arihant arshiya
1
Load Calculation sheet Load demand based on proposed built up area: Residential Load: Total buildup area: 28689.52 sq meter Hence (28689.52x75)/(1000)=2152 KVA ------- A Commercial load: Total build up area:921.13 sq meter Hence(921.13x200)/(1000)=185 KVA --------B Common load:100 KVA-----------C Total KVA:2437 KVA Hence 4 nos 630 KVA DTC proposed. DyEE Khopoli Junior Engineer Wavoshi
-
Upload
nikhil-meshram -
Category
Documents
-
view
214 -
download
2
description
BUILDING
Transcript of arihant arshiya
Load Calculation sheet
Load demand based on proposed built up area:
Residential Load:
Total buildup area: 28689.52 sq meter
Hence (28689.52x75)/(1000)=2152 KVA ------- A
Commercial load:
Total build up area:921.13 sq meter
Hence(921.13x200)/(1000)=185 KVA --------B
Common load:100 KVA-----------C
Total KVA:2437 KVA
Hence 4 nos 630 KVA DTC proposed.
DyEE Khopoli Junior Engineer Wavoshi