Alstom Grid Inc.- P 1 Big Data Analytics for Power Grid Operations Manu Parashar, Corporate Power System Engineer IEEE-Northwest Energy Systems Symposium (NWESS) May 1 st , 2014

Transcript of Big Data Analytics for Power Grid Operationscialab.ee.washington.edu/nwess/2014/speakers/6A... ·...

Alstom Grid Inc.- P 1

Big Data Analytics for Power Grid Operations

Manu Parashar, Corporate Power System Engineer IEEE-Northwest Energy Systems Symposium (NWESS)

May 1st, 2014

Alstom Grid Inc.- P 2

Agenda

Synchrophasor Data Analytics for Real Time Grid Operations

Synchrophasor Data Analytics for Offline Engineering Analysis

Solution Architecture for Managing Big Data Analytics

Big Data in the Energy Industry

Conclusions

Alstom Grid Inc.- P 3

Big Data in the Energy Industry

Field level PMU IED Meter DA DG CMU HAN Line sensor

Others photos,

videos,

labs analysis,

site reports,

Financial

Qty

Time

Resolution

Type

1k 100k 10k 100k 10k 10M 100M 10k

Weather

100k

1ms 100ms 10ms 1s 10min 1min

to 15min 100M 10k 100k

V I Ph

Hz

V I

Hz Sw MW MVA T°, Qual

MWh

V I ph

Hz

History

100M 10k 100k

Files

100Tb

Comm (AMI, Tcom)

Signal Processing and Local Automation

Grid Operations

Business Operations

Customer Engagement

Real Time

Data Management

Transactional

3

Scada PDC MDM

Alstom Grid Inc.- P 4

Big Data Analytics Measurement to Information Value Chain

1. Meters 2. Telecom infrastructure 3. Data concentrator and Head end 4. Data Aggregation, qualification, processing 5. Interaction with others utilities IT/OT systems

(scada, asset data, weather data, customers data, etc…) 6. Data analytics 7. Historian of large quantity of data from various sources 8. Utility Analytics 9. Presentation : User Interface, Business Intelligence

• Meter Data Management refers to layers 4 - 5 – 6

• MDM as Master Data Management refers to layers 7 – 8 –9

Concentrator

Telecom Backhaul

Aggregation and Qualification

1

3

2

3

4

5 6

Telecom last miles 2

Head End

Meter Analytics

9

7

Signals

Data

Information

meters M M

M M

M

4

Grid

Operations

Business

Operations Customer

Engagement Meter

Meter

MDM

IT and OT Systems

IT and OT Systems

Historian

Presentation UI & BI

Utility Analytics 8

Master

MDM

Information

Alstom Grid Inc.- P 5

Holistic Approach to Big Data Analytics A functional transverse layer that pull data from all sources and generate value to each domain

5

Field level PMU IED Meter DA

PDC Scada

Comm

Field

gateways

Applications DMS EMS OSS

DG

CIS ERP GIS

Geo - Spatial

MMS

CMU

Telecom and AMR

ACM

UI Op Stations Mobile UI

DR Planning

HAN

DER

Meter DM

Customer Services

Utility Perfor mance

Grid Operations

Data Transform and Load

Data to Information Additional

Value to Users

Data Segmentation and Storage

UMDM is a facility to integrate real time data, meter data, financial data, and analytics

to bring value to Network Operations, Network Planning, Customer Services and Company Efficiency

UI Information

Presentation

Grid Asset & Planning

HAN Mgr

Analytics

Containers

Collectors

UMDA

Others photos, videos, labs analysis, site reports …

Focus

Data

Data

Information

Alstom Grid Inc.- P 6

SynchroPhasor Technology

− Next generation measurement technology. (voltages, currents, frequency, frequency

rate-of-change, etc)

− Higher resolution scans (e.g. 30 samples/second). ─ Improved visibility into dynamic grid conditions. ─ Early warning detection alerts. − Precise GPS time stamping. ─ Wide-area Situational Awareness. ─ Faster Post-Event Analysis. ─ Coordinated Wide-area Control Actions.

“PMUs: MRI quality , color 3-D visibility compared to

X-ray quality , B&W 2-D visibility of SCADA” – Terry Boston (CEO, PJM)

PMU ‘Sub-second’ Resolution

SCADA ‘Seconds’ Resolution

Phasor Measurement Units (PMUs)

p6

Alstom Grid Inc.- P 7

Synchrophasor Deployment in North America Changing Landscape

Source: NASPI Website (www.naspi.org)

p7

Approx. 200 PMUs in 2007 Over 1200 PMU deployed by 2014 (over 10TB/Month of “raw” PMU data)

Alstom Grid Inc.- P 8

Data Archiving

• Short Term Rolling Buffer (e.g. 3-12 months)

• Long Term Rolling Buffer (e.g. 1-5 years)

• Event Trigger (Snapshot)

• Transparent to user

• Limited only by hardware

• Flexible data rates

Short Term e.g. 50Hz

LongTerm e.g. 1Hz

Snapshot e.g. 50Hz

Search returns highest

resolution available

Alstom Grid Inc.- P 9

Data Compression (Lossy v.s. Lossless Compression)

(courtesy Dmitry Kosterev, BPA)

Alstom Grid Inc.- P 10

Approaches for Processing Big Data

• Temporal Processing (compression) – Pre-calculated analytics (results archived).

• Spatial Processing – Distributed Analytics (at substation & control center)

Control Center Analytics

RTUs IEDs PMUs

Control

Center

Analytics

Substation

Analytics

Meters

Data

Information

Alstom Grid Inc.- P 11

Control Center

Control Center Level Topology Processor

Control Center Level State EstimatorSystem

Topology

Power System Communication Network

RT-Database

SL-SESL-TP

Topology States

Substation

Substation

SubstationServer

Substation

SubstationServer

SubstationServer

Static-Database

SL-TP: Substation Level Topology Processor

SL-SE: Substation Level State Estimator

RT: Real Time

System-levelRT-Database

Control Center

Topology Processor

State Estimator

Real Time Database

Static Database

AnalogueMeasurements

DigitalStatus

CB/ND connections ND/Equip

Connections

EquipmentParameters

SystemTopology

SubstationRTU

SubstationRTU Substation

RTU

SCADA

Maintenance

Two-Level Linear State Estimator Example of distributed analytics

Currently underway in collaboration with WSU (Prof. Anjan Bose) Being deployed at PG&E under their Synchrophasor Project

Control Center

Substation

Alstom Grid Inc.- P 12

Data Analytics – Modes of Operation

REAL-TIME OFFLINE (AFTER-THE-FACT)

CONT

INUO

US

(PUS

H)

ON D

EMAN

D (P

ULL)

Centrally administered (modeled & configured). No end-user intervention.

Continually processed using a ‘Time-Window’ of data at periodic update rates.

View-only mode to review the results.

Analysis results may be archived.

Examples: Oscillatory Stability Monitoring. End-user or event triggered.

Little to none end-user intervention.

Single real-time view of the results.

Results are made available as soon as they are generated.

Examples: Event capture and reporting.

Typically ‘data mining’ analytics that “walk-through” large volumes of historical data in smaller chunks (i.e. batch processing).

May require initial metadata from end-user.

Results are presented once the entire processing is complete.

Examples: Baselining.

Locally processed by the end-user.

Fully interactive end-user experience; close feedback between data-analytics-UI.

Results are locally archived & presented to the end-user.

Examples: Post-Event Analysis.

Alstom Grid Inc.- P 13

WAMS IN OPERATIONS PLANNING

Examples of Real-Time Data Analytics

System Disturbance Characterization Oscillatory Stability Monitoring Understanding grid vulnerabilities Big data analytics

e-terra Phasor Point

Alstom Grid Inc.- P 14

System Disturbance Characterization Application Theory and Concepts

Concept: Illustration of Angle Movement in Response to a Disturbance

• Angle (δ) and Speed (ω) can’t change

instantaneously at a generator

• δ & ω near a generator influenced by generator angle

• δ & ω move more rapidly near the disturbance than far away

• Disturbance appears to propagate as a kind of “wave”

Alstom Grid Inc.- P 15

“Typical” Disturbance

Electromechanical oscillations

Inertial response (f)

Angle difference

System Disturbance Characterization Example of “Typical” Disturbance (Load Loss)

Alstom Grid Inc.- P 16

Freq (& angle) moves first close to disturbance

System Disturbance Characterization Example

Alstom Grid Inc.- P 17

Disturbance Characterization

Type Characteristics

Generation Trip - Frequency drops initially (RoC α amount of load loss) - First Angle/Frequency changes occurs near the disturbance - Oscillations due to the electromechanical responses

Load Loss - Similar to Generation Trip, but frequency moves upwards - Positive Frequency RoC

Line Trip - Increasing angle separation - Change in angle (with ringdown) - Frequency is not affected (but oscillations)

Cascading Failure Multiples types of disturbances in sequence: - Common mode generation loss - Sequential protection tripping - Storm damage

System Disturbance Characterization

Alstom Grid Inc.- P 18

System Disturbance Management

1) Detect disturbance

2) Locate trigger point

3) Detect event type

4) Estimate impact

1 sec

Alstom Grid Inc.- P 19

System Disturbance Characterization Analytic

Alstom Grid Inc.- P 20

Dynamic (Oscillatory) Stability Management

“The interconnected electric power grid is one of the largest dynamic system of today”

p20

• Numeric SCADA displays today

• With synchro-phasors – high resolution trend display

Rapidly changing digits on a numeric display

Oscillations seen by SCADA and PMU data

-5 0 5 10 15 20 2559.98

59.99

60

60.01

60.02

60.03

60.04

60.05

60.06

Time (sec)

Freq

uenc

y (Hz

)

Western Interconnection Frequencies - August 4 2000 Oscillation

Grand CouleeMalinDevers

Alstom Grid Inc.- P 21

Oscillatory Stability Monitoring Analytics

Mode Alarming: 3 min window, 5 sec update, for alarms

Mode Trending: 20-180 min window, 20 sec update, for analysis

Alstom Grid Inc.- P 22

Operational Warnings

• Observe mode behaviour

− Alarm if Abnormal, Near Instability

1/F MODE FREQUENCY

MODE DECAY TIME

EXP(-t/ ? )

Mode Freq

Mode decay time Exp(-t/τ) MODE AMPLITUDE

A

MODE PHASE

Mode Amplitude

Mode Phase In the Mode Selector Tabs the Frequency and

Damping of the poorest damped PDX result is

shown (5 seconds update rate)

Mode Shape, derived from the PDX, is shown

for each mode band

Return to Section Index

Alstom Grid Inc.- P 23

Example: Modes Observed in Colombia

• Ecuador Mode 0.49Hz

• Governor Mode 0.06Hz

Inter-area mode at 0.49Hz (Colombia-Ecuador).

Opposing phase in South

Governor common-mode: whole system oscillates

in coherent phase

Alstom Grid Inc.- P 24

WAMS IN OPERATIONS PLANNING

Examples of Offline Data Analytics

Model Validation (Ringdown Analysis) Dynamic Perfomance Baselining Automated Reporting

Alstom Grid Inc.- P 25

Offline Data Analytics

P25

Leveraging Synchrophasors in Operations Planning

Synchrophasor benefits for Post-Event Analysis

In the case of the 2007 Florida blackout, NERC investigators used

phasor data to create the sequence of events and determine the cause of

the blackout in only two days; in contrast, lacking high-speed, time-

synchronized disturbance data it took many engineer years of labor to

compile a correct sequence of events for the 2003 blackout in the

Northeast U.S. and Ontario.

NERC RAPIR Report, 2010.

• New Risk Indicators • Tune Real-Time Analytics • Quicker post-mortem analysis.

• Sequence of events & root cause analysis. Post Event Analysis

• Dynamic model verification.

• Generator model calibration.

• Load characterization.

Dynamic Model

Validation

• Assess dynamic performance of the grid.

• Steady-state angular separation.

• System disturbance impact measures.

Baselining

• Primary frequency (governing) response.

• Power System Stabilizer (PSS) tuning

Compliance

Monitoring

Alstom Grid Inc.- P 26

Model Validation – Comparison Modes Between PMU data and Simulation Data

Both PMU measured and simulated power contain 0.72Hz Mode

Original signals (in solid lines)

and reconstructed signals (in

dash lines)

Selected exactly same time period on both PMU measured power and simulated power.

PMU Observations (from PhasorPoint)

TSAT Simulations (from Powertech’s DSA)

Alstom Grid Inc.- P 27

Offline Model Validation with Synchrophasors

Both PMU measured and simulated power contain

1.10Hz Mode

Simulation data shows negative damping ratio!

Selected exactly same time period on both PMU measured power and simulated power.

Original signals (in solid lines) and reconstructed

signals (in dash lines)

TSAT Simulations (from Powertech’s DSA)

PMU Observations (from PhasorPoint)

Alstom Grid Inc.- P 28

Offline Analysis Application (Dynamic Performance Trending)

Oscillatory mode trends

Apply post-analysis filters

“Filtered” oscillatory mode trends….

Alstom Grid Inc.- P 29

Monthly Performance Report

• Review of Modes of Oscillation − Baseline - normal behaviour patterns − Unusual events – source location

• Review Disturbances − Examples of Post-Event Analysis

• Threshold Settings (Statistics) − OSM Oscillation Alarms − SDM Disturbance parameters − Angle Behaviour Templates & Alarms

PSY-CLIENT-SDR1105-V1

CLIENT

May 2012

Regular Monthly Reporting

Alstom Grid Inc.- P 30

Closing Remarks

• Big data management/analytics require a holistic approach across multiple data sources serving different stakeholders.

• Synchrophasors are increasingly becoming a part of ‘Big Data’ within the energy industry (next generation SCADA)

• Approaches to handling big data include: − Temporal processing (compression) – i.e. pre-calculated results/stats. − Spatially distributed processing – i.e. processing at the meter/substation/control center

levels.

• Big data analytics operate in different modes including real-time, offline, continuous (automated), and on-demand. → combination of “push”/ “pull” mechanisms needed to satisfy these needs.