BUILDING SCIENCE INTEGRATION PROJECT
Transcript of BUILDING SCIENCE INTEGRATION PROJECT
SCHOOL OF ARCHITECTURE, BUILDING & DESIGN
BACHELOR OF SCIENCE (HONS) IN ARCHITECTURE
PROJECT 2: INTEGRATION PROJECT
BUILDING SCIENCE 2 [BLD61303]
NAME : TEOH HUI YU
STUDENT ID : 0313701
LECTURER : MR. AZIM
2
BUILDING SCIENCE 2 | PROECT 2: INTEGRATION PROJECT
CONTENT
1.0 INTRODUCTION TO STUDIO
2.0 LIGHTING
2.1 Day Lighting (Children Playing Area)
2.2 Day Lighting (Discussion room)
2.3 Artificial lighting (Children Playing Area)
2.4 Ecotect analysis
2.5 Artificial lighting (Discussion room)
2.6 PSALI (Children Playing Area)
2.7 PSALI (Discussion room)
3.0 ACOUSTIC
3.1 Reverberation Time, RT (Discussion Room)
3.2 Sound Reduction Index, SRI (Children Playing Area)
4.0 REFERENCES
3
BUILDING SCIENCE 2 | PROECT 2: INTEGRATION PROJECT
1.0 INTRODUCTION TO STUDIO
Name of building : Sentul Science Library
Location : Jalan Sultan Azlan Shah, Sentul, KL
Building size : 1800 β 2000 square meter
Figure: Location plan
Aim:
We are required to design an urban contemporary community library within a
dense inner-city street of Sentul, and takes into consideration an understanding of
applicable current legislations, building technologies and cultural imperatives of
the site and its surrounding.
4
BUILDING SCIENCE 2 | PROECT 2: INTEGRATION PROJECT
2.0 LIGHTING
2.1 Day Lighting (Children Playing Area)
According to MS1525, Daylight Factor distribution as below:
Daylight Factor (%) Distribution
>6 Very bright with thermal & glare problem
3-6 Bright
1-3 Average
0-1 Dark
Figure 01: Location of children playing area at first floor.
5
BUILDING SCIENCE 2 | PROECT 2: INTEGRATION PROJECT
The selected space (Children Playing Area) is located at the first floor, with double
volume space. Children Playing Area are basically a βglass blockβ inside the library.
It is surrounded by aluminum frame and laminated glass panel. The North East
facing area receive high amount of natural daylighting into the space. Minimal
artificial lighting will be required in this space during the day, and required artificial
lighting during the night time.
Figure 02: A zoom in plan showing the direction of sunlight penetrate into the children playing area.
6
BUILDING SCIENCE 2 | PROECT 2: INTEGRATION PROJECT
2.2 Day Lighting (Discussion room)
According to MS1525, Daylight Factor distribution as below:
Daylight Factor (%) Distribution
>6 Very bright with thermal & glare problem
3-6 Bright
1-3 Average
0-1 Dark
Figure 03: Location of discussion room on second floor.
7
BUILDING SCIENCE 2 | PROECT 2: INTEGRATION PROJECT
The selected space (discussion room) is located at second floor in the library. It is
a cantilever room connected to the mezzanine floor. The discussion room is mostly
concrete, with laminated glass panel facing towards the green wall structure, which
allow the sunlight to penetrate into the space. Artitifical lighting is required to make
sure the whole discussion room are achieve the lighting requirement in a space.
Figure 04: the laminated glass panel on the other side of the discussion room allow daylight to penetrate in.
8
BUILDING SCIENCE 2 | PROECT 2: INTEGRATION PROJECT
Task Illuminance(Lux) Example of Applications
Lighting for infrequently used area
20 100 100 100 100 150 100 100 100 100 200 200
Minimum service illuminance Interior walkway and car park Hotel bedroom Lift interior Corridor, passageway, stairs Escalator, travellator Entrance and exit Staff changing room, cleaner room Laboratories, stores Entrance hall, lobbies, waiting room Inquiry desk Gate house
Lighting for working interiors
300-400 300-400 150 200 150-300 150 150 100 100 300-500 200-750 300 500 1000
Infrequent reading and writing General offices, shops and stores Reading and writing Drawing office Restroom Restaurant, canteen, cafeteria Kitchen Lounge Bathroom Toilet Bedroom Class room, Library Shop/ supermarket/ Department store Store
Localized lighting for exacting task
2000 Museum and gallery Proof reading Exacting drawing Detailed and precise work
Table: Recommended average illuminance levels.
9
BUILDING SCIENCE 2 | PROECT 2: INTEGRATION PROJECT
2.3 Artificial lighting (Children Playing Area)
Children playing area located at first floor, which strategy location can allow the
space to receive daylight from day to night. Artificial lighting is still required in the
space especially during night. According to MS 1525, the minimum lighting
required is 200 lux.
Figure 05: Location of children playing area in first floor plan
Component Material Color Surface finish Reflectance value (%)
Wall Concrete Dark grey Matte 15
Aluminum frame
Black Matte 10
Laminated glass
Transparent Glossy 8
Floor Concrete Dark grey Matte 15
Ceiling Concrete Dark grey Matte 15
Door Glass door Transparent Glossy 8
Aluminum frame
Black Matte 10
Furniture Fabric chair Light green Matte 45
Aluminum table
White Glossy 30
10
BUILDING SCIENCE 2 | PROECT 2: INTEGRATION PROJECT
Light type (LM-X7 LED Downlight)
Application Downlight
Type of light bub
Material of fixture Aluminum
Nominal life (hours) 50,000
Wattage Range (W) 44
CRI 85
Color temperature (K) 3000
Color White
Lumens 3735
Lumen Method Calculation
Location First floor, double volume space
Dimension of space (m) 9 x 8.5
Total Floor Area/ A (mΒ²) 76.5
Type of lighting fixture LED ceiling downlight
Lumens 3735
Height of Luminaire (M) 7.5
Height of work level (M) 0.8
Mounting height 6.7
Assumption Reflection factors Ceiling : 0.3 Floor : 0.3 Wall : 0.5
Room Index π πΌ = (
πΏ π₯ π
π»π (πΏ + π))
π πΌ = (9 π₯ 8.5
6.7(9 + 8.5))
= 0.65
Utilization factor (UF) 0.46
11
BUILDING SCIENCE 2 | PROECT 2: INTEGRATION PROJECT
Maintenance factor (MF) 0.8
Standard Illuminance 200
Number of light required π = (
πΈπ₯π΄
πΉ π₯ ππΉ π₯ ππΉ)
π = (200π₯76.5
3735 π₯ 0.46 π₯ 0.8)
= 11 nos
Fitting layout by approximately (m) Smax = 1.0 x Hm = 1.0 x 6.7 = 6.7 m
12
BUILDING SCIENCE 2 | PROECT 2: INTEGRATION PROJECT
2.4 Ecotect Analysis
Figure 06: Daylighting contour diagram
Figure 07: Artificial lighting contour diagram
According to the artificial lighting contour diagram of children playing area, it shows
that the intensity of light is highest in the center of space, where the light bulbs are
allocate. During night, the total amount of 12 light bulbs are on to provide sufficient
lighting to the space. The light intensity are getting lower when far from the location
of light bulbs.
13
BUILDING SCIENCE 2 | PROECT 2: INTEGRATION PROJECT
2.5 Artificial lighting (Discussion room)
There are total of two discussion room which can be found at second floor. For the
selected discussion room, the glass panel are facing outwards which allow natural
daylighting to enter the room. The discussion room are mostly concrete to prevent
undesired glare penetrate into the space, and also for privacy purpose. Based on
MS 1525, the minimum lighting required is 200 lux.
Figure 08: Location of discussion room on second floor plan.
Component Material Color Surface finish Reflectance value (%)
Wall Concrete White Matte 15
Aluminum frame
Black Matte 10
Clear glass Transparent Glossy 8
Floor Concrete Light grey Matte 15
Ceiling Concrete Light grey Matte 15
Door Glass door Transparent Glossy 8
Aluminum frame
Black Matte 10
Furniture Fabric chair Light green Matte 45
Wooden table Brown Matte 30
14
BUILDING SCIENCE 2 | PROECT 2: INTEGRATION PROJECT
Light type (10W E27 LED Pendant Light)
Application Pendant light
Type of light bub
Material of fixture Aluminum
Nominal life (hours) 40,000
Wattage Range (W) 10
CRI 85
Color temperature (K) 2700
Color Warm white
Lumens 810
Lumen Method Calculation
Location Second floor
Dimension of space (m) 4 x 3
Total Floor Area/ A (mΒ²) 12
Type of lighting fixture LED ceiling pendant
Lumens 810
Height of Luminaire (M) 2.5
Height of work level (M) 0.8
Mounting height 1.7
Assumption Reflection factors Ceiling : 0.3 Floor : 0.3 Wall : 0.5
Room Index π πΌ = (
πΏ π₯ π
π»π (πΏ + π))
π πΌ = (4 π₯ 3
1.7(4 + 3))
= 1.0
Utilization factor (UF) 0.46
Maintenance factor (MF) 0.8
Standard Illuminance 200
Number of light required π = (
πΈπ₯π΄
πΉ π₯ ππΉ π₯ ππΉ)
15
BUILDING SCIENCE 2 | PROECT 2: INTEGRATION PROJECT
π = (200π₯12
810 π₯ 0.46π₯ 0.8)
= 8nos
Fitting layout by approximately (m) Smax = 1.0 x Hm = 1.0 x 1.7 = 1.7m
16
BUILDING SCIENCE 2 | PROECT 2: INTEGRATION PROJECT
2.6 PSALI (Children Playing Area)
Figure 09: Lighting arrangement in children playing area
Diagram above showing the lighting arrangement in children playing area. Children
playing area receive high amount of natural lighting as it is surrounded by
laminated glass wall panel and its double volume space allow more daylight to
penetrate into the area. According to MS 1525, children playing area required 200
lux. From the calculation, 12 nos of lights are required in the space. The lighting
arrangement are divided into 4 x 3 rows. It can be control by 3 switches.
Section
Figure 10: Day time Figure 11: Night time
During daytime, more than half of the children area receive natural daylighting. The
artificial lights are only required at the inner side of the children playing area. During
night time, the space will needed all artificial lighting to function to support the
lighting in that area. The lighting arrangement can reduce the amount of artificial
lighting used during the day, and also ensure the sufficiency of lighting during the
night.
17
BUILDING SCIENCE 2 | PROECT 2: INTEGRATION PROJECT
2.7PSALI (Discussion room)
Figure 12: Lighting arrangement in discussion room
Diagram above showing the lighting arrangement in Discussion room. One side of
discussion room are glass wall which allow daylighting to penetrate in, while the
other side of space required artificial lighting to fulfill the lighting requirement.
According to MS 1525, discussion room required total of 200 lux. Based on the
calculation, there are 8 nos of lights required in the space. The lights are divided
into two switches, which are easier to control the light amount required according
to the occupants need.
Section
Figure 13: Day time Figure 14: Night time
During the day, only 4 nos of artificial light need to switch on, which is the inner
side of the room. During the night, all the artificial light need to be switched on.
18
BUILDING SCIENCE 2 | PROECT 2: INTEGRATION PROJECT
3.0 ACOUSTIC
3.1 Reverberation Time, RT (Discussion Room)
Materials Absorption Coefficient at 500 Hz during non-peak hour
Component Material Absorption coefficient (500Hz), s
Area, A (mΒ²) Sound Absorption (SA)
Wall Concrete 0.05 17.5 0.875
Aluminum frame 0.25 1.2 0.3
Clear glass 0.1 12.5 1.25
Floor Concrete 0.05 12 0.6
Ceiling Concrete 0.05 12 0.6
Door Glass door 0.1 2 0.2
Aluminum frame 0.25 0.3 0.075
Furniture Fabric chair 0.2 2.4 0.48
Wooden table 0.1 3.2 0.32
Occupants (non-peak)
0.46 4 1.84
Total Absorption 6.54
Volume of space, V= 4 x 3 x 2.5
= 30 mΒ²
π π = 0.16 π₯ ππππ’ππ ππ π ππππ
π΄ππ ππππ‘πππ ππππ
π π = 0.16 π₯ 30
6.54
RT = 0.73s
Conclusion
During non-peak hour, discussion room has the reverberation time of 0.73 seconds,
which fall on the standard comfortable reverberation between 0.6 to 0.8s. Hence,
the reverberation time for discussion room has meet the standard requirement and
thus provide a comfortable speech environment for the occupants.
19
BUILDING SCIENCE 2 | PROECT 2: INTEGRATION PROJECT
Materials Absorption Coefficient at 500 Hz during peak hour
Component Material Absorption coefficient (500Hz), s
Area, A (mΒ²) Sound Absorption (SA)
Wall Concrete 0.05 17.5 0.875
Aluminum frame 0.25 1.2 0.3
Clear glass 0.1 12.5 1.25
Floor Concrete 0.05 12 0.6
Ceiling Concrete 0.05 12 0.6
Door Glass door 0.1 2 0.2
Aluminum frame 0.25 0.3 0.075
Furniture Fabric chair 0.2 2.4 0.48
Wooden table 0.1 3.2 0.32
Occupants (non-peak)
0.46 6 2.76
Total Absorption 7.46
Volumne of space, V= 4 x 3 x 2.5
= 30 mΒ²
π π = 0.16 π₯ ππππ’ππ ππ π ππππ
π΄ππ ππππ‘πππ ππππ
π π = 0.16 π₯ 30
7.46
RT = 0.64s
Conclusion
During peak hour, the reverberation time for discussion room is 0.64s. With the
total 6 occupants, the reverberation time still falls within the comfort reverberation
time between 0.6 to 0.8s. This has shown that the acoustic absorption of
discussion room is sufficient.
20
BUILDING SCIENCE 2 | PROECT 2: INTEGRATION PROJECT
Materials Absorption Coefficient at 2000 Hz during non-peak hour
Component Material Absorption coefficient (500Hz), s
Area, A (mΒ²) Sound Absorption (SA)
Wall Concrete 0.05 17.5 0.875
Aluminum frame 0.25 1.2 0.3
Clear glass 0.07 12.5 0.875
Floor Concrete 0.05 12 0.6
Ceiling Concrete 0.05 12 0.6
Door Glass door 0.07 2 0.14
Aluminum frame 0.25 0.3 0.075
Furniture Fabric chair 0.2 2.4 0.48
Wooden table 0.1 3.2 0.32
Occupants (non-peak)
0.51 4 2.04
Total Absorption 6.305
Volumne of space, V= 4 x 3 x 2.5
= 30 mΒ²
π π = 0.16 π₯ ππππ’ππ ππ π ππππ
π΄ππ ππππ‘πππ ππππ
π π = 0.16 π₯ 30
6.305
RT = 0.76s
Conclusion
During non-peak hour at 2000Hz, with four person occupying the space,
discussion room has the reverberation time of 0.76 seconds, which fall on the
standard comfortable reverberation between range of 0.6 to 0.8s. Hence, the
reverberation time for discussion room has meet the standard requirement and
thus provide a comfortable speech environment for the occupants.
21
BUILDING SCIENCE 2 | PROECT 2: INTEGRATION PROJECT
Materials Absorption Coefficient at 2000 Hz during peak hour
Component Material Absorption coefficient (500Hz), s
Area, A (mΒ²) Sound Absorption (SA)
Wall Concrete 0.05 17.5 0.875
Aluminum frame 0.25 1.2 0.3
Clear glass 0.07 12.5 0.875
Floor Concrete 0.05 12 0.6
Ceiling Concrete 0.05 12 0.6
Door Glass door 0.07 2 0.14
Aluminum frame 0.25 0.3 0.075
Furniture Fabric chair 0.2 2.4 0.48
Wooden table 0.1 3.2 0.32
Occupants (non-peak)
0.51 6 3.06
Total Absorption 7.325
Volumne of space, V= 4 x 3 x 2.5
= 30 mΒ²
π π = 0.16 π₯ ππππ’ππ ππ π ππππ
π΄ππ ππππ‘πππ ππππ
π π = 0.16 π₯ 30
7.325
RT = 0.66s
Conclusion
During peak hour at 2000Hz, with total of six person occupying the space,
discussion room has the reverberation time of 0.66 seconds, falls within the
comfort reverberation time between 0.6 to 0.8s. Hence, we can conclude that
acoustic absorption of discussion room is sufficient.
22
BUILDING SCIENCE 2 | PROECT 2: INTEGRATION PROJECT
3.2 Sound Reduction Index, SRI (Children Playing Area)
Sound Reduction Index (SRI) is used to measure the sound insulation of the
materials such as wall, window, door and etc. The sound insulation of a material
can aid in reduce the sound level transmit from space into another space.
Figure 15: Relationship between children playing area and adjacent spaces.
Transmission Coefficient of material:
Component Material Surface Area, mΒ² SRI , dB
Wall Concrete 34 42
Laminated glass 211.5 26
Aluminum frame 10 44
Door Glass door 4 26
Aluminum frame 0.5 44
Formula:
ππ πΌ = 10 log (1
πππππ πππ π πππ πππππππππππ‘)
23
BUILDING SCIENCE 2 | PROECT 2: INTEGRATION PROJECT
For concrete wall,
ππ πΌ = 10 log (1
πππππ πππ π πππ πππππππππππ‘)
42 = 10 log (1
πππππ πππ π πππ π€πππ)
Transmission of wall = 6.31 x 10β5
For laminated glass,
ππ πΌ = 10 log (1
πππππ πππ π πππ πππππππππππ‘)
26 = 10 log (1
πππππ πππ π πππ π€πππ)
Transmission of wall = 2.51 x 10β3
For aluminum frame,
ππ πΌ = 10 log (1
πππππ πππ π πππ πππππππππππ‘)
44 = 10 log (1
πππππ πππ π πππ π€πππ)
Transmission of wall = 3.98 x 10β5
For glass door,
ππ πΌ = 10 log (1
πππππ πππ π πππ πππππππππππ‘)
26 = 10 log (1
πππππ πππ π πππ π€πππ)
Transmission of wall = 2.51x 10β3
24
BUILDING SCIENCE 2 | PROECT 2: INTEGRATION PROJECT
For aluminum frame,
ππ πΌ = 10 log (1
πππππ πππ π πππ πππππππππππ‘)
44 = 10 log (1
πππππ πππ π πππ π€πππ)
Transmission of wall = 3.98 x 10β5
Calculation for children playing areaβs SRI:
Material Surface Area, mΒ²
SRI (dB) Transmission coefficient (T)
ST
Concrete 34 42 6.31 x 10β5 2.14 x 10β3
Laminated glass 211.5 26 2.51 x 10β3 0.53
Aluminum frame 10 44 3.98 x 10β5 3.98 x 10β4
Glass door 4 26 2.51x 10β3 0.01
Aluminum frame 0.5 44 3.98 x 10β5 1.99 x 10β5
Total surface area 260
Total sound reduction index,
πππ£πππππ = (Sn β Tn
πππ‘ππ π π’πππππ ππππ)
πππ£πππππ = (2.14 x 10β3 + 0.53 + 3.98 x 10β4 + 0.01 + 1.99 x 10β5
260)
= 2.09 x 10β3
ππ πΌ = 10 log (1
πππππ πππ π πππ πππππππππππ‘)
ππ πΌ = 10 log (1
2.09 x 10β3)
= 26.8dB
25
BUILDING SCIENCE 2 | PROECT 2: INTEGRATION PROJECT
STC Rating
STC Rating Speech heard through wall or floor
Noise control level
25 Normal speech understandable
poor
30 Loud speech understandable
Marginal
40 Loud speech audible as murmur but unintelligible
Good
50 Loud speech barely audible
Very good
55 and above Loud speech not heard Excellent
Conclusion
Based on calculation, the overall Sound Reduction Index for children playing area
is 26.8dB. According to the general sound environment, the values that
categorized less than 35dB are meaning normal speech can be understood quite
easily and distinctly through the walls and transmit the sound to adjacent spaces.
The reason why the SRI value are low is because of the double volume laminated
glass wall. To further reduce the sound transmit into other space, few steps will be
taken. For example are the choice chosen on fabric furniture, the use of
soundproof glass panel, use carpet to cover the concrete flooring or using sound
proofing flooring materials, and also may consider the use of acoustical wall panel
for sound absorption.
26
BUILDING SCIENCE 2 | PROECT 2: INTEGRATION PROJECT
4.0 REFERENCES
Architectsβ Data. (2012). Chicester: John Wiley and Sons.
Noise: Building Acoustic and Reverberation Time. (n.d.) Retrived July 2, 2016,
from http;//www.noisenet.org/Noise_Room_Acoustic_Reverb.htm
Reverberation Time. (n.d.). Retrieved July 2, 2016, from
http://hyperphysics.phy-astr.gsu.edu/hbase/acoustic/revtim.html
Sound Absorption Coefficients of architectural acoustical materials. (1957). New
York.