George Hannah,Product Development Director
Better by design, exploring containment options to optimise every Cooling kW
Why Airedale?
Global provider of efficient cooling solutions
Almost 40 years experience in IT industry
Largest UK manufacturer of IT cooling solutions
A pioneer in free-cooling technology
An industry leader in rack level cooling
Who Are We?
Who Are We?
What Do We Do?
50,000 applications since 1974 1,200 last year2011
Business Issues
Uptime
Efficiency
Capital Costs
Operational Costs
FootprintAnd Density
Types of Containment
The 2nd Law of Thermodynamics
“The second law states that spontaneous natural processes increase entropy overall, or in another formulation that heat can spontaneously be conducted or radiated only
from a higher-temperature region to a lower-temperature region, but not the other way around.”
TH TC
TW
Temperature (oC)
Total heat load
Total number of cabinets
Open Aisle (500kW Facility)
40
35
15
5
10
30
25
20
Return
5 kW per Rack
100
45
Supply
Cold Aisle Containment (500kW Facility)
Temperature (oC)
Total heat load
Total number of cabinets
5 kW per Rack
100
40
35
15
5
10
30
25
20
45
Hot Aisle Containment (500kW Facility)
Temperature (oC)
Additional IT opportunity =
420kW
Total heat load
Total number of cabinets
10 kW per Rack
50
40
35
15
5
10
30
25
20
45
InRak Hot Aisle Containment (500kW Facility)
Temperature (oC)
Additional IT opportunity =
420kW
Total heat load
Total number of cabinets
9.8 kW per Rack
51
40
35
15
5
10
30
25
20
45
OnRak Compact Hot Aisle (500kW Facility)
Temperature (oC)
Additional IT opportunity
=1880kW
Total heat load
Total number of cabinets
20 kW per Rack
25
40
35
15
5
10
30
25
20
45
Temperature (oC)
40
35
15
5
10
30
25
20
45
ECHO - Compact Hot Aisle (500kW Facility)
Additional IT opportunity = 894kW
Total heat load
Total number of cabinets
20 kW per Rack
25
Temperature (oC)
40
35
15
5
10
30
25
20
45
Open Aisle
OnRak
Supply and Return Temperatures
ECHO
InRak
Cold Aisle
Hot Aisle
ReturnSupply
ECHOInRakHot Aisle
Open Aisle
Supply and Return Temperatures
05
40
10152025
3530
CRACCold Aisle
Temperature 0C
45Return Air
Supply Air
OnRakCold Aisle
Indirect - AIR Direct - AIR Indirect - WATER
What is Free Cooling?
OUT
IN
Free Cooling
Hours per year
600
300
Ambient Temperature (ºC) -6 -2 2 6 10 14 18 22 26 30
48% 51%
1%
Open Aisle
Free cooling Concurrent Mode Mechanical
Free Cooling
Hours per year
600
300
Ambient Temperature (ºC) -6 -2 2 6 10 14 18 22 26 30
62% 32%
Cold Aisle
6%
Free cooling Concurrent Mode Mechanical
Free Cooling
Hours per year
600
300
Ambient Temperature (ºC) -6 -2 2 6 10 14 18 22 26 30
67% 18%
Hot Aisle
25%
Free cooling Concurrent Mode Mechanical
Free Cooling
Hours per year
600
300
Ambient Temperature (ºC) -6 -2 2 6 10 14 18 22 26 30
67% 18%
InRak
25%
Free cooling Concurrent Mode Mechanical
Free Cooling
Hours per year
600
300
Ambient Temperature (ºC) -6 -2 2 6 10 14 18 22 26 30
69% 11%
OnRak
20%
Free cooling Concurrent Mode Mechanical
Free Cooling
Hours per year
600
300
Ambient Temperature (ºC) -6 -2 2 6 10 14 18 22 26 30
ECHO
89%
Free cooling Concurrent Mode Mechanical
10%
1%
Free cooling
Free Cooling
Open Aisle Cold Aisle Hot Aisle
OnRakInRak ECHO
Concurrent Mode
Mechanical
Technical Matrix
FREE
COOL
Free-coolingopportunity
(%)
Systemefficiency
(Annualised PUE)
Space claim(cooling
equipment (m²)
Space claim(IT
equipment (m²)
Open Aisle
Cold Aisle
Hot Aisle
InRak
OnRak
ECHO
49% 1.45 14 60
68% 1.38 14 60
92% 1.30 14 30
92% 1.29 12 30
89% 1.26 3 15
99% 1.24 14 15
Commercial Matrix
Capital costsOperating
costs(annualised)
Total operating£/kW p.a.
Payback period
(months)
Open Aisle
Cold Aisle
Hot Aisle
InRak
OnRak
ECHO
£139,996 £291,402 £99 13
£143,878 £125,869 £84 14
£124,383 £95,585 £58 16
£190,575 £60,350 £56 14
£186,620 £57,827 £33 15
£192,208 £42,992 £27 15
Month
Free-coolingopportunity
(%)
Systemefficiency
(Annualised PUE)
Space claim(cooling
equipment (m²)
Space claim(IT
equipment (m²)
Open Aisle
Cold Aisle
Hot Aisle
InRak
OnRak
ECHO
49% 1.45 14 60
68% 1.38 14 60
92% 1.30 14 30
92% 1.29 12 30
89% 1.26 3 15
99% 1.24 14 15
Case Study: Open Aisle Containment
FREE
COOL
0
1.5
2.0PUE
The chillers give us 1500kW n + 1 cooling plus a stunning reduction in electricity consumption i.e.
2.5 times cooling capacity for 100 – 150kW less power consumption per day.
Mark Ford
Data Centre Manager
Case Study: Open Aisle Containment
Free-coolingopportunity
(%)
Systemefficiency
(Annualised PUE)
Space claim(cooling
equipment (m²)
Space claim(IT
equipment (m²)
Open Aisle
Cold Aisle
Hot Aisle
InRak
OnRak
ECHO
49% 1.45 14 60
68% 1.38 14 60
92% 1.30 14 30
92% 1.29 12 30
89% 1.26 3 15
99% 1.24 14 15
Case Study: Cold Aisle Containment
FREE
COOL
Free-coolingopportunity
(%)
Systemefficiency
(Annualised PUE)
Space claim(cooling
equipment (m²)
Space claim(IT
equipment (m²)
Open Aisle
Cold Aisle
Hot Aisle
InRak
OnRak
ECHO
49% 1.45 14 60
68% 1.38 14 60
92% 1.30 14 30
92% 1.29 12 30
89% 1.26 3 15
99% 1.24 14 15
Case Study: Hot Aisle Containment
FREE
COOL
FREE
COOL
------------------------
95%
Airedale provides us with a fully integrated cooling solution designed for maximum efficiency and
critical redundancy…Our carbon neutral status helps our clients take huge steps towards their own
environmental goals and carbon reduction commitments.
Rob Garbutt
Chief Executive Officer
Case Study: Hot Aisle Containment
Free-coolingopportunity
(%)
Systemefficiency
(Annualised PUE)
Space claim(cooling
equipment (m²)
Space claim(IT
equipment (m²)
Open Aisle
Cold Aisle
Hot Aisle
InRak
OnRak
ECHO
49% 1.45 14 60
68% 1.38 14 60
92% 1.30 14 30
92% 1.29 12 30
89% 1.26 3 15
99% 1.24 14 15
Case Study: InRak Hot Aisle Containment
FREE
COOL
Guaranteed PUE 1.29
The InRak is perfectly designed…the units are very clever; they ‘talk’ to each other and maintain pressure
in the room. ACIS gives us 24/7 control of the operation and peace of mind.
Mike Marchant
Data Centre Manager
Case Study: InRak Hot Aisle Containment
Free-coolingopportunity
(%)
Systemefficiency
(Annualised PUE)
Space claim(cooling
equipment (m²)
Space claim(IT
equipment (m²)
Open Aisle
Cold Aisle
Hot Aisle
InRak
OnRak
ECHO
49% 1.45 14 60
68% 1.38 14 60
92% 1.30 14 30
92% 1.29 12 30
89% 1.26 3 15
99% 1.24 14 15
Case Study: OnRak Compact Hot Aisle
35% savings vs. standard DX
Our HPC facility at Leeds is growing …by meeting our space constraints and slotting into our existing cooling loop, the OnRak units from Airedale have saved us space in an already densely packed
environment
Dr Jon Summers
Senior Lecturer, School of Mechanical Engineering
Case Study: OnRak Compact Hot Aisle
Increased IT Opportunity
0
20
100
40
60
80
Space m2Cooling
Equipment (m2)Rack (m2)
ECHOInRakHot
AisleOpenAisle
OnRakColdAisle
30m² 32m² 56m² 45m²
Additional Space (m2)
ECHOInRakHot
AisleOpenAisle
OnRakColdAisle
3 Year Lifecycle Cost
0
0.2
1.2
0.4
0.6
0.8
1.0
£ (millions)
1.45 1.38 1.30 1.29 1.26 1.24
Operating Costs
(over 3 years)Total Capital
CostPUE
Business Issues
Uptime
Efficiency
Capital Costs
Operational Costs
FootprintAnd Density
Contact Us
For more information on any of our products please visit: