Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet Andrew Ferenac & Lucas Ellis ICT - Remote Systems Group 6 th May 2013

Transcript of Breakout Session 4 - SCADA -...

Page 1: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Breakout Session 4 - SCADA

SCD5200 Usage & Project Implementation at SP AusNet

Andrew Ferenac & Lucas Ellis

ICT - Remote Systems Group

6th May 2013

Page 2: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Safety Topic

• Did you bring a suitcase?

• When packing up to go home try and remember safe manual handling

2

Page 3: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

• Lucas Ellis

– Software Developer

• WinRadio

– Protection and Control Tester

• SP AusNet

Field Tests

Project Delivery

– Real Time Systems Analyst

• SP AusNet

Who are we?

3

• Andrew Ferenac

– Electrical Technician (Field Tester)

• SECV

– SCADA Technician

• SECV / VPX

– SCADA Consultant

• Distribution Businesses

– Technical Specialist / Project Manager

• Logica

– SCADA Engineer

• AGL, Jemena, Tenix Aliance

– Senior Real Time Systems Analyst

• SP AusNet

[email protected] [email protected]

Page 4: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Session Agenda

• Introduction

• SP AusNet Business Overview

• Case Study: Network Wide SCD5200/P3 Firmware Upgrade Project

• Project Implementation Using the SCD5200

• Automation Tools Developed In-house

• SP AusNet SCD5200/P3 Security Implementation

• Questions

4

Page 5: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Business Overview

• A diversified energy infrastructure business

• A workforce of around 1600 office & field based employees

• Owns & operates $6.3billion worth of assets

• 51% owned by Singapore Power and listed on both the Singapore &

Australian Stock Exchanges

5

Page 6: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

About SP

6

Electricity

Transmission

Page 7: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Electricity

Distribution

Page 8: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Gas

Distribution

Gas

Distribution

Page 9: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Business Overview: Area of Operation

9

Page 10: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Remote System Group (RSG) Overview

• Transmission Electricity Systems – All aspects of station automation

• new projects

• system augmentation

• maintenance

• Distribution Electricity Systems – All aspects of substation automation

• new projects

• system augmentation

• maintenance since 2009

10

Page 11: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

RSG Overview: Activities

11

New projects 60%

- New stations

- Rebuilds

- Augmentations

- Internal projects

Incidents 30%

- Faults

- Hotline support

Others 10%

- Meetings

- Training

- Email

Page 12: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

RSG Overview: SCD5200 RTUs

• SCD5200 implemented in Transmission & Distribution stations

• Optonet Systems range from 3 nodes to 30+ Nodes

• IO counts range from 100 to 1000s

• Multiple Masters:

– Station HMI (Human Machine Interface)

– Transmission & Distribution Control Rooms

– Other Distribution Businesses

– Generation Businesses

– Major Customer, i.e. Victorian Desalination Plant

• Multiple IEDs using various protocols (DNP, Modbus, IEC103, ASCII)

12

Page 13: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

RSG Overview: Keilor Terminal Station (KTS)

13

Page 14: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

RSG Overview: KTS Nodes 19 to 29 (500kV Relay House)

14

Page 15: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

RSG Overview: Remote Connections

• WAN

– IP network gigabit speeds

– Fibre to most stations (OPGW)

• NEXTG / 3G

– Coverage to areas without WAN

– Slow but quicker than driving

• Media Converter

– Enables SCD5200 connection

15

Page 16: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Case Study: Network wide SCD5200/P3

Firmware Upgrade Project

Upgrading firmware at 55 sites

Lucas Ellis

Remote Systems Group

6th of May 2013

Page 17: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Upgrade Drivers – Why Upgrade?

17

Page 18: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Upgrade Drivers – Why Upgrade?

Improvements to system configurator

Improvements to RTV

Updated firmware

Enable network security features

18

Page 19: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Upgrade Overview – What was involved?

19

Page 20: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Upgrade Overview – What was involved?

Updating configurator

Updating configurations

Deploy the configurations

& new firmware

20

10 workstation installations

55+ RTU configurations:

Restore, update, fix, generate, check, backup, check

300+ nodes to upgrade

Page 21: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Upgrade Roadblocks

21

Page 22: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Updating configurator

Updating configurations

Deploy the configurations

& new firmware

Upgrade Roadblocks

22

No Windows 7 Support

Risk introducing errors

Many manual tasks

Data Interruption

Remote locations

Page 23: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Updating configurator

Updating configurations

Deploy the configurations

& new firmware

Upgrade Roadblocks – Solutions

23

No Windows 7 Support

Risk introducing errors

Many manual tasks

Data Interruption

Remote locations

Virtual Machine

Automation Tools

Procedures

Remote Connectivity

Page 24: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Upgrade Process – Planning Stage

Define scope and requirements

Investigate process – find issues & resolve issues

Opportunity: Develop automation tools to reduce labour and error

Develop a procedure and instructions

-Optimised to cut down on manual tasks

-Provides a consistent approach

24

CREATE

Page 25: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Upgrade Process – Testing stage

Test the procedure and firmware – Real equipment

Peer review – Another set of eyes

Confirm RTU works as expected – Sanity check

25

TEST

Page 26: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Upgrade Process – Testing Again!

Deploy to a pilot site

Choose a complex site (33 nodes)

Use experienced staff

26

CHECK

Page 27: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Upgrade Process – Deploy

Divide and conquer – Allocate resources

Deadline (motivation)

Keep track of progress

27

DELIVER

Page 28: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Lessons Learnt & Project Outcome

28

Page 29: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Lessons Learnt & Project Outcome

Successfully completed project!

What went wrong?

- Testing revealed a problem with configurator (IEC103 Di SOE Di)

- Feature creep (extra checking not part of upgrade)

- One case where an old configuration was left in service (1 node only)

What is next?

– Smooth the way for future upgrades

– Implement security

More automation tools are required

– Saves time

– Reduce errors

29

Page 30: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Questions?

Next Up: Project Implementation using SCD5200 RTU

30

Page 31: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Project implementation using the SCD5200 RTU

Andrew Ferenac

ICT - Remote Systems Group

6th May 2013

Page 32: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Project Design

32

• Project Design is generally contracted out to 3rd party Design

Service Providers (DSP).

• DSP is responsible for documenting project SCADA changes

via SPA supplied Mapping Table, use available templates and

documented standards.

• SPA documentation is available to assist DSPs to implement

SCADA changes into Mapping Table correctly.

• Utilizing standards provides consistent and accurate

information for project implementation = TIME SAVINGS during

configuration.

• Poorly implemented standards creates more work for RSG –

mistakes take time to identify and correct.

Page 33: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

SCADA Standards - Mapping Table

33

Pros:

• Consistent layout of SCADA information using MS Excel Mapping

Table.

• Details ALL SCADA IO, Rack Layout, Deleted IO.

• Mapping Table templates are created for each standard IED

implementation to be used during project design.

Cons:

• DSPs often take considerable time to grasp Mapping Table concept.

• Updated Mapping Tables often require considerable time to review

and correct.

Page 34: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Mapping Table

34

Source

Device

of point

Protocol

to

Master

Masters

To RTU

Unique TagName

Point Title =

Name + DevType + Function

Master

Protocol

Index

Source

Connection

Type

Source

Connection Index

Or Termination Analog

Ranges

Page 35: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

RSG Delivery Stages

35

• Review and Check supplied information (Mapping Table)

• Configuration of RTU, HMI & Master Station

• FAT of RTU & HMI configurations

• Site Delivery of RTU & HMI configurations

• Commissioning Support

• Correct problems detected during commissioning

Page 36: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Review & Configuration

36

• Review & Configuration is automated as much as possible using In-

House developed Tools – assists to ensure consistent

configurations.

• Mapping Table Tool – Excel VBA

• Checks Mapping Table for common errors and deviations from

Mapping Table standards.

• CiBuilder – VB Application

• Further checks Mapping Table against standards, particularly

TagNames, and builds HMI configuration data & graphical objects.

• FoxBuilder – Excel VBA

• Further checks Mapping Table against standards and creates Foxboro

CSV formatted sheets ready for pasting into SysConfigurator.

Page 37: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Configuration

37

• RTU configurations are stored as Single Site SysConfigurator Backups zipped

along with .CFG, .RPT, .SAL & .ELF files for each Node.

• Version control of configurations changes are mandatory.

• This is a manual process for RSG.

• New Master & Slave communications ports must be created manually within

SysConfigurator before pasting to ensure that correct port parameters are setup.

• IEDs & IO are added to the configuration using the SysConfigurator Paste From

Spreadsheet function, pasting the prepared data from FoxBuilder.

• The FoxBuilder CSV sheets can also be saved (manually) to CSV files and

imported into SysConfigurator using the Import CSV Files … function.

• Pasting or Importing needs to be done in a logical order.

Page 38: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

FAT – Test set or IEDs

38

• Where possible FAT is completed using IEDs configured with actual settings being

implemented during the project.

• In some cases new panels are

delivered for FAT with the RTU & HMI.

• RSG have a Test Bed facility which

contains RTUs, IEDs, Communications

devices, etc.

• Everything we need for

FAT (generally!)

• Not always possible to cover each

IED implementation as there are

varying IO module configurations

from site to site.

Page 39: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

FAT

39

• Where we can’t test to a real IED we use Software Test Sets such as IO Server.

• Supports many protocols via Serial or Ethernet.

• Allows different Test configurations to be saved, i.e. DNP Master, DNP Slave, etc.

• Provides a PLC function for ramping AIs and turning DIs on / off automatically.

• Integrates with MS Office (Excel) using DDE.

• We have developed an Excel workbook with Graphical interface (Buttons) to drive

Binary & Analog Inputs via IO Server. Reduces testing time dramatically.

• We aim to test every IO point to every Master before delivering changes to site.

• Reduces our involvement during commissioning and provides confidence in what

is delivered.

Page 40: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Site Delivery

40

Before performing Site Delivery consider / determine:

• Impact to TOC & DOC, AEMO!

• Can all changes be delivered at once?

OR

Do we have to schedule the changes in-line with Secondary changes onsite.

• Remotely OR On-Site.

• Perform a compare of Before and After configuration & report files.

• Create a Test Schedule for commissioning staff based on Mapping Table.

• Effective and Proactive communication with all stakeholders is essential.

Page 41: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Pre-Commissioning & Commissioning Support

41

• Field staff pre-commission through to Master Station SCADA staff & HMI.

• They often require assistance getting IEDs communicating.

• Cabling Issues and Communications Parameters

• Issues List is generated for RSG to action.

• Unfortunately pre-commissioning is often scheduled close to in-service date, doesn't

leave much time!

All going well RSG will not have much involvement past Site Delivery.

( Wishful Thinking?)

Page 42: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Conclusion

42

• Documented Standards allow for consistent Design information.

• Correctly implemented Standards improve configuration efficiencies &

development time through the use of automated Tools.

• Implemented standards in SCADA should line up with IED configuration

standards.

• Aligned IED & SCADA standards allow for efficient / smooth FAT.

• Complete FAT provides confidence for Site Delivery & Commissioning.

Page 43: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Questions?

Next Up: In-house Automation Tools

43

Page 44: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Automation tools developed In-house

Improve efficiency and reduce errors

Andrew Ferenac & Lucas Ellis

ICT - Remote Systems Group

6th May 2013

Page 45: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

SCD5200 Tools: DeleteCSVFiles.bat

45

• Simple to use

• Keeps backups clean

• Wouldn’t get done otherwise (36 directories to check by hand?)

Page 46: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

SCD5200 Tools: GenerateReportFiles.bat

46

• Simple to use

• Creates reports used to compare each new RTU configuration

• One tool, not one batch file per site

• External to system configurator

Page 47: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

SCD5200 Tools: ToshSALFix.bat

47

• Nested comments

/*** comment

/*** Nested comment ***/

end of comment ***/

• All our Toshiba PLC calculations had this problem

• Problem solved

Page 48: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

SCD5200 Tools: CheckReportFiles.bat

48

• Saves a lot of manual checking

• Easy to add new checks

Page 49: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

SCD5200 Tools: Future Tools

49

• Interact with the RTU from command line

• Roadblocks:

– No security support

– Found a bug in the download tool

• Wish list:

– Download all files to RTU

– Backup RTU files to PC

– Audit all RTU configurations (wrong f/w or cfg in service?)

– Restart all nodes on an RTU

– Switch all nodes of an RTU to second configuration

– Many many more

Page 50: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Mapping Table Check Tool

50

Simple Excel VBA app to check Mapping Tables for common

errors and against agreed SCADA standards.

• A simple dialog allows the user to select an already

opened mapping table to check.

• Can check each item one at a time, or all at once.

• Can check a 500 row Mapping Table in 10 seconds.

• This might take hours, even days manually.

• Uses Excel Ranges to specify accepted values, which

can be edited at any time, not hard coded!

• Each stage provides a “Completed” dialog with the # of

errors found. A column is inserted into the Mapping

Table to detail errors for each cell.

Page 51: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Cibuilder

51

A Multi-Pass process to build HMI configurations.

• The “Create Device List” function

checks the Mapping Table IO

list against Standards.

• An Error column is inserted into

the Mapping table to provide detailed

error comments.

• Agreed standards are hard-coded into CiBuilder.

• Even though CiBuilder’s primary function is to build HMI configurations, it is a

valuable tool for checking Mapping Table data.

• Once the “Create Device List” passes without error the “Create Database File”

and “Create / Place Devices” functions are used to complete the HMI configuration

changes.

Page 52: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

FoxBuilder

52

A Multi-Pass process for building the various parts of a SCD5200 RTU configuration.

• It is imperative that the Mapping Table passes Mapping Table Tool & CiBuilder

checking before running FoxBuilder.

• A stand-alone Excel spread sheet VBA application.

• Has individual sheets representing each SysConfig CSV file.

• Is run from Custom menu items,

Run Builder and Clean Data.

• The Mapping Table data is copied into a FoxBuilder MapAll worksheet.

Page 53: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

FoxBuilder

53

• Run Builder provides the Build Options Interface.

• Can process all rows in the MapAll sheet or selected

rows.

• Can be used for Transmission or Distribution

configurations.

• Laid out in a logical order of stages.

• Provides progress indication, status and # of records

processed.

• Allows CSVs for a complete RTU configuration to

be prepared in a matter of minutes.

• In this screen shot 625 rows were processed and 4 IEDs added

to the DNPM sheet in 5 seconds.

• When processing DNP Master IO (3.1) 625 rows were

processed and 276 records added to DNP Polled in 7 seconds.

Page 54: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

FoxBuilder

54

• Dialogs are displayed at the end of processing each stage if errors are present.

• Detailed error information is provided in each CSV sheet.

• Control parameters for each IED are defined in a separate sheet “Control Types”.

• Allows for new IEDs to be added without the need for code changes.

• Health Point Names, Polling Parameters, etc. are currently hard-coded.

• Future changes include defining these parameters in a work sheet range

allowing for changes by users at any time.

• FoxBuilder allows CSVs to be prepared in approx. 15 minutes instead of 4 hours

or more preparing them manually.

Page 55: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Questions?

Next Up: SCD5200/P3 Security Implementation

55

Page 56: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

SP AusNet SCD5200/P3 Security

Implementation

Creating site specific security files with RTV

Lucas Ellis

ICT - Remote Systems Group

6th May 2013

Page 57: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Overview

• SCD5200 RTU’s connected to WAN need security

• When applying passwords have to consider

– Human error

– Remote locations

– Consequences of error

• Our approach

– Create site specific security files

– Test the file locally

– Deploy to the field

• Security Configurator

– Create default security file

– Previous presentations

57

Page 58: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Process: Creating the password file.

58

Download

“Default.SCF” file to

RTU

Reset

RTU

Enter Default

Password

Copy & Paste SiteX

Password from Excel

Upload

“Security.SCF” as

SiteX.SCF

SiteX.SCF

created.

Repeat as

needed for

other sites

Page 59: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Process: Testing the password file.

59

Download “SiteX.SCF”

file to test RTU

Reset

Test RTU

Copy & Paste SiteX

Password from Excel

Confirm entry to

test RTU

SiteX.SCF

tested.

Repeat as

needed for

other sites

Page 60: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Process: Deploy the password file.

60

Call control room

Reset RTU

Confirm access to RTU

Call control room

RTU password

updated.

Repeat as

needed for

other sites

Update records

Download “SiteX.SCF” file to RTU

Page 61: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Process Issues

• Time consuming

• Risk of human error

– Easy to do, hard to notice

– A wrongly copied password could potentially lock out the RTU, requiring a site visit

• Creating and testing 50+ SCV files can take upwards of eight hours. This

is not a job that can be rushed.

• This is over a full day of work wasted, without even starting to roll the

passwords out to a live site.

• Repeat the process every 6 months.

61

Page 62: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Example: Creating a password file

1: Download and reset

62

Page 63: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Example: Creating a password file

1: Download and reset

2: Wait for reset

63

Page 64: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Example: Creating a password file

1: Download and reset

2: Wait for reset

3: Connect and enter default password

64

Page 65: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Example: Creating a password file

1: Download and reset

2: Wait for reset

3: Connect and enter default password

4: Enter site specific password

- From excel

- Twice!

65

Page 66: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Example: Creating a password file

1: Download and reset

2: Wait for reset

3: Connect and enter password

4: Enter site specific password

- From excel

- Twice!

5: Backup new password file

66

Page 67: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

Example: Creating a password file

1: Download and reset

2: Wait for reset

3: Connect and enter password

4: Enter site specific password

- From excel

- Twice!

5: Backup new password file

6: Save with site name

67

Page 68: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

A better way?

C:\gen_SCF.exe –user USER –password PASSWORD siteX.SCF

siteX.SCF generated.

C:\

68

• Command line tool

• Saves time

• Reduces errors

• Automation – Can create files for all sites at once

• Doesn’t actually exist (yet)

Page 69: Breakout Session 4 - SCADA - Invensysiom.invensys.com/AP/Documents/OpsManage-ANZ-2013/OpsManage_… · Breakout Session 4 - SCADA SCD5200 Usage & Project Implementation at SP AusNet

69

Questions?