BUILDING WATER SUPPLY & SANITARY INSTALLATION · building water supply & sanitary installation ....
Transcript of BUILDING WATER SUPPLY & SANITARY INSTALLATION · building water supply & sanitary installation ....
![Page 1: BUILDING WATER SUPPLY & SANITARY INSTALLATION · building water supply & sanitary installation . chapter 4 . aait.ced zerihun alemayehu](https://reader031.fdocuments.net/reader031/viewer/2022021420/5ae3f6af7f8b9a495c8de49d/html5/thumbnails/1.jpg)
& BUILDING WATER SUPPLY
SANITARY INSTALLATION CHAPTER 4
AAiT.CED ZERIHUN ALEMAYEHU
![Page 2: BUILDING WATER SUPPLY & SANITARY INSTALLATION · building water supply & sanitary installation . chapter 4 . aait.ced zerihun alemayehu](https://reader031.fdocuments.net/reader031/viewer/2022021420/5ae3f6af7f8b9a495c8de49d/html5/thumbnails/2.jpg)
BUILDING WATER SUPPLY
![Page 3: BUILDING WATER SUPPLY & SANITARY INSTALLATION · building water supply & sanitary installation . chapter 4 . aait.ced zerihun alemayehu](https://reader031.fdocuments.net/reader031/viewer/2022021420/5ae3f6af7f8b9a495c8de49d/html5/thumbnails/3.jpg)
Purpose Provide potable water supply to each fixture from water sources
For sanitation and fire protection
![Page 4: BUILDING WATER SUPPLY & SANITARY INSTALLATION · building water supply & sanitary installation . chapter 4 . aait.ced zerihun alemayehu](https://reader031.fdocuments.net/reader031/viewer/2022021420/5ae3f6af7f8b9a495c8de49d/html5/thumbnails/4.jpg)
Types of System
• Direct connection from the main
• Pumped system
![Page 5: BUILDING WATER SUPPLY & SANITARY INSTALLATION · building water supply & sanitary installation . chapter 4 . aait.ced zerihun alemayehu](https://reader031.fdocuments.net/reader031/viewer/2022021420/5ae3f6af7f8b9a495c8de49d/html5/thumbnails/5.jpg)
System Selection
• Demand (pressure and flow) • Type of building occupancy • Aesthetics • Economy • Use • Maintainability • Flexibility to failure
![Page 6: BUILDING WATER SUPPLY & SANITARY INSTALLATION · building water supply & sanitary installation . chapter 4 . aait.ced zerihun alemayehu](https://reader031.fdocuments.net/reader031/viewer/2022021420/5ae3f6af7f8b9a495c8de49d/html5/thumbnails/6.jpg)
Storage Cisterns • Capacity
– Type and use of buildings – Likelihood and frequency of supply breakdown – Number of occupants – Pattern of use
![Page 7: BUILDING WATER SUPPLY & SANITARY INSTALLATION · building water supply & sanitary installation . chapter 4 . aait.ced zerihun alemayehu](https://reader031.fdocuments.net/reader031/viewer/2022021420/5ae3f6af7f8b9a495c8de49d/html5/thumbnails/7.jpg)
Pipe sizing
• Layout to each fixtures
• Assume a pipe diameter
• Determine the flow rate
• Determine the effective pipe length
• Calculate the permissible loss of head
• Determine the pipe diameter
![Page 8: BUILDING WATER SUPPLY & SANITARY INSTALLATION · building water supply & sanitary installation . chapter 4 . aait.ced zerihun alemayehu](https://reader031.fdocuments.net/reader031/viewer/2022021420/5ae3f6af7f8b9a495c8de49d/html5/thumbnails/8.jpg)
Fixtures flow rate Loading units- a factor or number given to an appliance relating flow rate to the duration and frequency of use (probable usage).
For simultaneous flow
Q= 𝟎.𝟐𝟐 𝒁𝟏 + 𝒁𝟐 + ⋯+ 𝒁𝒏
𝑍 =𝑞
0.25
2
![Page 9: BUILDING WATER SUPPLY & SANITARY INSTALLATION · building water supply & sanitary installation . chapter 4 . aait.ced zerihun alemayehu](https://reader031.fdocuments.net/reader031/viewer/2022021420/5ae3f6af7f8b9a495c8de49d/html5/thumbnails/9.jpg)
Fixtures flow rate
12 wash basins x 0.5 = 6 10 WCs x 0.5 = 5 2 urinals x 0.5 = 1 2 sinks x 1 = 2 Total loading units = 14
Q = 0.25 14 = 0.935 𝑙/𝑠𝑠𝑠
![Page 10: BUILDING WATER SUPPLY & SANITARY INSTALLATION · building water supply & sanitary installation . chapter 4 . aait.ced zerihun alemayehu](https://reader031.fdocuments.net/reader031/viewer/2022021420/5ae3f6af7f8b9a495c8de49d/html5/thumbnails/10.jpg)
Effective pipe length Measure pipe length + equivalent pipe length
![Page 11: BUILDING WATER SUPPLY & SANITARY INSTALLATION · building water supply & sanitary installation . chapter 4 . aait.ced zerihun alemayehu](https://reader031.fdocuments.net/reader031/viewer/2022021420/5ae3f6af7f8b9a495c8de49d/html5/thumbnails/11.jpg)
Effective pipe length
![Page 12: BUILDING WATER SUPPLY & SANITARY INSTALLATION · building water supply & sanitary installation . chapter 4 . aait.ced zerihun alemayehu](https://reader031.fdocuments.net/reader031/viewer/2022021420/5ae3f6af7f8b9a495c8de49d/html5/thumbnails/12.jpg)
Head loss calculation
![Page 13: BUILDING WATER SUPPLY & SANITARY INSTALLATION · building water supply & sanitary installation . chapter 4 . aait.ced zerihun alemayehu](https://reader031.fdocuments.net/reader031/viewer/2022021420/5ae3f6af7f8b9a495c8de49d/html5/thumbnails/13.jpg)
Head loss calculation
![Page 14: BUILDING WATER SUPPLY & SANITARY INSTALLATION · building water supply & sanitary installation . chapter 4 . aait.ced zerihun alemayehu](https://reader031.fdocuments.net/reader031/viewer/2022021420/5ae3f6af7f8b9a495c8de49d/html5/thumbnails/14.jpg)
Determine pipe diameter
For diameter of 20 mm With Q = 0.93 l/sec From the graph we’ve: Head loss = 0.42 m/m Ok! V = 2.8 m/s hmmmm!
For diameter of 25 mm With Q = 0.93 l/sec From the graph we’ve: Head loss = 0.15 m/m ok! V = 1.8 m/s ok!