1 | P a g e
BANK OF INDIA
STAR HOUSE-2, 3RD FLOOR, PREMISES DEPARTMENT, C-4, G-BLOCK, BANDRA KURLA COMPLEX, BANDRA (E), MUMBAI-
400051
Event No. BOI/BKC/ 8 / 19-20 / ET/ 10
TENDER DOCUMENT FOR
Interior and Allied Services work of 3rd Corporate Office Building at C-29, G-Block, Bandra-Kurla Complex,
Mumbai.
REPLY OF PRE-BID QUERIES
CLIENT GENERAL MANAGER,
PREMISES DEPARTMENT 3rd FLOOR, STAR HOUSE 2, BKC
BANK OF INDIA Ph: 022-61317528
ARCHITECT & PROJECT MANAGEMENT CONSULTANTS
M/S ARK DESIGNS PVT LIMITED. ARCHITECTS, DESIGNERS AND PROJECT MANAGEMENT CONSULTANTS
101, Anish Tower CHS LTD., Senapati Bapat Marg, Matunga West, Mumbai
2 | P a g e
Reply of Online Pre-bid queries
Select Event BOI/BKC/8/19-20/ET/10
1 Vendor Query:- Kindly Provide approved make list for furniture items.
Reply:- To be made by the contractor, Vendor can outsource on his own responsibility. Maximum furniture can be made in the factory, as per the Architect’s design. All Furniture Should be manufactured in BEFMA certified factory and all IGBC regulations must be complied. The successful bidder will submit the complete details of the furniture manufacture for approval. The agency will be approved by the bank and Bank’s decision will be final in the matter.
2 Vendor Query:- Only One Brand KICH is Mentioned for Furniture hardware. Please Provide Alternate Brands Also.
Reply:- For all Furniture hardware KICH, Haffle, Hettich.
3 Vendor Query:- The Capacity/Size for Kitchen equipments not Mentioned. Please Provide list of Preferred Brands name for Kitchen Equipments.
Reply:- Please refer annexure for Drawings and details of sizes . The approved manufacture are Sigmax Technologies Pvt. Ltd., Suraj Engineers, Jai Engineering Works etc. The successful bidder will submit the complete details of the manufacture for approval. The agency will be approved by the bank and their decision will be final in the matter.
4 Vendor Query:- Para 2.4.0 on Page- 72: NO NIGHT OR REST DAY WORK: Please Clarify if work can be Continued on Sundays and Holidays.
Reply:- Condition remain Unchanged
5
Vendor Query:- For AV BOQ Package - Technical Specifications - Request you to provide us the CAD layouts along with elevation details (Cad format), to check the mounting feasibility of AV equipments. (for Boardroom as well as Conference Room)
Reply:- Please refer annexure and layout plans mentioned in tender having seating arrangement of boardroom and conference room of each floor. CAD layout will be provided to the successful bidder while execution of work.
6
Vendor Query:- For AV BOQ Package - Technical Specifications - For AV BOQ Package - Request you to provide us the AV connectivity as per BOQ, to understand the technical workability of the AV solution. (for Boardroom as well as Conference Room)
Reply:- All the input and output are given in the BOQ; the bidder has to generate the AVC Schematic.
7 Vendor Query:- For AV BOQ Package - Technical Specifications - Request you to provide us the equipment placement and rack position in the room. (for Boardroom as well as Conference Room)
Reply:- Boardroom’s rack will be placed in the Hub room, which is about 20 mtrs away from boardroom. Conference rooms Racks are within the room.
8 Vendor Query:- For AV BOQ Package - Final Excel BOQ - Request you to provide us the desired functionality that needs to be achieved with the AV
3 | P a g e
system. (for Boardroom as well as Conference Room)
Reply:- Kindly refer the compliance and scope of work document. Refer annexure.
9
Vendor Query:- For AV BOQ Package - Final Excel BOQ - Request you to provide us the desired functionality that needs to be achieved with the AV system. (for Boardroom as well as Conference Room). Once we receive the details like Cad layouts, elevation, connectivity
Reply:- Kindly refer the compliance and scope of work document. Refer annexure. CAD layout will be provided to the successful bidder while execution of work.
10 Vendor Query: - For complete Package - Payment Terms - Request you to provide more clarity on the payment terms.
Reply:- Please Ref Volume – 1 “ANNEXURE – TF ”
11 Vendor Query:- Kindly Provide Approved insurance Agencies refer Page 32
Reply:- Vender can get insurance from any reputed insurance Agencies
12 Vendor Query:- Final BOQ (excel BOQ)- SECTION C- ELECTRICAL BOQ EARTHING- 3.1,3.2,3.3, kindly specify the size of GI and Cu strip .
Reply:- Item No-3.1-25X 3 Cu strip, Item No-3.2-25X3 G.I strip, Item No-3.3- 8 SWG Cu bare annealed conductor
13 Vendor Query:- Final BOQ (excel BOQ)- SECTION D- POINT WIRING- 4.1,4.2-kindly specify the size and make of GI conduit. Also share the lighting layout.
Reply:- Item No-4.1 & 4.2- Use 25 mm G.I conduit, Lighting layout already shared.
14 Vendor Query:- Final BOQ (excel BOQ)- SECTION D- CIRCUIT WIRING- Kindly specify the size and make of steel conduit.
Reply:- 25mm G.I conduit of make- AKG,BEC, VIMCO
15 Vendor Query:- Final BOQ (excel BOQ)- SECTION D- POWER POINT- Sr no 4.7,4.8,4.9,4.10-Kindly share the power layout.
Reply:- Power Layout already shared with circuiting and DB scheduled.
16 Vendor Query:- Final BOQ (excel BOQ)- SECTION E- INTERNAL LIGHT FIXTURES- Sr no 5.1-Wheather we have to consider 28W or 18W.please specify.
Reply:- 2400mm (L) 18 W (718 Qty.) and 1200mm (L) 18 W(36 Qty.)
17 Vendor Query:- Final BOQ (excel BOQ)- SECTION E- INTERNAL LIGHT FIXTURES- Sr no 5.2-Wheather we have to consider 20W or 35W.please specify.
Reply:- Consider 20 W
18 Vendor Query:- Provision of Material Advance on TF Page 50 and Page 81 are Different.
Reply:- Considered Volume – 1 “ANNEXURE – TF” says “No Material Advance for any Item”. Condition of NO MATERIAL ADVANCE will prevail over all similar clause of tenders.
19 Vendor Query:- Final BOQ (excel BOQ)- SECTION G- UPS SYSTEM- Kindly specify the battery backup for ups system.
4 | P a g e
Reply:- 30 Min battery backup required.
20 Vendor Query:- Final BOQ (excel BOQ)- SECTION L- RODENT REPELLENT- Sr no 11.8, Cabling for Rodent repellent is not given in BOQ.
Reply:- Please consider cabling part from item no 11.14
21 Vendor Query:- Final BOQ (excel BOQ)- SECTION L- PERIMETER SECURITY- Sr no 11.1 to 11.6 ,Cabling part is not given in BOQ
Reply:- Please consider cabling part from item no 11.14
22 Vendor Query:- Final BOQ (excel BOQ)- SECTION M- BMS SYSTEM- IO Summary is not there in BOQ.
Reply:- IO summary attached. Please refer annexure.
23 Vendor Query:- page 80 release of Security deposit Mentioned Fify percent and Twenty Five Percent. Time for Releasing Remaining Twenty Five Percent May be Clarify.
Reply:- Clause b)- Retention Money : Balance 50% of retention money will be refunded in 15 days after the end Defect Liability period. (Please read 50% in place of 25%).
24 Vendor Query:- Kindly include Hospitals, Guest House and other Non-residential Buildings for PQ in addition to Corporate office Building and Institutional Buildings at Para 5 (iii).
Reply:- Please refer amended definition of SIMILAR WORKS from Corrigendum no.3.
25 Vendor Query:- General Query , Please clarify, Basic Rates mentioned are including Taxes or Not?
Reply:- Basic prices are inclusive of taxes and all other duties levied by Government . Ref Volume – 1 Page no 87 – Condition remain unchanged.
26 Vendor Query:- BOQ no 2_17 , PVC Flooring - Need Contact Details of Hego and Heritage.
Reply:- Vender has to find the contact details on his own For all Makes.
27 Vendor Query:- BOQ no 2_41 , Louvers - Need Detailed drawing of Louvers
Reply:- Refer BOQ & drawing which is already given.
28 Vendor Query:- BOQ no 50 , Texture paint - Need Basic Rate of Zinc Texture Paint.
Reply:- Not Applicable. Conditions remain Unchanged.
29 Vendor Query:- BOQ no 3_1 , Partition - Need Detailed drawings of Partition and Panelling Works.
Reply:- Detail drawing is Attached. Please refer annexure.
30 Vendor Query:- BOQ no 3_8 , Glasswool - Is Polythene Bag mandatory for wrapping of Glasswool as it is banned for useage.
Reply:- BOQ item remain Unchanged.
31 Vendor Query:- BOQ no 3_14 , Aluminium skirting - Need Make of Aluminium Skirting.
Reply:- Vetra, Bottom line, Kubik. The successful bidder will submit the complete details of the make for approval. The make will be approved by the bank and their decision will be final in the matter.
5 | P a g e
32 Vendor Query:- BOQ no 4 , Loose Furniture part- Need Detailed drawings of Storages , Meeting Tables, Conference Table , AGM Table , Executive /Dinning Tables , Reception Tables.
Reply:- Refer BOQ & drawing which is already given.
33 Vendor Query:- BOQ no 5, Modular Furniture - Need Detailed Drawings of Modular Furniture , Work Stations , Table , Storages .
Reply:- Refer BOQ & drawing which is already given.
34 Vendor Query:- BOQ no 7_4 , Murals - Need details of Wall Mural .
Reply:- Considered Basic rate Rs. 95,000/- per Sqm. for complete Mural.
35 Vendor Query:- BOQ no 7_9 , Kitchen Equipments - Need Detailed Specification ,Drawings , Ref. Images of all Kitchen Equipments.
Reply:- Please refer enclosed annexure.
36 Vendor Query:- BOQ no 8 , Landscaping works- Need Vendor details of Landscaping Work .
Reply:- S.T. Vision., Ganpat Rao Garden etc. The successful bidder will submit the complete details of the Vendor for approval. The agency will be approved by the bank before and their decision will be final in the matter.
37 Vendor Query:- BOQ no 2_9 , Steel Protection system for 2 hours fire rating(Beam Protection) - 1) Required Fire rating, 2) Application ( where these are being used ? for what application ? 3) Type
Reply:- Steel Protection system for 2 hours fire rating in Board form for steel Beams Protection at wherever required.
38 Vendor Query:- BOQ no 2_9 , Steel Protection system for 2 hours fire rating(Beam Protection) 3) Type
Reply: Not applicable as incomplete query.
39 Vendor Query:- BOQ no 2_9 , Steel Protection system for 2 hours fire rating(Beam Protection) 3) Type
Reply:- Not applicable as incomplete query.
40 Vendor Query:- BOQ no 2_9 , Steel Protection system for 2 hours fire rating(Beam Protection) - 3) Type
Reply:- Not applicable as incomplete query.
41 Vendor Query:- BOQ no 2_9 - Beam Protection - 3) Type
Reply:- Not applicable as incomplete query.
42 Vendor Query:- BOQ no 2_9 - Beam Protection - 3) Type and size of steel sections 4) Test Standard required to be followed
Reply:- Please refer BOQ as details are already given.
43 Vendor Query:- We will be able to share detailed queries on the AV package BOQ line-items, once CAD layouts, functionality and connectivity layouts are received.
Reply:- All the input and output are given in the BOQ & Annexures. The bidder has to quote accordingly.
44 Vendor Query:- Time for execution is only eight months. May kindly review considering monsoon and extend reasonable period.
Reply:- Condition remain Unchanged.
45 Vendor Query:- 1.IS code for Particle board to interior Grade where as in BOQ
6 | P a g e
its mentioned exterior grade, please clarify which one we have to consider.
Reply:- Consider exterior grade particle board.
46 Vendor Query:- 2.If we have to consider post laminated particle board as mentioned in BOQ, cost of post laminated particle board will be very high compared to pre laminated particle board. Please advise.
Reply:- Condition remain Unchanged, quote as per BOQ Specifications.
47 Vendor Query:- 3.Also clarify on thickness of external laminate to be used for PB if we are considering post laminated particle board.
Reply:- 0.8 mm thick laminate for the table top and .6mm thick for bottom.
48 Vendor Query:- Kindly advise on the type of the wood to be used in furniture
Reply:- 1st Class Wood matching to veneer.
49 Vendor Query:- 5. For aluminium partitions we have 60 mm particle available with us, please advise if 60 mm can be used or else we have to manufacture 65mm particle as per BOQ.
Reply:- Follow BOQ which is already given.
50 Vendor Query:- Kindly provide images for chairs and sofas
Reply:- Refer Tender drawing
51 Vendor Query:- Full height Glass Partition.-Please specify the size of U Channel and aluminium profile also.
Reply:- 12mm thick glass partition and refer BOQ.
52 Vendor Query:- Back Painted Glass partition-Do we need to consider any back support for glass partition.
Reply:- Support in aluminium frame work.
53 Vendor Query:- Mirror-Please mention the thickness of plywood
Reply:- 19 mm thick marine plywood support for mirror.
54 Vendor Query:- Aluminium Frame Work for partitions
Reply:- Not applicable as incomplete query.
55 Vendor Query:- SKINNING /PANELLING /BOXING.-Please specify the code no along with basic cost of laminate
Reply:- Basic cost for all laminate item are Rs.600 per SQM.
56 Vendor Query:- natural wood veneer of required finish-Please mention the thickness of plywood along with the grade of plywood that need to consider for back
Reply:- Refer BOQ item thickness is given.
57 Vendor Query:- Loose Furniture-For all Loose furniture please provide any reference image
Reply:- Refer drawings for images.
58 Vendor Query:- Supply and Install in for work ready Dry Pantry-Equipment ( KITCHEN)- Please provide size and drawing for all equipments
Reply:- Revised Drawing and Specifications attached as per annexure.
59 Vendor Query:- Please clear the terms for release /refund of initial security deposit
Reply:- Please refer tender clause. Clause b)- Retention Money : Balance 50% of retention money will be refunded in 15 days after the end Defect Liability period. (Please read 50% in
7 | P a g e
place of 25%).
60 Vendor Query:- Please clear the terms for release /refund of initial security deposit.
Reply:- Please refer tender clause. Clause b)- Retention Money : Balance 50% of retention money will be refunded in 15 days after the end Defect Liability period. (Please read 50% in place of 25%).
61 Vendor Query:- 2.9 Steel Protection system for 2 hours fire rating ( Beam protection)- Which board need to be consider
Reply:- Steel Protection system for 2 hours fire rating in Board form for steel Beams Protection at wherever required. Make – Promat or equivalent. The successful bidder will submit the complete details of the make for approval. The make/agency will be approved by the bank and their decision will be final in the matter.
62 Vendor Query:- 2.37 Gypsum Board False ceiling.- What we need to consider GI Section or MS section
Reply:- GI Section to be used for gypsum false ceiling as per manufacturer duly supplied.
63 Vendor Query:- 2.38 Calcium Silicate Board False Ceiling - What we need to consider GI Section or MS section
Reply:- GI Section to be used for calcium silicate board false ceiling as per manufacturer duly supplied.
64 Vendor Query:- Please Extend the Time For Submission at Least 10 Days
Reply:- Please refer corrigendum No.3.
65 Vendor Query:- The Tender Calls for EN Certified Digital Public Address System . The List of make mentioned are Bosch , Dante , Bose
Reply:- Please adhere to tender makes.
66 Vendor Query:- Dante
Reply:- Not applicable as incomplete query.
67 Vendor Query:- Dante
Reply:- Not applicable as incomplete query.
68 Vendor Query:- Kindly let us know the Number of Zone Required , We need Zone wise speaker quantity to estimate the optimum amplifier quantity.
Reply:- The no. of zones and quantities of amplifier has been designed based on the building floors, wattage and no. of speakers mentioned , please follow the BOQ & drawing, Floor wise speaker drawing already shared.
69 Vendor Query:- Kindly approve an Equivalent make i.e Ateis for Parity . Ateis is the recognized OEM in the Public as well as Private Sector for EN Certified Digital Public Address System
Reply:- Please adhere to tender makes
70 Vendor Query:- Kindly confirm how many audio channel we need to use with Public address controller?
Reply:- 4 Audio Channels.
71 Vendor Query:- Kindly confirm any redundancy to be considered in Amplifiers as this is one of the important feature in today's complex requirement of Digital Public Address System .
8 | P a g e
Reply:- Redundancy can be add on feature for future requirement so conditions remain unchanged.
72 Vendor Query:- Kindly let us know at what tapping (wattage) we should consider of Individual type of speaker .
Reply:- Full wattage as given in BOQ.
73 Vendor Query:- As per the BOQ description for Line item No 8.9
Reply:- Consider armoured cable.
74 Vendor Query:- Kindly approve Hanwha - Samsung Make for Cameras , as Hanwha - Samsung is Top 5 I.H.S / IMS Research report
Reply:- Please adhere to tender makes. Please refer annexure
75
Vendor Query:-Tender BOQ - 7.12 & 7.13, Section H - Data Networking, 24PORT SEMI MANAGEBLE GIGABYTE POE SWITCH - Pg 320 - As per the BOQ Description , It is been Asked as all Switches should be Layer 3 Whereas the same should be Layer 2 Switch & 1 nos of Layer 3 Switch.
Reply:- Please consider them as a access switches.
76
Vendor Query:-Tender BOQ - 8.1 & 8.2, Section I - Public Address System, Technical Specification of Public Address System - The Tender Calls for EN Certified Digital Public Address System . The List of make mentioned are Bosch , Dante , Bose . Dante & Bose are more of Professional Audio & Hence does not have all the components mentioned in the tender. Since This is the public tender we request to Kindly approve an Equivalent make i.e Ateis for Parity . Ateis is the recognized OEM in the Public as well as Private Sector for EN Certified Digital Public Address System . Some of the Key Large Ateis Installation in India are Chennai Metro , Nuclear Power plant (IGCAR) etc .
Reply:- Please adhere to tender makes.
77
Vendor Query:- Tender BOQ - 8.1 & 8.2, Section I - Public Address System, Technical Specification of Public Address System - Kindly let us know the Number of Zone Required , We need Zone wise speaker quantity to estimate the optimum amplifier quantity.
Reply:- The no. of zones and qty of amplifier has been designed based on the building floors, wattage and no. of speakers mentioned , please follow the BOQ& drawing, Floor wise speaker drawing already shared.
78 Vendor Query:- Tender BOQ - 8.1 & 8.2, Section I - Public Address System, Technical Specification of Public Address System - Kindly confirm how many audio channel we need to use with Public address controller ?
Reply:- 4 audio channel.
79
Vendor Query:- Tender BOQ - 8.1 & 8.2, Section I - Public Address System, Technical Specification of Public Address System - Kindly confirm any redundancy to be considered in Amplifiers as this is one of the important feature in today's complex requirement of Digital Public Address System .
Reply:- Redundancy can be add on feature for future requirement.
80 Vendor Query:- Tender BOQ - 8.6 , 8.7 & 8.8, Section I - Public Address System, Clause No 6 – Loudspeaker - Kindly let us know at what tapping (wattage) we should consider of Individual type of speaker .
Reply:- Full wattage as given in the BOQ
9 | P a g e
81
Vendor Query:- Tender BOQ - 8.9, Section I - Public Address System, Hard Wiring - As per the BOQ description for Line item No 8.9 & 9.12 it is been asked for flexible armoured control cables , Kindly let us know whether we should Quote Flexible Cable OR Armoured Cable.
Reply:- Consider armoured cable.
82
Vendor Query:- Tender BOQ - 8.9, Hard Wiring, Kindly Include Technoflex make for ELV Cables which is a recognized brand in the Extra Low Voltage Industry . Large Customer like IOCL , ONGC , Reliance , Cisco , Adani have been using Technoflex for the last 10 years for IBMS & ELV System .
Reply:- Please Adhere to tender makes.
83
Vendor Query:- Tender BOQ - 9 .1, Section J - Access Control System, Technical Specification of Access Control System (Clause 1 - Access Control Software) - As per Sr No 1.4 it is been asked that "the ACS must provide a web server-based solution. Only Internet Explorer is required for a workstation to access the ACS login server." Since Web Based Login is not secure . Please accept Server-Client Architecture for same and Client installation is required to Access the Application.
Reply:- User should not be restricted to a Predefined Workstation. By using web client user can log into the system from anywhere in the same network by authenticating through user name & password.
84
Vendor Query:- Tender BOQ - 9 .3, Section J - Access Control System, Technical Specification of Access Control System Access Controller - As per Sr No 1.2 it is been asked that "The controller shall provide access control processing and host functionality for 8 readers maximum." Whereas the BOQ Line item 9.3 mention 4 Wiegand Readers . Kindly Confirm what to be Consider.
Reply:- That is the max capacity of the controller. As per line item consider 4 readers/controller
85
Vendor Query:- Tender BOQ - 9 .3, Section J - Access Control System, Technical Specification of Access Control System Access Controller - As per BOQ Line item No 9.3 , The Controller <mention about LCD display this Functionality is available with only one OEM Among the list of make. In order to have Parity between the list of make we request you to kindly remove the functionality.
Reply:- Makes having LCD display only shall be considered while quoting the rates.
86
Vendor Query:- Tender BOQ - 9 .5, Section J - Access Control System, Technical Specification of Access Control System Biometric Reader - We Request you to Kindly Approve Virdi in the biometric reader as Virdi is one of the top global OEM of Biometric readers.
Reply:- Please adhere to tender makes
87 Vendor Query:- Tender BOQ - 9 .4, Section J - Access Control System, - We Request you to Kindly Approve Gallagher in the list of Mifare Card Reader as Gallagher is already approved for Software &Controller .
Reply:- Please adhere to tender makes
88 Vendor Query:- Tender BOQ - 9 .7, Section J - Access Control System -
10 | P a g e
Please Note in the Lock you have mentioned Lock with Inbuilt Contact & Also there is sepearte Line item 9.8 Magnetic Contact , Kindly Confirm Whether we should conisder Sepearte Magnetic contact this or not .
Reply:- Please quote in-built and separate magnetic contact as mentioned in the BOQ.
89 Vendor Query:- Tender BOQ - 9 .10, Section J - Access Control System - As Long range Reader is not manufactured by HID & Hence we request you to Kindly approve IDCube /EINS which are HID Certified OEM partner .
Reply:- Please adhere to tender makes
90 Vendor Query:- Tender BOQ - 9 .11, Section J - Access Control System - As Vehicle Tag is not manufactured by HID & Hence we request you to Kindly approve IDCube /EINS which are HID Certified OEM partner .
Reply:- Please adhere to tender makes
91
Vendor Query:- Tender BOQ - 9 .3, Section J - Access Control System, - As per Sr No 1.9.b it is been asked that "Communications -10/100 Ethernet, RS 485 for Extension modules ." We recommend Feature as IPv6 & OSDP for same.
Reply:- Communication protocols are for the controller and the extension modules.
92
Vendor Query:- Tender BOQ - 9 .3, Section J - Access Control System - As per Sr No 1.9.f it is been asked that "Certification: CE, EN, UL." We recommend that UL Certification should be mandatory for access Control system
Reply:- :- Conditions remain unchanged.
93
Vendor Query:- Tender BOQ - 9 .6, Section J - Access Control System - As per Sr No 4.12 it is been asked that "The Card reader shall be capable of reading the selected card technologies. (HID iClass/MiFareDESFire EV1 within the 13.56 MHz range)." We recommend that UL Certification should be mandatory for access Control system
Reply:- :- Conditions remain unchanged.
94
Vendor Query:- Tender BOQ - 9 .3, Section J - Access Control System - As per Sr No 1.9.f it is been asked that "Certification: CE, EN, UL." We recommend that UL Certification should be mandatory for access Control system
Reply:- :- Conditions remain unchanged.
95 Vendor Query:- Tender BOQ - 10.4 , 10.5 ,10.6 , 10.7, Section K - CCTV Surveillances System - Kindly approve Hanwha - Samsung Make for Cameras , as Hanwha - Samsung is Top 5 I.H.S / IMS Research report.
Reply:- Please adhere to tender makes
96 Vendor Query:- Tender BOQ - 10.1, Section K - CCTV Surveillances System - We Request you to Please Approve System architecture of VMS as per OEM Recommendation , Storage Calculation as per the requirement.
Reply:- System architecture of VMS as per OEM recommendation should 100% comply to technical specifications and BOQ description as mentioned in the tender Principal bidder to arrange for compliance document by OEM . Storage calculation to be vetted by both camera and VMS OEM.
11 | P a g e
97 Vendor Query:- Tender BOQ - 11.1, Section L - Perimeter Security - Kindly let us know whether the requirement is for Swing typw Barrier OR Flap type barrier , As the Specification calls for Swing barrier .
Reply:- Swing type barrier
98
Vendor Query:- Tender BOQ - 11.2, Section L - Perimeter Security - Kindly approve Krystal Vision one of the Leading manufacturer of Baggage scanner , They have supplied almost more than 150 units to Reliance Convention center which is next to your Current Projects
Reply:- Please adhere to tender makes
99 Vendor Query:- Tender BOQ - 11.3, Section L - Perimeter Security - Number of languages mentioned are German , French , Spanish , English , please remove all the Foreign language as the same is not required here in India.
Reply:- There is no language point mentioned in item no-11.3 which is UVSS.
100
Vendor Query:- Tender BOQ - 11.4, Section L - Perimeter Security - Threat Image Projection (TIP) function For Baggage scanner - As per Industry standard is 400 images total and 100 images of guns, knifes, bombs and IEDs Kindly Confirm the same.
Reply:- Please adhere to tender specifications and makes.
101
Vendor Query:- Tender BOQ - 11.6, Section L - Perimeter Security - AS per the BOQ Specification Boom Arm Length is not mentioned & As per the Tender Specification Boom Length is asked for 4/5/6 meter . Kindly Confirm Which Boom Length we should consider while Quoting.
Reply:- Consider the max length.
102
Vendor Query:- Tender BOQ - 11.8, Section L - Perimeter Security - As per the Tender Specification for Rodent repellant Controller it seems that requirements is for Maser VHFO Model whereas as per the BOQ Specification for Rodent repellant Controller it seems that requirements is for Maser Torrant Model . We assume that BOQ Specification will supercede Tender specification Kindly confirm the same.
Reply:- Please offer as per BOQ description.
103
Vendor Query:- Tender BOQ - 11.9, Section L - Perimeter Security - As per the Tender Specification for Rodent repellant Transducer it seems that requirements is to Cover area for 300 sqft whereas as per the BOQ Specification for Rodent repellant Trasducer it seems that requirements is to Cover area of 500 sqft . We assume that BOQ Specification will supercede Tender specification Kindly confirm the same.
Reply:- Please offer as per BOQ description.
104 Vendor Query:- Tender BOQ - 11.11, Section L - Perimeter Security - Kindly Include Mircom in Approved List of Make.
Reply:- Please adhere to tender makes
105
Vendor Query:- Tender BOQ - 11.12, Section L - Perimeter Security- As per the Tender Specification for Addresable WLD it seems that requirements asked for 10 Zonal Panel ,whereas as per the BOQ Specification for Water Leak Detection asks requirements for 4 zonal Panel . We assume that BOQ Specification will supercede Tender specification Kindly confirm the same.
Reply:- Please offer as per BOQ description.
12 | P a g e
106 Vendor Query:- Tender BOQ - 12.1.2, Section M - BMS System - Kindly approve O3i Impact Make for BMS software
Reply:- Please adhere to tender makes
107 Vendor Query:- Tender BOQ - 12.1.3, Section M - BMS System - Kindly approve Easy IO Make for BMS DDC Controller
Reply:- Please adhere to tender makes
108 Vendor Query:- Tender BOQ - 12.1.3, Section M - BMS System - Kindly Share Latest IO Summary for DDC Configuration without it we are unable to Quote DDC & Integrators for 3rd Party Integration.
Reply:- IO summary attached. Please refer annexure.
109 Vendor Query:- Tender BOQ - 12.1.3 , Section M - BMS System - Kindly approve Dwyer / Aerosense make for Field devices (sensors ) in BMS
Reply:- Please adhere to tender makes
110
Vendor Query:- Through the directive of various Initiatives taken by the Government of India under the various policies and notifications issued as listed below, it is given to understand that the List of Makes given in any Tender for Public Procurement is a “Recommended Suggestion” and cannot be Finite in nature. Subject to meeting Non-Proprietary Technical Specifications as Prescribed in the Tender, any List of Make which carries the Qualification of Not Being Debarred, Black Listed or Under Investigation for Malpractice by any State/Central/PSU/Govt Entity/Govt Funded Entity etc should be considered and allowed to be Included by the Bidders without taking any Technical Deviations. The Reference to the above has been cited under various sections of the following Acts and Gazetted Orders Issued by the Government of India 1. Competition Commission of India, 2002 ( https://www.cci.gov.in/sites/default/files/cci_pdf/competitionact2012.pdf ) a. Overall Provides Guidelines for Monopolistic Specification or Dominant Position During Participation in a Public Procurement Tender b. Provides Provisions to Ensure that there is Fair Market Competition to protect the Advent of Commercial Disadvantage to the Reply being a State/Central/PSU/Govt Entity/Govt Funded Entity 2. Central Vigilance Commission Act of India, 2003 ( http://cvc.gov.in/sites/default/files/cvcact_0.pdf ) . Provides a Clear Framework for Inclusion of Integrity Pact in every State/Central/PSU/Govt Entity/Govt Funded Entity which clearly prohibits cartelling, proprietary technology specification, limitations of competition etc to protect the Interest of the State/Central/PSU/Govt Entity/Govt Funded Entity a. Provides a Clear Framework for a Fair and Transparent Tendering Process which is subject to Investigation in the event of Unfair Tendering Policies related to Bidder Participation & List of Makes prescribed in the Tender In keeping in view the Technical Specifications of the Tender & the Commercial Disadvantage on the Non-Monopolistic Participation of Brands in
13 | P a g e
the Tender, we request for the addition of the List of Makes and Changes to the Technical Specifications to make the Tendering Process Fair and Transparent.
Reply:- :- Please adhere to tender makes and specifications.
111
Vendor Query:- Page No. 406 of Volume-II, Tunnel Size, not to exceed: 620mm (24.4”) Wide x 420mm (16.5”) High - As per the MHA Specification for medium XBIS, the tunnel size should be minimum 600 mm (W) X 400 mm (H), hence requesting to kindly consider the same as per MHA Specification
Reply:- The Specifications of Ministry of Home Affairs is applicable to Police departments and other agencies affiliated to MHA. Please adhere to tender makes and specifications.
112
Vendor Query: - Page No. 406 of Volume-II, Max. object size: not less than 615mm (24.2") Wide x 410mm (16.1") High - As per the MHA Specification for medium XBIS, the tunnel size should be minimum 600 mm (W) X 400 mm (H), hence requesting to kindly consider the same as per MHA Specification
Reply:- The Specifications of Ministry of Home Affairs is applicable to Police departments and other agencies affiliated to MHA. Please adhere to tender makes and specifications.
113
Vendor Query:- Page No. 406 of Volume-II, Maximum conveyor load not less than 165kg (364lbs) - As per MHA Standard Specification of XBIS it should be range from 150 to 160 Kg evenly distributed, request you to kindly consider the same.
Reply:- The Specifications of Ministry of Home Affairs is applicable to Police departments and other agencies affiliated to MHA. Please adhere to tender makes and specifications.
114
Vendor Query:- Page No. 407 of Volume-II, All safety or operational relevant labels on the system's housing must be realized either as pictogram or as one label in the four languages: English, French, Spanish and German - We assuming that English Language should be suffice here as in India, Other mentioned language is not required to understand.
Reply:- English Language is ok
115
Vendor Query:- Page No. 407 of Volume-II , The system must be designed as a high resolution system. The system shall have at least 1152 humidity protected X-ray detectors. All detectors shall be supported by the system electronics and must be used for the generation of the high resolution image.- Request you to kindly clarify the terminology of 1152 humidity protection.
Reply:- The Photo Diodes/Detector Boards/Scintillator Crystals in the Photo Diodes should be coated with a Special Protection which can withstand varied environmental issues like dampness, Moistures which will reflect low resolution X-Ray Images. Please adhere to tender makes and specifications.
116
Vendor Query:- Page No. 408 of Volume-II, Resolution: at least 39 AWG measured with pure copper wire at belt speed of 0.2 m/s - We assume that it is typo error since the standard Sensitivity or Resolution is 38AWG/42 SWG, hence request you to kindly consider the same.
14 | P a g e
Reply:- We require the machine to provide a Wire Resolution of 39 AWG (0.09 Cu) equivalent to 44 SWG wire Resolution at a Belt speed of 0.2 M/sec. Please adhere to tender makes and specifications.
117 Vendor Query:- Page No. 410 of Volume-II, The system must comply to NFC-74-100 standard. - Request you to kindly clarify the terminology.
Reply:- NFC is internationally recognized as a type-approval and consists not only of a strict evaluation of the X-ray performance but also tests the robustness of the design, X-ray safety, and ensures compliance with CE declaration of conformity and is a required. Please adhere to tender makes and specifications.
118
Vendor Query:- Page No. 410 of Volume-II, The system must comply to IEEE/ANSI N42.44-2008 standard. All relevant measurements must be proven by reports of an accredited external laboratory. - We are Indian OEM of X-Ray baggage Scanner, hence in India and for Indian OEM AERB Certificate should be considered only.
Reply:- N42.44-2008 - American National Standard for the Performance of Checkpoint Cabinet X-Ray Imaging Security Systems and is not related to the certificate provided by AERB. Kindly provide an equivalent certificate which conforms to the required performance. Please adhere to tender makes and specifications.
119
Vendor Query:- Page No. 410 of Volume-II, The system must comply to DIN IEC 61010-2-091 standard. All relevant measurements be proven by reports of an accredited external laboratory. - We assuming that here it is indicating NABL accredited Lab certified ISO1600DIN test report, kindly clarify.
Reply:- DIN IEC 61010-2-091 standard refers Safety requirements for electrical equipment for measurement, control and laboratory use - Part 2-091: Particular requirements for cabinet X-ray system. ISO1600DIN is related to FILM Safety and not for electrical safety. Please adhere to tender makes and specifications.
120
Vendor Query:- Page No. 410 of Volume-II, A fire load calculation by an accredited external laboratory must be available for the system. - Request you to kindly clarify the requirement here., we assume not relevant to the the XBIS system.
Reply:- The weight of combustible material per square foot of floor space is called as fire load. Kindly share the certificate accordingly. Please adhere to tender makes and specifications.
121
Vendor Query:- Removal all types of brick work, block work, P.C.C. walls including plaster, Dado including concealed conduits, wiring, electrical boxes etc., complete. - Please Advice On Mode Of Measurement. Shall Get Paid Vertically And Horizontally Or Not
Reply:- Please adhere to BOQ Specification
122 Vendor Query:- Removal all types of false ceiling including frame work, electrical fixtures, AC ducts, etc., complete. - Please Provide Segrigated Items Of Mep Part
Reply:- Please adhere to BOQ Specification
123 Vendor Query:- DAKU ROOF GARDEN - Landscaping Waterproofing system - Please Provide Specific Vendor Querys Contact Details
15 | P a g e
Reply:- Vender has to find the contact details on his own For all Makes.
124 Vendor Query:- Vitrified Floor Tiles - Please Advice On Both Qty For Same Item Or Not
Reply:- Yes
125 Vendor Query:- Granite. - Basic Rate Unit Is Missing
Reply:- Its in SQM
126 Vendor Query:- Vitrified Tiles in dado - Basic Rate Unit Is Missing
Reply:- Its in SQM
127 Vendor Query:- Glass door Shutter - Please Provide Basic Rate Of Veneer
Reply:- Wherever basic cost is not given for Veneer considered Rs.1500 Per SQM.
128 Vendor Query:- Providing and fixing Wood door handle of size 400mm X 50mm all complete as specified and drawing and as directed by the Engineer-in-Charge. - Please Provide Make And Model
Reply:- Vendor have to craft a handle at site or at factory as per given design in drawing
129 Vendor Query:- Providing and fixing Fire Rated wood door handle size 400mm X 50mm ( 1Pair) all complete as specified and drawing and as directed by the Engineer-in-Charge. - Please Provide Make And Model
Reply:- Vendor have to craft a handle at site or at factory as per given design in drawing
130 Vendor Query:- Textured Zinc Paint - Please Provide Basic Rate
Reply:- No Basic Rate
131 Vendor Query:- Aluminium Frame Work for partitions & panelling. - Please Provide Thick Of Frame And Center To Center Gap Of Frame
Reply:- Aluminium box should be of 2 mm Thick and Vendor and Centre to centre distances should be 450 mm to 600 mm.
132 Vendor Query:- 1mm thick non-metallic decorative laminate with plain/wood grain finish of approved design & shade. - Please Provide Basic Rate
Reply:- Basic cost of 1mm thick non-metallic decorative laminate Rs. 500 / Sqm.
133 Vendor Query:- 6 MM Thick Solid Surface Materials. - Please Provide Basic Rate
Reply:- Basic cost of 6 MM Thick Solid Surface Materials Rs. 12000 / Sqm.
134 Vendor Query:- Teak Wood Moulding (Veneer Matching) - Please Provide Type Of Wood
Reply:- 1st Class Wood matching to veneer
135 Vendor Query:- Soffit Veneer Finish. - Please Provide Bsaic Rate Veneer
Reply:- Wherever basic cost is not given for Veneer considered Rs.1500 /SQM
136 Vendor Query:- Soffit Laminate Finish. - Please Provide Basic Rate Of Laminate
Reply:- Wherever basic cost is not given for laminate considered Rs.600/ SQM
137 Vendor Query:- Pelmet Veneer Finish. - Please Provide Basic Rate Veneer
Reply:- Wherever basic cost is not given for Veneer considered Rs.1500/ SQM
138 Vendor Query:- Pelmet Laminate Finish. - Please Provide Basic Rate Of
16 | P a g e
Laminate
Reply:- Wherever basic cost is not given for laminate considered Rs.600 /SQM
139 Vendor Query:- 3M Dusted film of series 7725-314 or approved equivalent of Saint Gobain or LG- Please Provide Basic Rate
Reply:- No Basic rate as Series is given
140 Vendor Query:- 3M Crystal film of series 7725-324 or approved equivalent Saint Gobain or LG - Please Provide Basic Rate
Reply:- No Basic rate as Series is given
141 Vendor Query:- Safety and Security film - Please Provide Basic Rate
Reply:- No Basic rate as Series is given
142 Vendor Query:- Console unit in meeting rooms (Height 750 mm) - Please Provide Basic Rate Of Veneer
Reply:- Wherever basic cost is not given for Veneer considerd Rs.1500/ SQM
143 Vendor Query:- Over Head Storage (Depth 350 mm) - Please Provide Basic Rate Of Laminate
Reply:- Wherever basic cost is not given for laminate considerd Rs.600 SQM
144 Vendor Query:- Pantry-Platform Shutter - Please Provide Basic Rate Of Laminate
Reply:- Wherever basic cost is not given for laminate considerd Rs.600 /SQM
145 Vendor Query:- Board Room Table (TYPE U Size 6500 x 750 x 900) - Please Provide Basic Rate Of Veneer
Reply:- Wherever basic cost is not given for Veneer considerd Rs.1500 /SQM
146 Vendor Query:- Board Room Table (TYPE U Size 6500 x 750 x 900) - Please Provide Basic Rate Of Veneer
Reply:- Wherever basic cost is not given for Veneer considerd Rs.1500 /SQM
147 Vendor Query:- AGM Table Size (1700 x 900 MM) (1400 X550 X 600MM) - Please Provide Basic Rate Of Veneer
Reply:- Wherever basic cost is not given for Veneer considerd Rs.1500 /SQM
148 Vendor Query:- GM Table Size (2250 x 1050 MM) (1200 X550 X 650MM) - Please Provide Basic Rate Of Marble And Laminate
Reply:- Wherever basic cost is not given for Veneer considerd Rs.1500/ SQM&basic cost for marble Rs.10000 / SQM
149 Vendor Query:- Secretary Table :(1800 x 750 MM) (1300 X550 X 600MM) - Please Provide Basic Rate Of Veneer
Reply:- Wherever basic cost is not given for Veneer considerd Rs.1500 /SQM
150 Vendor Query:- Lunch Table (1200 x 600 x750MM) - Please Provide Basic Rate Of Corian
Reply:- Basic cost of Corian Rs. 12000 / Sqm.
151 Vendor Query:- Meeting Room Table :(1800 x 900 x750MM) - Please Provide Basic Rate Of Veneer
Reply:- Wherever basic cost is not given for Veneer considerd Rs.1500 /SQM
152 Vendor Query:- Dinning Table : - Please Provide Basic Rate Of Corian
Reply:- Basic cost of Corian Rs. 12000 / Sqm.
153 Vendor Query:- EXECUTIVE DINNING TABLES - Please Provide Basaic Of
17 | P a g e
Jute Fabric
Reply:- Basic cost of Jute Fabric Rs. 1000 / Sqm.
154 Vendor Query:- Reception Table (3000 X 750 X 1000MM)- Please Provide Basic Rate
Reply:- No Basic rate
155 Vendor Query:- Circular Side-Table - Please Provide Basic Rate Of Veneer
Reply:- Wherever basic cost is not given for Veneer considerd Rs.1500 /SQM
156 Vendor Query:- Photocopier Counter - Please Provide Basic Rate Of Granite
Reply:- Basic Rate-Rs.4850 / SQM
157 Vendor Query:- Discussion Table size 1500 X 600 mm - Please Advice What To Quote . Discussion Table Or Work Station With Pedestal And Credenza
Reply:- Quote as combined item as one no (unit) of workstation
158 Vendor Query:- Discussion Table size 1200 X 600 mm - Please Advice What To Quote . Discussion Table Or Work Station With Pedestal And Credenza
Reply:- Quote as combined item as one no (unit) of workstation
159 Vendor Query:- Low Height Storage 1200 mm - Please Provide Basic Rate Of Laminate
Reply:- Basic Rate-Rs.500 / SQM
160 Vendor Query:- Mural in Composite marble. - Please Provide Basic Rate
Reply:- Considered Basic rate Rs. 95000 per Sqm for complete Mural.
161
Vendor Query:- CABLE MANAGER : Providing and fixing DIA 60 MM PVC wire cable manager with shutter & chain in work station of 90mm dia of approved make as per direction of Architects. - Please Provide Specifc Vendor Querys Name
Reply:- Ebco or equivalent . The successful bidder will submit the complete details of the make for approval. The make/agency will be approved by the bank and their decision will be final in the matter.
162
Vendor Query:- KEY BOARD : Providing & fixing M.S. powder coated (powder coating 45-50 microns) computer key board tray of ebco (model no-KBT-45) or equivalent with necessary screws complete as per direction of Archietcs. - Please Provide Specific Vendors Name
Reply:- Ebco or equivalent . The successful bidder will submit the complete details of the make for approval. The make/agency will be approved by the bank and their decision will be final in the matter.
163
Vendor:- CPU STAND :Providing & fixing adjustable M.S. powder coated (powder coating 45-50microns) C.P.U.Stand fixed on Partation brackt system (hanging) complete as per direction of Architects. - Please Provide Specifc Vendors Name
Reply:- Ebco or equivalent . The successful bidder will submit the complete details of the make for approval. The make/agency will be approved by the bank and their decision will be final in the matter.
164 Vendor Query:- Supply and Install in for work ready Dry Pantry-Equipment ( KITCHEN) - Any Specific Kitchen Vendor If Yes Please Provide Contact Details
18 | P a g e
Reply:- Sigmax Technologies Pvt. Ltd., Suraj Engineers, Jai Engineering Works etc. The successful bidder will submit the complete details of the make for approval. The make/agency will be approved by the bank and their decision will be final in the matter.
165 Vendor Query:- VERTICAL WALL WITH FRAMING & DRIP IRRIGATION SYSTEM - Please Provide Basic Rate And Lumpsum Cost Of Pots As Per The Qty Mentioned
Reply:- Basic cost of pots Rs 250/ No.
166
Vendor Query:- Providing and wartering of irrigation water through automatic system of Horticulture features i.e. lawn, tree, shrubs, hedge/edge, ground cover etc. at the site (Ground Floor, Terraces an Car lift top) of work. compling IGBC ruls and critarea (All kind of sencers), wartering at site with all inclusive as per direction of officer-in-charge. - Please Provide Vendors Contact Details
Reply:- Name of vendor - S. T. Vision., Ganpat Rao Garden etc. The successful bidder will submit the complete details of the make for approval. The make/agency will be approved by the bank and their decision will be final in the matter.
167 Vendor Query:- Please Share Civil &Interior Make List
Reply:- It’s Already in Volume 2 – Tender specification
168 Vendor Query:- Please Share Mep Drawings
Reply:- Drawings are already shared.
169 Vendor Query:- Please Provide Average Length For Primary Point
Reply:- Consider 15 Mtr. avg. length for primary, drawings are also shared with location of DB’S so please check drawings also.
170 Vendor Query:- Temporary Lighting And Power Will Be In Client Scope, Please Confirm
Reply:- Temporary water, Lighting And Power will be In Vendor Scope
171
Vendor Query:- Supply, installation, testing and commissioning of 400A '36KA' FP MCCB with spreder links & nessesary accesaries including metal ENCLOSURE Make-Legrand/L&T/Schneider/KEW/LSIS - Please Suggest Type Of Tripping Mechanism, Tmd Or Mp Based?
Reply:- Please consider Thermo magnetic type MCCB.
172 Vendor Query Query:- SECTION B - LT CABLES, CABLE TRAYS, FLOOR TRUNKING - Please Furnish Us Material & Type Of Glands - Single Compression/ Double Compression, As Well As Type Of Lugs
Reply:- consider Single compression gland for DB’s and for UPS I/P & O/P enclosure/Panel use Double compression gland , Use Pin type lugs for DB’s and for higher size of cable use palm type lugs
173 Vendor Query Query:- UPS System - Please share backup time requirement for UPS
Reply:- Please consider 30 Min backup for UPS.
174 Vendor Query:- BMS System - Kindly Provide IO Summary
Reply:- IO summary attached. Please refer annexure.
175 Vendor Query:- Baggage Scanner - Please Provide Vendor Contact Details
19 | P a g e
Reply:- Vender has to find the contact details on his own For all Makes mentioned in Tender.
176 Vendor Query:- 'Supply, installation, testing and commissioning of Under Vehicle Security System - Please Provide Vendor Contact Details
Reply:- Vender has to find the contact details on his own For all Makes.
177 Vendor Query:- Can We Do Site Visit, Please Confirm
Reply:- Yes
178 Vendor Query:- Please Confirm Retention Shall Be Released Against Bank Guarantee Or Not.
Reply:- Condition remain unchanged .Please refer Volume - 1
179 Vendor Query:- Please Confirm Construction Water / Power Scope , Shall Be Provided By Client ?
Reply:- Temporary water, Lighting And Power will be In Vendor Scope
180 Vendor Query:- Please Confirm Any Working Hrs Limitation On Site.
Reply:- Condition remain unchanged .Please refer Volume - 1
181 Vendor Query:- Please Confirm Any Material Movement Limitation On Site.
Reply:- Vendor have to plan their material procurement on his own as per site condition and as per requirement.
182 Vendor Query:- Please Confirm Service Lift Available For Material Movement Or Not.
Reply:- The lift is available however the Bank reserves right to restrict lift use/ not to permit the lift for use for material lifting. In case of non-availability of lift, the vendor will move materials on their own resources and no claim will be admissible in the matter. The lift need to be restored in their original form failing which cost will be recovered from the successful bidder.
183 Vendor Query:- Any Tax Emaxption, Please Confirm.
Reply:- No Exemption will given
184 Vendor Query:- Please Confirm Labour Cess @ 1 % Shall Be Paid By Client Or We Need To Consider In Our Cost.
Reply:- Yes , the labour cess will be deducted from RA Bills of contractors . Therefore the bidder shall consider in their quote.
185
Vendor Query:- EMD should be exempted for MSME Companies. EMD AND Performance security should be accepted in Bank guarantee form. The overall retention should be restricted to 5% (i.e. 2% performance + 3% retention amount.) Post completion said amount can be released against the submitted Bank guarantee.
Reply:- All MSMEs firms having registration as per provisions of the Government of India Policy i.e. registration with District Industries Centre (DIC) or Khadi and Village Industries Commission (KVIC) or Khadi and Industries Board (KVIB) or Coir Board or National Small Industries Commission (NSIC) or directorate of Handicrafts and Handlooms or Udyog Aadhaar Memorandum or any other body specified by Ministry of MSME will be exempted from submission of EMD. The firm must have a valid registration under relevant category failing which their bid will be rejected. The firm must enclosed all relevant documents while submitting the bid.
20 | P a g e
All other clauses will remain unchanged.
186
Vendor Query:- Last date of pre-bid queries should be extended so as the tender submission date for the following reasons as below: a) The Bills of quantities have varied items and hence it will take time to get queries and replies from respective vendors.
Reply:- Please refer Corrigendum 3.
187 Vendor Query:- Mobilization period should be at least 30 days as list of the items to be fulfilled during mobilization period is exhaustive.
Reply:- Condition remain Unchanged.
188 Vendor Query:- The proper break up for release of security deposit as well as retention amount need to be specified. Same is not clear in the tender documents.
Reply:- Please refer Volume - 1
189 Vendor Query: The work and balance sheet should have escalation clause up to 7% per year for pre-qualification.
Reply:- The value of the executed works shall be brought to the current level by enhancing the actual value of work done at a simple rate of 7% per year, calculated from the date of completion to 31.12.2019.
190 Vendor Query:- The Turnover criteria should be 30% of the estimated value. Considering period of completion it should be 50% of the estimated value.
Reply:- Condition remain Unchanged.
191 Vendor Query:- Whether the commercial mall finishing can be considered under corporate office building or institutional work for prequalification criteria?
Reply:- Please refer corrigendum No. 3.
192 Vendor Query:- Request to reduce the government value to 305 of the estimated value i.e. 12 crores. It should be restricted only in Maharashtra.
Reply:- Condition remain Unchanged
193 Vendor Query:- The approval including O.C. should have basic cost items in tender. The scope of contractor should be restricted to only supporting PMC/Architect.
Reply:- Condition remain Unchanged
194 Vendor Query:- The period of completion should be at least 12 months since the work is varied in nature and scope is vast.
Reply:- Condition remain Unchanged
195 Vendor Query:- Value of interim bill should reduce to 1 crore. Material advance should not be restricted to Interim bill value in order to have cash flow and material delivery in time.
Reply:- Condition remain Unchanged
196 Vendor Query:- Final bill certification should be reduced to 30 days from 50 days & payment within 15 days of final bill. All RA bill should be certified in 7 days and payment in next seven days.
Reply:- Condition remain Unchanged
197 Vendor Query:- Since temporary Water supply and electricity is already available with the owner. It will be difficult to have one more temporary connection. Owner can give connection on actual chargeable basis.
21 | P a g e
Reply:- Temporary water, Lighting And Power will be In Vendor Scope.
198 Vendor Query:- since the work would be round the clock basis. It will be difficult for the labor to travel. We request you to provide accommodation on site.
Reply:- Condition remain Unchanged
199 Vendor Query:- Allowable period to submit Bar chart/PERT chart within 30 days after the approval of all material (So that lead period can be considered)
Reply:- Condition remain Unchanged
200 Vendor Query:- Subletting should be allowed as the work is varied in nature and special expertise team might require for all the specialized activities.
Reply:- Condition remain Unchanged
201 Vendor Query:- Subject to approval of EIC & PMC, Request to allow holiday/Night Shift since the work is urgent in nature.
Reply:- Condition remain Unchanged
202
Vendor Query:- Request to delete the said clause 2.4.0 on Page 72 of GC States: In case if the Contractor falls to take necessary steps, the PMC/Architect shall be entitled to cause them to be taken and recover cost thereof from the Contractor. Provided that if any steps, taken by the Contractor in meeting his obligations under this clause involves the Employer in additional supervision costs, such costs shall, after due consultation with the Employer and the Contractor, be determined by the PMC/ ARCHITECT and shall be recoverable from the Contractor by the Employer, and shall be Deducted by the PMC/ ARCHITECT from any monies due or to become due to the contractor And The PMC/ARCHITECT shall notify the Contractor accordingly, with a copy to the Employer.
Reply:- No - Condition remain Unchanged
203
Vendor Query:- Page 75 of GCC Clause d should not be applicable as under the said contract, the contractor shall remain liable for any default during maintenance period and has to attain the rectification. Hence 21 days period and additional undertaking should not be required.
Reply:- Condition remain Unchanged
204 Vendor Query:- With regards to the make list we request you to add the below mentioned makes to existing makes. We have marked the makes to be included in RED and attached with this letter.
Reply:- Make list remain unchanged. Please refer annexure/ Corrigendum.
205 Vendor Query:- Item on truck basis or cum basis to be given for removal of debris as ascertaining lump sum Quantities would be difficult
Reply:- Condition remain Unchanged.
206 Vendor Query:- Item for liasioning should be lump sum item in BOQ
Reply:- Condition remain Unchanged
207 Vendor Query:- Clearing by professional agency should be a payable item in BOQ.
Reply:- No.
208 Vendor Query:- Prequalification Condition 10 mentions: “Should possess in name of company or nominated sub-contractor valid license for executing
22 | P a g e
water supply, sanitary, drainage works, Firefighting, fire detection and electrification, HVAC, IBMS works and AV systems” – However there are no licenses available for HVAC, IBMS, AV and fire Detection system . Registration exists for plumbing, electrical an firefighting system. Hence kindly change the condition accordingly.
Reply:- Please consider the services wherever clause applicable as per prevailing market practice i.e. water supply, sanitary, Firefighting, and electric works etc. In case of sub-contract, The successful bidder will submit the complete details of the agency for approval. The agency will be approved by the bank and their decision will be final in the matter.
List of makes (For all items): The successful bidder will submit the complete details of the make/agency for approval. The make/agency will be approved by the bank and their decision will be final in the matter.