BLUE DIAMOND’S EXCLUSIVE RANGE OF PERKINS POWERED … · Fuel tank size 85 L Run time @ 75% load...

4
PERKINS POWERED DIESEL GENERATORS THE MOST COST EFFECTIVE PERKINS POWER FOR BUSINESS! BLUE DIAMOND’S EXCLUSIVE RANGE OF BDM 12KVA PERKINS GENERATOR 240/415V No disruption to operating your business, lighting, machinery and computer system Keep your security system powered so your premises are protected from theft Keep refrigerators and freezers in continuous use so no loss of refrigerated goods Gain a competitive advantage when your doors stay open to serve customers’ needs in an emergency Maintain safety in an emergency with schools and public buildings able to operate as emergency shelters Benefits of an automatic Perkins powered system: INDUSTRIAL MINING COMMERCIAL

Transcript of BLUE DIAMOND’S EXCLUSIVE RANGE OF PERKINS POWERED … · Fuel tank size 85 L Run time @ 75% load...

Page 1: BLUE DIAMOND’S EXCLUSIVE RANGE OF PERKINS POWERED … · Fuel tank size 85 L Run time @ 75% load 28 H MINE SITE USE AND SAFETY Bunded fuel tank YES Emergency stop YES Battery isolator

PERKINS POWERED DIESEL GENERATORSTHE MOST COST EFFECTIVE PERKINS POWER FOR BUSINESS!

BLUE DIAMOND’S EXCLUSIVE RANGE OF

BDM 12KVA PERKINS GENERATOR 240/415V

•No disruption to operating your business,

lighting, machinery and computer system

•Keep your security system powered so

your premises are protected from theft

•Keep refrigerators and freezers in

continuous use so no loss of refrigerated

goods

•Gain a competitive advantage when your

doors stay open to serve customers’

needs in an emergency

•Maintain safety in an emergency with

schools and public buildings able to

operate as emergency shelters

Benefits of an automatic Perkins powered system:

INDUSTRIALMINING COMMERCIAL

Page 2: BLUE DIAMOND’S EXCLUSIVE RANGE OF PERKINS POWERED … · Fuel tank size 85 L Run time @ 75% load 28 H MINE SITE USE AND SAFETY Bunded fuel tank YES Emergency stop YES Battery isolator

EXHAUST SYSTEM

Maximum back pressure 10.2 kpa

Exhaust outlet size-horizontal/vertical

42 mm

ELECTRICAL SYSTEM

Alternator 65 amps -12 V

Starter motor Bosch 2 kW -12 V

FUEL SYSTEM

Type of injection Indirect injection

Fuel injection pump Cassette type

Nozzle opening pressure 14.7 MPa

Maximum particle size 25 microns

Blue Diamond’s exclusive Perkins power range has been designed specifically with mining, industrial, and commercial power in mind.

• Easy to Use premium ComAp controller and ATS connection – makes

installing the generator to automatically switch on in the event of a

power failure easy, with the help of an electrician

• Remote Start and Online Monitoring – Start your generator via the

web or a downloadable App. Use in conjunction with off grid Solar

Systems

• Diesel Engine – Diesel is far safer to store over long periods of time

than petrol. Also gives better fuel efficiency and is generally safer

• Low Capital Cost – Our Perkins powerd range are extremely

cost effective

• Back up and Support – Blue Diamond operates a Kewdale based

mechanical work shop with full spare parts and support

Powered by:

BLUE DIAMOND’S PERKINS POWER DIESEL GENERATORS

FUEL CONSUMPTION

100% load 3.8 L/h

75% prime power 3.0 L/h

50% prime power 2.8 L/h

Fuel tank size 85 L

Run time @ 75% load 28 H

MINE SITE USE AND SAFETY

Bunded fuel tank YES

Emergency stop YES

Battery isolator YES

Australian standards YES

www.bluedm.com.au

BDM 12Perkins 240/415V Diesel Generator

ENGINE

Manufacturer PERKINS

Cylinders 3

ArrangementVertical in-line three

Cycle Stroke naturally

Induction system Aspirated

Compression ratio 22.5:1

Bore 85 mm

Stroke 90 mm

Cubic capacity 1.496 L

Estimated total weight (dry)

197kg

Engine rated speed 1500 rpm

Gross engine power-prime 12.5 kW

Gross engine power-Standby

13.5 kW

Brake mean effective pressure

65 kPa

Mean piston speed 4.5 m/s

Engine coolant flow 37.7 L/min

Combustion air flow 1.1 m3/min

Exhaust gas flow (max) 2.7 m3/min

Exhaust gas temperature outlet (max)

445 C

DATA

Model BDM 12 -Perkins 240V

Prime 12 KVA

Voltage 240/415V - 50Hz

Blue Diamond carries all spare parts and supports the

engine with a 12 month or 1000 hour warranty

Page 3: BLUE DIAMOND’S EXCLUSIVE RANGE OF PERKINS POWERED … · Fuel tank size 85 L Run time @ 75% load 28 H MINE SITE USE AND SAFETY Bunded fuel tank YES Emergency stop YES Battery isolator

DIMENSIONS & WEIGHTS

www.bluedm.com.au

ALTERNATOR

Frequency and speed 50Hz/1500rpm

Voltage 240/415V

Prime power 12.5 kVA

Standby power 10 kW

Power efficiency 82.1%

Input power 12.2 kW

Voltage regulation 0.5%

Rated power factor 0.8

Stator winding 2/3

Maximum over speed 2250min-1

Sustained short circuit

72 Amps

Cooling air (m3/sec) 0.09

SOUND PROOF STYLE

Dimensions

Length 1550 mm

Width 780 mm

Height 950 mm

Weight 560kg NET

BDM 12KVA PERKINS GENERATOR 240/415V

Blue Diamond’s Perkins Series

Alternators come equipped with

AVR and are electronically governed.

This means they are safe to use

with electronic equipment including

computers.

Computer safe

Page 4: BLUE DIAMOND’S EXCLUSIVE RANGE OF PERKINS POWERED … · Fuel tank size 85 L Run time @ 75% load 28 H MINE SITE USE AND SAFETY Bunded fuel tank YES Emergency stop YES Battery isolator

CONTROLLER SYSTEM

www.bluedm.com.au6 Hodgson Way, Kewdale08 9353 4436

1300 998 647

Blue Diamond has chosen to partner with CompAp forthe control systems on our Perkins series generators.

• Easy Plug & Play solution• Simply connected using AirGate

technology• System works using WebSupervisor

with all of its benefits• Fleet monitoring and control• Alarm monitoring• On-line notification on alarms• System offers large number of

monitored units (100-1000+)• Server – client based solution• User-friendly graphical interface• Accessible from any PC with

Internet connection• Data is periodically updated from

machines to database server

• Automatic generation of reports - User defined XLSx files

• Access from any web enabled device such as PC/netbook, tablet and smartphone.

• E-mail notification

• Compact gen-set controller for single operating genset• Manual and remote start (MRS) applications• Full gen-set monitoring and protection• Running hours event and performance log• Multiple languages (user changeable) in controller, even

more in installation suite• Plug-in extension modules capability• WebSupervisor, AirGate and Locate support*• Automatic SMS on alarm or event & gen-set control over

SMS*• On-line control and monitoring over web pages

(embedded web server) via plug & play IB-Lite

• Optional GSM/GPRS modem/wireless Internet via IL-NT GPRS

• Fuel theft protection• Alternative switchable configuration• Automatic and manual GCB control• Magnetic pickup input• D+ preexcitation terminal• True RMS measurement• 3 phase power measurement• 3 configurable analog inputs• 6 binary inputs• 6 binary outputs

Cloud Based System for Monitoring and Controlling of ComAp Controllers

*Plug-in module required

InteliLiteNT MRS 10Manual Remote Start (MRS) Gen-set Controller