    HIGH EFFICIENCY

    SINGLE PACKAGE HEAT PUMPS

    BP 090 & 120

    7-1/2 & 10 NOMINAL TONS

    9.3-10.7 EER (WORLD 50HZ)

    TECHNICAL

    GUIDE

    TECHNICAL

    GUIDE

    TM

    Tested in Accordance With:

    1This product was manufactured in

    a plant whose quality system is

    certified/registered as being

    in conformity with ISO9001.

    DESCRIPTION

    ASHRAE 90.1 COMPLIANT

    YORK Predator heat pump units are convertible single pack-

    ages with a common footprint cabinet and common roof curb for

    all 7-1/2 through 10 ton models. The units were designed for

    light commercial applications and can be easily installed on a roof

    curb, slab, or frame.

    All Predator heat pump units are self-contained and assembled

    on rigid full perimeter base rails allowing for 3-way forklift access

    and overhead rigging. Every unit is completely charged, wired,

    piped, and tested at the factory to provide a quick and easy field

    installation.

    All units are convertible between side and down airflow. Indepen-

    dent economizer designs are used on side and down discharge

    applications, as well as all tonnage sizes.

    RETURN HOME

    http://pagina%20inicial%20compactos%20heat%20pump.pdf/
  • 8/12/2019 BP090&120 50 HZ TECH

    2/24

    Unitary Products Group

    B P 120 C 00 A 7 A AA 1 A

    TABLE 1: PRODUCT NOMENCLATURE

    Model #Model Number

    DescriptionOptions

    B Product Category B = Single Package Heat Pumps

    P Product Identifier P = High Efficiency

    120 Nominal Cooling CapacityMBH

    090 = 7-1/2 Ton 120= 10 Ton

    C Heat Type C = Cooling Only

    00Nominal Heating

    Capacity00 = No Heat Installed

    A Airflow

    A = SM

    B = SM/EC/BR

    C = SM/EC/PE

    D = SM/MD

    N = High Static Motor

    P = High Static Motor/EC/BR

    Q = High Static Motor/EC/PE

    R = High Static Motor/MD

    7 Voltage 7 = 380/415-3-50

    A Installation Options

    A= None

    B = 1

    C = 2

    D = 1 & 2E = 3

    F = 4

    G = 1 & 3

    H = 1 & 4

    J = 1, 2 & 3

    K = 1, 2 & 4

    L = 1, 3 & 4

    M = 1, 2, 3 & 4

    N = 2 & 3

    P = 2 & 4

    Q = 2, 3 & 4

    R = 3 & 4

    AA Additional Options

    AA = NoneAB = PM

    AC = CG

    AD = DFS

    AE = PM & CG

    AF = PM & DFS

    AG = CG & DFSAH = PM, CG & DFS

    RC = CG & AM

    TA = TCC

    TB = TCC & PM

    TC = TCC & CG

    TD = TCC & DFS

    TE = TCC, PM & CG

    TF = TCC, PM & DFS

    TG = TCC, CG & DFS

    TH = TCC, PM, CG & DFS

    1 Product Generation 1 = First Generation

    A Product Style A = Style A

    TABLE 2: AIRFLOW ABBREVIATIONS

    ABBREVIATION MEANING

    BR Barometric Relief

    EC EconomizerMD Motorized Damper

    PE Power Exhaust

    SM Standard Motor

    TABLE 3: INSTALLATION ABBREVIATIONS

    ABBREVIATION MEANING

    1 Disconnect

    2 Convenience Outlet

    3 Smoke Detector Supply Air

    4 Smoke Detector Return Air

    TABLE 4: ADDITIONAL OPTIONS ABBREVIATIONS

    ABBREVIATION MEANING

    AM American Flag

    CG Coil GuardDFS Dirty Filter Switch

    PM Phase Monitor

    TCC Technicoat Condenser Coil

  • 8/12/2019 BP090&120 50 HZ TECH

    3/24Unitary Products Group 3

    FEATURES

    High Efficiency High efficiency units reach as high as

    10.7 EER.

    Service Friendly The Predatorincorporates a num-

    ber of enhancements which improve serviceability.

    The motor and blower slide out of the unit as a common

    assembly. This facilitates greater access to all the indoorairflow components, thus simplifying maintenance and

    adjustment.

    Service time is reduced through the use of hinged, tool-

    less panels. Such panels provide access to frequently

    inspected components and areas, including the control

    box, compressors, filters, indoor motor & blower, and the

    heating section. The panels are screwed in place at the

    factory to prevent access by children or other unautho-

    rized persons. It is recommended that the panels be

    secured with screws once service is complete.

    Service windows have been placed in both condenser

    section walls. Rotation of the cover allows easy access

    to the condenser coils for cleaning or inspection.

    The unit control board utilizes flash codes to aid in diag-

    nosis of unit malfunctions. Unique flash codes quickly

    identify the source of the unit alarm.

    All units use the same standard filter size. This stan

    dardization removes any confusion on which filter sizes

    are needed for replacement.

    The non-corrosive drain pan slides out of the unit to per-

    mit easy cleaning. The drain pan is accessed by remov

    ing the drain pan cover plate on the rear of the unit

    FIGURE 1 : PREDATOR COMPONENT LOCATION

    Compressor #1 Access

    (High-Eff Compressor)Tool-less

    Door Latch

    Side entry powerand control wiring

    knockouts

    Slide-out drain painwith steel 3/4 FPT

    Connection

    Belt-drive

    blower

    motor

    Condenser

    section

    Filter drier (solid core)Filter access(2 throw-away)

    Disconnect location

    (optional disconnect switch)

    Compressor #2Access (High-Eff

    Compressor)

    SimplicityTM Control

    board w/screw connec-

    tors for T-stat wiring and

    network connection

    Roof curbs in eight- and

    fourteen-inch heights.Roof

    curbs for transitioning from

    Sunline footprint to the

    BP series footprint are also

    available (field installed

    accessory)

    ase Rails w/ Fork-

    ift Slots (3 Sides)

    Lifting Holes

    Terminal blockfor hi-voltage

    connection

    Dual stage cool-ing for maximumcomfort (7-1/2 -10 Only)

    Second Model

    Nameplate Inside

    Control Door

    Slide-out motor and

    blower assembly for

    easyadjustmentand

    service.

  • 8/12/2019 BP090&120 50 HZ TECH

    4/244 Unitary Products Group

    Once the plate is removed, the drain pan slides out

    through the rear of the unit.

    All Predator units have a second model nameplate

    located inside the control access door. This is to prevent

    deterioration of the nameplate through weathering.

    Environmentally Aware For improved Indoor Air

    Quality, foil faced insulation is used exclusively through-out the units.

    Convertible Airflow Design The side duct openings

    are covered when they leave the factory. If a side sup-

    ply/return is desired, the installer simply removes the two

    side duct covers from the outside of the unit and installs

    them over the down shot openings. No panel cutting is

    required. Convertible airflow design allows maximum

    field flexibility and minimum inventory.

    System Protection Suction line freezestats are sup-

    plied on all units to protect against loss of charge and coil

    frosting when the economizer operates at low outdoor air

    temperatures while the compressors are running. Every

    unit has solid-core liquid line filter-driers and high and

    low-pressure switches. Internal compressor protection is

    standard on all compressors. Crankcase heaters are

    standard on reciprocating compressors. Scroll compres-

    sors do not require crankcase heaters.

    Advanced Controls - Predatorcontrol boards have

    standardized a number of features previously available

    only as options or by utilizing additional controls.

    Low Ambient- An integrated low-ambient control

    allows all units to operate in the cooling mode down

    to 0F outdoor ambient without additional assis-

    tance. Optionally, the control board can be pro-

    grammed to lockout the compressors when theoutdoor air temperature is low or when free cooling

    is available.

    Anti-Short Cycle Protection - To aid compressor

    life, an anti-short cycle delay is incorporated into the

    standard controls. Compressor reliability is further

    ensured by programmable minimum run times. For

    testing, the anti-short cycle delay can be temporarily

    overridden with the push of a button.

    Fan Delays- Fan on and fan off delays are fully pro-

    grammable. Furthermore, the heating and cooling

    fan delay times are independent of one another. All

    units are programmed with default values based

    upon their configuration of cooling and heating.

    Safety Monitoring- The control board monitors the

    high and low-pressure switches, the freezestats and

    the temperature limit switch on electric heat units.

    The unit control board will alarm on compressor

    lockouts and repeated limit switch trips.

    Nuisance Trip Protection and Strikes- To prevent

    nuisance trouble calls, the control board uses a

    three times, youre out philosophy. The high and

    low-pressure switches and the freezestats must trip

    three times within two hours before the unit control

    board will lock out the associated compressor.

    On Board Diagnostics- Each alarm will energize a

    trouble light on the thermostat, if so equipped, and

    flash an alarm code on the control board LED. Each

    high and low-pressure switch alarm as well as each

    freezestat alarm has its own flash code. The control

    board saves the five most recent alarms in memory,

    and these alarms can be reviewed at any time.

    Alarms and programmed values are retained

    through the loss of power.

    Reliable From the beginning All units undergo com-

    puter automated testing before they leave the factory.

    Units are tested for refrigerant charge and pressure, unit

    amperage, and 100% functionality. All Predatorunits

    are painted with a long lasting, powder paint that stands

    up over the life of the unit. The paint used has been

    proven by a 750 hour salt spray test.

    Flexible Placement All models and configurationsshare the same cabinet/footprint and thus the same roof

    curb. You have the flexibility to set one curb and choose

    the correct tonnage size after the internal loads have

    been determined.

    To further simplify planning and installation, Predator

    cabinets are designed to fit your roof. With the optional

    roof curb, the unit ductwork is designed to fit around 24

    on-center joists or between 48 on-center joists.

    The drain pan can be rotated to drain to either the front

    or the rear of the unit. Additionally, the drain pan can be

    fitted to drain through the roof curb. As it is sometimes

    difficult to have a level installation, the drain pan features

    a generous slope to ensure proper drainage.

    Full Perimeter Base Rails The permanently attached

    base rails provide a solid foundation for the entire unit

    and protect the unit during shipment. The rails offer fork-

    lift access from 3 sides, and rigging holes are available

    so that an overhead crane can be used to place the units

    on a roof.

    Easy Installation Electric utility knockouts are sup-

    plied in the unit underside as well as the side of the unit.

    A clearly identified location is provided to mount a field

    supplied electrical disconnect switch. Utility connections

    can be made quickly and with a minimum amount of field

    labor.

    All units are shipped with 2 throw-away filters installed.

    Wide Range of Indoor Airflows All indoor fan motors

    are belt-drive type providing maximum flexibility to han-

    dle most airflow requirements. For high static applica-

    tions, factory installed alternate indoor fan motors are

    available. With the optional indoor fan motor, all units can

    supply nominal airflow at up to 1.5 ESP.

  • 8/12/2019 BP090&120 50 HZ TECH

    5/24Unitary Products Group 5

    Warranty- All models include a 1-year limited warranty

    on the complete unit. Compressors and electric heater

    elements each carry a 5-year warranty.

    FACTORY INSTALLED OPTIONS

    YORKoffers several equipment options/accessories factory

    installed, for the Predator line.

    Alternate Indoor Blower Motor- For applications with

    high restrictions, units are offered with optional indoor

    motors that provide higher static output and/or higher air-

    flow, depending upon the installers needs.

    Coil Guard- Customers can purchase a coil guard kit to

    protect the condenser coil from damage. Additionally,

    this kit stops animals and foreign objects from entering

    the space between the inner condenser coil and the

    main cabinet. This is not a hail guard kit.

    Convenience Outlet - (Non-Powered) - This optionlocates a 120V GFCI single-phase outlet with cover on

    the corner of the unit housing the compressors. The

    installer must provide the 120V single-phase power

    source and wiring. Factory installed option only.

    Dirty Filter Switch- This kit includes a differential pres-

    sure switch that energizes the fault light on the unit ther-

    mostat, indicating that there is an abnormally high

    pressure drop across the filters. Factory installed option

    or field installed accessory.

    Disconnect Switch - For gas heat units, a HACR

    breaker sized to the unit is provided. For cooling units

    with electric heat, a switch sized to the largest electric

    heat available for the particular unit is provided. Factoryinstalled option only.

    Downflow Economizer- (With barometric relief) - The

    economizer is provided with a single enthalpy input. The

    economizer is 2% low leakage type. The economizers

    are shipped installed and wired. The installer needs only

    assemble and mount the outdoor air hood. The econo-

    mizer has spring return, fully modulating damper actua-

    tors and is capable of introducing up to 100% outdoor air.

    As the outdoor air intake dampers open, the return air

    dampers close. The changeover from mechanical refrig-

    eration to economizer operation is regulated by the stan-

    dard single enthalpy input. There is an optional input

    dual dry bulb available. To meet regulated air standards,the economizer control accepts an optional CO2input for

    demand ventilation.

    With single enthalpy input, the economizer control moni-

    tors outdoor air. The dual enthalpy kit provides a second

    input used to monitor the return air. With a dual input kit

    installed, the economizer control compares the values of

    the two enthalpy or temperature inputs and positions the

    dampers to provide the maximum efficiency possible.

    Sideflow Economizer- (Without barometric relief) - Al

    features as the downflow economizer exist except you

    must order the barometric relief separately.You mus

    order a 1EH0408 if you are installing a powe

    exhaust. You can order a 1RD0411 Barometric Relie

    kit for sideflow economizer only.

    Motorized Outdoor Air Damper- The motorized out

    door air damper includes a slide-in/plug-in dampe

    assembly with an outdoor air hood and filters. The out

    door air dampers open to the preset position when the

    indoor fan motor is energized. The damper has a range

    of 0% to 100% outdoor air entry. Factory installed option

    or field installed accessory.

    Power Exhaust (Downflow only) - This accessory

    installs in the unit with a down flow economizer. Powe

    exhaust plugs into the connector in the unit bulkhead.

    Phase Monitors- This accessory monitors the incoming

    power to the unit and protects the unit from phase loss

    and reversed phase rotation (Standard on units with

    scroll compressors).

    Smoke Detectors- The smoke detectors stop operation

    of the unit by interrupting power to the control board if

    smoke is detected within the air compartment.

    Stainless Steel Heat Exchanger- For applications in

    corrosive environments, this option provides a full stain

    less steel heat exchanger assembly.

    Technicoat Condenser Coils- The condenser coils are

    coated with a phenolic coating for protection against cor

    rosion due to harsh environments.

    Technicoat Evaporator Coil - The evaporator coil is

    coated with a phenolic coating for protection agains

    harsh environments.

    Novar BAS Control - The Novar ETC-3 building

    automation system controller is factory installed. Incudes

    supply air sensor, return air sensor, dirty filter indicato

    switch, and air proving switch.

    Johnson Controls BAS Control- The Johnson Contro

    YK-UNT-1126 building automation system controller is

    factory installed. Includes supply air sensor, return ai

    sensor, dirty filter indicator switch, and air proving switch

    CPC BAS Control - The Computer Process Controls

    Model 810-3060 ARTC Advanced Rooftop building auto

    mation system controller is factory installed. Includes

    supply air sensor, return air sensor, dirty filter indicatoswitch, and air proving switch.

    Honeywell BAS Control - The Honeywell W7750C

    building automation system controller is factory installed

    Includes air supply sensor, return air sensor, dirty filter

    indicator switch, and air proving switch.

    BAS Ready Economizer- The economizer is provided

    with a Belimo actuator that requires a 0-10V DC inpu

    from an external source (i.e., field installed building auto

    mation system controller). Barometric relief or powe

  • 8/12/2019 BP090&120 50 HZ TECH

    6/246 Unitary Products Group

    exhaust options are available. The economizer is 2% low

    leakage type with spring return and fully modulating

    dampers capable of introducing up to 100% outside air.

    Also include 2 pleated filters.

    FIELD INSTALLED ACCESSORIES

    YORK offers several equipment options/accessories forfield installation, for the Predator Magnum line.

    Barometric Relief- Zero to 100% capacity barometric

    relief damper for use with sideflow economizer.

    Burglar Bars- Mount in the supply and return openings

    to prevent entry into the duct work.

    CO2 Sensor - Senses CO2 levels and automatically

    overrides the economizer when levels rise above the

    preset limits.

    Coil Guard -Field installed decorative wire coil guard.

    Dirty Filter Switch- This kit includes a differential pres-

    sure switch that energizes the fault light on the unit ther-mostat, indicating that there is an abnormally high

    pressure drop across the filters.

    Enthalpy Accessory Control Kit- This kit contains the

    required components to convert a single enthalpy econo-

    mizer to dual enthalpy.

    Economizer(Downflow with barometric relief) - Econo-

    mizer with relief damper and single enthalpy input (2%

    low leakage damper).

    Spring return fully modulating motor capable of introduc-

    ing up to 100% outside air. For power exhaust, add the

    power exhaust accessory.

    Economizer(Horizontal) - Horizontal economizers aredesigned to install in the lower return section on the side

    of the unit. It is specifically designed for horizontal return

    applications. A 1EH0408 barometric relief/power

    exhaust hood must be purchased separately. You

    may also order a 1RD0411 Barometric Relief if a

    power exhaust isnt being installed. The horizontal

    economizer is available with standard single enthalpy

    control. Dual enthalpy may be added by installing the

    dual enthalpy kit.

    Electric Heaters- The electric heaters range from 18

    kW to 54kW and are available in all the voltage options

    of the base units. All heaters are dual staged. Cooling

    units include an adapter panel for easy installation of theelectric heaters. Necessary hardware and connectors

    are included with the heaters. All heaters are intended

    for single point power supply.

    Hail Guard - This kit includes a sloped hood which

    installs over the outside condenser coil and prevents

    damage to the coil fins from hail strikes. Field installed

    accessory only.

    Manual Outdoor Air Damper- Like the motorized out-

    door air damper, each manual outdoor air damper

    includes a slide-in damper assembly with an outdoor air

    hood and filters. Customers have a choice of dampers

    with ranges of 0% to 100% or 0% to 35% outdoor air

    entry.

    Power Exhaust- This accessory installs in the unit with

    a down flow economizer. Power exhaust plugs into the

    connector in the unit bulkhead.You must purchase

    1EH0408 barometric relief/power exhaust hood when

    applying to a sideflow application.

    Roof Curbs- The roof curbs have insulated decks and

    are shipped disassembled The roof curbs are available

    in 8 and 14 heights.

    For applications with security concerns, burglar bars are

    available for the duct openings of the roof curbs.

    Roof Curb AdaptorSingle Piece Adapter (10 High) -

    Roof curbs for transitioning from Sunline units to Pred-

    ator Magnum. Fits 7.5 to 12.5 Sunline roof curbs

    only.

    Smoke Detectors- The smoke detectors stop operation

    of the unit by interrupting power to the control board if

    smoke is detected within the air compartment.

    Thermostat- The units are designed to operate with 24-

    volt electronic and electro-mechanical thermostats. All

    units (with or without an economizer) operate with two-

    stage heat/two-stage cool or two-stage cooling only ther-

    mostats, depending upon unit configuration. Motorized Outdoor Air Damper- The motorized out-

    door air damper includes a slide-in/plug-in damper

    assembly with an outdoor air hood and filters. The out-

    door air dampers open to the preset position when the

    indoor fan motor is energized. The damper has a range

    of 0% to 100% outdoor air entry. Factory installed option

    or field installed accessory.

  • 8/12/2019 BP090&120 50 HZ TECH

    7/24Unitary Products Group 7

    TABLE 5: ACCESSORIES

    Part Number Description

    1RC0470 Roof Curb, 8" Height

    1RC0471 Roof Curb, 14" Height

    1RC0472 Roof Curb, Adapter (6-1/2 ton through

    12-1/2 ton) (1 Piece)

    2TP04510925 Electric Heat 9kW 230V2TP04511825 Electric Heat 18kW 230V

    2TP04512425 Electric Heat 24kW 230V

    2TP04513625 Electric Heat 36kW 230V

    2HP04505425 Electric Heat 54KW 230V (10 ton only)

    2HP04515425 Electric Heat 54kW 230V (12-1/2 ton only)

    2TP04510946 Electric Heat 9kW 460V

    2TP04511846 Electric Heat 18kW 460V

    2TP04512446 Electric Heat 24kW 460V

    2TP04513646 Electric Heat 36kW 460V

    2HP04515446 Electric Heat 54kW 460V

    2TP04510958 Electric Heat 9kW 575V

    2TP04511858 Electric Heat 18kW 575V

    2TP04512458 Electric Heat 24kW 575V2TP04513658 Electric Heat 36kW 575V

    2HP04515458 Electric Heat 54kW 575V

    1FA0411 Manual Outside Damper 6.5-12.5 T 0-35%

    1FA0412 Manual Outside Damper 6.5-12.5 T 0-100%

    2MD04702724 Motorized Damper Accessory

    (6-1/2 ton to 12-1/2 ton)

    2EE04705124 Economizer Downflow Accy

    6-1/2 - 12-1/2T w/ Baro Relief (124 LBS)

    2PE04703246 Power Exhaust Accy 6-1/2 - 12-1/2T 460V

    2PE04703258 Power Exhaust Accy 6-1/2 - 12-1/2T 575V

    2PE04703225 Power Exhaust Accy 6-1/2 - 12-1/2T 230V

    2EC04700924 Dual Enthalpy Control Accy

    1EH0407 Power Exhaust Hood with Barometric Relief Downflow (25 LBS)

    1EH0408 Power Exhaust (Duct Mount) Hood w/Barometric Relief (Sideflow)

    1RD0411 Barometric Relief (Duct Mount for Sidef low)

    2EE04700514 Economizer, Sideflow Accessory without Barometric Relief (6-1/2T to

    12-1/2T) (97 LBS)

    2AQ04700424 Sensor, CO2 Duct Accessory

    2AQ04700324 CO2 Space Accessory

    2SD04700224 Sensor, Duct Smoke Detector Accy for Supply or Return

    2DF0401 Dirty Filter Switch

    1CG0419 Coil Guard (3 Pieces for

    Electric / Electric / Heat Pump)

    1BD0408 Burglar Bars

    1HG0411 Hail Guard Kit

    1FL0402 Permanent Filter Kit

    2ET0770010024 Programmable Thermostat 2H, 2C

    2ET0770010124 Non-programmable Thermostat 2H, 2C

  • 8/12/2019 BP090&120 50 HZ TECH

    8/24

    TABLE 6: PHYSICAL DATA

    ComponentModels

    090 120

    Evaporator Blower

    Blower, Centrifugal Dia. X Wd. in. (Dia. X Wd. mm) 15 x 15 (381 x 381) 15 x 15 (381 x 381)

    Motor, Standard HP (kW) 1-1/2 (1.1) 2 (1.5)Motor, Optional HP (kW) 2 (1.5) 4 (3)

    Evaporator Coil

    Rows 3 4

    Fins per Inch (2.54 cm.) 15 15

    Height in. (mm) 40 (1020) 40 (1020)

    Face Area ft.2each (m2) 13.2 (1.23) 13.2 (1.23)

    Condenser Fan

    (2 per Unit)

    Propeller Dia. in., each (mm) 24 (610) 24 (610)

    Motor HP, each (kW) 3/4 (.56) 3/4 (.56)

    CFM, Nominal (each) 4000 4000

    Condenser Coil

    (2 per unit)

    Rows (each) 1 2

    Fins per Inch (2.54 cm) 20 20

    Height in., each (mm) 44 (1120) 44 (1120)

    Face Area ft.2each (mm) 14.5 (1.35) 14.5 (1.35)

    Refrigerant

    Charge

    System 1 lb./oz. (kg) 9 lbs. 4 oz. (4.20) 15 lbs. 12 oz. (7.14)

    System 2 lb./oz. (kg) 9 lbs. 0 oz. (4.06) 16 lbs. 8 oz. (7.48)

    CompressorsQuantity 2 2

    Type Recip Recip

    Air FiltersSize Wd. x Ht. x Thickness in. (Wd. x Ht x Thickness mm)

    25x20x2

    (635 x 508 x 51)

    25x20x2

    (635 x 508 x 51)

    Number Per Unit 4 4

  • 8/12/2019 BP090&120 50 HZ TECH

    9/24

    TABLE 7: COOLING CAPACITY 7-1/2 TON UNITRETURN AIR OUTDOOR AMBIENT TEMPERATURE (F): 85 OUTDOOR AMBIENT TEMPERATURE (F): 95

    W.B. GROSS*

    INPUT Sensible Capacity (MBH) GROSS*

    INPUT Sensible Capacity (MBH)

    CFM TEMP CAP. POWER

    Return Dry Bulb (F) CAP. POWER

    Return Dry Bulb (F)

    (F) (MBh) (kW) 86 83 80 77 74 71 68 (MBh) (kW) 86 83 80 77 74 71 68

    2250 72 109,0 8,71 61,0 54,6 48,2 41,7 35,3 103,6 9,41 58,2 51,8 45,4 39,0 32,5

    67 98,4 8,36 74,4 68,0 61,6 55,2 48,8 42,4 35,9 92,1 8,94 72,1 65,7 59,3 52,9 46,5 40,1 33,6

    62 89,2 8,02 87,8 81,3 74,9 68,5 62,1 55,7 49,3 83,4 8,60 83,4 79,1 72,7 66,2 59,8 53,4 47,0

    57 94,9 7,97 93,3 86,8 80,4 74,0 67,6 61,2 54,8 84,2 8,55 84,2 81,7 75,3 68,8 62,4 56,0 49,6

    2625 72 111,9 8,81 66,8 59,2 51,6 44,0 36,5 106,2 9,51 63,9 56,3 48,7 41,2 33,6

    67 101,0 8,45 81,2 73,6 66,0 58,5 50,9 43,3 35,7 94,4 9,03 78,9 71,3 63,7 56,1 48,5 41,0 33,4

    62 91,6 8,11 90,9 87,7 80,3 72,7 65,2 57,6 50,0 85,4 8,69 85,4 83,3 78,0 70,5 62,9 55,3 47,7

    57 97,4 8,06 96,6 93,4 86,2 78,6 71,1 63,5 55,9 86,3 8,64 86,3 85,1 80,8 73,3 65,7 58,1 50,5

    3000 72 114,8 8,90 72,6 63,8 55,1 46,3 37,6 108,8 9,61 69,6 60,8 52,1 43,4 34,6

    67 103,6 8,54 88,0 79,2 70,5 61,7 53,0 44,2 35,5 96,7 9,13 85,6 76,8 68,1 59,3 50,6 41,8 33,1

    62 94,0 8,20 94,0 94,0 85,7 77,0 68,2 59,5 50,7 87,5 8,78 87,5 87,5 83,4 74,7 65,9 57,2 48,4

    57 99,9 8,14 99,9 99,9 92,0 83,3 74,5 65,8 57,0 88,4 8,73 88,4 88,4 86,4 77,7 68,9 60,2 51,4

    3375 72 117,3 8,95 77,8 67,9 57,9 47,9 38,0 111,7 9,69 74,9 64,9 55,0 45,0 35,0

    67 105,9 8,58 94,0 84,0 74,1 64,1 54,1 44,2 34,2 99,4 9,21 91,8 81,8 71,8 61,9 51,9 41,9 32,0

    62 96,0 8,23 96,0 96,0 90,1 80,1 70,1 60,2 50,2 89,9 8,86 89,9 89,9 87,9 77,9 67,9 58,0 48,0

    57 102,1 8,18 102,1 102,1 96,7 86,7 76,8 66,8 56,8 90,9 8,80 90,9 90,9 89,8 79,9 69,9 59,9 50,0

    3750 72 119,7 8,99 83,0 71,9 60,7 49,5 38,3 114,7 9,77 80,2 69,0 57,8 46,6 35,5

    67 108,1 8,62 100,0 88,8 77,6 66,5 55,3 44,1 32,9 102,0 9,29 97,9 86,8 75,6 64,4 53,2 42,0 30,9

    62 98,1 8,27 98,1 98,1 94,4 83,3 72,1 60,9 49,7 92,3 8,93 92,3 92,3 92,3 81,1 70,0 58,8 47,657 104,2 8,22 104,2 104,2 101,4 90,2 79,0 67,8 56,7 93,3 8,88 93,3 93,3 93,3 82,1 70,9 59,7 48,5

    OUTDOOR AMBIENT TEMPERATURE (F): 105 OUTDOOR AMBIENT TEMPERATURE (F): 115

    2250 7 2 101,0 10,15 5 9,6 5 3,2 4 6,8 4 0,3 3 3,9 98,5 10,89 6 1,0 5 4,6 4 8,1 4 1,7 3 5,3

    67 87,9 9,64 73,7 67,3 60,9 54,5 48,1 41,6 35,2 83,7 10,35 75,3 68,9 62,5 56,1 49,6 43,2 36,8

    62 78,9 9,24 78,9 76,7 73,5 67,1 60,7 54,3 47,9 74,4 9,89 74,4 74,4 74,4 67,9 61,5 55,1 48,7

    57 79,1 9,20 79,1 77,8 74,6 68,2 61,8 55,4 48,9 73,9 9,86 73,9 73,9 73,9 67,5 61,1 54,7 48,3

    2625 7 2 102,5 10,20 6 3,6 5 6,0 4 8,5 4 0,9 3 3,3 98,7 10,89 6 3,3 5 5,8 4 8,2 4 0,6 3 3,0

    67 89,2 9,69 78,3 70,7 63,1 55,5 47,9 40,4 32,8 84,0 10,35 77,7 70,1 62,5 54,9 47,4 39,8 32,2

    62 80,0 9,29 80,0 78,9 76,3 68,7 61,1 53,6 46,0 74,6 9,89 74,6 74,6 74,6 67,0 59,4 51,8 44,2

    57 80,2 9,25 80,2 79,6 77,5 69,9 62,3 54,7 47,2 74,2 9,86 74,2 74,2 74,2 66,6 59,0 51,4 43,8

    3000 7 2 103,9 10,25 6 7,7 5 8,9 5 0,2 4 1,4 3 2,7 99,0 10,89 6 5,7 5 7,0 4 8,2 3 9,5 3 0,7

    67 90,5 9,74 82,8 74,1 65,3 56,6 47,8 39,1 30,3 84,2 10,35 80,1 71,3 62,6 53,8 45,1 36,3 27,6

    62 81,2 9,34 81,2 81,2 79,1 70,4 61,6 52,9 44,1 74,8 9,90 74,8 74,8 74,8 66,0 57,3 48,5 39,8

    57 81,4 9,30 81,4 81,4 80,4 71,6 62,9 54,1 45,4 74,4 9,86 74,4 74,4 74,4 65,6 56,9 48,1 39,4

    3375 72 106,0 10,32 73,2 63,2 53,3 43,3 33,3 100,3 10,96 71,5 61,6 51,6 41,6 31,7

    67 92,3 9,81 87,5 79,3 69,4 59,4 49,5 39,5 29,5 85,3 10,41 83,3 76,9 66,9 57,0 47,0 37,1 27,1

    62 82,8 9,41 82,8 82,8 81,8 71,9 61,9 51,9 42,0 75,8 9,95 75,8 75,8 75,8 65,8 55,8 45,9 35,9

    57 83,1 9,36 83,1 83,1 82,6 72,6 62,7 52,7 42,7 75,3 9,92 75,3 75,3 75,3 65,4 55,4 45,5 35,5

    3750 72 108,2 10,40 78,7 67,6 56,4 45,2 34,0 101,6 11,02 77,3 66,1 55,0 43,8 32,6

    67 94,2 9,88 92,2 84,6 73,4 62,3 51,1 39,9 28,7 86,4 10,47 86,4 82,5 71,3 60,1 49,0 37,8 26,6

    62 84,5 9,47 84,5 84,5 84,5 73,4 62,2 51,0 39,8 76,8 10,01 76,8 76,8 76,8 65,6 54,4 43,2 32,0

    57 84,8 9,43 84,8 84,8 84,8 73,6 62,4 51,3 40,1 76,3 9,98 76,3 76,3 76,3 65,1 54,0 42,8 31,6

    These capacities are gross ratings. For net capacity, deduct air blower motor, MBH = 3.415 x kW.

    Refer to the appropriate Blower Perfomance Table for the kW of the supply blower motor.

    These ratings include condenser fan motors and the compressor motors but not the supply air blower motor.

  • 8/12/2019 BP090&120 50 HZ TECH

    10/24

    TABLE 8: COOLING CAPACITY 10 TON UNIT

    RETURN AIR OUTDOOR AMBIENT TEMPERATURE (F): 85 OUTDOOR AMBIENT TEMPERATURE (F): 95

    W.B. GROSS*

    INPUT Sensible Capacity (MBH) GROSS*

    INPUT Sensible Capacity (MBH)

    CFM TEMP CAP. POWER

    Return Dry Bulb (F) CAP. POWER

    Return Dry Bulb (F)

    (F) (MBh) (kW) 86 83 80 77 74 71 68 (MBh) (kW) 86 83 80 77 74 71 68

    3000 72 132,5 10,59 80,7 72,2 63,6 55,1 46,5 128,2 11,47 77,3 68,8 60,2 51,7 43,1

    67 123,2 10,29 97,9 89,3 80,8 72,2 63,7 55,1 46,6 117,4 11,03 96,0 87,5 78,9 70,4 61,8 53,3 44,7

    62 114,9 9,95 114,9 108,7 100,2 91,6 83,0 74,5 65,9 110,5 10,73 110,5 104,5 95,9 87,3 78,8 70,2 61,7

    57 110,0 9,94 110,0 110,0 102,6 94,0 85,5 76,9 68,4 105,6 10,72 105,6 105,6 97,3 88,7 80,2 71,6 63,03500 72 137,3 10,70 88,1 78,0 67,9 57,8 47,7 132,6 11,57 85,0 74,9 64,8 54,7 44,5

    67 127,6 10,40 106,5 96,3 86,2 76,1 66,0 55,9 45,8 121,5 11,14 105,1 95,0 84,9 74,8 64,7 54,6 44,5

    62 119,1 10,05 119,1 116,0 106,9 96,8 86,7 76,6 66,5 114,3 10,82 114,3 111,3 103,2 93,1 82,9 72,8 62,7

    57 114,0 10,04 114,0 114,0 109,5 99,4 89,3 79,2 69,1 109,3 10,82 109,3 109,3 104,6 94,5 84,4 74,3 64,2

    4000 72 142,2 10,81 95,6 83,9 72,2 60,6 48,9 137,0 11,68 92,7 81,0 69,3 57,7 46,0

    67 132,1 10,51 115,0 103,4 91,7 80,0 68,4 56,7 45,0 125,5 11,24 114,2 102,5 90,9 79,2 67,5 55,9 44,2

    62 123,3 10,16 123,3 123,3 113,7 102,0 90,3 78,7 67,0 118,1 10,92 118,1 118,1 110,4 98,8 87,1 75,4 63,8

    57 118,0 10,15 118,0 118,0 116,4 104,8 93,1 81,5 69,8 112,9 10,92 112,9 112,9 112,0 100,3 88,7 77,0 65,3

    4500 72 145,1 10,87 103,9 90,6 77,3 64,0 50,7 140,5 11,77 100,9 87,6 74,3 61,0 47,7

    67 134,8 10,57 124,7 111,4 98,2 84,9 71,6 58,3 45,0 128,7 11,33 123,0 110,7 97,4 84,1 70,8 57,5 44,3

    62 125,8 10,22 125,8 125,8 121,0 107,7 94,4 81,1 67,8 121,1 11,01 121,1 121,1 117,2 104,0 90,7 77,4 64,1

    57 120,4 10,21 120,4 120,4 119,6 106,3 93,0 79,8 66,5 115,7 11,01 115,7 115,7 115,3 102,0 88,7 75,4 62,2

    5000 72 147,9 10,94 112,2 97,3 82,4 67,5 52,6 143,9 11,86 109,1 94,2 79,3 64,4 49,5

    67 137,5 10,63 134,4 119,5 104,6 89,7 74,8 59,9 45,0 131,9 11,41 131,9 118,8 103,9 89,0 74,1 59,2 44,3

    62 128,3 10,28 128,3 128,3 128,3 113,4 98,5 83,6 68,7 124,1 11,09 124,1 124,1 124,1 109,2 94,3 79,3 64,4

    57 122,8 10,27 122,8 122,8 122,8 107,9 93,0 78,1 63,2 118,6 11,09 118,6 118,6 118,6 103,7 88,8 73,9 59,0

    OUTDOOR AMBIENT TEMPERATURE (F): 105 OUTDOOR AMBIENT TEMPERATURE (F): 115

    3000 72 121,4 12,22 74,5 65,9 57,4 48,8 40,3 114,6 12,97 71,7 63,1 54,6 46,0 37,5

    67 109,6 11,71 92,6 84,0 75,5 66,9 58,4 49,8 41,3 101,9 12,38 89,1 80,6 72,0 63,5 54,9 46,3 37,8

    62 103,4 11,40 103,4 100,0 91,4 82,9 74,3 65,8 57,2 96,2 12,08 96,2 95,5 86,9 78,4 69,8 61,3 52,7

    57 102,0 11,44 102,0 98,4 89,9 81,4 72,8 64,2 55,7 98,3 12,16 98,3 91,1 82,6 74,0 65,5 56,9 48,3

    3500 72 125,5 12,33 82,3 72,2 62,1 52,0 41,9 118,4 13,09 79,7 69,6 59,5 49,4 39,3

    67 113,4 11,82 101,9 91,8 81,7 71,6 61,5 51,4 41,3 105,3 12,50 98,7 88,6 78,5 68,4 58,3 48,2 38,1

    62 106,9 11,51 106,9 105,2 99,0 88,8 78,7 68,6 58,5 99,5 12,19 99,5 99,1 94,7 84,6 74,5 64,4 54,3

    57 105,4 11,55 105,4 103,6 97,3 87,2 77,1 67,0 56,9 101,6 12,27 101,6 98,0 90,0 79,9 69,8 59,7 49,6

    4000 72 129,6 12,45 90,2 78,5 66,9 55,2 43,5 122,2 13,22 87,7 76,1 64,4 52,7 41,1

    67 117,1 11,93 111,3 99,6 87,9 76,3 64,6 52,9 41,3 108,7 12,62 108,3 96,6 85,0 73,3 61,6 50,0 38,3

    62 110,4 11,61 110,4 110,4 106,5 94,8 83,2 71,5 59,8 102,7 12,31 102,7 102,7 102,6 90,9 79,2 67,6 55,9

    57 108,9 11,65 108,9 108,9 104,7 93,0 81,4 69,7 58,1 104,9 12,38 104,9 104,9 97,4 85,8 74,1 62,4 50,8

    4500 72 132,3 12,55 97,8 84,5 71,3 58,0 44,7 124,2 13,33 94,8 81,5 68,2 54,9 41,7

    67 119,6 12,03 116,7 107,0 93,7 80,4 67,1 53,9 40,6 110,5 12,73 110,3 103,3 90,0 76,7 63,5 50,2 36,9

    62 112,7 11,71 112,7 112,7 110,8 97,5 84,2 70,9 57,6 104,4 12,42 104,4 104,4 104,3 91,0 77,7 64,5 51,2

    57 111,2 11,75 111,2 111,2 109,1 95,8 82,5 69,2 55,9 106,6 12,49 106,6 106,6 102,9 89,6 76,3 63,0 49,7

    5000 72 135,1 12,66 105,5 90,6 75,7 60,8 45,9 126,2 13,45 101,9 87,0 72,1 57,2 42,3

    67 122,0 12,13 122,0 114,4 99,5 84,6 69,7 54,8 39,9 112,2 12,84 112,2 110,0 95,1 80,2 65,3 50,4 35,5

    62 115,1 11,81 115,1 115,1 115,1 100,2 85,3 70,3 55,4 106,1 12,53 106,1 106,1 106,1 91,2 76,3 61,4 46,4

    57 113,5 11,85 113,5 113,5 113,5 98,6 83,7 68,7 53,8 108,3 12,61 108,3 108,3 108,3 93,4 78,5 63,6 48,7

    These capacities are gross ratings. For net capacity, deduct air blower motor, MBH = 3.415 x kW.

    Refer to the appropriate Blower Perfomance Table for the kW of the supply blower motor.

    These ratings include condenser fan motors and the compressor motors but not the supply air blower motor.

  • 8/12/2019 BP090&120 50 HZ TECH

    11/24Unitary Products Group 11

    TABLE 9: HEATING APPLICATION DATA 7-1/2 TON UNIT

    CFM ID DB CAP & kW

    OUTDOOR TEMPERATURE (F) (72% RH)

    -10 0 10 20 30 40 50 60

    2250

    55

    MBH 15.161 26.385 37.609 48.833 60.057 71.281 82.505 93.729

    KW 3.755 4.253 4.752 5.251 5.750 6.248 6.747 7.246

    70

    MBH 13.702 24.926 36.150 47.374 58.598 69.822 81.046 92.270

    KW 4.342 4.840 5.339 5.838 6.337 6.835 7.334 7.833

    80

    MBH 11.610 22.834 34.058 45.282 56.506 67.730 78.954 90.178

    KW 4.722 5.220 5.719 6.218 6.717 7.215 7.714 8.213

    3000

    55

    MBH 17.179 28.403 39.627 50.851 62.075 73.299 84.523 95.747

    KW 3.420 3.918 4.417 4.916 5.415 5.913 6.412 6.911

    70

    MBH 15.720 26.944 38.168 49.392 60.616 71.840 83.064 94.288

    KW 4.007 4.505 5.004 5.503 6.002 6.500 6.999 7.498

    80

    MBH 13.628 24.852 36.076 47.300 58.524 69.748 80.972 92.196

    KW 4.387 4.885 5.384 5.883 6.382 6.880 7.379 7.878

    3750

    55

    MBH 18.177 29.401 40.625 51.849 63.073 74.297 85.521 96.745

    KW 2.889 3.387 3.886 4.385 4.884 5.382 5.881 6.380

    70

    MBH 16.718 27.942 39.166 50.390 61.614 72.838 84.062 95.286

    KW 3.476 3.974 4.473 4.972 5.471 5.969 6.468 6.967

    80

    MBH 14.626 25.850 37.074 48.298 59.522 70.746 81.970 93.194

    KW 3.856 4.354 4.853 5.352 5.851 6.349 6.848 7.347

    THE MBH AND KW VALUES DO NOT INCLUDE THE SUPPLY AIR BLOWER MOTOR.

    FOR NET CAPACITY, ADD THE SUPPLY AIR BLOWER MOTOR HEAT (MBH = 3.415 x KW)

  • 8/12/2019 BP090&120 50 HZ TECH

    12/24Unitary Products Group 12

    TABLE 10: HEATING APPLICATION DATA 10 TON UNIT

    CFM ID DB CAP & kW

    OUTDOOR TEMPERATURE (F) (72% RH)

    -10 0 10 20 30 40 50 60

    3000

    55

    MBH 17.601 32.584 47.567 62.549 77.532 92.515 107.498 122.480

    KW 5.642 6.082 6.522 6.962 7.401 7.841 8.281 8.721

    70

    MBH 18.204 33.187 48.170 63.152 78.135 93.118 108.101 123.083

    KW 6.590 7.030 7.469 7.909 8.349 8.789 9.228 9.668

    80

    MBH 15.834 30.817 45.800 60.782 75.765 90.748 105.731 120.713

    KW 7.118 7.558 7.997 8.437 8.877 9.317 9.756 10.196

    4000

    55

    MBH 18.040 33.023 48.006 62.989 77.971 92.954 107.937 122.920

    KW 5.215 5.655 6.095 6.535 6.974 7.414 7.854 8.294

    70

    MBH 18.643 33.626 48.609 63.592 78.574 93.557 108.540 123.523

    KW 6.163 6.603 7.042 7.482 7.922 8.362 8.801 9.241

    80

    MBH 16.273 31.256 46.239 61.222 76.204 91.187 106.170 121.153

    KW 6.691 7.131 7.570 8.010 8.450 8.890 9.329 9.769

    5000

    55

    MBH 16.305 31.287 46.270 61.253 76.236 91.218 106.201 121.184

    KW 5.090 5.530 5.970 6.410 6.849 7.289 7.729 8.169

    70

    MBH 16.908 31.890 46.873 61.856 76.839 91.821 106.804 121.787

    KW 6.038 6.478 6.917 7.357 7.797 8.237 8.676 9.116

    80

    MBH 14.538 29.520 44.503 59.486 74.469 89.451 104.434 119.417

    KW 6.566 7.006 7.445 7.885 8.325 8.765 9.204 9.644

    THE MBH AND KW VALUES DO NOT INCLUDE THE SUPPLY AIR BLOWER MOTOR.

    FOR NET CAPACITY, ADD THE SUPPLY AIR BLOWER MOTOR HEAT (MBH = 3.415 x KW)

  • 8/12/2019 BP090&120 50 HZ TECH

    13/24

    Unitary Products Group 1

    TABLE 11: ELECTRICAL DATA 7-1/2 TON

    Voltage

    Compressors OD Fan

    Motors

    FLA ea.

    Blower Motor

    Supply FLAElectric Heater

    Min. Circuit

    Ampacity

    (Amps)

    Max Fuse*

    Size (Amps)

    RLA ea. LRA ea.1.5

    HP

    2

    HP

    Model

    #Rated kW Heater Amps 1.5 HP 2 HP 1.5 HP 2 HP

    380 8.0 62 1.1 4.3 5.2

    None - - 24.5 25.4 30 30

    2TP04510950 5.6 15.5 35.1 36.0 40 40

    2TP04511850 11.3 31.4 46.0 46.9 50 50

    2TP04512450 15.0 41.6 53.0 53.9 60 60

    2TP04513650 21.3 70.8 65.0 65.9 70 70

    415 8.0 62 1.1 4.3 5.2

    None - - 24.5 25.4 30 30

    2TP04510950 6.7 16.1 36.2 37.1 40 40

    2TP04511850 13.5 32.5 48.0 48.9 50 50

    2TP04512450 17.9 43.1 55.6 56.5 60 60

    2TP04513650 25.4 61.1 68.7 69.6 70 70

    * Maximum HACR breaker of the same AMP size is applicable.

    TABLE 12: ELECTRICAL DATA 10 TON

    VoltageCompressors OD Fan

    Motors

    FLA ea.

    Blower Motor

    Supply FLAElectric Heater

    Min. Circuit

    Ampacity

    (Amps)

    Max Fuse*

    Size (Amps)

    RLA ea. LRA ea. 2 HP 3 HP Model # Rated kW Heater Amps 2 HP 3 HP 2 HP 3 HP

    380 9.6 79 1.1 5.2 5.4

    None - - 29.0 29.2 35 35

    2TP04511850 11.3 31.4 50.5 50.7 60 60

    2TP04512450 15.0 41.6 57.5 57.7 60 60

    2TP04513650 21.3 59.1 69.5 69.7 70 70

    2HP04515450 33.8 93.8 70.7 70.9 80 80

    415 9.6 79 1.1 5.2 5.4

    None - - 29.0 29.2 35 35

    2TP04511850 13.5 32.5 52.5 52.7 60 60

    2TP04512450 17.9 43.1 60.1 60.3 70 70

    2TP04513650 25.4 61.1 73.2 73.4 80 80

    2HP04515450 40.4 97.2 76.8 77.0 80 80

    * Maximum HACR breaker of the same AMP size is applicable. Only 25.4kW of electric heat can be simultaneously energized with the mechanical heating. The full 40.4kW operates only if both

    compressors are locked-out

  • 8/12/2019 BP090&120 50 HZ TECH

    14/24

    Unitary Products Group

    TABLE 13: ADDITIONAL STATIC RESISTANCE

    CFM Cooling Only* Economizer Electric Heat KW

    9 18 24 36 54

    1900 0.06 0.02 0.05 0.06 0.07 0.08 0.10

    2100 0.07 0.02 0.06 0.07 0.08 0.09 0.11

    2300 0.08 0.02 0.07 0.08 0.09 0.10 0.13

    2500 0.09 0.02 0.08 0.09 0.10 0.11 0.14

    2700 0.11 0.03 0.09 0.10 0.12 0.13 0.16

    2900 0.12 0.03 0.10 0.11 0.13 0.14 0.18

    3100 0.14 0.03 0.12 0.13 0.15 0.16 0.20

    3300 0.16 0.03 0.13 0.14 0.17 0.18 0.22

    3500 0.18 0.04 0.15 0.16 0.19 0.20 0.24

    3700 0.20 0.04 0.17 0.18 0.21 0.22 0.26

    3900 0.23 0.04 0.19 0.20 0.23 0.24 0.28

    4100 0.25 0.04 0.21 0.22 0.25 0.26 0.31

    4300 0.28 0.05 0.23 0.24 0.28 0.29 0.344500 0.30 0.05 0.25 0.26 0.30 0.31 0.37

    4700 0.33 0.05 0.28 0.29 0.33 0.34 0.40

    4900 0.36 0.05 0.30 0.31 0.35 0.37 0.43

    5100 0.39 0.06 0.33 0.34 0.38 0.40 0.46

    5300 0.42 0.06 0.35 0.37 0.41 0.43 0.49

    5500 0.45 0.06 0.38 0.40 0.44 0.46 0.53

    5700 0.48 0.06 0.41 0.43 0.47 0.49 0.56

    5900 0.52 0.07 0.44 0.46 0.50 0.53 0.59

    6100 0.56 0.07 0.47 0.49 0.53 0.56 0.62

    6300 0.60 0.07 0.50 0.53 0.56 0.59 0.65

    * Add these resistance values to the available static resistance in the respective Blower Performance Tables. Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return

    air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.

    TABLE 14: 7-1/2 TON STANDARD MOTOR DOWN SHOT BLOWER PERFORMANCE*

    ESP

    TURNS OPEN**

    0 1 2 3 4 5

    CFM W BHP CFM W BHP CFM W BHP CFM W BHP CFM W BHP CFM W BHP

    0.2 - - - 3715 1573 1.69 3634 1434 1.54 3431 1265 1.36 3218 901 0.97 3024 976 1.05

    0.4 3650 1657 1.78 3510 1490 1.60 3320 1313 1.41 3079 1145 1.23 2832 810 0.87 2586 860 0.92

    0.63334 1522 1.63 3146 1351 1.45 2910 1169 1.25 2621 1005 1.08 2307 706 0.76 - - -

    0.8 2903 1352 1.45 2622 1167 1.25 2404 1013 1.09 2054 858 0.92 - - - - - -

    1.0 2356 1159 1.24 - - - - - - - - - - - - - - -

    * Blower performance is for gas heat which includes maximum number of heat tubes available for each tonnage. Add the E.S.P.

    from Table 17. Blower performance includes two-inch throwaway filters. ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been

    deducted from the total static pressure of the blower.** Turns Open refers to the setting of the variable pitch motor sheave, where 0 Turns Open is fully closed. W = Watts

  • 8/12/2019 BP090&120 50 HZ TECH

    15/24

    Unitary Products Group 1

    TABLE 15: 7-1/2 TON OPTIONAL MOTOR DOWN SHOT BLOWER PERFORMANCE*

    ESP

    TURNS OPEN**

    0 1 2 3 4 5

    CFM W BHP CFM W BHP CFM W BHP CFM W BHP CFM W BHP CFM W BHP

    0.2 - - - - - - - - - - - - 3992 1904 2.04 3798 1679 1.80

    0.4 - - - - - - - - - 3930 2017 2.16 3734 1786 1.92 3486 1552 1.66

    0.6 - - - - - - 3947 2176 2.33 3670 1895 2.03 3394 1641 1.76 3084 1401 1.50

    0.8 - - - 4138 2384 2.56 3623 2009 2.15 3323 1742 1.87 2971 1477 1.58 2591 1236 1.33

    1.0 4126 2430 2.61 3643 2145 2.30 3224 1820 1.95 2889 1569 1.68 2466 1306 1.40 - - -

    1.2 3613 2238 2.40 3143 1921 2.06 2748 1621 1.74 2369 1385 1.49 - - - - - -

    1.4 3099 2039 2.19 2636 1714 1.84 2195 1424 1.53 - - - - - - - - -

    1.6 2586 1833 1.97 - - - - - - - - - - - - - - -

    *

    Blower performance is for gas heat which includes maximum number of heat tubes available for each tonnage. Add the E.S.P.from Table 17.

    Blower performance includes two-inch throwaway filters. ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been

    deducted from the total static pressure of the blower.** Turns Open refers to the setting of the variable pitch motor sheave, where 0 Turns Open is fully closed. W = Watts

    TABLE 16: 10 TON STANDARD MOTOR DOWN SHOT BLOWER PERFORMANCE*

    ESP

    TURNS OPEN**

    0 1 2 3 4 5

    CFM W

    BHP CFM W

    BHP CFM W

    BHP CFM W

    BHP CFM W

    BHP CFM W

    BHP

    0.2 - - - - - - - - - 3896 1639 1.76 3688 1453 1.56 3447 1268 1.36

    0.4 4040 2076 2.23 4005 1934 2.07 3790 1698 1.82 3569 1508 1.62 3333 1330 1.43 3057 1147 1.23

    0.6 3890 2006 2.15 3697 1790 1.92 3427 1550 1.66 3152 1356 1.45 - - - - - -

    0.8 3620 1882 2.02 3324 1629 1.75 2972 1380 1.48 - - - - - - - - -

    1.0 3227 1708 1.83 - - - - - - - - - - - - - - -

    * Blower performance is for gas heat which includes maximum number of heat tubes available for each tonnage. Add the E.S.P.

    from Table 17. Blower performance includes two-inch throwaway filters. ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been

    deducted from the total static pressure of the blower.**

    Turns Open refers to the setting of the variable pitch motor sheave, where 0 Turns Open is fully closed. W = Watts

  • 8/12/2019 BP090&120 50 HZ TECH

    16/24

    Unitary Products Group

    TABLE 17: 10 TON OPTIONAL MOTOR DOWN SHOT BLOWER PERFORMANCE*

    ESP

    TURNS OPEN**

    0 1 2 3 4 5

    CFM W BHP CFM W BHP CFM W BHP CFM W BHP CFM W BHP CFM W BHP

    0.4 4965 3485 3.74 4875 3150 3.38 4613 2739 2.94 4322 2374 2.55 4156 2106 2.26 3907 1860 1.99

    0.6 4876 3416 3.66 4651 2997 3.21 4359 2582 2.77 4038 2220 2.38 3860 1966 2.11 3590 1724 1.85

    0.8 4713 3291 3.53 4387 2823 3.03 4077 2417 2.59 3719 2059 2.21 3541 1827 1.96 3242 1584 1.70

    1.0 4476 3116 3.34 4084 2632 2.82 3768 2245 2.41 3365 1892 2.03 3197 1691 1.81 - - -

    1.2 4165 2898 3.11 3741 2427 2.60 3432 2070 2.22 - - - - - - - - -

    1.4 3779 2646 2.84 3359 2212 2.37 3069 1895 2.03 - - - - - - - - -

    1.6 3319 2372 2.54 - - - - - - - - - - - - - - -

    * Blower performance is for gas heat which includes maximum number of heat tubes available for each tonnage. Add the E.S.P.

    from Table 17.

    Blower performance includes two-inch throwaway filters. ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been

    deducted from the total static pressure of the blower.** Turns Open refers to the setting of the variable pitch motor sheave, where 0 Turns Open is fully closed. W = Watts

    TABLE 18: 7-1/2 TON STANDARD MOTOR SIDE SHOT BLOWER PERFORMANCE*

    ESP

    TURNS OPEN**

    0 1 2 3 4 5

    CFM W BHP CFM W BHP CFM W BHP CFM W BHP CFM W BHP CFMW

    BHP

    0.4 - - - - - - 3736 1476 1.58 3487 1284 1.38 3231 1109 1.19 3001 970 1.04

    0.6 - - - 3572 1514 1.62 3389 1339 1.44 3094 1151 1.23 2764 972 1.04 2446 824 0.88

    0.8 3422 1558 1.67 3179 1364 1.46 2889 1164 1.25 2554 985 1.06 - - - - - -

    1.0 2891 1347 1.44 2372 1088 1.17 2050 922 0.99 - - - - - - - - -

    1.2 2017 1051 1.13 - - - - - - - - - - - - - - -

    * Blower performance is for gas heat which includes maximum number of heat tubes available for each tonnage. Add the E.S.P.

    from Table 17. Blower performance includes two-inch throwaway filters. ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been

    deducted from the total static pressure of the blower.** Turns Open refers to the setting of the variable pitch motor sheave, where 0 Turns Open is fully closed.

    W = Watts

  • 8/12/2019 BP090&120 50 HZ TECH

    17/24

    Unitary Products Group

    Blower performance includes dry coil and two-inch

    filters. Blower performance for gas heat includes the maximum

    number of heat tubes available for each tonnage.

    ESP (External Static Pressure) given is that available for

    the supply and return air duct system. All internal resis-tances have been deducted from the total static pressure

    of the blower.

    TABLE 19: 10 TON OPTIONAL MOTOR SIDE SHOT BLOWER PERFORMANCE*

    ESP

    TURNS OPEN**

    0 1 2 3 4 5

    CFM W BHP CFM W BHP CFM W BHP CFM W BHP CFM W BHP CFM W BHP

    0.2 - - - - - - - - - - - - 5067 2614 2.80 4809 2290 2.46

    0.4 - - - - - - 5179 3112 3.34 4884 2703 2.90 4729 2401 2.57 4459 2113 2.27

    0.6 - - - - - - 4925 2943 3.16 4585 2521 2.70 4429 2244 2.41 4137 1964 2.11

    0.8 - - - 4974 3220 3.45 4607 2727 2.92 4267 2342 2.51 4099 2080 2.23 3783 1809 1.94

    1.0 4975 3453 3.70 4657 2995 3.21 4305 2550 2.73 3941 2171 2.33 3751 1919 2.06 3371 1630 1.75

    1.2 4679 3423 3.67 4366 2808 3.01 4022 2373 2.54 3545 1978 2.12 3305 1741 1.87 - - -

    1.4 4429 3065 3.29 4040 2607 2.80 3669 2673 2.87 2918 1700 1.82 - - - - - -

    1.6 4107 2845 3.05 3620 2357 2.53 2931 1830 1.96 - - - - - - - - -

    1.8 3553 2500 2.68 2756 1899 2.04 - - - - - - - - - - - -

    2.0 2439 1939 2.08 - - - - - - - - - - - - - - -

    * Blower performance is for gas heat which includes maximum number of heat tubes available for each tonnage. Add the E.S.P.

    from Table 17. Blower performance includes two-inch throwaway filters. ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been

    deducted from the total static pressure of the blower.** Turns Open refers to the setting of the variable pitch motor sheave, where 0 Turns Open is fully closed. W = Watts

    TABLE 20: INDOOR BLOWER SPECIFICATIONS

    MODELMOTOR MOTOR SHEAVE BLOWER SHEAVE

    BELTHP RPM Eff. SF Frame Datum Dia. (in.) Bore (in.) Model Datum Dia. (in.) Bore (in.) Model

    BP0901-1/2 1725 80% 1.15 56 3.4 - 4.4 7/8 1VM50 7.5 1 AK79 A55

    2 1725 80% 1.15 56 3.4 - 4.4 7/8 1VM50 6.5 1 AK69 A53

    BP1202 1725 80% 1.15 56 3.4 - 4.4 7/8 1VM50 7 1 AK74 A54

    3 1725 80% 1.15 184T 4.3-5.3 1-1/8 1VP56 6.2 1 AK66 B55

  • 8/12/2019 BP090&120 50 HZ TECH

    18/24

    Unitary Products Group 1

    TABLE 21: 7-1/2 TON OPTIONAL MOTOR SIDE SHOT BLOWER PERFORMANCE*

    ESP

    TURNS OPEN**

    0 1 2 3 4 5

    CFM W BHP CFM W BHP CFM W BHP CFM W BHP CFM W BHP CFM W BHP

    0.4 - - - - - - - - - - - - - - - 3910 1726 1.85

    0.6 - - - - - - - - - - - - 3857 1842 1.98 3597 1430 1.53

    0.8 - - - - - - - - - 3804 1957 2.10 3503 1689 1.81 3172 1430 1.53

    1.0 - - - - - - 3774 2088 2.24 3406 1778 1.91 3032 1497 1.61 2248 1143 1.23

    1.2 - - - - - - 3327 1866 2.00 2926 1578 1.69 2160 1217 1.31 - - -

    1.4 - - - 3270 1971 2.11 2537 1544 1.66 2043 1296 1.39 - - - - - -

    1.6 3196 2077 2.23 2460 1651 1.77 - - - - - - - - - - - -

    1.8 2426 1768 1.90 - - - - - - - - - - - - - - -

    *

    Blower performance is for gas heat which includes maximum number of heat tubes available for each tonnage. Add theE.S.P. from Table 17.

    Blower performance includes two-inch throwaway filters. ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have

    been deducted from the total static pressure of the blower.** Turns Open refers to the setting of the variable pitch motor sheave, where 0 Turns Open is fully closed. W = Watts

    TABLE 22: 10 TON STANDARD MOTOR SIDE SHOT BLOWER PERFORMANCE*

    ESP

    TURNS OPEN**

    0 1 2 3 4 5

    CFM W

    BHP CFM W

    BHP CFM W

    BHP CFM W

    BHP CFM W

    BHP CFM W

    BHP

    0.2 - - - - - - - - - 4368 1843 1.98 4132 1624 1.74 3870 1423 1.53

    0.4 - - - 4515 2192 2.35 4213 1885 2.02 4020 1692 1.81 3791 1491 1.60 3499 1283 1.38

    0.6 - - - 4192 2027 2.17 3905 1741 1.87 3657 1537 1.65 3383 1345 1.44 3062 1149 1.23

    0.8 - - - 3838 1858 1.99 3534 1591 1.71 3236 1386 1.49 2934 1202 1.29 - - -

    1.0 3755 1942 2.08 3489 1695 1.82 3081 1425 1.53 - - - - - - - - -

    1.2 3337 1757 1.88 2918 1475 1.58 - - - - - - - - - - - -

    * Blower performance is for gas heat which includes maximum number of heat tubes available for each tonnage. Add the E.S.P.

    from Table 17. Blower performance includes two-inch throwaway filters. ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been

    deducted from the total static pressure of the blower.** Turns Open refers to the setting of the variable pitch motor sheave, where 0 Turns Open is fully closed. W = Watts

  • 8/12/2019 BP090&120 50 HZ TECH

    19/24Unitary P roducts Group

    FIGURE 2: UNIT DIMENSIONS

    TABLE 23: UNIT CLEARANCES

    Top*

    * Units must be installed outdoors. Overhanging structure or

    shrubs should not obstruct condenser air discharge outlet.

    72 Right 12

    Front 36 Left 36

    Rear

    To remove the slide-out drain pan, a rear clearance of 60 is

    required. If space is unavailable, the drain pan can be

    removed through the front by separating the corner wall.

    36 Bottom

    Units may be installed on combustible floors made from

    wood or class A, B or C roof covering materials.

    0

    DETAIL A

    DETAIL B

    5-3/8

    3/4" D ra in

    Opening

  • 8/12/2019 BP090&120 50 HZ TECH

    20/24

    036-21046-005-A-1102

    Unitary Products Group 2

    FIGURE 3: HORIZONTAL ECONOMIZER DETAIL

    FIGURE 4: DOWNFLOW ECONOMIZER HOOD DETAIL

  • 8/12/2019 BP090&120 50 HZ TECH

    21/24

    0A-1102

    Unitary Products Group

    FIGURE 5: PREDATOR ROOF CURB DIMENSIONS

    FIGURE 6: SUNLINE TO PREDATOR TRANSITION ROOF CURBS

  • 8/12/2019 BP090&120 50 HZ TECH

    22/24Unitary Products Group 2

    FIGURE 7: BOTTOM DUCT OPENINGS (FROM ABOVE)

    FIGURE 8: REAR DUCT DIMENSIONS

  • 8/12/2019 BP090&120 50 HZ TECH

    23/24

    JOB NAME:________________________________________LOCATION:_______________________________________

    PURCHASER:______________________________________ORDER NO:_______________________________________

    ENGINEER:_________________________________________________________________________________________

    SUBMITTED TO:__________________FOR: _______REF: ________APPROVAL:________ CONSTRUCTION:_______

    SUBMITTED BY:____________________________________DATE:____________________________________________

    UNIT DESIGNATION: SCHEDULE NO. __________________MODEL NO:_______________________________________

    SINGLE PACKAGE HEAT PUMP UNITS

    7-1/2 AND 10 TONS

    MODEL BP 090, AND 120

    036-22033-002 Rev A (0401) CD: 6-22033

    Supersedes: 036-22033-001 Rev A (500)

    COOLING PERFORMANCE

    TOTAL CAPACITY _____ MBH

    SENSIBLE CAPACITY _____ MBH

    OUTDOOR DESIGN TMP. _________ F DB/WB

    TOTAL SUPPLY AIR _____ CFM

    TEMP. OF AIR ENTERING

    EVAPORATOR COIL _____ F

    POWER INPUT REQ. _____ KW

    (LESS BLOWER MOTOR)

    HEATING PERFORMANCE

    CAPACITY @ 47F _____ MBH

    @ 17F _____ MBH

    COEFFICIENT OF PERFORMANCE

    @ 47F _____ MBH

    @ 17F _____ MBH

    ELECTRIC HEAT _____ KW

    SUPPLY AIR BLOWER PERFORMANCE

    TOTAL SUPPLY AIR _____ CFM

    EXT. STATIC PRESS. _____ IWG

    BLOWER SPEED ____ RPM

    POWER OUTPUT REQ. _____ BHPMOTOR RATING _____ HP

    POWER INPUT REQ. _____ KW

    ELECTRICAL DATA

    POWER SUPPLY __________

    TOTAL UNIT AMPACITY _____ AMPS

    MAX. OVERCURRENT DEVICE

    __ FUSE __ BREAKER _____ AMPS

    TOTAL UNIT WEIGHT

    INCLUDING FACTORY- INSTALLED

    OPTIONS _____ LBS

    For BaserailDimensionsSee Detail A

    8927

    59

    50-3/4

    4-1/4

    6-3/16

    17-3/16

    24-3/16

    30-3/16

    ConveniencePowerOutletEntry 7/8

    PowerEntry

    2-1/2

    30-11/32

    ControlEntry

    7/8

    PowerEntry

    2-1/2

    LEFT

    FRONTFor DrainDimensionsSee Detail B

  • 8/12/2019 BP090&120 50 HZ TECH

    24/24

    FACTORY INSTALLED OPTIONS

    ALTERNATE INDOOR BLOWER MOTOR- - - - - - - - - - - - - - - - !

    BAS OPTION

    Synthesys - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !

    Novar - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !

    COIL GUARD - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !

    CONVENIENCE OUTLET- - - - - - - - - - - - - - - - - - - - - - - - - - - !

    DIRTY FILTER SWITCH- - - - - - - - - - - - - - - - - - - - - - - - - - - - !

    DISCONNECT SWITCH- - - - - - - - - - - - - - - - - - - - - - - - - - - - !

    ECONOMIZERBarometric Relief- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !

    Power Exhaust - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !

    Dual Enthalpy - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !

    MOTORIZED AIR DAMPER- - - - - - - - - - - - - - - - - - - - - - - - - - !

    PHASE MONITOR1 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !

    SMOKE DETECTOR

    Supply Air- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !

    Return Air - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !

    TECHNICOAT CONDENSER COILS - - - - - - - - - - - - - - - - - - - - !

    FIELD INSTALLED ACCESSORIES

    COIL GUARD - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !

    DIRTY FILTER SWITCH- - - - - - - - - - - - - - - - - - - - - - - - - - - - !

    DISCONNECT SWITCH- - - - - - - - - - - - - - - - - - - - - - - - - - - - !

    ECONOMIZER

    Barometric Relief- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !

    Power Exhaust - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !

    Dual Enthalpy - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !

    CO2Sensor - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !

    ELECTRIC HEATER MODEL- - -________________________ !

    HAIL GUARD - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !

    LOW AMBIENT KIT - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !

    MOTORIZED OUTDOOR AIR DAMPER - - - - - - - - - - - - - - - - - - !

    MANUAL OUTDOOR AIR DAMPER- - - - - - - - - - - - - - - - - - - - !

    PERMANENT FILTERS - - - - - - - - - - - - - - - - - - - - - - - - - - - - !PHASE MONITOR1 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !

    ROOF CURB

    8 Roof Curb - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !

    14 Roof Curb - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !

    Transition Roof Curb - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !

    Burglar Bars (Downflow Only)- - - - - - - - - - - - - - - - - - - - - - - - - - !

    SMOKE DETECTOR

    Supply Air- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !

    Return Air - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !

    UNIT CLEARANCES

    Top1

    1. Units must be installed outdoors. Overhanging structure or

    shrubs should not obstruct condenser air discharge outlet.

    72 Right 12

    Front 36 Left 36

    Rear2

    2. To remove the slide-out drain pan, a rear clearance of 60 is

    required. If space is unavailable, the drain pan can be

    removed through the front by separating the corner wall.

    36 Bottom3

    3. Units may be installed on combustible floors made from

    wood or class A, B or C roof covering materials.

    0

    HORIZONTAL DISCHARGE DIMENSIONS

    ROOFCURB

    Dot Plugs

    18-1/4

    5-5/3228-1/4

    31-11/16

    2-31/32

    18-1/16

    28-1/4

    18-1/4

    ReturnAir

    SupplyAir