    CSR ROOFING ARCHITECTURAL MANUAL

    The design o a Tiled roo and iTs supporTing sTrucTure requires careul

    consideraTion, involving undersTanding o a number o building sTandards.

    one o The key responsibiliTies o The speciier is To deTermine The design gusT

    wind speed aecTing a parTicular siTe.

    design

  • 7/27/2019 Australia Wind Roofing Classification

    2/14

    conTenTs

    design consideraTions 1

    wind caTegories 2

    Terrain caTegories 5

    ixing requiremenTs or Tiles and accessories 6

    edge Technology ixing speciicaTion 10

    raTer lengTh and spacings 11

    baTTen sizes and raTer spacings 12

  • 7/27/2019 Australia Wind Roofing Classification

    3/14

    d

    esign

    CSR ROOFING ARCHITECTURAL MANUAL

    1

    secTion3

    designconsideraTions

    The installation specications given in this

    manual are based on a basic wind speed

    or ultimate strength o 74m/s at a height

    o 6m rom ground level. This is suitable

    or sites in Regions A, B and New Zealand.

    For installation specications or designated

    cyclonic areas i.e. Regions C and D it is

    also advisable to consult both your building

    engineer and your local CSR Roong oce.

    This section will cover CSR Roongs

    recommended installing specications

    based on the design gust wind speed, as

    well as:

    Minimum roo pitch requirements

    Maximum rater length requirements

    Rater and truss spacings and batten

    requirements

    Batten installing requirements

    Sarking/underlay installation

    requirements

    Please note that relevant local authorities

    may apply special specication to the

    nal structure. Speciers are advised

    to determine local requirements beore

    proceeding.

    Furthermore, regional CSR Roong oces

    may recommend additional installing

    specications based on experience o a

    particular region, so it is also advisable to

    consult your local CSR Roong oce prior

    to commencement o work.

    To acilitate this, the Australian Standards AS

    1170.2, AS 4055 and NZS 4203 are to be

    considered, regarding:

    The regional design wind speeds

    The terrain category o a building site

    The Technical Record 440 (TR440)

    extension o this code, which is

    deemed to be the standard or design o

    products or most cyclonic areas

    This is particularly applicable inAustralia to areas north o the latitude

    250 south, and within 50kms o the

    coast (including o shore islands).

    Local requirements and covenants

    determined by State and/or local

    statutory authorities. Special conditions

    may apply to the site in relation to

    items a), b) and c)

  • 7/27/2019 Australia Wind Roofing Classification

    4/14

    CSR ROOFING ARCHITECTURAL MANUAL

    wind caTegories

    Winds and the pressure they create,

    must be considered when speciying roo

    structures and roong materials.

    The negative pressure exerted to the leeward

    side o a pitched roo at 35m/s can be

    greater than the weight o the tiles, thereore

    determining the wind orce aecting a

    site at height is essential to identiy theappropriate level o security installation.

    The magnitude o these wind orces is

    aected by the ollowing actors:

    Basic wind speed, Direction, Terrain and

    Building height.

    Basic wind speed categoriesAS 1170.2/Amdt 3 and AS 4055 provides

    inormation on wind speeds generally

    aecting dierent regions o Australia.

    r b

    r c

    r b(ausTralian TerriTory only)

    r b

    r b

    r d

    r c

    r c

    r c

    r a4

    r a1

    r a5(wiThin 70km

    o melbourne gpo)

    r a3

    r a2

    lord howe islandregion a

    norolk islandsregion bcorindi

    brisbaneToowoomba

    kyogle

    bourke

    bundaberg

    rockhampTon

    biloela

    collinsville

    Townsville

    aTherTon

    dunbar

    cairns

    mareeba

    moreTonmcdonnell creek

    142

    11

    burkeTown

    wesT moreland

    borroloola

    adelaideriver

    kununurra

    alice springs

    ivanhoe

    darwin

    wyndham (c)

    broome

    porT hedland

    croydonkarraTha

    onslowmarble bar

    millsTream

    gascoyne JuncTion

    callyTharra

    mullewa

    morawakalgoorlie

    gunyidi

    perThesperance

    albany

    greenhead

    carnarvon

    woomera

    adelaidecanberra

    geelong70kmmounT gambier

    sydney

    hobarT

    sTaTe border

    50km

    easT sale

    200km

    20

    25

    35

    40

    45

    30

    35

    30

    25

    20

    27

    a3

    r t t tta [a1 t a5], b, c d.

    ct r t t t t 50, 100, 150 200.

    i t 50 t t t r t jt t.

    r a

    non-cyclonic classiicaTion

    r b r c r d

    cyclonic classiicaTion

    chrisTmas islandregion b

    cocos islandregion c

    ausTralia

    negaTive pressure (sucTion) leeward side

    regions v(m/s)

    a 41

    b 49

    c 57

    d 69

    regions v(m/s)

    a 50

    b 60

    c 70

    d 85

    regions v(m/s)

    a 38

    b 38

    c 45

    d 50

  • 7/27/2019 Australia Wind Roofing Classification

    5/14

    CSR ROOFING ARCHITECTURAL MANUAL

    d

    esign

    3

    secTion3

    * NZS 4203 General Structual

    Design and Design Loading or

    Buildings provides inormation on

    wind speeds generally aecting

    dierent regions o New Zealand.

    For urther inormation on Wind

    Loads in New Zealand reer to NZS

    4203 General Structual Design

    and Design Loading or Buildings.

    kaiTaia

    whangarei

    auckland

    morrinsvillehunTly

    hamilTon

    new plymouTh

    ohakuna

    waiouruwanganui

    palmersTon norTh

    Tauranga

    roTorua

    gisborneTaupo

    napier

    waipawa

    waipukurau

    upper huT

    wellingTonnelson

    wesTporT bienheim

    hammersprings

    hokiTika

    haasT

    milord sound

    cromwell

    alexandra

    invercargilldunedin

    Twizel Timaru

    meThven

    chrisTchurch

    culverden

    kaikoura

    r a6

    r a7

    r wr a7

    44

    37

    dt t t t t tt .

    s : 012

    souTh easT wind

    ot : 1230

    s : 012

    ot : 1230

    norTh wesT wind

    lee mulTiplier, m

    new zealand

  • 7/27/2019 Australia Wind Roofing Classification

    6/14

    CSR ROOFING ARCHITECTURAL MANUAL

    Based on the Wind Class

    specication provided, CSR Roong

    is able to assess the appropriate

    level o security installation required

    or the roo in accordance with AS

    2050 Installation o Roo Tiles.

    Wind Classication system N1, N2,

    N3, N4, N5, N6 or non-cyclonic

    Regions A and B, and C1, C2, C3

    and C4 or cyclonic Regions C and

    D shall be considered. The system

    includes the combinations o

    regions, terrain categories, shielding

    o housing and topographic eects

    given in Table 2.

    It is the speciers responsibility to

    determine the wind speed aecting a site

    and a house design. In other words to

    determine the Wind Class o a regional area

    combined with the Wind Speeds aecting

    a site. Cyclone aected regions will have a

    Wind Class rom C1 to C4. For non-cyclonic

    regions, a Wind Class rom N1 to usually

    N4 is required to be specied on your

    roong structure plan.

    The table below summarises the

    relationship between the Wind Speeds and

    the Wind Class.

    taBle 1: design wind speed equivalent values/as 4055

    wind caTegory km/hor non-cyclonic

    regions a and b

    or cyclonic

    regions c and d

    design gusT wind speed

    (m/sec) permissible

    sTress meThod only

    w28 101 n1 28

    w33 119 n2 33

    w41 148 n3 c1 41

    w50 180 n4 c2 50

    w60 216 n5 c3 60

    w70 252 n6 c4 70

    taBle 2: wind classification system (refer as 4055)region Terrain

    caTegoryTopographic classiicaTion

    T1

    s ps ns

    T2

    s ps ns

    T3

    s ps ns

    T4

    s ps ns

    T5

    s ps ns

    a Tc 3 n1 n1 n1 n2 n2 n2 n2 n3 n3 n2 n3 n3 n3 n3 n4

    Tc 2.5 n1 n1 n2 n2 n3 n3 n2 n3 n3 n3 n3 n4 n3 n4 n4

    Tc 2 N1 N2 N2 n2 n3 n3 n3 n3 n3 n3 n4 n4 n4 n4 n4

    Tc 1 n2 n3 n3 n3 n3 n4 n3 n4 n4 n4 n4 n4 n4 n5 n5

    b Tc 3 n2 n2 n3 n3 n3 n4 n3 n4 n4 n4 n4 n4 n4 n5 n5

    Tc 2.5 n2 n3 n3 n3 n4 n4 n3 n4 n4 n4 n4 n5 n4 n5 n5

    Tc 2 n2 n3 n3 n3 n4 n4 n4 n4 n5 n4 n5 n5 n5 n5 n6

    Tc 1 n3 n4 n4 n4 n5 n5 n4 n5 n5 n5 n5 n6 n5 n6 n6c Tc 3 c1 c1 c2 c2 c2 c3 c2 c3 c3 c3 c3 c3 c3 c4 c4

    Tc 2.5 c1 c2 c2 c2 c3 c3 c3 c3 c3 c3 c4 c4 c4 c4 na

    Tc 1, Tc 2 c2 c2 c2 c2 c3 c3 c3 c4 c4 c3 c4 c4 c4 na na

    d Tc 3 c2 c3 c3 c3 c4 c4 c3 c4 c4 c4 na na na na na

    Tc 2.5 c2 c3 c3 c3 c4 c4 c4 na na c4 na na na na na

    Tc 1, Tc 2 c3 c3 c4 c4 na na c4 na na na na na na na na

    FS ull shielding PS partial shielding

    NS no shielding N non-cyclonic

    C cyclonic N/A not applicable

  • 7/27/2019 Australia Wind Roofing Classification

    7/14

    d

    esign

    CSR ROOFING ARCHITECTURAL MANUAL

    5

    secTion3

    Terrain caTegories

    the four terraincategories are:Terrain Category 1

    Zo= 0.002M

    Exposed open terrain with ew or no

    obstructions, in which the average

    height o objects surrounding the

    structure is less than 1.5 metres.

    This category includes water

    suraces (open sea coast and lakes),

    fat and treeless plains, and open

    snowelds.

    Terrain Category 2

    Zo= 0.02M

    Open terrain, grassland with ew

    well-scattered obstructions having

    heights generally rom 1.5 to 10.0

    metres. This category includes

    open parkland and sparsely built up

    outskirts o towns and suburbs.

    Terrain Category 3

    Zo= 0.2M

    Terrain with numerous closely

    spaced obstructions having the size

    o domestic houses. This includes

    most suburban areas.

    Terrain Category 4

    Zo= 2.0M

    Terrain with numerous large,

    high (10.0 to 30.0 metres) and

    close obstructions, such as large

    city centres and well-developed

    industrial complexes.

    terrainThe shielding provided by permanent

    structures, hills and vegetation has the

    eect o modiying wind speeds.

    Terrain categories are used or determining

    a sites exposure to wind. In Australia,

    terrain is dened in accordance with AS

    1170.2 and AS 4055 into our categories.

    In NZ, the relevant standard is NZS 4203.

    For the eective use o this tool, the

    direction and speed o wind fows towards a

    site must be assessed.

    0.000

    0.002 Natural snow surace (fat)

    0.006 Desert (stones)

    0.008 Cut grass (10mm)

    0.02 Rough open water suraces

    at wind speeds (Vu) and (Vp),

    Isolated trees, uncut grass and

    airelds

    0.04 Crops

    0.06 Few trees

    Long grass (600mm)

    0.2 Level wooded country,

    Suburban buildings

    0.4 Centres o small towns

    0.8 High density metropolitan

    1.0 Forests

    2.0 City buildings (10.0m to 30.0m)

    roughness length (2)m

  • 7/27/2019 Australia Wind Roofing Classification

    8/14

    CSR ROOFING ARCHITECTURAL MANUAL

    ixing requiremenTs orTiles and accessories

    taBle 3: as2050 minimum mechanical installing requirements for tiles and ancillaries

    wind classiicaTion Tile insTalling ancillary insTalling

    edge o roo ield o roo ridge, hip and barge Tiles

    u t

    n2 n1 n2

    m t t t

    t t

    tt

    m t t

    u t n3 c1 m t

    t

    m t

    t

    m t t

    n4 c1/c3 m t

    t

    m t

    t

    m t t

    taBle 4: as 2050 wind classification and maXimum design gust wind speed

    wind classiicaTion maximum design gusT wind speed (m/s)

    permissable sTress

    meThod (vp)

    serviceabiliTy limiT

    sTaTe (vs)

    ulTimaTe limiT

    sTaTe (vu)

    n1 28 (w28n) 26 34

    n2 33 (w33n) 26 40

    n3c1 41 (w41n/c) 32 50

    n4c2 50 (w50n/c) 39 61

    c3 60 (w60c) 47 74

    Note: Wind classifcations are as defned in AS 4055

    taBle 5: australian mechanical requirements for tiles and accessories

    design windvelociTy (m/s)

    Tile ixing ridge ixing barge ixing

    edge o roo ield o roo ridge Tiles hip ridge Tiles

    u t t t

    < 33

    m f t t 2

    t t 2 t

    , t 2

    m f

    t.

    m f

    t.

    m f

    t.

    > 34 < 41 m f

    t 2

    m f

    2 t

    m f

    t

    m f t

    t.

    m f

    t.

    > 41 < 60 m f

    t

    m f

    t

    m f

    t

    m f

    t.

    m f

    t.

  • 7/27/2019 Australia Wind Roofing Classification

    9/14

    d

    esign

    CSR ROOFING ARCHITECTURAL MANUAL

    7

    secTion3

    taBle 6: new zealand minimum fiXing requirements for tiles and accessories

    design wind velociTy(m/s)

    Tile ixing

    edge o roo/body

    o roo

    ridge & hip ixing barge ixing

    low wind speed

    u t 32 /

    m f t

    2 t t

    2 t ,

    t 2

    a

    t

    m f

    t

    medium wind speed

    u t 37 /

    m f t

    2 t t

    2 t ,

    t 2

    a

    t

    m f

    t

    high wind speed

    up To 44 m/s

    m f t

    2 t t

    2 t ,

    t 2

    a

    t

    m f

    t

    very high wind speed

    u t 50 /

    m f t a

    t

    m f

    t

    speciic engineering

    designo 50 /

    p t r

    csr rf of

    p t r

    csr rf of

    p t r

    csr rf of

    Note:

    Accepted methods o mechanical fxing are specifed later in this manual.

    CSR Roofng recommends the use o Flexible Pointing as standard or all roos, removing the need or other orms o mechanical fxing. Flexible Pointing also provides

    other signifcant benefts reerred to later in this manual.

    Please consult your regional CSR Roofng ofce or their specifc recommendations.

    taBle 7: australian fiXing recommendations

    windclass

    sarking/underlay

    securiTy pads mechanicallyix Tiles

    mechanicallyix eave Tiles

    anTi-pondingboard

    ixingbody and edgeo roo

    n1 ot

    t

    ot

    ot ot

    r

    t 20

    jt t tt

    ft

    s t 3

    n2

    r

    n3

    mt

    f as

    4200.2

    n4

    mt r

    c1

    c2

    c3

  • 7/27/2019 Australia Wind Roofing Classification

    10/14

    CSR ROOFING ARCHITECTURAL MANUAL

    taBle 8: new zealand fiXing recommendations

    wind class underlay mechanically ix Tiles

    mechanicallyix eave Tiles

    anTi-pondingboard

    ixing body &edge o roo

    l ot

    t

    r

    t 200s T 6

    m r

    t 200s T 6

    h r

    t 200s T 6

    v h mt r

    t 200s T 6

    Denotes recommendation

    minimum roof pitchCSR Roong tiles are designed and tested

    to cope with the diverse range o wind and

    weather conditions across Australia and

    New Zealand.

    The ollowing actors aect the design o

    your roo:

    the roof tile selectionWith a proled roo tile, the depressions

    in the body o the tile act as a natural

    watercourse, enabling water to be

    channelled down the roo quickly.

    For fatter proled tiles, these depressions

    are either less prominent or do not eature.

    As a result, water is reer to be pushed

    across the roo surace by wind. The eect

    is that water migrates to the watercourse o

    the tile.

    the pitch of the roofThe greater the pitch, the greater the orce

    o gravity combined with wind orce to pull

    water rom the roo.

    Conversely, the lesser the pitch, the lesser

    the orce o gravity combined with wind

    orce to pull water rom the roo.

    For this reason, tiling is not recommended

    below 15 degrees without special

    precautions being taken in direct

    consultation with your regional CSR Roong

    oce. Indeed, AS 2050 states where

    it is intended to x tiles to roos with a

    pitch o less than 15 degrees, the tile

    manuacturers advice should be sought.

    Sarking/underlay is a pliable oil installed

    prior to xing the roo battens.

    In New Zealand underlay is a sel

    supporting building paper. Not only does

    sarking/underlay act as a secondary water

    catchment, sarking/underlay also aids with

    keeping your home cooler and dust ree.

    There are several diering grades o

    sarking/underlay, it is recommended that

    you consult with your local CSR Roong

    representative who can assist you with the

    correct application to suit your particular

    design.

    Table 9 indicates the minimum roo pitch at

    which CSR Roong tiles are to be installed,

    with and without the need or sarking/

    underlay, or each region.

  • 7/27/2019 Australia Wind Roofing Classification

    11/14

    D

    ESIGN

    CSR ROOFING ARCHITECTURAL MANUAL

    9

    SECTION3

    TABLE 9: MINIMUM ROOF PITCH DEGREES

    MINIMUMPITCH

    NSW VIC QLD SA WA(SURROUNDING

    PERTH)

    NZ CYCLONEAREA

    MONIER

    CONCRETEWithout

    Sark

    With

    Sark

    Without

    Sark

    With

    Sark

    Without

    Sark

    With

    Sark

    Without

    Sark

    With

    Sark

    Without

    Sark

    With

    Sark

    Without

    Sark

    With

    Sark

    Without

    Sark

    With

    Sark

    Elabana 20 15 20 15 20 15 20 15 20 15 20 15 # 17.5

    Centurion 20 15 20 15 20 15 20 15 20 15 20 15 # 17.5

    Tudor 20 15 20 15 20 15 20 15 20 15 na na na 17.5

    Waverley 20 15 20 15 20 15 20 15 20 15 na na na 17.5

    Homestead 20 15^ 20 15^ 20 15^ 20 15^ 20 15 na na na 17.5

    Traditional 20 15^ 20 15^ 20 15^ 20 15^ 20 15 na na # 17.5

    Georgian 20 15^ 20 15^ 20 15^ 20 15^ 25 22.5 na na # 25

    Cambridge 20 15^ 20 15^ 20 15^ 20 15^ 25 22.5 na na # 25

    Horizon 20 15^ 20 15^ 20 15^ 20 15^ 25 22.5 # 25 # 25

    Madison 20 15^ 20 15^ 20 15^ 20 15^ 25 22.5 na na # 25

    WUNDERLICH TERRACOTTA

    Modern

    French

    20 15 20 15 20 15 20 15 20 15 25 20 # 17.5

    Nouveau 20 15 20 15 20 15 20 15 20 15 25 20 # 18.5

    Marseille 20 15 20 15 20 15 20 15 a a 25 20 # 17.5

    Nullarbour # 25 # 25 # 22.5 # 25 # 22.5 # 25 # 25

    Heritage

    Shingle*# 25 # 25 # 25 # 25 # 25 # 25 # 25

    # Sarking/underlay required regardless of pitch

    Anti ponding boards are required for pitches less than 20 deg and in cyclone areas

    Consideration must be given to rafter length, site exposure and terrain category when determining roof pitch

    ^ Refer to EDGE technology xing specication

    * Longer lead times and minimum order quantities apply Not all proles available in all states, check availability with your local sales ofce

    Maximum rafter lengths apply, refer to Table 10, page 11 in Section 4.

    na not available

  • 7/27/2019 Australia Wind Roofing Classification

    12/14

    CSR ROOFING ARCHITECTURAL MANUAL

    edge Technologyixing speciicaTion

    monier roof tiles treated with edge technology*

    edge technologyMoniers breakthrough EDGE Technology is a patented process that now oers architects

    and designers greater fexibility when it comes to contemporary roo design. EDGE

    technology has been comprehensively eld tested, and has also undergone rigorous wind

    tunnel testing to endure product perormance exceeds AS 2050-2002. Additionally,

    successul testing has also been conducted at Laarges world class acility in London England.

    product specificationThis xing specication is to be used when installing Monier roo tiles that have been

    treated with Moniers Patented EDGE technology. Available in selected states.

    product rangeHorizon, Georgian, Cambridge, Madison

    sarking/underlayMandatory or all pitches below 20 degrees. Additional consideration must be given to

    locations that are elevated, or in coastal regions with our exposed to high wind speeds.

    minimum roof pitch15 degrees with sarking/underlay.

    At the minimum roo pitch o 15 degrees, the maximum rater length is 4.5metres.

    For longer raters lengths add 2 degrees to the pitch or every addional metre.

    head lap100mm or all pitches below 20 degrees.

    I sarking/underlay is used at 20 degrees , a head lap o 80mm is permissible providing the

    terrain category is not less than T2.5.

    fiXingNailing is required or wind speeds up to N2.

    Cyclone clips are required or wind speeds o N3 or more.

    generalSpecial Consideration should be given to regions prone to cyclonic activity. Alternate xing

    methods may need to be adopted. Reer these enquiries to the technical support team.

    *Not available in all states

  • 7/27/2019 Australia Wind Roofing Classification

    13/14

    d

    esign

    CSR ROOFING ARCHITECTURAL MANUAL

    11

    secTion3

    raTer lengThand spacings

    rafter (truss) spacingsThe wider the rater spacing, the

    greater the stresses upon them, and

    the batten specied.

    Battens made o timber should

    be sound, and in sucient length

    and size to meet regional xing

    requirements. Batten sizes and

    types vary by region, however must

    be xed in accordance with the

    AS 1684 or AS 1720.1 and NZS

    3604 in New Zealand.

    rafter lengthconsiderationsCSR Roong tiles are designed

    to be dimensionally consistent,

    allowing some tolerance to assist

    the roo tiler during set out.

    However, it is advisable to consider

    the rater length at the design stage,

    to avoid the need to cut a short tile

    course.

    rafter lengthWith heavy rainall, a considerable volume

    o water can accumulate at the bottom o a

    roo. The longer the roo run (rater length),

    the more water accumulates.

    AS 2050 states long rater lengths may

    require sarking/underlay to preventinundation o water into the roo. These

    lengths may vary according to the tile, the

    pitch o the roo and the exposure.

    CSR Roong advises against the use o

    minimum pitch or long rater lengths

    without sarking/underlay. As a general guide

    or contoured tiles, rater length should not

    exceed 4.5m at a minimum pitch o 15

    degrees. For every 0.5m increase in rater

    length above 4.5 metres, the pitch should

    increase by 1 degree until the acceptable

    pitch o 22.5 degrees is reached or long

    raters.

    Table 10 indicates the rater length

    dimensions at which sarking/underlayshould be installed over the aected roo

    area. Advice should be sought rom your

    local CSR Roong oce with regard to

    regional sarking/underlay installation

    requirements.

    taBle 10: pitch levels in relation to rafter lengthmaximum raTer lengTh (mm) roo degrees o piTch

    4500 15

    5000 16

    5500 17

    6000 18

    6500 19

    7000 20

    7500 21

    8000 22

    1.

    000

    RATIO 1: 1.

    000

    1.

    250

    1.

    500

    1.

    750

    2.

    000

    2.

    250

    2.

    500

    2.

    750

    3.

    000

    3.

    250

    3.

    500

    3.

    750

    4.

    000

    4.

    250

    4.

    500

    4.

    750

    4.

    000

    rise and run chartPitch expressed as a ratio o rise to run.

    Equivalent pitch in degrees is a close approximation only

  • 7/27/2019 Australia Wind Roofing Classification

    14/14

    CSR ROOFING ARCHITECTURAL MANUAL

    baTTen sizes andraTer spacings

    The ollowing table summarises suitable batten types at varying rater spacings, with the current CSR Roong practice in each region.

    taBle 11: Batten sizes and rafter spacings (mm)

    baTTen maTerial speciicaTion

    raTer spacing up To 450 451600 601900 9011200

    n st w h 38 25 h 25 50 h 38 50 mt T 40

    st 38 28 st 38 38 st 50 50

    st 63 38

    mt T 40

    vt h 38 25 h 25 50 h 38 50/38 38 h 38 75

    st 38 28 st 38 38 st 50 50 mt T 40

    mt T 40 mt T 40

    q h 38 25 h 25 50 h 38 50 h 50 50

    st 38 38 st 40 50 mt T 40

    mt T 40

    st at h 38 25 h 25 38 h 38 50 h 50 75

    mt T 40 st 50 50 mt T 40

    mt T 40

    wt at h 38 25 h 38 25 h 38 38 h 50 50

    st 38 38 st 63 38

    mt T 40 mt T 40 mt T40

    T h 38 25 h 25 50 h 38 50 h 50 75

    st 38 38 st 50 50 mt T 40

    mt T 40 mt T 40

    at ct

    Tt

    h 38 25 h 25 50 h 38 50 h 50 50

    st 38 38 st 63 38 mt T 40

    mt T 40

    n z st 25 50 st 40 50 st 50 50 st 50 75*

    mt T 40 mt T 40 mt T 40*

    Green font denotes the recommended and commonly used batten specifcation in each region.

    * With engineer approval

    Where metal battens are used reer to the batten suppliers fxing specifcation.