BA444DF-F FOUNDATION fieldbus Issue 3Issue: 3 23rd June 2011 BA444DF-F FOUNDATION fieldbus...

26
Issue: 3 23 rd June 2011 BA444DF-F FOUNDATION™ fieldbus Intrinsically safe Field mounting 8 variable Fieldbus Indicator Issue 3 ul. Lechicka 14 ; 02-156 Warszawa Fax. (+48 022) 846 50 37 [email protected] TR Automatyka Sp. z o. o. Tel. (+48 022) 886 10 16 www.trautomatyka.pl

Transcript of BA444DF-F FOUNDATION fieldbus Issue 3Issue: 3 23rd June 2011 BA444DF-F FOUNDATION fieldbus...

  • Issue: 323rd June 2011

    BA444DF-FFOUNDATION™ fieldbus

    Intrinsically safeField mounting

    8 variableFieldbus Indicator

    Issue 3

    ul. Lechicka 14 ; 02-156 Warszawa Fax. (+48 022) 846 50 37 [email protected] Automatyka Sp. z o. o. Tel. (+48 022) 886 10 16 www.trautomatyka.pl

  • 2

    1. Description1.1 Documentation

    2. Operation2.1 Error messages

    3. Intrinsic Safety Certification3.1 ATEX certificate3.2 Zones, gas groups and T rating3.3 Fieldbus connection3.4 Certification Iabel Information

    4. System Design for Hazardous Area4.1 FISCO Systems4.2 Non-FISCO Sysems

    5. Installation5.1 Location5.2 Installation procedure5.3 EMC

    6. Configuration6.1 Configuration menus6.2 Node configuration menu

    6.2.1 Reset to node factory defaults6.2.2 Change from node to listener6.2.3 Access code for node

    configuration menu.6.3 Listener configuration menu

    6.3.1 Access6.3.2 Summary of listener functions6.3.3 Scan fieldbus segment6.3.4 List configured input

    parameters.6.3.5 Enter address & display

    parameters.6.3.6 Enable selected input6.3.7 Enter Device Address6.3.8 Enter Variable Identity6.3.9 Decimal point position6.3.10 Configuration of bargraph6.3.11 Scale numeric display6.3.12 Access code for listener

    configuration menu.6.3.13 Change from listener to node6.3.14 Reset the indicator to listener

    factory defaults.

    7. Maintenance7.1 Fault finding during commissioning7.2 Fault finding after commissioning7.3 Servicing7.4 Routine maintenance7.5 Guarantee7.6 Customer comments

    8. Accessories8.1 Scale and Tag marking8.2 Tag plate8.3 Pipe mounting kits

    Appendix 1ATEX dust certification

    Appendix 2FM Approval for use in the USA andcFM Approval for use in Canada.

    Appendix 3IECEx certification

    CONTENTS

    The BA444DF-F is CE marked to show compliance with the European Explosive AtmospheresDirective94/9/EC and the European EMC Directive 200 4/108/EC

  • 3

    1. DESCRIPTIONThe BA444DF-F fieldbus indicator is an intrinsicallysafe FOUNDATION™ fieldbus instrument that maybe configured as a fieldbus node or as a fieldbuslistener. It can display up to eight fieldbus processvariables on a five digit LCD and 31 segmentanalogue bargraph. The instrument is buspowered so no additional power supply is required.

    As a fieldbus node the indicator is configured viathe fieldbus host.

    Communication Fieldbus Fun ction Protocol Blocks

    FOUNDATION™ fieldbus Input Selector (2 x IS) Digital input (6 x DI)

    Device Description files may be downloaded fromthe Fieldbus Foundation or from the BEKAassociates websites.

    When configured as a fieldbus listener theBA444DF-F is not visible to the fieldbus host andcan only be configured using the push buttons onthe front of the instrument.

    Housed in a robust IP66 glass reinforced polyester(GRP) enclosure with a toughened glass window,the BA444DF-F is surface mounting, or may bepipe mounted using one of the accessory kits.

    The instrument is intrinsically safe and has beencertified by European Notified Body IntertekTesting and Certification Ltd (ITS) to harmonisedATEX explosive gas and combustible duststandards, confirming compliance with EuropeanATEX Directive 94/9/EC. ATEX dust certificationis an option – see Appendix 1.

    For use in the USA and Canada, the BA444DF-Fis available with optional intrinsic safety andnonincendive FM and cFM Approval – seeAppendix 2.

    For international applications, all versions of theBA444DF-F fieldbus listener have IECEx intrinsicsafety approval allowing installation in explosivegas atmospheres. IECEx dust certification isavailable as an option – see Appendix 3.

    The instrument’s communication protocol is shownon a label inside the terminal cover. The ‘-F’ ordercode suffix also indicates the protocol but is notshown on the instrument certification label. Thereis an alternative version of the fieldbus display,order code BA444DF-P for use on PROFIBUS PAnetworks

    1.1 DocumentationThis instruction manual describes ATEX systemdesign and installation of the BA444DF-F fieldbusindicator.

    System design information for non-ATEX and dustapprovals is shown in appendices to this manual.

    2. OPERATIONThe BA444DF-F fieldbus indicator can display upto eight pre-configured FOUNDATION™ fieldbusprocess variables designated in-1 to in-8. Theoperator can select which variable is displayedusing the ▼and ▲ push buttons which scroll thedisplay through the eight inputs. A numericannunciator on the left hand side of the displayshows which of the eight inputs is currently beingdisplayed.

    2.1 Error messagesWhen the BA444DF-F is configured as a listenerthe following error messages may be displayed:

    ‘no ConF’ No inputs have beenconfigured or are enabled.

    ‘no dAtA’ No data is being receivedwith the current configuration.

    3. INTRINSIC SAFETY CERTIFICATION

    3.1 ATEX certificateThe BA444DF-F has been issued with an EC-TypeExamination Certificate by Notified Body IntertekTesting and Certification Ltd (ITS) which has beenused to confirm compliance with the EuropeanATEX Directive 94/9/EC for Group II, Category 1gas atmospheres, Ga Ex ia IIC T4 and for dustatmospheres Ex iaD 20 T100ºC IP66. TheBA444DF-F is also FISCO compliant. Theinstrument bears the Community Mark and, subjectto local codes of practice, may be installed in anyof the European Economic Area (EEA) membercountries. ATEX certificates are also acceptablefor installations in Switzerland.

    This manual describes ATEX installations inexplosive gas atmospheres which conform withEN60079:Part14 Electrical Installation inHazardous Areas. When designing systems forinstallation outside the UK, the local Code ofPractice should be consulted.

    For use in the presence of combustible dust,please refer to Appendix 1 that describes ATEXinstallations complying with EN 61241: Part 14.

    ATEX certificates and BEKA Declarations ofConformity may be downloaded from the BEKAwebsite at www.beka.co.uk

  • 4

    3.2 Zones, gas groups and T ratingThe BA444DF-F has been issued with EC TypeExamination certificate ITS06ATEX25313confirming that it complies with the requirementsfor Group II Category 1G Ga Ex ia IIC T4Tamb = –40 to 70ºC specified in the ATEXDirective. When connected to a suitable certifiedsystem the BA444DF-F may be installed in:

    Zone 0 explosive gas air mixturecontinuously present.

    Zone 1 explosive gas air mixturelikely to occur in normaloperation.

    Zone 2 explosive gas air mixture notlikely to occur, and if it does willonly exist for a short time.

    Be used with gases in groups:Group A propaneGroup B ethyleneGroup C hydrogen

    Having a temperature classification of:T1 450ºCT2 300ºCT3 200ºCT4 135ºC

    At an ambient temperature between –40 & +70ºC.

    Note: minimum guaranteed operating temperatureis –20ºC.

    This allows the BA444DF-F fieldbus indicator to beinstalled in all Zones and to be used with mostindustrial gases.

    3.3 Fieldbus connectionThe BA444DF-F Indicator is powered and receivesdata via the H1 fieldbus, which is connected toterminals 1 and 2. These terminals are non-polarised, comply with the Fieldbus IntrinsicallySafe Concept (FISCO) defined in IEC 60079 Part27 and also have separate entity parameters asshown below:

    FISCO EntityUi = 17.5V dc 22.0V dcIi = 380mA dc 250mA dcPi = 5.32W 1.2W

    The maximum equivalent capacitance andinductance at terminals 1 & 2 is:

    Ci = 0nFLi = 8µH

    3.4 Certification Label InformationThe certification information label is fitted in arecess on the top outer surface of the enclosure. Itshows details of the ATEX certification, astatement that the instrument is a FISCO FieldDevice, plus BEKA associates name and location.IECEx approval information is also included. Thelabel for some versions of the instrument will alsocontain non-European certification information.

    The instrument serial number and year ofmanufacture are recorded on a separate labelinside the terminal compartment.

    4. SYSTEM DESIGN FOR HAZARDOUS AREAS

    4.1 FISCO SystemsThe BA444DF-F fieldbus indicator may beconnected to any ATEX certified FISCO compliantfieldbus segment, providing the segment cansupply the additional 13mA required to operate theinstrument.

    Fig 1 shows a typical fieldbus segment. To complywith FISCO requirements, the power supply,terminators, field devices and the interconnectingcables must conform with IEC60079 part 27.

    Fig 1 FISCO fieldbus system

  • 5

    4.2 Non-FISCO SystemsFor non-FISCO applications the BA444DF-Ffieldbus indicator has a higher voltage entityintrinsic safety input parameter allowing connectionto a wide range of fieldbus segments.

    The BA444DF-F fieldbus indicator may beconnected to any intrinsically safe segmentproviding:

    The device powering the fieldbus segment isATEX certified and has output parametersequal to or less than:

    Uo = 22V dcIo = 250mA dcPo = 1.2W

    The segment can provide an additional 13mAto power the fieldbus listener.

    The equivalent internal capacitance Ci of theBA444DF-F fieldbus listener is zero and theequivalent internal inductance is insignificant.Therefore these BA444DF-F parameters do notneed to be considered.

  • 6

    5. INSTALLATION

    5.1 LocationThe BA444DF-F FOUNDATION™ fieldbusindicator is housed in a robust IP66 glassreinforced polyester (GRP) enclosure incorporatingan armoured glass window and stainless steelfittings. It is suitable for exterior mounting in mostindustrial environments, including offshore andwastewater treatment installations. Please consultBEKA associates if high vibration is anticipated.

    The BA444DF-F enclosure is surface mounting.Accessory kits described in sections 8.3 of thismanual enable the instrument to be mounted ontoa vertical or horizontal pipe.

    The field terminals and the two mounting holes arelocated in a separate compartment with a sealedcover allowing the instrument to be installedwithout exposing the display assembly.

    The BA444DF-F earth terminal is connected to thecarbon loaded GRP enclosure. If this enclosure isnot bolted to a post or structure connected to theplant potential equalising network, the instrument’searth terminal should be connected to thepotential equalising network as recommenced inEN 60079-14.

    The BA444DF-F enclosure is supplied with abonding plate to ensure electrical continuitybetween the three conduit / cable entries.

    5.2 Installation ProcedureFig 2 illustrates the instrument installationprocedure.

    a. Remove the instrument terminal cover byunscrewing the two captive 'A' screws.

    b. Mount the instrument on a flat surface andsecure with two M6 screws through the 'B'holes. Alternatively use one of the mountingkits described in section 8.3

    c. Remove the temporary dust seals from thethree cable entries and install the requiredglands, conduit fittings or blanking plugs.Note : The temporary dust seals fitted fortransit do not maintain the IP66 protection ofthe BA444DF-F enclosure.Cable glands, conduit fittings, blanking plugsand cables must be suitable for continuoususe at the maximum operating temperatureof the instrument.

    d. Connect the field wiring to the terminals asshown in Fig 3.

    e. Replace the instrument terminal cover andevenly tighten the two 'A' screws.

    Fig 2 BA444DF-F installation procedure

    5.3 EMCThe BA444DF-F complies with the requirements ofthe European EMC Directive 2004/108/EC. Forspecified immunity, all wiring should be inscreened twisted pairs with the screens earthed atone point in the safe area.

    Fig 3 Dimensions and terminal connections

  • 7

    6. CONFIGURATIONThe BA444DF-F 8 variable FOUNDATION™fieldbus indicator may be configured as a fieldbusnode or as a fieldbus listener. When used as afieldbus node the indicator is configured via thefieldbus host. For detailed node conditioninginformation please refer to the BEKAFOUNDATION™ fieldbus Interface Guide whichmay be downloaded from www.beka.co.uk

    As a fieldbus listener the BA444DF-F is not visibleto the fieldbus host and can only be configured viathe front panel push buttons using the menushown in Fig 6.

    Throughout this manual the four BA444DF-F pushbuttons are identified P E ▼ ▲ and legendsdisplayed by the fieldbus indicator are shownwithin inverted commas e.g. ‘CodE’ and ‘LiSt’.

    6.1 Configuration menusThe configuration menu is separated into twosections, fieldbus node and fieldbus listener. Bothcontain the ‘tYPE’ function that enables transferbetween the two. Unless otherwise requestedwhen ordered, all FOUNDATION™ fieldbusBA444DF-F indicators are supplied as fieldbusnodes but can easily be reconfigured on-site.

    6.2 Node configuration menuThe node configuration menu is shown in Fig 4.Access to the menu is obtained by operating the Pand E buttons simultaneously. If the BA444DF-Fis not protected by an access code the firstparameter 'rESEt’ will be displayed*. If theinstrument is protected by an access code, ‘CodE’will be displayed first. Pressing P will allow thefour digit security code to be entered digit by digitusing the ▼ or ▲ button to adjust the flashing digitand P to move control to the next digit. When thecorrect code has been entered, pressing E willcause the first parameter ‘rESEt’ to be displayed*.If an incorrect code is entered, or no button ispressed for ten seconds, the BA444DF-F willautomatically return to the display mode.

    * If the indicator displays ‘SCAn’ it is conditionedas a fieldbus listener, see section 6.3.13 to changeit to a fieldbus node.

    6.2.1 Reset the indicator to node factory defaults ‘rESEt’The BA444DF-F may be reset to the factorydefaults that are shown below:

    Security Code 0000 (disabled)Device address UnconfiguredLast variable 8

    For each of the eight inputs:Decimal point XXX.XXBar Type LeftBar lower limit 0.0Bar Upper limit 100.0Gain 1.0Offset 0.0

    To reset the BA444DF-F select ‘rESEt’ in theconfiguration menu by operating the ▼ or ▲button. To enter the function press P which willreveal ‘0000’ with the left hand digit flashing. Toprevent accidental use of this function, ‘5urE’ mustbe entered to confirm that the instrument is to bereset.

    Using the ▼ or ▲ button set the flashing digit to ‘5’and press the P button to move control to the nextdigit which should be set to ‘u’. When the fourletters of ‘5urE’ have been entered operating the Ebutton will reset the BA444DF-F to the factorydefaults.

    CAUTIONAll the instrument’s node configurationand links will be lost when it is reset.

    6.2.2 Change from node to listener ‘tYPE’This function enables the instrument to bechanged from a fieldbus node to a fieldbus listener.Select ‘tYPE’ in the node configuration menu usingthe ▼ or ▲ button. To enter the function press Pwhich will show that the instrument is configuredas a fieldbus node, to change to a fieldbus listenerpress the ▼ or ▲ button which will toggle thedisplay to ‘LStnr’ To prevent accidental changesthis request must be confirmed by operating the Pbutton and entering ‘5urE’. The instrument willdisplay ‘0000’ with the first digit flashing, using the▼ or ▲ button set the flashing digit to ‘5’ and pressthe P button to move control to the next digit whichshould be set to ‘u’. When the four letters of ‘5urE’have been entered, operating the E button willcause the instrument to restart as a fieldbuslistener in the display mode.

    CAUTIONAll the instrument’s node configurationand links will be lost when it is changedfrom a fieldbus node to a fieldbuslistener.

  • 8

    6.2.3 Access code for node configuration menu ‘CodE’Access to the node configuration menu may beprotected by a four digit security code which mustbe entered to gain access. New instruments aresupplied configured with the default code 0000which disables this protection and allowsunrestricted access to the configuration menu.

    To enter a new access code select ‘CodE’ in theconfiguration menu by operating the ▼ or ▲button. To enter the function press P which willreveal the current access code with one digitflashing. The code may be changed using the ▼ or▲ button to adjust the flashing digit and the Pbutton to move control to the next digit. When therequired code has been selected, press E to enterthe selection and return to the ‘CodE’ prompt in theconfiguration menu. The revised access code willbe activated when the indicator is returned to thedisplay mode.

    If the access code is lost please contact BEKAassociates.

    Fig 4 Node configuration menu

    6.3 Listener configuration menuThe listener configuration menu is separated intothree sections, ‘SCAn’, ‘LISt’ and ‘Edit’, plus threehousekeeping functions ‘CodE’, ‘tYPE’ and ‘rESEt’as shown in Fig 6.

    ‘SCAn’ is the simplest method of configuration ifthe fieldbus Device Address and Variable Identityof the data to be displayed by the BA444DF-Flistener are not known.

    In the ‘SCAn’ function pressing the P buttoncauses the BA444DF-F indicator to search thefieldbus segment to which it is connected for allpublishers. Fig 5 shows how the indicator displaysthe hexadecimal Device Address and VariableIdentity associated with each publisher.

    A Publisher is a device that places it's outputdata onto the bus as part of a cyclical pre-determined data exchange schedule.

    The Device Address is a unique address thatidentifies each fieldbus instrument connected tothe bus.

    The Variable Identity is the fieldbus deviceData Link Connection End Point (DLCEP)which identifies each Function Block output(process variable) transmitted by a fieldbusdevice such as flow and temperaturetransmitted by a fieldbus flowmeter.

    The ▼ and ▲ push buttons scroll the displaythrough all the publishers on the segment showingthe Device Address and Variable Identity for eachone - see Fig 5. To aid identification, operatingthe P button will preview the value of the data ateach selected address, if required it may then beallocated to one of the eight BA444DF-F listenerinputs in-1, to in-8 by operating the P button again.If the format of the data at the selected DeviceAddress and Variable Identity is not DS-65 (float +status) ‘no dAt’ will be displayed.

    Fig 5 Device Address and Variable Identity

    If the Device Address and Variable Identity of theprocess variable to be displayed by the BA444DF-F indicator are known, they may be directlyentered via the edit sub-menu. This sub-menualso provides full control of both the numeric andbargraph display parameters.

  • 9

    6.3.1 AccessAccess to the listener configuration menu isobtained by operating the P and E buttonssimultaneously. If the BA444DF-F is not protectedby an access code the first parameter 'SCAn’ willbe displayed.* If the indicator is protected by anaccess code, ‘CodE’ will be displayed first.Pressing P will allow the four digit security code tobe entered digit by digit using the ▼ or ▲ button toadjust the flashing digit and P to move control tothe next digit. When the correct code has beenentered, pressing E will cause the first parameter‘SCAn’ to be displayed.* If an incorrect code isentered, or no button is pressed for ten seconds,the indicator will automatically return to the displaymode.

    * If the indicator displays ‘rESEt’ it is conditionedas a fieldbus node, see section 6.2.2 to change itto a fieldbus listener.

    6.3.2 Summary of listener configuration functions.This section contains a summary of all the listenerconfiguration functions including a reference tomore detailed information. It should be read inconjunction with Fig 6.

    Indicator Summary display of function

    ‘SCAn’ Scan fieldbus segment Identifies all publishers on the fieldbussegment to which the listener isconnected and enables selected data tobe allocated to one of the eight listenerinputs.See section 6.3.3

    ‘LiSt’ List configured input parametersFor each of the eight BA444DF-Flistener input, in-1 to in-8 shows if theinput is enabled and the allocatedDevice Address and Variable Identity.Parameters can not be changed fromwithin this function.See section 6.3.4

    ‘Edit’ Enter addresses and displayparametersContains six sub-functions that enableknown fieldbus Device Address andVariable Identity to be entered and alldisplay parameters adjusted for each ofthe eight fieldbus listener inputs.See section 6.3.5

    ‘Enb’ Enable listener inputEach of the eight listener inputs in-1to in-8 may be enabled or disabledwithout affecting any parameters.See section 6.3.6

    ‘Adr’ Enter fieldbus Device AddressAllows hexadecimal fieldbus deviceaddress for each of the eight listenerinputs in-1 to in-8 to be entered.See section 6.3.7

    ‘id’ Enter Variable IdentityAllows hexadecimal Variable Identityfor each listener input in-1 to in-8 tobe entered.See section 6.3.8

    ‘dP’ Decimal point positionDefines position of displayed decimalpoint for each listener input in-1 toin-8.See section 6.3.9

    ‘bAr’ Configuration of bargraph display.Defines bargraph type, plus digitaldisplay at which bargraph is zero andfull scale for each listener input in-1 toin-8.See section 6.3.10

    ‘SCALE’ Scale numeric displayApplies zero offset and scale factor tothe numeric display for each listenerinput in-1 to in-8.See section 6.3.11

    ‘CodE’ Access code for listenerconfiguration menuEnters a four digit security accesscode for configuration menu. Defaultcode 0000 disables this function.See section 6.3.12

    ‘tYPE’ Change from listener to nodeChanges the function of the fieldbusindicator from a listener to a node.See section 6.3.13

    ‘rESEt’ ResetReturns the BA444DF-F listener tofactory defaults.See section 6.3.14

  • 10

  • 11

    6.3.3 Scan fieldbus segment ‘SCAn’If the Device Address and Variable Identity of aprocess variable are not known, the ‘SCAn’function provides a simple way to identify them.This function scans the fieldbus segment to whichthe BA444DF-F indicator is connected andidentifies all the publishers. To aid identification itenables the value of each process variable to bepre-viewed and, if required, allocated to one of theeight BA444DF-F Fieldbus indicator inputs.

    The BA444DF-F indicator only supports DS-65formatted data (float + status) which is the usualformat for analogue process variables. The‘SCAn’ function will identify all publishers on thesegment irrespective of format, but when pre-viewed, non DS-65 formatted data will produce a‘no dAt’ error message.

    ‘SCAn’ is the first function displayed when enteringthe listener configuration menu, or it may beselected from within the menu by operating the ▼or ▲ button. To scan the fieldbus segment towhich the indicator is connected for all publisheddata press P which will reveal the hexadecimalDevice Address and Variable Identity of the firstpublisher found as shown in Fig 5. If there ismore than one publisher operating the ▼ or ▲button will scroll though all of them.

    If no cyclic data is being published on the fieldbussegment the BA444DF-F indicator will display‘noPub’.

    When the Device Address and Variable Identity ofa process variable is being displayed, pressing Pwill preview the value of the process variabledisplayed with maximum resolution on the five digitdisplay. If this confirms that it is one of theprocess variables to be displayed, it may beallocated to one of the eight BA444DF-F listenerinputs in-1 to in-8.

    To select the required indicator input press P todisplay the first input in-1, operating the ▼ or ▲button will scroll the display through the otherinputs. When the required input is displayedpressing E will allocate the selected processvariable to the selected input and return the displayto the Device Address and Variable Identity fromwhich another process variable may be selected.

    When a process variable is allocated to a indicatorinput any previous allocation will be overwritten.

    6.3.4 List configured input parameters ‘LiSt’The ‘LiSt’ function enables the Device Address andVariable Identity allocated to each lindicator inputto be viewed without danger of it being accidentallychanged.

    The ‘LiSt’ function may be selected from within themenu by operating ▼ or ▲ button. To enter thefunction press P which will display the indicatorinput currently selected in the display mode, otherinputs may be selected using the ▼ or ▲ button.Operating the P button will cause the followingparameters for the selected input to be displayedsequentially:

    Display Explanation‘Enb: Y or N’ Input Enabled yes or no‘Adr: 00’ Device Address ‘id: 00’ Variable Identity

    The display then automatically returns to theselected BA444DF-F indicator input from whereanother input may be selected.

    If one of the eight BA444DF-F indicator’s inputs in-1 to in-8 has not had a Device Address andVariable Identity allocated to it, ‘LiSt’ will show bothas invalid address FF.

    6.3.5 Enter address & display parameters ‘Edit’The ‘Edit’ function may be selected from within themenu by operating ▼ or ▲ button. To enter thefunction press P which will display the indicatorinput currently selected in the display mode, otherlistener inputs may be selected using the ▼ or ▲button. When the required input has beenselected operating the P button will enter the editsub-menu at ‘Enb’ for the selected input.

    6.3.6 Enable selected input ‘Enb’‘Enb’ turns the indicator input selected in the Editfunction on or off without affecting the conditioning.To enter the function press P which will revealwhether the selected input is ‘on’ or ‘oFF’.Operating the ▼ or ▲ buttons will toggle betweenthe two conditions. When set as requiredoperating the E button will enter the selection andreturn to the edit sub-menu.

  • 12

    6.3.7 Enter Device Address ‘Adr’This function allows a known fieldbus DeviceAddress to be entered and allocated to theindicator input selected in the Edit function. Toenter the function press P which will reveal theexisting two digit hexadecimal address with onedigit flashing which may be changed by operatingthe ▼ or ▲ button. When set as requiredoperating the P button will transfer control to thesecond digit that may be adjusted in the sameway. When both digits are set as requiredoperating the E button will enter the selection andreturn to the ‘Adr’ prompt in the edit sub-menu.

    6.3.8 Enter Variable Identity ‘id’Enables a known Variable Identity to be enteredand allocated to the indicator input selected in theEdit function. To enter the function press P whichwill reveal the existing two digit hexadecimaladdress with one digit flashing which may bechanged by operating the ▼ or ▲ button. Whenset as required operating the P button will transfercontrol to the second digit that may be adjusted inthe same way. When both digits are set asrequired operating the E button will enter theselection and return to the ‘id’ prompt in the editsub-menu.

    6.3.9 Decimal point position ‘dP’Defines the position the decimal point in thenumeric display. To enter the function press Pwhich will reveal the existing decimal pointposition. Operating the ▼ or ▲ button will movethe decimal point to the required position, omit it,or activate all the decimal points whichautomatically provides maximum resolution in thedisplay mode irrespective of the numeric value.When positioned as required, operating the Ebutton will enter the selection and return to the ‘dP’prompt in the edit sub-menu.

    6.3.10 Configuration of bargraph display‘bAr’This function contains three sub-functions thatenable the bargraph, justify its position and definethe relationship between the bargraph and theinstrument’s numeric display.

    Sub-function ‘b.tYPE’ allows the bargraph to beleft, centre or right justified, or to be turned off.Sub-functions ‘bArLo’ and ‘bArhi’ define thelistener’s numeric display at which the bargraphstarts and is at full scale.

    The ‘bAr’ function may be selected from within theedit sub-menu by operating the ▼ or ▲ button.To enter the function press P which will display the‘b.tYPE’ sub-function, pressing P again will revealthe existing bargraph justification.

    The ▼ or ▲ button will scroll through the fouroptions, when the required justification isdisplayed, pressing E will enter the selection andreturn the display to the ‘b.tYPE’ prompt in the editsub-menu from which ‘bArLo’ may be selectedusing the ▼ or ▲ button.

    ‘bArLo’ defines the indicator’s numeric display atwhich the bargraph starts, to enter the functionpress P which will reveal the existing setting. Thedisplay may be changed using the ▼ or ▲ buttonto adjust the flashing digit and the P button tomove control to the next digit. When the requiredstarting display has been selected, press E toreturn to the ‘bArLo’ prompt in the edit sub-menufrom which the ‘bArHi’ function may be selected.

    ‘bArHi’ defines the indicator’s numeric display atwhich the bargraph is full scale, to enter thefunction press P which will reveal the existingsetting. The display may be changed using the ▼or ▲ button to adjust the flashing digit and the Pbutton to move control to the next digit. When therequired display has been selected, press E twiceto enter the new values and return to the ‘bAr’prompt in the edit sub-menu.

    Note: If the ‘dP’ function has been set to provideautomatic maximum resolution irrespective of thedisplayed value, it may be necessary to manuallyposition the decimal point before adjusting ‘bArLo’or ‘bArHi’. This can be achieved by repeatedlyoperating the P button until the activated decimalpoint flashes, the decimal point can then bepositioned using either the ▼ or ▲ button.Pressing the P button again will return control toone of the digits.

    6.3.11 Scale numeric display ‘SCALE’A scaling factor ‘Gain’ and an offset ‘oFFSt’ maybe applied to the fieldbus process variable usingthis function, thus allowing the indicator to displaythe fieldbus process variable in alternative units.

    The ‘SCALE’ function may be selected from withinthe edit sub-menu by operating the ▼ or ▲ button.To enter the function press P which will display the‘GAin’ sub-function, pressing P again will revealthe existing gain with one digit flashing. Thisflashing digit may be changed by operating the ▼or ▲ button; when adjusted the P button will movecontrol to the next digit or to the decimal pointwhich can be positioned using the ▼ or ▲ button.When ‘GAin’ has been set to the required valueoperating the E button will enter the selection andreturn to the ‘GAin’ prompt in the sub-menu fromwhere the ‘oFFSt’ function can be selected usingthe ▼ or ▲ button.

  • 13

    To enter the ‘oFFSt’ function press P which willreveal the existing offset with one digit flashing.Again the flashing digit may be changed byoperating the ▼ or ▲ button and the P button willmove control to the next digit or to the decimalpoint. When ‘oFFSt’ has been set to the requiredvalue operating the E button will enter the selectionand return to the ‘oFFSt’ prompt in the sub-menu.Three operations of the E button will return to the‘Edit’ function in the listener configuration menu.

    6.3.12 Access code for listener configuration menu. ‘CodE’Access to the listener menu may be protected by afour digit security code which must be entered togain access. New instruments are suppliedconfigured with the default code 0000 whichdisables this protection and allows unrestrictedaccess to the configuration menu.

    To enter a new access code select ‘CodE’ in thelistener configuration menu by operating the ▼ or▲ button. To enter the function press P which willreveal the current access code with one digitflashing. The code may be changed using the ▼ or▲ button to adjust the flashing digit and the Pbutton to move control to the next digit. When therequired code has been selected, press E to enterthe selection and return to the ‘CodE’ prompt in thelistener configuration menu. The revised accesscode will be activated when the indicator isreturned to the display mode.

    If the access code is lost please contact BEKAassociates.

    6.3.13 Change from listener to node ‘tYPE’This function enables the instrument to bechanged from a fieldbus listener to a fieldbus nodeby selecting ‘tYPE’ in the listener configurationmenu using the ▼ or ▲ button. To enter thefunction press P which will show that theinstrument is configured as a fieldbus listener, tochange to a fieldbus node press the ▼ or ▲ buttonwhich will toggle the display to ‘nodE’ To preventaccidental changes this request must beconfirmed by operating the P button and entering‘5urE’. The instrument will display ‘0000’ with thefirst digit flashing, using the ▼ or ▲ button set theflashing digit to ‘5’ and press the P button to movecontrol to the next digit which should be set to ‘u’.When the four letters of ‘5urE’ have been entered,operating the E button will cause the instrument torestart as a fieldbus node in the display mode.

    CAUTIONAll the instrument’s listener configurationwill be lost when it is changed from afieldbus listener to a fieldbus node.

    6.3.14 Reset the indicator to listener factory defaults ‘rESEt’The BA444DF-F indicator may be reset to thelistener factory defaults shown below:

    Security Code 0000 (disabled)

    For each of the eight inputs:Input enable OffDecimal point Auto (maximum resolution)Bar Type LeftBar lower limit 0.0Bar Upper limit 100.0Gain 1.0Offset 0.0

    To reset the BA444DF-F indicator to the listenerfactory defaults select ‘rESEt’ in the listenerconfiguration menu by operating the ▼ or ▲button. To enter the function press P which willreveal ‘0000’ with the left hand digit flashing. Toprevent accidental use of this function, ‘5urE’ mustbe entered to confirm that the instrument is to bereset.

    Using the ▼ or ▲ button set the flashing digit to ‘5’and press the P button to move control to the nextdigit which should be set to ‘u’. When the fourletters of ‘5urE’ have been entered operating the Ebutton will reset the BA444DF-F to the factorydefaults. Any existing configuration andaddresses will be lost when the indicator is reset.

  • 14

    7. MAINTENANCE

    7.1 Fault finding during commissioningIf a BA444DF-F indicator fails to function duringcommissioning the following procedure should befollowed:

    Symptom Cause Check:No Display Instrument not

    correctlyconnected or

    powered.

    9 to 22V betweenterminals 1 & 2.

    When configuredas a listener

    displays‘no ConF’

    No inputs areenabled.

    Configuration ofeach input.

    When configuresas a listener

    displays‘no dAtA’

    No data beingreceived with the

    currentconfiguration.

    Device Addressand VariableIdentities are

    correct.

    That data hasDS-65 format.

    Display shows‘9.9.9.9.9’ with all

    decimal pointsflashing; allbargraphsegments

    activated andbargraph scale

    flashing.

    Valueover-range

    Configuration.and

    decimal pointposition.

    Display shows‘-9.9.9.9.9’ with

    all decimal pointsflashing; no

    bargraphsegments

    activated andbargraph scale

    flashing.

    Valueunder-range

    ConfigurationAnd

    decimal pointposition.

    Displayalternates

    between valueand the word

    ‘bAd’. Bargraphflashes.

    Status of fieldbusvariable has a

    quality of ‘BAD’or a fault state is

    active.

    Fieldbusconfiguration.

    Bargraph scaleflashes.

    Process variableis outside the

    limits defined forthe bargraph.

    Bargraphconfiguration.

    All displaysegmentsactivated.

    Display isinitialising.

    This is normaloperation, after afew seconds themodel numberfollowed by the

    firmware versionwill be displayedprior to entering

    the displaymode.

    7.2 Fault finding after commissioning

    ENSURE PLANT SAFETY BEFORESTARTING MAINTENANCE

    Live maintenance is permitted onintrinsically safe equipment installed in ahazardous area, but only certified testequipment should be used unless a gasclearance certificate is available.

    If a BA444DF-F fails after it has been functioningcorrectly, the table shown in section 7.1 may helpto identify the cause of the failure.

    If this procedure does not reveal the cause of thefault, it is recommended that the instrument isreplaced.

    7.3 ServicingWe recommend that faulty BA444DF-F Fieldbusindicators are returned to BEKA associates or toour local agent for repair.

    7.4 Routine maintenanceThe mechanical and electrical condition of theinstrument should be regularly checked. Initiallyannual inspections are recommended, but theinspection frequency should be adjusted to suit theenvironmental conditions.

    7.5 GuaranteeInstruments which fail within the guarantee periodshould be returned to BEKA associates or our localagent. It is helpful if a brief description of the faultsymptoms is provided.

    7.6 Customer commentsBEKA associates is always pleased to receivecomments from customers about our products andservices. All communications are acknowledgedand whenever possible, suggestions areimplemented.

  • 15

    8. ACCESSORIES

    8.1 Scale and tag markingBA444DF-F indicators are fitted with a blankescutcheon around the liquid crystal display. Ifspecified when the instrument is ordered, this canbe supplied printed with units of measurement andtag information, plus a scale for the horizontalbargraph. Alternatively, information may be addedon-site via an embossed strip, dry transfer or apermanent marker.

    If separate units of measurement or identificationare required for each process variable this can beprovided on the tag plate see 8.2

    To gain access to the display escutcheon removethe terminal cover by unscrewing the two 'A'screws which will reveal two concealed 'D' screws.Unscrew all four 'D' screws and carefully lift off thefront of the instrument. The location of thesescrews is shown in Fig 2.

    After adding the required legends, or fitting a newpre-printed self-adhesive escutcheon, ensure thatthe gasket is correctly positioned beforereassembling the instrument enclosure.

    8.2 Tag plateThe BA444DF-F can be supplied with a blank orcustom laser marked stainless steel plate securedby two screws to the front of the instrumentenclosure. This plate can accommodate:

    1 row of 9 alphanumeric characters 10mm high

    or 1 row of 11 alphanumeric characters 7mm high

    or 2 rows of 18 alphanumeric characters 5mm high.

    or 8 cells each containing units of measurement or identification for one of the 8 inputs.

    Fig 7 Typical 8 cell tag plate

    8.3 Pipe mounting kitsTwo pipe mounting kits are available for securingthe BA444DF-F to a horizontal or vertical pipe.

    BA392D Stainless steel bracket secured by twoworm drive hose clips for 60 to 80mmoutside diameter pipes.

    BA393 Heavy-duty stainless steel bracketsecured by a single 'V' bolt. Will clampto any pipe with an outside diameterbetween 40 and 80mm.

  • 16

    APPENDIX 1ATEX dust certification

    A1.0 ATEX dust certificationIn addition to ATEX certification permittinginstallation in explosive gas atmospheres which isdescribed in the main section of this instructionmanual, the BA444DF-F is available with optionalATEX certification permitting use in the presenceof combustible dusts. If ATEX dust certification isrequired it must be requested when the BA444DF-F fieldbus listener is purchased.

    WARNINGBefore installing a BA444DF-F fieldbusindicator in the presence of acombustible dust, ensure that thecertification information label, which islocated on the top of the instrument,specifies dust certification – see sectionA1.2

    A1.1 Zones and Maximum Surface TemperatureThe BA444DF-F has been ATEX certified asGroup II, Category 1D Ex iaD 20 T100oC IP66apparatus Tamb = -20 to 60oC. When installedas specified by EN 61241-14 ‘Electrical apparatusfor use in the presence of combustible dust –Selection and installation’, the fieldbus listener maybe installed in:

    Zone 20 explosive atmosphere in theform of a cloud ofcombustible dust in air iscontinuously present, or forlong periods or frequently.

    Zone 21 explosive atmosphere in theform of a cloud ofcombustible dust in air islikely to occur occasionallyin normal operation.

    Zone 22 explosive atmosphere in theform of a cloud ofcombustible dust in air is notlikely to occur in normaloperation, but if it doesoccur, will only persist for ashort period.

    Be used with dusts having a Minimum IgnitionTemperature of:

    Dust cloud 150oC

    Dust layer on BA444DF-F 175oCup to 5mm thick

    Dust layer on BA444DF-F Refer toover 5mm thick. EN 61241-14

    At an ambient temperature between –20 and+60oC

    A1.2 Certification Label InformationThe certification label is fitted in a recess on thetop outer surface of the enclosure. It shows detailsof the ATEX dust certification including themaximum surface temperature and ingressprotection plus BEKA associates name andlocation. IECEx dust approval information is alsoshown, non-European certification information mayalso be included.

    The instrument serial number and date ofmanufacture are recorded on a separate labelinside the terminal compartment.

    A1.3 Installation & maintenanceThe ATEX dust certification relies on the Fieldbuslistener enclosure being dust-tight. Therefore theterminal cover should only be removed when dustcan not enter the instrument enclosure. Beforereplacing the terminal cover ensure that thesealing gaskets are undamaged and are free fromforeign bodies.

  • 17

    APPENDIX 2FM Approval for use in the USA andcFM Approval for use in Canada

    A2.0 Factory Mutual ApprovalFor installations in the USA and Canada, a versionof the BA444DF-F is available with FM and cFMintrinsic safety and nonincendive approval, projectidentifications 3027031 and 3027031C. Copiesof the Certificates of Compliance are availablefrom BEKA associates sales office andwww.beka.co.uk

    The FM and cFM Approved version is identical tothe ATEX version except the three M20 x 1,5tapped cable entries are replaced by three plainunthreaded 22.25mm diameter entries. Approvedhubs and glands are listed in note 6 of IntrinsicallySafe Control Drawing CI410-12 and note 5 ofNonincendive Control Drawing CI410-13. Thecertification label on the FM and cFM Approvedversion includes ATEX gas certification informationso that the fieldbus indicator may be used insystems covered by either authority.

    A2.1 Intrinsic safety approvalThe BA444DF-F is approved to FM Class 3610intrinsic safety standard for use in indoor andoutdoor hazardous (classified) locations.Installations must comply with BEKA associatesControl Drawing CI410-12, which is attached tothis Appendix, ANSI/ISA RP12.06.01 ‘Installationof Intrinsically Safe Systems for Hazardous(Classified) Locations’ and with the NationalElectrical Code ANSI/NFPA70.

    Canadian installations must comply with theCanadian Electrical Code C22.2 and with BEKAassociates Control Drawing CI410-12, which isattached to this Appendix.

    The BA444DF-F has a T4 rating at ambienttemperatures up to +70oC and may be used withthe following gases and dusts:

    Intrinsic SafetyDivision 1 or 2

    Class I Group A & B Group C Group D

    Class II Group E, F & G

    Class III

    Zone 0, 1 or 2Class 1 Group IIC Group IIB Group IIA

    The FM and cFM entity parameters are identical tothe ATEX parameters and, like the ATEXcertification, confirm that the BA444DF-F complieswith the FISCO Field Device requirementsspecified in IEC60079-27. The intrinsically safesystem shown in Fig 1 of this manual maytherefore be used for installations in the USA andCanada, providing the fieldbus power supply,terminators, Zener barriers and galvanic isolatorsare FM Approved for US installations and cFM orCSA Approved for Canadian installations. Allinstallations must comply with BEKA associatesControl Drawing CI410-12.

    FM and cFM Approvals also allows the BA444DF-F to be connected to non-FISCO systems usingthe entity concept – see section 4.2 of this manual.

    A2.2 Nonincendive approvalThe BA444DF-F is FM Class 3611 nonincendiveapproved allowing it to be installed in Division 2indoor and outdoor hazardous (classified) locationswithout the need for Zener barriers or galvanicisolators. US installations must comply with theBEKA associates Control Drawing CI410-13, whichis attached to this Appendix, and with the NationalElectrical Code ANSI/NFPA70.

    Canadian nonincendive installations must complywith the Canadian Electrical Code C22.2 and withBEKA associates Control Drawing CI410-13, whichis attached to this Appendix.

    The FM and cFM Nonincendive Approvals alsoallow the BA444DF-F fieldbus listener to beconnected to any appropriately certified FNICOcompliant fieldbus segment.

    The BA444DF-F has a T4 rating at ambienttemperatures up to +70ºC and may be used withthe following gases and dusts:

    NonincendiveDivision 2

    Class I Group A & B Group C Group D

    Class II Groups E, F & G

    Class III

    Zone 2Class I Group IIC Group IIB Group IIA

  • 18

  • 19

  • 20

  • 21

  • 22

  • 23

  • 24

  • 25

    APPENDIX 3IECEx Certification

    A3.0 The IECEx Certification SchemeIECEx is a global certification scheme forexplosion protected products which aims toharmonise international certification standards.For additional information about the IECExcertification scheme and to view the BEKAassociate certificates, please visit www.iecex.com

    A3.1 IECEx Certificate of Conformity for use in an explosive gas atmospheresThe BA444DF-F fieldbus indicator has been issuedwith an IECEx Certificate of Conformity numberIECEx ITS 06.0012 which specifies the followingcertification codes and marking:

    Ex ia IIC T4 GaFISCO Field Device Ex ia IIC T4Ta = -40ºC to 70 ºC

    When connected to a certified IECEx system theBA444DF-F may be installed in:

    Zone 0 explosive gas air mixturecontinuously present.

    Zone 1 explosive gas air mixturelikely to occur in normaloperation.

    Zone 2 explosive gas air mixture notlikely to occur, and if it does willonly exist for a short time.

    Be used with gases in groups:Group A propaneGroup B ethyleneGroup C hydrogen

    Having a temperature classification of:T1 450ºCT2 300ºCT3 200ºCT4 135ºC

    At an ambient temperature between –40 and+70ºC.

    A3.1.1 Installation in an explosive gas atmosphereFor installations in gas atmospheres the BA444DF-F IECEx and ATEX certifications have identicalintrinsic safety parameters and installationrequirements. The ATEX system designrequirements described in section 4 of this manualmay therefore be used for IECEx installations ingas atmospheres, but the local code of practiceshould also be consulted.

    A3.2 IECEx Certificate of Conformity Use in presence of combustible dustsIn addition to IECEx certification permittinginstallation in explosive gas atmospheres, theBA444DF-F is available with optional IECExcertification permitting use in the presence ofcombustible dusts.

    The IECEx Certificate of Conformity specifies thefollowing certification codes and marking:

    Ex ia IIIC T100ºC Da IP66Ta = -20oC to 60 ºC

    If IECEx dust certification is required it must berequested when the BA444DF-F fieldbus indicatoris purchased.

    WARNINGBefore installing a BA444DF-F fieldbusindicator in the presence of acombustible dust, ensure that thecertification information label, which islocated on the top of the instrument,specifies dust certification - see below.

    When connected to a certified IECEx system theBA444DF-F may be installed in:

    Zone 20 explosive atmosphere in theform of a cloud ofcombustible dust in air iscontinuously present, or forlong periods or frequently.

    Zone 21 explosive atmosphere in theform of a cloud ofcombustible dust in air islikely to occur occasionallyin normal operation.

    Zone 22 explosive atmosphere in theform of a cloud ofcombustible dust in air is notlikely to occur in normaloperation, but if it doesoccur, will only persist for ashort period.

  • 26

    3.2.1 Installation in the presence of combustible dustThe IECEx dust certification relies on the fieldbuslistener enclosure being dust-tight. Therefore theterminal cover should only be removed when dustcan not enter the instrument enclosure. Beforereplacing the terminal cover ensure that thesealing gaskets are undamaged and are free fromforeign bodies.

    The IECEx certificate may be downloaded fromwww.beka.co.uk, www.iecex.com or requestedfrom the BEKA sales office.

    A3.3 Versions of the BA444DF-FAll versions of the BA444DF-F fieldbus indicatorhave IECEx certification. This includes:

    ATEX version for use in gas atmospheresIECEx code Ex ia IIC T4 Ga

    FISCO Field Device Ex ia IIC T4Ta = -40ºC to 70ºoC

    ATEX version for use in gas and dustatmospheres.

    IECEx code Ex ia IIC T4 GaFISCO Field Device Ex ia IIC T4Ex ia IIIC T100oC Da IP66Ta = -20ºC to 60 ºC

    Factory Mutual Approved versionIECEx code Ex ia IIC T4 Ga

    FISCO Field Device Ex ia IIC T4Ta = -40ºC to 70ºC

    ul. Lechicka 14 ; 02-156 Warszawa Fax. (+48 022) 846 50 37 [email protected] Automatyka Sp. z o. o. Tel. (+48 022) 886 10 16 www.trautomatyka.pl