Calatogue Disconnector, EHV

download Calatogue Disconnector, EHV

of 5

Transcript of Calatogue Disconnector, EHV

  • 8/19/2019 Calatogue Disconnector, EHV

    1/8

    www.siemens.com/energy

    High Voltage Disconnectors 

    Answers for energy.

    s

    High quality and reliability delivered.

  • 8/19/2019 Calatogue Disconnector, EHV

    2/8

    High-Voltage Disconnectorsavailable up to 800kV 

     Years of experience in high-voltage switching

    technology go into the design and production of the

    disconnectors that set an international trend. Customers

    know Siemens as a powerful partner – a supplier

    of attractive products and solutions at competitive

    prices with high quality standard. We comply with

    our customer’s demand for reliability, safety and cost-

    effectiveness and serve them throughout the world.

    Irrespective of your application our disconnectors

    provide the best solution for your requirements every

    time.

    Siemens Ltd. has an integrated facility for design, testing

    and manufacturing of disconnectors at Hyderabad. Larg-

    est of its kind in India, this plant, manufacturers center

    break, double break, pantograph and knee type discon-

    nectors. The products range from 36kV upto 800kV for

    various current ratings from 630A to 3150A* as well as

    associated earth switches and drive mechanisms.

    The disconnectors are supplied throughout India

    covering almost all the switchyards/substations, power

    stations, paper, sugar, cement, and petrochemical

    Industries etc. 

    In the modern period, the switchyards are going for

    unmanned stations and with the advent of digital relays,

    the system is totally computerized and all actions are

    being carried out away from the switchyard through

    remote operation control, SCADA systems etc. Any failure

    in operation on a command or maloperation can create

    disastrous consequences like power loss, loss of equipment

    or outages triggering even the grid failure.

    Under these circumstances, this would call for a very reliable

    & quality conscious product in disconnectors.

    • Expertise in manufacturing disconnectors for varied

    climatic conditions.

    • Suggestions on possible interchangeability of

    components/modifications at design stage itself to

    optimize the resultant performance.

    • Accessories like insulators, support structure and

    terminal connectors can also be supplied as per the

    customers requirements.

    • Highly experienced service team for on-site supervision

    of erection, commissioning and testing.

    2

  • 8/19/2019 Calatogue Disconnector, EHV

    3/8

    Product Portfolio

    Double Break Dicconnector can be installed in locations,

    which have minimal overhead clearance, as blades swing

    open to the side rather than lifting upwards. Double

    break disconnectors are normally supplied with earth or

    without earth switch based on the requirement and they

    can be either with mechanical gang or with electrical

    gang operation in order to ensure the smooth operation

    of all the three poles simultaneoulsy.They are excellent

    for installations, which have large amount of fault cur-

    rent due to reverse loop contact design. The design of

    two breaks per phase in series provides much greater linecharging or magnetizing current interrupting capability

    with standard arcing horns.

    Special Features in our Double Break Isolators:

    Successfully type tested design meeting the

    requirements of IEC 62271-102.

      Successfully tested for short circuit level of 40kA,

    50kA and 63kA.

      Confirming to mechanical endurance of class M2

    as per IEC requirements.

    Horizontal Double Break Disconnector

    Centre Break Disconnector can be installed in locations,

    which have minimal overhead clearance, as blades swing

    open to the side rather than lifting upwards. An economic

    advantage of using Centre Break Disconnector is that it

    requires only six insulators per Disconnector versus nine

    insulators required for Double End Break Disconnector.Centre break disconnectors are normally supplied with

    earth or without earth switch based on the requirement

    and they can be either with mechanical gang or with

    electrical gang operation in order to ensure the smooth

    operation of all the three poles simultaneoulsy.

    Horizontal Centre Break Disconnector

    Special Features in our Centre Break Isolators:

      Successfully type tested design meeting the

    requirements of IEC 62271-102.

      Successfully tested for Short circuit level of 40kA,50kA.

      Confirming to mechanical endurance of class M2

    as per IEC requirements.

    3

  • 8/19/2019 Calatogue Disconnector, EHV

    4/8

    Pantograph Disconnectors can be installed in locations

    where coupling of buses/current transfer are required at

    two different heights. Current transfer will take place from

    the top-level bus to the bottom level bus through this type

    of disconnector.

    Pantograph disconnectors are normally supplied with one

    earth switch and without earth switch based on the re-

    quirement and they are usually electrically gang oper-

    ated in order to ensure smooth opeartion of all the three

    poles simultaneously.

    Pantograph Disconnector

    Horizontal Knee Type Disconnector

    Special Features in our Pantograph Isolators:

      Successfully type tested design meeting the

    requirements of IEC 62271-102.

      Successfully tested for Short circuit level of 40kA.

      Confirming to mechanical endurance of class M2 as

    per IEC requirements.

    A particular advantage of using Horizontal knee type

    disconnector is reduced vertical dimension and these

    disconnectors can be used for any conventional applica-

    tion. The reliable and safe performance of our discon-nector is ensured through silver plated contacts, a special

    mechanism to achieve the high contact pressure and

    completely free rotating unit bearings. Our disconnectors

    can withstand short circuit current rating upto 50kA/1sec

    and the applicable standard is IEC 62271-102.

    Note: Further information will be provided on specific

    request from customer

    4

  • 8/19/2019 Calatogue Disconnector, EHV

    5/8

    Operating Mechanisms

    Motor Operating Mechanism

      Motor coupled with a reduction worm gear toincrease the output torque.

      Electrical interlock between breaker and

    disconnector.

    Robust mechanical interlock between disconnector

    and earth switch.

    Local/remote control facility.

    Single phase preventer and overload protection

    device.

    Pole discrepancy relay in case of individual pole

    operation.  Local manual operation in case of emergency

    operation.

    Manual Operating Mechanism

      Hand lever operated or through reduction gear

    depending on customer’s requirement.

    Electro-Mechanical interlock.

    Provision for padlock.

      Snap action for auxiliary contacts for customer’s

    use.

      Snap action auxiliary switches with silver-plated

    contacts for customer’s use.

    Provision for padlock.

    Motor rated for 415Volts, 3 phase AC or

    220V/110V DC to meet the customers’

    requirement.

    Siemens Disconnectors come with two types of operating mechanism depending on

    the customer’s requirement

    5

  • 8/19/2019 Calatogue Disconnector, EHV

    6/8

    Product Range & Technical Data 

    Horizontal Centre Break Disconnector

    Technical Particulars Unit Rated Values

    Rated voltage (kV) [kV] 36 72.5 123 145 245 420

    Rated frequency [Hz] 50 50 50 50 50 50

    Rated current [A] 3150 3150 3150 3150 3150 3150*

    Rated short circuit withstand value [kA] 25 40 40 40 40 40/50

    Rated short circuit duration S 3 3 3 3 3 3/1

    Rated PF withstand voltage across isolating distance [kVr] 80 160 265 315 530 610

    Rated PF withstand voltage between live terminals

    and ground

    [kVr] 70 140 230 275 460 520

    Lightning Impulse withstand across Isolating

    distance

    [kVp] 195 375 630 750 1200 1425

    Lightning Impulse withstand between live terminals

    and ground

    [kVp] 170 325 550 650 1050 1665

    Switching Impulse withstand across Isolating

    distance

    [kVp] - - - - - 1245

    Switching Impulse withstand across between live

    terminals and ground

    [kVp] - - - - - 1050

    Horizontal Double Break Disconnector

    Technical Particulars Unit Rated Values

    Rated voltage (kV) [kV] 36 72.5 123 145 245 420

    Rated frequency [Hz] 50 50 50 50 50 50

    Rated current [A] 3150 3150 3150 3150 3150 3150*

    Rated short circuit withstand value [kA] 25 40 40 40/50 40/50 40/50/63

    Rated short circuit duration S 3 3 3 3/1 3/1 3/1/1

    Rated PF withstand voltage across isolating distance [kVr] 80 160 265 315 530 610

    Rated PF withstand voltage between live terminals

    and ground

    [kVr] 70 140 230 275 460 520

    Lightning Impulse withstand across Isolating

    distance

    [kVp] 195 375 630 750 1200 1425

    Lightning Impulse withstand between live terminals

    and ground

    [kVp] 170 325 550 650 1050 1665

    Switching Impulse withstand across Isolating

    distance

    [kVp] - - - - - 1245

    Switching Impulse withstand across between live

    terminals and ground

    [kVp] - - - - - 1050

    6

  • 8/19/2019 Calatogue Disconnector, EHV

    7/8

    Pantograph Disconnector

    Technical Particulars Unit Rated Values

    Rated voltage (kV) [kV] - - - - 245 420

    Rated frequency [Hz] - - - - 50 50

    Rated current [A] - - - - 3150 3150*

    Rated short circuit withstand value [kA] - - - - 40 40

    Rated short circuit duration S - - - - 3 3

    Rated PF withstand voltage across isolating distance [kVr] - - - - 530 610

    Rated PF withstand voltage between live terminals

    and ground

    [kVr] - - - - 460 520

    Lightning Impulse withstand across Isolating

    distance

    [kVp] - - - - 1200 1425

    Lightning Impulse withstand between live terminals

    and ground

    [kVp] - - - - 1050 1665

    Switching Impulse withstand across Isolating

    distance

    [kVp] - - - - - 1245

    Switching Impulse withstand across between live

    terminals and ground

    [kVp] - - - - - 1050

    Horizontal Knee Type Disconnector

    Technical Particulars Unit Rated Values

    Rated voltage (kV) [kV] - - - - - 800

    Rated frequency [Hz] - - - - - 50

    Rated current [A] - - - - - 3150*

    Rated short circuit withstand value [kA] - - - - - 50

    Rated short circuit duration S - - - - - 1

    Rated PF withstand voltage across isolating distance [kVr] - - - - - 1150

    Rated PF withstand voltage between live terminals

    and ground

    [kVr] - - - - - 830

    Lightning Impulse withstand across Isolating

    distance

    [kVp] - - - - - 2100(+455)

    Lightning Impulse withstand between live terminals

    and ground

    [kVp] - - - - - 2100

    Switching Impulse withstand across Isolating

    distance

    [kVp] - - - - - 1175(+650)

    Switching Impulse withstand across between live

    terminals and ground

    [kVp] - - - - - 1550

    * The rating of disconnector for 4500A is available against specific request.

    7

  • 8/19/2019 Calatogue Disconnector, EHV

    8/8

    Siemens Ltd.

    Plot No 89 and 90, IDA -Gandhinagar,Balanagar(Post), Hyderabad-500037,Andhra Pradesh,IndiaFax:+91 40 23079992

    www.siemens.com/energy

    XX-XX-XXX-XXX

    Product upgradation is a continuous process. Hence, data inthis catalog is subject to change without prior notice. For thelatest information, please get in touch with our Sales Offices.

    A worldwide 24 hours service is available, which immediately

    sends out service personnel and/or delivers spare parts as needed.

    Customer Support Center:-

    Toll free Phone no. in India: 1800 2667 480

    Email: [email protected]