 Bolts'/S Thread in Grip

O.~__--&...-..__----I,--__--.a..-__----I -.L.-__----L_

60

20

~ 40BOLTLOAD(kips)

.12.10

H Lot t A325 Bolts1/21 Thread in Grip

., .08.06.04

/ AB Lot I A490 Bolts .-'-_ 9,,~ Thread in Grip

.",.....--- -- - .......--- --

.02 .o

60A490.,ProofLoQd -

BOLTLOAD 40 A325,(kips) Proof

Load

20

BOLT ELONGATION, (inches)FIG. 15 COMPARISON OF LOAD-ELONGATION RELATIONSHIPS OF

"A490 WITH A325 BOLTS; BOTH TORQUED IN HYDRAULICCALIBRATOR .,