    EXTERNAL ALARM ALLOCATIONREQUIREMENTS SPEC. 1 (6)

    Prepared (also subject responsible if other) No.

    OC/ENP/SO/D/S Alec Atienza DIG01.0004.045.149 UenApproved Checked Date Rev Reference

    OC/ENP/SO/D/SC Khairy Hassan 4/18/2005 A

    PROJECT:DMPI Ph 4A BASE TRANSCEIVER STATION (GSM1800, RBS2206, TMR9202)

    SITE : ALL BTS - CHANGEOUT SITES (VISMIN)

    EQUIPMENT TYPE : BTS SITE 16 External Alarms

    ALARM

    NO.

    DESIGNATION ID

    NO.

    TYPE SEVERITY

    LEVEL

    01 Illegal Entry 0 Breaking 1

    02 ACU Alarm 1 Breaking 1

    03 High Temp. Alarm 2 Breaking 1

    04 Water Alarm 3 Breaking 1

    05 Fire Alarm 4 Breaking 1

    06 AC Mains Failure

    CabinAlarmS

    ystem

    5 Breaking 2

    07 Battery Low 6 Breaking 1

    08 Rectifier Failure 7 Breaking 1

    09 Rectifier MCB Alarm 8 Breaking 1

    10 Rectifier High Temp. 9 Breaking 1

    11 LVDS Alarm

    RectifierC

    abinet

    A Breaking 1

    12 Obstruction Light Failure B Breaking/Closing 2

    13 Genset Fault C Breaking 1

    14 Battery Charger Fail D Breaking 1

    15 Day/Bulk Tank Fuel Low E Breaking 2

    16 Load on Genset GeneratorAlarm

    System

    F Breaking 2

    Type Indicates the condition for the contact of the each individual alarm. Normally Closed (N.C.) Contacts indicates -Breaking Normally Open (N.O.) Contacts indicates - Closing

    Severity Level Indicates the severity of the alarm. Priority alarm indicates 1 Non-priority alarm indicates 2

  • 8/12/2019 BTS TRM External Alarms R3A

    3/30

  • 8/12/2019 BTS TRM External Alarms R3A

    4/30

    EXTERNAL ALARM ALLOCATIONREQUIREMENTS SPEC. 2 (6)

    Prepared (also subject responsible if other) No.

    OC/ENP/SO/D/S Alec Atienza DIG01.0004.045.149 UenApproved Checked Date Rev Reference

    OC/ENP/SO/D/SC Khairy Hassan 4/18/2005 A

    PROJECT:DMPI Ph 4A BASE TRANSCEIVER STATION (GSM1800, RBS2206, TMR9202)

    SITE : ALL BTS - NEW SITES (VISMIN)

    EQUIPMENT TYPE : BTS SITE 16 External Alarms

    ALARM

    NO.

    DESIGNATION ID

    NO.

    TYPE SEVERITY

    LEVEL

    01 Illegal Entry 0 Breaking 1

    02 ACU Alarm 1 Breaking 103 High Temp. Alarm 2 Breaking 1

    04 Water Alarm 3 Breaking 1

    05 Fire AlarmCabinAlarmS

    ystem

    4 Breaking 1

    06 Rectifier A1 Alarm 5 Breaking 1

    07 Rectifier A2 Alarm 6 Breaking 1

    08 Rectifier O1 Alarm 7 Breaking 2

    09 AC Mains Failure

    RectifierCabinet

    8 Breaking 210 Obstruction Light Failure 9 Breaking/Closing 2

    11 Genset Fault A Breaking 1

    12 Battery Charger Fail B Breaking 1

    13 Day Tank Fuel Low C Breaking 2

    14 Bulk Tank Fuel Low D Breaking 2

    15 Load on Genset E Breaking 2

    16 SPAREGeneratorAlarmS

    ystem

    F

    Type Indicates the condition for the contact of the each individual alarm. Normally Closed (N.C.) Contacts indicates -Breaking Normally Open (N.O.) Contacts indicates - Closing

    Severity Level Indicates the severity of the alarm. Priority alarm indicates 1 Non-priority alarm indicates 2

  • 8/12/2019 BTS TRM External Alarms R3A

    5/30

  • 8/12/2019 BTS TRM External Alarms R3A

    6/30

    ~ See Cable Distribution Diagram for Sub-Distribution Frame, (2/193 18 - IPA 8003 Uen)

    NOTE:

    GENSET ALARM

    MONITORING SYSTEM

    FACILITIES ALARM

    MONITORING SYSTEM,FMS

    RECTIFIER ALARM

    MONITORING SYSTEM

    NERA SDH CABINET

    SUB

    DISTRIBUTION

    FRAME,

    SDF

    A

    B

  • 8/12/2019 BTS TRM External Alarms R3A

    7/30

    EXTERNAL ALARM ALLOCATIONREQUIREMENTS SPEC. 3 (6)

    Prepared (also subject responsible if other) No.

    OC/ENP/SO/D/S Alec Atienza DIG01.0004.045.149 UenApproved Checked Date Rev Reference

    OC/ENP/SO/D/SC Khairy Hassan 4/18/2005 A

    PROJECT:DMPI Ph 4A BASE TRANSCEIVER STATION (GSM1800, RBS2206, TMR9202)

    SITE : ALL REPEATER CHANGEOUT SITES (VISMIN)

    EQUIPMENT TYPE : REPEATER SITE 16 External Alarms(SDH TRANSMISSION ONLY)

    ALARM

    NO.

    DESIGNATION ID

    NO.

    TYPE SEVERITY

    LEVEL

    01 Illegal Entry 01 Breaking 1

    02 ACU Alarm 02 Breaking 1

    03 High Temp. Alarm 03 Breaking 1

    04 Water Alarm 04 Breaking 1

    05 Fire Alarm 05 Breaking 1

    06 AC Mains Failure

    CabinAlarmS

    ystem

    06 Breaking 2

    07 Battery Low 07 Breaking 1

    08 Rectifier Failure 08 Breaking 109 Rectifier MCB Alarm 09 Breaking 1

    10 Rectifier High Temp. 10 Breaking 1

    11 LVDS Alarm

    RectifierCabi

    net

    11 Breaking 1

    12 Obstruction Light Failure 12 Breaking/Closing 2

    13 Genset Fault 13 Breaking 1

    14 Battery Charger Fail 14 Breaking 1

    15 Day/Bulk Tank Fuel Low 15 Breaking 216 Load on Genset G

    ene

    ratorAlarm

    System

    16 Breaking 2

    Type Indicates the condition for the contact of the each individual alarm. Normally Closed (N.C.) Contacts indicates -Breaking Normally Open (N.O.) Contacts indicates - Closing

    Severity Level Indicates the severity of the alarm. Priority alarm indicates 1 Non-priority alarm indicates 2

  • 8/12/2019 BTS TRM External Alarms R3A

    8/30

  • 8/12/2019 BTS TRM External Alarms R3A

    9/30

    EXTERNAL ALARM ALLOCATIONREQUIREMENTS SPEC. 4 (6)

    Prepared (also subject responsible if other) No.

    OC/ENP/SO/D/S Alec Atienza DIG01.0004.045.149 UenApproved Checked Date Rev Reference

    OC/ENP/SO/D/SC Khairy Hassan 4/18/2005 A

    PROJECT:DMPI Ph 4A BASE TRANSCEIVER STATION (GSM1800, RBS2206, TMR9202)

    SITE : ALL REPEATER NEW SITES (VISMIN)

    EQUIPMENT TYPE : REPEATER SITE 16 External Alarms(SDH TRANSMISSION ONLY)

    ALARM

    NO.

    DESIGNATION ID

    NO.

    TYPE SEVERITY

    LEVEL

    01 Illegal Entry 01 Breaking 1

    02 ACU Alarm 02 Breaking 1

    03 High Temp. Alarm 03 Breaking 1

    04 Water Alarm 04 Breaking 1

    05 Fire AlarmCabinAlarmS

    ystem

    05 Breaking 1

    06 Rectifier A1 Alarm 06 Breaking 1

    07 Rectifier A2 Alarm 07 Breaking 1

    08 Rectifier O1 Alarm 08 Breaking 209 AC Mains Failure R

    ectif

    ierCabinet

    09 Breaking 2

    10 Obstruction Light Failure 10 Breaking/Closing 2

    11 Genset Fault 11 Breaking 1

    12 Battery Charger Fail 12 Breaking 1

    13 Day Tank Fuel Low 13 Breaking 2

    14 Bulk Tank Fuel Low 14 Breaking 2

    15 Load on Genset 15 Breaking 216 SPARE

    Gen

    eratorAlarmS

    ystem

    16

    Type Indicates the condition for the contact of the each individual alarm. Normally Closed (N.C.) Contacts indicates -Breaking Normally Open (N.O.) Contacts indicates - Closing

    Severity Level Indicates the severity of the alarm. Priority alarm indicates 1 Non-priority alarm indicates 2

  • 8/12/2019 BTS TRM External Alarms R3A

    10/30

  • 8/12/2019 BTS TRM External Alarms R3A

    11/30

    USER I/O

    (D-SUB 25)

    SAU EXPANSION 2 MODULE

    SUB

    DISTRIBUTION

    FRAME,

    SDF

    FACILITIES ALARM

    MONITORING SYSTEM,FMS

    RECTIFIER ALARM

    MONITORING SYSTEM

    GENSET ALARM

    MONITORING SYSTEM

    TMR 9202 CABINET, AMM01

    NOTE:

    ~ See Cable Distribution Diagram for Sub-Distribution Frame, (2/193 18 - IPA 8002 Uen)

    ~ See Pin Configuration Diagram for USER I/O External Connector, (4-114, EN/LZT 110 2014 R6D)

  • 8/12/2019 BTS TRM External Alarms R3A

    12/30

    EXTERNAL ALARM ALLOCATIONREQUIREMENTS SPEC. 5 (6)

    Prepared (also subject responsible if other) No.

    OC/ENP/SO/D/S Alec Atienza DIG01.0004.045.149 UenApproved Checked Date Rev Reference

    OC/ENP/SO/D/SC Khairy Hassan 4/18/2005 A

    PROJECT:DMPI Ph 4A BASE TRANSCEIVER STATION (GSM1800, RBS2206, TMR9202)

    SITE : ALL REPEATER CHANGEOUT SITES (VISMIN)

    EQUIPMENT TYPE : REPEATER SITE 12 External Alarms(PDH TRANSMISSION ONLY)

    ALARM

    NO.

    DESIGNATION USER

    I/O

    TYPE SEVERITY

    LEVEL

    01 Illegal Entry 1 Breaking 1

    02 Water Alarms 2 Breaking 1

    03 High Temp./Fire Alarms 3 Breaking 1

    04 AC Mains Failure 4 Breaking 2

    05 Obstruction Light FailureCabinAlarmS

    ystem

    5 Breaking 2

    06 Battery Low 6 Breaking 1

    07 Rectifier Failure 7 Breaking 1

    08 Rectifier MCB Alarm 8 Breaking 109 Rectifier High Temp. R

    ectif

    ierCabinet

    9 Breaking 1

    10 Genset Fault 10 Breaking 1

    11 Battery Charge Fail 11 Breaking 1

    12 Load on GensetGenerator

    Alarm

    System

    12 Breaking 2

    Type Indicates the condition for the contact of the each individual alarm. Normally Closed (N.C.) Contacts indicates -Breaking Normally Open (N.O.) Contacts indicates - Closing

    Severity Level Indicates the severity of the alarm. Critical Alarmrequires immediate action/response, whatever the time of day or night. Major Alarmrequires immediate action/response, if it occurs during working-hours, otherwise as soon as

    the working-hours commence. Minor Alarmrequires non-immediate action/response that could be attended within the day. Warning Alarmis an observation alarm that indicates a temporary state of operation and does not

    normally require any action. However, if the alarm persists more than 20 hours, it must be investigated.

  • 8/12/2019 BTS TRM External Alarms R3A

    13/30

  • 8/12/2019 BTS TRM External Alarms R3A

    14/30

    EXTERNAL ALARM ALLOCATIONREQUIREMENTS SPEC. 6 (6)

    Prepared (also subject responsible if other) No.

    OC/ENP/SO/D/S Alec Atienza DIG01.0004.045.149 UenApproved Checked Date Rev Reference

    OC/ENP/SO/D/SC Khairy Hassan 4/18/2005 A

    PROJECT:DMPI Ph 4A BASE TRANSCEIVER STATION (GSM1800, RBS2206, TMR9202)

    SITE : ALL REPEATER NEW SITES (VISMIN)

    EQUIPMENT TYPE : REPEATER SITE 12 External Alarms(PDH TRANSMISSION ONLY)

    ALARM

    NO.

    DESIGNATION USER

    I/O

    TYPE SEVERITY

    LEVEL

    01 Illegal Entry 1 Breaking 1

    02 Water Alarms 2 Breaking 1

    03 High Temp./Fire Alarms 3 Breaking 1

    04 Obstruction Light FailureCabinAlarm

    System

    4 Breaking 2

    05 Rectifier A1 Alarm 5 Breaking 1

    06 Rectifier A2 Alarm 6 Breaking 1

    07 Rectifier O1 Alarm 7 Breaking 2

    08 AC Mains FailureRectifierCabinet

    8 Breaking 209 Genset Fault 9 Breaking 1

    10 Battery Charge Fail 10 Breaking 1

    11 Day/Bulk Tank Fuel Low 11 Breaking 2

    12 Load on Genset GeneratorAlarm

    System

    12 Breaking 2

    Type Indicates the condition for the contact of the each individual alarm. Normally Closed (N.C.) Contacts indicates -Breaking Normally Open (N.O.) Contacts indicates - Closing

    Severity Level Indicates the severity of the alarm. Critical Alarmrequires immediate action/response, whatever the time of day or night. Major Alarmrequires immediate action/response, if it occurs during working-hours, otherwise as soon as

    the working-hours commence. Minor Alarmrequires non-immediate action/response that could be attended within the day. Warning Alarmis an observation alarm that indicates a temporary state of operation and does not

    normally require any action. However, if the alarm persists more than 20 hours, it must be investigated.

  • 8/12/2019 BTS TRM External Alarms R3A

    15/30

  • 8/12/2019 BTS TRM External Alarms R3A

    16/30

  • 8/12/2019 BTS TRM External Alarms R3A

    17/30

  • 8/12/2019 BTS TRM External Alarms R3A

    18/30

  • 8/12/2019 BTS TRM External Alarms R3A

    19/30

  • 8/12/2019 BTS TRM External Alarms R3A

    20/30

  • 8/12/2019 BTS TRM External Alarms R3A

    21/30

  • 8/12/2019 BTS TRM External Alarms R3A

    22/30

  • 8/12/2019 BTS TRM External Alarms R3A

    23/30

  • 8/12/2019 BTS TRM External Alarms R3A

    24/30

  • 8/12/2019 BTS TRM External Alarms R3A

    25/30

  • 8/12/2019 BTS TRM External Alarms R3A

    26/30

  • 8/12/2019 BTS TRM External Alarms R3A

    27/30

  • 8/12/2019 BTS TRM External Alarms R3A

    28/30

  • 8/12/2019 BTS TRM External Alarms R3A

    29/30

  • 8/12/2019 BTS TRM External Alarms R3A

    30/30