Bank of Zambia, Excutive Building, Lusaka Proposed Air ......Model PLFY-P50VBM-E or equal and...

28
Bank of Zambia, Excutive Building, Lusaka Proposed Air Conditioning and Ventilation Services Item Description Unit Qty. Rate Amount K BILL No. 1 PRELIMINARY AND GENERAL ITEMS PRELIMINARIES & GENERAL The Tenderer is to allow for all Contract Preliminaries detailed in Section 3 of the Contract documents and which he considers necessary to comply with all his obligations mentioned therein including access to site, general attendance, security of works, materials, tools and equipment, supervision and labour, insurances, possession and completion of works, variations, fluctuations, terms of payment, antiquities & arbitration Item Testing and commissioning Item 3 Sets Operation and Maintenance Manuals Item Handover Item 4 year maintenance Item One year guarantee Item The Tenderer is advised that should he require to insert prices for any items not specifically included in this section or any other section of this Bill of Quantities and which he considers necessary in order to comply with all his obligations under the Contract Documents, He shall insert the prices in the amount column Item Contractor should take note that the installations shall be done in stages floor per floor, i.e, not all floors at once CARRIED TO SUMMARY OF BILLS OF QUANTITIES North Atlantic Engineering Consultants Lusaka, Zambia 1

Transcript of Bank of Zambia, Excutive Building, Lusaka Proposed Air ......Model PLFY-P50VBM-E or equal and...

  • Bank of Zambia, Excutive Building, Lusaka Proposed Air Conditioning and Ventilation Services

    Item Description Unit Qty. Rate Amount

    K

    BILL No. 1

    PRELIMINARY AND GENERAL ITEMS

    PRELIMINARIES & GENERAL

    The Tenderer is to allow for all Contract Preliminaries

    detailed in Section 3 of the Contract documents and

    which he considers necessary to comply with all his

    obligations mentioned therein including access to site,

    general attendance, security of works, materials, tools

    and equipment, supervision and labour, insurances,

    possession and completion of works, variations,

    fluctuations, terms of payment, antiquities & arbitration Item

    Testing and commissioning Item

    3 Sets Operation and Maintenance Manuals Item

    Handover Item

    4 year maintenance Item

    One year guarantee Item

    The Tenderer is advised that should he require to insert

    prices for any items not specifically included in this

    section or any other section of this Bill of Quantities and

    which he considers necessary in order to comply with all

    his obligations under the Contract Documents, He shall

    insert the prices in the amount column Item

    Contractor should take note that the installations shall

    be done in stages floor per floor, i.e, not all floors at

    once

    CARRIED TO SUMMARY OF BILLS OF QUANTITIES

    North Atlantic Engineering Consultants

    Lusaka, Zambia 1

  • Bank of Zambia, Excutive Building, Lusaka Proposed Air Conditioning and Ventilation Services

    Item Description Unit Qty. Rate Amount

    K

    BILL No. 2

    2.0.0 FIRST FLOOR SERVICES

    2.1.0 AIR CONDITIOINING SERVICES

    Specified Air-conditioning units

    Mitsubishi City Multi Y Series' Multiple air-cooled split

    Type air-conditioning units with occupancy sesors accessory

    of the following types and capacities or equal and approved:

    Note

    Refrigerant shall be R410A.

    2.1.1 Indoor Units

    2.1.2 Mitsubishi Multi-Split Ceiling Cassette No. 2

    Model PLFY-P32VCM-E or equal and approved

    Capacity: 12,300 Btu/hr (Cooling); 13,600 Btu/hr (Heating)

    2.1.3 Mitsubishi Multi-Split Ceiling Cassette No. 8

    Model PLFY-P63VBM-E or equal and approved

    Capacity: 24,200 Btu/hr (Cooling); 24,300 Btu/hr (Heating)

    2.1.4 Mitsubishi Multi-Split Ceiling Cassette No. 4

    Model PLFY-P50VBM-E or equal and approved

    Capacity: 19,100 Btu/hr (Cooling); 21,500 Btu/hr (Heating)

    2.1.5 Mitsubishi Multi-Split Ceiling Cassette No. 2

    Model PLFY-P40VBM-E or equal and approved

    Capacity: 15,400 Btu/hr (Cooling); 17,100 Btu/hr (Heating)

    2.1.6 Mitsubishi Multi-Split Ceiling Cassette No. 1

    Model PLFY-P25VCM-E or equal and approved

    Capacity: 9,600 Btu/hr (Cooling); 10,900 Btu/hr (Heating)

    2.1.7 Mitsubishi Multi-Split Ceiling Cassette No. 6

    Model PCFY-P125VGM-E or equal and approved

    Capacity: 47,800 Btu/hr (Cooling); 54,600 Btu/hr (Heating)

    2.1.8 Multi-Split Hideaway as 'Mitsubishi' No. 2

    Model PEFFY-P40VMM-E or equal and approved

    Capacity: 30,700 Btu/hr (Cooling); 34,100 Btu/hr (Heating)

    2.1.9 Outdoor Unit

    2.1.10 Mitsubishi PUHY-P950YSHM-A or equal and approved

    including filter dryer and shunt-off valve.

    Capacity:385,600 Btu/hr (Cooling);433,300 Btu/hr (Heating) No. 1

    2.1.11 Mitsubishi PUHY-P700YSHM-A or equal and approved

    including filter dryer and shunt-off valve.

    Capacity:273,000 Btu/hr (Cooling);300,300 Btu/hr (Heating) No. 1

    2.1.12 Allow for construction of concrete plinth and erection of the

    I-Section beams to support the outdoor unit item

    2.1.13 Air Conditioning Accessories

    2.1.14 200mm Dia. Flexible duct m 40

    2.1.15 935 x 550 mm Return Air Grilles as 'Europair'; type ECA

    with OBD Baked Enamel White No. 2

    CARRIED TO COLLECTION PAGE

    North Atlantic Engineering Consultants

    Lusaka, Zambia 2

  • Bank of Zambia, Excutive Building, Lusaka Proposed Air Conditioning and Ventilation Services

    Item Description Unit Qty. Rate Amount

    K

    2.1.16 Allow for trunking to cover exposed refigerant pipes from item

    hideaway air conditoning units

    2.1.17 Refrigerant Piping (including all fittings and insulation

    on Tray)

    2.1.18 Allow for installation of refrigerant suction and discharge item

    pipes

    2.1.19 Dia. 32mm Condensate Drain pipe in insulation and fittings m 56

    2.1.20 Dia. 50mm Condensate Drain pipe in insulation and fittings m 45

    2.1.21 Include drilling through wall for condensate drain pipes Item

    2.1.22 Junction Pipe Kits

    2.1.23 Allow for the supply and installation of joint kits item

    2.1.24 Controllers

    2.1.25 PAR-F27MEA-E Local Wired Remote Controller No. 25

    (Including chiseling, plastering and painting)

    2.1.26 PAC-SF44SRA System Remote Controller No. 1

    2.1.27 Existing Airconditioners

    2.1.28 Include for removal and handover to client, of existing

    wall mounted type air-conditioner in the server room Item

    2.1.29 Include for Sealing of openings in walls for existing

    wall mounted type air-conditioners (to include plastering and

    painting matching the existing wall finish) Item

    2.1.30 Allow for removal and handover to Client of the existing

    air conditioning piping in the Floor Void. Item

    2.2.1 VENTILATION SERVICES

    Supply and install the following equipment as recommended

    by the manufacturer's manuals and instructions:

    2.2.2 Wall/Window mounted Extract Fan as 'Expelair' GX9

    or equal and approved

    Extract Performance: 728m3/hr

    Power Source: 220V/1Phase/50Hz

    Power Consumption : 60 Watts No. 5

    2.2.3 Wall/Window mounted Extract Fan as 'Expelair' GX12

    or equal and approved

    Extract Performance: 1614m3/hr

    Power Source: 220V/1Phase/50Hz

    Power Consumption : 60 Watts No. 1

    2.2.4 600 x 600mm Fresh Air Grilles 'Europair'; Type ECA-Egg

    Crate; Enamel White Complete with opposed blade dampers No. 9

    2.2.5 Constant Ceiling Diffuser as manufactured by 'Europair'

    Steel; White;Dimensions 595mm x 595mm

    Neck Diameter: 200mm No 2

    CARRIED TO COLLECTION PAGE

    North Atlantic Engineering Consultants

    Lusaka, Zambia 3

  • Bank of Zambia, Excutive Building, Lusaka Proposed Air Conditioning and Ventilation Services

    Item Description Unit Qty. Rate Amount

    K

    3.2.8 Xpelair Raper STOF roof fan model: STOF-500HEC-302-0

    or equal and approved:

    Extract Performance: 9216 cubic metre per second

    Power Source: 380V/3phase/50Hz

    Power Consumption : 1.96 Kw No. 1

    3.2.9 Xpelair Raper STOF roof fan model: STOF-400HAC-302-0

    or equal and approved:

    Extract Performance: 2340 cubic metre per second

    Power Source: 380V/3phase/50Hz

    Power Consumption : 0.515 Kw No. 1

    3.2.10 Allow for electrical cabling to indoor and outdoor units for the

    entire first floor item

    3.2.11 Allow for the replacement of damaged ceiling portions to

    match the existing ceiling item

    3.2.12 1000x900mm 0.6mm thick GI Duct m 6

    3.2.13 1000x900mm wire Mesh No. 1

    3.3.0 ELECTRICAL SERVICES

    3.3.15A Surface Mounted Single Socket Outlet for AC Indoor Units

    Power Points No. 22

    3.3.25A Flush Mounted Single Socket Outlet for AC Indoor Units

    Power Points No. 6

    3.3.313A Surface Mounted Single Socket Outlet for Extract Fans

    Power Points No. 5

    3.3.4 40A SP Weatherproof Industrial Isolator No. 3

    3.3.5 Electrical Distribution Board Complete with the following: No. 1

    50A TP MCB No. 1

    40A SP MCB No. 3

    10A SP MCB No. 2

    6A SP MCB No. 30

    10kA Surge Arrestors No. 3

    Neutral Bar Item 1

    Earth Bar Item 1

    3.3.6 10mm.sq 4-Core PVC/SWA Armoured Cable M 25

    3.3.7 6mm.sq Bare Core Earth Wire Cable M 25

    3.3.8

    Supply and installation of power points for Extract Fans

    complete with 2.5mm.sq PVC/SWA armoued cable + Earth,

    draw boxes, conduiting and all associated installation

    accessories

    No. 5

    3.3.9

    Supply and installation of power points for AC Indoor Units

    complete with 2.5mm.sq PVC/SWA armoued cable + Earth,

    draw boxes, conduiting and all associated installation

    accessories

    No. 22

    3.3.10

    Supply and installation of power points for AC Outdoor Units

    complete with 6.0mm.sq PVC/SWA armoued cable + Earth,

    draw boxes, conduiting and all associated installation

    accessories

    No. 3

    CARRIED TO COLLECTION PAGE

    North Atlantic Engineering Consultants

    Lusaka, Zambia 4

  • Bank of Zambia, Excutive Building, Lusaka Proposed Air Conditioning and Ventilation Services

    Item Description Unit Qty. Rate Amount

    K

    BILL No. 2

    FIRST FLOOR SERVICES

    COLLECTION PAGE

    Page 2

    Page 3

    Page 4

    CARRIED TO SUMMARY OF BILLS OF QUANTITIES

    North Atlantic Engineering Consultants

    Lusaka, Zambia 5

  • Bank of Zambia, Excutive Building, Lusaka Proposed Air Conditioning and Ventilation Services

    Item Description Unit Qty. Rate Amount

    K

    BILL No. 3

    3.0.0 SECOND FLOOR SERVICES

    3.1.0 AIR CONDITIONING SERVICES

    3.1.1 Specified Air-conditioning units

    Mitsubishi City Multi Y Series' Multiple air-cooled split

    Type air-conditioning units with occupancy sesors accessory

    of the following types and capacities or equal and approved:

    Note

    Refrigerant shall be R410A.

    3.1.2 Indoor Units

    3.1.3 Mitsubishi Multi-split Ceiling cassette, No. 12

    Model PLFY-P63VBM-E or equal and approved

    Capacity: 24,200 Btu/hr (Cooling); 24,300 Btu/hr (Heating)

    3.1.4 Mitsubishi Multi-split Ceiling cassette, No. 7

    Model PLFY-P50VBM-E or equal and approved

    Capacity: 19,100 Btu/hr (Cooling); 21,500 Btu/hr (Heating)

    3.1.5 Mitsubishi Multi-split Ceiling cassette, No. 2

    Model PLFY-P40VCM-E or equal and approved

    Capacity: 15,400 Btu/hr (Cooling); 17,100 Btu/hr (Heating)

    3.1.6 Mitsubishi Multi-split Ceiling cassette, No. 4

    Model PLFY-P25VCM-E or equal and approved

    Capacity: 9,600 Btu/hr (Cooling); 10,900 Btu/hr (Heating)

    3.1.7 Outdoor Unit

    3.1.8 Mitsubishi PUHY-P550YSHM-A or and approved including

    filter dryer and shunt-off valve.

    Capacity: 215,000 Btu/hr (Cooling); 235,400 Btu/hr (Heating) No. 1

    3.1.9 Mitsubishi PUHY-P600YSHM-A or and approved including

    filter dryer and shunt-off valve.

    Capacity: 235,000 Btu/hr (Cooling); 261,000 Btu/hr (Heating) No. 1

    3.1.10 Allow for construction of concrete plinth and erection of the

    I-Section beams to support the outdoor unit item

    3.1.11 Single Split Air Conditioning Units

    3.1.12 Single split air conditioninng unit as 'Samsung' No. 2

    Model AC100FB4DEH

    Capacity: 34,100 Btu/hr (Cooling); 38,200 Btu/hr (Heating)

    Max. Lenghth (Outdoor to Indoor): 50m (55m)

    Max. Lenghth (between outdoor to Indoor): 30m (30m)

    3.1.13 Single split air conditioninng unit as 'Samsung' No. 1

    Model AC052FBNDEH

    Capacity: 17,100 Btu/hr (Cooling); 20,500 Btu/hr (Heating)

    Max. Lenghth (Outdoor to Indoor): 30m (35m)

    Max. Lenghth (between outdoor to Indoor): 30m (30m)

    CARRIED TO COLLECTION PAGE

    North Atlantic Engineering Consultants

    Lusaka, Zambia 6

  • Bank of Zambia, Excutive Building, Lusaka Proposed Air Conditioning and Ventilation Services

    Item Description Unit Qty. Rate Amount

    K

    3.1.14 Single split air conditioninng unit as 'Samsung' No. 1

    Model AC071FBNDEH

    Capacity: 23,200 Btu/hr (Cooling); 25,600 Btu/hr (Heating)

    Max. Lenghth (Outdoor to Indoor): 50m (55m)

    Max. Lenghth (between outdoor to Indoor): 30m (30m)

    3.1.15 Single split air conditioning Hideaway Unit as 'Samsung' No. 1

    Model AM140FNLDEH

    Capacity: 47,800 Btu/hr (Cooling); 54,600 Btu/hr (Heating)

    Max. Lenghth (Outdoor to Indoor): 30m (35m)

    Max. Lenghth (between outdoor to Indoor): 30m (30m)

    3.1.16 Refrigerant Piping (including all fittings and insulation

    on Tray)

    3.1.17 Allow for installation of refrigerant suction and discharge item

    pipes

    3.1.18 Dia. 32mm Condensate Drain pipe in insulation and fittings m 135

    3.1.19 Dia. 50mm Condensate Drain pipe in insulation and fittings m 20

    3.1.20 Include drilling through wall for condensate drain pipe Item

    3.1.21 Junction Pipe Kits

    3.1.22 Allow for supply and installation of joint kits Item

    3.1.23 Controllers

    3.1.24 PAR-F27MEA-E Local Wired Remote Controller No. 25

    (Including chiseling, plastering and painting)

    3.1.25 PAC-SF44SRA System Remote Controller No. 5

    3.1.26 Existing Air Conditioners

    3.1.27 Include for removal and handover to client of existing

    air conditioners Item

    3.1.28 Include for sealing of openings in walls for existing

    air conditioners (to include plastering and painting matching

    the existing wall finish) Item

    3.1.29 Allow for removal and handover to client of the existing

    air conditioning piping in the ceiling void Item

    3.1.30 Occupancy Sensors

    3.2.1 VENTILATION SERVICES

    Supply and install the following equipment as recommended

    by the manufacturer's manuals and instructions:

    3.2.2 Wall/Window Mounted Extract Fan as 'Expelair' GX6

    or equal and approved:

    Extract Performance: 250 cubic metre per hour

    Power Source: 220V/1Phase/50Hz

    Power Consumption: 40 Watts No. 1

    CARRIED TO COLLECTION PAGE

    North Atlantic Engineering Consultants

    Lusaka, Zambia 7

  • Bank of Zambia, Excutive Building, Lusaka Proposed Air Conditioning and Ventilation Services

    Item Description Unit Qty. Rate Amount

    K

    3.2.3 Wall/Window Mounted Extract Fan as 'Expelair' GX6

    or equal and approved:

    Extract Performance:728 cubic metre per hour

    Power Source: 220V/1Phase/50Hz

    Power Consumption: 60 Watts No. 5

    3.2.4 600x600mm Fresh Air Grilles 'Europar' ; type ECA-Egg

    Crate; Enamel White complete with opposed blade dampers No. 11

    3.2.5 Wall/Axial Plate Mounted Extract Fan as 'Flaxt Woods'

    H56041

    Model HIFLO 560 or equal and approved.

    Air Flow: Q = 3.17m/s

    Static Pressure: P(st) = 50pa

    Power Source: 220V/1Phase/50Hz

    Power Consumption: 1.10kW No. 1

    3.2.6 600mm x 600mm fixed weather louvre as 'FlaxtWoods'

    with Natural Anodised Aluminium No. 1

    3.2.7 Extract fan as 'Xpelair' In-Line; XID125

    Extract Performance : 375 cubic meter per hour

    Power Source : 220V/1phase/50Hz

    Power Consumption: 90 Watts No. 1

    3.2.8 Extract fan as 'Xpelair' In-Line; XID315

    Extract Performance : 1656 cubic meter per hour

    Power Source : 220V/1phase/50Hz

    Power Consumption: 244 Watts No. 1

    3.2.9 200mm Neck Diameter White Metallic Disc Valves No. 10

    3.2.10 450 x 300mm 0.6mm thick G.I Extract Air Duct m 27

    3.2.11 500 x 350mm Weather Louvre as 'Europair'

    With Natural Anodised Aluminium No. 2

    3.2.12 Constant Volume Supply Diffuser as 'Europair' 600 x 600mm No. 6

    3.2.13 700 x 300mm 0.6mm thick G.I Extract Air Duct m 24

    3.2.14 600 x 600mm Weather Louvre as 'Europair'

    With Natural Anodised Aluminium complete with filter No 1

    3.2.15 Allow for electrical cabling to indoor and outdoor units for the

    entire second floor item

    3.2.16 Allow for the replacement of damaged ceiling portions with

    same ceiling as existing item

    3.2.17 1000 x 900mm 0.6mm thick GI Duct for outdoor units m 6

    3.2.18 1000 x 900mm wire Mesh for outdoor units No. 1

    CARRIED TO COLLECTION PAGE

    North Atlantic Engineering Consultants

    Lusaka, Zambia 8

  • Bank of Zambia, Excutive Building, Lusaka Proposed Air Conditioning and Ventilation Services

    Item Description Unit Qty. Rate Amount

    K

    3.3.0 ELECTRICAL SERVICES

    3.3.15A Surface Mounted Single Socket Outlet for AC Indoor Units

    Power Points No. 29

    3.3.213A Surface Mounted Single Socket Outlet for Extract Fans

    Power Points No. 9

    3.3.3 32A SP Weatherproof Industrial Isolator No. 3

    3.3.4 Electrical Distribution Board Complete with the following: No. 1

    50A TP MCB No. 1

    30A SP MCB No. 3

    10A SP MCB No. 2

    6A SP MCB No. 30

    10kA Surge Arrestors No. 3

    Neutral Bar Item 1

    Earth Bar Item 1

    3.3.5 10mm.sq 4-Core PVC/SWA Armoured Cable M 25

    3.3.6 6mm.sq Bare Core Earth Wire Cable M 25

    3.3.7

    Supply and installation of power points for Extract Fans

    complete with 2.5mm.sq PVC/SWA armoued cable + Earth,

    draw boxes, conduiting and all associated installation

    accessories

    No. 9

    3.3.8

    Supply and installation of power points for AC Indoor Units

    complete with 2.5mm.sq PVC/SWA armoued cable + Earth,

    draw boxes, conduiting and all associated installation

    accessories

    No. 29

    3.3.9

    Supply and installation of power points for AC Outdoor Units

    complete with 4.0mm.sq PVC/SWA armoued cable + Earth,

    draw boxes, conduiting and all associated installation

    accessories

    No. 3

    CARRIED TO COLLECTION PAGE

    North Atlantic Engineering Consultants

    Lusaka, Zambia 9

  • Bank of Zambia, Excutive Building, Lusaka Proposed Air Conditioning and Ventilation Services

    Item Description Unit Qty. Rate Amount

    K

    BILL No. 3

    SECOND FLOOR SERVICES

    COLLECTION PAGE

    Page 6

    Page 7

    Page 8

    Page 9

    CARRIED TO SUMMARY OF BILLS OF QUANTITIES

    North Atlantic Engineering Consultants

    Lusaka, Zambia 10

  • Bank of Zambia, Excutive Building, Lusaka Proposed Air Conditioning and Ventilation Services

    Item Description Unit Qty. Rate Amount

    K

    BILL No. 4

    4.0.0 THIRD FLOOR SERVICES

    4.1.0 AIR CONDITIONING SERVICES

    4.1.1 Specified Air-conditioning units

    Mitsubishi City Multi Y Series' Multiple air-cooled split

    Type air-conditioning units with occupancy sesors accessory

    of the following types and capacities or equal and approved:

    Note

    Refrigerant shall be R410A.

    4.1.2 Indoor Units

    4.1.3 Mitsubishi Multi-split Ceiling cassette, No. 1

    Model PLFY-P80VBM-E or equal and approved

    Capacity: 30,700 Btu/hr (Cooling); 34,100 Btu/hr (Heating)

    4.1.4 Mitsubishi Multi-split Ceiling cassette, No. 3

    Model PLFY-P63VBM-E or equal and approved

    Capacity: 24,200 Btu/hr (Cooling); 24,300 Btu/hr (Heating)

    4.1.5 Mitsubishi Multi-split Ceiling cassette, No. 10

    Model PLFY-P50VBM-E or equal and approved

    Capacity: 19,100 Btu/hr (Cooling); 21,500 Btu/hr (Heating)

    4.1.6 Mitsubishi Multi-split Ceiling cassette, No. 5

    Model PLFY-P40VBM-E or equal and approved

    Capacity: 15,400 Btu/hr (Cooling); 17,100 Btu/hr (Heating)

    4.1.7 Mitsubishi Multi-split Ceiling cassette, No. 2

    Model PLFY-P25VCM-E or equal and approved

    Capacity: 9,600 Btu/hr (Cooling); 10,900 Btu/hr (Heating)

    4.1.8 Mitsubishi Multi-split Ceiling cassette, No. 3

    Model PLFY-P32VCM-E or equal and approved

    Capacity: 12,300 Btu/hr (Cooling); 13,600 Btu/hr (Heating)

    4.1.9 Outdoor Unit

    4.1.10 Mitsubishi PUHY-P700YSHM-A or equal and approved

    including filter dryer and shunt-off valve.

    Capacity:273,000 Btu/hr (Cooling);300,300 Btu/hr (Heating) No. 1

    4.1.11 Mitsubishi PUHY-P450YHM-A or equal and approved

    including filter dryer and shunt-off valve.

    Capacity:170,600 Btu/hr (Cooling);191,100 Btu/hr (Heating) No. 1

    4.1.12 Allow for construction of concrete plinth and erection of the

    I-Section beams to support the outdoor unit item

    4.1.13 Single Split Air Conditioning Units

    4.1.14 Single split air conditioning unit as 'Samsung' Model

    AC052FBNDEH or equal and approved:

    Capacity:17,100 Btu/hr (Cooling);20,500 Btu/hr (Heating)

    Max. Length (outdoor to indoor) : 30m (35m)

    Max. Height (between outdoor and indoor) : 30m (30m)

    Power source: 220V/1Phase/50Hz

    Power Consumption: 3.15kW No. 1

    CARRIED TO COLLECTION PAGE

    North Atlantic Engineering Consultants

    Lusaka, Zambia 11

  • Bank of Zambia, Excutive Building, Lusaka Proposed Air Conditioning and Ventilation Services

    Item Description Unit Qty. Rate Amount

    K

    4.1.15 Refrigerant Piping (including all fittings and insulation

    on Tray)

    4.1.16 Allow for installation of refrigerant suction and discharge item

    pipes

    4.1.17 Dia. 32mm Condensate Drain pipe in insulation and fittings m 56

    4.1.18 Dia. 50mm Condensate Drain pipe in insulation and fittings m 110

    4.1.19 Include drilling through wall for condesate drain pipes Item

    4.1.20 Junction Pipe Kits

    4.1.21 Allow for the supply and installation of joint kits item

    4.1.22 Controllers

    4.1.23 PAR-F27MEA-E Local Wired Remote Controller No. 24

    (Including chiseling, plastering and painting)

    4.1.24 PAC-SF44SRA System Remote Controller No. 2

    4.1.25 Existing Airconditioners

    4.1.26 Include for removal and handover to client, of existing

    air-conditioner Item

    4.1.27 Include for Sealing of openings in walls for existing

    air-conditioners (to include plastering and

    painting matching the existing wall finish) Item

    4.1.28 Allow for removal and handover to Client of the existing

    air conditioning piping in the ceiling Void. Item

    4.1.29 Occupancy Sensors

    4.2.0 VENTILATION SERVICES

    Supply and install the following equipment as recommended

    by the maufacturer's manuals and instructions:

    4.2.1 Wall/Window Mounted Extract Fan as 'Expelair' GX9

    or equal and approved:

    Extract Performance: 728m cubic meter per hour

    Power Source : 220V/1Phase/50Hz

    Power Consumption: 60 Watts No. 3

    4.2.2 600 x 600mm Fresh Air Grilles 'Europair'; type ECA- Egg

    Crate; Enamel White complete with opposed blade dampers No. 9

    4.2.3 Extract fan as 'Xpelair' In-Line; XID150

    Extract Performance : 830m cubic meter per hour

    Power Source : 220V/1phase/50Hz

    Power Consumption: 104 Watts No. 1

    4.2.4 Extract fan as 'Xpelair' In-Line; XID125

    Extract Performance : 375m cubic meter per hour

    Power Source : 220V/1phase/50Hz

    Power Consumption: 90 Watts No. 1

    4.2.5 200mm Diameter White Metallic Disc Valves No. 6

    CARRIED TO COLLECTION PAGE

    North Atlantic Engineering Consultants

    Lusaka, Zambia 12

  • Bank of Zambia, Excutive Building, Lusaka Proposed Air Conditioning and Ventilation Services

    Item Description Unit Qty. Rate Amount

    K

    4.2.6 200x200mm 0.6mm thick G.I. Extract Air Duct m 20

    4.2.7 300mm x 300mm Weather Louvre as 'Europair'

    with Natural Anodised Aluminium m 2

    4.2.8 Allow for electrical cabling to indoor and outdoor units for the

    entire Third floor item

    4.2.9 Allow for the replacement of damaged ceiling portions with

    same ceiling as existing item

    4.2.10 1000x900mm 0.6mm thick G.I Duct m 6

    4.2.11 1000x900mm Wire Mesh No. 1

    4.3.0 ELECTRICAL SERVICES

    4.3.1

    5A Surface Mounted Single Socket Outlet for AC Indoor Units

    Power Points No. 25

    4.3.2

    13A Surface Mounted Single Socket Outlet for Extract Fans

    Power Points No. 5

    4.3.3 32A SP Weatherproof Industrial Isolator No. 1

    4.3.4 Electrical Distribution Board Complete with the following: No. 1

    40A TP MCB No. 1

    30A SP MCB No. 1

    6A SP MCB No. 27

    10kA Surge Arrestors No. 3

    Neutral Bar Item 1

    Earth Bar Item 1

    4.3.5 10mm.sq 4-Core PVC/SWA Armoured Cable M 25

    4.3.6 6mm.sq Bare Core Earth Wire Cable M 25

    4.3.7

    Supply and installation of power points for Extract Fans

    complete with 2.5mm.sq PVC/SWA armoued cable + Earth,

    draw boxes, conduiting and all associated installation

    accessories

    No. 5

    4.3.8

    Supply and installation of power points for AC Indoor Units

    complete with 2.5mm.sq PVC/SWA armoued cable + Earth,

    draw boxes, conduiting and all associated installation

    accessories

    No. 25

    4.3.9

    Supply and installation of power points for AC Outdoor Units

    complete with 4.0mm.sq PVC/SWA armoued cable + Earth,

    draw boxes, conduiting and all associated installation

    accessories

    No. 1

    TOTAL AMOUNT CARRIED TO TOTAL SUMMARY

    North Atlantic Engineering Consultants

    Lusaka, Zambia 13

  • Bank of Zambia, Excutive Building, Lusaka Proposed Air Conditioning and Ventilation Services

    Item Description Unit Qty. Rate Amount

    K

    BILL No. 4

    THIRD FLOOR SERVICES

    COLLECTION PAGE

    Page 11

    Page 12

    Page 13

    TOTAL AMOUNT CARRIED TO TOTAL SUMMARY

    North Atlantic Engineering Consultants

    Lusaka, Zambia 14

  • Bank of Zambia, Excutive Building, Lusaka Proposed Air Conditioning and Ventilation Services

    Item Description Unit Qty. Rate Amount

    K

    BILL No. 5

    5.0.0 FOURTH FLOOR SERVICES

    5.1.0 AIR CONDITIONING SERVICES

    5.1.1 Specified Air-conditioning units

    Mitsubishi City Multi Y Series' Multiple air-cooled split

    Type air-conditioning units with occupancy sesors accessory

    of the following types and capacities or equal and approved:

    Note

    Refrigerant shall be R410A.

    5.1.2 Indoor Units

    5.1.3 Mitsubishi Multi-split Ceiling cassette, No. 6

    Model PLFY-P80VBM-E or equal and approved

    Capacity: 30,700 Btu/hr (Cooling); 34,100 Btu/hr (Heating)

    5.1.4 Mitsubishi Multi-split Ceiling cassette, No. 3

    Model PLFY-P63VBM-E or equal and approved

    Capacity: 24,200 Btu/hr (Cooling); 24,300 Btu/hr (Heating)

    5.1.5 Mitsubishi Multi-split Ceiling cassette, No. 1

    Model PLFY-P50VBM-E or equal and approved

    Capacity: 19,100 Btu/hr (Cooling); 21,500 Btu/hr (Heating)

    5.1.6 Mitsubishi Multi-split Ceiling cassette, No. 6

    Model PLFY-P40VBM-E or equal and approved

    Capacity: 15,400 Btu/hr (Cooling); 17,100 Btu/hr (Heating)

    5.1.7 Mitsubishi Multi-split Ceiling cassette, No. 2

    Model PLFY-P25VCM-E or equal and approved

    Capacity: 9,600 Btu/hr (Cooling); 10,900 Btu/hr (Heating)

    5.1.8 Mitsubishi Multi-split Ceiling cassette, No. 3

    Model PLFY-P32VCM-E or equal and approved

    Capacity: 12,300 Btu/hr (Cooling); 13,600 Btu/hr (Heating)

    5.1.9 Outdoor Unit

    5.1.10 Mitsubishi PUHY-P800YSHM-A or equal and approved

    including filter dryer and shunt-off valve.

    Capacity:307,000 Btu/hr (Cooling);341,200 Btu/hr (Heating) No. 1

    5.1.11 Mitsubishi PUHY-P350YHM-A or equal and approved

    including filter dryer and shunt-off valve.

    Capacity:136,500 Btu/hr (Cooling);153,500 Btu/hr (Heating) No. 1

    5.1.12 Allow for construction of concrete plinth and erection of the

    I-Section beams to support the outdoor unit item

    5.1.13 Single Split Air Conditioning Units

    5.1.14 Single split air conditioning unit as 'Samsung' Model

    AC052FBNDEH or equal and approved:

    Capacity:17,100 Btu/hr (Cooling);20,500 Btu/hr (Heating)

    Max. Length (outdoor to indoor) : 30m (35m)

    Max. Height (between outdoor and indoor) : 30m (30m)

    Power Consumption: 3.15kW No. 1

    CARRIED TO COLLECTION PAGE

    North Atlantic Engineering Consultants

    Lusaka, Zambia 15

  • Bank of Zambia, Excutive Building, Lusaka Proposed Air Conditioning and Ventilation Services

    Item Description Unit Qty. Rate Amount

    K

    5.1.15 Refrigerant Piping (including all fittings and insulation

    on Tray)

    5.1.16 Allow for installation of refrigerant suction and discharge item

    pipes

    5.1.17 Dia. 32mm Condensate Drain pipe in insulation and fittings m 56

    5.1.18 Dia. 50mm Condensate Drain pipe in insulation and fittings m 45

    5.1.19 Include drilling through wall for condesate drain pipes Item

    5.1.20 Junction Pipe Kits

    5.1.21 Allow for the supply and installation of joint kits item

    5.1.22 Controllers

    5.1.23 PAR-F27MEA-E Local Wired Remote Controller No. 21

    (Including chiseling, plastering and paiting)

    5.1.24 PAC-SF44SRA System Remote Controller No. 2

    5.1.25 Existing Airconditioners

    5.1.26 Include for removal and handover to client, of existing

    air-conditioners Item

    5.1.27 Include for Sealing of openings in walls for existing

    air-conditioners (to include plastering and

    painting matching the existing wall finish) Item

    5.1.28 Allow for removal and handover to Client of the existing

    air conditioning piping in the ceiling Void. Item

    5.1.29 Occupancy Sensors

    5.2.0 VENTILATION SERVICES

    Supply and install the following equipment as recommended

    by the manufacturer's manuals and instructions:

    5.2.1 Wall/Window Mounted Extract Fan as 'Expelair' GX9

    or equal and approved:

    Extract Performance: 728m cubic meter per hour

    Power Source : 220V/1Phase/50Hz

    Power Consumption: 60 Watts No. 1

    5.2.2 600 x 600mm Fresh Air Grilles 'Europair'; type ECA- Egg

    Crate; Enamel White complete with opposed blade dampers No. 8

    5.2.3 Extract fan as 'Xpelair' In-Line; XID125

    Extract Performance : 375m cubic meter per hour

    Power Source : 220V/1phase/50Hz

    Power Consumption: 90 Watts No. 1

    5.2.4 200mm Diameter White Metallic Disc Valves No. 3

    5.2.5 300x300mm 0.6mm thick G.I. Extract Air Duct m 20

    5.2.6 300mm x 300mm Weather Louvre as 'Europair' m 2

    with Natural Anodised Aluminium

    CARRIED TO COLLECTION PAGE

    North Atlantic Engineering Consultants

    Lusaka, Zambia 16

  • Bank of Zambia, Excutive Building, Lusaka Proposed Air Conditioning and Ventilation Services

    Item Description Unit Qty. Rate Amount

    K

    5.2.7 Allow for electrical cabling to indoor and outdoor units for the

    entire Fourth floor item

    5.2.8 Allow for the replacement of damaged ceiling portions with

    same ceiling as existing item

    5.2.9 1000x900mm 0.6mm thick G.I Duct m 6

    5.2.10 1000x900mm Wire Mesh No. 1

    5.3.0 ELECTRICAL SERVICES

    5.3.15A Surface Mounted Single Socket Outlet for AC Indoor Units

    Power Points No. 22

    5.3.213A Surface Mounted Single Socket Outlet for Extract Fans

    Power Points No. 5

    5.3.3 32A SP Weatherproof Industrial Isolator No. 1

    5.3.4 Electrical Distribution Board Complete with the following: No. 1

    40A TP MCB No. 1

    30A SP MCB No. 1

    6A SP MCB No. 24

    10kA Surge Arrestors No. 3

    Neutral Bar Item 1

    Earth Bar Item 1

    5.3.5 10mm.sq 4-Core PVC/SWA Armoured Cable M 25

    5.3.6 6mm.sq Bare Core Earth Wire Cable M 25

    5.3.7

    Supply and installation of power points for Extract Fans

    complete with 2.5mm.sq PVC/SWA armoued cable + Earth,

    draw boxes, conduiting and all associated installation

    accessories

    No. 5

    5.3.8

    Supply and installation of power points for AC Indoor Units

    complete with 2.5mm.sq PVC/SWA armoued cable + Earth,

    draw boxes, conduiting and all associated installation

    accessories

    No. 22

    5.3.9

    Supply and installation of power points for AC Outdoor Units

    complete with 4.0mm.sq PVC/SWA armoued cable + Earth,

    draw boxes, conduiting and all associated installation

    accessories

    No. 1

    CARRIED TO COLLECTION PAGE

    North Atlantic Engineering Consultants

    Lusaka, Zambia 17

  • Bank of Zambia, Excutive Building, Lusaka Proposed Air Conditioning and Ventilation Services

    Item Description Unit Qty. Rate Amount

    K

    BILL No. 5

    FOURTH FLOOR SERVICES

    COLLECTION PAGE

    Page 15

    Page 16

    Page 17

    CARRIED TO SUMMARY OF BILLS OF QUANTITIES

    North Atlantic Engineering Consultants

    Lusaka, Zambia 18

  • Bank of Zambia, Excutive Building, Lusaka Proposed Air Conditioning and Ventilation Services

    Item Description Unit Qty. Rate Amount

    K

    BILL No. 6

    FIFTH FLOOR SERVICES

    6.1.0 AIR CONDITIONING SERVICES

    6.1.1 Specified Air-conditioning units

    Mitsubishi City Multi Y Series' Multiple air-cooled split

    Type air-conditioning units with occupancy sesors accessory

    of the following types and capacities or equal and approved:

    Note

    Refrigerant shall be R410A.

    6.1.2 Indoor Units

    6.1.3 Mitsubishi Multi-split Ceiling cassette, No. 9

    Model PLFY-P80VBM-E or equal and approved

    Capacity: 30,700 Btu/hr (Cooling); 34,100 Btu/hr (Heating)

    6.1.4 Mitsubishi Multi-split Ceiling cassette, No. 2

    Model PLFY-P63VBM-E or equal and approved

    Capacity: 24,200 Btu/hr (Cooling); 24,300 Btu/hr (Heating)

    6.1.5 Mitsubishi Multi-split Ceiling cassette, No. 1

    Model PLFY-P50VBM-E or equal and approved

    Capacity: 19,100 Btu/hr (Cooling); 21,500 Btu/hr (Heating)

    6.1.6 Mitsubishi Multi-split Ceiling cassette, No. 3

    Model PLFY-P40VBM-E or equal and approved

    Capacity: 15,400 Btu/hr (Cooling); 17,100 Btu/hr (Heating)

    6.1.7 Mitsubishi Multi-split Ceiling cassette, No. 2

    Model PLFY-P25VCM-E or equal and approved

    Capacity: 9,600 Btu/hr (Cooling); 10,900 Btu/hr (Heating)

    6.1.8 Mitsubishi Multi-split Ceiling cassette, No. 10

    Model PLFY-P32VCM-E or equal and approved

    Capacity: 12,300 Btu/hr (Cooling); 13,600 Btu/hr (Heating)

    6.1.9 Outdoor Unit

    6.1.10 Mitsubishi PUHY-P800YSHM-A or equal and approved

    including filter dryer and shunt-off valve.

    Capacity:307,000 Btu/hr (Cooling);341,200 Btu/hr (Heating) No. 1

    6.1.11 Mitsubishi PUHY-P550YHM-A or equal and approved

    including filter dryer and shunt-off valve.

    Capacity:215,000 Btu/hr (Cooling);235,400 Btu/hr (Heating) No. 1

    6.1.12 Allow for construction of concrete plinth and erection of the

    I-Section beams to support the outdoor unit item

    6.1.13 Single Split Air Conditioning Units

    6.1.14 Single split air conditioning unit as 'Samsung' Model

    AC052FBNDEH or equal and approved:

    Capacity:17,100 Btu/hr (Cooling);20,500 Btu/hr (Heating)

    Max. Length (outdoor to indoor) : 30m (35m)

    Max. Height (between outdoor and indoor) : 30m (30m)

    Power source: 220V/1Phase/50Hz

    Power Consumption: 3.15kW No. 1

    CARRIED TO COLLECTION PAGE

    North Atlantic Engineering Consultants

    Lusaka, Zambia 19

  • Bank of Zambia, Excutive Building, Lusaka Proposed Air Conditioning and Ventilation Services

    Item Description Unit Qty. Rate Amount

    K

    6.1.15 Refrigerant Piping (including all fittings and insulation

    on Tray)

    6.1.16 Allow for installation of refrigerant suction and discharge item

    pipes

    6.1.17 Dia. 32mm Condensate Drain pipe in insulation and fittings m 56

    6.1.18 Dia. 50mm Condensate Drain pipe in insulation and fittings m 45

    6.1.19 Include drilling through wall for condesate drain pipes Item

    6.1.20 Junction Pipe Kits

    6.1.21 Allow for the supply and installation of joint kits item

    6.1.22 Controllers

    6.1.23 PAR-F27MEA-E Local Wired Remote Controller No. 26

    (Including chiseling, plastering and painting)

    6.1.24 PAC-SF44SRA System Remote Controller No. 2

    6.1.25 Existing Airconditioners

    6.1.26 Include for removal and handover to client, of existing

    air-conditioners Item

    6.1.27 Include for Sealing of openings in walls for existing

    air-conditioners (to include plastering and

    painting matching the existing wall finish) Item

    6.1.28 Allow for removal and handover to Client of the existing

    air conditioning piping in ceiling void Item

    6.1.29 Occupancy Sensors No. 13

    6.2.0 VENTILATION SERVICES

    Supply and install the following equipment as recommended

    by the manufacturer's manuals and instructions:

    6.2.1 Wall/Window Mounted Extract Fan as 'Expelair' GX9

    or equal and approved:

    Extract Performance: 728m cubic meter per hour

    Power Source : 220V/1Phase/50Hz

    Power Consumption: 60 Watts No. 3

    6.2.2 600 x 600mm Fresh Air Grilles 'Europair'; type ECA- Egg

    Crate; Enamel White complete with opposed blade dampers No. 10

    6.2.3 Extract fan as 'Xpelair' In-Line; XID150

    Extract Performance : 830m cubic meter per hour

    Power Source : 220V/1phase/50Hz

    Power Consumption: 104 Watts No. 1

    6.2.4 Extract fan as 'Xpelair' In-Line; XID100

    Extract Performance : 250m cubic meter per hour

    Power Source : 220V/1phase/50Hz

    Power Consumption: 67 Watts No. 1

    6.2.5 200mm Diameter White Metallic Disc Valves No. 7

    CARRIED TO COLLECTION PAGE

    North Atlantic Engineering Consultants

    Lusaka, Zambia 20

  • Bank of Zambia, Excutive Building, Lusaka Proposed Air Conditioning and Ventilation Services

    Item Unit Qty. Rate Amount

    K

    6.2.6 300x300mm 0.6mm thick G.I. Extract Air Duct m 20

    6.2.7 300mm x 300mm Weather Louvre as 'Europair'

    with Natural Anodised Aluminium m 3

    6.2.8 Allow for electrical cabling to indoor and outdoor units for the

    entire Fifth floor item

    6.2.9 Allow for the replacement of damaged ceiling portions with

    same ceiling as existing item

    6.2.10 1000x900mm 0.6mm thick G.I Duct m 6

    6.2.11 1000x900mm Wire Mesh No. 1

    6.3.0 ELECTRICAL SERVICES

    6.3.15A Surface Mounted Single Socket Outlet for AC Indoor Units

    Power Points No. 28

    6.3.213A Surface Mounted Single Socket Outlet for Extract Fans

    Power Points No. 6

    6.3.3 32A SP Weatherproof Industrial Isolator No. 1

    6.3.4 Electrical Distribution Board Complete with the following: No. 1

    40A TP MCB No. 1

    30A SP MCB No. 1

    6A SP MCB No. 30

    10kA Surge Arrestors No. 3

    Neutral Bar Item 1

    Earth Bar Item 1

    6.3.5 10mm.sq 4-Core PVC/SWA Armoured Cable M 25

    6.3.6 6mm.sq Bare Core Earth Wire Cable M 25

    6.3.7

    Supply and installation of power points for Extract Fans

    complete with 2.5mm.sq PVC/SWA armoued cable + Earth,

    draw boxes, conduiting and all associated installation

    accessories

    No. 6

    6.3.8

    Supply and installation of power points for AC Indoor Units

    complete with 2.5mm.sq PVC/SWA armoued cable + Earth,

    draw boxes, conduiting and all associated installation

    accessories

    No. 28

    6.3.9

    Supply and installation of power points for AC Outdoor Units

    complete with 4.0mm.sq PVC/SWA armoued cable + Earth,

    draw boxes, conduiting and all associated installation

    accessories

    No. 1

    CARRIED TO COLLECTION PAGE

    North Atlantic Engineering Consultants

    Lusaka, Zambia 21

  • Bank of Zambia, Excutive Building, Lusaka Proposed Air Conditioning and Ventilation Services

    Item Description Unit Qty. Rate Amount

    K

    BILL No. 6

    AIR CONDITIONING SERVICES

    COLLECTION PAGE

    Page 19

    Page 20

    Page 21

    TOTAL AMOUNT CARRIED TO TOTAL SUMMARY

    North Atlantic Engineering Consultants

    Lusaka, Zambia 22

  • Bank of Zambia, Excutive Building, Lusaka Proposed Air Conditioning and Ventilation Services

    Item Description Unit Qty. Rate Amount

    K

    BILL No. 7

    7.0.0 SIXTH FLOOR SERVICES

    7.1.0 AIR CONDITIONING SERVICES

    7.1.1 Specified Air-conditioning units

    Mitsubishi City Multi Y Series' Multiple air-cooled split

    Type air-conditioning units with occupancy sesors accessory

    of the following types and capacities or equal and approved:

    Note

    Refrigerant shall be R410A.

    7.1.2 Indoor Units

    7.1.3 Mitsubishi Multi-split Ceiling cassette, No. 8

    Model PLFY-P80VBM-E or equal and approved

    Capacity: 30,700 Btu/hr (Cooling); 34,100 Btu/hr (Heating)

    7.1.4 Mitsubishi Multi-split Ceiling cassette, No. 3

    Model PLFY-P63VBM-E or equal and approved

    Capacity: 24,200 Btu/hr (Cooling); 24,300 Btu/hr (Heating)

    7.1.5 Mitsubishi Multi-split Ceiling cassette, No. 3

    Model PLFY-P50VBM-E or equal and approved

    Capacity: 19,100 Btu/hr (Cooling); 21,500 Btu/hr (Heating)

    7.1.6 Mitsubishi Multi-split Ceiling cassette, No. 5

    Model PLFY-P40VBM-E or equal and approved

    Capacity: 15,400 Btu/hr (Cooling); 17,100 Btu/hr (Heating)

    7.1.7 Mitsubishi Multi-split Ceiling cassette, No. 2

    Model PLFY-P25VCM-E or equal and approved

    Capacity: 9,600 Btu/hr (Cooling); 10,900 Btu/hr (Heating)

    7.1.8 Mitsubishi Multi-split Ceiling cassette, No. 4

    Model PLFY-P32VCM-E or equal and approved

    Capacity: 12,300 Btu/hr (Cooling); 13,600 Btu/hr (Heating)

    7.1.9 Outdoor Unit

    7.1.10 Mitsubishi PUHY-P700YSHM-A or equal and approved

    including filter dryer and shunt-off valve.

    Capacity:273,000 Btu/hr (Cooling);300,300 Btu/hr (Heating) No. 1

    7.1.11 Mitsubishi PUHY-P600YHM-A or equal and approved

    including filter dryer and shunt-off valve.

    Capacity:235,000 Btu/hr (Cooling);261,000 Btu/hr (Heating) No. 1

    7.1.12 Allow for construction of concrete plinth and erection of the

    I-Section beams to support the outdoor unit item

    7.1.13 Single Split Air Conditioning Units

    7.1.14 Single split air conditioning unit as 'Samsung' Model

    AC052FBNDEH or equal and approved:

    Capacity:17,100 Btu/hr (Cooling);20,500 Btu/hr (Heating)

    Max. Length (outdoor to indoor) : 30m (35m)

    Max. Height (between outdoor and indoor) : 30m (30m)

    Power source: 220V/1Phase/50Hz

    Power Consumption: 3.15kW No. 1

    CARRIED TO COLLECTION PAGE

    North Atlantic Engineering Consultants

    Lusaka, Zambia 23

  • Bank of Zambia, Excutive Building, Lusaka Proposed Air Conditioning and Ventilation Services

    Item Description Unit Qty. Rate Amount

    K

    7.1.15 Refrigerant Piping (including all fittings and insulation

    on Tray)

    7.1.16 Allow for installation of refrigerant suction and discharge item

    pipes

    7.1.17 Dia. 32mm Condensate Drain pipe in insulation and fittings m 56

    7.1.18 Dia. 50mm Condensate Drain pipe in insulation and fittings m 45

    7.1.19 Include drilling through wall for condesate drain pipes Item

    7.1.20 Junction Pipe Kits

    7.1.21 Allow for the supply and installation of joint kits item

    7.1.22 Controllers

    7.1.23 PAR-F27MEA-E Local Wired Remote Controller No. 25

    (Including chiseling, plastering and paiting)

    7.1.24 PAC-SF44SRA System Remote Controller No. 2

    7.1.25 Existing Airconditioners

    7.1.26 Include for removal and handover to client, of existing

    wall mounted type air-conditioner in the server room Item

    7.1.27 Include for Sealing of openings in walls for existing

    air-conditioners (to include plastering and

    painting matching the existing wall finish) Item

    7.1.28 Allow for removal and handover to Client of the existing

    air conditioning piping in the Ceiling Void. Item

    7.1.29 Occupancy Sensors No. 18

    7.2.0 VENTILATION SERVICES

    Supply and install the following equipment as recommended

    by the manufacturer's manuals and instructions:

    7.2.1 Wall/Window Mounted Extract Fan as 'Expelair' GX9

    or equal and approved:

    Extract Performance: 728 cubic meter per hour

    Power Source : 220V/1Phase/50Hz

    Power Consumption: 60 Watts No. 3

    7.2.2 600 x 600mm Fresh Air Grilles 'Europair'; type ECA- Egg

    Crate; Enamel White complete with opposed blade dampers No. 9

    7.2.3 Extract fan as 'Xpelair' In-Line; XID125

    Extract Performance : 375 cubic meter per hour

    Power Source : 220V/1phase/50Hz

    Power Consumption: 90 Watts No. 1

    7.2.4 Extract fan as 'Xpelair' In-Line; XID100

    Extract Performance : 250 cubic meter per hour

    Power Source : 220V/1phase/50Hz

    Power Consumption: 67 Watts No. 1

    7.2.5 200mm Diameter White Metallic Disc Valves No. 7

    CARRIED TO COLLECTION PAGE

    North Atlantic Engineering Consultants

    Lusaka, Zambia 24

  • Bank of Zambia, Excutive Building, Lusaka Proposed Air Conditioning and Ventilation Services

    Item Description Unit Qty. Rate Amount

    K

    7.2.6 0.6mm thick G.I. Extract Air Duct m 20

    7.2.7 300mm x 300mm Weather Louvre as 'Europair'

    with Natural Anodised Aluminium m 3

    7.2.8 Allow for electrical cabling to indoor and outdoor units for the

    entire sixth floor Item

    7.2.9 Allow for the replacement of damaged ceiling portions with

    same ceiling as existing Item

    7.2.10 1000x900mm 0.6mm thick GI Duct m 6

    7.2.11 1000x900mm Wire Mesh No. 1

    7.3.0 ELECTRICAL SERVICES

    7.3.15A Surface Mounted Single Socket Outlet for AC Indoor Units

    Power Points No. 26

    7.3.213A Surface Mounted Single Socket Outlet for Extract Fans

    Power Points No. 5

    7.3.3 32A SP Weatherproof Industrial Isolator No. 1

    7.3.4 Electrical Distribution Board Complete with the following: No. 1

    40A TP MCB No. 1

    30A SP MCB No. 1

    6A SP MCB No. 27

    10kA Surge Arrestors No. 3

    Neutral Bar Item 1

    Earth Bar Item 1

    7.3.5 10mm.sq 4-Core PVC/SWA Armoured Cable M 25

    7.3.6 6mm.sq Bare Core Earth Wire Cable M 25

    7.3.7

    Supply and installation of power points for Extract Fans

    complete with 2.5mm.sq PVC/SWA armoued cable + Earth,

    draw boxes, conduiting and all associated installation

    accessories

    No. 5

    7.3.8

    Supply and installation of power points for AC Indoor Units

    complete with 2.5mm.sq PVC/SWA armoued cable + Earth,

    draw boxes, conduiting and all associated installation

    accessories

    No. 26

    7.3.9

    Supply and installation of power points for AC Outdoor Units

    complete with 4.0mm.sq PVC/SWA armoued cable + Earth,

    draw boxes, conduiting and all associated installation

    accessories

    No. 1

    8.0.0 Removal of obsolete equipment

    Allow for Removal of all obsolete air conditioning equipment

    on 8th floor plant room

    CARRIED TO SUMMARY OF BILLS OF QUANTITIES

    North Atlantic Engineering Consultants

    Lusaka, Zambia 25

  • Bank of Zambia, Excutive Building, Lusaka Proposed Air Conditioning and Ventilation Services

    Item Description Unit Qty. Rate Amount

    K

    9.0.0 8th FLOOR ELECTRICAL SERVICES

    9.1.0 32A TP Weatherproof Industrial Isolator No. 1

    9.1.1 50A TP Weatherproof Industrial Isolator No. 5

    9.1.2 63A TP Weatherproof Industrial Isolator No. 3

    9.1.3 80A TP Weatherproof Industrial Isolator No. 2

    9.1.4 100A TP Weatherproof Industrial Isolator No. 1

    9.1.5 Electrical Distribution Board Complete with the following: No. 1

    32A TP MCB No. 1

    50A TP MCB No. 5

    63A TP MCB No. 3

    80A TP MCB No. 2

    100A TP MCB No. 1

    500A TP MCCB No. 1

    35kA Surge Arrestors No. 3

    Neutral Bar Item 1

    Earth Bar Item 1

    9.1.6 6mm.sq 4-Core PVC/SWA Armoured Cable M 30

    9.1.7 16mm.sq4-CorePVC/SWA Armoured Cable M 300

    9.1.8 25mm.sq 4-CorePVC/SWA Armoured Cable M 30

    9.1.9 120mm.sq 4-Core PVC/SWA Armoured Cable M 200

    9.1.10 4mm.sq Bare Core Earth Wire Cable M 30

    9.1.11 10mm.sq Bare Core Earth Wire Cable M 300

    9.1.12 16mm.sq Bare Core Earth Wire Cable M 30

    9.1.13 120mm.sq Bare Core Earth Wire Cable M 100

    9.1.14300mm Wide Heavy Duty Wire Mesh Cable Tray complete

    with mounting and installation accessories M 100

    CARRIED TO SUMMARY OF BILLS OF QUANTITIES

    North Atlantic Engineering Consultants

    Lusaka, Zambia 26

  • Bank of Zambia, Excutive Building, Lusaka Proposed Air Conditioning and Ventilation Services

    Item Description Unit Qty. Rate Amount

    K

    BILL No. 7

    AIR CONDITIONING SERVICES

    COLLECTION PAGE

    Page 23

    Page 24

    Page 25

    Page 26

    TOTAL AMOUNT CARRIED TO TOTAL SUMMARY

    North Atlantic Engineering Consultants

    Lusaka, Zambia 27

  • Bank of Zambia, Excutive Building, Lusaka Proposed Air Conditioning and Ventilation Services

    Item Description Unit Qty. Rate Amount

    K

    8.0.0 SUMMARY OF BILLS OF QUANTITIES

    8.1.0 Bill No. 1

    PRELIMINARY AND GENERAL ITEMS

    8.2.0 Bill No. 2

    FIRST FLOOR SERVICES

    8.3.0 Bill No. 3

    SECOND FLOOR SERVICES

    Bill No. 4

    8.4.0 THIRD FLOOR SERVICES

    Bill No. 5

    8.5.0 FOURTH FLOOR SERVICES

    Bill No. 6

    8.6.0 FIFTH FLOOR SERVICES

    Bill No. 7

    8.7.0 SIXTH FLOOR SERVICES

    Contingency Sum @ 5%

    Sub-total

    Add VAT @ 16.0%

    TOTAL AMOUNT CARRIED TO FORM OF TENDER

    North Atlantic Engineering Consultants

    Lusaka, Zambia 28