Basics of Instrumentation & Control systems
in a TPS
![Page 2: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/2.jpg)
Role of Instrumentation & ControlCase-I
To generate 210 MW we have to introduce steam of 640 TPH at 130 Kg/cm2 and 540 oC
4% of oxygen in the flue gas indicates proper combustion
Furnace pressure shall be maintained at
-10 mmWcl Water level in the drum shall be maintained to
ensure flow of water through boiler tubes
![Page 3: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/3.jpg)
Role of Instrumentation & ControlCase-II
Consider Boiler Feed Pump
To Start the BFP Suction pressure should be adequate Suction valve fully open Recirculation valve fully open Lube oil pressure should be adequate
![Page 4: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/4.jpg)
During Pump Run
Start AOP, if Lube oil pressure falls below 1.5 Kg/cm2
Stop AOP, if Lobe oil pressure reaches 3.5 Kg/cm2
Close the Recirculation valve if the suction flow is >220 TPH
Open the Recirculation valve if suction flow is < 110 TPH
![Page 5: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/5.jpg)
BFP should be Tripped if
Suction pressure < 2.5 Kg/cm2
Discharge pressure < 40 Kg/cm2
Lube oil pressure < 0.8 Kg/cm2
Working oil temperature > 130oC Motor bearing temperature > 80oC Discharge water temperature > 175oC Deaerator level < 1520 mm
![Page 6: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/6.jpg)
Role of Instrumentation & ControlCase-III
Drum Level Super heated steam temperature Main steam pressure Deaerator level control Reheated steam temperature Furnace pressure Mill outlet temperature Oxygen percentage in the flue gas Hotwell level Heater levels
![Page 7: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/7.jpg)
Role of Instrumentation & Controls
Monitoring the parameters Permissives and Interlocks & Protections Controlling the Parameters
![Page 8: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/8.jpg)
MonitoringMost common parameters that are to be
monitored are PressureTemperature LevelFlow
Local Remote
![Page 9: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/9.jpg)
Local Monitoring
Pressure - Gauges
Temperature - Gauges
Level - Gauge glass
Flow - Flow meter
![Page 10: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/10.jpg)
Pressure Gauge
Bourdon Type
![Page 11: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/11.jpg)
Pressure Gauge
Bourdon Type
![Page 12: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/12.jpg)
Temperature Gauge
Mercury Gauge
![Page 13: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/13.jpg)
Gauge Glass
See through glass
![Page 14: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/14.jpg)
Remote
Pressure/Flow/Level
- Transducers Temperature
- Thermocouple, RTD
![Page 15: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/15.jpg)
Transducer
-Converts quantity of physical variable from one form to another
-Pressure transducer converts quantity of process pressure in to Electrical quantity
-Voltage Transducer (0-5, 0-10, 1-5 etc.,)
-Current TransducerTransmitter=Transduce + Transmit
![Page 16: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/16.jpg)
Pressure Transmitter
-4-wire system of measurement
-2-wire system of measurement
-True Zero (0-20 mA) measurement
-Live Zero (4-20 mA) measurement
![Page 17: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/17.jpg)
4-wire Transmitter (0-20/4-20 mA)
+ Tx-
Load Control / Monitoring mA
Wiring schematic of 4-wireTransmitter
+24 V DC
-Ve
![Page 18: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/18.jpg)
2-wire Transmitter (4-20 mA)
+ Tx
-Load
Control / Monitoring
4-20 mA
Wiring schematic of 2-wireTransmitter
+24 V DC
-Ve
- Tx drives constant current up to a Load of 600 Ω
![Page 19: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/19.jpg)
Transmitter Power supply Vs Load
400 600 800 1000 1200
40
30
20
![Page 20: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/20.jpg)
Transmitter
- Capacitance based
![Page 21: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/21.jpg)
Thermocouple- Junction of two dissimilar metals in contact, produce voltage
between the two (unjoined) wire ends
- Any pair of dissimilar metals will produce a measurable voltage when their junction is heated
![Page 22: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/22.jpg)
Voltage is directly proportional to the temperature difference between joined and open ends
Commonly used thermocouples generate
5 µV/oC to 50 µV/oC Relationship between temperature and
voltage is very much Non-linear
Thermocouple
![Page 23: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/23.jpg)
![Page 24: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/24.jpg)
CJC – Cold Junction Compensation
![Page 25: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/25.jpg)
Selection of Thermocouple
Which combination gives more µV/oC Which combination gives better linear
relationship between voltage and temperature
![Page 26: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/26.jpg)
Thermocouple Temp Vs volt
![Page 27: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/27.jpg)
K-Type Thermocouple K type thermocouple has 41 µV/oC
Chromel (Nickel-Chromium alloy) Alumel(Ni-aluminium alloy)
It can measure in the range of -200 to +1200oC
![Page 28: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/28.jpg)
RTD – Resistance Temperature Detector
Electrical resistance of metals changing with temperature
temperature coefficient of metals is of the order - 0.003 to 0.007 ohms/ohm/°C
Most common metals used are
platinum (Pt-100), nickel, copper and molybdenum
![Page 29: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/29.jpg)
![Page 30: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/30.jpg)
2-wire configuration
Wheatstone Bridge
employed to measure
the RTD resistance Lead Resistance causes
error in the
measurement
![Page 31: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/31.jpg)
3-wire configuration
![Page 32: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/32.jpg)
Flow Measurement
Steam Flow
P1 P2
DP across orifice = P1-P2
![Page 33: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/33.jpg)
Level measurement
P1
P2
![Page 34: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/34.jpg)
DP Transmitter
![Page 35: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/35.jpg)
CONTROL SYSTEMS
![Page 36: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/36.jpg)
Control systems
Control systemControl system
Open Loop ControlOpen Loop Control Closed Loop ControlClosed Loop Control
Concentrated controlConcentrated control Distributed controlDistributed control
Distributed Analog
controlDistributed Analog
control
Distributed Digital
Control (DCS)Distributed Digital
Control (DCS)
![Page 37: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/37.jpg)
Open Loop control system
SYSTEMInput Output
![Page 38: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/38.jpg)
Closed Loop Control system
CONTROLLER Final control element
Measurement system
Setpoint
Feedback path
Output
![Page 39: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/39.jpg)
PID controller
Proportional controllerController output α Error
= Kp * e(t)
Where, Kp =Proportional Gain
![Page 40: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/40.jpg)
PID controller
Integral controllerController output α ∫ e(t) dt
= Ki ∫ e(t) dt
Where, Ki = Integral time constant
![Page 41: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/41.jpg)
PID controller
Derivative controllerController output α de(t)/dt
= Kd de(t)/dt
Where, Kd = Derivative time constant
![Page 42: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/42.jpg)
PID controller
![Page 43: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/43.jpg)
![Page 44: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/44.jpg)
DCS Features Single Input can be utilized for monitoring/I&P/Control Modifications in the I&P/control can be done easily in
software Redundancy Isolated Input / Output modules Remove and insert modules while powered Data Highway speed is 10/100 Mbps Centralized Engineering Station for programming,
configuration Point database (Global Data) accessible at any station
across the Network Facility for simulation of control logic schemes with
virtual processor
![Page 45: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/45.jpg)
Points to Remember Monitoring Permissives and Interlocks & Protections Controlling Local and Remote monitoring Current transducers/Live-zero system (4-20 mA)/2-wire Thermocouples require Cold junction
compensation 3-wire configuration of RTDs eliminate error due
to lead wires resistance Distributed control system
![Page 46: Basics of I&C](https://reader030.fdocuments.net/reader030/viewer/2022020714/544cb1d2b1af9fca498b4855/html5/thumbnails/46.jpg)