BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES 6.4 H Putter.pdf · Source: IEEE 400.2 (2013) –...

22
1 BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES HEIN PUTTER Productmanager cable testing and -diagnosis Megger Site Germany 13 th Insucon conference – 16 -18 th Mai 2017, Birmingham, UK

Transcript of BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES 6.4 H Putter.pdf · Source: IEEE 400.2 (2013) –...

Page 1: BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES 6.4 H Putter.pdf · Source: IEEE 400.2 (2013) – Table G.1. 9 Case Study: Acceptance testing PD Mapping @ Uo PD Mapping @ 2Uo DAC

1

BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES

HEIN PUTTERProductmanager cable testing and -diagnosis

Megger Site Germany

13th Insucon conference – 16 -18th Mai 2017, Birmingham, UK

Page 2: BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES 6.4 H Putter.pdf · Source: IEEE 400.2 (2013) – Table G.1. 9 Case Study: Acceptance testing PD Mapping @ Uo PD Mapping @ 2Uo DAC

2

Agenda■ Introduction■ Case Study: Acceptance/ commissioning testing■ Case Study: Condition Monitoring■ Summary & Conclusions

Page 3: BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES 6.4 H Putter.pdf · Source: IEEE 400.2 (2013) – Table G.1. 9 Case Study: Acceptance testing PD Mapping @ Uo PD Mapping @ 2Uo DAC

3

Introduction Offline cable diagnostics on MV cables are nowadays widely accepted

and in some countries already standardized (for commissioning)

This, as it is known that a pure withstand test will not identify all workmanship issues

In addition, offline cable diagnostics are also very useful for condition assessment of service aged MV cables

Page 4: BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES 6.4 H Putter.pdf · Source: IEEE 400.2 (2013) – Table G.1. 9 Case Study: Acceptance testing PD Mapping @ Uo PD Mapping @ 2Uo DAC

4

Introduction Offline cable diagnostics we need to divide into:

• PD diagnostics • Dielectric diagnostics

Dielectric diagnostics are mainly performed on service aged cables only, most familiar method is a dielectric loss measurement (tanDelta)

Offline PD diagnostics can be performed with a number of excitations voltages each having their own benefits

Page 5: BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES 6.4 H Putter.pdf · Source: IEEE 400.2 (2013) – Table G.1. 9 Case Study: Acceptance testing PD Mapping @ Uo PD Mapping @ 2Uo DAC

5

Introductioncontinuous AC

sinusoidal

0.1 Hz

Damped AC Cosine rectangular

50 Hz

20 - 300 Hz

20 - 500 Hz 0.1 Hz 20 - 300 Hz

Ground wave

Transition

Page 6: BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES 6.4 H Putter.pdf · Source: IEEE 400.2 (2013) – Table G.1. 9 Case Study: Acceptance testing PD Mapping @ Uo PD Mapping @ 2Uo DAC

6

Agenda■ Introduction■ Case Study: Acceptance/ commissioning testing■ Case Study: Condition Monitoring■ Summary & Conclusions

Page 7: BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES 6.4 H Putter.pdf · Source: IEEE 400.2 (2013) – Table G.1. 9 Case Study: Acceptance testing PD Mapping @ Uo PD Mapping @ 2Uo DAC

7

Case Study: Acceptance testing

Commissioning test on a newly installed XLPE cable

Operation voltage: 12/20 kV Cable length: 2308 m Cable type: XLPE, 3x1x240 mm2

Joints: 7 Year of installation: 2016 Withstand test: passed (3Uo, 60 minutes)

Page 8: BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES 6.4 H Putter.pdf · Source: IEEE 400.2 (2013) – Table G.1. 9 Case Study: Acceptance testing PD Mapping @ Uo PD Mapping @ 2Uo DAC

8

Case Study: Acceptance testing TanDelta Measurement

Source: IEEE 400.2 (2013) – Table G.1

Page 9: BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES 6.4 H Putter.pdf · Source: IEEE 400.2 (2013) – Table G.1. 9 Case Study: Acceptance testing PD Mapping @ Uo PD Mapping @ 2Uo DAC

9

Case Study: Acceptance testingPD Mapping @ Uo PD Mapping @ 2Uo

DAC Excitation Voltage

Page 10: BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES 6.4 H Putter.pdf · Source: IEEE 400.2 (2013) – Table G.1. 9 Case Study: Acceptance testing PD Mapping @ Uo PD Mapping @ 2Uo DAC

10

Case Study: Acceptance testingPD Mapping @ Uo PD Mapping @ 2Uo

Sinus Excitation Voltage (measurement from far end)

Page 11: BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES 6.4 H Putter.pdf · Source: IEEE 400.2 (2013) – Table G.1. 9 Case Study: Acceptance testing PD Mapping @ Uo PD Mapping @ 2Uo DAC

11

Case Study: Acceptance testingSummary: Withstand test at 3Uo for 60 minutes did not identify weak spot.

tanDelta measurement showed „further study advised“, althoughcable is new typical behaviour for new co-polymer cables/ resistive field stress control heat shrink joints

tanDelta measurement did not identify local problem in phase L3

Both excitation voltages (VLF sinus 0.1 Hz and DAC) showedcomparable results (PDIV, PD intensity and PD level)

Page 12: BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES 6.4 H Putter.pdf · Source: IEEE 400.2 (2013) – Table G.1. 9 Case Study: Acceptance testing PD Mapping @ Uo PD Mapping @ 2Uo DAC

12

Agenda■ Introduction■ Case Study: Acceptance/ commissioning testing■ Case Study: Condition Monitoring■ Summary & Conclusions

Page 13: BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES 6.4 H Putter.pdf · Source: IEEE 400.2 (2013) – Table G.1. 9 Case Study: Acceptance testing PD Mapping @ Uo PD Mapping @ 2Uo DAC

13

Case Study: Condition MonitoringCondition monitoring on a service aged mixed cable

Operation voltage: 12/20 kV Cable length: 653 m Cable type : Mixed cable (XLPE, paper insulated) Joints: 7 Year of installation: 1973

Page 14: BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES 6.4 H Putter.pdf · Source: IEEE 400.2 (2013) – Table G.1. 9 Case Study: Acceptance testing PD Mapping @ Uo PD Mapping @ 2Uo DAC

14

Case Study: Condition Monitoring TanDelta Measurement

tanDelta results Local problem in L3

Page 15: BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES 6.4 H Putter.pdf · Source: IEEE 400.2 (2013) – Table G.1. 9 Case Study: Acceptance testing PD Mapping @ Uo PD Mapping @ 2Uo DAC

15

Case Study: Condition Monitoring Fault located in L3 positioned at 470m, not caused by

external damage, pure internal fault.

Page 16: BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES 6.4 H Putter.pdf · Source: IEEE 400.2 (2013) – Table G.1. 9 Case Study: Acceptance testing PD Mapping @ Uo PD Mapping @ 2Uo DAC

16

Case Study: Condition MonitoringPD Mapping @ Uo PD Mapping @ UoVLF Sinus 0.1Hz VLF CR 0.1Hz (210Hz)

Page 17: BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES 6.4 H Putter.pdf · Source: IEEE 400.2 (2013) – Table G.1. 9 Case Study: Acceptance testing PD Mapping @ Uo PD Mapping @ 2Uo DAC

17

Case Study: Condition MonitoringPD Mapping @ 2Uo PD Mapping @ 2UoVLF Sinus 0.1Hz VLF CR 0.1Hz (210Hz)

Page 18: BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES 6.4 H Putter.pdf · Source: IEEE 400.2 (2013) – Table G.1. 9 Case Study: Acceptance testing PD Mapping @ Uo PD Mapping @ 2Uo DAC

18

Case Study: Condition MonitoringSummary: tanDelta measurement helped to identify local problem

PD diagnosis with VLF Sinus 0.1Hz did not identify the fault position, VLF CR did

At operating voltage cable, apart from failure position, PD free

At elevated voltages several PD defects in accessories localised

Trending measurement recommended after 3 years

Page 19: BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES 6.4 H Putter.pdf · Source: IEEE 400.2 (2013) – Table G.1. 9 Case Study: Acceptance testing PD Mapping @ Uo PD Mapping @ 2Uo DAC

19

Agenda■ Introduction■ Case Study: Acceptance/ commissioning testing■ Case Study: Condition Monitoring■ Summary & Conclusions

Page 20: BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES 6.4 H Putter.pdf · Source: IEEE 400.2 (2013) – Table G.1. 9 Case Study: Acceptance testing PD Mapping @ Uo PD Mapping @ 2Uo DAC

20

Summary & ConclusionsCommissioning testing: Withstand testing only is not sufficient as a commissioning test

tanDelta diagnosis on a new cable can be misleading (co-polymer/ local problem)

PD diagnostics are strongly recommended

Excitation voltage should be comparable to operatingfrequency

Page 21: BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES 6.4 H Putter.pdf · Source: IEEE 400.2 (2013) – Table G.1. 9 Case Study: Acceptance testing PD Mapping @ Uo PD Mapping @ 2Uo DAC

21

Summary & ConclusionsCondition monitoring: For condition monitoring in addition a tanDelta diagnosis is

recommended

A tanDelta diagnosis can also identify local problems

Excitation voltage should be comparable to operatingfrequency, differences between Sinus 0.1Hz and DAC or VLF CR have been observed.

Page 22: BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES 6.4 H Putter.pdf · Source: IEEE 400.2 (2013) – Table G.1. 9 Case Study: Acceptance testing PD Mapping @ Uo PD Mapping @ 2Uo DAC

22

Questions ?