BS7671 Formula and Tips

Transcript of BS7671 Formula and Tips. The earth fault loop impedance of that part of the system external to the...

Page 1: BS7671 Formula and Tips. The earth fault loop impedance of that part of the system external to the installation. Ze = the external earth fault loop impedance.

BS7671 Formula and Tips

Page 2: BS7671 Formula and Tips. The earth fault loop impedance of that part of the system external to the installation. Ze = the external earth fault loop impedance.

The earth fault loop impedance of that part of the system external to the installation.

Ze = the external earth fault loop impedance of the supply cableZs = the earth fault loop impendence of the Internal current carrying circuit.R1+R2 = the sum of the resistance of the line conductor (R1) and the circuit protective conductor (R2) between the point of utilisation and the origin of the installation.Equitation: Zs = Ze + (R1 + R2)

Page 3: BS7671 Formula and Tips. The earth fault loop impedance of that part of the system external to the installation. Ze = the external earth fault loop impedance.

Ohms Law

Resistance of the cable in ohms = R Current being drawn from the circuit = IVoltage being delivered to the circuit = VPower being developed by the circuit = PThis can give us two triangles for formula

Resistance triangle Power triangle

VP

I R V I

Page 4: BS7671 Formula and Tips. The earth fault loop impedance of that part of the system external to the installation. Ze = the external earth fault loop impedance.

Ohms Law

Power Voltage P - watts V - volts

PowerP = watts

VoltageV = volts

CurrentI = amperes

ResistanceR = ohms

V2R

I2 X R

V x I

PI

P x R

I x R

VR

PV

VI

PI2

V2P

PR

Page 5: BS7671 Formula and Tips. The earth fault loop impedance of that part of the system external to the installation. Ze = the external earth fault loop impedance.

Description Lighting Other uses

(i) Low voltage installations supplied directly from a public low voltage distribution system

3% 5%

(ii) Low voltage installation supplied from private LV supply (*)

6% 8%

(*) The voltage drop within each final circuit should not exceed the values given in (i)

525 – Voltage drop in consumers’ installations

Regulation 525.3 directs readers to a table in Appendix 12. pg 314

Where a distribution circuit (from origin) feeds another distribution board, the total allowable voltage drop should be split between the distribution circuit(s) and final circuit(s).

Page 6: BS7671 Formula and Tips. The earth fault loop impedance of that part of the system external to the installation. Ze = the external earth fault loop impedance.

Voltage drop calculations

Where the voltage drop is in volts and:

mV is the millivolts dropped per ampere permetre taken from Tables 4D1A to 4J4A pg332-374

Ib is the design current of the circuit (thecurrent intended to be carried)

Length is the length of the circuit in metres. Thedivision by 1000 gives the answer in volts.

1000

lengthImVdropVoltage b

Page 7: BS7671 Formula and Tips. The earth fault loop impedance of that part of the system external to the installation. Ze = the external earth fault loop impedance.

Volt Drop

Cable CalculationA lighting circuit protected by a BS3036 fuse consisting of 10 x 100W luminaires is wired in single copper pvc 700C insulated cable installed with two other circuits in conduit fixed to a wall. The circuit length is 23m and the ambient temperature of the surroundings is 350C.Carry out a cable calculation and check that the circuit complies with BS7671:2008 incorporating Amendment no.1 2011.

Step 1. Gather the relevant information from the question.• 10 x 100W luminaires = 1000W700C PVC single copper cables run in conduit fixed to wall = Reference method B (BS7671 Table 4A2 p.317)• BS3036 protective device = Cf = 0.725 (BS7671 Appendix 4 p.308)• Circuit Length = 23m• Grouping with 2 other circuits (total 3) = Cg = 0.7 (BS7671 Table 4C1 p.327)

• Ambient temperature 350C = Ca = 0.94 (BS7671 Table 4B1 p.325)

Page 8: BS7671 Formula and Tips. The earth fault loop impedance of that part of the system external to the installation. Ze = the external earth fault loop impedance.

Volt DropStep 2. Calculate the circuit design current. (Ib) using ohms law power triangle I = P / V

Ib = P = 1000 =4.35A

V 230

Step 3. Determine the rating of the protective device (In)

In ≥ Ib = 5A (BS7671 Table 41.2 p.55)

Step 4. Determine the minimum current carrying capacity of the cable (It) (BS7671 Appendix 4 p.308)

It = In = In = 5 = 5 = 10.48A

Correction factors (Cg x Ca x Cf ) (0.7 x 0.94 x 0.725) 0.477

Cable must be capable of carrying 10.48A

Page 9: BS7671 Formula and Tips. The earth fault loop impedance of that part of the system external to the installation. Ze = the external earth fault loop impedance.

Volt DropStep 5. Identify a suitable cable. = (BS7671 Table 4D1A p.332 reference method B)

1mm2 cable has a rating of 13.5A Step 6. Calculate the volt drop. (Vd) = (BS7671 Table 4D1B page 333 reference method A and B) Voltage drop = (mV/A/m)x Ib x L = 44 x 4.35 x 23 = 4.4V

1000 1000 Appendix 4 page 314This circuit complies with the requirements of BS7671 in that the calculated volt drop 4.4V is less than the maximum permitted 3% for a single phase lighting circuits.Single phase; 3% of 230 = 6.9VTherefore the cable is suitable.

Page 10: BS7671 Formula and Tips. The earth fault loop impedance of that part of the system external to the installation. Ze = the external earth fault loop impedance.

Resistance of copper and aluminium conductors

Uo = the normal voltage to earthZs = the earth fault loop impedanceand: Zs = Ze + (R1 + R2)Ze = the external earth fault loop impedance of the supply cableZs = the earth fault loop impendence of the Internal current carrying circuit.R1+R2 = the sum of the resistance of the line conductor (R1) and the circuit protective conductor (R2) between the point of utilisation and the origin of the installation.

Page 11: BS7671 Formula and Tips. The earth fault loop impedance of that part of the system external to the installation. Ze = the external earth fault loop impedance.

Resistance of copper and aluminium conduct

Similarly, in order to design circuits for compliance with BS7671 limiting values of earth fault loop impedance given in Tables 41.2 to 41.4, it is necessary to establish the relevant impedance of the circuit conductors concerned at their operating temperatures.For example 1.5mm2 with 1.0mm2 earth c.p.c. is given as 30.20 mΩ/m therefore if the cable is 20mts in length this will be30.20 x 20 = 0.60Ω which is the value of R1+R2 1000

Page 12: BS7671 Formula and Tips. The earth fault loop impedance of that part of the system external to the installation. Ze = the external earth fault loop impedance.

Electrical systems and earthing arrangements

TTTN-C-STN-S

Page 13: BS7671 Formula and Tips. The earth fault loop impedance of that part of the system external to the installation. Ze = the external earth fault loop impedance.

TN-S system

Typical quoted value for Ze is 0.8 W

Page 14: BS7671 Formula and Tips. The earth fault loop impedance of that part of the system external to the installation. Ze = the external earth fault loop impedance.

TN-C-S system

Typical quoted value for Ze is 0.35 W

Page 15: BS7671 Formula and Tips. The earth fault loop impedance of that part of the system external to the installation. Ze = the external earth fault loop impedance.

TT system

This system affords a relatively high Ze value, which must not exceed 21 W

Ra ≤ 200 W

Page 16: BS7671 Formula and Tips. The earth fault loop impedance of that part of the system external to the installation. Ze = the external earth fault loop impedance.

TN-C system• A TN-C system is uncommon in the United Kingdom.

• Neutral and protective functions are combined in a single conductor (a PEN conductor) throughout the system (although, the term CNE is sometimes used for such a conductor forming part of the distributor’s lines).

• The exposed-conductive-parts of the installation are connected to the PEN conductor, and hence to the earthed point of the source of energy.

• Regulation 8(4) of the Electricity Safety, Quality and Continuity Regulations 2002 prohibits the use of PEN conductors in consumers’ installations.

Page 17: BS7671 Formula and Tips. The earth fault loop impedance of that part of the system external to the installation. Ze = the external earth fault loop impedance.

Nominal Voltages in the UK

• Single phase (U0) 230 V (Actual 240 V)

• Three Phase (U) 400 V (Actual 415 V)

Page 18: BS7671 Formula and Tips. The earth fault loop impedance of that part of the system external to the installation. Ze = the external earth fault loop impedance.

IP code lettering/numbering systempg381

Discuss:• IP2X,• IP4X• IPXXB, and• IPXXD

Page 19: BS7671 Formula and Tips. The earth fault loop impedance of that part of the system external to the installation. Ze = the external earth fault loop impedance.

‘DEAD’ TESTING

Prescribed tests:

• Continuity

• Polarity

• Insulation resistance

DEAD OR LIVE TESTING?

‘LIVE’ TESTING

Prescribed tests:

• Earth fault loop impedance

• Fault current measurement

• RCD operation

Page 20: BS7671 Formula and Tips. The earth fault loop impedance of that part of the system external to the installation. Ze = the external earth fault loop impedance.

Insure these items are tested

External Ze

Earth electrode RA (if applicable)

Continuity of protective conductors

Insulation between Live conductors and earth

Insulation between Live conductors

Polarity

Earth Loop-Impedance

Operation of Residual Current device

Functional Testing

Page 21: BS7671 Formula and Tips. The earth fault loop impedance of that part of the system external to the installation. Ze = the external earth fault loop impedance.

VERIFICATION & CERTIFICATION - CERTIFICATES

Three types of Certificate could be used for a domestic electrical installation:-

An Periodic Inspection (Electrical Condition Report) An Electrical Installation Certificate A Minor Works Certificate

Page 22: BS7671 Formula and Tips. The earth fault loop impedance of that part of the system external to the installation. Ze = the external earth fault loop impedance.

Tips

Lets look at a typical question from the exam and follow it through at various stages.

Page 23: BS7671 Formula and Tips. The earth fault loop impedance of that part of the system external to the installation. Ze = the external earth fault loop impedance.

BS7671 identifies that the cross-sectional area of a conductor shall be determined by

A the admissible maximum temperature

B the nominal voltage

C voltage tolerances

D the earthing system

y

Example Question

Page 24: BS7671 Formula and Tips. The earth fault loop impedance of that part of the system external to the installation. Ze = the external earth fault loop impedance.

Tips

Now if we go straight to the BS7671 index and look up cross-sectional area of conductors and cables page 442. We find a reference to 132.6 Sec 524, we would now look in part 1 chapter 32 regulation 6 page 19. On reading the regulation we find:The cross-sectional area of conductors shall be determined for both normal operating conditions and where appropriate, for fault conditions according to: ( 1 ) the admissible maximum temperature. Therefore we know that ( A ) must be the answer.

Page 25: BS7671 Formula and Tips. The earth fault loop impedance of that part of the system external to the installation. Ze = the external earth fault loop impedance.

BS7671 identifies that the cross-sectional area of a conductor shall be determined by

A the admissible maximum temperature

B the nominal voltage

C voltage tolerances

D the earthing system

Example Question

Page 26: BS7671 Formula and Tips. The earth fault loop impedance of that part of the system external to the installation. Ze = the external earth fault loop impedance.

Tips

Lets try another example and follow that through!

Page 27: BS7671 Formula and Tips. The earth fault loop impedance of that part of the system external to the installation. Ze = the external earth fault loop impedance.

The algebraic sum of the currents in the live conductors of a circuit at a point in the electrical installation is known as the

A residual current

B harmonic current

C line current

D neutral current

y

Example Question

Page 28: BS7671 Formula and Tips. The earth fault loop impedance of that part of the system external to the installation. Ze = the external earth fault loop impedance.

Tips

Looking in the BS7671 index the only phrase we can find from the question is Electrical installation definition Part 2 page 444.We then go to Part 2 Definitions we can only find Residual current. Algebraic sum of the currents in the live conductors of a circuit at a point in the electrical installation. Page 33We now know that ( A ) is the answer.

Page 29: BS7671 Formula and Tips. The earth fault loop impedance of that part of the system external to the installation. Ze = the external earth fault loop impedance.

The algebraic sum of the currents in the live conductors of a circuit at a point in the electrical installation is known as the

A residual current

B harmonic current

C line current

D neutral current

Example Question

Page 30: BS7671 Formula and Tips. The earth fault loop impedance of that part of the system external to the installation. Ze = the external earth fault loop impedance.

Tips

As we can see from the last question it is not always plain sailing in finding out an answer!But keeping calm and looking in the question for the various words or the answers, you can find what you are looking for. Now you try the next one!

Page 31: BS7671 Formula and Tips. The earth fault loop impedance of that part of the system external to the installation. Ze = the external earth fault loop impedance.

Which one of the following cannot be used as basic protection

A insulation of live parts

B barriers or enclosures

C protective earthing and bonding

D obstacles

y

Example Question

Page 32: BS7671 Formula and Tips. The earth fault loop impedance of that part of the system external to the installation. Ze = the external earth fault loop impedance.

Which one of the following cannot be used as basic protection

Options a,b,d, all provide basic protection (see Section 416 and 417) option c provides fault protection therefore C is the answer.

A insulation of live parts

B barriers or enclosures

C protective earthing and bonding

D obstacles

y

Example Answer