Attachments to Section 4.2 - CF E&M

14
SCALE: NTS CAD File Name : Drawing No. : Scale Designed Drawn Checked of Sheet 1 1 A4 Date Approved Rev. - Drawing Title : Project Title : LTA Endorsement : Qualified Person Endorsement : Description Rev. Date By App’d Chk’d $DATE$ $TIME$ $FILE$ MELVYN THONG N.T.S. JULI JULY 2007 L/ROAD/MES/SD/1001 LROADMES-SD1001-.dgn NURLY STANDARD INSTALLATION DETAILS MALVIN HO T TYPICAL SINGLE LINE DIAGRAM FOR EXISTING OG-BOX (POB/LINKWAY/TAXI STAND/BUS SHELTER) TYPICAL SINGLE LINE DIAGRAM FOR EXISTING OG-BOX (POB / LINKWAY / TAXI STAND / BUS SHELTER) NOTES: 1. CONTRACTOR IS RESPONSIBLE TO REPLACE ITEM * TO A 32A RATING AND PROVIDE THE LINKWAY VICINITY AS SHOWN IN SLD (B)

Transcript of Attachments to Section 4.2 - CF E&M

Page 1: Attachments to Section 4.2 - CF E&M

SCALE: NTS

CAD File Name :

Drawing No. :

Scale

Designed

Drawn

Checked

ofSheet 1 1 A4

Date

Approved

Rev.

-

Drawing Title :

Project Title :

LTA Endorsement :

Qualified Person Endorsement :

DescriptionRev. Date By App’dChk’d

$DATE$ $TIME$ $FILE$

MELVYN THONG

N.T.S. JULI JULY 2007

L/ROAD/MES/SD/1001

LROADMES-SD1001-.dgn

NURLY

STANDARD INSTALLATION DETAILS

MALVIN HO

T

TYPICAL SINGLE LINE DIAGRAM FOR EXISTING OG-BOX

(POB/LINKWAY/TAXI STAND/BUS SHELTER)

TYPICAL SINGLE LINE DIAGRAM FOR EXISTING OG-BOX (POB / LINKWAY / TAXI STAND / BUS SHELTER)

NOTES:

1. CONTRACTOR IS RESPONSIBLE TO REPLACE ITEM * TO

A 32A RATING AND PROVIDE THE LINKWAY VICINITY

AS SHOWN IN SLD (B)

Page 2: Attachments to Section 4.2 - CF E&M

SCALE: NTS

CAD File Name :

Drawing No. :

Scale

Designed

Drawn

Checked

ofSheet 1 1 A4

Date

Approved

Rev.

-

Drawing Title :

Project Title :

LTA Endorsement :

Qualified Person Endorsement :

DescriptionRev. Date By App’dChk’d

$DATE$ $TIME$ $FILE$

MELVYN THONG

N.T.S. JULI JULY 2007

L/ROAD/MES/SD/1002

LROADMES-SD1002-.dgn

NURLY

STANDARD INSTALLATION DETAILS

MALVIN HO

TYPICAL SINGLE LINE DIAGRAM FOR NEW OG-BOX

(BUS SHELTER/LINKWAY)

NOTES:

1. CONTRACTOR IS RESPONSIBLE TO REPLACE ITEM * TO

A 32A RATING AND PROVIDE THE LINKWAY VICINITY

AS SHOWN IN SLD(B)

TYPICAL SINGLE LINE DIAGRAM FOR NEW OG-BOX (BUS SHELTER / LINKWAY)

Page 3: Attachments to Section 4.2 - CF E&M

SCALE: NTS

CAD File Name :

Drawing No. :

Scale

Designed

Drawn

Checked

ofSheet 1 1 A4

Date

Approved

Rev.

-

Drawing Title :

Project Title :

LTA Endorsement :

Qualified Person Endorsement :

DescriptionRev. Date By App’dChk’d

$DATE$ $TIME$ $FILE$

MELVYN THONG

N.T.S. JULI JULY 2007

L/ROAD/MES/SD/1003

LROADMES-SD1003-.dgn

NURLY

STANDARD INSTALLATION DETAILS

MALVIN HOTYPICAL SINGLE LINE DIAGRAM FOR NEW OG-BOX (BUS SHELTER)

TYPICAL SINGLE LINE DIAGRAM FOR NEW OG-BOX

(BUS SHELTER)

NOTES:

1. CONTRACTOR IS RESPONSIBLE TO REPLACE ITEM * TO

A 32A RATING AND PROVIDE THE LINKWAY VICINITY

AS SHOWN IN SLD(B).

Page 4: Attachments to Section 4.2 - CF E&M

SCALE: NTS

CAD File Name :

Drawing No. :

Scale

Designed

Drawn

Checked

ofSheet 1 1 A4

Date

Approved

Rev.

-

Drawing Title :

Project Title :

LTA Endorsement :

Qualified Person Endorsement :

DescriptionRev. Date By App’dChk’d

$DATE$ $TIME$ $FILE$

MELVYN THONG

N.T.S. JULI JULY 2007

L/ROAD/MES/SD/1004

LROADMES-SD1004-.dgn

NURLY

STANDARD INSTALLATION DETAILS

MALVIN HO

T

TYPICAL SINGLE LINE DIAGRAM FOR EXISTING OG-BOX

(DBO BUS SHELTER/POB/LINKWAY/TAXI STAND)

NOTES:

TYPICAL SINGLE LINE DIAGRAM FOR EXISTING OG-BOX (DBO BUS SHELTER / POB / LINKWAY / TAXI STAND)

1. CONTRACTOR IS RESPONSIBLE TO REPLACE ITEM * TO

A 32A RATING AND PROVIDE THE LINKWAY VICINITY

AS SHOWN IN SLD(B).

Page 5: Attachments to Section 4.2 - CF E&M

SCALE: NTS

CAD File Name :

Drawing No. :

Scale

Designed

Drawn

Checked

ofSheet 1 1 A4

Date

Approved

Rev.

-

Drawing Title :

Project Title :

LTA Endorsement :

Qualified Person Endorsement :

DescriptionRev. Date By App’dChk’d

$DATE$ $TIME$ $FILE$

MELVYN THONG

N.T.S. JULI JULY 2007

L/ROAD/MES/SD/1005

LROADMES-SD1005-.dgn

NURLY

STANDARD INSTALLATION DETAILS

MALVIN HO

TYPICAL DETAIL OF POB OG-BOX

TYPICAL DETAIL OF OG-BOX

SIDE VIEW

NAME PLATE

LAND TRANSPORTAUTHORITYLOGO

NEOPRENE SEAL

UV RESISTANTWINDOW C/W

CABLE ENTRYOPENING FOR

PLINTH C/W

WEATHERPROOF TO IP 54

EXTERNAL VIEW

ABLOY MASTER KEY

FOR POWERGRID

FRONT INTERNAL VIEW

REMOVEABLE

PLATE

ABLOY MASTER KEYAS PER LTA’s

REQUIREMENTS

2 NOS. POWER GRID

KWH METER

LEAD IN C/W 90^ LONG BEND PIPES

FOR POWER GRID INCOMING CABLING

2 NOS Ø100mm HEAVY DUTY uPVC

2 NOS Ø50mm

HEAVY DUTY

UPVC PIPE FOR

POB ELECTRICAL

DISTRIBUTION

2 NOS Ø50mm HEAVY DUTY

uPVC PIPE FOR FUTURE

BUS SHELTER ELECTRICAL

DISTRIBUTION

SINGAPORE 498825SPANNERS BUILDING

SPANNERS INTERNATIONAL PTE LTD6 CHANGI NORTH STREET 1

Certified Company9002ISO

CONTRRACT NO:SERIAL NO:

YEAR MANUFACTURE:

LAND TRANSPORT

LOGOAUTHORITY

300

Page 6: Attachments to Section 4.2 - CF E&M

SCALE: NTS

CAD File Name :

Drawing No. :

Scale

Designed

Drawn

Checked

ofSheet 1 1 A4

Date

Approved

Rev.

-

Drawing Title :

Project Title :

LTA Endorsement :

Qualified Person Endorsement :

DescriptionRev. Date By App’dChk’d

$DATE$ $TIME$ $FILE$

MELVYN THONG

N.T.S. JULI JULY 2007

L/ROAD/MES/SD/1006

LROADMES-SD1006-.dgn

NURLY

STANDARD INSTALLATION DETAILS

MALVIN HO

TYPICAL DETAIL OF POB OG-BOX

TYPICAL DETAIL OF OG-BOX

REMOVABLE PLATE

3273-A

ABLOY

FIX PLATE

70 70

REMOVABLE PLATE

70

27.5

82.5

REMOVABLE PLATE

27.5

82.5

1Ø KWH

METER

POWER

GRID

T’wood= 230

70

Std= 235

T’wood= 230

Std= 235

138138

T’wood= 230 T’wood= 230

560

1Ø KWH

METER

POWER

GRID

BI Supply

and Installed

By PG

3273-A

ABLOY

3273-A

ABLOY

EXTERNAL FRONT DOOR

PARTITION

FIX PLATE

Front

Back

EXTERNAL BACK DOOR

GLASS

EXTERNAL VIEW INTERNAL FRONT VIEW

PLAN VIEW

EXTERNAL BACK VIEW

BUS SHELTER

SIDE VIEWINTERNAL SIDE VIEW

SUPPORT FOR BREAKER

PARTITION

SUPPORTFOR BREAKER

EXTERNALFRONTDOOR

POB/LINKWAY

PARTITION

EXTERNAL FRONT DOOR

Ø100mm HEAVY DUTY UPVC PIPEFOR POB/LINKWAY ELECTRICAL DISTRIBUTION

GLASS GLASS

2 NOS Ø100mm HEAVY DUTY UPVCLEAD IN C/W 90^ LONG BEND PIPESFOR POWER GRID INCOMING CABLING

2 NOS Ø100mm HEAVY DUTY UPVCLEAD IN C/W 90^ LONG BEND PIPESFOR POWER GRID INCOMING CABLING

Ø100mm HEAVY DUTY UPVC PIPEFOR POB/LINKWAY ELECTRICAL DISTRIBUTION

Ø100mm HEAVY DUTY UPVC PIPEFOR BUS SHELTER ELECTRICAL DISTRIBUTION

PLINTH C/W OPENINGFOR CABLE ENTRY

Overall Length = min 1120mm

Overall Length = min 1120mm

420

Depth = min 450mm Depth = min 450mm

Ø50mm HEAVY DUTY UPVC PIPEFOR BUS SHELTER ADVERTISING PANEL

Ø100mm HEAVY DUTY UPVC PIPE FOR BUS SHELTER ELECTRICAL DISTRIBUTION

Ø50mm HEAVY DUTY UPVC PIPE FOR BUS SHELTER ADVERTISING PANEL

Page 7: Attachments to Section 4.2 - CF E&M

SCALE: NTS

CAD File Name :

Drawing No. :

Scale

Designed

Drawn

Checked

ofSheet 1 1 A4

Date

Approved

Rev.

-

Drawing Title :

Project Title :

LTA Endorsement :

Qualified Person Endorsement :

DescriptionRev. Date By App’dChk’d

$DATE$ $TIME$ $FILE$

MELVYN THONG

N.T.S. JULI JULY 2007

L/ROAD/MES/SD/1007

LROADMES-SD1007-.dgn

NURLY

STANDARD INSTALLATION DETAILS

MALVIN HO

TYPICAL LIGHTING LAYOUT PLAN AND

LIGHTNING PROTECTION SYSTEM

FOR BUS SHELTER (WITH OR WITHOUT RAILING)

2 NOS. Ø50mm HEAVY DUTY

UPVC PIPE C/W PULL WIRE

2 NOS. Ø100mm HEAVY DUTY UPVC

HEAD-IN 90^ LONG BEND PIPES FOR

POWERGRID’S INCOMING CABLE

1 NO. Ø50mm HEAVY DUTY

UPVC PIPE C/W PULL WIRES

FROM 0G-BOX TO ADVERTISING PANEL

PVC CABLE IN

FLEXIBLE CONDUIT

PROPOSED 1 x 18W

(IP 65) LIGHT FITTING

TYPICAL LIGHTNING PROTECTION SYSTEM LAYOUT PLAN

TYPICAL LIGHTING LAYOUT PLANSCALE: NTS

EARTH PIT

(TOTAL RESISTANCE < 10ohm)

EARTH PIT

(TOTAL RESISTANCE < 10ohm)

NEW

OG BOX

WITHOUT RAILING

A

A

ROOF EAVES ABOVE

R O A D

CONC. SLAB TO ENGR’S DTLS COMPLETE WITH 20mm THK

GRANOLITHIC FINISHES TO SO’S APPROVAL

MIN. 10mm THK. ALUM. HONEYCOMB ROOF

PANEL COMPLETE WITH MIN. 1 mm THK

TOP PANEL TO SO’S APPROVAL

1 2 3

1 2 3

7500

750 3000 3000 750

1400 100 1400

M.S. RHS POST UNDERNEATH TO ENGR’S DTL

ALUM. SEAT TO DTL

200 WIDE YELLOW LINE IN HOT APPLIED

THERMOPLASTIC ROAD MARKING MATERIALS

3

3

BUS STOP ADDRESS & NUMBER SIGN

PLATE TO FACE ONCOMING TRAFFIC IN

ACCORDANCE TO LTA STD DRAWING NO.

LTA/ARCH/CF/97/8/13 LATEST REVISION

LINE OF ROAD KERB OR ROAD RESERVE LINE

NOTICE BOARD WITH ALUM. FRAME C/W

10mm THK. TEMPERED GLASS

50 X 50 X 3 THK ALUM. ANGLE PLATE FOR

BUS STOP ADDRESS & NUMBER SIGN PLATE

MS ANGLE ROOF FASCIA TO ENGR’S DTL

ROOF CAPPING @ 1500mm C/C TO

MFR’S DTL

1 NO. ELECT. PIPE FOR ADVERTISEMENT

PANEL (AP) TO BE LOCATED AT THE

DOWNSTREAM EDGE OF BUS SHELTER

7500

750 3000 3000 750

1500 1500 1500 1500

M.S. RHS POST @ 3000 mm C/C TO ENGR’S DTL

Ø600 REFUSE BIN

Page 8: Attachments to Section 4.2 - CF E&M

SCALE: NTS

CAD File Name :

Drawing No. :

Scale

Designed

Drawn

Checked

ofSheet 1 1 A4

Date

Approved

Rev.

-

Drawing Title :

Project Title :

LTA Endorsement :

Qualified Person Endorsement :

DescriptionRev. Date By App’dChk’d

$DATE$ $TIME$ $FILE$

MELVYN THONG

N.T.S. JULI JULY 2007

L/ROAD/MES/SD/1008

LROADMES-SD1008-.dgn

NURLY

STANDARD INSTALLATION DETAILS

MALVIN HO

PROPOSED 1 x 18W (IP65) LIGHT FITTING

2 NOS Ø50mm HEAVY DUTY UPVC PIPES

2 NOS Ø100mm HEAVY DUTY UPVC

PIPES LEAD IN 90^ LONG BEND PIPES

FOR POWERGRID INCOMING CABLING

NEW OG BOX (IP55)

LOCATION SHALL BE SUBJECTED TO

SITE CONDITIONS AND POWERGRID’S APPROVAL

PROPOSED 1 x 18W (IP65) LIGHT FITTING

2 NOS Ø50mm HEAVY DUTY UPVC PIPES

BONDING TO ALUMINIUM SEAT

2 NOS Ø100mm HEAVY DUTY UPVC

PIPES LEAD IN 90^ LONG BEND PIPES

FOR POWERGRID INCOMING CABLING

NEW OG BOX (IP55)

LOCATION SHALL BE SUBJECTED TO

SITE CONDITIONS AND POWERGRID’S APPROVAL

6mÀ PVC EARTH BONDING CABLE IN

Ø25mm HEAVY DUTY UPVC PIPE

PVC CABLE IN PVC

FLEXIBLE CONDUIT

PVC CABLE IN PVC

FLEXIBLE CONDUIT

6mÀ PVC EARTH BONDING CABLE IN

Ø25mm HEAVY DUTY UPVC PIPE

LIGHT FITTING TO M&E SPECS & SHALL

NOT PROTRUDE FROM M.S. RAFTER /

CONTRACTOR TO PROPOSE FIXING

BRACKET FOR LIGHT FITTING

CONDUIT

ENCASED IN

CONCRETE

CONDUIT

ENCASED IN

CONCRETE

LIGHT FITTING TO M&E SPECS & SHALL

NOT PROTRUDE FROM M.S. RAFTER /

CONTRACTOR TO PROPOSE FIXING

BRACKET FOR LIGHT FITTING

TYPICAL FRONT ELEVATION OF BUS SHELTER (WITH RAILING)

SCALE: NTS

TYPICAL FRONT ELEVATION OF BUS SHELTER (WITHOUT RAILING) TYPICAL SECTION OF BUS SHELTER (WITHOUT RAILING)SCALE: NTS

SCALE: NTS

TYPICAL SECTION OF BUS SHELTER (WITH RAILING)

CABLE ENTRY

ACCESS PANEL

(REFER TO TYPICAL

SUPPORT POST DETAIL)

CABLE ENTRY

ACCESS PANEL

(REFER TO TYPICAL

SUPPORT POST DETAIL)

TYPICAL ELECTRICAL INSTALLATION DETAILS

FOR BUS SHELTER (WITH AND WITHOUT RAILING)

ELEVATION 1

FFL

1 2 3

ALUM. SEAT TO DTL

CONC. SLAB TO ENGR’S DTLS COMPLETE WITH

20mm THK GRANOLITHIC FINISHES TO SO’S APPROVAL

BUS STOP ADDRESS & NUMBER SIGN

PLATE TO FACE ONCOMING TRAFFIC IN

ACCORDANCE TO LTA STD DRAWING NO.

LTA/ARCH/CF/97/8/13 LATEST REVISION

(TO BE BOLTED TO ALUM. ANGLE PLATE)

NOTICE BOARD WITH ALUM. FRAME

C/W 10mm THK. TEMPERED GLASS

MS ANGLE ROOF FASCIA TO ENGR’S DTL

M.S. ’C’ CHANNEL RAFTER @ 3000 mm C/C

TO ENGR’S DETAIL

M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL

7500

750 3000 3000 750

1000 1000

1500 1500 1500 1500

M.S. RHS TO ENGR’S DETAIL

LIGHT FITTING TO M&E SPECS

REFUSE BIN TO BE FIXED IN POSITION

FFL

SECTION A-A

A

3^ FALL

FOOTING TO ENGR’ S DETAIL

M.S. ’C’ CHANNEL RAFTER @ 3000 mm C/C

TO ENGR’S DETAIL

M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL

M.S. ANGLE ROOF FASCIA TO ENGR’S DETAIL

ROAD

300

ALUM SEAT TO DETAIL

ELECTRICAL CABLE IN PVC

FLEXIBLE PIPE IN SUPPORT POST

(REFUSE BIN NOT SHOWN FOR CLARITY)

Scale 1 :20

REF. DWG. NO. L/STLBS/AR/STD/0002

MIN. 10mm THK. ALUM. HONEYCOMB ROOF

PANEL COMPLETE WITH MIN. 1 mm THK

TOP PANEL TO SO’S APPROVAL

CONC. SLAB TO ENGR’S DTL COMPLETE WITH 20mm THK

GRANOLITHIC FINISHES TO SO’S APPROVAL

3000 MIN. 600

300 2700

G.I. PIPE ALONG BACK OF M.S. FASCIA FOR

ELECT. CABLES TO M&E DWG. & SPEC.

LIGHT FITTING TO M&E SPECS & SHALL

NOT PROTRUDE FROM M.S. RAFTER /

CONTRACTOR TO PROPOSE FIXING

BRACKET FOR LIGHT FITTING

CATCH BASIN AND UPVC PIPE IN

ACCORDANCE WITH THE CURRENT

LTA STANDARD DETAILS OF ROAD

ELEMENTS

ELEVATION 1

S/S RAILING TO BE PROVIDED WHERE THERE

IS SUDDEN GREAT DIFFERENCE IN LEVEL

FFL

1 2 3

ALUM. SEAT TO DTL

BUS STOP ADDRESS & NUMBER SIGN

PLATE TO FACE ONCOMING TRAFFIC IN

ACCORDANCE TO LTA STD DRAWING NO.

LTA/ARCH/CF/97/8/13 LATEST REVISION

(TO BE BOLTED TO ALUM. ANGLE PLATE)

NOTICE BOARD WITH ALUM. FRAME

C/W 10mm THK. TEMPERED GLASS

MS ANGLE ROOF FASCIA TO ENGR’S DTL

M.S. ’C’ CHANNEL RAFTER @ 3000 mm C/C

TO ENGR’S DETAIL

M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL

7500

750 3000 3000 750

1000 1000

1500 1500 1500 1500

M.S. RHS TO ENGR’S DETAIL

LIGHT FITTING TO M&E SPECS

REFUSE BIN TO BE FIXED IN POSITION

FFL

SECTION A-A

A

3^ FALL

FOOTING TO ENGR’ S DETAIL

M.S. ’C’ CHANNEL RAFTER @ 3000 mm C/C

TO ENGR’S DETAIL

M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL

M.S. ANGLE ROOF FASCIA TO ENGR’S DETAIL

300

ALUM SEAT TO DETAIL

ELECTRICAL CABLE IN PVC

FLEXIBLE PIPE IN SUPPORT POST

(REFUSE BIN NOT SHOWN FOR CLARITY)

Scale 1 :20

REF. DWG. NO. L/STLBS/AR/STD/0004

MIN. 10mm THK. ALUM. HONEYCOMB ROOF

PANEL COMPLETE WITH MIN. 1 mm THK

TOP PANEL TO SO’S APPROVAL

CONC. SLAB TO ENGR’S DTL COMPLETE WITH 20mm THK

GRANOLITHIC FINISHES TO SO’S APPROVAL

3000 MIN. 600

300 2700

G.I. PIPE ALONG BACK OF M.S. FASCIA FOR

ELECT. CABLES TO M&E DWG. & SPEC.

LIGHT FITTING TO M&E SPECS & SHALL

NOT PROTRUDE FROM M.S. RAFTER /

CONTRACTOR TO PROPOSE FIXING

BRACKET FOR LIGHT FITTING

ROAD

CATCH BASIN AND UPVC PIPE IN

ACCORDANCE WITH THE CURRENT

LTA STANDARD DETAILS OF ROAD

ELEMENTS

Page 9: Attachments to Section 4.2 - CF E&M

CAD File Name :

Drawing No. :

Scale

Designed

Drawn

Checked

ofSheet 1 1 A4

Date

Approved

Rev.

-

Drawing Title :

Project Title :

LTA Endorsement :

Qualified Person Endorsement :

DescriptionRev. Date By App’dChk’d

$DATE$ $TIME$ $FILE$

MELVYN THONG

N.T.S. JULI JULY 2007

L/ROAD/MES/SD/1009

LROADMES-SD1009-.dgn

NURLY

STANDARD INSTALLATION DETAILS

MALVIN HO

TEAKWOOD FOR MOUNTING

CABLE GLAND FOR ARMOURED CABLE

C1 WELDED ALL-ROUND TO

300x300x20 THK MS PLATE

10mm THK NON SHRINK GROUT

TERMINAL BLOCK CONNECTOR

MOUNTED ON TEAKWOOD BLOCK

25mm x 3mm COPPER TAPE

FLAT BAR TO SUPPORT TEAKWOOD BLOCK

ARMOURED CABLE IN UPVC PIPE

PVC CABLE + 2.5mÀ PVC EARTH CABLE

IN FLEXIBLE CONDUIT

FROM OG BOX TO FIRST LIGHTING POINT

SECTION K-K

SECTION B-B

SECTION C-C

DETAIL 2

DETAIL 1

LIGHT FITTING TO M&E SPECS & SHALL NOT PROTRUDE FROM M.S. RAFTER /

CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING

ELECTRICAL CABLE CONCEALED IN PVC

FLEXIBLE CONDUIT TO M&E DWG. & SPEC.

LIGHT FITTING TO M&E SPECS & SHALL NOT PROTRUDE FROM M.S. RAFTER /

CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING

EARTH PIT

(TOTAL EARTH

RESISTANCE

<10 ohms)

TYPICAL SUPPORT POST DETAIL

TYPICAL CABLE ENTRY DETAIL FOR BUS SHELTER

SEE DETAIL X

SECTION Y-Y

Y-

Y-

25mm x 3mm COPPER TAPE

ALUMINIUM OR

STEEL SUPPORT POST

M8 ALUMINIUM COPPER BOLT

TO STEEL SUPPORT POST

DETAIL X´

A

Scale 1:5

DETAIL 1

GASKET

SECTION K-KScale 1:5

S/S SCREW

´

Scale 1:5

3^ FALL

S/S SCREW

ISOLATOR / BONDING TAPE BETWEEN

ALUM. ROOF FRAME & M.S. MEMBER

ISOLATOR / BONDING TAPE BETWEEN

ALUM. ROOF FRAME & M.S. MEMBER

1500

DETAIL 2

ISOLATOR / BONDING TAPE BETWEEN

ALUM. ROOF FRAME & M.S. MEMBER

750

M.S. ’C’ CHANNEL RAFTER TO ENGR’S DETAIL

M.S. ANGLE ROOF FASCIA

TO ENGR’S DETAIL

FFL

Scale 1:5

B-

B-

SECTION B-BScale 1:5

´

´

OPENING FOR INCOMING CABLES COVERED

BY POST CAPPING

(TO BE PROVIDED AT 1ST & LAST POST ONLY)

MS BASE PLATE TO ENGR’S DETAIL

CONC. SLAB TO ENGR’S DTL COMPLETE WITH

20mm THK GRANOLITHIC FINISHES TO SO’S APPROVAL

TYPICAL SUPPORT POST DETAIL

RC FOOTING TO ENGR’S DETAIL

M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL

Ø50 mm PVC FLEXIBLE CONDUIT

FOR INCOMING CABLES TO M&E DETAIL

K-

CENTRE LINE OF LIGHT FITTING

´

BUS STOP ADDRESS & NUMBER SIGN

PLATE TO FACE ONCOMING TRAFFIC IN

ACCORDANCE TO LTA STD DRAWING NO.

LTA/ARCH/CF/97/8/13 LATEST REVISION

(TO BE BOLTED TO ALUM. ANGLE PLATE)

MS RHS TO ENGR’S DETAIL

3000

300 2700

1500

MIN. 10mm THK. ALUM. HONEYCOMB ROOF

PANEL COMPLETE WITH MIN. 1mm THK.

TOP PANEL TO SO’S APPROVAL

MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL COMPLETE

WITH MIN. 1mm THK.TOP PANEL TO SO’S APPROVAL

MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL

COMPLETE WITH MIN. 1mm THK. TOP PANEL

TO SO’S APPROVAL

K-

10

100 100

M.S. ANGLE ROOF FASCIA TO ENGR’S DETAIL

3%%d

40

40

G.I. PIPE ALONG BACK OF M.S. FASCIA

FOR ELECT. CABLES TO M&E DWG. & SPEC.

M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL

M.S. ’C’ CHANNEL RAFTER @ 3000 mm C/C TO ENGR’S DETAIL

200

3%%d

ALUM. ROOF CAPPING FOR ROOF PANEL TO MFR’S DETAIL

C-

C-

SECTION C-CScale 1:5

M.S. ’C’ CHANNEL RAFTER TO ENGR’S DETAIL

MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL

COMPLETE WITH MIN. 1mm THK. TOP PANEL

TO SO’S APPROVAL

ALUM. ROOF CAPPING FOR ROOF PANEL

TO MFR’S DETAIL

M.S. ANGLE ROOF FASCIA TO ENGR’S DETAIL

M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL

G.I. PIPE ALONG BACK OF M.S. FASCIA

FOR ELECT. CABLES TO M&E DWG. & SPEC.

ELECTRICAL CABLE CONCEALED IN PVC

FLEXIBLE CONDUIT TO M&E DWG. & SPEC.

OPENING FOR INCOMING CABLES COVERED

BY POST CAPPING

(TO BE PROVIDED AT 1ST & LAST POST ONLY)

ELECTRICAL CABLE CONCEALED IN PVC

FLEXIBLE CONDUIT IN SUPPORT POST

LIGHT FITTING MOUNTING BRACKET TO CONTRACTOR PROPOSAL

LIGHT FITTING TO M&E SPECS & SHALL NOT PROTRUDE FROM M.S. RAFTER /

CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING

LIGHT FITTING TO M&E SPECS & SHALL NOT PROTRUDE FROM M.S. RAFTER /

CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING

Page 10: Attachments to Section 4.2 - CF E&M

CAD File Name :

Drawing No. :

Scale

Designed

Drawn

Checked

ofSheet 1 1 A4

Date

Approved

Rev.

-

Drawing Title :

Project Title :

LTA Endorsement :

Qualified Person Endorsement :

DescriptionRev. Date By App’dChk’d

$DATE$ $TIME$ $FILE$

MELVYN THONG

N.T.S. JULI JULY 2007

L/ROAD/MES/SD/1010

LROADMES-SD1010-.dgn

NURLY

STANDARD INSTALLATION DETAILS

MALVIN HO

EARTH ROD

25mm x 3mm ALUMINIUM CONDUCTOR TAPE

ENCASED IN Ø50mm HEAVY DUTY UPVC PIPE

25mm x 3mm COPPER CONDUCTOR TAPE

ENCASED IN Ø50mm HEAVY DUTY UPVC PIPE

EARTH ROD

25mm x 3mm ALUMINIUM CONDUCTOR TAPE

ENCASED IN Ø50mm HEAVY DUTY UPVC PIPE

25mm x 3mm COPPER CONDUCTOR TAPE

ENCASED IN Ø50mm HEAVY DUTY UPVC PIPE

PIPE SLEEVE PIPE SLEEVE

PURPOSE MADE BOND

CONTRACTOR TO ENSURE THAT BONDED

IN ACCORDANCE TO CP33 REQUIREMENTS

PURPOSE MADE BOND

CONTRACTOR TO ENSURE THAT BONDED

IN ACCORDANCE TO CP33 REQUIREMENTS

EARTH PIT

(TOTAL EARTH RESISTANCE 10ohms)

EARTH PIT

(TOTAL EARTH RESISTANCE 10ohms)

TYPICAL LIGHTNING PROTECTION SYSTEM

FOR COVERED PEDESTRIAN OVERHEAD BRIDGE

FOR COVERED POB (EXPRESSWAY)

FOR COVERED POB (NON-EXPRESSWAY)

UPVC PIPE SEALED

WITH APPROVED

SEALANT TO PREVENT

WATER INGRESS

BI-METALLIC BOND/CLAMP AND

ALUMINIUM CONDUCTOR TAPE

BOLTED ON BEARING PLATE.

CONCRETE SURFACE PAINTED OVER

TO PREVENT ALUMINIUM TAPE

TO HAVE DIRECT CONTACT

WITH CONCRETE SURFACE

DETAIL X

BI-METALLIC BOND/CLAMP AND ALUMINIUM CONDUCTOR TAPE

BOLTED ON BEARING PLATE CONCRETE SURFACE

PAINTED OVER TO PREVENT ALUMINIUM TAPE

TO HAVE DIRECT CONTACT WITH CONCRETE SURFACE

(SEE DETAIL X)

BI-METALLIC BOND/CLAMP AND ALUMINIUM CONDUCTOR TAPE

BOLTED ON BEARING PLATE CONCRETE SURFACE

PAINTED OVER TO PREVENT ALUMINIUM TAPE

TO HAVE DIRECT CONTACT WITH CONCRETE SURFACE

(SEE DETAIL X)

ENCASED HEAVY

DUTY UPVC PIPES

STAINLESS STEEL

COVER PLATE

ENCASED HEAVY

DUTY UPVC PIPES

R.C. COLUMN25mm x 3mm

COPPER TAPE

BI-METALLIC

CONNECTOR

PROTECTION

TEST

BOX

LIGHTNING

NUT INSERTM5 COUNTERSUNK BOLT

Y-

Y-

STAINLESS STEEL

COVER PLATE

SECTION Y-Y

25mm x 3mm

ALUMINIUM TAPE

BI-METALLIC

CONNECTOR

25mm x 3mm

COPPER TAPE

25mm x 3mm

ALUMINIUM TAPE

TYPICAL LIGHTNING PROTECTIONTEST BOX AT POB

ELEVATION VIEW(WITH COVER)

ELEVATION VIEW(WITHOUT COVER)

150mm x 150mm TEST LINK BOX

AT 1500mm HEIGHT FROM

GROUND LEVEL (SURFACE MOUNT)

IN ACCORDANCE TO CP33 REQUIREMENTS

(SEE TYPICAL LIGHTNING PROTECTION

TEST BOX AT POB)

150mm x 150mm TEST LINK BOX

AT 1500mm HEIGHT FROM

GROUND LEVEL (SURFACE MOUNT)

IN ACCORDANCE TO CP33 REQUIREMENTS

(SEE TYPICAL LIGHTNING PROTECTION

TEST BOX AT POB)

10x10mm CHAMFER

TO ROADSIDE DRAIN

12%%d

PILE CAP TO ENGR’S DETAIL

R.C. GRATING

2800

3702060370

1800

MIN. 40 MIN. 40

EQ EQ

FALL

2200 700

75

675

625

´ OF POB DECK

AND ROOF

TYPICAL CROSS BEAM

TO ENGR’S DETAIL

RC COLUMN TO ENGR’S DETAIL WITH

20mm THK PRECASTED GRANOLITHIC

CHIPPING FINISHED TO S.O’S APPROVAL

10x10mm CHAMFER

TO ROADSIDE DRAIN

12%%d

PILE CAP TO ENGR’S DETAIL

2800

3702060370

1800

MIN. 40 MIN. 40

EQ EQ

FALL

2200 700

75

675

625

TYPICAL CROSS BEAM

TO ENGR’S DETAIL

RC COLUMN TO ENGR’S DETAIL WITH

20mm THK PRECASTED GRANOLITHIC

CHIPPING FINISHED TO S.O’S APPROVAL

Ø45mm S.S. RAILING Ø45mm S.S. RAILING

CHS HOT-DIPPED GALVANISED M.S. POST

TO ENGR’S DETAIL COMPLETE WITH SPRAY

COATING FINISH TO SO’S APPROVAL

CHS HOT-DIPPED GALVANISED M.S. MEMBER

TO ENGR’S DETAIL COMPLETE WITH SPRAY

COATING FINISH TO SO’S APPROVAL

´ OF POB DECK

AND ROOF

CHS HOT-DIPPED GALVANISED M.S. POST

TO ENGR’S DETAIL COMPLETE WITH SPRAY

COATING FINISH TO SO’S APPROVAL

CHS HOT-DIPPED GALVANISED M.S. MEMBER

TO ENGR’S DETAIL COMPLETE WITH SPRAY

COATING FINISH TO SO’S APPROVAL

FALL FALL

20mm THK PRECASTED GRANOLITHIC

CHIPPING FINISHED TO S.O’S APPROVAL

PLANTING TROUGH WITH WATERPROOFING

MEMBRANE TO SO’S APPROVAL

PLANTING TROUGH WITH WATERPROOFING

MEMBRANE TO SO’S APPROVAL

20mm THK PRECASTED GRANOLITHIC

CHIPPING FINISHED TO S.O’S APPROVAL

R.C. GRATING

Ø50mm PVC PIPE FOR LIGHTING CIRCUITS

TO OG BOX TO M&E SPECIFICATIONS

FFL OF

POB DECK

Ø15mm S.S. ROD AT NOT MORE THAN 100mm CLEAR Ø15mm S.S. ROD AT NOT MORE THAN 100mm CLEAR

FFL OF

POB DECK

FOOTPATH LEVEL

ROAD LEVEL

FOOTPATH LEVEL

ROAD LEVEL

MIN. 10mm THK. ALUM. HONEY COMB ROOF PANEL COMPLETE

WITH MIN. 1mm THK. TOP PANEL TO SO’S APPROVAL

MIN. 10mm THK. ALUM. HONEY COMB ROOF PANEL COMPLETE

WITH MIN. 1mm THK. TOP PANEL TO SO’S APPROVAL

Page 11: Attachments to Section 4.2 - CF E&M

CAD File Name :

Drawing No. :

Scale

Designed

Drawn

Checked

ofSheet 1 1 A4

Date

Approved

Rev.

-

Drawing Title :

Project Title :

LTA Endorsement :

Qualified Person Endorsement :

DescriptionRev. Date By App’dChk’d

$DATE$ $TIME$ $FILE$

MELVYN THONG

N.T.S. JULI JULY 2007

L/ROAD/MES/SD/1011

LROADMES-SD1011-.dgn

NURLY

STANDARD INSTALLATION DETAILS

MALVIN HO

EARTH ROD

25mm x 3mm ALUMINIUM CONDUCTOR TAPE

ENCASED IN Ø50mm HEAVY DUTY UPVC PIPE

25mm x 3mm COPPER CONDUCTOR TAPE

ENCASED IN Ø50mm HEAVY DUTY UPVC PIPE

EARTH ROD

25mm x 3mm ALUMINIUM CONDUCTOR TAPE

ENCASED IN Ø50mm HEAVY DUTY UPVC PIPE

25mm x 3mm COPPER CONDUCTOR TAPE

ENCASED IN Ø50mm HEAVY DUTY UPVC PIPE

PIPE SLEEVE

EARTH PIT

(TOTAL EARTH RESISTANCE 10ohms)

EARTH PIT

(TOTAL EARTH RESISTANCE 10ohms)

TYPICAL LIGHTNING PROTECTION SYSTEM

FOR UNCOVERED PEDESTRIAN OVERHEAD BRIDGE

FOR UNCOVERED POB (EXPRESSWAY)

FOR UNCOVERED POB (NON-EXPRESSWAY)

25mm x 3mm ALUMINIUM CONDUCTOR TAPE

PIPE SLEEVE

25mm x 3mm ALUMINIUM CONDUCTOR TAPEUPVC PIPE SEALED

WITH APPROVED

SEALANT TO PREVENT

WATER INGRESS

BI-METALLIC BOND/CLAMP AND

ALUMINIUM CONDUCTOR TAPE

BOLTED ON BEARING PLATE.

CONCRETE SURFACE PAINTED OVER

TO PREVENT ALUMINIUM TAPE

TO HAVE DIRECT CONTACT

WITH CONCRETE SURFACE

DETAIL X

BI-METALLIC BOND/CLAMP AND ALUMINIUM CONDUCTOR TAPE

BOLTED ON BEARING PLATE CONCRETE SURFACE

PAINTED OVER TO PREVENT ALUMINIUM TAPE

TO HAVE DIRECT CONTACT WITH CONCRETE SURFACE

(SEE DETAIL X)

BI-METALLIC BOND/CLAMP AND ALUMINIUM CONDUCTOR TAPE

BOLTED ON BEARING PLATE CONCRETE SURFACE

PAINTED OVER TO PREVENT ALUMINIUM TAPE

TO HAVE DIRECT CONTACT WITH CONCRETE SURFACE

(SEE DETAIL X)

ENCASED HEAVY

DUTY UPVC PIPES

STAINLESS STEEL

COVER PLATE

ENCASED HEAVY

DUTY UPVC PIPES

R.C. COLUMN25mm x 3mm

COPPER TAPE

BI-METALLIC

CONNECTOR

PROTECTION

TEST

BOX

LIGHTNING

NUT INSERTM5 COUNTERSUNK BOLT

Y-

Y-

STAINLESS STEEL

COVER PLATE

SECTION Y-Y

25mm x 3mm

ALUMINIUM TAPE

BI-METALLIC

CONNECTOR

25mm x 3mm

COPPER TAPE

25mm x 3mm

ALUMINIUM TAPE

TYPICAL LIGHTNING PROTECTIONTEST BOX AT POB

ELEVATION VIEW(WITH COVER)

ELEVATION VIEW(WITHOUT COVER)

150mm x 150mm TEST LINK BOX

AT 1500mm HEIGHT FROM

GROUND LEVEL (SURFACE MOUNT)

IN ACCORDANCE TO CP33 REQUIREMENTS

(SEE TYPICAL LIGHTNING PROTECTION

TEST BOX AT POB)150mm x 150mm TEST LINK BOX

AT 1500mm HEIGHT FROM

GROUND LEVEL (SURFACE MOUNT)

IN ACCORDANCE TO CP33 REQUIREMENTS

(SEE TYPICAL LIGHTNING PROTECTION

TEST BOX AT POB)

S.S. LIGHTING ENCASEMENT TO DETAIL

TO ROADSIDE DRAIN

PILE CAP TO ENGR’S DETAIL

R.C. GRATING

1800

MIN. 40 MIN. 40

FALL

LIGHT FITTING TO M&E SPEC. & SO’S APPROVAL

2200 700

75

675

625

TYPICAL CROSS BEAM

TO ENGR’S DETAIL

RC COLUMN TO ENGR’S DETAIL WITH

20mm THK PRECASTED GRANOLITHIC

CHIPPING FINISHED TO S.O’S APPROVAL

S.S. LIGHTING ENCASEMENT TO DETAIL

TO ROADSIDE DRAIN

PILE CAP TO ENGR’S DETAIL

R.C. GRATING

1800

MIN. 40 MIN. 40

FALL

2200 700

75

675

625

TYPICAL CROSS BEAM

TO ENGR’S DETAIL

RC COLUMN TO ENGR’S DETAIL WITH

20mm THK PRECASTED GRANOLITHIC

CHIPPING FINISHED TO S.O’S APPROVAL

Ø45mm S.S. RAILING Ø45mm S.S. RAILING

LOCATION OF SUPPORT POST FOR FUTURE COVERLOCATION OF SUPPORT POST FOR FUTURE COVER

FALL FALL

20mm THK PRECASTED GRANOLITHIC

CHIPPING FINISHED TO S.O’S APPROVAL

PLANTING TROUGH WITH WATERPROOFING

MEMBRANE TO SO’S APPROVAL

Ø100mm PVC PIPE WITH Ø5mm HOLES

PERFORATION AT 100mm C/C ALL DIRECTIONS

PLANTING TROUGH WITH WATERPROOFING

MEMBRANE TO SO’S APPROVAL

Ø100mm PVC PIPE WITH Ø5mm HOLES

PERFORATION AT 100mm C/C ALL DIRECTIONS

20mm THK PRECASTED GRANOLITHIC

CHIPPING FINISHED TO S.O’S APPROVAL

FFL OF

POB DECK

FFL OF

POB DECK

Ø15mm S.S. ROD AT NOT MORE THAN 100mm CLEAR

FOOTPATH LEVEL

ROAD LEVEL

FOOTPATH LEVEL

ROAD LEVEL

Page 12: Attachments to Section 4.2 - CF E&M

CAD File Name :

Drawing No. :

Scale

Designed

Drawn

Checked

ofSheet 1 1 A4

Date

Approved

Rev.

-

Drawing Title :

Project Title :

LTA Endorsement :

Qualified Person Endorsement :

DescriptionRev. Date By App’dChk’d

$DATE$ $TIME$ $FILE$

MELVYN THONG

N.T.S. JULI JULY 2007

L/ROAD/MES/SD/1012

LROADMES-SD1012-.dgn

NURLY

STANDARD INSTALLATION DETAILS

MALVIN HO

SECTION K-K

SECTION B-B

SECTION C-C

TEAKWOOD FOR MOUNTING

CABLE GLAND FOR ARMOURED CABLE

C1 WELDED ALL-ROUND TO

300x300x20 THK MS PLATE

10mm THK NON SHRINK GROUT

TERMINAL BLOCK CONNECTOR

MOUNTED ON TEAKWOOD BLOCK

FLAT BAR TO SUPPORT TEAKWOOD BLOCK

25mm x 3mm

COPPER TAPE

DETAIL 1

PVC CABLE + 2.5mÀ PVC EARTH CABLE

IN FLEXIBLE CONDUIT

ARMOURED CABLE IN UPVC PIPE

FROM OG BOX TO FIRST LIGHTING POINT

G.I. PIPE ALONG BACK OF M.S. FASCIA

FOR ELECT. CABLES TO M&E DWG. & SPEC.

EARTH PIT

(TOTAL EARTH

RESISTANCE

<10 ohms)

LIGHT FITTING TO M&E SPEC. & SHALL NOT PROTRUDE FROM M.S. RAFTER /

CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING

TYPICAL CROSS SECTION FOR SINGLE POST COVERED LINKWAY

LIGHT FITTING TO M&E SPEC & SHALL NOT PROTRUDE FROM M.S. RAFTER /

CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING ELECTRICAL CABLE CONCEALED IN PVC

FLEXIBLE CONDUIT IN SUPPORT POST

LIGHT FITTING TO M&E SPEC

(DESIGN TO REFER TO ARCH DWG)

LIGHT FITTING TO M&E SPEC & SHALL NOT PROTRUDE FROM M.S. RAFTER /

CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING

TYPICAL LONGITUDINAL CROSS SECTION AT ROOF WITH LEVEL DIFFERENCE

LIGHT FITTING TO M&E SPEC & SHALL NOT PROTRUDE FROM M.S. RAFTER /

CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING

TYPICAL CABLE ENTRY DETAIL

FOR SINGLE POST COVERED LINKWAY

SEE DETAIL X

SECTION Y-Y

Y-

Y-

25mm x 3mm COPPER TAPE

ALUMINIUM OR

STEEL SUPPORT POST

M8 ALUMINIUM COPPER BOLT

TO STEEL SUPPORT POST

DETAIL X

´

A

Scale 1:5

DETAIL 1

GASKET

SECTION K-K

S/S SCREW

´

Scale 1:5

3^ FALL

S/S SCREW

ISOLATOR / BONDING TAPE BETWEEN

ALUM. ROOF FRAME & M.S. MEMBER

ISOLATOR / BONDING TAPE BETWEEN

ALUM. ROOF FRAME & M.S. MEMBER

1500

SECTION J-J

TYPICAL LONGITUDINAL CROSS SECTION AT ROOF WITH LEVEL DIFFERENCE

DETAIL 2

ISOLATOR / BONDING TAPE BETWEEN

ALUM. ROOF FRAME & M.S. MEMBER

ELECTRICAL CABLE CONCEALED IN PVC

FLEXIBLE CONDUIT IN SUPPORT POST

M.S. ’C’ CHANNEL RAFTER TO ENGR’S DETAIL

M.S. ANGLE ROOF FASCIA

TO ENGR’S DETAIL

M.S. ANGLE ROOF FASCIA

TO ENGR’S DETAIL

40

FFL

Scale 1:5

B-

B-

SECTION B-BScale 1:5

´

´

MS BASE PLATE TO ENGR’S DETAIL

OPENING FOR INCOMING CABLES COVERED

BY POST CAPPING

(TO BE PROVIDED AT 1ST & LAST POST ONLY)

CONC. SLAB TO ENGR’S DTL COMPLETE WITH

20mm THK GRANOLITHIC FINISHES TO SO’S APPROVAL

TYPICAL SUPPORT POST DETAIL

RC FOOTING TO ENGR’S DETAIL

M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL

Ø50 mm PVC FLEXIBLE CONDUIT

FOR INCOMING CABLES TO M&E DETAIL

M.S. ’C’ CHANNEL RAFTER TO ENGR’S DETAIL

M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL

50 x 50 x 3 ALUM ANGLE PLATE

MS RHS TO ENGR’S DETAIL

100 100

750

Scale 1:5

REF. DWG. NO. L/STLLW/AR/STD/1002

Scale 1:5

REF. DWG. NO. L/STLLW/AR/STD/1002

300

MIN. 10mm THK. ALUM. HONEYCOMB ROOF

PANEL COMPLETE WITH MIN. 1mm THK.

TOP PANEL TO SO’S APPROVAL

MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL COMPLETE

WITH MIN. 1mm THK.TOP PANEL TO SO’S APPROVAL

MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL

COMPLETE WITH MIN. 1mm THK. TOP PANEL

TO SO’S APPROVAL

MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL

COMPLETE WITH MIN. 1mm THK. TOP PANEL

TO SO’S APPROVAL

750

¨81

750

M.S. ANGLE ROOF FASCIA TO ENGR’S DETAIL

ALUM FLASHING PIECE BOLTED AT BOTH END

OPENING FOR INCOMING CABLES COVERED

BY POST CAPPING

(TO BE PROVIDED AT 1ST & LAST POST ONLY)

M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL

C-

C-

SECTION C-CScale 1:5

M.S. ’C’ CHANNEL RAFTER TO ENGR’S DETAIL

MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL

COMPLETE WITH MIN. 1mm THK. TOP PANEL

TO SO’S APPROVAL

ALUM. ROOF CAPPING FOR ROOF PANEL TO MFR’S DETAIL

ALUM. ROOF CAPPING FOR ROOF PANEL

TO MFR’S DETAIL

M.S. ANGLE ROOF FASCIA TO ENGR’S DETAIL

M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL

G.I. PIPE ALONG BACK OF M.S. FASCIA

FOR ELECT. CABLES TO M&E DWG. & SPEC.

ELECTRICAL CABLE CONCEALED IN PVC

FLEXIBLE CONDUIT TO M&E DWG. & SPEC.

G.I. PIPE ALONG BACK OF M.S. FASCIA

FOR ELECT. CABLES TO M&E DWG. & SPEC.

ALUM. ROOF CAPPING FOR ROOF PANEL

TO MFR’S DETAIL

M.S. ’C’ CHANNEL RAFTER @ 3000 mm C/C TO ENGR’S DETAIL

LIGHT FITTING TO M&E SPEC & SHALL NOT PROTRUDE FROM M.S. RAFTER /

CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING

LIGHT FITTING TO M&E SPEC & SHALL NOT PROTRUDE FROM M.S. RAFTER /

CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING

LIGHT FITTING TO M&E SPEC. & SHALL NOT PROTRUDE FROM M.S. RAFTER /

CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING

LIGHT FITTING MOUNTING BRACKET TO CONTRACTOR PROPOSAL

LIGHT FITTING TO M&E SPEC & SHALL NOT PROTRUDE FROM M.S. RAFTER /

CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING

Page 13: Attachments to Section 4.2 - CF E&M

CAD File Name :

Drawing No. :

Scale

Designed

Drawn

Checked

ofSheet 1 1 A4

Date

Approved

Rev.

-

Drawing Title :

Project Title :

LTA Endorsement :

Qualified Person Endorsement :

DescriptionRev. Date By App’dChk’d

$DATE$ $TIME$ $FILE$

MELVYN THONG

N.T.S. JULI JULY 2007

L/ROAD/MES/SD/1013

LROADMES-SD1013-.dgn

NURLY

STANDARD INSTALLATION DETAILS

MALVIN HO

SECTION D-D

SECTION C-C

TEAKWOOD FOR MOUNTING

CABLE GLAND FOR ARMOURED CABLE

C1 WELDED ALL-ROUND TO

300x300x20 THK MS PLATE

10mm THK NON SHRINK GROUT

TERMINAL BLOCK CONNECTOR

MOUNTED ON TEAKWOOD BLOCK

FLAT BAR TO SUPPORT TEAKWOOD BLOCK

25mm x 3mm

COPPER TAPE

PVC CABLE + 2.5mÀ PVC EARTH CABLE

IN FLEXIBLE CONDUIT

ARMOURED CABLE IN UPVC PIPE

FROM OG BOX TO FIRST LIGHTING POINT

EARTH PIT

(TOTAL EARTH

RESISTANCE

<10 ohms)

TYPICAL CROSS SECTION FOR DOUBLE POST COVERED LINKWAY

ELECTRICAL CABLE CONCEALED IN PVC

FLEXIBLE CONDUIT IN SUPPORT POST

LIGHT FITTING TO M&E SPEC

(DESIGN TO REFER TO ARCH DWG)

TYPICAL LONGITUDINAL CROSS SECTION AT ROOF WITH LEVEL DIFFERENCE

TYPICAL CABLE ENTRY DETAIL

FOR DOUBLE POST COVERED LINKWAY

LIGHT FITTING TO M&E SPEC. / CONTRACTOR TO

PROPOSE MOUNTING BRACKET FOR LIGHT FITTING

SECTION B-B

LIGHT FITTING TO M&E SPEC. / CONTRACTOR TO

PROPOSE MOUNTING BRACKET FOR LIGHT FITTING

SEE DETAIL X

SECTION Y-Y

Y-

Y-

25mm x 3mm COPPER TAPE

ALUMINIUM OR

STEEL SUPPORT POST

M8 ALUMINIUM COPPER BOLT

TO STEEL SUPPORT POST

DETAIL X

A B

FFL

Scale 1:5

B-

B-

CONC. SLAB TO ENGR’S DTL COMPLETE WITH

20mm THK GRANOLITHIC FINISHES TO SO’S APPROVAL

RC FOOTING TO ENGR’S DETAIL

3^ FALL

S/S SCREW

ISOLATOR / BONDING TAPE BETWEEN

ALUM. ROOF FRAME & M.S. MEMBER

MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL COMPLETE

WITH MIN. 1mm THK.TOP PANEL TO SO’S APPROVAL

ELECTRICAL CABLE CONCEALED IN PVC

FLEXIBLE CONDUIT IN SUPPORT POST

2400

CENTRE OF LIGHT FITTING

1200

100 100

M.S. ’C’ CHANNEL RAFTER @ 3000 mm C/C TO ENGR’S DETAIL

TYPICAL CROSS SECTION

SECTION B-BScale 1:5

´

´

´

GASKET

SECTION D-D

´

1500

ISOLATOR / BONDING TAPE BETWEEN

ALUM. ROOF FRAME & M.S. MEMBER

M.S. ANGLE ROOF FASCIA

TO ENGR’S DETAIL

750

MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL

COMPLETE WITH MIN. 1mm THK. TOP PANEL

TO SO’S APPROVAL

ALUM. ROOF CAPPING FOR ROOF PANEL TO MFR’S DETAIL

Scale 1:5

300 1800 300

G.I. PIPE ALONG BACK OF M.S. FASCIA

FOR ELECT. CABLES TO M&E DWG. & SPEC.

PVC FLEXIBLE CONDUIT FOR

INCOMING CABLES TO M&E DETAIL

M.S. ’C’ CHANNEL RAFTER @ 3000 mm C/C TO ENGR’S DETAIL

SECTION C-CScale 1:5

M.S. ’C’ CHANNEL RAFTER TO ENGR’S DETAIL

MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL

COMPLETE WITH MIN. 1mm THK. TOP PANEL

TO SO’S APPROVAL

ALUM. ROOF CAPPING FOR ROOF PANEL

TO MFR’S DETAIL

M.S. ANGLE ROOF FASCIA TO ENGR’S DETAIL

G.I. PIPE ALONG BACK OF M.S. FASCIA

FOR ELECT. CABLES TO M&E DWG. & SPEC.

ELECTRICAL CABLE CONCEALED IN PVC

FLEXIBLE CONDUIT TO M&E DWG. & SPEC.

C-

C-

OPENING FOR INCOMING CABLES COVERED

BY POST CAPPING

(TO BE PROVIDED AT 1ST & LAST POST ONLY)

40

80

LIGHT FITTING MOUNTING BRACKET TO CONTRACTOR PROPOSAL100

40

LIGHT FITTING TO M&E SPEC. / CONTRACTOR TO

PROPOSE MOUNTING BRACKET FOR LIGHT FITTING

M.S. ANGLE ROOF FASCIA

TO ENGR’S DETAIL

1720 BOTTOM OPENING FOR INCOMING CABLES

COVERED BY POST CAPPING

(TO BE PROVIDED AT 1ST & LAST POST)

M.S. SUPPORT POST @ 3000 mm C/C TO ENGR’S DETAIL

M.S. SUPPORT POST @ 3000 mm C/C TO ENGR’S DETAIL

M.S. SUPPORT POST @ 3000 mm C/C

TO ENGR’S DETAIL

M.S. SUPPORT POST @ 3000 mm C/C TO ENGR’S DETAIL

M.S. BASE PLATE TO ENGR’S DETAIL

M.S. RHS TO ENGR’S DETAIL

LIGHT FITTING TO M&E SPEC. / CONTRACTOR TO

PROPOSE MOUNTING BRACKET FOR LIGHT FITTING

FFL

SECTION E-E

TYPICAL LONGITUDINAL CROSS SECTION AT ROOF WITH LEVEL DIFFERENCE

M.S. ’C’ CHANNEL RAFTER TO ENGR’S DETAIL

50 X 50 X 3 ALUM ANGLE PLATE

Scale 1:5

REF. DWG. NO. L/STLLW/AR/STD/2002

MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL

COMPLETE WITH MIN. 1mm THK. TOP PANEL

TO SO’S APPROVAL

750

¨81

750

M.S. ANGLE ROOF FASCIA TO ENGR’S DETAIL

ALUM FLASHING PIECE BOLTED AT BOTH END

ALUM. ROOF CAPPING FOR ROOF PANEL

TO MFR’S DETAIL

M.S. SUPPORT POST @ 3000 mm C/C TO ENGR’S DETAIL

LIGHT FITTING TO M&E SPEC. / CONTRACTOR TO

PROPOSE MOUNTING BRACKET FOR LIGHT FITTING

Page 14: Attachments to Section 4.2 - CF E&M

CAD File Name :

Drawing No. :

Scale

Designed

Drawn

Checked

ofSheet 1 1 A4

Date

Approved

Rev.

-

Drawing Title :

Project Title :

LTA Endorsement :

Qualified Person Endorsement :

DescriptionRev. Date By App’dChk’d

$DATE$ $TIME$ $FILE$

MELVYN THONG

N.T.S. JULI JULY 2007

L/ROAD/MES/SD/1014

LROADMES-SD1014-.dgn

NURLY

STANDARD INSTALLATION DETAILS

MALVIN HO

TYPICAL OG BOX POSITION FOR COVERED LINKWAY

EARTH

PIT

EARTH

PIT

BONDING DETAILS TO

ROOF SPECIALIST’S REQUIREMENTS

BONDING TO UPPER ROOF

LIGHTNING PROTECTION SYSTEM

(BONDING DETAILS TO ROOF

SPECIALIST’S REQUIREMENTS)

BONDING TO UPPER ROOF

LIGHTNING PROTECTION SYSTEM

(BONDING DETAILS TO ROOF

SPECIALIST’S REQUIREMENTS)

BONDING DETAILS TO

ROOF SPECIALIST’S REQUIREMENTS

OG BOX

2 NOS. Ø100mm HEAVY DUTY UPVC PIPE

EMBEDED UNDER GROUND FOR POWERGRID

INCOMING CABLES TO M&E SPEC. & APPROVAL

(LOCATION & ORIENTATION TO BE

DETERMINED ON SITE)

(LOCATION TO BE DETERMINED

ON SITE & TO RO APPROVAL)

BONDING DETAILS TO

ROOF SPECIALIST’S REQUIREMENTS

OG BOX ON CONC. PLINTH TO M&E DTLS

(LOCATION TO BE DETERMINED ON SITE &

TO POWERGRID’S APPROVAL)

LIGHTNING PROTECTION LAYOUT PLAN

OG BOX POSITION LAYOUT PLAN

FRONT ELEVATION OF OG BOX POSITION

FRONT ELEVATION OF LIGHTNING PROTECTION LAYOUT PLAN

1 2 3 4 5 6 7

A

A

Scale 1:50

Scale 1:50

Scale 1:50

1-

1-

ROOF EAVES ABOVE

1500 1500

750 3000 3000 3000 3000 3000 3000 750

1 2 3 4 5 6 7

1 2 4 5 7

1 2 3 4 5 6 7

R O A D

FRONT ELEVATION 1 (WITHOUT LEVEL DIFFERENCE)

FRONT ELEVATION WITH LEVEL DIFFERENCE

KL/STLLW/AR/STD/1006

2 NOS. Ø100mm HEAVY DUTY UPVC PIPE

EMBEDED UNDER GROUND FOR POWERGRID

INCOMING CABLES TO M&E SPEC. & APPROVAL

(LOCATION & ORIENTATION TO BE

DETERMINED ON SITE) CONC. SLAB TO ENGR’S DTLS COMPLETE WITH

20mm THK. GRANOLITHIC FINISHES TO SO’S APPROVAL

MS ANGLE ROOF FASCIA TO ENGR’S DETAIL

SUPPORT POST TO ENGR’S DETAIL

EXPANSION JOINT AT REGULAR INTERVAL

ALONG CENTRE OF GRID TO ENGR’S DETAIL

ROOF CAPPING TO MFR’S DETAIL

ROOF CAPPING TO MFR’S DETAIL

LINE OF ROAD KERB

K-

3 8

ROOF PLAN OF LINKWAY (WITHOUT LEVEL DIFFERENCE)

LAYOUT PLAN OF LINKWAY (WITHOUT LEVEL DIFFERENCE)

OG BOX

820

FFL

MS ANGLE ROOF FASCIA

TO ENGR’S DETAIL

SUPPORT POST TO ENGR’S DETAIL

FFL

MS ANGLE ROOF FASCIA

TO ENGR’S DETAIL

SUPPORT POST TO ENGR’S DETAIL

ALUM FLASHING PIECE

FFL

JL/STLLW/AR/STD/1006

SUPPORT POST TO ENGR’S DETAIL

MS ANGLE ROOF FASCIA TO

ENGR’S DETAIL

750 3000 3000 3000 3000 3000 3000 750

15001500 15001500 15001500 15001500 15001500 15001500

SUPPORT POST TO ENGR’S DETAIL

MS ANGLE ROOF FASCIA TO ENGR’S DETAIL

MIN. 10mm THK. ALUM. HONEY COMB ROOF PANEL

COMPLETE WITH MIN. 1mm THK. TOP PANEL TO

SO’S APPROVAL

6 9 10

ROOF CAPPING TO MFR’S DETAIL

750 3000 3000 3000 3000 3000 3000 750

750 3000 3000 750

75030003000750

¨81750300030003000750

¨81

SUPPORT POST TO ENGR’S DETAIL

OG BOX

200 820

(CLEAR)

200

(CLEAR)

820

FFL

200

(CLEAR)

OG BOX

OG BOX ON CONC. PLINTH TO M&E DTLS

(LOCATION TO BE DETERMINED ON SITE &

TO POWERGRID’S APPROVAL)

OG BOX ON CONC. PLINTH TO M&E DTLS

(LOCATION TO BE DETERMINED ON SITE &

TO POWERGRID’S APPROVAL)

OG BOX ON CONC. PLINTH TO M&E DTLS

(LOCATION TO BE DETERMINED ON SITE &

TO POWERGRID’S APPROVAL)