At the end of this chapter you should be able to:

• Describe a single-phase supply

• Describe a three-phase supply

• Understand a star connection, and recognise that IL =Ip and VL = √3Vp

• Draw a complete phasor diagram for a balanced, star connected load

• Understand a delta connection, and recognise that VL =Vp and IL =3Ip

• Draw a phasor diagram for a balanced, delta connected load

• Calculate power in three-phase systems using P=√3 VLIL cos Ø

• Appreciate how power is measured in a three-phase system, by the one two and three-wattmeter methods

• Compare star and delta connections

• Appreciate the advantages of three-phase systems

Page 3: Bab 3- Sistem 3 Fasa Update 13 Nov2011

3.1 Introduction Generation, transmission and distribution of electricity via the National Grid system is accomplished by three phase alternating currents.

The voltage induced by a single coil when rotated in a uniform magnetic field is shown in Figure and is known as a single-phase voltage.

Page 4: Bab 3- Sistem 3 Fasa Update 13 Nov2011

3.1 Introduction Most consumers are fed by means of a single-phase a.c. supply.

Two wires are used, one called the live conductor (usually coloured red) and the other is called the neutral conductor (usually coloured black).

The neutral is usually connected via protective gear to earth, the earth wire being coloured green.

The standard voltage for a single phase a.c. supply is 240V.

The majority of single-phase supplies are obtained by connection to a three-phase supply

Page 5: Bab 3- Sistem 3 Fasa Update 13 Nov2011

3.2 Three-Phase SupplyA three-phase supply is generated when three coils are placed 120◦ apart and the whole rotated in a uniform magnetic field

Page 6: Bab 3- Sistem 3 Fasa Update 13 Nov2011

3.2 Three-Phase Supply The convention adopted to identify each of the phase voltages

is: R-red,Y-yellow, and B-blue,. The phase-sequence is given by the sequence in which the

conductors pass the point initially taken by the red conductor. The national standard phase sequence is R,Y, B.

Page 7: Bab 3- Sistem 3 Fasa Update 13 Nov2011

3.3 Three Phase Connection If the three-phase windings are kept independent

then six wires are needed to connect a supply source (such as a generator) to a load (such as motor).

To reduce the number of wires it is usual to interconnect the three phases.

There are two ways in which this can be done, these being:

i. a star connection

ii. a delta connection

Page 8: Bab 3- Sistem 3 Fasa Update 13 Nov2011

3.3 Three Phase Connection

Star connection (3 phase - 3 Wires)

R

Y

B

ZR

ZB ZY

Page 9: Bab 3- Sistem 3 Fasa Update 13 Nov2011

3.3 Three Phase Connection

Star connection (3 phase - 4 Wires)

R

Y

B

N

ZR

ZB ZY

Page 10: Bab 3- Sistem 3 Fasa Update 13 Nov2011

3.3 Three Phase ConnectionDelta connection

R

Y

B

ZRB ZRY

ZBY

Page 11: Bab 3- Sistem 3 Fasa Update 13 Nov2011

3.4 Star Connection

VR, VY and VB are called phase voltages or line to neutral voltages. ( generally denoted by VP).

VRY, VYB and VBR are called line voltages

Page 12: Bab 3- Sistem 3 Fasa Update 13 Nov2011

3.4 Star Connection

IR, IY and IB line current (denoted by IL)= Phase current denoted by IP

For a star connection IL=IP

Page 13: Bab 3- Sistem 3 Fasa Update 13 Nov2011

3.4 Star ConnectionFor a balanced system

Page 14: Bab 3- Sistem 3 Fasa Update 13 Nov2011

3.4 Star Connection

VRY =VR −VY

VRY =VR +(−VY))

By trigonometry, or by measurement,

Page 15: Bab 3- Sistem 3 Fasa Update 13 Nov2011

3.4 Star ConnectionThe star connection of the three phases of a supply, together with a neutral conductor, allows the use of two voltages — the phase voltage and the line voltage.

A 4-wire system is also used when the load is not balanced. The standard electricity supply to consumers in Malaysia is 415/240V, 50 Hz, 3-phase, 4-wire alternating current

Page 16: Bab 3- Sistem 3 Fasa Update 13 Nov2011

3.4 Star Connection

Page 17: Bab 3- Sistem 3 Fasa Update 13 Nov2011

3.4 Star Connection

Page 18: Bab 3- Sistem 3 Fasa Update 13 Nov2011

3.4 Star Connection

Page 19: Bab 3- Sistem 3 Fasa Update 13 Nov2011

3.4 Star Connection

(i) Draw VR =VY =VB =240V and spaced 120◦ apart

(ii) Power factor= cos φ=0.966 lagging phase angle is given by cos−1(0.966)=15◦IR =IY =IB =5A, lagging VR, VY and VB respectively by 15◦.

(iii) VRY =VR −VY

VYB =VY −VB

VBR =VB −VR

VR=240V

VY=240VVB=240V

IR=5A

IY=5A

IB=5A

15˚

VRY=415V

30˚

VYB=415V

VBR=415V

Page 20: Bab 3- Sistem 3 Fasa Update 13 Nov2011

3.4 Star Connection

Page 21: Bab 3- Sistem 3 Fasa Update 13 Nov2011

3.4 Star Connection

Page 22: Bab 3- Sistem 3 Fasa Update 13 Nov2011

3.5 Delta Connection

VRY, VYB and VBR phase voltages

For delta connection VP=VL

Page 23: Bab 3- Sistem 3 Fasa Update 13 Nov2011

3.5 Delta Connection

IR =IRY −IBR =IRY +(−IBR)

Page 24: Bab 3- Sistem 3 Fasa Update 13 Nov2011

3.5 Delta Connection

IR =IRY −IBR =IRY +(−IBR)

By trigonometri @ measurement

Page 25: Bab 3- Sistem 3 Fasa Update 13 Nov2011

3.5 Delta Connection

Page 26: Bab 3- Sistem 3 Fasa Update 13 Nov2011

3.5 Delta Connection

1

Page 27: Bab 3- Sistem 3 Fasa Update 13 Nov2011

3.5 Delta Connection

Page 28: Bab 3- Sistem 3 Fasa Update 13 Nov2011

3.5 Delta Connection

Page 29: Bab 3- Sistem 3 Fasa Update 13 Nov2011

3.5 Delta Connection

Thus when the load is connected in delta,

three times the line current is taken from the supply than is taken if connected in star.

Page 30: Bab 3- Sistem 3 Fasa Update 13 Nov2011

3.6 Power in three-phase systems The power dissipated in a three-phase load is given by the sum of the power dissipated in each phase

If a load is balanced then the total power P is given by:

P=3×power consumed by one phase.

The power consumed in one phase= or

VpIp cos Ø

(where Ø is the phase angle between Vp and Ip).

p2pRI

Page 31: Bab 3- Sistem 3 Fasa Update 13 Nov2011

3.6 Power in three-phase systems

For a star connection,

Page 32: Bab 3- Sistem 3 Fasa Update 13 Nov2011

3.6 Power in three-phase systems

For a delta connection,

Page 33: Bab 3- Sistem 3 Fasa Update 13 Nov2011

3.6 Power in three-phase systemsHence for either a star or a delta balanced connectionthe total power P is given by:

Total volt-amperes

Page 34: Bab 3- Sistem 3 Fasa Update 13 Nov2011

3.6 Power in three-phase systems

Page 35: Bab 3- Sistem 3 Fasa Update 13 Nov2011

3.6 Power in three-phase systems

Page 36: Bab 3- Sistem 3 Fasa Update 13 Nov2011

3.6 Power in three-phase systems

Page 37: Bab 3- Sistem 3 Fasa Update 13 Nov2011

3.6 Power in three-phase systems

Page 38: Bab 3- Sistem 3 Fasa Update 13 Nov2011

3.6 Power in three-phase systems

Page 39: Bab 3- Sistem 3 Fasa Update 13 Nov2011

3.6 Power in three-phase systems

Hence loads connected in delta dissipate three times the power than when connected in star, and also take a line current three times greater

Page 40: Bab 3- Sistem 3 Fasa Update 13 Nov2011

3.7 Measurement of power in three-phase systems

(i) One-wattmeter method for a balanced load

Page 41: Bab 3- Sistem 3 Fasa Update 13 Nov2011

3.7 Measurement of power in three-phase systems

(ii) Two-wattmeter method for balanced or unbalanced loads

Page 42: Bab 3- Sistem 3 Fasa Update 13 Nov2011

3.7 Measurement of power in three-phase systems

(iii) Three-wattmeter method for a three-phase, 4-wire system for balanced and unbalanced loads

Page 43: Bab 3- Sistem 3 Fasa Update 13 Nov2011
Page 44: Bab 3- Sistem 3 Fasa Update 13 Nov2011