BMS option for Daikin water chillers

download BMS option for Daikin water chillers

of 36

Transcript of BMS option for Daikin water chillers

  • 8/19/2019 BMS option for Daikin water chillers

    1/88

    4899

      erial

    module

    µ

    chiller

    ompact

    l

    i

    n

     

    p

    r

    i

    n

    t

     

    o

    u

    t

    a

    l

    a

    r

    m

     

    a

    l

    a

    r

    m

     

    2

    r

    x

    t

    x

    r

     

    s

     

    t

      tew y

      S

    Service Manual BMS option for Daikin water chillers 

    Gateway EKBMSMBAEKBMSBNA

    Address card EKAC10A/30A/60A/120A

    ESIE99-03 

  • 8/19/2019 BMS option for Daikin water chillers

    2/88

    ESIE99–03

    Table of Contents i

    3

    4

    5

    1

    Table of Contents

    1 Introduction

     

    1.1 About This Manual ........................................................................................................v

    1.2 Building Management System (BMS) .......................................................................... vi

     

    Part 1

    System Outline

     

    1 System Outline

     

    1.1 What Is in This Chapter?........................................................................................... 1-31.2 Communication Outline............................................................................................. 1-41.3 Product Range .......................................................................................................... 1-6

    1.4 Protocol and Data Transfer ....................................................................................... 1-71.5 Outline of the Gateway.............................................................................................. 1-8

    1.6 Outline of the Address Card in kit EKAC10A .......................................................... 1-101.7 Outline of the Address Cards in the EKAC30A/60A/120A kits................................ 1-11

  • 8/19/2019 BMS option for Daikin water chillers

    3/88

     

    ESIE99–03

     

    ii Table of Contents

      

    Part 2

    Installation

     

    1 Installing and Connecting the System

     

    1.1 What Is in This Chapter? ...........................................................................................2-31.2 Connecting an Address Card in the Serial Line.........................................................2-4

    1.3 Installing the Address Card EKAC10A.......................................................................2-51.4 Connecting the Address Card EKAC10A to the Controller ........................................2-61.5 Connecting the Address Card EKAC10A to the Transfo ...........................................2-7

    1.6 Installing the Address Card EKAC30A/60A/120A......................................................2-81.7 Connecting the Address Card EKAC30A/60A/120A to the Field Rail........................2-9

    1.8 Connecting the Gateway to the Configuration Computer ........................................2-101.9 Connecting the Gateway to the BMS.......................................................................2-11

     

    2 Configuration

     

    2.1 What Is in This Chapter? .........................................................................................2-132.2 Gateway Hardware Configuration............................................................................2-142.3 Gateway Software Configuration (MS–DOS program) ............................................2-17

    2.4 How to Read or Adjust BMS Parameter Settings with the Small Daikin Controller .2-192.5 Settings: Direct and User Parameters in the Small Daikin Controller......................2-20

    2.6 How to Read or Adjust BMS Parameter Settings with the Large Daikin Controller .2-222.7e

     

    User Settings Menu in the Large Daikin Controller ............................................2-23

  • 8/19/2019 BMS option for Daikin water chillers

    4/88

     

    ESIE99–03

     

    Table of Contents iii

     

    3

    4

    5

    1

     

    Part 3

    Functional Description

     

    1 General

     

    1.1 What Is in This Chapter?........................................................................................... 3-31.2 Generalities on the Protocols .................................................................................... 3-4

    1.3 References to ASHRAE Manual of the BACnet Protocol.......................................... 3-5

     

    2 Implemented Commands in the Gateway

     

    2.1 What Is in This Chapter?........................................................................................... 3-7

    2.2 Protocol ..................................................................................................................... 3-82.3 Implemented Commands.......................................................................................... 3-9

     

    3 Database

     

    3.1 What Is in This Chapter?......................................................................................... 3-113.2 Database creation................................................................................................... 3-12

    3.3 The Address Card EKAC10A Database ................................................................. 3-163.4 The Address Card EKAC30A Database ................................................................. 3-18

    3.5 The Address Card EKAC60A Database ................................................................. 3-21

    3.6 The Address Card EKAC120A Database ............................................................... 3-24

  • 8/19/2019 BMS option for Daikin water chillers

    5/88

     

    ESIE99–03

     

    iv Table of Contents

      

    Part 4

    Troubleshooting

     

    1 Troubleshooting

     

    1.1 What Is in This Chapter? ...........................................................................................4-31.2 Fault Indications.........................................................................................................4-4

    1.3 Troubleshooting .........................................................................................................4-6

     

    Appendix A

    Drawings

     Index

  • 8/19/2019 BMS option for Daikin water chillers

    6/88

     

    ESIE99–03 Introduction

     

    v

     

    3

    4

    5

     

    1 Introduction

     

    1.1 About This Manual

     

    Introduction

     

    The purpose of the Daikin Gateway and address cards is to connect the Daikin water chillers to a larger

    Building Management System (BMS).

    There are two different Gateways:

     

     

    EKBMSMBA to connect with a system using Modbus-Jbus protocol

     

     

    EKBMSBNA to connect with a system using BACnet protocol.

    There are 2 different types of address cards:

     

     

    The first card is only used in kit EKAC10A.

     

     

    The other card is used in the EKAC30A, EKAC60A and EKAC120A kits.

      Before starting up the system for the first time, ensure it has been properly installed.

    You will find the following tools at the back of the manual:

     

     

    A list of drawings. Refer to Appendix A Drawings.

     

     

    An index. Refer to Index.

     

    Usage of the

    manual

     

    The present manual gives you all the information you need to do the set up and the troubleshootingrelated to the BMS option for Daikin water chillers. It is intended for and should only be used by

    qualified engineers. It is not intended to replace technical know-how acquired through training andexperience.

     

    Using icons

     

    Icons are used to attract the attention of the reader to specific information. The meaning of each iconis described in the table below:

    IconType of

    informationDescription

     

    Note A ‘note’ provides information that is not indispensable, but maynevertheless be valuable to the reader, such as tips and tricks.

    Caution A ‘caution’ is used when there is danger that the reader, throughincorrect manipulation, may damage equipment, loose data, get anunexpected result or has to restart (part of) a procedure.

    Warning A ‘warning’ is used when there is danger of personal injury.

    Reference A ‘reference’ guides the reader to other places in this binder or in thismanual, where he/she will find additional information on a specifictopic.

  • 8/19/2019 BMS option for Daikin water chillers

    7/88

    Introduction ESIE99–03

     

    vi

      

    1.2 Building Management System (BMS)

     

    Introduction

     

    As buildings, plants or other sites become too large to control manually, the need for automaticdistance control becomes more important. Building Management Systems (BMS) were developed to

    have a centralized overview of complete sites.

    In general, control of lights, elevators, water supply, air conditioning, power consumption, etc. can be

    controlled by one control system.

     

    Communication

     

    To implement correct communication between the connected subsystems and the control system, the

    same communication protocol must be used.

     

    Daikin BMS option

     

    The Daikin BMS option makes it possible to connect the Daikin chillers to a larger control system. The

    tools necessary for this communication are the Gateway and the address cards.

    After installing address cards and Gateway, the BMS must be programmed to be able to control and

    monitor the chillers through the Gateway. To enable this configuration, individual parameters andrelative addresses of the chillers are described in this manual.

     

    Illustration

     

    The illustration below gives an example of a centralized building control by a BMS.

    Serialmodule 

    µ chiller compact 

      l  i  n e

      p  r  i  n  t  o

      u  t

     a  l a  r  m

       1

     a  l a  r  m

       2

      r  x   t  x   r e s e  t

    Gateway 

    BMS water supply

    lights

    elevators

    ...

    Daikin chiller

    Daikin chiller

    Daikin chiller

    Gateway

  • 8/19/2019 BMS option for Daikin water chillers

    8/88

    ESIE99–03

     

    Part 1 – System Outline 1–1

     

    3

    4

    5

    1

     

    Part 1

    System Outline

     

    Introduction

     

    The purpose of this part is to describe the communication network outline and the outline of theindividual parts.

     

    Overview

     

    This part contains the following chapter:

     

    chapter See ...

     

    1 – System Outline page 1-3

  • 8/19/2019 BMS option for Daikin water chillers

    9/88

    ESIE99–03

     

    1–2 Part 1 – System Outline

     

  • 8/19/2019 BMS option for Daikin water chillers

    10/88

     

    ESIE99–03 System Outline

     

    Part 1 – System Outline 1–3

     

    3

    1

    4

    5

    Part 1

     

    1 System Outline

     

    1.1 What Is in This Chapter?

     

    Introduction

     

    The purpose of this chapter is to display a communication network example, to display the Gateway

    and address card outline and to display the applicable Daikin chillers’ software versions.

     

    Overview

     

    This chapter covers the following topics:

     

    Topic See ...

     

    1.2 – Communication Outline page 1-4

    1.3 – Product Range page 1-6

    1.4 – Protocol and Data Transfer page 1-7

    1.5 – Outline of the Gateway page 1-8

    1.6 – Outline of the Address Card in kit EKAC10A page 1-10

    1.7 – Outline of the Address Cards in the EKAC30A/60A/120A kits page 1-11

  • 8/19/2019 BMS option for Daikin water chillers

    11/88

    System Outline ESIE99–03

     

    1–4 Part 1 – System Outline

      

    1.2 Communication Outline

     

    Introduction

     

    The communication between Gateway and address cards is possible in Carel protocol. Thecommunication between Gateway and BMS is possible in Modbus-Jbus or BACnet protocol.

    The chillers, address cards and the Gateway are Daikin parts. The other equipment must be fieldsupplied.

     

    Communication

    outline example

     

    The illustration below shows a communication outline example.

    Serial module 

    µ chiller compact 

      l  i  n e

      p  r  i  n  t o

      u  t

     a  l a  r  m

      1

     a  l a  r  m

      2

      r  x   t  x   r e s e  t

    Gateway 

    BMS

    Field supplied equipment

    Daikin supplied equipment Gateway

    Address card

    EKAC10A

    Address cardEKAC30A/60A

    Address cardEKAC120A

    Modbus-Jbus or

    BACnet protocol

    Carel protocol

    EUWY10HCW1 or

    EUWA12HDZW1 or ...

    EUWA35HDZW1 or

    EUW*100KXY1 orEUWAT50KAY1 or ...

    EUWA200KX orEUW(*)120KX or ...

    ...

    water supply

    lights

    elevators

    ConfigurationPC

  • 8/19/2019 BMS option for Daikin water chillers

    12/88

    ESIE99–03 System Outline

     

    Part 1 – System Outline 1–5

     

    3

    1

    4

    5

     

    Parts and

    description

     

    The table below gives a description of the different parts of the communication outline:

     

    Part Description

     

    BMS The Building Management System is the customer’s control unit. Refer to

    ‘Building Management System (BMS)’ on page vi.

    Gateway The Gateway is necessary as an interface between the chillers and the BMS.It translates the Carel protocol, which is used by the address cards to theModbus-Jbus or BACnet protocol, used by the BMS. Refer to ‘Outline of the

    Gateway’ on page 1-8.

    Address CardEKAC10A

    The EKAC10A is a small module that should be clicked on a DIN-rail of thechiller. It enables the chiller to communicate with the Gateway. Refer to ‘Out-

    line of the Address Card in kit EKAC10A’ on page 1-10.

    Address cardEKAC30A/60A

    The EKAC30A/60A is a small electronic board that must be attached to themain electronic board of the chiller. It enables the chiller to communicate withthe Gateway. Refer to ‘Outline of the Address Cards in the

    EKAC30A/60A/120A kits’ on page 1-11.Address CardEKAC120A

    The EKAC120A are two small electronic boards that must be attached to thetwo electronic boards of the chiller. It enables the chiller to communicate with

    the Gateway. Refer to ‘Outline of the Address Cards in theEKAC30A/60A/120A kits’ on page 1-11.

    Configuration PC The configuration PC is only necessary for configurating the Gateway. Oncethis is done, it must be removed. Refer to ‘Connecting the Gateway to the

    Configuration Computer’ on page 2-10.

  • 8/19/2019 BMS option for Daikin water chillers

    13/88

    System Outline ESIE99–03

     

    1–6 Part 1 – System Outline

      

    1.3 Product Range

    Introduction

     

    From this series onwards, all Daikin chillers can be connected to a supervisory BMS.

    To make it possible to connect 5–12HP chillers to a BMS system, a complete redesign of the switchboxand the controller had to be done. This means that not on all chillers 5–12HP BMS is applicable.

    The only changes for the larger chillers were made in the software. During the first year of production,the chillers were not equipped with BMS-applied software. To ensure that the chiller is usable for theBMS the software version must be checked first.

    To change the EPROM for the correct software, refer to "Procedure for the Changing of the PCB" inthe relevant Daikin chiller service manual.

     

    Address cards

     

    The table below displays the product range of the address cards:

     

    Gateway

     

    The table below displays the two different Gateways:

     

    Address card kitname Applicable chillers Software version

    Number of

    addressesper chiller

     

    EKAC10A EUWA5-12H(C/D)(Z) – 1

    EUWY5-10H(C/D)

    EKAC30A EUWA15-30(35)HD(Z) EPDAIECHOAV2.012 or later

    1

    EUWY15-30HD

    EKAC60A EUWA*40-60KA EPDAIECHLAV2.012 or later

    1

    EUWA*40-60KAX

    EUW*40-100KX EPDAIECHWAV2.012 or later

    EKAC120A EUWA*80-120KA EPDAIECHPA

    V2.012 or later

    2

    EUWA*80-120KAX

    EUWA*160-200KX EPDAIECHZA

    V2.012 or laterEUW*120-200KX

     

    Gateway name Supported protocol Communication is possiblewith maximum ... addresses.

    EKBMSMBA Modbus-Jbus 16

    EKBMSBNA BACnet 8

  • 8/19/2019 BMS option for Daikin water chillers

    14/88

     

    ESIE99–03 System Outline

     

    Part 1 – System Outline 1–7

     

    3

    1

    4

    5

     

    1.4 Protocol and Data Transfer

     

    Introduction

     

    The communication between the Daikin chillers and the supervisory BMS is achieved in two steps witha different communication protocol:

     

     

    in Carel protocol between the address cards and the Gateway

     

     

    in BACnet or Modbus-Jbus protocol between the Gateway and the BMS.

     

    BACnet and

    Modbus-Jbus

    differences

     

    There are two major differences between the BACnet system and the Modbus-Jbus system:

     

    Address of the

    Gateway

     

    The Gateway can be identified by the supervisor through the assignment of a univocal address within

    the Modbus-Jbus and the BACnet network. The address of the Gateway is programmable during theconfiguration.

    Refer to ‘Gateway Software Configuration (MS–DOS program)’ on page 2-17.

     

    Master-slave

     

    The management of the communication occurs in accordance with a master-slave structure in polling,where the Gateway is the master and the address cards are the slaves.

     

    The variable

    database of each

    address card

     

    For each address card it is possible to manage up to:

     

     

    128 analog variables

     

     

    128 integer variables

     

     

    200 digital variables.

    The chillers’ variable databases are used as the point of reference for the supplier of the supervisory

    BMS to assign a suitable meaning to the variables.

    The variables can be read and/or written by the supervisory BMS according to the connected chiller

    and/or the application program being used.

    The supervisory BMS can’t assign a value to a variable in real mode. The command would be

    ineffective.

    The variables requested from the supervisory BMS, but not available in the chiller with installedaddress card, are sent from the Gateway to the supervisory BMS with the value 0. The supervisoryBMS will have to manage them properly.

    Refer to ‘Database’ on page 3-11.

     

    BACnet system Modbus-Jbus system

     

    The Gateway uses a standard RS-232

    (Point-to-Point) to communicate with the super-visory BMS.

    The Gateway uses a standard RS-232

    (Point-to-Point) or RS-485 (multidrop) to com-municate with the supervisory BMS.

    The Carel standard permits up to eight address

    card connections to the Gateway.

    The Carel standard permits up to 16 address

    card connections to the Gateway.

  • 8/19/2019 BMS option for Daikin water chillers

    15/88

     

    System Outline ESIE99–03

     

    1–8 Part 1 – System Outline

      

    1.5 Outline of the Gateway

     

    Introduction

     

    The Gateway is the interface between the chillers’ address cards communicating in Carel protocol anda supervisory BMS communicating in Modbus-Jbus or BACnet protocol.

    The Gateway should be installed indoors, next to the BMS.

     

    Gateway kit

     

    The Gateway kit consists of the following parts:

     

     

    one Gateway

     

     

    one PC diskette with an MS-DOS-formatted program for the initial configuration of the Gateway

     

     

    one Cable terminal (resistor 120 Ω 1/4 W).

     

    Illustration

     

    The illustrations below display a general overview of the Gateway and its dimensions.

     

    Front view buttons The table below shows the different front view buttons:

      l  i  n e

      p  r  i  n  t  o  u  t

     a  l a  r  m

       1

     a  l a  r  m

       2

      r  x  t  x

      r e s e  t

    G a t e w a y 

    G        a       t         e      w        a          y        

    226130

    52

    166

    18

    7105.4

    2020

      l  i  n e

      p  r  i  n  t  o

      u  t

     a  l a  r  m

       1

     a  l a  r  m

       2

      r  x   t  x   r e s e  t

    Gateway 

    config.

    Carel Net. relay fuse

        c    o     d .modem

    rs422/485

    FRONT VIEW REAR VIEW

    DIMENSIONS

     

    Button Function

     

    print out No function

    reset It will reset the Gateway and restart the internal configurationand external inquiry process of the address cards.

  • 8/19/2019 BMS option for Daikin water chillers

    16/88

     

    ESIE99–03 System Outline

     

    Part 1 – System Outline 1–9

     

    3

    1

    4

    5

     

    Front view LED

    indicators

     

    The table below describes the different LED indicators:

    Refer to ‘Fault Indications’ on page 4-4.

    Connections

     

    The table below shows the different connectors:

     

    Technical data

     

     

    Intel 8032 microprocessor, 12 MHz

     

     

    240 VAC factory standard power supply (can be changed into 24 VAC or 120 VAC (1))

    Resident program, EPROM, 64 KB

    (1) Refer to ‘Changing to 24 or 120 VAC’ on page 2-15.

    LED Colour indicates that ...

    line yellow The power supply is on

    alarm 1 red An error in the configuration has been stored in

    the buffered RAM

    alarm 2 red A malfunction in the communication between

    the Gateway and the address card has occured,

    probably due to an inconsistency with the initial

    configuration

    rx green Communication is OK (flashing)

    tx green Communication is OK (flashing)

    Connector name Type Connect to ... Refer to ...

    modem 9-pin

    male

    BMS/supervisory system with

    RS-232 standard

    ‘Connecting the Gateway tothe BMS’ on page 2-11

    RS-422/485 9-pin

    female

    BMS/supervisory system with

    RS-485 standard

    ‘Connecting the Gateway to

    the BMS’ on page 2-11

    config. 9-pin

    male

    Configuration PC or terminal ‘Connecting the Gateway to

    the Configuration Computer’ on page 2-10

    Carel Net. 9-pin

    female

    Address cards with RS-485

    standard

    ‘Connecting an Address Card

    in the Serial Line’ on page 2-4

    fuse – fuse for 240 or 120 VAC

    fuse for 24 VAC

    page 2-16

  • 8/19/2019 BMS option for Daikin water chillers

    17/88

    System Outline ESIE99–03

    1–10 Part 1 – System Outline

    1.6 Outline of the Address Card in kit EKAC10A

    Introduction The address card EKAC10A will enable the chillers EUWA5-12H(C/D)(Z) and EUWY5-10H(C/D) to

    communicate with the Gateway.

    Address card kit The address card kit consists of:

    one address card (type EKAC10A)

    one connection cable to the chiller’s controller

    one connection cable + one fused connection cable (power supply).

    Illustration The illustration below shows the dimensions of the address card EKAC10A.

    Connections on the

    address card

    The address card, installed on the chiller’s DIN rail (1), has to be connected to:

    the chiller’s transfo for power supply (2) the Gateway or another address card in the serial line (3)

    the chiller’s controller (4).

    (1) Refer to ‘Installing the Address Card EKAC10A’ on page 2-5.

    (2) Refer to ‘Connecting the Address Card EKAC10A to the Transfo’ on page 2-7.

    (3) Refer to ‘Connecting an Address Card in the Serial Line’ on page 2-4.

    (4) Refer to ‘Connecting the Address Card EKAC10A to the Controller’ on page 2-6.

    Serial module 

    µ chiller compact 

    70 64

    88 44

  • 8/19/2019 BMS option for Daikin water chillers

    18/88

    ESIE99–03 System Outline

    Part 1 – System Outline 1–11

    3

    1

    4

    5

    1.7 Outline of the Address Cards in the EKAC30A/60A/120A kits

    Introduction The address card in the EKAC30A/60A/120A kits will enable the Daikin chillers to communicate with

    the Gateway.

    Address card kits

    and applicable

    chillers

    The table below gives the address card kits and the applicable chillers:

    Illustration The illustration below shows the dimensions of the address cards EKAC30A/60A/120A.

    Connections into

    the serial line

    To connect the address card into the serial line the following connections have to be made:

    from the address card to the chiller’s field rail (1)

    from the field rail to the Gateway or another address card in the serial line (2).

    (1) Refer to ‘Connecting the Address Card EKAC30A/60A/120A to the Field Rail’ on page 2-9.

    (2) Refer to ‘Connecting an Address Card in the Serial Line’ on page 2-4.

    The address card kit ... consist of ... Applicable chillers

    EKAC30A one address card with connector

    one connection wire to field rail.

    EUWA15-30HD(Z)

    EUWY15-30HD

    EKAC60A one address card with connector

    one connection wire to field rail.

    EUWA*40-60KA

    EUWA*40-60KAX

    EUW*40-100KX

    EKAC120A two address cards with connectors

    one connection wire to field rail

    one connection wire for connecting

    PCB A to PCB B.

    EUWA*80-120KA

    EUWA*80-120KAXEUWA*160-200KX

    EUW*120-200KX

    43

    705 5

         G     R     O     U     N     D

         R     X    +     /     T     X    +

         R     X   -     /     T     X   -

    M1

    JS2

  • 8/19/2019 BMS option for Daikin water chillers

    19/88

    System Outline ESIE99–03

    1–12 Part 1 – System Outline

  • 8/19/2019 BMS option for Daikin water chillers

    20/88

    ESIE99–03

    Part 2 – Installation 2–1

    4

    3

    4

    5

    2

    Part 2

    Installation

    Introduction The purpose of this part is to tell you how to install, connect and configurate the system. The chillers’ 

    set up may differ slightly depending on the model.

    Refer to the relevant Daikin chiller service manual if the screens described in this manual differ too

    much from the screens on the chiller’s controller.

    Overview This part contains the following chapters:

    Chapter See ...

    1 – Installing and Connecting the System page 2-3

    2 – Configuration page 2-13

  • 8/19/2019 BMS option for Daikin water chillers

    21/88

    ESIE99–03

    2–2 Part 2 – Installation

    2

  • 8/19/2019 BMS option for Daikin water chillers

    22/88

    ESIE99–03 Installing and Connecting the System

    Part 2 – Installation 2–3

    3

    2

    4

    5

    1Part 2

    1 Installing and Connecting the System

    1.1 What Is in This Chapter?

    Introduction The purpose of this chapter is to tell you how to set up the system. The troubleshooting chapter refers

    to this chapter to check correct installation and wiring.

    Precautions

    Observe the following precautions:

    Do not install the Gateway near power cables or radio-transmitting sources.

    Do not touch the electronic components with your fingers when manipulating internal jumpers.

    Thus, you will prevent stray currents, which could irreparably damage the components.

    Earth the Gateway casing to the stud identified by the appropriate yellow label.

    Connect all wires correctly because erroneous connection could damage the entire system.

    Ensure that the Gateway is switched off prior to inserting the cables into the connectors.

    Strictly follow the instructions on the use of the relevant program during the configuration phase.

    Keep the communication cables to link the chillers away from power cables to avoid interference.

    Before installing

    the Gateway

    Before installing the Gateway ensure you have installed the address cards correctly. Follow the

    instructions in the installation manuals of the address cards or use the pages listed in the table below.

    Overview This chapter covers the following topics:

    Topic See ...

    1.2 – Connecting an Address Card in the Serial Line page 2-4

    1.3 – Installing the Address Card EKAC10A page 2-5

    1.4 – Connecting the Address Card EKAC10A to the Controller page 2-6

    1.5 – Connecting the Address Card EKAC10A to the Transfo page 2-7

    1.6 – Installing the Address Card EKAC30A/60A/120A page 2-8

    1.7 – Connecting the Address Card EKAC30A/60A/120A to the Field Rail page 2-9

    1.8 – Connecting the Gateway to the Configuration Computer page 2-10

    1.9 – Connecting the Gateway to the BMS page 2-11

  • 8/19/2019 BMS option for Daikin water chillers

    23/88

    Installing and Connecting the System ESIE99–03

    2–4 Part 2 – Installation

    2

    1.2 Connecting an Address Card in the Serial Line

    Introduction An address card (EKAC10A) or the field rail of an address card (EKAC30A/60A/120A) can be

    connected to:

    the Gateway

    another address card.

    The serial line must be terminated with the resistor (120 Ω 1/4 W) between the TX/RX+ and

    TX/RX- terminals of the address card situated at the end of the network.

    Example The illustration below shows you a possible serial line connection to the Gateway.

    Connecting an

    address card in the

    serial line

    The table below shows where address cards must be connected in the serial line:

    If you have to connect two address cards or field rails, use AWG20 or AWG22 shielded couple type

    cables.

    Connections The table below shows you which connections must be made:

    Serial module 

    µ chiller compact 

    1

    config.

    Carel Net. relay fuse

    modem

    rs422/485

    45

    1 2 3

    GND TX+RX+ TX-RX-

    to serial line

         G     R     O     U     N     D

         R     X    +     /     T     X    +

         R     X   -     /     T     X   -

    197198199

    198 199197 field rail connection

    screw connector

    9-pole male

    EKAC10A

    EKAC30A

    Gateway

    If the chiller is…then connect the address card (EKAC10A) or the field

    rail of the address card (EKAC30A/60A/120A) to ...

    the first in line, the Gateway connector ’Carel Net.’.

    the sole connection, the Gateway connector ’Carel Net.’.

    not the sole connection and is not

    the first in line,another address card or another field rail.

    Gateway EKAC10A EKAC30A/60A/120A

    9-pole male screw connectors field rail

    1. GND 1. GND 197. GND

    4. TX+ 2. RX+ 198. RX+

    5. TX- 3. RX- 199. RX-

  • 8/19/2019 BMS option for Daikin water chillers

    24/88

    ESIE99–03 Installing and Connecting the System

    Part 2 – Installation 2–5

    3

    2

    4

    5

    11.3 Installing the Address Card EKAC10A

    Introduction Before the address card EKAC10A can be connected in the serial line, the EKAC10A module must be

    installed on the chiller’s DIN-rail.

    Installing the

    address card

    The illustration below shows you how to install the address card EKAC10A.

    Installation

    procedure

    Follow the steps in the table below to install the address card:

    Removing theaddress card Follow the steps in the table below should you wish to remove the address card:

    Se r i al  mo d ul e 

    µc hi l l e r c o mp ac t 

    Step Action

    1 Turn the power off.

    2 Place the address card on the upper side of the omega rail.

    3 Push the bottom side of the address card until you hear it click into place.

    The address card is now locked onto the omega rail.

    Step Action

    1 Turn the power off.

    2 Release the grey clip at the bottom of the address card using a screwdriver.

    3 Pull the bottom side of the address card upwards.

    The address card is now free from the rail.

  • 8/19/2019 BMS option for Daikin water chillers

    25/88

    Installing and Connecting the System ESIE99–03

    2–6 Part 2 – Installation

    2

    1.4 Connecting the Address Card EKAC10A to the Controller

    Introduction The address card EKAC10A must be connected to the chiller ’s controller.

    Installation

    procedure

    Follow the steps in the table below to connect the address card to the controller:

    Step Action Illustration

    1 Push the crimp terminal of the connection wire

    in the 7-pin header on the upper side of the

    address card.

    2 Disconnect the cable from the right upper

    socket on the rear panel of the controller.

    3 Insert the crimp terminal into the 7-pin socket

    as indicated in the illustration.

    4 Reconnect the cable into the right upper

    socket.

  • 8/19/2019 BMS option for Daikin water chillers

    26/88

    ESIE99–03 Installing and Connecting the System

    Part 2 – Installation 2–7

    3

    2

    4

    5

    11.5 Connecting the Address Card EKAC10A to the Transfo

    Introduction The address card EKAC10A must be connected to the chiller ’s transfo for power supply.

    Illustration The illustration below shows you how to connect the address card to the transfo.

    Installation

    procedure

    Follow the steps in the table below to connect the address card to the transfo:

    Serialmodule 

    µ chiller compact 

    12 11

    Gpower supply

    G0

    50 51

    50 51

    fuse

    Step Action

    1 Connect screw connection 11 G0 on the address card to terminal 50 on the main rail. Use

    the supplied unfused connection wire.

    2 Connect screw connection 12 G on the address card to terminal 51 on the main rail. Use

    the supplied fused connection wire.

  • 8/19/2019 BMS option for Daikin water chillers

    27/88

    Installing and Connecting the System ESIE99–03

    2–8 Part 2 – Installation

    2

    1.6 Installing the Address Card EKAC30A/60A/120A

    Introduction Before the address card can be connected in the serial line, first it must be installed on the PCB(s).

    Installing the

    address card

    The illustration below shows you how to install the address card EKAC30A/60A/120A.

    Installation

    procedure for

    EKAC30A/60A

    Follow the steps in the table below to install the address card:

    Installation

    procedure for

    EKAC120A

    Units with two circuits have two PCBs. You have to install an address card on each PCB.

    Follow the steps in the table below to install the address card:

    Connections

    between PCB A and

    PCB B (EKAC120A)

    PCB A and PCB B of the chillers with 2 circuits must be connected as listed below:

    Step Action

    1 Turn the power off before installing the address card.

    2 Handle the address card by its edges as indicated in the illustration above.

    3 Carefully place the address card with the socket into the 7-pin PCB header.

    Step Action

    1 Turn the power off before installing the address card.

    2 Handle the address card by its edges as indicated in the illustration above.

    3 Carefully place the address card with the socket into the 7-pin PCB header (PCB A).

    4 Repeat steps 2 and 3 to install the address card on PCB B.

    5 Connect the address card of PCB A to the address card of PCB B as listed below. Always

    use the same screw connectors.

    PCB A wire colour PCB B

    GROUND red GROUND

    RX+/TX+ white RX+/TX+

    RX-/TX- brown RX-/TX-

  • 8/19/2019 BMS option for Daikin water chillers

    28/88

    ESIE99–03 Installing and Connecting the System

    Part 2 – Installation 2–9

    3

    2

    4

    5

    11.7 Connecting the Address Card EKAC30A/60A/120A to the Field Rail

    Introduction The address card EKAC30A/60A/120A has to be connected to the field rail and this field rail has to be

    connected in the serial line.

    EKAC30A/60A to

    the field rail

    The figure below shows you how to connect the address card EKAC30A/60A to the field rail.

    EKAC120A of

    PCB B to the field

    rail

    The figure below shows you how to connect the address card EKAC120A of PCB B to the field rail.

    Connections of the

    EKAC30A/60A/120A

    Connect as listed below:

         G     R     O     U     N     D

         R     X    +     /     T     X    +

         R     X   -     /     T     X   -

    197198199

    198 199197 field rail terminal

         G     R     O     U     N     D

         R     X    +     /     T     X    +

         R     X   -     /     T     X   -

    PCB BPCB A

    198 199197

    197198199

    field rail terminal

    Connection on the screw

    connectorwire colour Connection on the field rail

    GROUND grey 197

    RX+/TX+ white 198

    RX-/TX- brown 199

  • 8/19/2019 BMS option for Daikin water chillers

    29/88

    Installing and Connecting the System ESIE99–03

    2–10 Part 2 – Installation

    2

    1.8 Connecting the Gateway to the Configuration Computer

    Introduction To configurate the Gateway, you must first make a connection between the Gateway and the

    configuration computer. Disconnect the link to the PC after configuration.

    Illustration The illustration below shows you how to connect the Gateway to the configuration computer.

    The wires 2 and 3 are crossed.

    Different cables The configuration computer connection to the Gateway is made via the 9-pin male connector at the

    back of the Gateway labelled ‘config.’. Two different cables can achieve connection:

    a cable with a 9-pin female connector at both ends

    a cable with one 9-pin female connector (to the Gateway) and one 25-pin female connector (to the

    computer).

    A program on a disk delivered with the kit can start the initial configuration once the cable connects

    the Gateway to the computer.

    Refer to ‘Gateway Software Configuration (MS–DOS program)’ on page 2-17.

    Cable with one

    25-pin female

    connector

    Make the connections as listed below:

    Cable with two

    9-pin female

    connectors

    Make the connections as listed below:

    2

    config.

    Carel Net . rel ay fuse

    modem

    rs422/485

    3 53

    25

    2375-p n

    female

    9-pin

    female

    GatewayConfiguration PC

    Computer Gateway (connector labelled 'config.')

    25-pin female cable end 9-pin female cable end

    2. TX 2. RX

    3. RX 3. TX

    7. GND 5. GND

    Computer Gateway (connector labelled 'config.')

    9-pin female cable end 9-pin female cable end

    3. TX 2. RX

    2. RX 3. TX

    5. GND 5. GND

  • 8/19/2019 BMS option for Daikin water chillers

    30/88

    ESIE99–03 Installing and Connecting the System

    Part 2 – Installation 2–11

    3

    2

    4

    5

    11.9 Connecting the Gateway to the BMS

    Introduction There are two possibilities for connecting the BMS to the Gateway:

    using the RS-232 standard (for BMS using BACnet or Modbus-Jbus protocol)

    using the RS-485 standard (only for BMS using Modbus-Jbus protocol).

    Illustration RS-232 The illustration below shows you how to connect with RS-232.

    The wires 2 and 3 are crossed.

    RS-232 connection

    (Modbus-Jbus and

    BACnet)

    The RS-232 connection to the supervisory BMS in Modbus-Jbus and BACnet is standard. The

    Gateway using the BACnet protocol has no other options to make a connection with the BMS.

    Make the RS-232 connection at the Gateway side to the 9-pin male connector labelled ‘modem’.

    Connections depend on which cable you use.

    Refer to the specifications of the supervisory BMS for other possible connection types. However, theGateway only manages the TX and RX signals.

    A 25-pin female

    connector

    Make the connections as listed below:

    Two 9-pin female

    connectors

    Make the connections as listed below:

    BMS

    2

    config.

    Carel Net . relay f use

    modem

    rs422/485

    3 5

    237

    325

    25-pin

    female

    9-pin

    female

    Gateway

    Supervisory system Gateway (connector labelled 'modem')

    25-pin female cable end 9-pin female cable end

    2. TX 2. RX

    3. RX 3. TX

    7. GND 5. GND

    Supervisory system Gateway (connector labelled 'modem')

    9-pin female cable end 9-pin female cable end

    2. RX 3. TX

    3. TX 2. RX

    5. GND 5. GND

  • 8/19/2019 BMS option for Daikin water chillers

    31/88

    Installing and Connecting the System ESIE99–03

    2–12 Part 2 – Installation

    2

    Illustration RS-485 The illustration below shows you how to connect with RS-485.

    RS-485 connection

    (only for

    Modbus-Jbus)

    For connection between Gateway and BMS using the Modbus-Jbus protocol the possible connections

    are listed below:

    The RS-485 connection diagram can only be used by Modbus-Jbus.

    BMS

    1

    config.

    Carel Net . relay f use

    modem

    rs422/485

    4 5

    Gateway

    9-pin

    male

    Supervisory BMS

    Gateway (connector labelled

    ’RS-422/RS-485’)

    9-pin male cable end

    The pinning from the supervisory BMS side is

    omitted because it changes depending on the

    particular supervisory BMS being utilised.

    1. GND

    4. TX+/RX+

    5. TX-/RX-

  • 8/19/2019 BMS option for Daikin water chillers

    32/88

    ESIE99–03 Configuration

    Part 2 – Installation 2–13

    3

    2

    4

    5

    12 Configuration

    2.1 What Is in This Chapter?

    Introduction The purpose of this chapter is to tell you how to configure the Gateway and how to address the chillers

    with the controller.

    Overview This chapter covers the following topics:

    Topic See ...

    2.2 – Gateway Hardware Configuration page 2-14

    2.3 – Gateway Software Configuration (MS–DOS program) page 2-17

    2.4 – How to Read or Adjust BMS Parameter Settings with the Small Daikin Control-

    ler

    page 2-19

    2.5 – Settings: Direct and User Parameters in the Small Daikin Controller page 2-20

    2.6 – How to Read or Adjust BMS Parameter Settings with the Large Daikin Con-troller

    page 2-22

    2.7 – e User Settings Menu in the Large Daikin Controller page 2-23

  • 8/19/2019 BMS option for Daikin water chillers

    33/88

    Configuration ESIE99–03

    2–14 Part 2 – Installation

    2

    2.2 Gateway Hardware Configuration

    Introduction Configuration of the hardware must be performed to enable the Gateway:

    to determine which connections towards the BMS and to the address cards there are used

    to use the correct power supply.

    Enabling the used

    connections

    To enable the connections that you want the Gateway to use, you have to set the jumpers A, B, C and

    D on the Gateway PCB according to the table below:

    Other jumper positions will lead to error codes and communication malfunction.

    Locating the

    jumpers

    The illustration below shows the Gateway PCB with the 4 jumpers.

    To enable ...place

    jumper

    in posi-

    tion

    then ... protocol

    can be usedRemark 

    RS-232 serial port

    (‘modem’) towards

    the BMS

    A 1–2 Modbus-Jbus orBACnet

    This way the ‘RS-422/485’ modes and respective port are

    disabled.

    RS-422/485 serialport towards the

    BMS

    A 2–3 Modbus-Jbus orBACnet This way the RS-232 modesand the respective ‘modem’ portare disabled.

    output communica-

    tion RS-485 at the

    ‘RS-422/485’ port

    from the Gateway to

    the BMS

    B 1–2 Modbus-Jbus You can only enable output

    communication RS-485 when

     jumper A is in position 2-3.

    communication from

    the Gateway to the

    chillers’ network inRS-485 mode

    C 1–2 Modbus-Jbus orBACnet

    This function uses the output of

    the ‘Carel. net’ port.

    123

    AB

    123

    C

    D

    123

    NO NC

    12C BUS OPTION

     jumper A jumper B

     jumper C

     jumper D

  • 8/19/2019 BMS option for Daikin water chillers

    34/88

    ESIE99–03 Configuration

    Part 2 – Installation 2–15

    3

    2

    4

    5

    1Possible powersupply The Gateway can run off one of the following voltages: 24 VAC

    120 VAC

    240 VAC.

    The Gateway itself uses 240 VAC 50/60 Hz.

    Changing the

    power supply

    The illustration below shows the power supply on the PCB of the Gateway.

    Changing to 24 or

    120 VAC

    Follow the instruction given below to change the 240 VAC to 24 or 120 VAC:

    240V~

    fuse

    transformer

    power

    supply

    unit24V~

    1  2   0  V ~

    Step Action

    1 Disconnect the power cable from the mains.

    2 Remove the Gateway cover.

    3 Disconnect the cable end coming from the power supply and located at the position

    marked with ’240 V~’.

    4 Remove the cover from the position marked with:

    ’24 V~’ and place it over the free connection ( ’240 V~’) when you want to change to

    24 VAC power supply.

    ’120 V~’ and place it over the free connection ( ’240 V~’) when you want to change to120 VAC power supply.

    5 Connect the cable end, which you’ve disconnected in step 3, with the connection marked

    with:

     ’24 V~’ when you want to change to 24 VAC power supply

     ’120 V~’ when you want to change to 120 VAC power supply.

  • 8/19/2019 BMS option for Daikin water chillers

    35/88

    Configuration ESIE99–03

    2–16 Part 2 – Installation

    2

    6 240 VAC and 120 VAC use the same fuse (on the Gateway PCB):

    type T time-delay

    nominal current 250 mA

    nominal voltage 250 V

    sizes 5 x 20.

    When you change the power supply to 24 VAC then replace the fuse with a fuse with the

    following specifications:

    type T time-delay

    nominal current 315 mA

    nominal voltage 250 V

    sizes 5 x 20.

    7 Tighten the nuts of the cover and ensure the chassis is grounded again.

    Step Action

  • 8/19/2019 BMS option for Daikin water chillers

    36/88

    ESIE99–03 Configuration

    Part 2 – Installation 2–17

    3

    2

    4

    5

    12.3 Gateway Software Configuration (MS–DOS program)

    Introduction The Gateway must be configured before it can be used to transfer variables. Therefore a PC has to

    be connected to the Gateway (1). The PC (field supplied) must have the following system

    requirements: 3.0 or higher DOS operating system

    RS–232 serial port.

    (1) Refer to ‘Connecting the Gateway to the Configuration Computer’ on page 2-10.

    Installation

    procedure

    To configure the Gateway from the PC follow the steps in the table below:

    Parameter writing To write the parameters:

    digitize for BACnet: a:\wrbaccnf parameter list

    digitize for Modbus-Jbus: a:\writemb0 parameter list

    Parameter list means the sequence of parameter selection with the following syntax:

    parameter list =

    Parameter reading To read the parameter selection:

    digitize for BACnet: a:\rdbaccnf

    digitize for Modbus-Jbus: a:\readmb0

    The PC screen displays the present Gateway configuration in which the parameters depend on the

    software version.

    Step Action

    1 Insert the disk.

    2 Run the program writemb0 (for Modbus-Jbus) or wrbaccnf (for BACnet).

    3 Configure the parameters (see parameter writing).

    4 When the configuration is successful the following message appears ***GATEWAY PRO-GRAMMED*** on the display.

    5 Restart the Gateway by pressing the Gateway reset button.

      l  i  n e

      p  r  i  n  t  o

      u  t

     a  l a  r  m

       1

     a  l a  r  m

       2

      r  x   t  x   r e s e  t

    Gateway 

  • 8/19/2019 BMS option for Daikin water chillers

    37/88

    Configuration ESIE99–03

    2–18 Part 2 – Installation

    2

    Parameter

    selections

    The table below shows the possible parameter selections:

    If you only digitize wrbaccnf (for BACnet) or writemb0 (for Modbus-Jbus) without parameters or if

    certain parameters are not defined, the DOS program will display the correct syntax to be used.Parameter values must be separated from the next by means of a blank space.

    These parameters are chosen in consultation with the supervisory BMS supplier.

    Error messages

    Refer to ‘Troubleshooting’ on page 4-1 should one of the following error messages appear on-screen:

    ***ERROR READING GATEWAY CONFIGURATION***

    ***ERROR SENDING GATEWAY CONFIGURATION***

    Example

    The example below is a possible configuration command for the site on page 3-14:

    a:\writemb0/COM1 1 4 19200 9600 1 NONE

    parameter Description Possible selection

    com Communication serial port utilized by the configura-

    tion computer.

     /COM1- /COM2

    net_address Address with which the BACnet or the Modbus-Jbus

    sees the Gateway.

    1-16

    n_of_slaves Max. number of slaves (address cards) connected

    1-8 (for BACnet) -1-16 (for Modbus-Jbus) to the

    Gateway. The first slave is always address 1, thesuccessive ones are numbered incrementally.

    1-8 (for BACnet) - 1-16

    (for Modbus-Jbus)

    carel _baud Baud rate of the address card/Gateway communica-

    tion.

    19200

    gateway_baud Baud rate of the supervisory BMS/Gateway commu-

    nication.

    600 - 1200 - 2400 -

    4800 - 9600

    stop Bit stop in the supervisory BMS/Gateway communi-

    cation.

    1- 2

    parity Parity in the supervisory BMS/Gateway communica-

    tion.

    NONE - ODD - EVEN

  • 8/19/2019 BMS option for Daikin water chillers

    38/88

    ESIE99–03 Configuration

    Part 2 – Installation 2–19

    3

    2

    4

    5

    12.4 How to Read or Adjust BMS Parameter Settings with the Small Daikin Controller

    Addressing

    procedure

    To address the chillers using the address card EKAC10A, proceed as follows:

    After 5 seconds the display starts flashing when no buttons are pressed.

    You can exit at every step by leaving the buttons untouched for 1 minute. The modifications will

    not be saved.

    Refer to ‘Settings: Direct and User Parameters in the Small Daikin Controller’ on page 2-20 for an

    overview of the parameters.

    START

    Enter the user-password 22 using theu andd buttons.

    Presss.

    Select the HA parameter using theu andd buttons.

    Presss to display the value.

    Do you want to

    adjust the value? 

    Adjust the value using theu andd buttons.

    Presss to display the parameter.

    Pressp to save and exit.

    STOP

    Pressp for five seconds.

    YES

    NO

  • 8/19/2019 BMS option for Daikin water chillers

    39/88

    Configuration ESIE99–03

    2–20 Part 2 – Installation

    2

    2.5 Settings: Direct and User Parameters in the Small Daikin Controller

    Introduction The grey-filled boxes relate to the chillers’ addressing procedure with address card EKAC10A.

    Refer to ‘How to Read or Adjust BMS Parameter Settings with the Small Daikin Controller’ onpage 2-19.

    Direct and user

    parameters

    The digital controller provides direct and user parameters:

    direct parameters are used for the every day usage of the unit (for example to set the cooling and

    heating temperature point and to read operational information)

    user parameters provide advanced features (for example remote control).

    Each parameter is defined by a code and a value.

    How to access the

    parameters

    To access the parameters, proceed as follows:

    Parameter overview In the table below you will find the description, the type, the code and the values of all of the

    parameters:

    Hold the ... button down

    for five secondsto have access to … A password is …

    s the direct parameters. not required.

    p all parameters (direct and user). required. Use 22.

    Description Type CodeDefault

    Value Limit valuesStep

    value

    measurement unit (˚C or ˚F) user   d 0 ˚C 0 or 1 1

    cooling temperature set point direct   r1 12.0 ˚C 7.0 ˚C to 25.0 ˚C 0.1 ˚C

    cooling temperature difference direct   r2 3.0 ˚C 0.1 ˚C to 11.0 ˚C 0.1 ˚C

    heating temperature set point direct   r3 40.0 ˚C 25.0 ˚C to 55.0 ˚C 0.1 ˚C

    heating temperature difference direct   r4 3.0 ˚C 0.1 ˚C to 11.0 ˚C 0.1 ˚C

    outlet water temperature direct   r6 read only — 0.1 ˚C

    coil temperature direct   r8 read only — 0.1 ˚C

    not used —   c4 10 — —

    not used —   c5 00 — —

    not used —   c6 0 — —

    time delay between the pump

    start-up and the compressor

    start-up

    user   c7 20 s 0 to 150 s 1 s

    time delay between the unit

    shutdown and the pump shut-

    down

    user   c8 20 min 0 to 150 min 1 min

    total running hours of the com-pressor

    direct   c9 read only — 1 hour

  • 8/19/2019 BMS option for Daikin water chillers

    40/88

    ESIE99–03 Configuration

    Part 2 – Installation 2–21

    3

    2

    4

    5

    1

    (1) Never lock the keyboard. Unlocking is not possible with the same password. Refer to "Unlocking

    the Keyboard" in the service manual for small Daikin chillers ESIE98–06.

    The following advanced functions are unavailable when you lock the keyboard:

    Modifying direct and user parameters (parameters can be displayed but not modified).

    Selecting cooling or heating mode.

    Forcing a defrost cycle.

    Resetting the timers.

    Refer to the service manual for small Daikin chillers ESIE98–06 for more information how to changethe parameters.

    not used —   ca — — —

    timer threshold for mainte-

    nance warning

    user   cb 0 hours

    (disabled)

    0 to 10 000 hours 100 hours

    total running hours of the pump direct   cv read only — 1 hour

    activation period of the buzzer user   p4 1 min 0 min: buzzer

    disabled

    1-14 min:

    buzzer

    activation

    period

    15 min: buzzer

    activated until

    m button ispressed

    1 min

    remote cool/heat user   h6 0 0 or 1 1

    remote start/stop user   h7 0 0 or 1 1

    controller keyboard lock (1) user   h9 1 0 or 2: locked and

    1 or 3: unlocked

    1

    unit’s serial address user   ha 1 1 to 16 1

    not used —   hb — — —

    Description Type CodeDefault

    ValueLimit values

    Step

    value

  • 8/19/2019 BMS option for Daikin water chillers

    41/88

    Configuration ESIE99–03

    2–22 Part 2 – Installation

    2

    2.6 How to Read or Adjust BMS Parameter Settings with the Large Daikin Controller

    Addressing

    procedure

    To address the chillers using the address card EKAC30A/60A/120A, proceed as follows:

    (1) The display shows a screen of the last menu used.

    START (1)

    Press the USER SETTINGS menu-buttone.

    Enter the password using theh button.

    Press thej button.

    Select screen 2 (see page 2-23) using theh button.

    Change "BMS CARD INSTALLED" to "Y"using theh button.

    Select the parameter BMS CARD INSTALLED using thej button.

    want to save the

    Pressj until the cursor stands in the left upper corner.

    Select screen 5 (see page 2-24) and 6 (see page 2-25) using theh button.

    YES

    NO

    Adjust the parameters in screen 5 (see page 2-24) and 6 (see page 2-25).

    Do you 

    modifications? 

    STOP

    Pressj until the cursor stands in the left upper corner.

    Press any menu-button butj to leave the user settings menu.

  • 8/19/2019 BMS option for Daikin water chillers

    42/88

    ESIE99–03 Configuration

    Part 2 – Installation 2–23

    3

    2

    4

    5

    12.7   e User Settings Menu in the Large Daikin Controller

    Introduction The grey-filled boxes relate to the chillers’ addressing procedure with address cardEKAC30A/60A/120A (1).

    You need the password to enter this menu. The units leave the factory with password 1914. You can

    also create your own password (2).

    (1) Refer to ‘How to Read or Adjust BMS Parameter Settings with the Large Daikin Controller’ on

    page 2-22.

    (2) Refer to the relevant Daikin chiller service manual.

    Menu description This menu allows a full customizing of the units and displays the following nine screens:

    Screen 1 You need to enter the correct password before you can consult the screens in this menu:

    Screen 2 This screen allows you to activate the remote control by BMS:

    Screen No. Display Description

    1 ENTER PASSWORD To enter the password.

    2 REMOTE CONTROL To activate remote control or BMS control.

    3 CONTROL SETTINGS To adjust and activate manual control mode.

    4 THERM. SETTINGS To adjust the thermostat settings.

    5 BMS SETTINGS To adjust the BMS settings

    6 BMS BOARD

    SETTINGS

    To adjust the BMS board settings

    7 LEAD-LAG SETTINGS To adjust the lead-lag settings.

    8PUMP CONTROL

    To control the pump.

    9 SETPOINT PASSWORD To assign password protection to the set points menu.

    Line No. Display Description

    1 ENTER PASSWORD screen title

    2 PASSWORD: 0000 1914

    Line No. Display DescriptionPossible set-

    tings

    1 REMOTE CONTROL screen title

    2 REMOTE ON/OFF to activate remote start/stop Y/N

    3 BMS CARD INSTALLED used to define if there is a BMSaddress card

    Y N

  • 8/19/2019 BMS option for Daikin water chillers

    43/88

    Configuration ESIE99–03

    2–24 Part 2 – Installation

    2

    Screen 3 This screen allows you to modify the control settings:

    Screen 4 This screen allows you to modify the thermostat parameters:

    Screen 5 This screen allows you to activate the PC control mode and to modify the BMS settings:

    This screen will only be displayed if you mentioned that the optional BMS card is installed. You can do

    this in screen 2.

    Line No. Display Description Possible settings

    1 CONTROL SETTINGS screen title

    2 MODE to select the control mode INLET WATER CONTROL

    OUTLET WATER CONTROL

    MANUAL CONTROL

    3 CIR1 /C1R2 capacity step circuit 1 / 2 (manual

    mode)

    0/25/40/70/100 %

    4 F1/F2 OFF/LOW/MED/HIGH

    Line No. Display DescriptionLower

    limit

    Upper

    limitStep Default

    1 THERM. SETTINGS screen title

    2 STPLENGTH ( C) step length (a) 0.4 2.0 0.1 1.5

    3 STEPDIFFERENCE ( C) step difference (b) 0.2 0.8 0.1 0.5

    4 LOADUP (30 s) load up time (s) 15 300 1 180

    5 LOADDOWN load down time (s) 15 300 1 20

    Line No. Display DescriptionPossible

    settings

    1 BMS SETTINGS screen title

    2 BMS CONTROL ALLOWED to allow BMS control Y N

    3 ADDRESS PCB A

    ADDRESS PCB B

    used to address circuits of the unit towards

    the Gateway

    00-31

    4 PROTOCOL indicates the communication protocol CAREL

  • 8/19/2019 BMS option for Daikin water chillers

    44/88

    ESIE99–03 Configuration

    Part 2 – Installation 2–25

    3

    2

    4

    5

    1Screen 6 This screen allows you to adjust the BMS board settings:

    This screen will only be displayed if you mentioned that the optional BMS card is installed. You can dothis in screen 2.

    Screen 7 This screen allows you to adjust the lead-lag settings:

    Screen 8 This screen allows you to force the pump via the chiller ’s controller and to adjust the pump lead andlag time:

    Line No. Display Description Possible settings

    1 BMS BOARD

    SETTINGS

    screen title

    2 SERIAL BOARD to select the communication protocol

    between the BMS and the Gateway

    RS485 (default)

    RS422

    3 BAUD RATE to select the baud rate for

    communication between the BMS card

    and the Gateway

    19200 BPS (default)

    9600

    4800

    2400

    1200

    Line No. Display DescriptionPossible

    settings

    1 LEAD-LAG SETTING screen title

    2 LEAD-LAG MODE to select whether circuit 1 or circuit 2 starts

    up first

    AUTO

    C1>C2

    C2>C1

    3 LEAD-LAG HOURS time after which the other circuit should start

    at next start-up

    100-1000 H

    4 EQUAL START-UP to select if both circuits should go up in

    capacity alternatingly

    Y/N

    Line No. Display DescriptionPossible

    settings

    1 PUMP CONTROL screen title

    2 PUMP LEAD TIME time to run the water pump before starting

    up the chiller

    0-180 S

    3 PUMP LAG TIME time to keep the pump on, after stopping the

    chiller

    0-180 S

  • 8/19/2019 BMS option for Daikin water chillers

    45/88

    Configuration ESIE99–03

    2–26 Part 2 – Installation

    2

    Screen 9 This screen allows you to assign password protection to the set point menu:

    Line No. Display DescriptionPossible

    settings

    1 SETPOINT PASSWORD screen title

    2 PASSWORD NEEDED TO

    CHANGE SETPOINTS

    assign password protection to set point

    menu

    Y/N

  • 8/19/2019 BMS option for Daikin water chillers

    46/88

    ESIE99–03

    Part 3 – Functional Description 3–1

    4

    3

    4

    5

    3

    Part 3

    Functional Description

    Introduction The purpose of this part is to give some general and some more specific information about the used

    protocols, the implemented commands and the databases.

    Overview This part contains the following chapters:

    Chapter See ...

    1 – General page 3-3

    2 – Implemented Commands in the Gateway page 3-7

    3 – Database page 3-11

  • 8/19/2019 BMS option for Daikin water chillers

    47/88

    ESIE99–03

    3–2 Part 3 – Functional Description

    3

  • 8/19/2019 BMS option for Daikin water chillers

    48/88

    ESIE99–03 General

    Part 3 – Functional Description 3–3

    33

    4

    5

    1Part 3

    1 General

    1.1 What Is in This Chapter?

    Introduction The purpose of this chapter is to give some general information and some references on the used

    protocols.

    Overview This chapter covers the following topics:

    Topic See ...

    1.2 – Generalities on the Protocols page 3-4

    1.3 – References to ASHRAE Manual of the BACnet Protocol page 3-5

  • 8/19/2019 BMS option for Daikin water chillers

    49/88

    General ESIE99–03

    3–4 Part 3 – Functional Description

    3

    1.2 Generalities on the Protocols

    BACnet

    conformities

    The reference to "BACnet protocol" has been defined in official documentation:

    ANSI ASHRAE – Standard 135-1995

    Approved by the National Standards Institute – December 19, 1995

    The configuration is of the point-to-point type in RS-232.

    Modbus-Jbus

    conformities

    The Modicon Modbus protocol implemented in the Gateway complies with the content of the

    document:

    Modicon Modbus Protocol

    Reference Guide

    March 1992, PI-MBUS-300 Rev. D

    The implemented Modbus-Jbus protocol is of the RTU type based on times. The configuration is of the

    multi-drop in RS-485 or point-to-point RS-232. The address sent into the Modbus packet addresses

    the Gateway.

    BACnet

    communication

    parameters

    The communication parameters between the supervisory system using the BACnet protocol and the

    Gateway, selectable by the user, are listed below:

    Modbus-Jbus

    communication

    parameters

    The communication parameters between the supervisory system using the Modbus-Jbus protocol and

    Gateway, selectable by the user, are listed below:

    Parameter Selectable value

    baud rate 600 – 1200 – 2400 – 4800 – 9600

    word bit no. 8 (fixed)

    parity NONE - ODD - EVEN

    stop bit no. 1 – 2

    Parameter Selectable value

    baud rate 600 – 1200 – 2400 – 4800 – 9600

    word bit no. 8 (fixed)

    parity NONE - ODD - EVEN

    stop bit no. 1 – 2

  • 8/19/2019 BMS option for Daikin water chillers

    50/88

    ESIE99–03 General

    Part 3 – Functional Description 3–5

    33

    4

    5

    11.3 References to ASHRAE Manual of the BACnet Protocol

    ASHRAE manual All pages mentioned below refer to the ASHRAE manual of the BACnet.

    Characteristics BACnet characteristics are listed in the table below:

    Characteristics of

    the Gateway

    The Gateway ”Conformity Class, Object and Service” characteristics are listed in the table below:

    Errors and

    messages

    BACnet errors and messages are listed in the table below:

    Examples BACnet examples are listed in the table below:

    Chapter Page

    General information on the protocol structure page 8-13

    Detail on the protocol application layer page 14-24

    Description of the network layer page 50-73

    Data link layer Point-to-point page 103-134

    Description of the BACnet "objects" from page 138

    Chapter Page

    Error codes page 313-317

    Coding of the BACnet messages page 322-334

    Coding of the elements that constitute the mes-

    sages (tags)

    page 334-347

    Formal description of the messages from page 348

    Chapter Page

    Error codes page 313-317

    Coding of the BACnet messages page 322-334

    Coding of the elements that constitute the mes-

    sages (tags)

    page 334-347

    Formal description of the messages from page 348

    Chapter Page

    Example of a BACnet message of the "Read-

    Property" type

    page 467

    Example of a BACnet message of the "Write-

    Property" type

    page 475

  • 8/19/2019 BMS option for Daikin water chillers

    51/88

    General ESIE99–03

    3–6 Part 3 – Functional Description

    3

  • 8/19/2019 BMS option for Daikin water chillers

    52/88

    ESIE99–03 Implemented Commands in the Gateway

    Part 3 – Functional Description 3–7

    33

    4

    5

    1Part 3

    2 Implemented Commands in the Gateway

    2.1 What Is in This Chapter?

    Introduction The purpose of this chapter is to provide further information concerning the implemented commands

    in the Gateway.

    Overview This chapter covers the following topics:

    Topic See ...

    2.2 – Protocol page 3-8

    2.3 – Implemented Commands page 3-9

  • 8/19/2019 BMS option for Daikin water chillers

    53/88

    Implemented Commands in the Gateway ESIE99–03

    3–8 Part 3 – Functional Description

    3

    2.2 Protocol

    BACnet Implemented BACnet protocol commands correspond to the Conformity Classes 1 and 2, namely

    ReadProperty and WriteProperty. With these functions, it is possible to read and write a single value

    at a time.

    Modbus-Jbus The software commands of the Modbus-Jbus protocol, ensure the compatibility between Modbus and

    Jbus.

    The data representation of the Modbus-Jbus protocol:

    digital data

    analogue data.

    Digital data

    Modbus-Jbus

    Data is coded by a single digit:

    '0' for OFF

    '1' for ON.

    All the digital variables are assigned to bit of consecutive registers, each one having:

    the lower-address variable assigned to the less significant bit

    the higher-address variable assigned to the most significant bit.

    Analogue data

    Modbus-Jbus

    An analogue value is represented by a 16-bit register in binary notation in complement on two with:

    the most significant part on the byte of higher address

    the less significant part on the byte of lower address.

    Example: the value 10.0 is represented as 0064H

    The Gateway operates on registers where one register must be considered at 16-bit.

  • 8/19/2019 BMS option for Daikin water chillers

    54/88

    ESIE99–03 Implemented Commands in the Gateway

    Part 3 – Functional Description 3–9

    33

    4

    5

    12.3 Implemented Commands

    In the Gateway

    program

    The implemented commands in the Gateway program are listed below:

    Due to the variety of chillers with installed address cards no distinction is made between input

    variables (read only) and output variables (read/write) so that the knowledge of the database and

    its management depends on the part present on the supervisory system.

    Due to the generality of the system, the Gateway answers in the same way to various Modbuscommands.

    Modbus command Meaning Notes

    1 read coil/input status obtains current status (ON/OFF) of a group of

    logic coils or discrete input

    2 read coil/input status obtains current status (ON/OFF) of a group of

    logic coils or discrete input

    3 read holding or input

    registers

    obtains current binary value in one or more

    holding registers

    4 read holding or input

    registers

    obtains current binary value in one or more

    holding registers

    5 force single coil forces single coil to ON or OFF states

    6 preset single register places a specific binary value into a holding

    register

    15 force multiple coils forces a series of consecutive logic coils to

    defined ON or OFF states

    16 preset multiple regis-

    ters

    places specific binary values into a series of

    consecutive holding registers

  • 8/19/2019 BMS option for Daikin water chillers

    55/88

    Implemented Commands in the Gateway ESIE99–03

    3–10 Part 3 – Functional Description

    3

  • 8/19/2019 BMS option for Daikin water chillers

    56/88

    ESIE99–03 Database

    Part 3 – Functional Description 3–11

    33

    4

    5

    1Part 3

    3 Database

    3.1 What Is in This Chapter?

    Introduction The purpose of this chapter is to give further information about on database creation.

    Overview This chapter covers the following topics:

    Topic See ...

    3.2 – Database creation page 3-12

    3.3 – The Address Card EKAC10A Database page 3-16

    3.4 – The Address Card EKAC30A Database page 3-18

    3.5 – The Address Card EKAC60A Database page 3-21

    3.6 – The Address Card EKAC120A Database page 3-24

  • 8/19/2019 BMS option for Daikin water chillers

    57/88

    Database ESIE99–03

    3–12 Part 3 – Functional Description

    3

    3.2 Database creation

    Introduction The supervisory BMS and the address cards communicate through a fixed set of variables, also called

    address numbers.

    These variables are transferred from:

    each address card database to the Gateway, where they are put in the Gateway database

    the Gateway database to the supervisory BMS.

    From the address

    card to the Gateway

    The variables from each address card database can be digital, analogue or integer. The maximum

    number of transferable variables from an address card to the Gateway is given below:

    From the Gateway

    to the supervisory

    BMS

    The BACnet and Modbus-Jbus protocols do not distinguish between analogue and integer variables.

    Therefore variables leaving the Gateway to the BMS can only be digital or analogue.

    The analogue and integer variables of the address card database are in the Gateway database put

    together in the analogue variables. The old analogue variables are numbered from 1 to 128 and the

    old integer variables from 129 to 256.

    The maximum number of transferable variables from the Gateway to the supervisory BMS is given

    below:

    If requested by the supervisory BMS, the Gateway sends out the variables that are not present on the

    machine with the value 0.

    This way, extra inline traffic is created, but the generality of the application is saved. The database is

    dimensioned for the address card with the largest number of variables.

    Example EKAC10A

    database

    The table below shows an example of a digital, an analogue and an integer variable for the address

    card EKAC10A:

    Variable type Maximum number

    digital 200

    analogue 128

    integer 128

    Variable type Maximum numberCorresponding BACnet

    object

    digital 200 binary value

    analogue 256 analogue value

    Variable

    type

    Address

    number

    Read/ 

    write

    Parameter

    CommentDirect/ 

    userName Description

    digital 47 r/w U H7 Enable/disable "remote on/off"

    digital input

    1=enable

    0=disable

    analogue 13 r/w D r4 Heating difference

    integer 38 r/w U H9 Lock of user & direct parameters 0=keyboard disabled

    1=keyboard enabled

  • 8/19/2019 BMS option for Daikin water chillers

    58/88

    ESIE99–03 Database

    Part 3 – Functional Description 3–13

    33

    4

    5

    1Gateway databasecreation To create a database that can be implemented in a Modbus-Jbus or a BACnet supervisor proceed asfollows: The digital variables are transferred with their addresses to the Gateway (Modbus-Jbus or BACnet)

    database. In the Modbus-Jbus database they are read using the commands 1 or 2 (1).

    The analogue variables are transferred with their addresses to the Gateway (Modbus-Jbus orBACnet database). In the Modbus-Jbus database they are read using the commands 3 or 4 (1).

    The integer variables are transferred with their addresses on top of the analogue variables to the

    Gateway (Modbus-Jbus or the BACnet) database. In the Modbus-Jbus database they are read

    using the commands 3 or 4 (1).

    (1) Refer to ‘Implemented Commands’ on page 3-9.

    Gateway database

    diagram

    The creation of a Gateway database from address card databases (slave n databases) is given below.

    Modbus supervisor In the Modbus supervisor, the operator must reserve 25 bytes for the digitals (200 digital variables)and 512 bytes for the analogues (128 analogue variables and 128 integer variables) for a total of 456

    variables for each address card.

    Digital variables

    Slave n database (for each PCB address) Gateway database

    Digital variables

    1

    200

    1

    Analogue variables1

    200

    400...

    ...

    (n-1)*200

    (n-1)*256

    (n-1)*256+128

    Analog variables1

    128

    Integer variables1

    128

    256

    512

  • 8/19/2019 BMS option for Daikin water chillers

    59/88

    Database ESIE99–03

    3–14 Part 3 – Functional Description

    3

    Address list

    creation illustration

    The illustration below shows the Daikin chillers and the BMS.

    Gateway database

    creation: digital

    variables

    The Gateway database creation for the digital variables in the illustration above is herewith given:

    Serial module 

    µ chiller compact 

      l  i  n e

      p  r  i  n  t o

      u  t

     a  l a  r  m

      1

     a  l a  r  m

      2

      r  x   t  x   r e s e  t

    Gateway 

    BMS

    EUWY10HCW1

    EUWAT50KAY1

    EUWT200KXY1

    Address 2

    Address 1

     PCB A: Address 3

     PCB B: Address 4

    UnitAddress towards

    the Gateway

    Assigned address in the Gateway database

    (digital variables)

    EUWY10HCW1 1 001→ 200

    EUWAT50KAY1 2 201→ 400

    EUWT200KXY1

    PCB A

    PCB B

    3

    4

    401→ 600

    601→ 800

  • 8/19/2019 BMS option for Daikin water chillers

    60/88

    ESIE99–03 Database

    Part 3 – Functional Description 3–15

    33

    4

    5

    1Gateway databasecreation: analoguevariables

    The Gateway database creation for the analogue variables in the illustration above is herewith given:

    UnitAddress towards

    the BMS

    Assigned address in

    the Gateway database

    (analogue variables)

    Variable type in the

    address card database

    EUWY10HCW1 1 001→ 128

    129→ 256

    Analogue

    Integer

    EUWAT50KAY1 2 257→ 384

    385→ 512

    Analogue

    Integer

    EUWT200KXY1

    PCB A

    PCB B

    3

    4

    513→ 640

    641→ 768

    769→ 896

    897→

     1025

    Analogue

    Integer

    Analogue

    Integer

  • 8/19/2019 BMS option for Daikin water chillers

    61/88

    Database ESIE99–03

    3–16 Part 3 – Functional Description

    3

    3.3 The Address Card EKAC10A Database

    Introduction The BMS or supervisory system and the address card communicate through a fixed set of variables,

    also called address numbers. Information about the digital, integer and analogue variables that the

    BMS or supervisory system can read from, or write to, the chiller’s address card is given in this section.

    Digital variables The table below shows the digital variables:

    Parameter CommentAddress Read /write

    Direct/ user Name Description EUWA5-10HB(Z)

    EUWY5-10HB*

    1 r/w Cooling or Heating 1=cooling 0=Heating

    2 r/w On or off 1=on 0=off

    5 r H1 Alarm: high pressure or discharge protector orovercurrent

    1= alarm 0=no alarm

    6 r L1 Alarm: evaporating temperature thermostat 1= alarm 0=no alarm

    8 r FL Alarm: flow switch 1= alarm 0=no alarm

    9 r E3 Alarm Ambienttemperature

    Coiltemperature

    10 r E2 Alarm

    11 r E1 Alarm

    12 r n1 Warning: compressor requires maintenance 1= warning 0=no warning

    13 r EP Alarm: EEPROM defective 1= alarm 0=no alarm

    14 r EE Alarm: EEPROM defective 1= alarm 0=no alarm

    15 r EL Alarm: power supply has unusual noise 1= alarm 0=no alarm

    17 r d1 Defrost cycle 1= active 0=not active

    18 r r1 Warning: defrost cycle not completed 1= warning 0=no warning

    19 r A1 Alarm: anti-freeze 1= alarm 0=no alarm

    21 r EO Alarm: supply voltage is high 1= alarm 0=no alarm

    22 r EU Alarm: supply voltage is low 1= alarm 0=no alarm

    25 r Output of pump 1=on 0=off

    26 r Output of compressor 1=on 0=off28 r Output of reversing valve - 1=on 0=off

    29 r Output of alarm 1=on 0=off

    30 r Output of fan 1=on 0=off

    31 r Input of high pressure or discharge protector orovercurrent alarm

    1= closed 0=open

    32 r Input of evaporating temperature thermostat alarm 1= closed 0=open

    33 r Input of remote on/off 1= closed 0=open

    40 r/w U /d Measurement unit of temperature

    47 r/w U H7 Enable/disable “remote on/off” digital input 1=enable 0=disable

  • 8/19/2019 BMS option for Daikin water chillers

    62/88

  • 8/19/2019 BMS option for Daikin water chillers

    63/88

    Database ESIE99–03

    3–18 Part 3 – Functional Description

    3

    3.4 The Address Card EKAC30A Database

    Introduction The BMS or supervisory system and the address card communicate through a fixed set of variables,

    also called address numbers. Information about the digital, integer and analogue variables that the

    BMS or supervisory system can read from, or write to, the chiller’s address card is given in this section.1. If there is referred to a circuit the following syntax is used:

      X/Y: circuit X of EUWA/Y 15-20HB(Z): these chillers have a maximum of 2 circuits

      circuit Y of EUWA/Y25-30HB(Z): these chillers have a maximum of 3 circuits

    2. For all possible values of user settings, refer to the chiller ’s operation manual.

  • 8/19/2019 BMS option for Daikin water chillers

    64/88

    ESIE99–03 Database

    Part 3 – Functional Description 3–19

    33

    4

    5

    1Digital variables The table below shows the digital variables:CommentsAddress Read

     /writeDescription

    EUWA15-30HB(Z) EUWY15-30HB

    1 r Digital input 1 Safety circuit 1/1

    2 r Digital input 2 Safety circuit -/23 r Digital input 3 Safety circuit 2/3

    4 r Digital input 4 - Remote cooling/heatingselection

    5 r Digital input 5 Flow switch

    6 r Digital input 6 - Defrost circuit 1/1

    7 r Digital input 7 - Defrost circuit -/2

    8 r Digital input 8 - Defrost circuit 2/3

    9 r Digital input 9 Dual setpoint

    10 r Digital input 10 Remote on/off

    11 r Digital input 11 Reverse phase protector

    12 r Digital output 1 Compressor 1/1

    13 r Digital output 2 Compressor -/2

    14 r Digital output 3 Compressor 2/3

    15 r Digital output 4 LP bypass circuit 1/1

    16 r Digital output 5 LP bypass circuit -/217 r Digital output 6 Pump

    18 r Digital output 7 General Alarm

    19 r Digital output 8 System on

    20 r Digital output 9 Fanspeed 1 (ry1)

    21 r Digital output 10 Fanspeed 2 (ry2)

    22 r Digital output 11 Fanspeed 3 (ry3)

    23 r Digital output 12 Lp bypass circuit 2/3

    24 r Digital output 13 Evaporator heater Reversing valve

    25 r Cooling/heating mode - 0=heating 1=cooling

    26 r Unit status 1=on 0=off

    27 r Freeze up circuit 1/1 active 1=yes 0=no

    28 r Freeze up circuit -/2 active 1=yes 0=no

    29 r Freeze up circuit 2/3 active 1=yes 0=no

    30 r Circuit 1/1 safety active 1=yes 0=no

    31 r Circuit -/2 safety active 1=yes 0=no

    32 r Circuit 2/3 safety active 1=yes 0=no

    33 r Manual mode active 1=yes 0=no

    37 r Load up timer active 1=not zero 0=zero

    38 r Load down timer active 1=not zero 0=zero

    39 r Start timer active 1=not zero 0=zero

    40 r Flow start timer 1=not zero 0=zero

    41 r Flow stop timer 1=not zero 0=zero

    42 r Guard timer compressor 1/1 active 1=not zero 0=zero

    43 r Guard timer compressor -/2 active 1=not zero 0=zero

    44 r Guard timer compressor 2/3 active 1=not zero 0=zero

    45 r Anti-recycling time compressor 1/1 active 1=not zero 0=zero

    46 r Anti-recycling time compressor -/2 active 1=not zero 0=zero

    47 r Anti-recycling time compressor 2/3 active 1=not zero 0=zero

    48 r Defrost busy compressor 1/1 - 1=yes 0=no49 r Defrost busy compressor -/2 - 1=yes 0=no

    50 r Defrost busy compressor 2/3 - 1=yes 0=no

    51 r Compressor 1/1 off for defrost of other circuit - 1=yes 0=no

    52 r Compressor -/2 off for defrost of other circuit - 1=yes 0=no

    53 r Compressor 2/3 off for defrost of other circuit - 1=yes 0=no

    54 w On-off command If 1 is written, then toggle status of the unit.After this action the controller resets this parameter

    55 w Cool-heat selection command - If 1 is written, then togglestatus of the unit. After thisaction the controller resets thisparameter

  • 8/19/2019 BMS option for Daikin water chillers

    65/88

    Database ESIE99–03

    3–20 Part 3 – Functional Description

    3

    Integer variables The table below shows the integer variables:

    Analogue variables The table below shows the analogue variables:

    CommentAddress Read/ write

    Description

    EUWA15-30HB(Z) EUWY15-30HB

    1 r Actual step number Actual step number2 r Enable of remote chiller-heat pump User setting

    3 r Enable of remote on/off User setting

    4 r Enable write BMS User setting

    5 r Unit type 0=EUWA151=EUWA202=EUWA253=EUWA30

    4=EUWY155=EUWY206=EUWY257=EUWY30

    6 r Refrigeration type 0=R22 1=R407C

    7 r Manufacturer number 1 First digit

    8 r Manufacturer number 2 Second digit

    9 r Manufacturer number 3 Third digit

    10 r Manufacturer number 4 Fourth digit

    11 r Manufacturer number 5 Fifth digit

    12 r Manufacturer number 6 Sixth digit

    13 r Manufacturer number 7 Seventh digit14 r/w Total steps number User setting

    15 r/w Manual setting of compressor 1/1 User setting in manual mode

    16 r/w Manual setting of compressor -/2 User setting in manual mode

    17 r/w Manual setting of compressor 2/3 User setting in manual mode

    18 r/w Manual setting of fans 0=very high, 1=high, 2=medium , 3=low

    19 r/w Load up time User setting

    20 r/w Load down time User setting

    21 r/w Running mode 0=auto, 1=manual

    27 r Water/air-cooled unit 0=air-cooled unit1=water-cooled unit

    28 r Cooling only/heat pump unit 0=cooling only1= heat pump

    29 r Uniq