BOB, 27th floor, Gift City, Ahemdabad S.No. DESCRIPTION Amount (Rs) A) MV PANEL BOARDS 0.00 B) MV CABLES 0.00 C) SAFETY EQUIPMENTS 0.00 D) DISTRIBUTION BOARDS 0.00 E) POINT WIRING 0.00 F) ELV SYSTEM (DATA/TELE) 0.00 G) TELEPHONE SYSTEM 0.00 H) IP CCTV SYSTEM 0.00 I) ACCESS CONTROL SYSTEM 0.00 J) SENSOR SYSTEM 0.00 K) TV SYSTEM 0.00 L) LIGHTING FIXTURES 0.00 ELECTRICAL BOQ FOR BOB OFFICE AT 27TH FLOOR GIFTCITY, GUJARAT BOQ Electrical BOQ 1 M) FIRE ALARM SYSTEMS 0.00 N) PA SYSTEM FOR FIRE ALARM 0.00 O) EARTHING 0.00 P) FIRE SUPPRESSION SYSTEM 0.00 Q) VIDEO SYSTEM 0.00 R) RODENT PROTECTION SYSTEM 0.00 I TOTAL - II GST EXTRA AS APPLICABLE 0.00 III 0.00 GST 18% GRAND TOTAL AMOUNT (Rs) Electrical BOQ 1

Transcript of BOB ELECTRICAL BOQ WEB DISPLAY · 2019-07-19 · BOB, 27th floor, Gift City, Ahemdabad 16.0 17.0...

Page 1: BOB ELECTRICAL BOQ WEB DISPLAY · 2019-07-19 · BOB, 27th floor, Gift City, Ahemdabad 16.0 17.0 18.0 19.0 20.0 21.0 All connections shall be through, aluminium ferrules for aluminum

BOB, 27th floor, Gift City, Ahemdabad

S.No. DESCRIPTION Amount (Rs)

A) MV PANEL BOARDS 0.00

B) MV CABLES 0.00

C) SAFETY EQUIPMENTS 0.00

D) DISTRIBUTION BOARDS 0.00

E) POINT WIRING 0.00

F) ELV SYSTEM (DATA/TELE) 0.00

G) TELEPHONE SYSTEM 0.00

H) IP CCTV SYSTEM 0.00

I) ACCESS CONTROL SYSTEM 0.00

J) SENSOR SYSTEM 0.00

K) TV SYSTEM 0.00

L) LIGHTING FIXTURES 0.00

ELECTRICAL BOQ FOR BOB OFFICE AT 27TH FLOOR GIFTCITY, GUJARAT

BOQ

Electrical BOQ 1

)

M) FIRE ALARM SYSTEMS 0.00

N) PA SYSTEM FOR FIRE ALARM 0.00

O) EARTHING 0.00

P) FIRE SUPPRESSION SYSTEM 0.00

Q) VIDEO SYSTEM 0.00

R) RODENT PROTECTION SYSTEM 0.00I TOTAL -

II GST EXTRA AS APPLICABLE 0.00

III 0.00

GST 18%

GRAND TOTAL AMOUNT (Rs)

Electrical BOQ 1

Page 2: BOB ELECTRICAL BOQ WEB DISPLAY · 2019-07-19 · BOB, 27th floor, Gift City, Ahemdabad 16.0 17.0 18.0 19.0 20.0 21.0 All connections shall be through, aluminium ferrules for aluminum

BOB, 27th floor, Gift City, Ahemdabad

1.0

2.0

3.0

4.0

5.0

6.0

7.0

8.0

i)

ii)

iii)

iv)

v)

Execute the work as per specifications and drawings to the full satisfaction of engineer incharge.

All liabilities, obligations and risks arising out of conditions of contract.

Wastage on material and labour.

Loading, unloading, handling charges, hoisting the material to all upper levels.

The rates of all the items of the BOQ shall include the cost of :-

All materials, fixing hardware, accessories, tools and plants, freight, insurance, labour, taxes, duties, testing commissioning and

The work shall be executed as per relevant specification and drawings.

All material and equipment shall be as per specification and as per approved makes of material. Where specifications are notavailable the material shall be as per Indian standard specifications. The quantities and capacities of the equipments shall meetthe requirement for successful completion of the work.

All Electrical panel must have provision of potential free contacts for BMS/FAS.

All Electrical panel must have digital type energy meter with RS 485 port.

The installation and testing shall also be as per specifications and as per direction and satisfaction of Engineer in charge.

Contractor shall submit the shop drawings for approval by consultants / Engineer in charge. The work shall be carried out as per

Panels shall be fabricated as per specifications after approval of fabrication drawings by consultant / Engineer incharge.

Electrical BOQ 2

vi)

vii)

9.0

10.0

11.0

12.0

13.0

14.0

15.0

Testing and commissioning shall be carried out as per IS 732-1989 for the installation. The record of test results shall bemaintained and submitted to the engineer in charge who would check the same at random.

Contractor shall visit the site before quoting the rates and satisfying himself about the working conditions. Since this is a tallbuilding, hoisting the material to upper levels may be taken into account white quoting the rates. No extra claim on this accountshall be entertained.

Price bid shall be submitted online only

Totaling errors or missing amounts shall be corrected and incorporated in tendered amount.

Approval of all makes of material to be supplied out of approved list, shall be obtained by the contractor. Sample of the material

shall be kept at site to check with the material actually installed at site.

Engineer in charge may get the material tested at authorized labs. In case material is found under specifications as per IS, same

shall be replaced by the contractor. The test fee for 1st test shall be borne by the client but for subsequent test, fee due to failureof first sample, would be borne by the contractor.

In the event of conflict between BOQ, specifications and drawings, the most stringent shall apply. The decision of Architect /

Engineer incharge / Consultant shall be final and binding.

The quantities of the items in the BOQ are for general guidance only based on the consultants drawings and documents. The

All requirements for successful completion of the work whether mentioned in BOQ, specifications land drawings or not.

Electrical BOQ 2

Page 3: BOB ELECTRICAL BOQ WEB DISPLAY · 2019-07-19 · BOB, 27th floor, Gift City, Ahemdabad 16.0 17.0 18.0 19.0 20.0 21.0 All connections shall be through, aluminium ferrules for aluminum

BOB, 27th floor, Gift City, Ahemdabad

16.0

17.0

18.0

19.0

20.0

21.0

All connections shall be through, aluminium ferrules for aluminum conductors and copper ferrules for copper conductor cables.

Continuous earth wire shall run alongwith circuit wiring and point wiring. All switch boxes and fixtures shall be earthed. Only

Where only conduits are laid for other services 16 SWG steel wire shall run in the conduit for pulling the wires at later date, by

other agencies.

Earth wire with point wiring, circuit wiring, shall be of green colour with solid conductor.

DBs shall be circuit numbered.

As built drawing shall be prepared by the contractor after successful completion of the work these drawings shall incorporate the

actual layouts, routes of cables and conduits with sizes, locations of outlets, DBS switch rooms panel, Tag blocks EPABX,

Switches servers, fire detectors, zonal and main fire panels, location of CCTV cameras, monitors, etc. sets of blue prints of

switch drawings shall be submitted to the Engineer incharge for verification with actual layout at site and for record.

Electrical BOQ 3Electrical BOQ 3

Page 4: BOB ELECTRICAL BOQ WEB DISPLAY · 2019-07-19 · BOB, 27th floor, Gift City, Ahemdabad 16.0 17.0 18.0 19.0 20.0 21.0 All connections shall be through, aluminium ferrules for aluminum

BOB, 27th floor, Gift City, Ahemdabad

S.No. Description Unit Qty. Rate (Rs) Amount (Rs)

A) MV PANEL BOARDS

Design, fabrication, loading, unloading at store,Supply, installaton, testing &

commissioning as directed by Engineer-in-Charge, of LT Panels fabricated out of 2mm

thick for structural members (Load bearing members) and 1.6mm thick for door and

covers (Non load bearing members) CRCA sheet in cubicle compartmentalize free

standing floor mounted, dust and vermin proof with reinforcement of suitable size angle

iron, channel 'T' irons and / or flats wherever necessary, 16 gauge CRCA sheet steel

shall be used for final distribution panels. Cable gland plates shall be provided on top as

well as at the bottom of the panels. Panels shall be treated with all anticorrosive process

before painting as per specifications with 2 coats of zinc chromate primer and final

approved shade of enamelled paint. 2 Nos. earthing terminals shall be provided for all

distribution panels. Panels shall be suitable for 415V, 3-phase, 4-wire, 50Hz supply

system and with 15% spare space, lifting hooks shall also be provided in case of large

panels. Panel must be BMS/FAS Compatible.

Approval shall be taken for each panel before fabrication. Galvanized hardwares withzinc passivation shall be used in fabrication of panels.

General Notes:

1.0 MCCB:

MCCBs shall be used with Thermal Magnetic Based releases upto 250A andmicroprocessor based Over Load, Short Circuit / Earth Fault release.

2.0 Breaking capacity mentioned is Ics value.

3.0 This BOQ to be read in conjunction with technical specifications and Single Line Diagram(attached for reference). If any discrepancy occurs that should be brought to the notice ofClient/Consultant before quoting the price otherwise stringent condition will be deemed to

Electrical BOQ 4

have been considered.

4.0 All MCCBs shall be provided with rotary operating handle and ON/OFF lamps.

5.0 All meters shall be digital type (unless otherwise specified) with RS 485 Port.

6.0 All Incoming and outgoing breaker must have provision of Potential free contacts forBMS/FAS.

7.0 All MCBs shall be motor duty type.

8.0 All current/voltage transformer shall be cast resin type.

9.0 All indicating lamps shall be LED type.

10.0 Current density for Cu. bus bars shall not be more than 1.6A/Sqmm. Rating of Bus bar isafter considering all derating factors. (Bus bar sizing calculation to be submitted forapproval.)

11.0 All internal control wiring shall be heat resistant type.

12.0 All TP feeders shall be provided with Isolable neutral link.

13.0 Bus bar chamber & cable entry both shall be provided at top only.

14.0 All feeders shall be provided with door interlocked with door defeat, pad lock facility.

15.0 Live parts shall not be accessible after opening the door, Transparent acrylic sheet to beprovided to cover the same.

16.0 Spare contacts of MCCBs / Relay / Contactor shall be wired upto terminal block.

17.0 20% spare control terminal to be provided.

18.0 All incoming/outgoing cables shall be terminated on links/terminals.

Electrical BOQ 4

Page 5: BOB ELECTRICAL BOQ WEB DISPLAY · 2019-07-19 · BOB, 27th floor, Gift City, Ahemdabad 16.0 17.0 18.0 19.0 20.0 21.0 All connections shall be through, aluminium ferrules for aluminum

BOB, 27th floor, Gift City, Ahemdabad

1.0 MAIN PANEL :

Supply,Installation, testing & commissioning of compartmentalized Fabricated typepowder coated Power & Lighting Distribution boards as per Drawing, Specification. Theunit rate shall include loading/unloading, shifting from site store to the place ofinstallation, assembling the Panel including mounting & wiring of loose parts bymanufacturers, interconnection of shipping sections, installation on readymade Cabletrench (provied support for panel mounting) or directly on floor, assembling of looseaccessories supplied by the manufacturer, wiring & connection of auxiliary circuits,installation, testing & commissioning of all Panel, interlocking and supply of all necessary hardware. Aligning, levelling, grouting, testing and setting of relays and meters includingall hardware. ( 400Amp Cu Busbar 100% Nutral)

INCOMER :--1No. 400Amp. FP MCCB (36KA) with rotary handle, sperader link , on-off, trip indicator…

1 No. digital Multifunction Meter for measurement with all pera meters, RS-485 port,BMS compitible with selector Push button and one set of CTs of ratio 400A/5A, CL 1.0,15VA (RISH DELTA ENERGY of RISHABH or Equivalent)

OUTGOING :--12No. 63A-100A FP MCCB,1 Nos. 160A FP MCCB with require internal wiring, busbar,powder coated enclouser etc. as per requirment.

1.01 UPS PANEL :

Incomer

Three (3) Nos. 125A, 4P MCCB 25KA , connected as per SLD, to form a By-passarrangement.One (1) No.125A, 4P MCCB (25 kA)

2 No. digital Multifunction Meter for measurement of voltage and current with selectorPush button and one set of CTs of ratio 125A/5A, CL 1.0, 15VA (RISH DELTA ENERGYof RISHABH or Equivalent)6 Nos. phase indication lamps and 3 Nos. status indication lamp for ON/OFF/Trip withback up SPMCB.

Busbar

200A TPN Cu busbar of short circuit withstand capacity 36 kA. Bus bar shall be insulatedwith heat shrinkable sleeves and shall be color coded.

Nos. 1 0

Nos. 1 0

Electrical BOQ 6

Outgoing

4 Nos. 63A 4P MCCB.

4 Nos. 40/63A DP MCB.

TOTAL CARRIED OVER TO SUMMARY -

Electrical BOQ 6

Page 6: BOB ELECTRICAL BOQ WEB DISPLAY · 2019-07-19 · BOB, 27th floor, Gift City, Ahemdabad 16.0 17.0 18.0 19.0 20.0 21.0 All connections shall be through, aluminium ferrules for aluminum

BOB, 27th floor, Gift City, Ahemdabad

B) MV CABLES

1 Supplying, Laying, testing & commissioning of the following sizes of XLPE Al. Conductor

armoured cables of 1.1KV grade on the surface of wall or on existing cable trays

complete with hangers, properclamps fixing hardware etc. as required

a) 3.5 C x 185 Sq. mm Al. Cable Mtrs 245 0

b) 3.5 C x 70 Sq. mm Al. Cable Mtrs 315 0

c) 4 C x 50 Sq. mm Al. Cable Mtrs 85 0

d) 4 C x 35 Sq. mm Al. Cable Mtrs 165 0

e) 4 C x 25 Sq. mm Al. Cable Mtrs 225 0

f) 4 C x 16 Sq. mm Al. Cable Mtrs 280 0

g) 4 C x 10 Sq. mm Cu. Cable Mtrs 125 0

h) 4 C x 6 Sq. mm Cu. Cable Mtrs 175 0

i) 4 x 25 sqmm Copper Wire with conduit ( For, UPS input ) Mtrs 175 0

2 Suppling, making, testing & commissioning of end termination with brass mettalic double

compression glands suitable for the following sizes of XLPE Al. conductor arnoured

cables including proper sizes of copper thimbles etc. as required.

a) 3.5 C x 185 Sq. mm Al. Cable Nos. 6 0

b) 3.5 C x 70 Sq. mm Al. Cable Nos. 4 0

c) 4 C x 50 Sq. mm Al. Cable Nos. 6 0

d) 4 C x 35 Sq. mm Al. Cable Nos. 8 0

e) 4 C x 25 Sq. mm Al. Cable Nos. 12 0

f) 4 C x 16 Sq. mm Al. Cable Nos. 6 0

g) 4 C x 10 Sq. mm Cu. Cable Nos. 6 0

h) 4 C x 6 Sq. mm Cu. Cable Nos. 10 0

Electrical BOQ 7

) q Nos. 10 0

i) 4 x 25 sqmm Copper Wire with conduit Nos. 10 0

3 Supply and installation of following sizes of perforated GI cable tray made cut of 2 mmthick GI sheet, suspended from the ceiling or fixed on wall/column etc complete withsuspenders, runners and fixing hard ware etc. as required.

a) 50 mm x 450mm x 50 mm Mtrs 75 0

b) 50 mm x 300mm x 50 mm Mtrs 110 0

c) 50 mm x 150 mm x 50 mm Mtrs 230 0

4 Fabricating, supplying to site of installation, in floor including chase cutting of

floor,leveling, refilling and making good the same from 1.6 mm thick and 2 mm thick

cover pregalvanised MS CRCA sheet, totally enclosed, height 40 mm . The two lengths

of raceways shall be fitted with Collars , 50 mm wide, 3 mm thick , press fit type. The

raceways shall be clamped to the floor slab with GI clamps , 3mm thick and shall be

screwed to the floor slab. The joint between raceway and junction box will be made with

GI flexible strip( 3 nos), 3 mm thick, 4 inches long ,15 mm wide which will be nut bolted

to the Junction box complete as required etc.a) 50 mm x 50 mm( height) Mtrs 50 0

b) 100mm x 40 mm (height) Mtrs 150 0

c) 150mm x 40 mm (height) Mtrs 100 0

d) 200mm x 40 mm (height) Mtrs 170 0

e) 300mm x 40 mm (height) Mtrs 150 0

f) 400mm x 40 mm (height) Mtrs 75 0

5.0 Fabricating supplying to site of installation, Junction boxes for Floor and Ceiling

raceways made from 2 mm thick , with 2.5 mm thick GI cover including providing

neoprene gaskets between the cover and the junction box, cadmium plated flat/round

head screws, height as per site condition,totally enclosed. Proper cutouts shall be made

in the side walls for raceway entry wherever required. The junction box shall be all side

walls should be welded expect top cover and all side walls shall have suitable size of

rectangular knock out holes for taking raceways / conduits as required and not a

complete cut out. The top cover should be sealed with M Seal to make it dust and water

proof complete as required etc. a) 75 mm x 75 mm x 60 mm Nos. 15 0

b) 110 mm x 110mm x 60 mm Nos. 30 0

Electrical BOQ 7

Page 7: BOB ELECTRICAL BOQ WEB DISPLAY · 2019-07-19 · BOB, 27th floor, Gift City, Ahemdabad 16.0 17.0 18.0 19.0 20.0 21.0 All connections shall be through, aluminium ferrules for aluminum

BOB, 27th floor, Gift City, Ahemdabad

c) 160 mm x 160mm x 60 mm Nos. 25 0

d) 210 mm x 210 mm x 60 mm Nos. 21 0

e) 310 mm x 310 mm x 60 mm Nos. 35 0

f) 410 mm x 410 mm x 60 mm Nos. 10 0

6.0 100x50MM PVC trunking with end cap and coplar Supply & Fixing. Mtr. 80 0

TOTAL CARRIED OVER TO SUMMARY -

C) SAFETY EQUIPMENTS

1.0 Supplying & fixing or Rubber matting of 12 mm thick, 1 Mtrs wide suitable for voltage of

1.1 KV etc. as required. Sq.Mtrs 20 0

2.0 Supplying & fixing of Shock treatment chart printed in atle;ast three languages i.e, Hindi,English and a local language fitted in wooden frame and glass at front side and hardboard at back side etc. as required.

Nos. 1 0

Electrical BOQ 8Electrical BOQ 8

Page 8: BOB ELECTRICAL BOQ WEB DISPLAY · 2019-07-19 · BOB, 27th floor, Gift City, Ahemdabad 16.0 17.0 18.0 19.0 20.0 21.0 All connections shall be through, aluminium ferrules for aluminum

BOB, 27th floor, Gift City, Ahemdabad

3.0 Providing & fixing of MV / HV Danger Notice Plate of 200 mm x 150 mm ,made of mildsteel at least 2mm thick and vitreous enameled, white on both side & with inscription insignal red colour on front side as required.

Nos. 2 0

4.0 Supplying and fixing of carbon dioxide type fire extinguisher 4.5 kgs. capacity ofapproved make with wall mounting bracket (Push type) as required conforming to IS:15683-2006 (Latest ammended) .

Nos. 4 0

TOTAL CARRIED OVER TO SUMMARY 0

D) DISTRIBUTION BOARDS

Supplying, installation, testing & commissioning of following type wall mounted

Horizontal TPN/SPN distribution board of double door type design made out of MS sheet

with supplying and fixing following accessories including painting, interconnections,

painting, earthing and labeling etc. as required.

1.0 12 WAY TPN DB

Incoming

a) 63Amp TPN MCB (10KA) - 1 No

63Amp DP RCCB (30mA) - 3 Nos

Busbars

a) 100 Amp TPN copper busbars - 1 Set

Outgoing

a) 10/16/20/25 Amp SP MCB (10KA) - 36 Nos

Neutral links - 3 Nos (Separate for each phase)

2.0 8 WAY TPN DB

Incoming

a) 63Amp TPN MCB (10KA) - 1 No

63Amp DP RCCB (30mA) - 3 Nos

Set 8 0.0

Electrical BOQ 9

Busbars

a) 100 Amp TPN copper busbars - 1 Set

Outgoing

a) 10/16/20/25 Amp SP MCB (10KA) - 24 Nos

Neutral links - 3 Nos (Separate for each phase)

3.0 6 WAY TPN DB

Incoming

a) 63Amp TPN MCB (10KA) - 1 No

b) 63Amp DP RCCB (30mA) - 3 Nos

Busbars

a) 100 Amp TPN copper busbars - 1 Set

Outgoing

a) 10/16/20/25 Amp SP MCB (10KA) - 18 Nos

b) Neutral links - 3 Nos

Set 7 0.00

Set 5 0.00

Electrical BOQ 9

Page 9: BOB ELECTRICAL BOQ WEB DISPLAY · 2019-07-19 · BOB, 27th floor, Gift City, Ahemdabad 16.0 17.0 18.0 19.0 20.0 21.0 All connections shall be through, aluminium ferrules for aluminum

BOB, 27th floor, Gift City, Ahemdabad

(Separate for each phase)

4.0 250 Amp. 4 P ,25KA MCCB with Box for UPS Set 2 0

TOTAL CARRIED OVER TO SUMMARY -

E) POINT WIRING

1.0 Wiring for switch controlled Light Point with 3 x 1.5 Sq. mm PVC insulated FRLS

multistrand copper conductor 1100 Volt grade wires in recessed/surface MMS FRLS

PVC conduit with accessories including cost of providing saddles etc for surface

conduiting and/or cost of cutting and filling chases for recessed conduiting and including

the cost of supplying and fixing a 6 Amp 240 Volt grid plate mounted switch with moulded

cover plate in zinc chromate passivated MS box, and costing circuit wiring with 3 x

2.5sq. mm 1100 volt grade PVC insulated FRLS Multistrand copper conductor wires, in

PVC conduit complete as per specifications and as required.

(i) Primary Point Points 40 0.00

(ii) Secondary Point Points 80 0.00

2.0 Wiring for MCB controlled Light Point with 3 x 1.5 Sq. mm PVC insulated FRLS

multistrand copper conductor 1100 Volt grade wires in recessed/surface MMS FRLS

PVC conduit with accessories including cost of providing saddles etc for surface

conduiting and/or cost of cutting and filling chases for recessed conduiting.

(i) Primary Point Points 120 0.00

(ii) Secondary Point Points 385 0.00

3 0 Wiring for 5 pin 6 A Light plug point with 3 x 1 5 Sq mm PVC insulated FRLS multistrand

Electrical BOQ 10

3.0 Wiring for 5 pin 6 A Light plug point with 3 x 1.5 Sq.mm PVC insulated FRLS multistrand

copper conductor 1100 Volt grade wires in recessed/surface MMS FRLS PVC conduit

with accessories including cost of providing saddles etc for surface conduiting and/or

cost of cutting & filling chases for recessed conduiting, including the cost of providing &

fixing 1 No. Modular type 3 pin 6 A socket outlet controlled by 6 A switch in zinc

chromate passivated MS box, and circuit wiring with 3 x 2.5 sq mm complete as per

specfications and as required.

Points 20 0.00

4.0 Wiring for 3 nos. 5 pin 6 A Light plug point below table, controled by 16 A Switch on

table top with 3 x 2.5 Sq.mm PVC insulated FRLS multistrand copper conductor 1100

Volt grade wires in recessed/surface MMS FRLS PVC conduit with accessories

including cost of providing saddles etc for surface conduiting and/or cost of cutting &

filling chases for recessed conduiting, including the cost of providing & fixing 1 No.

Modular type 3nos.5 pin 6 A socket outlet controlled by 6 A switch in zinc chromate

passivated MS box, and circuit wiring with 3 x 2.5 sq mm complete as per specfications

and as required.

Points 495 0.00

5.0 Wiring for following. 13 A Socket controlled by 1 No. 16A Switch with 3 x 2.5 Sq. mmPVC insulated FRLS multi strand copper conductor 1100 Volt grade wires inrecessed/surface MMS FRLS PVC conduit with accessories including cost ofproviding saddles etc for surface conduiting and/or cost of cutting chases for recessedconduiting, including the cost of providing & fixing 1 No. Modular type 20 A socket outletcontrolled by 1 No. 6 A switch in zinc chromate passivated MS box, complete as perspecification and as required.

Points 40 0.00

6.0 Wiring for following. 2 Nos. 5 pin 6 A Power plug point controlled by 1 No. 16A Switchwith 3 x 2.5 Sq. mm PVC insulated FRLS multi strand copper conductor 1100 Volt gradewires in recessed/surface MMS FRLS PVC conduit with accessories including cost ofproviding saddles etc for surface conduiting and/or cost of cutting chases for recessedconduiting, in zinc chromate passivated MS box, complete as per specification and asrequired.

Points 495 0.00

Electrical BOQ 10

Page 10: BOB ELECTRICAL BOQ WEB DISPLAY · 2019-07-19 · BOB, 27th floor, Gift City, Ahemdabad 16.0 17.0 18.0 19.0 20.0 21.0 All connections shall be through, aluminium ferrules for aluminum

BOB, 27th floor, Gift City, Ahemdabad

7.0 Wiring for ceiling/wall fan Point with 3 x 1.5 Sq. mm PVC insulated FRLS multi strand

copper conductor 1100 Volt grade wires in surface / recessed, PVC conduit with

accessories including cost of providing saddles etc for surface conduiting and/or cost of

cutting and filling chases for recessed conduiting and including the cost of supplying and

fixing a 6 Amp 240 Volt grid plate mounted switch & 300W electronic regulator with

moulded cover plate in zinc chromate passivated MS box, and including the cost of

circuit wiring with 3 x 2.5sq. mm 1100 volt grade PVC insulated FRLS multi strand

copper conductor wire, inPVC conduit complete as per specifications and as required.

Points 15 0.00

Electrical BOQ 11Electrical BOQ 11

Page 11: BOB ELECTRICAL BOQ WEB DISPLAY · 2019-07-19 · BOB, 27th floor, Gift City, Ahemdabad 16.0 17.0 18.0 19.0 20.0 21.0 All connections shall be through, aluminium ferrules for aluminum

BOB, 27th floor, Gift City, Ahemdabad

8.0 Wiring for exhaust fan Point with 3 x 1.5 Sq. mm PVC insulated FRLS multi strand

copper conductor 1100 Volt grade wires in surface / recessed PVC conduit with

accessories including cost of providing saddles etc for surface conduiting and/or cost of

cutting and filling chases for recessed/surface MMS FRLS PVC conduit and including

the cost of supplying and fixing a 6 Amp 240 Volt grid plate mounted switch with moulded

cover plate in zinc chromate passivated MS box, and including the cost of circuit wiring

with 3 x 2.5sq. mm 1100 volt grade PVC insulated FRLS multi strand copper conductor

wire, complete as per specifications and as required.

Points 6 0.00

9.0 Wiring for 16A Single Phase metal clad socket outlet with 3 x 2.5 sqmm PVC insulatedFRLS multistrand copper wire of 1100 volt grade in recessed/surface MMS FRLSPVC conduit with accessories including supply and fixing 16A 3 pin metal clad plug andsocket and 16A SP MCB (MD) in IP 44 Poly carbonate box complete as per specificationand as required.

Point 10 0.00

10.0 Wiring for 20A Single Phase metal clad socket outlet with 2 x 4 +1 x 2.5 sqmm PVCinsulated FRLS multistrand copper wire of 1100 volt grade in recessed/surface heavyduty FRLS PVC conduit with accessories including supply and fixing 20A 3pin metalclad plug and socket and 20A SP MCB (MD) in IP 44 Poly carbonate box complete asper specification and as required.

Points 10 0.00

11.0 Wiring for 32A Single Phase metal clad socket outlet with 3 x 6 sqmm PVC insulatedFRLS multistrand copper wire of 1100 volt grade in recessed/surface heavy dutyFRLS PVC conduit with accessories including supply and fixing 32A 3pin Metal cladplug & socket and 32A SP MCB (MD) in IP 44 Poly carbonate box complete as perspecification and as required.

Points 4 0.00

12.0 Wiring for 20A 3 Phase metal clad socket outlet with 4 x 4 sqmm + 2 x 2.5 Sqmm PVC

insulated FRLS multistrand copper conductor wire of 1100 volt grade in

recessed/surface heavy duty FRLS PVC conduit with accessories including supply

and fixing 20A 5pin metal clad plug and socket and 20A 4P MCB (MD) in IP 44 Poly

carbonate box complete as per specification and as required.

Point 2 0.00

13 0 Wiring for 32A 3 Phase metal clad socket outlet with 4 x 4 sqmm + 2 x 2 5 Sqmm PVC

Electrical BOQ 12

13.0 Wiring for 32A 3 Phase metal clad socket outlet with 4 x 4 sqmm + 2 x 2.5 Sqmm PVC

insulated FRLS multistrand copper conductor wire of 1100 volt grade in

recessed/surface heavy duty FRLS PVC conduit with accessories including supply

and fixing 32A 5pin metal clad plug and socket and 32A 4P MCB (MD) in IP 44 Poly

carbonate box complete as per specification and as required.

Points 2 0.00

Electrical BOQ 12

Page 12: BOB ELECTRICAL BOQ WEB DISPLAY · 2019-07-19 · BOB, 27th floor, Gift City, Ahemdabad 16.0 17.0 18.0 19.0 20.0 21.0 All connections shall be through, aluminium ferrules for aluminum

BOB, 27th floor, Gift City, Ahemdabad

14.0 Providing and fixing of following sizes of PVC Flexibale Conduits suitable for various

applications, halogen free, oil and petrol resistant, flame retardant, self extiguishing, high

compressive strength and good wearing properties along with connectors complete with

conduit gland & all accessories required. a) 25mm dia RM 650 0.00

2.0 Supply & fixing the following sizes of PVC conduit in recessed or on surface of wall .

False ceiling including cutting the wall and making good the same as required.a) 25 mm dia Mtrs 1650 0.00

15

Supply, Laying & connection of 3#1.5 sq.mm copper flexible FR wires from DB/Panel toswitch board / Power Point in 25mm Dia. MMS PVC conduit in wall / slab / floor. The unitrate shall include rate of Supply, Laying & connection of pipes & wires. RM 800 0.00

16

Supply, Laying & connection of 2#2.5 sq.mm & 1#1.5 sq.mm copper flexible FR wiresfrom DB/Panel to switch board / Power Point in 25mm Dia. MMS PVC conduit in wall /slab / floor. The unit rate shall include rate of Supply, Laying & connection of pipes &wires.

RM 4500 0.00

17

Supply, Laying & connection of 2#4.0 sq.mm & 1#2.5 sq.mm copper flexible FR wiresfrom DB/Panel to switch board / Power Point in 25mm Dia. MMS PVC conduit in wall /slab / floor. The unit rate shall include rate of Supply, Laying & connection of pipes &wires.

RM 2500 0.00

TOTAL CARRIED OVER TO SUMMARY -

F) ELV SYSTEM (DATA/TELE)

LAN SYSTEM

1.0 Supplying and drawing of UTP 4 pair CAT 6A 23AWG LSOH LAN Cable in the existing

surface/ recessed steel/ PVC conduit as required. 4 Pair CAT6A LHOS Unshielded,

Twisted Pair (U/UTP) Cable 500 mtr per Box. Yellow (RAIL 1018) in colour conforming to

the following standards like EIA/TIA 568-C.2, EN50173, EN52288, IEC 11801, IEC

61156 5 500Mhz etc Cat 6A U/UTP cable with minimum bending radius when

Mtrs. 45000 0.00

Electrical BOQ 13

61156-5, 500Mhz etc. Cat 6A U/UTP cable with minimum bending radius when

laying(mm) is 36. (Make : Legrand / Panduit - Pannet/Siemon).

2.0 Supplying, installing, testing and commissioning of Cat 6A UTP , Tool less Information

outlet for Data. Cat6A U/UTP built in crimping hands-free, minimum 5 times reconnection

possibilities. LCS2 Toolless RJ45 Information outlet where insertion test (in & out) must

be 2500 times (I/O) along with front side Label holded and projection white in colour,

including front plate and anodised GI box in concealed manner of adequate sizes,

including all fixing accessories. Standard & Approval : ISO 11801 2nd ED, EN 50173 2nd

ED, EIA/TIA-568-B.2, NF C 20730, Standard 8077 - 603.7 (Make : Legrand / Panduit -

Pannet/Siemon).

Nos. 525 0.00

3.0 Supplying, installing, testing and commissioning of 48 port 1U Cat 6A UTP Patch Panels

available with block of four equipped with tool less IO, Rack Mountable. 19" Modular

Patch Panel, loaded CAT6A U/UTP 24 port LCS2 rack mountable to be compatible in

4nos of 6 X RJ 45 Tool less connector U/UTP unit in a block. Standard & Approval : ISO

11801 2nd ED, EN 50173 2nd ED, EIA/TIA-568-B.2, NF C 20730, Standard 8077 - 603.7

(Make: Legrand / Panduit - Pannet/Siemon).

Nos. 12 0.00

4.0 4 Feet : CAT6A UTP 26 AWG LSOH Patch Cord - 1 mtr - Rack End for Data Points.

Factory crimped LCS2 Patch cord in Green colour. Standard & Approval : EN 50173,

ISO/IEC 60603-7, ISO/IEC 11801 (Make: Legrand / Panduit - Pannet/Siemon).

Nos. 525 0.00

5.0 7 Feet : CAT6A UTP 26 AWG LSOH Patch Cord - 2 mtr - User End for Data Points.

Factory crimped LCS2 Patch cord in Green colour. Standard & Approval : EN 50173,

ISO/IEC 60603-7, ISO/IEC 11801 (Make: Legrand / Panduit - Pannet/Siemon).

Nos. 525 0.00

6.0 Supplying and fixing following Modular base & cover plate on existing modular metalboxes etc. as required.

7.0 1 Module : Single Module Face Plate with Arteor White (Make: Legrand/Panduit -

Pannet/Siemon).Nos. 10 0.00

8.0 2 Module : Dual Module Face Plate with Arteor White (Make: Legrand/ Panduit -

Pannet/Siemon).Nos. 300 0.00

Electrical BOQ 13

Page 13: BOB ELECTRICAL BOQ WEB DISPLAY · 2019-07-19 · BOB, 27th floor, Gift City, Ahemdabad 16.0 17.0 18.0 19.0 20.0 21.0 All connections shall be through, aluminium ferrules for aluminum

BOB, 27th floor, Gift City, Ahemdabad

9.0 Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed

steel/PVC conduit as required. 4 Pair CAT6 Unshielded, Twisted Pair (U/UTP) Cable 305

mtr per Box. Blue in colour conforming to the following standards like ANSI/TIA 568 C.2,

EN50173, IEC 11801 2nd ED, 700Mhz etc. in Cat 6 U/UTP LCS2 cable with 23AWG.

Mtrs. 32000 0.00

10.0 Supplying, installing, testing and commissioning of Cat 6 , Tool less Information outlet for

Data,Voice,CCTV,Wi-Fi, & Access Control. Cat6 U/UTP built in crimping hands-free,

minimum 5 times reconnection possibilities. LCS2 Toolless RJ45 Information outlet

where insertion test (in & out) must be 2500 times (I/O) along with front side Label holded

and transparent shutter for projection Arteor category white in colour, including front plate

and anodised GI box in concealed manner of adequate sizes,including all fixing

accessories.Makes : LEGRAND / PANDUIT / SIEMON

Nos. 495 0.00

11.0 Supplying, installing, testing and commissioning of 24 port Cat 6 patch panels available

with block of four equipped with tool less IO, Rack Mountable. 19" Modular Patch Panel,

loaded CAT6 U/UTP 24 port LCS2 rack mountable to be compatible in 4nos of 6 X RJ 45

Tool less connector U/UTP unit in a block.Makes : LEGRAND / PANDUIT / SIEMON

Nos. 22 0.00

12.0 Supplying, installing, testing and commissioning of following length of Cat - 6 patch cord.

4 Feet : CAT6 UTP 23 AWG Patch Cord - 1 mtr - Rack End. Factory crimped LCS2

Patch cord in Blue colour. Makes : LEGRAND / PANDUIT / SIEMON

Nos. 495 0.00

13.0 Supplying, installing, testing and commissioning of following length of Cat - 6 patch cord.

7 Feet : CAT6 UTP 23 AWG Patch Cord - 2 mtr - User End.Factory crimped LCS2 Patch

cord in Blue colour. Makes : LEGRAND / PANDUIT / SIEMON

Nos. 495 0.00

14.0 Supplying and fixing following Modular base & cover plate on existing modular metalboxes etc. as required.1 or 2 Module Face Plate. Makes : LEGRAND / PANDUIT / SIEMON

Nos. 495 0.00

15.0 Supplying, installing, testing and commissioning of Cabinet. Size 2026 X 800 X 800 mm

Electrical BOQ 14

(HXWXD) following accessories, Width (mm) 800, Depth (mm) 800, Approx.Net Wt (kg)

150, CRCA 'D' Grade thickness (mm) 1.2, RAL 9017(Matt Black), Glass: 4mm

Toughened Tinted Glass Door,Injected one piece polyurethane gasket on frame,

Accessories: Cooling Fan (230V A/C 90 CFM) - 4 Nos, Cable Manager Metal- 4

Nos,PDU 230VAC - 1 No (12 nos. 6A/16A sockets with plugs 6A/16A - 1/1pc & MCB

16A/32A -0/1 Pc), cable channel 100mm wide 42U- 2 Nos,Heavy Duty Stationary shelf

M6 screws,washer,cage nuts (nickel coated))3 Nos. Earthling Strips 150mm H - 1 No,

Door Lock - 1 No, Castor Wheels (with Brake) - 2 Nos, Castor Wheels (without Brake) - 2

Nos, Front Metal Band - 1 No. Packing: 5 ply cardboard & Inside 28 ply EP foam. In the

rack there must be maintained 1 U = 1.75 inches space. Nos. 1 etc complete as required

Nos. 3 0.00

16.0 Supply , Installation , Testing and Commissioning of L3 Switch should have Min 24

x100/1000T , Min 4 X 10 G Based SFP+ port , 2x Stacking port comprising 140 Gbps of

stacking bandwidth from day 1, Support less than 50 Millisecond convergence based of

RFC 3619./REP/G.8032 , Min Operating temp 0-50 Degree C ,Must have Common

criteriacertification EAL3/NDcPP/NDPP, should support AVB,CE.2 and CB certified.RPS

Support . Min 196 Gbps switching backplane , Min 220 Mpps forwarding Rate .Should

be upgardable to Min 2x QSFP+ port .Operating Temperature 0-50 Degree C , Should

support SyNCE E , MPLS .Auto adustable fan based on temperture variation.

Makes : Juniper / HP / Cisco / Extreme

Nos. 1 0.00

Electrical BOQ 14

Page 14: BOB ELECTRICAL BOQ WEB DISPLAY · 2019-07-19 · BOB, 27th floor, Gift City, Ahemdabad 16.0 17.0 18.0 19.0 20.0 21.0 All connections shall be through, aluminium ferrules for aluminum

BOB, 27th floor, Gift City, Ahemdabad

17.0 Supply , Installation , Testing and Commissioning of Access switch should have 24

x10/100/1000T port , , should be upgradable to Min 4x 10 G based SFP+ port , 2x

Stacking port comprising 10 Gbps of stacking bandwidth from day 1 ,Support less than

50 Millisecond convergence based of RFC , Min Operating temp 0-50 Degree C ,Must

have Common criteriacertification EAL3/NDcPP/NDPP, should support AVB,CE.2 and

CB certified.RPS Support.Auto adustable fan based on temperture variation.

Makes : Juniper / HP / Cisco / Extreme

Nos. 18 0.00

18.0 Supply , Installation , Testing and Commissioning of Access switch should have 24x10/100/1000T port , , should be upgradable to Min 4x 10 G based SFP+ port , 2xStacking port comprising 10 Gbps of stacking bandwidth from day 1 ,Support less than50 Millisecond convergence based of RFC , Min Operating temp 0-50 Degree C ,Musthave Common criteriacertification EAL3/NDcPP/NDPP, should support AVB,CE.2 andCB certified.Min 370 Watt PoE/PoE+ power budget based on IEEE 802.3af/IEEE802.3at,RPS Support, Min 1GB RAM & 4GB Flash.Auto adustable fan based ontemperture variation.Makes : Juniper / HP / Cisco / Extreme

Nos. 4 0.00

19.0 OM3 6 Core Fiber Cable in PVC Conduite Supply & Laying. Mtr 350 0.00

20.0 FIBER SLIDING DRW liu 24 PORT, LC ADAPTER PLATE MM 12 PORT, BLANKS FOR LIU, FUFION SPLICE, PIGTAIL SUPPLY & FIXING Set 8 0.00

21.0 OM 3 LC Patch coard 3 Mtr Supply & Fixing. Nos. 8 0.00

22.0 500 Pair Telephone Tag Box With Krone Strip Supply & Fixing. Nos. 2 0.00

23.0 100 Pair Jelly Arm Cable Supply & Laying. Mtr. 250 0.00

TOTAL CARRIED OVER TO SUMMARY 0.00

G) TELEPHONE SYSTEM

Electrical BOQ 15

1.0 Supply , Installation , Testing and Commissioning of KTS Telephone instrument - ( NEC - SV NEC 9100 or equivalent )Makes : Cisco / NERON / Karel /

Nos. 2 0.00

Electrical BOQ 15

Page 15: BOB ELECTRICAL BOQ WEB DISPLAY · 2019-07-19 · BOB, 27th floor, Gift City, Ahemdabad 16.0 17.0 18.0 19.0 20.0 21.0 All connections shall be through, aluminium ferrules for aluminum

BOB, 27th floor, Gift City, Ahemdabad

2.0 Supply , Installation , Testing and Commissioning of Telephone Instrument. ( Beetel: M71 or equivalent)Makes : / BEETEL /BINATONE/PANASONIC

Nos. 450 0.00

TOTAL CARRIED OVER TO SUMMARY -

H) IP CCTV SYSTEM

1.0 Supply , Installation , Testing and Commissioning of 4 MP Dome Camera ,UL , CE , FCC

Certified , 1/2.8" CMOS sensor ,2.8mm to 12 mm varifocal , triple stream ,Min

Illumination :0.05Lux @ (F1.2,AGC ON), 0 Lux with IR , Shutter Speed : 1/5 ̴ 1/100,000

s , Video Compression : H.265 , H.264 ,frame rate 30 fps @ 3MP , Inbuilt IR LED , IR

distance upto 30 mtrs ,IP 66 , POE .Make s : Pelco / Honeywell/ AXIS

Nos. 12 0.00

2.0 Supply , Installation , Testing and Commissioning of 4 MP Bullet Camera ,S & G ,UL , CE

, FCC Certified , 1/2.8" CMOS sensor ,3.6 mm fixed focal , triple stream ,Min Illumination

:0.05 Lux @ (F1.2, AGC ON), 0 Lux with IR , Shutter Speed : 1/5 ̴ 1/100,000 s , Video

Compression : H.265 , H.264 , 120 dB WDR ,frame rate 30 fps @ 3MP , Inbuilt IR LED ,

IR distance upto 30 mtrs ,IP 66 , POE

Makes : Pelco / Honeywell / AXIS

Nos. 4 0.00

3.0 Supply , Installation , Testing and Commissioning of 16 Channel NVR , 2 SATA ports ,

each SATA capacity of upto 6 TB , Recording Bandwidth 200 Mbps , 1 X HDMI , 1 X

VGA , Alarm : 16ch in / 1ch out , 1 X RJ45 port , 1x3.0 USB for backup / upgrade, 2x 2.0

USB for mouse , Smart Phone support : iOS, Android.

Makes : Pelco / Honeywell / AXIS

Nos. 1 0.00

4.0 Supply , Installation , Testing and Commissioning of 6TB Surviellance Hard Disk. Nos. 2 0.00

5.0 Supply , Installation , Testing and Commissioning of Full HD 42" LED ProfessionalNos 1 0 00

Electrical BOQ 16

Display Panel. Nos. 1 0.00

6.0 Supply , Installation , Testing and Commissioning of 24 port L2 Managed switch having

port density 24 Nos. of 10M/100M/1G RJ45 Port POE/POE+ ports , 4 Nos. of 1G/10G

SFP+ Port , 1X console port , Available POE power 370 W , 128 Gbps switching

bandwidth , Support L2 feature STP, RSTP ,MSTP . Support 802.1Q VLAN , port based

VLAN , MAC based VLAN , IP subnet based VLAN . Support IEEE 802.3ad LACP . L3

features - static routing , DHCP server , Device Management system - topology view ,

floor view , map view , dashboard , traffic monitoring , cable diagnostics.CE,FCC

certified.

Makes : Juniper / HP / Cisco / Extreme

Nos. 1 0.00

TOTAL CARRIED OVER TO SUMMARY -

Electrical BOQ 16

Page 16: BOB ELECTRICAL BOQ WEB DISPLAY · 2019-07-19 · BOB, 27th floor, Gift City, Ahemdabad 16.0 17.0 18.0 19.0 20.0 21.0 All connections shall be through, aluminium ferrules for aluminum

BOB, 27th floor, Gift City, Ahemdabad

I) ACCESS CONTROL SYSTEM

1.0 ACS Controller:

Supply, installing, testing and commissioning of Standalone Controller :- 2.4-inch TFT

color screen and Touch keys, Ultra thin and elegant design With Builtin Wifi Fingerprint

Identification Fingerprint Capacity: 3,000 Log Capacity: 30,000

Communication:TCP/IP,RS232/485,USB Host Access Control Interface for electric

lock,door sensor,alarm,exit button and door bell. Wiegand input&output

Nos. 10 0.00

2.0 Exit Reader :- Finger Print Reader Weather Proof Read Fingerprint and Proximity card Communication: RS485 with inBIO controller or Fingerprint devices DIP switch for RS485 address

Nos. 10 0.00

3.0 RFID Cards :- ISO RFID Cards Nos. 500 0.00

4.0 Bracket :- U Bracket For Glass Door Nos. 5 0.00

5.0 Bracket :- L Bracket For Locks Nos. 5 0.00

6.0 Lock :- Single Electromagnetic Locks - 600 lbs as per specifications Nos. 10 0.00

7.0 Egress :- No Touch Exit SensorExit No Touch Sensor-Stainless steel Nos. 5 0.00

8.0 Enrollment Unit :- Finger print Enrollment device, is a stable and excellent fingerprint reader. The device can capture fingerprint image and upload to the PC by USB interface. High-performance, maintenance-free optical fingerprint sensor.

Nos. 1 0.00

9.0 Software :- Web Base ACS & Time-attendance software Nos. 1 0.00

Electrical BOQ 17

10.0 Supply, installing, testing and commissioning of Emergency Break Glass with required

accessories as per technical specifications Nos. 10 0.00

11.0 Cables: Supply, installing, testing and commissioning of :All the cables Should be weatherproof, outdoor grade & as per BIS standard.

11.a 8 core 20 to 22 AWG, 6 or 8-conductor, stranded, shielded armoured cable with required

accessories Mtrs. 250 0.00

11.b 6 core, 2-conductor 20 to 22 AWG, stranded, shielded armoured cable with required

accessories Mtrs. 75 0.00

11.c 4 core, 2-conductor 20 to 22 AWG, stranded, shielded armoured cable with required

accessories Mtrs. 150 0.00

TOTAL CARRIED OVER TO SUMMARY -

Electrical BOQ 17

Page 17: BOB ELECTRICAL BOQ WEB DISPLAY · 2019-07-19 · BOB, 27th floor, Gift City, Ahemdabad 16.0 17.0 18.0 19.0 20.0 21.0 All connections shall be through, aluminium ferrules for aluminum

BOB, 27th floor, Gift City, Ahemdabad

J) SENSOR SYSTEM

1.0 Supplying of Digital PIR LightSpot HD Switching Sensors Ceiling Mount 360 degree. High Sensitivity Range 10 m Dia at height of 2.5 meter ( 7 m dia Micro Sensitivity 3 m macro) and . Current Capacity 10A. Digital Remote IR based Commissioning with hand held programmer for following programmable features: Absence mode, OFF delay time 10 Sec - 96 hrs, photocell and power up (status of luminaires when power is applied). It shall have provision to manually override luminary ON/OFF status using hand held remote control, similar to Honeywell LS3200R or equivalent

Nos 15 0.00

TOTAL CARRIED OVER TO SUMMARY -

K) TV SYSTEM

1.0 Supply , Installation , Testing and Commissioning of Full HD 55" LED Professional

Display Panel Contras Ratio -4000:1, H/W - Tempreture Sensor, Pivot Display, Clock

Battery (168 hrs Clock keeping) Built in speaker ( 10W 2ch) IP5x, Wifi S/W - Auto source

Switching & Recovery, LFD Home UI, Button lock, hot key option , Plug & Play initial

Setting. ( Equivalent to Samsung QB55N )

Nos. 6 0.00

2.0 Wiring for TV point with RG-6 TV coaxial cable in ExistingPVC conduit including supply

of all metarials complete as required.Mtrs 150 0.00

3.0 Supply & fixing the following sizes of PVC conduit in recessed or on surface of wall .

False ceiling including cutting the wall and making good the same as required.

a) 25 mm dia Mtrs 150 0.00

4.0 Supply & laying of RG-11 TV co-axial cable for cable TV system in 25 mm dia PVCconduit pipe in recess or on surface of wall including cutting the chases as making good Mtrs 75 0.00

Electrical BOQ 18

the damage etc as required. (For Vertical & Horizontal runs)

5.0 Supply & fixing of co-axial type TV socket in zinc chromate passivated M.S. Box &

Moduler plate including making connections etc. complete as required.Nos. 6 0.00

6.0 Supply & fixing the following type of splitter box / Tape Off box in recess in wall or ceilingor on surface etc as required.

a) 2 way splitter / Tape Off box Nos. 2 0.00

b) 4 way splitter / Tape Off box Nos. 1 0.00

TOTAL CARRIED OVER TO SUMMARY -

Electrical BOQ 18

Page 18: BOB ELECTRICAL BOQ WEB DISPLAY · 2019-07-19 · BOB, 27th floor, Gift City, Ahemdabad 16.0 17.0 18.0 19.0 20.0 21.0 All connections shall be through, aluminium ferrules for aluminum

BOB, 27th floor, Gift City, Ahemdabad

L) LIGHTING FIXTURES

Supply, storing, Installation, testing, & commissioning of All type of Recessed / Surface

mounted Lighting Fixtures (as approved by client/architect) including all fixing hardwares

complete as required (Light fittings shall be supplied by owner as free issue item )

1.0 Receiving, storing, unpacking, assembling, Installation, testing, & commissioning of LED

STRIP Light (as approved by client/architect) including all fixing hardwares complete as

required (Light fittings shall be supplied by owner as free issue item )

Mtr. 100 0.00

2.0 Supply, installation installation, testing & commissioning of 48/36" ceiling/wall fans

complete with all accessories such as blades, canopy etc. including wiring the down rod

with 3 x 1.5 sq mm FRLS PVC insulated multistranded copper conductor wires and

earthing the fans etc. complete as required.

Nos. 12 0.00

3.0 Supply installation, installation, testing & commissioning of 12/9" exhaust fans on existing

opening in wall including all fixing hardware, louvers, shutters etc. Connection with 3 x

1.5 Sqmm FRLS PVC insulated multistranded copper conductor wire from the socket

outlet to the fan earthing etc. complete as required.

Nos. 6 0.00

4.0 Supply & installation of self illuminated Exit / Fire Exit Signs boards (Glolite/Prolite make)hung from ceiling or on wall as per site conditions complete with all accessories etc. asrequired

a) Two Sided 11" x 4" Nos. 3 0.00

b) One Sided 11" x 4" Nos. 3 0.00

5.0 Supply, Installation, Testing and Commissioning of following LED Lighting Fixture

Electrical BOQ 19

a) 30W 2x2 - Supply of 30W, Recess mounted IP20 LED 2x2 Feet luminaire having greaterthan 3600 lm system output-120 lm/w system efficacy. Luminaire shall be made up ofCRCA powder coated housing. Driver shall be fixed inside the housing only, no separatedrier with wiring will be acceptable. Luminaire shall have Optical Grade High EfficiencyTranslucent Optical compartment for very high efficiency with minimum glare. Opticalcompartment shall have Unique HET diffuser for wider and uniform distribution. LM 80-08 compliant, ANSI rated LEDs from reputed makes such as Nichia, Japan / Cree,USA / Citizen Japan should be provided. Luminaire shall have CCT 5700K ±350K.Luminaire shall use multiple LEDs of less than 0.5W Class for better diffusion and heatmanagement. The LED shall be compliant with LM80-08 standard with Useful L70 life

(L70 B10 or L70 B50 not acceptable) of 50000 Hrs (Complete LM 80 test reportfor LED should be submitted). The LEDs used in luminaire should be McAdam Step 5standard Rated LED with CRI of Minimum 80. LEDs used must be tested as perEN62471 for Photobiological Safety of humans and Report of the same from LEDManufacturer shall be submitted. Driver shall be multi stage Constant Current ConstantVoltage with voltage range of 150-270V AC. Output voltage of driver should be compliedto Safety Extra Low Voltage norms not exceeding 60V DC only Driver Power factor shall

Nos. 250 0.00

b)

12W Downlighter - Supply of 12W, Recess mounted IP20 LED Circular Downlighterluminaire having greater than 1200 lm system output-100 lm/w system efficacy..Luminaire shall be made up of Die Cast powder coated housing with integral Fins. Drivershall be fixed with housing of the fixtures only, no separate driver with wiring will beacceptable. Luminaire shall have Optical Grade High Efficiency Translucent Opticalcompartment for very high efficiency with minimum glare. Optical compartment shallhave Unique HET diffuser for wider and uniform distribution. LM 80-08 compliant, ANSIrated LEDs from reputed makes such as Nichia, Japan / Cree, USA / CitizenJapan should be provided. Luminaire shall have CCT 5700K ±350K. Luminaire shalluse multiple LEDs of less than 0.5W Class for better diffusion and heat management.The LED shall be compliant with LM80-08 standard with Useful L70 life (L70 B10 orL70 B50 not acceptable) of 50000 Hrs (Complete LM 80 test report for LED shouldbe submitted). The LEDs used in luminaire should be McAdam Step 5 standard RatedLED with CRI of Minimum 80. LEDs used must be tested as per EN62471 forPhotobiological Safety of humans and Report of the same from LED Manufacturer shallbe submitted. Driver shall be multi stage Constant Current Constant Voltage with voltagerange of 150 270V AC Output voltage of driver should be complied to Safety Extra Low

Nos. 300 0.00

c) LED 4ft. 18 Watt ( Equivalent to. Wipro cat No D53206500K ) Nos. 10 0.00

d) Hanging Light 40 Watt ( Equivalent to Wipro cat No. LM 34-501-xxx-57-DD) Nos. 7 0.00

e) 5 watt / mt. 50/50 LED Strip Light With Driver (Equivalent to Wipro cat No. D45040

4000K )Mtr. 100 0.00

Electrical BOQ 19

Page 19: BOB ELECTRICAL BOQ WEB DISPLAY · 2019-07-19 · BOB, 27th floor, Gift City, Ahemdabad 16.0 17.0 18.0 19.0 20.0 21.0 All connections shall be through, aluminium ferrules for aluminum

BOB, 27th floor, Gift City, Ahemdabad

f) 9Watt Spot Light ( Equivalent to Wipro cat No D 120940) Nos. 70 0.00

g) 20W Wall Mounted Decorative Light Phillips 31425 Muziris Singale head Wall Light (

Equivalent to Phillips Bronze E27 Base )Nos. 30 0.00

TOTAL CARRIED OVER TO SUMMARY -

Electrical BOQ 20Electrical BOQ 20

Page 20: BOB ELECTRICAL BOQ WEB DISPLAY · 2019-07-19 · BOB, 27th floor, Gift City, Ahemdabad 16.0 17.0 18.0 19.0 20.0 21.0 All connections shall be through, aluminium ferrules for aluminum

BOB, 27th floor, Gift City, Ahemdabad

M) FIRE ALARM SYSTEMS

H

FIRE DETECTION SYSTEM (ANALOGUE ADDRESSABLE) Make: Honeywell/BOSCH/SIEMENS/UTC/Ravel Note:For Fire Alarm System (FAS) Standards : NFPA 72/IS 11360-1985/IS22189/IS-2175/EN54 Approvals: VdS/ UL/ LPCB or equivalentNote

All A.C Unit and Exit door shall be integrated with fire panel so that in case of fire signal, all shall be switched OFF.2 Layer For Ceiling and Above False Ceiling

1

SITC of Addressable Multi Sensor - Heat Cum Smoke detector with base with address setting. Dual LED’s for 360° visibility. Sleek low-profile housing design. Regular 100mm base. IP Rating : IP - 42. Approval: UL Listed

Nos 140 0.00

2SITC of Addressable Heat detector with base with address setting. Dual LED’s for 360° visibility. Sleek low-profile housing design. Regular 100mm base. IP Rating : IP - 42. Approval: UL Listed

Nos 1 0.00

Electrical BOQ 21Electrical BOQ 21

Page 21: BOB ELECTRICAL BOQ WEB DISPLAY · 2019-07-19 · BOB, 27th floor, Gift City, Ahemdabad 16.0 17.0 18.0 19.0 20.0 21.0 All connections shall be through, aluminium ferrules for aluminum

BOB, 27th floor, Gift City, Ahemdabad

3SITC of Addressable type Horn / Strobe wall mounted type rated at 90 dBA @ 1m for Audible annunciation and 15cd minimum flashing at 1 Hz for visual indication - Approval: UL Listed

Nos 8 0.00

4SITC of Addressable Manual Pull Stating - Single Action - with back box with Break Glass with Back Box for Manual Pull Station - Approval: UL Listed Nos 8 0.00

5 SITC of Fault isolator Module capable of monitoring shorted loop circuit Nos 20 0.00

6SITC of Addressable Control Relay Module for monitoring the field devices. Approval: UL Listed

Nos 10 0.00

7SITC of Addressable Monitor Module for monitoring the field devices. Approval: UL Listed

Nos 2 0.00

8Supply, installation, connecting, testing and commissioning of Response indicator.

Nos 57 0.00

Electrical BOQ 22Electrical BOQ 22

Page 22: BOB ELECTRICAL BOQ WEB DISPLAY · 2019-07-19 · BOB, 27th floor, Gift City, Ahemdabad 16.0 17.0 18.0 19.0 20.0 21.0 All connections shall be through, aluminium ferrules for aluminum

BOB, 27th floor, Gift City, Ahemdabad

9

SITC of Analogue Addressable Fire Alarm Control panel shall be Networkable with switch mode power supply, battery back up and charger .The panel shall have 4 loops as capacity with Builtin installed loop cards and with More than 250 devices per loop in any combination. The panel shall consisting with 160 character LCD display, Touch keys. Shall be networkable by RS 485 or TCP/IP , repeater/Mimic connectivity. USB - 2.0 for PC Interface. Degraded redundancy operating mode when the main CPU fails. UL Listed Along with Battery Backup up

Set 1 0.00

10Providing and fixing in position 1.2mm thick PVC outlet boxes for housing smoke detectors/heat detectors including providing 3 mm thick hylam sheet cover as required

Nos 12 0.00

a. 75mm x 75mm x 75mm Nos 12 0.00

11

Supply & laying of following grade with copper conductor armoured FIRE SURVIVAL cable with (EPR) Ethylene Propylene rubber insulation as per IEC-60502:2004 Part-1 (Armoured), Retain circuit integrity as per BS 6387 C.W.Z (armoured), BS- 8491:2008, BS 8434-2: 2009 (armoured), (Resistance to fire at 950º C for 3 hours), as per specifications in cable trays, clamped including anchor fastners to wall with suitable clamps, saddles fixing bolts,2 cable glands for each detector back box, complete in all respect as required as per specifications.(Red Colour)

a. 2 core x 1.5 sq. mm RM 1500 0.00

TOTAL CARRIED OVER TO SUMMARY -

N) PA SYSTEM FOR FIRE ALARM

1.0Supply, Installation, Testing & Commissioning of 2 Way Communication Fire Fighter'sTelephone Jack. Nos. 2

Electrical BOQ 23

2.0Supply, Installation, Testing & Commissioning of 2 Way Communication Fire Fighter'sHandset Nos. 2

3.0

SITC of followings with commnication cable and accessories as required for system.Voice Zone Controller as required for system. suitable Zone selector with micro phoneincluding keypad as required for system. Router as required for system. Systemcompressive of above as required

NOS. 1

4.0SITC of Pagging microphone Min 6 Zone for interface with controller includingcommunication cable and all accessories. NOS. 2

5.0

SITC of rack mounted dual Channel Power Amplifier capable of delivering 300 W RMSpower output or 480 W RMS burst output; complete with 100 V Line MatchingTransformer, built-in fan for temperature control, Distortion typically 0.03% @ 1 KHz,Hum and Noise 90 dB below rated output selection facility,provision for hookup with FireAlarm Panel, complete with connections and required circuitry

NOS. 1

6.0 Supply, Installation, Testing And Commissioning of Wireless microphone NOS. 4

7.0Supply, Installation, Testing And Commissioning of Ceiling loudspeaker, 6/3W,Frequency response of 110 Hz - 18 kHz. NOS. 50

8.0Supply, Installation, Testing And Commissioning of wall mount loudspeaker, 6/3W,Frequency response of 200Hz - 20KHz NOS. 10

9.0Supply, Installation, Testing and Commissioning of 2 Core X 1 Sq.mm flexible cable.

MTRS 850

10.0Supply, installation, testing and commissioning of 25mm pvc conduits for laying of abovecable. MTRS 850

11.0

Supply, installation, testing and commissioning of 18U (600 x 600) floor mount closedrack with front glass door, fan tray on top, perforated rear doors, keyboard tray with shelf.Casters & 2 nos vertical power strip with std. accessories. NOS 1

-

O) EARTHING

1.0 Supply and laying 1 x 16sqmm copper wire for UPS/Server Mtrs 200 0.00

2.0 Supplying and laying of 8 SWG G.I. Wire on surface / recess as required. Mtrs 400 0.00

3.0 25x3 Hot Dip Gi strip Supply & Laying. Mtrs 250 0.00

TOTAL CARRIED OVER TO SUMMARY

Electrical BOQ 23

Page 23: BOB ELECTRICAL BOQ WEB DISPLAY · 2019-07-19 · BOB, 27th floor, Gift City, Ahemdabad 16.0 17.0 18.0 19.0 20.0 21.0 All connections shall be through, aluminium ferrules for aluminum

BOB, 27th floor, Gift City, Ahemdabad

4.0 25x3 Cu Strip Supply & Fixing. Mtrs 50 0.00

-

P) FIRE SUPPRESSION SYSTEM

1.0Supply, Installation, testing & Commissioning of UL Listed 80 Ltr Seamless Cylinder and

Valve assembly.Nos. 1 0.00

2.0 Supply of Novec 1230 Fluid factory filled. Kg. 80 0.00

3.0Supply, Installation, testing & Commissioning of Nozzle Brass- 360 / 180 Degree.

Nos. 3 0.00

4.0Supply , Installation , Testing & Commisssiong of Conventional Smoke detecors.

Nos. 4 0.00

5.0 Supply , Installation , Testing & Commisssiong of Control Relay module. Nos. 1 0.00

6.0Providing, fixing, testing and commissioning of Manual Release & Abort Station.

Nos. 1 0.00

7.0 Providing, fixing, testing and commissioning of addressable monitor module. Nos. 2 0.00

8.0 Providing, fixing, testing and commissioning of Hooter. Nos. 2 0.00

9.0 Supply , Installation , Testing & Commisssiong of Control Release module. Nos. 1 0.00

-

TOTAL CARRIED OVER TO SUMMARY

TOTAL CARRIED OVER TO SUMMARY

Electrical BOQ 24

Q) VIDEO SYSTEM

1.0 Motorized screen (Product code AMS)120" Diagnal Motorised Screen set 1 0

2.0 Beyond Full HD resolutionWhite and colour brightness of 4,000 lumensLaser Light Source20000Hours Maintenance free use**Dual Screen seamless interactivityWireless Projection and Miracast® Finger Touch InteractiveUltra Short Throw 80” screen @ 47cm

set 1 0

3.0 Projector Mount Kit set 1 0

4.0 HDMI cable 15 mtr. Length set 12 0

5.0 1.5 sq mm x 2 core shilded flexibale cable with PVC conduite supply & Fixing. meter 100 0

6.0 Pop Up Box With 1 Nos HDMI , 1 Nos USB, 1 Nos plug point , 1 Nos DATA Point, 1 NosVoice ( Legrand Cat No :- 654003 & above items ) set 6 0

7.0 SITC of Subwoofer Cable - 1 sq mm x 2 core shilded flexibale in PVC Conduite.set 1 0

-

8 Rodent protection system

Supply, Instllation, testing and commissioning of roent protection system for server and switch rooms set 8 0

0TOTAL CARRIED OVER TO SUMMARY

TOTAL CARRIED OVER TO SUMMARY