AQUACIAT POWER Water chillers Heat pumps 1 HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 13.621 C Cooling capacity: 190 to 640 kW Heating capacity: 190 to 500 kW High energy efficiency Compact and quiet Scroll compressors High efficiency brazed plate heat exchangers CIAT self-adjusting electronic control Partial and total heat recovery Cooling only Heat pump Hydraulic module USE The latest generation of AQUACIAT POWER air-to-water heat pumps and water chillers offers an optimal solution for all cooling or heating applications used for the Office, Healthcare, Industry, Administration, Retail and collective housing sectors. These units are designed for outdoor installation and require no special protection against adverse weather conditions. The range has been optimised to use ozone-friendly HFC R410A refrigerant. The use of this refrigerant guarantees compliance with the most demanding requirements for environmental protection and increased seasonal energy efficiency (ESEER). RANGE AQUACIAT power LD series Cooling only version without hydraulic system. AQUACIAT power LDC - LDH series Cooling only version with hydraulic system (circulation pump only or pump and buffer tank). AQUACIAT power ILD series Reversible heat pumps without hydraulic system. AQUACIAT power ILDC - ILDH series Reversible heat pump version with hydraulic system (circulation pump only or pump and buffer tank). HFC R410A

Transcript of ater chillers Heat pumps - Intel · PDF fileater chillers Heat pumps HAT M AI COIIOI IAIO AI...

Page 1: ater chillers Heat pumps - Intel · PDF fileater chillers Heat pumps HAT M AI COIIOI IAIO AI HAI HA CHA A 161 C 1 Cooling capacity: 190 to 640 kW Heating capacity: ... RS485 communication

AQ

UA

CIA

T P

OW

ER

Water chillersHeat pumps

1HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 13.621 C

Cooling capacity: 190 to 640 kWHeating capacity: 190 to 500 kW

High energy efficiencyCompact and quietScroll compressorsHigh efficiency brazed plate heat exchangersCIAT self-adjusting electronic control

Partial and total heat recovery

Cooling only

Heat pump Hydraulic module

Use

The latest generation of AQUACIATPOWER air-to-water heat pumps and water chillers offers an optimal solution for all cooling or heating applications used for the Office, Healthcare, Industry, Administration, Retail and collective housing sectors.

These units are designed for outdoor installation and require no special protection against adverse weather conditions.

The range has been optimised to use ozone-friendly HFC R410A refrigerant. The use of this refrigerant guarantees compliance with the most demanding requirements for environmental protection and increased seasonal energy efficiency (ESEER).

Range

AQUACIATpower LD seriesCooling only version without hydraulic system.

AQUACIATpower LDC - LDH seriesCooling only version with hydraulic system (circulation pump only or pump and buffer tank).

AQUACIATpower ILD seriesReversible heat pumps without hydraulic system.

AQUACIATpower ILDC - ILDH seriesReversible heat pump version with hydraulic system (circulation pump only or pump and buffer tank).

HFCR410A

HFCR410A

HFCR134a

HFCR407C

HFCR134a

HFCR407C

Page 2: ater chillers Heat pumps - Intel · PDF fileater chillers Heat pumps HAT M AI COIIOI IAIO AI HAI HA CHA A 161 C 1 Cooling capacity: 190 to 640 kW Heating capacity: ... RS485 communication

HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 13.621 C

AQUACIAT POWER

2

Water chillersHeat pumps

DescRiptionThe AQUACIATpower units are packaged machines supplied as standard with the following components: - hermetic SCROLL compressors - water-cooled evaporator or hot water condenser with brazed plates - air-cooled exchanger with axial fan motor assembly - Electrical power and remote control cabinet: •generalelectricalpowersupply400V-3ph-50Hz(+10%/-10%)+earth •transformerfittedasstandardonthemachineforsupplyingtheremotecontrolcircuitwith230V-1ph-50Hz

(+10%/-10%) -CIATCONNECT2electroniccontrolmodule - casing for outdoor installation

The entire AQUACIATpowerrangeconformstostandardsEN60-204andEN378-2andthefollowingEuropeanDirectives: -Machinery2006/42EC -EMC2004/108/ECelectromagnetics -2006/95/EClowvoltage -Pressureequipmentdirective97/23/EC. category2forthecoolingonlyseries category3fortheheatpumpseries

nomenclatURe

ILD > heat pump version H > hydraulic with pump and buffer tank

LD > cooling only version 1800 > unit size

C > hydraulic with pump only V > R410Arefrigerant

configURation

STD > Standard(ventilation905rpm)

STDLN > StandardLowNoise(ventilation715rpm+acousticinsuationofcompressors)

STDXLN > Standard Xtra Low Noise (specificventilation715rpm+acousticinsuationofcompressors)

LDC - ILDC 1400V - 1500 V models

Page 3: ater chillers Heat pumps - Intel · PDF fileater chillers Heat pumps HAT M AI COIIOI IAIO AI HAI HA CHA A 161 C 1 Cooling capacity: 190 to 640 kW Heating capacity: ... RS485 communication

AQ

UA

CIA

T P

OW

ER

Water chillersHeat pumps

3HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 13.621 C

DescRiption of the main componentsn Compressors- Hermetic SCROLL- built-in electric motor cooled by suction gases- motor protected by internal winding thermostat- placed on anti-vibration mounts

n Evaporator- brazed plate exchanger -stainlesssteelplates(AISI316)- plate patterns optimised for high-efficiency- armaflex thermal insulation

n Condenser- high efficiency air-cooled exchanger, aluminium fins with

optimised profiles and grooved copper, tubes - condenser or evaporator mode heat exchanger on ILD-ILDC-ILDHreversibleheatpumpversions

- axial fans with profiled blades-IP54classFmotors

n Cooling accessories- dehumidifier filters with rechargeable cartridges- hygroscopic sight glasses- solenoid valves on refrigerant lines (reversible heat

pump version)- thermostatic expansion valves heat pump and cooling only versionsmodels702to1100V

-electronicexpansionvalves(coolingonlymodels1200Vto2400V)

n Control and safety instruments- low and high pressure sensors- safety valves on refrigeration circuit- water temperature regulation sensors - evaporator frost protection sensor- factory-assembled evaporator water flow controller

n Electrics box-IP44-400V-3Ph-50Hzpowersupply+earth(+10%/-10%)- main safety switch with handle on front- control circuit transformer- fan and compressor motor circuit breaker- fan and compressor motor contactors-CONNECT 2 microprocessor-controlled electronic

control module- wire numbering- marking of the main electrical components-RAL7035

n CONNECT 2 electronic control moduleThe CIAT electronic control module performs the following main functions:- regulation of the chilled or hot water temperature- regulation of the water temperature based on the outdoor

temperature (water law)- regulation for low temperature energy storage- second setpoint management

- complete management of compressors with start-up sequence, timer and runtime balancing

- self-adjusting and proactive functions with adjustment of settings on drift control

- series stage system on compressors lowers power according to cooling and heating demands

- management of compressor short-cycle protection- management of the machine operation limit according to

outdoor temperature- automatic switching between hot and cold according to

outside temperature- diagnosis of operation and fault states-managementofafaultmemoryallowingalogofthelast20

incidents to be accessed, with an operational reading taken when the fault occurs

-master/slavemanagementofthetwomachinesinparallelwithbalancing of the running times and automatic changeover if a fault occurs on one machine

- machine timer programming- display and access to the operating parameters via a multilingualLCDscreenwith4linesof24characters

n Remote controlCONNECT 2 is equipped as standardwith anRS485 serialport offering a range of remote management, monitoring and diagnostic options via the communication bus.

Several contacts are available as standard which enable the AQUACIATPOWER to be controlled remotely by cabled link:- automatic operation control: when this contact is open, the

machine stops-setpoint1/setpoint2selection:whenthiscontact isclosed,

a second cold setpoint is activated (energy storage mode, for example)

-HEATING/COOLING mode selection: this input switchesfrom one operating mode to another.

Contact closed = HEATING mode Contact open = COOLING mode-setpointadjustableby4-20mAsignal: this inputallows the

setpoint to be adjusted in HEATING or COOLING mode - compressor load shedding: closing the contact or contacts

concerned allows the power or cooling consumption of the machine to be limited by stopping one or more compressors

-waterpump1and2control:theseoutputscontrolthecontactswitches for one or two water pumps

- fault reporting: this contact indicates the presence of a major fault which has caused one or both cooling circuits to stop

n Power controlSeries stage output control system on the compressors

n FrameFramemadefromRAL7024andRAL7035paintedpanels

Page 4: ater chillers Heat pumps - Intel · PDF fileater chillers Heat pumps HAT M AI COIIOI IAIO AI HAI HA CHA A 161 C 1 Cooling capacity: 190 to 640 kW Heating capacity: ... RS485 communication

HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 13.621 C

AQUACIAT POWER

4

Water chillersHeat pumps

stanDaRD eqUipment/available options

l Supplied as standard sFactory-assembledoption z Option supplied as a kit - Not available

(1)Optionformodels702Vto1100V(2)SuppliedasstandardformodelsCandH

Note: Some technical options not listed above may be added on special request (please contact us).

AQUACIATpowerCOOLING ONLY HEAT PUMP

LD-LDC-LDH ILD-ILDH-ILDC

Safety switch ● ●Control circuit transformer ● ●Electrical cabinet wire numbers ● ●RS485communicationinterface ● ●Water flow controller ● ●All-seasonoperation(min.outdoortemp.:-15°C) ● ●Electronicexpansionvalve(1) ● ▬Optimised high pressure operation (All-season operation with energy optimisation) ▲ ▬

Fanspeedvariation(min.outdoortemp.:-20°C) ▲ ▲Phase controller (reversal. loss. asymmetry. over and under voltage) ▲ ▲

Low-noise version ▲ ▲

XtraLowNoiseVersion ▲ ▲

Compressor suction shut-off valves ▲ ▲

Frostprotection ▲ ▲

Low-temperatureglycol/watermix(0°Cto-12°C) ▲ ▲

Soft start ▲ ▲

Partialheatrecovery-Desuperheater ▲ ▲

Total heat recovery ▲ ▬

Energy meter ▲ ▲

Polyurethane coated coil fins ▲ ▲

ALTANA high-efficiency coil coating ▲ ▲

Single or dual pumps ▲ ▲

Container handling equipment ▲ ▲

Water filter ■ ■

Handling shackles ■ ■

Anti-vibration mounts ■ ■

Flexiblehydraulicsleeves ■ ■

Remote control unit (remote control console) ■ ■

Relay board with dry contacts ■ ■

MULTICONNECT multi-unit management ■ ■

LonWorks gateway ■ ■

Ethernet gateway ■ ■

Electricauxiliarymanagementboard(4stages) ▬ ■

Page 5: ater chillers Heat pumps - Intel · PDF fileater chillers Heat pumps HAT M AI COIIOI IAIO AI HAI HA CHA A 161 C 1 Cooling capacity: 190 to 640 kW Heating capacity: ... RS485 communication

AQ

UA

CIA

T P

OW

ER

Water chillersHeat pumps

7HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 13.621 C

(1)Netcapacityforchilledwatertemperature12°C/7°Candcondenserairinlettemperature35°C-EN14511EUROVENTconditions(2)Netpowerinput=compressors+fans(3)Lw:Overallsoundpowerlevel,asperISOstandard3744,atnominaloperatingconditionsEN14511 Lp:Overallpressurelevelsmeasuredat10minafreefield,calculatedusingtheformulaLP=Lw-10logS

technical specifications - cooling only

AQUACIATpower LD - LDC - LDH 702V 800V 900V 1000V 1100V

Standard version

Net cooling capacity (1) kW 188 210 245 268 289

Net power input (1) (2) kW 61.5 71.2 82.8 91.9 102.7

net EER/ESEER 3,07/ 4,08 2,95/ 4,04 2,96/ 4,05 2,92/ 4,04 2,82/ 4

Lw / Lp (3) dB(A) 91 92 92 92 93

Xtra Low Noise

Version

Net cooling capacity (1) kW 185 206 239 261 281

Net power input (1) (2) kW 60,5 70,7 83,5 93,1 104,4

net EER/ESEER 3,06/ 4,15 2,92/ 4,11 2,87/ 4,11 2,81/ 4,09 2,7/ 4,04

Lw / Lp Low Noise (3) dB(A) 84 84 84 84 84

Lw / Lp Xtra Low Noise (3) dB(A) 81 81 81 81 81

Refrigeration circuit

Refrigerant (GWP) R410A (2088)

Quantity 2

Refrigerant circuit 1 kg 20 20 23 25 25

Refrigerant circuit 2 kg 20 20 23 25 26

Compressor

Type HERMETIC SCROLL

Quantity 4

Rotation speed rpm 2900

Power control % 100-78-71-57-50-43-28-21-0

100-81-69-62.5-50-37.5-31-19-0

100-83-66-55-33-16-0

100-80-70-60-50-40-30-20-0

100-77-73-54-50-45-27-23-0

Type of oil for R410A POLYOLESTER POE 3MAF

Oil capacity circuit 1 litres 3.4 + 4.7 3.4 + 6.8 3.4 + 6.3 4.7 + 6.3 6.8 + 6.3

Oil capacity circuit 2 litres 3.4 + 4.7 3.4 + 6.8 3.4 + 6.3 4.7 + 6.3 6.8 + 6.3

Evaporator

Type BRAZED PLATES

Quantity 1

Water capacity litres 20.30 20.30 23.00 29.30 29.30

Hydraulic connection VICTAULIC DN 100

Max. pressure. water end bar 10 bar (LOD)/4 bar (LDC-LDH)

Min/max water flow m3/h 22/70 22/70 26/81 33/105 33/105

Air-cooled condenser

Fans DIRECT-DRIVE AXIAL- DIAMETER 800 mm

Number of fans 4

Rotation speed rpm HIGH PERFORMANCE 905 rpm VERSION

Air flow m3/h 84000 80800

Motor output power kW 1.64

Rotation speed tr/mn LOW NOISE - XTRA LOW NOISE 715 rpm VERSION

Air flow m3/h 68800 64800

Motor output power kW 1.13

Dimensions

Length versions LD-LDC mm 2820

Length version LDH mm 3850

Width mm 2200

Height mm 2260 (XTRA LOW NOISE VERSION: 2450)

Weight

LD version (empty/in operation) kg 2330 / 2350 2395 / 2415 2550 / 2570 2730 / 2755 2800 / 2825

LDC version (empty/in operation) kg 2515 / 2565 2605 / 2655 2770 / 2820 2960 / 3015 3025 / 3080

LDH version (empty/in operation) kg 3060 / 3580 3145 / 3665 3320 / 3840 3505 / 4030 3575 / 4100

Page 6: ater chillers Heat pumps - Intel · PDF fileater chillers Heat pumps HAT M AI COIIOI IAIO AI HAI HA CHA A 161 C 1 Cooling capacity: 190 to 640 kW Heating capacity: ... RS485 communication

HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 13.621 C

AQUACIAT POWER

8

Water chillersHeat pumps

(1)Netcapacityforchilledwatertemperature12°C/7°Candcondenserairinlettemperature35°C-EN14511EUROVENTconditions(2)Netpowerinput=compressors+fans(3)Lw:Overallsoundpowerlevel,asperISOstandard3744,atnominaloperatingconditionsEN14511 Lp:Overallpressurelevelsmeasuredat10minafreefield,calculatedusingtheformulaLP=Lw-10logS

technical specifications - cooling onlyAQUACIATpower LD - LDC - LDH 1200V 1400V 1600V 1800V 2000V 2100V 2400V

Standard version

Net cooling capacity (1) kW 333 379 437 491 532 568 640

Net power input (1) (2) kW 111.7 128.7 146.8 164.6 178.60 192.8 216

net EER/ESEER 2.98/3.93 2.95/4.05 2.97/3.91 2.99/4.05 2.98/3.99 2.95/4.02 2.96/3.99

Lw / Lp (3) dB(A) 95 / 62 97 / 65 99 / 67 96 / 64 100 / 67 99/66 101/68

Xtra Low Noise

Version

Net cooling capacity (1) kW 326 370 428 480 522 555 623

Net power input (1) (2) kW 112 130.7 147 165.7 177.50 191.7 214.9

net EER/ESEER 2.91/4.01 2.83/4.14 2.91/3.97 2.89/4.10 2.94/4.07 2.9/4.09 2.9/4.06

Lw / Lp Low Noise (3) dB(A) 87/55 88/56 89/57 89/57 90/57 90/57 90/57

Lw / Lp Xtra Low Noise (3) dB(A) 84/52 85/53 86/54 86/54 87/54 87/54 87/54

Refrigeration circuit

Refrigerant (GWP) R410A (2088)

Quantity 2

Refrigerant circuit 1 kg 30 40 45 49 60 63 60

Refrigerant circuit 2 kg 30 40 45 49 48 52 60

Compressor

Type HERMETIC SCROLL

Quantity 4 6 5 6

Rotation speed rpm 2900

Power control % 100-75- 50-25-0

100-78- 71-50-28-

21-0

100-75- 50-25-0

100-83- 66-50-33-

16-0

100-80- 60-40-20-0

100-84-66- 48-36-30- 18-15-0

100-83-66- 50-33-16-0

Type of oil for R410A POLYOLESTER POE 3MAF

Oil capacity circuit 1 litres 2 x 6.3 2 x 6.3 2 x 6.3 3 x 6.3 3 x 6.3 3 x 6.3 3 x 6.3

Oil capacity circuit 2 litres 2 x 6.3 2 x 6.3 2 x 6.3 3 x 6.3 2 x 6.3 3 x 6.3 3 x 6.3

Evaporator

Type BRAZED PLATES

Quantity 1

Water capacity litres 32 37 50 57 63 63 76

Hydraulic connection VICTAULIC DN 125 VICTAULIC DN 150

Max. pressure. water end bar 10 bar (LOD)/4 bar (LDC-LDH)

Min/max water flow m3/h 38 / 113 43 / 124 50 / 137 56 / 150 58/150 62/150 70/150

Air-cooled condenser

Fans DIRECT-DRIVE AXIAL- DIAMETER 800 mm

Number of fans 6 8 10

Rotation speed rpm HIGH PERFORMANCE 905 rpm VERSION

Air flow m3/h 126000 121200 168000 161600 206800 206800 202000

Motor output power kW 1.64

Rotation speed tr/mn LOW NOISE - XTRA LOW NOISE 715 rpm VERSION

Air flow m3/h 103200 97200 137600 129600 168000 168000 162000

Motor output power kW 1.13

Dimensions

Longueur versions LD-LDC mm 4185 5551 6913

Longueur version LDH mm 5215 6581 7942

Width mm 2200

Height mm 2260 (XTRA LOW NOISE VERSION: 2450)

Weight

Version LD (à vide / en service) kg 3225 / 3273 3482 / 3530 3929 / 4001 4605 / 4681 5090 / 5164 5282 / 5359 5603 / 5695

Version LDC (à vide / en service) kg 3700 / 3798 3930 / 4028 4384 / 4506 5065 / 5191 5588 / 5712 5786 / 5913 6101 / 6243

Version LDH (à vide / en service) kg 4296 / 5374 4554 / 5632 4994 / 6096 5660 / 6766 6220 / 7324 6432 / 7539 6732 / 7854

Page 7: ater chillers Heat pumps - Intel · PDF fileater chillers Heat pumps HAT M AI COIIOI IAIO AI HAI HA CHA A 161 C 1 Cooling capacity: 190 to 640 kW Heating capacity: ... RS485 communication

AQ

UA

CIA

T P

OW

ER

Water chillersHeat pumps

9HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 13.621 C

(1)Netcapacityforchilledwatertemperature12°C/7°Candcondenserairinlettemperature35°C-EN14511EUROVENTconditions(2)Netcapacityforhotwatertemperature40°C/45°Candoutdoorairtemperature+7°C-EN14511EUROVENTconditionsNetpowerinput=compressors+fans.(3)Netcapacityforhotwatertemperature30°C/35°Candoutdoorairtemperature+7°C-EN14511EUROVENTconditions(4)Lw:Overallsoundpowerlevel,asperISOstandard3744,forcoolingmodeatnominaloperatingconditionsEN14511. Lp:Overallpressurelevelsmeasuredat10minafreefield,calculatedusingtheformulaLP=Lw-10logS.

technical Data - ReveRsible heat pUmpsAQUACIATpower ILD - ILDC - ILDH 702V 800V 900V 1000V 1100V

Standard version

Net cooling capacity (1) kW 183 201 239 257 278

Net power input (1/2/3) kW 62.5/64/53.7 70.7/72.5/62.9 83.9/83.6/69.7 92.7/90.8/75.5 102.5/98.2/82

Net heating capacity (2) kW 192/199 214/222 249/258 266/276 287/296

net COP (2/3) 2.99/3.71 2.96/3.53 2.97/3.7 2.92/3.65 2.92/3.61

net EER/ESEER 2.93/3.7 2.84/3.67 2.84/3.62 2.77/3.63 2.71/3.5

Lw / Lp (4) dB(A) 91 92 92 92 93

Xtra Low Noise

Version

Net cooling capacity (1) kW 178 195 231 248 267

Net power input (1/2/3) kW 61.4/61/50.5 70.1/69.5/57.8 84.6/80.4/66.4 94.3/87.5/72.2 104.7/94.9/78.6

Net heating capacity (2) kW 188/195 210/215 243/251 259/268 279/287

net COP (2/3) 3.08/3.86 3.02/3.72 3.02/3.78 2.96/3.71 2.94/3.65

net EER/ESEER 2.9/3.78 2.78/3.75 2.73/3.54 2.63/3.59 2.55/3.42

Lw / Lp Low Noise (4) dB(A) 84 84 84 84 84

Lw / Lp Xtra Low Noise (4) dB(A) 81 81 81 81 81

Refrigeration circuit

Refrigerant (GWP) R410A (2088)

Quantity

Refrigerant circuit 1 kg 24 25 27 28 29

Refrigerant circuit 2 kg 24 25 26 27 28

Compressor

Type SCROLL HERMETIQUE

Quantity 4

Rotation speed rpm 2900

Power control % 100-78-71-57-50-43-28-21-0

100-81-69-62.5-50-37.5-31-19-0

100-83-66-55-33-16-0

100-80-70-60-50-40-30-20-0

100-77-73-54-50-45-27-23-0

Type of oil for R410A POLYOLESTER POE 3MAF

Oil capacity circuit 1 litres 3,4 + 4,7 3,4 + 6,8 3,4 + 6,3 4,7 + 6,3 6,8 + 6,3

Oil capacity circuit 2 litres 3,4 + 4,7 3,4 + 6,8 3,4 + 6,3 4,7 + 6,3 6,8 + 6,3

Evaporator

Type PLAQUES BRASEES

Quantity

Water capacity litres 15.8 15.8 18 20.4 20.4

Hydraulic connection VICTAULIC DN 100

Max. pressure. water end bar LD 10 bars / ILDC-ILDH 4 bars

Min/max water flow m3/h 22/63 24/70 29/77 32/77 34/77

Air-cooled condenser

Fans HELICOÏDE A ACCOUPLEMENT DIRECT - DIAMETRE 800 mm

Number of fans

Rotation speed rpm VERSION STANDARD 905 tr/mn

Air flow m3/h 84300

Motor output power kW 2.2

Rotation speed tr/mn VERSION LOW NOISE - XTRA LOW NOISE 715 tr/mn

Air flow m3/h 63180

Motor output power kW 1.5

Dimensions

Length versions ILD-ILDC mm 2820

Length version ILDH mm

Width mm 2200

Height mm 2260 (2450 VERSION XTRA LOW NOISE)

Weight

ILD version (empty/in operation) kg 2535/2575 2595/2635 2600/2640 2765/2805 2850/2890

ILDC version (empty/in operation) kg 2820/2890 2880/2950 2885/2955 3050/3120 3135/3205

ILDH version (empty/in operation) kg 3370/3940 3430/4000 3440/4010 3605/4175 3690/4260

Page 8: ater chillers Heat pumps - Intel · PDF fileater chillers Heat pumps HAT M AI COIIOI IAIO AI HAI HA CHA A 161 C 1 Cooling capacity: 190 to 640 kW Heating capacity: ... RS485 communication

HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 13.621 C

AQUACIAT POWER

10

Water chillersHeat pumps

(1)Netcapacityforchilledwatertemperature12°C/7°Candcondenserairinlettemperature35°C-EN14511EUROVENTconditions(2)Netcapacityforhotwatertemperature40°C/45°Candoutdoorairtemperature+7°C-EN14511EUROVENTconditionsNetpowerinput=compressors+fans.(3)Netcapacityforhotwatertemperature30°C/35°Candoutdoorairtemperature+7°C-EN14511EUROVENTconditions(4)Lw:Overallsoundpowerlevel,asperISOstandard3744,forcoolingmodeatnominaloperatingconditionsEN14511. Lp:Overallpressurelevelsmeasuredat10minafreefield,calculatedusingtheformulaLP=Lw-10logS.

technical Data - ReveRsible heat pUmps

AQUACIATpower ILD - ILDC - ILDH 1200V 1400V 1600V 1800V

Standard version

Net cooling capacity (1) kW 332 381 434 486Net power input (1/2/3) kW 113 / 113 / 95 132 / 127 /108 151 / 149 / 126 170 / 166 / 140Net heating capacity (2) kW 342 / 357 389 / 403 452 / 470 505 / 524net COP (2/3) 3.04 / 3.76 3.06 / 3.73 3.04 / 3.73 3.05 /3.74net EER/ESEER 2.93 / 4.01 2.89 / 4.09 2.88 / 3.79 2.85 / 3.74Lw / Lp (4) dB(A) 93 / 61 95 / 63 96 / 64 94 / 62

Xtra Low Noise

Version

Net cooling capacity (1) kW 321 366 421 473Net power input (1/2/3) kW 113 / 109 / 91 133 / 122 / 104 152 / 142 /120 173 / 160 /134Net heating capacity (2) kW 334 / 346 378 / 391 442 / 458 492 / 508net COP (2/3) 3.08 / 3.8 3.09 / 3.76 3.12 / 3.82 3.08 / 3.79net EER/ESEER 2.84 / 4.13 2.75 / 4.32 2.78 / 3.86 2.74 / 3.69Lw / Lp Low Noise (4) dB(A) 85 / 53 88 / 56 89 / 57 87 / 55Lw / Lp Xtra Low Noise (4) dB(A) 82 / 50 84 / 52 85 / 53 84 / 52

Refrigeration circuit

Refrigerant (GWP) R410A (2088)Quantity 2Refrigerant circuit 1 kg 38 44 51 55Refrigerant circuit 2 kg 38 33 43 53

Compressor

Type SCROLL HERMETIQUEQuantity 4 6Rotation speed rpm 2900

Power control % 100-75-50-25-0 100-83-66- 50-33-16-0

100-84-66- 48-36-30- 18-15-0

100-83-66- 50-33-16-0

Type of oil for R410A POLYOLESTER POE 3MAFOil capacity circuit 1 litres 2x6.3 3x6.8 3x6.8 3x6.3Oil capacity circuit 2 litres 2x6.3 3x6.8 3x6.3 3x6.3

Evaporator

Type PLAQUES BRASEESQuantity 2Water capacity litres 26 33.5 37 40.5Hydraulic connection VICTAULIC DN 125Max. pressure. water end bar LD 10 bars / ILDC-ILDH 4 barsMin/max water flow m3/h 38 / 106 43 / 110 50 / 110 56 / 110

Air-cooled condenser

Fans HELICOÏDE A ACCOUPLEMENT DIRECT - DIAMETRE 800 mmNumber of fans 6 8Rotation speed rpm VERSION STANDARD 905 tr/mnAir flow m3/h 121800 117000 159200 156000Motor output power kW 1.64Rotation speed tr/mn VERSION LOW NOISE - XTRA LOW NOISE 715 tr/mnAir flow m3/h 90000 87600 118400 116800Motor output power kW 1.13

Dimensions

Length versions LD-LDC mm 4185 5551Length version LD mm 5215 6581Width mm 2200Height mm 2260 (2450 VERSION XTRA LOW NOISE)

Weight

ILD version (empty/in operation) kg 3575 / 3657 4033 / 4130 4648 / 4758 4707 / 4818ILDC version (empty/in opera-tion) kg 3935 / 4021 4408 / 4508 5015 / 5130 5074 / 5189ILDH version (empty/in opera-tion) kg 4480 /5545 4946 / 6025 5560 / 6653 5618 / 6712

Page 9: ater chillers Heat pumps - Intel · PDF fileater chillers Heat pumps HAT M AI COIIOI IAIO AI HAI HA CHA A 161 C 1 Cooling capacity: 190 to 640 kW Heating capacity: ... RS485 communication

AQ

UA

CIA

T P

OW

ER

Water chillersHeat pumps

11HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 13.621 C

electRical chaRacteRisticsn Basic unit (excluding pump)

AQUACIATpower 702V 800V 900V 1000V 1100V

COMPRESSORS (1)Maximum rated current A 135 154 181 192 210Starting current (3) A 324 380 431 442 461Starting current with Soft Start option (3) A 234 271 307 318 337

FAN MOTORS (1)STANDARD VERSION: 905 rpm

Maximum rated current A 17,2 (4 x 4,3)LOW NOISE - XTRA LOW NOISE 715 rpm VERSIONS

Maximum rated current A 8,4 (4 x 2,1)LDC FROST PROTECTION (OPTION) (2)

Evaporator heating element power W 380Maximum rated current A 1.65

LDH FROST PROTECTION (OPTION)Evaporator heating element power + piping + expansion vessel W 580

Maximum rated current A 2.52LDH FROST PROTECTION (OPTION)

Evaporator heating element power + piping W 400

Maximum rated current A 1.74(2)Hydraulic module heating element power W 1500Maximum rated current A 2.3(1)

DESUPERHEATER FROST PROTECTION – TOTAL-RECOVERY CONDENSER (OPTION) (2)Heat exchanger heating element power W 200Maximum rated current A 0.81

REMOTE CONTROL AUXILIARY CIRCUIT (2)Maximum rated current A 4Transformer power VA 1000Machine protection rating IP 44

AQUACIATpower 1200V 1400V 1500V 1600V 1650V 1800V 2000V 2100V 2400V

COMPRESSORS (1)Maximum rated current A 237 266 275 295 315 356 369 399 443Starting current (3) A 488 586 501 615 566 607 689 720 763Starting current with Soft Start option (3) A 364 429 392 458 442 483 532 562 562

FAN MOTORS (1)STANDARD VERSION: 905 rpm

Maximum rated current A 20.4 (6 x 3.4) 27.2 (8 x 3.4) 34 (10 x 3.4)LOW NOISE - XTRA LOW NOISE 715 rpm VERSIONS

Maximum rated current A 12.6 (6 x 2.1) 16.8 (8 x 2.1) 21 (10 x 2.1)LD FROST PROTECTION (OPTION) (2)

Evaporator heating element power W 240Maximum rated current A 1.05

LDC FROST PROTECTION (OPTION) (2)Evaporator heating element power + piping + expansion vessel W 480

Maximum rated current A 2.1LDH FROST PROTECTION (OPTION)

Evaporator heating element power + piping W 360

Maximum rated current A 1,6 (2)Hydraulic module heating element power W 1500Maximum rated current A 2,3 (1)

DESUPERHEATER FROST PROTECTION – TOTAL-RECOVERY CONDENSER (OPTION) (2)Heat exchanger heating element power W 240Maximum rated current A 1.05

REMOTE CONTROL AUXILIARY CIRCUIT (2)Maximum rated current A 4 5Transformer power VA 1600 2000Machine protection rating IP 44

Page 10: ater chillers Heat pumps - Intel · PDF fileater chillers Heat pumps HAT M AI COIIOI IAIO AI HAI HA CHA A 161 C 1 Cooling capacity: 190 to 640 kW Heating capacity: ... RS485 communication

AQ

UA

CIA

T P

OW

ER

Water chillersHeat pumps

53HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 13.621 C

lD Dimensions

AQUACIATpower 702V to 1100V

4 holes Ø 20.2 mmfor securing to floor

** XTRA LOW NOISE version only.

AQUACIATPOWERChilled water Desuperheater hot water Total recovery hot water

Weight (kg)inlet sortie inlet outlet inlet outlet

a b c d e f empty in operation

LD 702V

VICTAULIC DN 100 G 2” male VICTAULIC

DN 100

2330 2350

LD 800V 2395 2415

LD 900V 2550 2570

LD 1000V 2730 2755

LD 1100V 2800 2825

2450

2260

2200

2820

145 1227

1870

476

298

900 299

378

725 1367 725 3021

2530

dooropeningapprox. 800

Page 11: ater chillers Heat pumps - Intel · PDF fileater chillers Heat pumps HAT M AI COIIOI IAIO AI HAI HA CHA A 161 C 1 Cooling capacity: 190 to 640 kW Heating capacity: ... RS485 communication

HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 13.621 C

AQUACIAT POWER

54

Water chillersHeat pumps

lD Dimensions

AQUACIATpower 1200V to 1400V

2200

2260

2450

**

568

359 805 558

2465

300

254

4185

a

b bd d

c c

dooropeningapprox. 800

6 holes Ø 20.2 mmfor securing to floor

8 holes Ø 20.2 mmfor securing to floor

1688 358

568

2125

3030725 1366 1367 725

f

e

AQUACIATpower 1600V - 1800V

dooropeningapprox. 800

22003009

5551

1125 1502 254

352

532

300

2260

2450

**

a

b

d

c

d

c

2542725 1367 1366 1367 725

3030

2125

352

532

f

e

** XTRA LOW NOISE version only.

AQUACIATPOWERChilled water Desuperheater hot water Total recovery hot water

Weight (kg)inlet sortie inlet outlet inlet outlet

a b c d e f empty in operation

LD 1200V

VICTAULIC DN 125 G 2” male VICTAULIC

DN 125

3225 3273

LD 1400V 3482 3530

LD 1600V 3929 4001

LD 1800V 4605 4681

Page 12: ater chillers Heat pumps - Intel · PDF fileater chillers Heat pumps HAT M AI COIIOI IAIO AI HAI HA CHA A 161 C 1 Cooling capacity: 190 to 640 kW Heating capacity: ... RS485 communication

AQ

UA

CIA

T P

OW

ER

Water chillersHeat pumps

55HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 13.621 C

lD Dimensions

AQUACIATpower 2000V to 2400V

door opening approx.

800

** XTRA LOW NOISE version only.

2200

e

f

2539

6913

352

352

884

306

300

996 15673907

2260

2450

**

a

b

d d

cc

10 holes Ø 20.2 mm for securing to floor

725

3030

2125

1367136713671367725

AQUACIATPOWERChilled water Desuperheater hot water Total recovery hot water Weight (kg)

inlet sortie inlet outlet inlet outleta b c d e f empty in operation

LD 2000VVICTAULIC

DN 125 G 2” male VICTAULIC DN 125

5090 5164

LD 2100V 5282 5359

LD 2400V 5603 5695

Page 13: ater chillers Heat pumps - Intel · PDF fileater chillers Heat pumps HAT M AI COIIOI IAIO AI HAI HA CHA A 161 C 1 Cooling capacity: 190 to 640 kW Heating capacity: ... RS485 communication

HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 13.621 C

AQUACIAT POWER

56

Water chillersHeat pumps

** XTRA LOW NOISE version only.

ilD Dimensions

AQUACIATpower 702V to 1100V

dooropeningapprox. 800

AQUACIATPOWERChilled water Desuperheater hot water

Weight (kg)inlet sortie inlet outlet

a b c d empty in operation

ILD 702V

VICTAULIC DN 100 G 2” male

2535 2575

ILD 800V 2595 2635

ILD 900V 2600 2640

ILD 1000V 2765 2805

ILD 1100V 2850 2890

2200

2450

2260

2820

1687

214 612

306

298

476

460

725 1367 725 3030

2125

4 holes Ø 20.2 mmfor securing to floor

Page 14: ater chillers Heat pumps - Intel · PDF fileater chillers Heat pumps HAT M AI COIIOI IAIO AI HAI HA CHA A 161 C 1 Cooling capacity: 190 to 640 kW Heating capacity: ... RS485 communication

AQ

UA

CIA

T P

OW

ER

Water chillersHeat pumps

57HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 13.621 C

ilD Dimensions

AQUACIATpower 1200V - 1500 V

AQUACIATpower 1650 V - 1800V

b

4185

2200

2260

2450

**

A

2414

B

DC

450

299

7251366

30301367726

2125

a d

c

d

c

6 holes Ø 20.2 mmfor securing to floor

dooropeningapprox. 800

2200

2260

2450

**

b

ABD

C

ad

c

d

c

7251366

303013671367

2125

725

5551

3779

450

299

8 holes Ø 20.2 mmfor securing to floor

dooropeningapprox. 800

** XTRA LOW NOISE version only.

AQUACIATPOWERChilled water Desuperheater hot water

Weight (kg)inlet sortie inlet outlet

a b c d empty in operation

ILD 1200V

VICTAULIC DN 125 G 2” male

3575 3657

ILD 1400V 4033 4130

ILD 1600V 4648 4758

ILD 1800V 4707 4818

Page 15: ater chillers Heat pumps - Intel · PDF fileater chillers Heat pumps HAT M AI COIIOI IAIO AI HAI HA CHA A 161 C 1 Cooling capacity: 190 to 640 kW Heating capacity: ... RS485 communication

HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 13.621 C

AQUACIAT POWER

58

Water chillersHeat pumps

lDh Dimensions

AQUACIATpower 702V to 1100V

** XTRA LOW NOISE version only.

AQUACIATPOWERChilled water Desuperheater hot water Total recovery hot water

Weight (kg)inlet sortie inlet outlet inlet outlet

a b c d e f empty in operation

LDH 702V

VICTAULIC DN 100 G 1”1/4” male VICTAULIC

DN 100

3060 3580

LDH 800V 3145 3665

LDH 900V 3320 3840

LDH 1000V 3505 4030

LDH 1100V 3575 4100

2450

2260

22003332

3850

1870

1227

298

476

145

900

299

368

286 453 1014 1367 723 3021

2530

dooropeningapprox. 800

8 holes Ø 20.2 mmfor securing to floor

Page 16: ater chillers Heat pumps - Intel · PDF fileater chillers Heat pumps HAT M AI COIIOI IAIO AI HAI HA CHA A 161 C 1 Cooling capacity: 190 to 640 kW Heating capacity: ... RS485 communication

AQ

UA

CIA

T P

OW

ER

Water chillersHeat pumps

59HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 13.621 C

lDh Dimensions

AQUACIATpower 1200V - 1400V

2200

2260

2450

**

536 56

835

9

4700

805 5582465

300

254

5215

b a

d d

c c

dooropeningapprox. 800

10 holes Ø 20.2 mmfor securing to floor

1688 358

568

f

e 288 453 725 1366 1367 725 3021

2530

288

AQUACIATpower 1600V - 1800V

dooropeningapprox. 800

22003009

6068

1125 1502 254

352

536 53

2

300

6581

2260

2450

**

ab

b

d

c

d

c

12 holes Ø 20.2 mmfor securing to floor

3030

2125

2542 352

532

f

e288 453

288725 1367 1366 1367 725

* Connections b based on pump selected: (1)PumpsNo.102-103-105-107-202-203-205-207 (2)PumpsNo.104-106-108-110-112-204-206-208-210-212

** XTRA LOW NOISE version only.

AQUACIATPOWER

Chilled water Desuperheater hot water Total recovery hot waterWeight (kg)

inlet sortie inlet outlet inlet outlet

a b* c d e f empty in operation

LDH 1200V

VICTAULIC DN 125

DN 65 (1) DN 80 (2) G 2” male VICTAULIC

DN 125

4296 5374

LDH 1400V 4554 5632

LDH 1600V 4994 6096

LDH 1800V 5660 6766

Page 17: ater chillers Heat pumps - Intel · PDF fileater chillers Heat pumps HAT M AI COIIOI IAIO AI HAI HA CHA A 161 C 1 Cooling capacity: 190 to 640 kW Heating capacity: ... RS485 communication

HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 13.621 C

AQUACIAT POWER

60

Water chillersHeat pumps

lDh Dimensions

AQUACIATpower 2000V to 2400Vdoor

opening approx.

800

* Connections b based on pump selected: (1)PumpsNo.102-103-105-107-202-203-205-207 (2)PumpsNo.104-106-108-110-112-204-206-208-210-212 (3)PumpsNo.111-113-114-115-211-213-214-215

** XTRA LOW NOISE version only.

2200

e

f

2539

7942

352

352

884

536

306

300

996 15673907

7433

2260

2450

**

a

b

d d

cc

14 holes Ø 20.2 mm for securing to floor

725

3030

2125

1367136713671367725453 288288

AQUACIATPOWERChilled water Desuperheater hot water Total recovery hot water

Weight (kg)inlet sortie inlet outlet inlet outlet

a b* c d e f empty in operation

LDH 2000VVICTAULIC

DN 125

DN 65 (1) DN 80 (2)

DN 100 (3)G 2” male VICTAULIC

DN 125

6220 7324

LDH 2100V 6432 7539

LDH 2400V 6732 7854

Page 18: ater chillers Heat pumps - Intel · PDF fileater chillers Heat pumps HAT M AI COIIOI IAIO AI HAI HA CHA A 161 C 1 Cooling capacity: 190 to 640 kW Heating capacity: ... RS485 communication

AQ

UA

CIA

T P

OW

ER

Water chillersHeat pumps

61HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 13.621 C

dooropeningapprox. 800

** XTRA LOW NOISE version only.

ilDh Dimensions

AQUACIATpower 702V to 1100V

AQUACIATPOWERChilled water Desuperheater hot water

Weight (kg)inlet sortie inlet outlet

a b c d empty in operation

ILDH 702V

VICTAULIC DN 100 G 2” male

3370 3940

ILDH 800V 3430 4000

ILDH 900V 3440 4010

ILDH 1000V 3605 4175

ILDH 1100V 3690 42060

2450

2260

2200

b a d

c766

3850

3332

298

476

1687214 612

288 453 1014 1367 725

2125

3030

8 holes Ø 20.2 mm for securing to floor

Page 19: ater chillers Heat pumps - Intel · PDF fileater chillers Heat pumps HAT M AI COIIOI IAIO AI HAI HA CHA A 161 C 1 Cooling capacity: 190 to 640 kW Heating capacity: ... RS485 communication

HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 13.621 C

AQUACIAT POWER

62

Water chillersHeat pumps

ilDh Dimensions

AQUACIATpower 1200V - 1500 V

AQUACIATpower 1650 V - 1800V

b

5215

2200

2260

2450

**

535.

5

A

2414

4700

B

DC

7251366

30301367726453288 288

2125

a d

c

d

c

450

299

10 holes Ø 20.2 mm for securing to floor

dooropeningapprox. 800

2200

2260

2450

**

b

6581

535.

5

A

3779

6063

BD

C

ad

c

d

c

7251366

303013671367453288 288

2125

725

450

299

12 holes Ø 20.2 mm for securing to floor

dooropeningapprox. 800

* Connections b based on pump selected: (1)PumpsNo.102-103-105-107-202-203-205-207 (2)PumpsNo.104-106-108-110-112-204-206-208-210-212

** XTRA LOW NOISE version only.

AQUACIATPOWERChilled water Desuperheater hot water Weight (kg)

inlet sortie inlet outleta b* c d empty in operation

ILDH 1200V

VICTAULIC DN 125

DN 65 (1) DN 80 (2) G 2” male

4480 5545

ILDH 1400V 4946 6025

ILDH 1600V 5560 6653

ILDH 1800V 5618 6712

Page 20: ater chillers Heat pumps - Intel · PDF fileater chillers Heat pumps HAT M AI COIIOI IAIO AI HAI HA CHA A 161 C 1 Cooling capacity: 190 to 640 kW Heating capacity: ... RS485 communication

AQ

UA

CIA

T P

OW

ER

Water chillersHeat pumps

63HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 13.621 C

** XTRA LOW NOISE version only.

lDc Dimensions

AQUACIATpower 702V to 1100V

AQUACIATPOWERChilled water Desuperheater hot water Total recovery hot water

Weight (kg)inlet sortie inlet outlet inlet outlet

a b c d e f empty in operation

LDC 702V

VICTAULIC DN 100 G 2” male VICTAULIC

DN 100

2515 2565

LDC 800V 2605 2655

LDC 900V 2770 2820

LDC 1000V 2960 3015

LDC 1100V 3025 3080

2450

2260

2200

2820

a d

c 476

298

145 12271870

f e

368

299

900 725 7251367 3030

2125

dooropeningapprox. 800

4 holes Ø 20.2 mmfor securing to floor

Page 21: ater chillers Heat pumps - Intel · PDF fileater chillers Heat pumps HAT M AI COIIOI IAIO AI HAI HA CHA A 161 C 1 Cooling capacity: 190 to 640 kW Heating capacity: ... RS485 communication

HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 13.621 C

AQUACIAT POWER

64

Water chillersHeat pumps

lDc Dimensions

AQUACIATpower 1200V - 1400V

AQUACIATpower 1600V - 1800V

dooropeningapprox. 800

6 holes Ø 20.2 mmfor securing to floor

8 holes Ø 20.2 mmfor securing to floor

dooropeningapprox. 800

* Connections b based on pump selected: (1)PumpsNo.102-103-105-107-202-203-205-207 (2)PumpsNo.104-106-108-110-112-204-206-208-210-212

** XTRA LOW NOISE version only.

2200

2260

2450

**

568

359 805 558

2465

300

254

4185

a

d d

c c

358

568

2125

3030725 1366 1367 725

f

e

b

22003009

5551

1125 1502 254

352

532

300

2260

2450

**

ad

c

d

c

2542725 1367 1366 1367 725

3030

2125

352

532

f

e

b

AQUACIATPOWERChilled water Desuperheater hot water Total recovery hot water

Weight (kg)inlet sortie inlet outlet inlet outlet

a b* c d e f empty in operation

LDC 1200V

VICTAULIC DN 125

DN 65 (1) DN 80 (2) G 2” male VICTAULIC

DN 125

3700 3798

LDC 1400V 3930 4028

LDC 1600V 4384 4506

LDC 1800V 5065 5191

Page 22: ater chillers Heat pumps - Intel · PDF fileater chillers Heat pumps HAT M AI COIIOI IAIO AI HAI HA CHA A 161 C 1 Cooling capacity: 190 to 640 kW Heating capacity: ... RS485 communication

AQ

UA

CIA

T P

OW

ER

Water chillersHeat pumps

65HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 13.621 C

lDc Dimensions

AQUACIATpower 2000V to 2400V door opening approx.

800

* Connections b based on pump selected: (1)PumpsNo.102-103-105-107-202-203-205-207 (2)PumpsNo.104-106-108-110-112-204-206-208-210-212 (3)PumpsNo.111-113-114-115-211-213-214-215

** XTRA LOW NOISE version only.

10 holes Ø 20.2 mm for securing to floor

2200

e

f

2539 352

352

884

306

300

996 15673907

2260

2450

**

ad d

cc

6913

725

3030

2125

1367136713671367725

b

AQUACIATPOWERChilled water Desuperheater hot water Total recovery hot water

Weight (kg)inlet sortie inlet outlet inlet outlet

a b* c d e f empty in operation

LDC 2000VVICTAULIC

DN 125

DN 65 (1) DN 80 (2)

DN 100 (3)G 2” male VICTAULIC

DN 125

5588 5712

LDC 2100V 5786 5913

LDC 2400V 6101 6243

Page 23: ater chillers Heat pumps - Intel · PDF fileater chillers Heat pumps HAT M AI COIIOI IAIO AI HAI HA CHA A 161 C 1 Cooling capacity: 190 to 640 kW Heating capacity: ... RS485 communication

HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 13.621 C

AQUACIAT POWER

66

Water chillersHeat pumps

door opening approx.

800

4 holes Ø 20.2 mm for securing to floor

** XTRA LOW NOISE version only.

ilDc Dimensions

AQUACIATpower 702V to 1100V

AQUACIATPOWERChilled water Desuperheater hot water

Weight (kg)inlet sortie inlet outlet

a b c d empty in operation

ILDC 702V

VICTAULIC DN 100 G 2” male

2820 2890

ILDC 800V 2880 2950

ILDC 900V 2885 2955

ILDC 1000V 3050 3120

ILDC 1100V 3135 3205

2200

2450

2260

b

725 7251367 3030

2125

a d

c460

2820

476

298

1687214 612

306

Page 24: ater chillers Heat pumps - Intel · PDF fileater chillers Heat pumps HAT M AI COIIOI IAIO AI HAI HA CHA A 161 C 1 Cooling capacity: 190 to 640 kW Heating capacity: ... RS485 communication

AQ

UA

CIA

T P

OW

ER

Water chillersHeat pumps

67HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 13.621 C

* Connections b based on pump selected: (1)PumpsNo.102-103-105-107-202-203-205-207. (2)PumpsNo.104-106-108-110-112-204-206-208-210-212.

** XTRA LOW NOISE version only.

ilDc Dimensions

AQUACIATpower 1200V - 1500 V

AQUACIATpower 1650 V - 1800V

b

4185

2200

2260

2450

**

A

2414

B

CD

597

375

7251366

30301367726

2125

a d

c

d

c450

299

12 holes Ø 20.2 mmfor securing to floor

dooropeningapprox. 800

14 holes Ø 20.2 mmfor securing to floor

dooropeningapprox. 800

2200

2260

2450

**

b

5551

A

3779

BD

C

ad

c

d

c

7251366

303013671367

2125

725

597

375 45

029

9

b

AQUACIATPOWERChilled water Desuperheater hot water

Weight (kg)inlet sortie inlet outlet

a b* c d empty in operation

ILDC 1200V

VICTAULIC DN 125

DN 65 (1) DN 80 (2) G 2” male

3935 4021

ILDC 1400V 4408 4508

ILDC 1600V 5015 5130

ILDC 1800V 5074 5189