Basic Motor Drive Fire Pump Controller Functions

9
- for - F.M. Approvals - by - James S. Nasby Columbia Engineering Motor Drive Controller Functions and Operation

description

Basic Functions, Features and Options of Electric Motor Driven Fire Pump Controllers

Transcript of Basic Motor Drive Fire Pump Controller Functions

Page 1: Basic Motor Drive Fire Pump Controller Functions

- for -

F.M. Approvals- by -

James S. Nasby

Columbia Engineering

Motor Drive Controller Functions and Operation

Page 2: Basic Motor Drive Fire Pump Controller Functions

C.E. F.M. Approvals 2

Topics Covered Type of Controller

Manual Combined Automatic

Measurement Timing Remote Functions

Page 3: Basic Motor Drive Fire Pump Controller Functions

C.E. F.M. Approvals 3

Type of Controller Manual Only Controller

Peerless "Mantrol" was U.L. Listed Most F.P. Engine Panels do this

Automatic Controller Must be both A Manual Controller -and- An Automatic Controller

Page 4: Basic Motor Drive Fire Pump Controller Functions

C.E. F.M. Approvals 4

Timing Cranking Delayed Starting: Which Demands?

Sequence Start: Static Demands• Pressure (Weekly Test)• Deluge• A.C. PF Start

Don’t Delay• Remote Momentary Switch (Push Button)

High Zone Start - Which Demands Static Demands -and- Remote Momentary (Don't Want to Start a Dry or

Cavitating Pump)

Page 5: Basic Motor Drive Fire Pump Controller Functions

C.E. F.M. Approvals 5

Non-Standard Functions Start Timing

Sequential (Parallel Pumps)• Which Demands are Delayed?

High Zone Delay (Pumps in Series)• Which Demands are Delayed?

Lockout - When OK?

Page 6: Basic Motor Drive Fire Pump Controller Functions

C.E. F.M. Approvals 6

Additional Functions Breaker Test Switch Re-Start Delay Avoids Re-closing Contactor with Motor

Back EMF present Will almost Always be Out of Phase 3/4 to 1-1/2 Seconds "Open Circuit Magnetic Time Constant"

for Induction Motors. Delay of 2 to 3 Seconds = One or More Time Constants (63%

Drop) to Safe Levels Single Phase Protection Shunt Trip

A.C. Powered = 1/3 Odds of Tripping D.C. Powered = Better Odds Triple Redundant CPTs & D.C. Powered = Best Odds of

Tripping.

Page 7: Basic Motor Drive Fire Pump Controller Functions

C.E. F.M. Approvals 7

A Very Large Military SiteVariable Speed Motor, Engine and Jockey Pump

Page 8: Basic Motor Drive Fire Pump Controller Functions

C.E. F.M. Approvals 8

Voltage Margins Low Line Performance

During Motor Starting (Weak Source)• 15% Minimum• 35% Better

Stand-by - High Line• 480 x 110% = 528*

Affect on Function Metering

*Can be Even Higher for Service Entrance Equipment due to Close Proximity to the Building Transformer which might have Taps set to Compensate for Long Wire Runs.

Page 9: Basic Motor Drive Fire Pump Controller Functions

C.E. F.M. Approvals 9