2 WON-DOOR FIREGUARD

Fire Safety by Design

Setting the standard. . . . . 2

Typical applications . . . . . 3

Egress applications . . . . . 4

Non egress applications . . 5

Listings and approvals . . . 6

Standard features. . . . . . . 7

How to specify . . . . . . . . . 8

WON - D O O RCORPORAT IONSalt Lake City, UT 84104

P h o n e : 8 0 0 - 4 5 3 - 8 4 9 4www .w o n d o o r . c om

Founded in 1962, the Won-Door Corporation introduced the world’s most durableacoustically rated folding partition. In 1977 the company pioneered the development ofthe first-ever accordion type, fire rated horizontal sliding door. Today, more than 40years later, Won-Door remains the industry leader in the manufacture of fire doors andmoveable firewalls. Technology developed by Won-Door engineers continues toinfluence the building products and fire protection industries.

Setting the standardThe first to gain universal acceptanceThe development of the accordion type, horizontally sliding fire door – as manufacturedby the Won-Door Corporation – has had a profound influence on the model coderequirements that regulate their use, leading to its universal acceptance for use invirtually any means of egress application.

The first to be UL listedThe Won-Door FireGuard was the first accordion type fire door to successfully passnationally recognized tests to withstand the passage of fire. Won-Door FireGuardproducts are listed by Underwriters Laboratories Inc. (UL) for up to 3 hours as a rateddoor assembly and 2 hours as a moveable fire wall.

Still on the cutting-edgeOnly the Won-Door FireGuard uses astate-of-the-art microprocessor activatedcontrol system to guarantee reliabilityand enhance door function. Thistechnology provides almost limitlessopportunities for electroniccommunication, supervision, alarmactivation and more.

Engineered to fit YOUR needsBuilding codes encourage larger openings so why be limited by traditional forms ofopening protectives like roll-down shutters or swing-type doors? The custom-made

Won-Door FireGuard fire door canaccommodate virtually any opening.Capable of spanning wide openings andheights up to 28 feet* – even radialconfigurations are possible. Best of all,the single- or bi-parting doors areinstalled in the open position and fold tojust inches per foot behind pocket doorsthat you can design to blend with thesurrounding architecture.

* Increased custom heights available

Area separation between the old and new BWIAirport terminal.

Opening protective for a non-rated glass entranceto a tenant suite.

Page 3: BuyLine 3726 WON-DOOR FireGuard...WON-DOORFIREGUARD 5 08 11 73/WON BuyLine 3726 UseWon-DoorFireGuardinlieuofshutters NonEgressApplications APPLICATION AreaSeparation PROJECT ProvoCityLibrary

WON-DOOR FIREGUARD 3

08 11 73/WONBuyLine 3726

Superior performance, superior serviceMore than twenty branch sales offices and two Regional Sales Offices, plus a highlyskilled team of designers, engineers and field technicians, provide product service andsupport across the United States. Thoroughly knowledgeable about building code aswell as construction, our sales force can be relied upon to guide you every step of theway so you can get your ideas off the drawing board and into existence.

Typical applications include:

APPLICATIONElevator LobbySeparation inType R Occupancy

PROJECTGold Country Hotel& Casino

LOCATIONOroville, California

PROJECTARCHITECTVarond Design GroupWon-Door FireGuardfire doors are used tocreate unobtrusive, yetcode-compliant,elevator lobbies thatare compatible withthe decor of thishigh-rise hotel andcasino in NorthernCalifornia.

The same Won-Door FireGuard fire doors are used in this elevator lobby/stairwell tosatisfy two code enclosure requirements – protection of a vertical opening as well aselevator lobby separation.

Area SeparationAtrium SeparationCorridor SeparationElevator Lobby SeparationHorizontal ExitsOccupancy SeparationSafe Areas of Refuge

Smoke BarrierSmoke and Draft ControlVertical Exit Enclosure SeparationSmoke CompartmentationStage Proscenium ProtectiveVertical Opening Protective

Page 4: BuyLine 3726 WON-DOOR FireGuard...WON-DOORFIREGUARD 5 08 11 73/WON BuyLine 3726 UseWon-DoorFireGuardinlieuofshutters NonEgressApplications APPLICATION AreaSeparation PROJECT ProvoCityLibrary

4 WON-DOOR FIREGUARD

Use Won-Door FireGuard in lieu of swing doors

Egress Applications

APPLICATIONVertical OpeningProtective

PROJECTArizona StateUniversity AthleticsFacility

LOCATIONTempe, Arizona

PROJECTARCHITECTDWL ArchitectsThe architect wantedthe natural light fromthe skylight of thisthree-story athleticbuilding to filterthrough colorfulbanners andilluminate a display ofathletic trophies andawards on the firstfloor. Using Won-DoorFireGuard fire doorsmade this possible.

Use Won-Door FireGuard in lieu of reducing thesize of rated openings

"Fire doors" are not limited to just hollow metal swings. Won-Door FireGuard firedoors are code recognized and accepted anywhere an opening protective is required.

Rated openings in fire walls and fire barriers are permitted to be as large as 156 squarefeet, even in unsprinkled environments. The Won-Door FireGuard provides maximumdesign flexibility – beyond that of any other fire door or shutter.

Page 5: BuyLine 3726 WON-DOOR FireGuard...WON-DOORFIREGUARD 5 08 11 73/WON BuyLine 3726 UseWon-DoorFireGuardinlieuofshutters NonEgressApplications APPLICATION AreaSeparation PROJECT ProvoCityLibrary

WON-DOOR FIREGUARD 5

08 11 73/WONBuyLine 3726

Use Won-Door FireGuard in lieu of shutters

Non Egress Applications

APPLICATIONArea Separation

PROJECTProvo City Library

LOCATIONProvo, Utah

PROJECTARCHITECTMJSA ArchitectsA non-rated clerestoryjoins the renovatedhistoric 1892 buildingwith a large modernlibrary addition.Combining the old andthe new presented acode compliancechallenge. Since theaggregate squarefootage exceeded theallowable area definedin the current code, a2-hour fire barrier –the Won-DoorFireGuard – was usedto separate a largeportion of the historicrenovation. By takingadvantage of theapproved wide spanopening protectivecapabilities, historicambiance and codecompliance wereeasily accommodated.

Use Won-Door FireGuard in lieu of fire-rated glass

By redefining what is typically described as an “atrium” Won-Door FireGuard firedoors meet the required fire separation between adjacent spaces while eliminatingcostly atrium requirements such as sprinklers and smoke evacuation systems.

Won-Door FireGuard, the only microprocessor controlled fire door on the market, is thepreferred solution for lower cost and clear openings. Some models are approved for useas an ASTM E-119 compliant moveable fire wall in non-egress openings in fire barriers.

Page 6: BuyLine 3726 WON-DOOR FireGuard...WON-DOORFIREGUARD 5 08 11 73/WON BuyLine 3726 UseWon-DoorFireGuardinlieuofshutters NonEgressApplications APPLICATION AreaSeparation PROJECT ProvoCityLibrary

6 WON-DOOR FIREGUARD

Listings & Approvals

APPLICATIONElevator LobbySeparation/AccessControl

PROJECTSan DiegoInternational Airport

LOCATIONSan Diego, California

PROJECTARCHITECTSPGAThe Won-DoorFireGuard fire doorcan be used to isolateand control a securitybreach as well as stopthe spread of fire andtoxic fumes.

Building Code Reference 1008.1.2 exc #5 1008.1.2 exc #6 7.2.1.14

Performance Criteria 1008.1.3.3 1008.1.3.3 7.2.1.14

APPLICATIONS 2006 NFPA 1012006 IBC1

1Any application without occupant load limitation except H occupancies.

2003 IBC1

MODELNUMBER

MAX. OVERSIZELABEL SIZE

TESTCRITERIA

HOURLYRATING

U.L. FILENUMBER

SINGLE ORBI-PARTING

28'0" (h)Unrestricted (w)

20 minutesBoth

Available

28'0" (h)Unrestricted (w)1 hour

BothAvailable

28'0" (h)Unrestricted (w)1 1/2 hours

BothAvailable

28'0" (h)Unrestricted (w)3 hours

BothAvailable

N.A.2 hourSingle Parting

Only

N.A.1 hourSingle Parting

Only

Door AssemblyFireGuard FG20

Door AssemblyFireGuard FG603

Door AssemblyFireGuard FG903

Door AssemblyFireGuard FG1803

Wall AssemblyFireGuard MFW24

Wall AssemblyFireGuard MFW14

Automatic ClosingSystem5 N.A.

Can be used on allWon-Door FireGuard models

listed up to 3 hours

Can be usedfor both

3 Each door assembly, when required, complies with UL1784; and with the exception of FG20,can be labeled as Temperature Rise (TR). See ESR1394.

4 MFW - Movable Fire Wall5 This listing applies for use on all Won-Door FireGuard models.6 Excluding cotton pad test.

ICC Research Rep. ESR-1394

State of California Door Assemblies MFW 3261-357:001; 1080-357:100

San Francisco Dept. of Public Works 387W18.2

City & County of Denver M-8275

State of Wisconsin 811003

City of New York Listed Assemblies MEA-127-79-M; MEA-124-79M; MEA-383-85-MOversized Assemblies MEA-377-86-M; MEA-70-87-M; MEA-69-87-M

Means of Egress Applications

Product Information

Other Won-Door FireGuard Listings and Reports

U.L. 10B(ASTM E-2074)6

U.L. 10B(ASTM E-2074)6

U.L. 10B(ASTM E-2074)6

U.L. 10B(ASTM E-2074)6

U.L. 263(ASTM E-119)

U.L. 263(ASTM E-119)

U.L. 864

R6799

R6799

R6799

R6799

R12272

R12272

E92690

Page 7: BuyLine 3726 WON-DOOR FireGuard...WON-DOORFIREGUARD 5 08 11 73/WON BuyLine 3726 UseWon-DoorFireGuardinlieuofshutters NonEgressApplications APPLICATION AreaSeparation PROJECT ProvoCityLibrary

WON-DOOR FIREGUARD 7

08 11 73/WONBuyLine 3726Standard Features

1. Exiting hardwareExiting hardware can be configured andplaced where appropriate, including toaccommodate persons with disabilities.

2. Leading edge obstruction detectorThe door will stop upon contact with anobstacle, pause, then re-seek the closedposition.

3. LeadpostDoors can be prevented from closing andcaused to re-open a preset distance byapplying light pressure to the leadpost.

4. Single- or bi-parting doorsA single door slides across the openinginto a recessed jamb located on theopposite wall. The spanning of largeropenings is possible by using thebi-parting configuration. The storagespace is then divided on each side ofthe opening.

5. Pocket cover doorPocket cover doors can be designed byyou to blend with any decor.

6. Track and trolley systemThis system allows the door toaccommodate wide span openings.Curved configurations are also possible.

7. Thermal lockout featureAmbient temperature at the door ismonitored and the operating device isautomatically disabled if the environmentbecomes untenable.

8. MicroprocessorA control unit located in the door’sstorage pocket provides continuousmonitoring of door status.

9. ElectronicsThe Won-Door FireGuard is a completelyelectronically supervised system utilizingsolid state circuitry as well as a backupDC power supply.

10. Floor gasket and fire linerA tight-fitting floor gasket and fiberglassliner provide an impenetrable barrieragainst the spread of smoke and flames.

11. Modular designModular design provides for in-placereparability using basic tools.

12. MaterialsDoor panels are constructed of 24-gaugesteel with a standard finish of platinumenamel. Optional colors are available fora nominal fee.

Standard features of the Won-Door FireGuard:

1

2

6

7

8

9

10

11

Page 8: BuyLine 3726 WON-DOOR FireGuard...WON-DOORFIREGUARD 5 08 11 73/WON BuyLine 3726 UseWon-DoorFireGuardinlieuofshutters NonEgressApplications APPLICATION AreaSeparation PROJECT ProvoCityLibrary

8 WON-DOOR FIREGUARD

Specifying the Won-Door FireGuardWhyWithout the use of floor tracks or exposed hardware of any kind, these fire doorsare the most trouble free product in the fire protection industry.

• Design flexibility

• Custom made to fit your design without compromising code requirements

• Lower maintenance costs

• Modular construction means in-place reparability

• No parts exposed to wear and tear

• Fewer service calls

• Can be reset by building management by simply pushing a button

• Backup power supply so door operates even during a power outage

• Increase useable space

• Code compliant

• Access control options available

• Often cost less than other solutions

How• Our Design Manual containing a complete summary of architectural details andspecifications is available for free from your local Won-Door representative. Or call800-453-8494 to order.

• The Won-Door FireGuard Product Catalog prepared to standard CSI format for usewith most CAD systems is also available for download from our website atwww.wondoor.com

• Additionally, videos, in a variety of formats, can be downloaded from our onlinevideo archive. These informative short movies cover a range of topics from typicalapplications and product demos to technical topics and code compliance.

Learn and earnAIA members can learn more about Won-Door products and earn credits byparticipating in a Won-Door seminar either online or in person. Contact your localrepresentative for more information or visit www.wondoor.com and click onContinuing Education.

For more information contact your local representative.

Fire Safety by Choice

WON - D O O RCORPORAT IONSalt Lake City, UT 84104

P h o n e : 8 0 0 - 4 5 3 - 8 4 9 4www .w o n d o o r . c om