EXTERNAL ALARM ALLOCATIONREQUIREMENTS SPEC. 1 (6)
Prepared (also subject responsible if other) No.
OC/ENP/SO/D/S Alec Atienza DIG01.0004.045.149 UenApproved Checked Date Rev Reference
OC/ENP/SO/D/SC Khairy Hassan 4/18/2005 A
PROJECT:DMPI Ph 4A BASE TRANSCEIVER STATION (GSM1800, RBS2206, TMR9202)
SITE : ALL BTS - CHANGEOUT SITES (VISMIN)
EQUIPMENT TYPE : BTS SITE 16 External Alarms
ALARM
NO.
DESIGNATION ID
NO.
TYPE SEVERITY
LEVEL
01 Illegal Entry 0 Breaking 1
02 ACU Alarm 1 Breaking 1
03 High Temp. Alarm 2 Breaking 1
04 Water Alarm 3 Breaking 1
05 Fire Alarm 4 Breaking 1
06 AC Mains Failure
CabinAlarmS
ystem
5 Breaking 2
07 Battery Low 6 Breaking 1
08 Rectifier Failure 7 Breaking 1
09 Rectifier MCB Alarm 8 Breaking 1
10 Rectifier High Temp. 9 Breaking 1
11 LVDS Alarm
RectifierC
abinet
A Breaking 1
12 Obstruction Light Failure B Breaking/Closing 2
13 Genset Fault C Breaking 1
14 Battery Charger Fail D Breaking 1
15 Day/Bulk Tank Fuel Low E Breaking 2
16 Load on Genset GeneratorAlarm
System
F Breaking 2
Type Indicates the condition for the contact of the each individual alarm. Normally Closed (N.C.) Contacts indicates -Breaking Normally Open (N.O.) Contacts indicates - Closing
Severity Level Indicates the severity of the alarm. Priority alarm indicates 1 Non-priority alarm indicates 2
-
8/12/2019 BTS TRM External Alarms R3A
3/30
-
8/12/2019 BTS TRM External Alarms R3A
4/30
EXTERNAL ALARM ALLOCATIONREQUIREMENTS SPEC. 2 (6)
Prepared (also subject responsible if other) No.
OC/ENP/SO/D/S Alec Atienza DIG01.0004.045.149 UenApproved Checked Date Rev Reference
OC/ENP/SO/D/SC Khairy Hassan 4/18/2005 A
PROJECT:DMPI Ph 4A BASE TRANSCEIVER STATION (GSM1800, RBS2206, TMR9202)
SITE : ALL BTS - NEW SITES (VISMIN)
EQUIPMENT TYPE : BTS SITE 16 External Alarms
ALARM
NO.
DESIGNATION ID
NO.
TYPE SEVERITY
LEVEL
01 Illegal Entry 0 Breaking 1
02 ACU Alarm 1 Breaking 103 High Temp. Alarm 2 Breaking 1
04 Water Alarm 3 Breaking 1
05 Fire AlarmCabinAlarmS
ystem
4 Breaking 1
06 Rectifier A1 Alarm 5 Breaking 1
07 Rectifier A2 Alarm 6 Breaking 1
08 Rectifier O1 Alarm 7 Breaking 2
09 AC Mains Failure
RectifierCabinet
8 Breaking 210 Obstruction Light Failure 9 Breaking/Closing 2
11 Genset Fault A Breaking 1
12 Battery Charger Fail B Breaking 1
13 Day Tank Fuel Low C Breaking 2
14 Bulk Tank Fuel Low D Breaking 2
15 Load on Genset E Breaking 2
16 SPAREGeneratorAlarmS
ystem
F
Type Indicates the condition for the contact of the each individual alarm. Normally Closed (N.C.) Contacts indicates -Breaking Normally Open (N.O.) Contacts indicates - Closing
Severity Level Indicates the severity of the alarm. Priority alarm indicates 1 Non-priority alarm indicates 2
-
8/12/2019 BTS TRM External Alarms R3A
5/30
-
8/12/2019 BTS TRM External Alarms R3A
6/30
~ See Cable Distribution Diagram for Sub-Distribution Frame, (2/193 18 - IPA 8003 Uen)
NOTE:
GENSET ALARM
MONITORING SYSTEM
FACILITIES ALARM
MONITORING SYSTEM,FMS
RECTIFIER ALARM
MONITORING SYSTEM
NERA SDH CABINET
SUB
DISTRIBUTION
FRAME,
SDF
A
B
-
8/12/2019 BTS TRM External Alarms R3A
7/30
EXTERNAL ALARM ALLOCATIONREQUIREMENTS SPEC. 3 (6)
Prepared (also subject responsible if other) No.
OC/ENP/SO/D/S Alec Atienza DIG01.0004.045.149 UenApproved Checked Date Rev Reference
OC/ENP/SO/D/SC Khairy Hassan 4/18/2005 A
PROJECT:DMPI Ph 4A BASE TRANSCEIVER STATION (GSM1800, RBS2206, TMR9202)
SITE : ALL REPEATER CHANGEOUT SITES (VISMIN)
EQUIPMENT TYPE : REPEATER SITE 16 External Alarms(SDH TRANSMISSION ONLY)
ALARM
NO.
DESIGNATION ID
NO.
TYPE SEVERITY
LEVEL
01 Illegal Entry 01 Breaking 1
02 ACU Alarm 02 Breaking 1
03 High Temp. Alarm 03 Breaking 1
04 Water Alarm 04 Breaking 1
05 Fire Alarm 05 Breaking 1
06 AC Mains Failure
CabinAlarmS
ystem
06 Breaking 2
07 Battery Low 07 Breaking 1
08 Rectifier Failure 08 Breaking 109 Rectifier MCB Alarm 09 Breaking 1
10 Rectifier High Temp. 10 Breaking 1
11 LVDS Alarm
RectifierCabi
net
11 Breaking 1
12 Obstruction Light Failure 12 Breaking/Closing 2
13 Genset Fault 13 Breaking 1
14 Battery Charger Fail 14 Breaking 1
15 Day/Bulk Tank Fuel Low 15 Breaking 216 Load on Genset G
ene
ratorAlarm
System
16 Breaking 2
Type Indicates the condition for the contact of the each individual alarm. Normally Closed (N.C.) Contacts indicates -Breaking Normally Open (N.O.) Contacts indicates - Closing
Severity Level Indicates the severity of the alarm. Priority alarm indicates 1 Non-priority alarm indicates 2
-
8/12/2019 BTS TRM External Alarms R3A
8/30
-
8/12/2019 BTS TRM External Alarms R3A
9/30
EXTERNAL ALARM ALLOCATIONREQUIREMENTS SPEC. 4 (6)
Prepared (also subject responsible if other) No.
OC/ENP/SO/D/S Alec Atienza DIG01.0004.045.149 UenApproved Checked Date Rev Reference
OC/ENP/SO/D/SC Khairy Hassan 4/18/2005 A
PROJECT:DMPI Ph 4A BASE TRANSCEIVER STATION (GSM1800, RBS2206, TMR9202)
SITE : ALL REPEATER NEW SITES (VISMIN)
EQUIPMENT TYPE : REPEATER SITE 16 External Alarms(SDH TRANSMISSION ONLY)
ALARM
NO.
DESIGNATION ID
NO.
TYPE SEVERITY
LEVEL
01 Illegal Entry 01 Breaking 1
02 ACU Alarm 02 Breaking 1
03 High Temp. Alarm 03 Breaking 1
04 Water Alarm 04 Breaking 1
05 Fire AlarmCabinAlarmS
ystem
05 Breaking 1
06 Rectifier A1 Alarm 06 Breaking 1
07 Rectifier A2 Alarm 07 Breaking 1
08 Rectifier O1 Alarm 08 Breaking 209 AC Mains Failure R
ectif
ierCabinet
09 Breaking 2
10 Obstruction Light Failure 10 Breaking/Closing 2
11 Genset Fault 11 Breaking 1
12 Battery Charger Fail 12 Breaking 1
13 Day Tank Fuel Low 13 Breaking 2
14 Bulk Tank Fuel Low 14 Breaking 2
15 Load on Genset 15 Breaking 216 SPARE
Gen
eratorAlarmS
ystem
16
Type Indicates the condition for the contact of the each individual alarm. Normally Closed (N.C.) Contacts indicates -Breaking Normally Open (N.O.) Contacts indicates - Closing
Severity Level Indicates the severity of the alarm. Priority alarm indicates 1 Non-priority alarm indicates 2
-
8/12/2019 BTS TRM External Alarms R3A
10/30
-
8/12/2019 BTS TRM External Alarms R3A
11/30
USER I/O
(D-SUB 25)
SAU EXPANSION 2 MODULE
SUB
DISTRIBUTION
FRAME,
SDF
FACILITIES ALARM
MONITORING SYSTEM,FMS
RECTIFIER ALARM
MONITORING SYSTEM
GENSET ALARM
MONITORING SYSTEM
TMR 9202 CABINET, AMM01
NOTE:
~ See Cable Distribution Diagram for Sub-Distribution Frame, (2/193 18 - IPA 8002 Uen)
~ See Pin Configuration Diagram for USER I/O External Connector, (4-114, EN/LZT 110 2014 R6D)
-
8/12/2019 BTS TRM External Alarms R3A
12/30
EXTERNAL ALARM ALLOCATIONREQUIREMENTS SPEC. 5 (6)
Prepared (also subject responsible if other) No.
OC/ENP/SO/D/S Alec Atienza DIG01.0004.045.149 UenApproved Checked Date Rev Reference
OC/ENP/SO/D/SC Khairy Hassan 4/18/2005 A
PROJECT:DMPI Ph 4A BASE TRANSCEIVER STATION (GSM1800, RBS2206, TMR9202)
SITE : ALL REPEATER CHANGEOUT SITES (VISMIN)
EQUIPMENT TYPE : REPEATER SITE 12 External Alarms(PDH TRANSMISSION ONLY)
ALARM
NO.
DESIGNATION USER
I/O
TYPE SEVERITY
LEVEL
01 Illegal Entry 1 Breaking 1
02 Water Alarms 2 Breaking 1
03 High Temp./Fire Alarms 3 Breaking 1
04 AC Mains Failure 4 Breaking 2
05 Obstruction Light FailureCabinAlarmS
ystem
5 Breaking 2
06 Battery Low 6 Breaking 1
07 Rectifier Failure 7 Breaking 1
08 Rectifier MCB Alarm 8 Breaking 109 Rectifier High Temp. R
ectif
ierCabinet
9 Breaking 1
10 Genset Fault 10 Breaking 1
11 Battery Charge Fail 11 Breaking 1
12 Load on GensetGenerator
Alarm
System
12 Breaking 2
Type Indicates the condition for the contact of the each individual alarm. Normally Closed (N.C.) Contacts indicates -Breaking Normally Open (N.O.) Contacts indicates - Closing
Severity Level Indicates the severity of the alarm. Critical Alarmrequires immediate action/response, whatever the time of day or night. Major Alarmrequires immediate action/response, if it occurs during working-hours, otherwise as soon as
the working-hours commence. Minor Alarmrequires non-immediate action/response that could be attended within the day. Warning Alarmis an observation alarm that indicates a temporary state of operation and does not
normally require any action. However, if the alarm persists more than 20 hours, it must be investigated.
-
8/12/2019 BTS TRM External Alarms R3A
13/30
-
8/12/2019 BTS TRM External Alarms R3A
14/30
EXTERNAL ALARM ALLOCATIONREQUIREMENTS SPEC. 6 (6)
Prepared (also subject responsible if other) No.
OC/ENP/SO/D/S Alec Atienza DIG01.0004.045.149 UenApproved Checked Date Rev Reference
OC/ENP/SO/D/SC Khairy Hassan 4/18/2005 A
PROJECT:DMPI Ph 4A BASE TRANSCEIVER STATION (GSM1800, RBS2206, TMR9202)
SITE : ALL REPEATER NEW SITES (VISMIN)
EQUIPMENT TYPE : REPEATER SITE 12 External Alarms(PDH TRANSMISSION ONLY)
ALARM
NO.
DESIGNATION USER
I/O
TYPE SEVERITY
LEVEL
01 Illegal Entry 1 Breaking 1
02 Water Alarms 2 Breaking 1
03 High Temp./Fire Alarms 3 Breaking 1
04 Obstruction Light FailureCabinAlarm
System
4 Breaking 2
05 Rectifier A1 Alarm 5 Breaking 1
06 Rectifier A2 Alarm 6 Breaking 1
07 Rectifier O1 Alarm 7 Breaking 2
08 AC Mains FailureRectifierCabinet
8 Breaking 209 Genset Fault 9 Breaking 1
10 Battery Charge Fail 10 Breaking 1
11 Day/Bulk Tank Fuel Low 11 Breaking 2
12 Load on Genset GeneratorAlarm
System
12 Breaking 2
Type Indicates the condition for the contact of the each individual alarm. Normally Closed (N.C.) Contacts indicates -Breaking Normally Open (N.O.) Contacts indicates - Closing
Severity Level Indicates the severity of the alarm. Critical Alarmrequires immediate action/response, whatever the time of day or night. Major Alarmrequires immediate action/response, if it occurs during working-hours, otherwise as soon as
the working-hours commence. Minor Alarmrequires non-immediate action/response that could be attended within the day. Warning Alarmis an observation alarm that indicates a temporary state of operation and does not
normally require any action. However, if the alarm persists more than 20 hours, it must be investigated.
-
8/12/2019 BTS TRM External Alarms R3A
15/30
-
8/12/2019 BTS TRM External Alarms R3A
16/30
-
8/12/2019 BTS TRM External Alarms R3A
17/30
-
8/12/2019 BTS TRM External Alarms R3A
18/30
-
8/12/2019 BTS TRM External Alarms R3A
19/30
-
8/12/2019 BTS TRM External Alarms R3A
20/30
-
8/12/2019 BTS TRM External Alarms R3A
21/30
-
8/12/2019 BTS TRM External Alarms R3A
22/30
-
8/12/2019 BTS TRM External Alarms R3A
23/30
-
8/12/2019 BTS TRM External Alarms R3A
24/30
-
8/12/2019 BTS TRM External Alarms R3A
25/30
-
8/12/2019 BTS TRM External Alarms R3A
26/30
-
8/12/2019 BTS TRM External Alarms R3A
27/30
-
8/12/2019 BTS TRM External Alarms R3A
28/30
-
8/12/2019 BTS TRM External Alarms R3A
29/30
-
8/12/2019 BTS TRM External Alarms R3A
30/30