Baofeng Substatiaon 220kV Bus Coupler Circuit Breaker Box to Operate Closed Loop Body Transformation
CHEN Zong-yan, DUAN Li-wei, GUO Zhong-liang
( Henan Pingdingshan Power Supply Co., Pingdingshan 467001,China; ) pds6yfgs@163.com
Abstract:220kV line protection agencies for me to operate closed-loop problem of the aging, operation of microprocessor-based protection combined with me now more reliable performance. Now take full advantage of the reliability of microprocessor-based protection devices can, circuit breaker will be closed to protect from the original single-loop combination locking relay, Now replaced by the use of closed-loop operation box, To improve the reliability of the circuit, Ensure the normal operation of microprocessor-based protection。
:Closed-loop operation;Operation box;Relay;Security;Reliability;
宝丰变 220kV 母联断路器机构箱操作闭锁回路改造
陈宗彦 段利伟 郭仲亮
(河南平顶山供电公司,河南 平顶山 467001)
pds6yfgs@163.com 【摘要】针对 220kV 线路保护机构箱操作闭锁回路老化的情况,结合现在微机保护操作箱性能比较可 靠,充分利用了现在微机保护装置的可靠性能,将线路断路器保护闭锁回路由原来的单只继电器组合 闭锁,改为现在的利用操作箱回路闭锁,提高了回路的可靠性,保证了微机保护的正常运行。
【关键词】操作闭锁回路;操作箱;继电器;安全性;可靠性
1.引言
随着新技术的不断发展,越来越多的新技术应用
于微机继电保护装置中,在原来的断路器机构操作闭
锁回路的设计中,通常用三只(VE、VD、VG)或五只
(VE、VD、VG、VD1、VD2)继电器组合,用于监视断
路器液压的情况,在压力降低的情况下,闭锁分、合
闸操作回路。这几只继电器通常安装在室外端子箱内,
由于室外环境受季节和天气影响,运行条件十分恶劣,
造成继电器老化快,其塑料框架破损破裂,接点严重氧
化,且在保护定检的过程中,容易被忽视遗忘,这些
回路又是最重要的操作回路,存在着很大的安全隐患,
因此用室内新元件替代继电器闭锁回路成为综自改造
过程中最重要的一个环节。
2 操作回路安全问题的发现
2008 年 10 月,在对宝丰变 220kV 母联保护进行综自
改造过程中,拆除原 22 旁保护,启用了充电保护装置
上的机构操作箱作为 220 断路器保护的操作箱,在施
工中发现操作闭锁回路中原来的几只单只继电器严重
老化,其塑料框架破损破裂,接点氧化严重,针对现场
具体情况,对 220kV 母联机构箱二次回路进行大胆创
新改造,并对出现的问题进行处理。
2 操作回路原设计方法
设计部门在二次回路设计中,通常采用的 3 只扩展闭
锁继电器(VE、VD、VG),如图 1 所示。
考虑到室外继电器受外界气候影响,运行条件十
分恶劣,现有 3 只扩展闭锁继电器外壳已经严重老化
易碎,接点氧化腐蚀严重,且室外继电器在定检工作
中容易被遗忘,造成事故隐患。针对以上存在的实际
情况,我们大胆创新,拆除原有的 3 只扩展闭锁继电
器(即 VE、VD、VG),改用线路微机保护操作箱的闭
锁回路。
3 创新改造后的微机闭锁回路
改造后,原来的液压降低闭锁合闸级液压降低闭锁分
闸正电位闭锁改成与操作箱相适应的负电位闭锁回
路,并保留 SF6 气体压力降低正电位禁止操作回路。
(如图 2中椭圆圈中的部分所示)
4 SF6 降低后闭锁回路的改进建议
16
Information and Communication Technology and Smart Grid
978-1-935068-23-5 © 2010 SciRes.
mailto:pds6yfgs@163.com mailto:pds6yfgs@163.com
HE Jia - li. Principle of Relay Protection (Third Edition) [M].
图 1 操作回路原设计
Figure1. original design of circuit operation
图 2 改进后的微机闭锁回路
Figure 2, the improved microprocessor lockout circuit
改进建议:为防止传动闭锁回路时造成短路,建
议厂家将闭锁回路均改为正电位闭锁或者均为负电位
闭锁,以便于传动和运行中的临时故障处理。(如图 3
所示)
图 3 SF6 降低后的闭锁回路(改进建议)
Figure3. SF6 circuit closed after the reduction (improvement suggestions)
5 结束语
该项技术改造改善了二次设备运行条件,完善了
二次操作回路,解除了事故隐患,现已投入运行,状
态良好,为电力系统安全可靠运行创造了可靠的保障,
具有良好的经济价值和社会价值。
[1] NARI-RELAYS Electric Co., Ltd. CZX-12R1-based relay device technical manual operation
南瑞继保电气有限公司,CZX-12R1 型操作继电器装置技术说
明书。 [2] National Power Dispatching and Communication Center.
“Questions and answers Practical Power System Protection” .Beijing: China Electric Power Press.2000.
国家电力调度通信中心,《电力系统继电保护实用技术问答》,
北京:中国电力出版社,2000.
[3] Henan Power Company. “The inspection of relay protection and automatic safety device”. Henan: Henan People's Publishing House.2008.
河南省电力公司,《继电保护及安全自动装置检验规程》,河
南:河南人民出版社,2008.
[4] National Power Dispatching and Communication Center. “Power System Protection provides compilation” (2d ed)[M],Beijing: China Electric Power Press.2000.5.
国家电力调度通信中心.《电力系统继电保护规定汇编》(第
二版)[M],北京:中国电力出版社,2000.5
[5]
贺家李.电力系统继电保护原理(第三版)[M],北京:中国
电力出版社,1994.10
[6]
毛锦庆.电力系统继电保护规定汇编(第二版)[M],北京:
中国电力出版社,2000.5
17
Information and Communication Technology and Smart Grid
978-1-935068-23-5 © 2010 SciRes.
References(参考文献)
Beijing: China Electric Power Press.1994.10
MAO Jin-qing. Power System Protection provides compilation
(Second Edition)[M]. Beijing: China Electric Power Press.2000.5