Battery Safety and Handling EFCOG Electrical Safety Task Group Module 9

25
09/06/07 EFCOG Electrical Safety T ask Group 1 Battery Safety and Handling EFCOG Electrical Safety Task Group Module 9

description

Battery Safety and Handling EFCOG Electrical Safety Task Group Module 9. Lead Acid Batteries. Typically Lead-Antimony. Made up of plates, lead, lead oxide with 35% sulfuric acid and 65% water solution. - PowerPoint PPT Presentation

Transcript of Battery Safety and Handling EFCOG Electrical Safety Task Group Module 9

Page 1: Battery Safety and Handling EFCOG Electrical Safety Task Group Module 9

09/06/07 EFCOG Electrical Safety Task Group

1

Battery Safety and Handling

EFCOG Electrical Safety Task Group

Module 9

Page 2: Battery Safety and Handling EFCOG Electrical Safety Task Group Module 9

09/06/07 EFCOG Electrical Safety Task Group

2

Lead Acid Batteries• Typically Lead-

Antimony.• Made up of plates,

lead, lead oxide with 35% sulfuric acid and 65% water solution.

• The solution is called electrolyte, which causes a chemical reaction that produces electrons.

Page 3: Battery Safety and Handling EFCOG Electrical Safety Task Group Module 9

09/06/07 EFCOG Electrical Safety Task Group

3

Posit ivePlate Group

NegativePlat e Group

Separator

Cell Element

Page 4: Battery Safety and Handling EFCOG Electrical Safety Task Group Module 9

09/06/07 EFCOG Electrical Safety Task Group

4

Hazards Associated With Industrial Batteries

Hydrogen Gas

Sulfuric Acid

Shock

Weight of the Battery

Page 5: Battery Safety and Handling EFCOG Electrical Safety Task Group Module 9

09/06/07 EFCOG Electrical Safety Task Group

5

Hydrogen Gas

A by-product of the battery’s charging process.

Lighter than air.Flammable in nature. Explosive mixture at 4 – 74% by volume of

air.Can not taste or see the gas vapors. You can

smell the acid in the battery if it heats up.

Page 6: Battery Safety and Handling EFCOG Electrical Safety Task Group Module 9

09/06/07 EFCOG Electrical Safety Task Group

6

Acid Hazards

Ph <2 (Typically Sulfuric Acid)Corrosive materialBurns to skinBurns to eyesNever open the battery caps with

your face directly over the battery.

Page 7: Battery Safety and Handling EFCOG Electrical Safety Task Group Module 9

09/06/07 EFCOG Electrical Safety Task Group

7

Electrical Hazard• Exposed terminals, even on disconnected

batteries, present an electrical shock hazard.

• Some battery systems are capable of discharging at extremely high rates of current. Accidental shorting of terminals or cables can result in severe electrical arcing, causing burns and electric shock to nearby personnel

Page 8: Battery Safety and Handling EFCOG Electrical Safety Task Group Module 9

09/06/07 EFCOG Electrical Safety Task Group

8

Electrical Safety Precautions Never touch both battery terminals with

your bare hands at the same time!Remove rings, watches and dangling

jewelry when working with or near batteries. The metal in the jewelry can cause a shock or burn if they contact the battery terminals.

Only use insulated/non-conducting tools to remove cell caps. Never lay tools or other metal parts on top of a battery.

Page 9: Battery Safety and Handling EFCOG Electrical Safety Task Group Module 9

09/06/07 EFCOG Electrical Safety Task Group

9

Electrical Safety Precautions Consider covering battery terminals and

connectors if possible with an insulating blanket before overhead inspections or repairs

Ensure charger is turned off before connecting or disconnecting a battery to prevent arcing

Page 10: Battery Safety and Handling EFCOG Electrical Safety Task Group Module 9

09/06/07 EFCOG Electrical Safety Task Group

10

Electrical Hazard• DOE Event-Worker lost

control of a jumper wire while working above battery bank

• Ends of jumper were not insulated and blanket was not installed over battery terminals

• Event resulted in severe arcing and potential for injury to worker

Page 11: Battery Safety and Handling EFCOG Electrical Safety Task Group Module 9

09/06/07 EFCOG Electrical Safety Task Group

11

Fire and Explosion Precautions Do not smoke in battery charging areas. Prevent open flames, sparks or electric arcs in

battery charging areas. Do not strike the sides of the battery with any

spark producing item. Keep tools and other metallic objects away from

uncovered batteries. Have an ABC dry chemical fire extinguisher in

charging areas or readily available.

Page 12: Battery Safety and Handling EFCOG Electrical Safety Task Group Module 9

09/06/07 EFCOG Electrical Safety Task Group

12

Fire and Explosion Precautions Neutralize static buildup just before working on

battery by contacting nearest grounded surface

Ensure battery area ventilation is operating prior to working on

Page 13: Battery Safety and Handling EFCOG Electrical Safety Task Group Module 9

09/06/07 EFCOG Electrical Safety Task Group

13

Battery Explosions• DOE Event-This

starting battery exploded during a load test for a diesel generator

• Explosion can expel debris and battery acid resulting in burns and injury to nearby personnel

Page 14: Battery Safety and Handling EFCOG Electrical Safety Task Group Module 9

09/06/07 EFCOG Electrical Safety Task Group

14

Handling Battery Acid• Use extreme caution when handling electrolyte and keep

an acid neutralizing solution—such as baking soda readily available

• Always wear proper eye, face and hand protection.

• Use non-metallic containers to handle liquid

• If the electrolyte is splashed into an eye, immediately force the eye open and flood it with clean, cool water for at least 15 minutes. Get prompt medical attention.

Page 15: Battery Safety and Handling EFCOG Electrical Safety Task Group Module 9

09/06/07 EFCOG Electrical Safety Task Group

15

Handling Battery Acid• If electrolyte is taken internally, drink large quantities of

water or milk. DO NOT induce vomiting. Call a physician immediately.

• Neutralize with baking soda any electrolyte that spills on a vehicle or in the work area. After neutralizing, rinse contaminated area clean with water.

• To prepare electrolyte of a desired specific gravity, always pour the concentrated acid slowly into the water; DO NOT pour water into the acid. Always stir the water while adding small amounts of acid. If noticeable heat develops, allow the solution to cool before continuing to add acid.

Page 16: Battery Safety and Handling EFCOG Electrical Safety Task Group Module 9

09/06/07 EFCOG Electrical Safety Task Group

16

Changing Batteries

Industrial batteries used to power mobile equipment can weight upwards of 1,500 lbs.

Ensure the battery is securely locked in place prior to pulling away from the battery changing area.

Do not attempt to stop a battery if it slides out of the equipment.

Page 17: Battery Safety and Handling EFCOG Electrical Safety Task Group Module 9

09/06/07 EFCOG Electrical Safety Task Group

17

Changing Batteries

Work on Batteries requires Non-Sparking and Insulated tools. Insulation must be listed for the voltage present Taped wrenches are not listed

Batteries should never be lifted by the post.

Page 18: Battery Safety and Handling EFCOG Electrical Safety Task Group Module 9

09/06/07 EFCOG Electrical Safety Task Group

18

Safe Handling of Batteries

Use appropriate equipment to load/unload batteries from mobile equipment.

Ensure you are trained in using the loading equipment.

Keep tools and other metallic objects away from uncovered batteries.

Use Baking Soda or cleaning agent specified in AHA to neutralize spilled acid.

Page 19: Battery Safety and Handling EFCOG Electrical Safety Task Group Module 9

09/06/07 EFCOG Electrical Safety Task Group

19

Jumping a Discharged Vehicle Battery

• When jump starting a vehicle, always wear proper eye protection and never lean over battery.

• Inspect both batteries before connecting booster cables. Do not jump start a damaged battery.

• Be sure vent caps are tight and level.

• Make certain that the vehicles are not touching and both ignition switches are turned to the OFF position.

• Refer to the vehicle owners' manual for other specific information.

Page 20: Battery Safety and Handling EFCOG Electrical Safety Task Group Module 9

09/06/07 EFCOG Electrical Safety Task Group

20

Jumping a Battery

Page 21: Battery Safety and Handling EFCOG Electrical Safety Task Group Module 9

09/06/07 EFCOG Electrical Safety Task Group

21

Battery Jumping Sequence• Connect positive (+) booster cable to positive (+) terminal

of discharged battery.

• Connect other end of positive (+) cable to positive (+) terminal of assisting battery.

• Connect negative (-) cable to negative (-) terminal of assisting battery.

• MAKE FINAL CONNECTION OF NEGATIVE (-) CABLE TO ENGINE BLOCK OF STALLED VEHICLE, AWAY FROM BATTERY.

• Start vehicle and remove cables in REVERSE order of connections.

Page 22: Battery Safety and Handling EFCOG Electrical Safety Task Group Module 9

09/06/07 EFCOG Electrical Safety Task Group

22

PROTECTIVE CLOTHING General Requirements for Handling

For general handling of batteries with terminal post taped

PPE Requirements:• As specified in

local AHA or procedure

Page 23: Battery Safety and Handling EFCOG Electrical Safety Task Group Module 9

09/06/07 EFCOG Electrical Safety Task Group

23

PROTECTIVE CLOTHING Requirements for Electrolyte Handling

PPE Requirements:• Safety Glasses/goggles• Rubber Gloves• Face Shield• Chemical Apron• Boots

Page 24: Battery Safety and Handling EFCOG Electrical Safety Task Group Module 9

09/06/07 EFCOG Electrical Safety Task Group

24

Safety Eye Wash & Shower Requirements

•An eyewash facility should be capable of flushing both eyes simultaneously for fifteen minutes and a water hose or safety shower that, if portable, is capable of drenching the body. •Eyewash and drenching facilities are to be located as close to the point of exposure as possible of battery handling areas (not to exceed 25 ft.) (OSHA)

•If Acid comes in contact with eyes, flush for 15 minutes and report to medical immediately.• If acid comes in contact with skin or clothing, rinse off for several minutes and try not to spread the electrolyte. Report to medical after rinsing.

Note: Eyewash and drenching facilities are not required for non-vented batteries.

Page 25: Battery Safety and Handling EFCOG Electrical Safety Task Group Module 9

09/06/07 EFCOG Electrical Safety Task Group

25

Battery Safety

Know the HazardsUse the required

PPENo Open Flame