Busbar Sizing for 50ka for 1 Sec

1
Author: K. C. Agrawal ISBN: 81-901642-5-2 Carrying power through metal-enclosed bus systems 28/999 The welded portion, such as at the flexible joints*, should also be safe up to this temperature. Welding of edges is essential to seal off flexible ends to prevent them from moisture condensation, oxidation and erosion of metal. Tin or lead solder starts softening at around this temperature and should not be used for this purpose. For joints other than flexibles it is advisable to use oxy- acetylene gas welding or brazing for copper and tungsten inert gas (TIG) or metal inert gas (MIG) welding for aluminium joints. Note In case of copper also, the end temperature is considered as 185C only. Although this metal can sustain much higher temperature than this, without any adverse change in its mechanical properties, merely as a consideration to Table 32.3, and to safeguard other components, insulations and welded parts etc., used in the same circuit. To determine the minimum size of conductor for a required fault level, I sc , to account for the thermal effects one can use the following formula to determine the minimum size of conductor for any fault level: q q t sc 2 20 = 100 (1 + ) k I A t Ê Ë ˆ ¯ μ (28.1) where q t = temperature rise (in C) I sc = symmetrical fault current r.m.s. (in Amps) A = cross-sectional area of the conductor (in mm 2 ) μ 20 = temperature coefficient of resistance at 20C/C, which as in Table 30.1 is 0.00403 for pure aluminium and 0.00363 for aluminium alloys and 0.00393 for pure copper q = operating temperature of the conductor at which the fault occurs (in C) k = 1.166 for aluminium and 0.52 for copper t = duration of fault (in seconds) Example 28.2 Determine the minimum conductor size for a fault level of 50 kA for one second for an aluminium conductor. Assuming the temperature rise to be 100C and the initial temperature of the conductor at the instant of the fault 85C then 100 = 1.166 100 50 000 (1 + 0.00403 85) 1 2 ¥ Ê Ë Á ˆ ¯ ˜ ¥ ¥ ¥ A or 100 = 1.166 100 50 000 1.34255 2 ¥ Ê Ë Á ˆ ¯ ˜ ¥ A or A = 50 000 100 1.166 1.34255 ¥ ¥ 625.6 mm 2 for pure aluminium or 617.6 mm 2 for alloys of aluminium (assuming a 20 = 0.00363) The standard size of aluminium flat nearest to this is 50.8 mm ¥ 12.7 mm or (2'' ¥ 1 / 2 '' ) or any other equivalent flat size (Tables 30.4 or 30.5). This formula is also drawn in the form of curves as shown in Figure 28.5, I A t sc ¥ (I sc in kA) versus final temperature. From these curves the minimum conductor size can be easily found for any fault level, for both aluminium and copper conductors and for any desired end temperature. As in the above case 100 = 1.166 100 1.34255 sc 2 ¥ Ê Ë ˆ ¯ ¥ I A t or I A t sc 4 6 = 10 1.166 1.34255 10 ¥ ¥ = 0.0799 (I sc is in kA) Generalizing, I A t sc = 0.0799 for an operating temperature at 85 C and end temperature on fault at 185 C ¥ (28.2) Therefore, for the same parameters as in Example 28.2 A = 50 0.0799 1 625.8 mm 2 ¥ A small difference, if any, between this and that calculated above may be due to approximation and interpolation only. This minimum conductor size will take account of the heating effects during the fault, irrespective of the current rating of the conductor. This much conductor size is essential for this fault level even for very low current ratings. However, the required conductor size may be more than this also, depending upon the continuous current it has to carry, as discussed later. Example 28.3 If the conductor is of copper then, assuming the same parameters, 100 = 0.52 100 50 000 (1 + 0.00393 85) 1 2 ¥ Ê Ë Á ˆ ¯ ˜ ¥ ¥ ¥ A or A = 50 000 0.52 100 1.33405 100 ¥ ¥ Ê Ë Á ˆ ¯ ˜ = 416 mm 2 Copper is two thirds the size of aluminium for the same parameters. The melting point of copper at almost 1083C (Table 30.1) is approximately 1.5 times that of aluminium at 660C. These melting points are also located on the nomograms in Figure 28.6. Refer to nomograms (a) and (b) for aluminium and (c) for copper conductors. The same area can also be obtained from the copper curves of Figure 28.5. Assuming the same end temperature at 185C, then corresponding to the operating curve of 85C, I A t sc = 0.12 (28.3) and for the same parameters as in Example 28.3, 50 1 = 0.12 A or A 416.7 mm 2 *Welding of flexible joints should preferably be carried out with high-injection pressing (welding by press heating), eliminating the use of welding rods.

Transcript of Busbar Sizing for 50ka for 1 Sec

Page 1: Busbar Sizing for 50ka for 1 Sec

Auth

or: K.

C. A

graw

al

ISBN

: 81

-901

642-

5-2

Carrying power through metal-enclosed bus systems 28/999

The welded portion, such as at the flexible joints*, shouldalso be safe up to this temperature. Welding of edges isessential to seal off flexible ends to prevent them frommoisture condensation, oxidation and erosion of metal.Tin or lead solder starts softening at around thistemperature and should not be used for this purpose. Forjoints other than flexibles it is advisable to use oxy-acetylene gas welding or brazing for copper and tungsteninert gas (TIG) or metal inert gas (MIG) welding foraluminium joints.

NoteIn case of copper also, the end temperature is considered as 185∞Conly. Although this metal can sustain much higher temperaturethan this, without any adverse change in its mechanical properties,merely as a consideration to Table 32.3, and to safeguard othercomponents, insulations and welded parts etc., used in the samecircuit.

To determine the minimum size of conductor for arequired fault level, Isc, to account for the thermal effectsone can use the following formula to determine theminimum size of conductor for any fault level:

q qtsc

2

20 = 100

(1 + ) k IA

t◊ Êˈ¯ ◊ µ ◊ (28.1)

whereqt = temperature rise (in ∞C)

Isc = symmetrical fault current r.m.s. (in Amps)A = cross-sectional area of the conductor (in mm2)

µ20 = temperature coefficient of resistance at 20∞C/∞C,which as in Table 30.1 is 0.00403 for purealuminium and 0.00363 for aluminium alloys and0.00393 for pure copper

q = operating temperature of the conductor at whichthe fault occurs (in ∞C)

k = 1.166 for aluminium and 0.52 for coppert = duration of fault (in seconds)

Example 28.2Determine the minimum conductor size for a fault level of 50kA for one second for an aluminium conductor.

Assuming the temperature rise to be 100∞C and the initialtemperature of the conductor at the instant of the fault 85∞C then

100 = 1.166100

50 000

(1 + 0.00403 85) 12

¥ ÊËÁ

ˆ¯̃

¥ ¥ ¥A

or 100 = 1.166100

50 000

1.342552

¥ ÊËÁ

ˆ¯̃

¥A

or A = 50 000100

1.166 1.34255¥ ¥

� 625.6 mm2 for pure aluminium

or � 617.6 mm2 for alloys of aluminium

(assuming a20 = 0.00363)

The standard size of aluminium flat nearest to this is 50.8

mm ¥ 12.7 mm or (2'' ¥ 1/2'' ) or any other equivalent flat size(Tables 30.4 or 30.5).

This formula is also drawn in the form of curves as shown

in Figure 28.5, IA

tsc ¥ (Isc in kA) versus final temperature.

From these curves the minimum conductor size can be easilyfound for any fault level, for both aluminium and copperconductors and for any desired end temperature. As in theabove case

100 = 1.166100

1.34255 sc2

¥ ÊË

ˆ¯ ¥ ◊

IA

t

orIA

tsc4

6 = 101.166 1.34255 10¥ ¥

= 0.0799 (Isc is in kA)

Generalizing,

IA

tsc = 0.0799 for an operating temperatureat 85 C and end temperature on fault at 185 C

¥∞

∞(28.2)

Therefore, for the same parameters as in Example 28.2

A = 50

0.0799 1 625.8 mm2¥ �

A small difference, if any, between this and that calculatedabove may be due to approximation and interpolation only.

This minimum conductor size will take account ofthe heating effects during the fault, irrespective of thecurrent rating of the conductor. This much conductorsize is essential for this fault level even for very lowcurrent ratings. However, the required conductor sizemay be more than this also, depending upon the continuouscurrent it has to carry, as discussed later.

Example 28.3If the conductor is of copper then, assuming the sameparameters,

100 = 0.52100

50 000 (1 + 0.00393 85) 12

¥ ÊËÁ

ˆ¯̃

¥ ¥ ¥A

or A = 50 000 0.52100

1.33405100

¥ ¥ÊËÁ

ˆ¯̃

= 416 mm2

Copper is two thirds the size of aluminium for the sameparameters. The melting point of copper at almost 1083∞C(Table 30.1) is approximately 1.5 times that of aluminiumat 660∞C. These melting points are also located on thenomograms in Figure 28.6. Refer to nomograms (a) and(b) for aluminium and (c) for copper conductors. Thesame area can also be obtained from the copper curvesof Figure 28.5. Assuming the same end temperature at185∞C, then corresponding to the operating curve of 85∞C,

IA

tsc = 0.12 (28.3)

and for the same parameters as in Example 28.3,50 1 = 0.12A

or A � 416.7 mm2

*Welding of flexible joints should preferably be carried out withhigh-injection pressing (welding by press heating), eliminating theuse of welding rods.