1GE Multilin

Instrument Transformers, Inc.

Are you using the right CT's and PT's for your application?

John Levine, P.E.

Levine Lectronics and LectricE-mail: [email protected]

GE Multilin / Instrument Transformers, Inc.

Page 2: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

2GE Multilin

Instrument Transformers, Inc.

Alternate Title of Presentation

Now I know what I do not know about CT’s and PT’s.

As engineers we do not need to know all the answers just where to get them.

Page 3: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

3GE Multilin

Instrument Transformers, Inc.

Current & Voltage Transformer Basics (IEEE Standards)

Page 4: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

4GE Multilin

Instrument Transformers, Inc.

Agenda

Current TransformersVoltage TransformersRequired Information for Specifying CTs & VTsTake Home Rules” for CTs & VTsApplications where used

Page 5: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

5GE Multilin

Instrument Transformers, Inc.

Why use Instrument Transformers?

Circuit Isolation

Reduce voltage and currents to reasonable working levels.

Phasor combinations for summing and measuring power

Page 6: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

6GE Multilin

Instrument Transformers, Inc.

CURRENT TRANSFORMERS TYPES OF C.T. CONSTRUCTION

The most common type of C.T. construction is the “DOUGHNUT” type. It is constructed of an iron toroid, which forms the core of the transformer, and is wound with secondary turns.

Secondary Winding Primary Conductor

Iron Core

Page 7: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

7GE Multilin

Instrument Transformers, Inc.

Transformer ratio (TR)

Primary Current(100 amps)

Secondary Current (5 amps)

Primary CurrentSecondary Current

Transformer Ratio = _____________________

100 5___ = 100:5 or 20:1

Page 8: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

8GE Multilin

Instrument Transformers, Inc.

Polarity

Direction ofPrimary Current

Direction of Secondary Current

H1

X1

Primary current into “polarity” =

Secondary current out of “polarity”

P1

IEEE

IEC

Primary PolarityMarks

IEEEIECS1

Secondary PolarityMarks

Remember:

Page 9: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

9GE Multilin

Instrument Transformers, Inc.

Polarity

Direction ofPrimary Current

Direction of Secondary Current

H1

X1

P1

IEEE

IEC

Primary PolarityMarks

IEEEIECS1

Secondary PolarityMarks

Primary current into “non-polarity” =

Secondary current out of “non-polarity”

Remember:

Page 10: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

10GE Multilin

Instrument Transformers, Inc.

Generator typical wiring

Page 11: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

11GE Multilin

Instrument Transformers, Inc.

What is your application?

If your application is metering , how high do I need to go in current? 2 times ?

If your application is protective relaying, how high do I need to go in current? 20 times ? 40 times ?

Page 12: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

12GE Multilin

Instrument Transformers, Inc.

CT Rating Factor (RF) -- IEEERated current x (RF) =

Maximum continuous current carrying capability:

Without exceeding temperature limits

Without loss of published accuracy class

Typical rating factors for Metering CTs are:1.0, 1.33, 1.5, 2.0, 3.0, 4.0

Page 13: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

13GE Multilin

Instrument Transformers, Inc.

0.30

0.30

0.60

0.60

Rating Factor

Accu

racy

Cla

ss -

%CT Rating Factor (RF) -- IEEE

10% 100% 200% 300% 400%

1.0 2.0 3.0 4.0

IEEE C57.13 Accuracy0.3% @ BX.X RF 4.0

0.3% Accuracy Region

0.6% Accuracy

Region

Page 14: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

14GE Multilin

Instrument Transformers, Inc.

Short-Time Thermal Current Rating

One (1) – second thermal ratingExpressed as value of RMS primary currentMain influencing factor:

CT primary & secondary wire size Can be converted to thermal rating for any time period (t) up to five (5) seconds:

(New RF at new Ambient/Stated RF at 30 degrees C)2=85-New Ambient/New Ambient

Example: CT with rating factor of 4 at 30 degrees = rating factor of 2.95 at 55 degreesX2/42=85-55/55 X=2.95

Page 15: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

15GE Multilin

Instrument Transformers, Inc.

CT Metering Accuracy

Actual secondary current

Rated secondary current=

Difference in % is known as the “Accuracy”

of the CT

Page 16: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

16GE Multilin

Instrument Transformers, Inc.

IEEE CT Metering AccuracyAccuracy Class ( * )

Application

0.15 High Accuracy Metering

0.15S “Special” High Accuracy Metering

0.3 Revenue Metering

0.6 Indicating Instruments

1.2 Indicating Instruments* All accuracy classes defined by IEEE C57.13 or C57.13.6

* Accuracy classes include both ratio & phase angle error

Page 17: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

17GE Multilin

Instrument Transformers, Inc.

IEEE CT Metering Accuracy

BurdenLoad connected to CT secondary

Includes devices & connecting leads

Expressed in ohms

Standard values = B0.1, B0.2, B0.5, B0.9, B1.8 E0.04, E0.2

All burdens defined by IEEE C57.13 or C57.13.6 for 60 Hz only

Page 18: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

18GE Multilin

Instrument Transformers, Inc.

Application Burden Designation

Impedance (Ohms)

VA @ 5 amps

Power Factor

Metering B0.1 0.1 2.5 0.9B0.2 0.2 5 0.9B0.5 0.5 12.5 0.9B0.9 0.9 22.5 0.9B1.8 1.8 45 0.9

Standard IEEE CT Burdens (5 Amp) (Per IEEE Std. C57.13-1993 & C57.13.6)

IEEE CT Metering Accuracy

E0.2E0.04

0.20.04

51

1.01.0

Page 19: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

19GE Multilin

Instrument Transformers, Inc.

A current transformer for metering purposes may typically have an accuracy of 0.3%. The C.T. must maintain this accuracy for normal load currents, provided the rated burden on the C.T. is not exceeded. It is quite acceptable, and in fact desirable, for the C.T. to saturate when fault current flows. The accuracy for a typical metering C.T. is specified as: 0.3 M 0.9

O.3% METERING O.9 OHMS BURDEN

This metering C.T. has an accuracy of 0.3% when the connected burden does not exceed 0.9 OHMS.

Page 20: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

20GE Multilin

Instrument Transformers, Inc.

IEEE CT Metering Accuracy

Accuracy Class(0.3, 0.6, 1.2) (*)

Burden (Ohms)(B0.1, B0.2, B0.5, B0.9, B1.8)

+

“Accuracy” expressed as:

0.3B0.20.6B0.91.2B1.80.15E0.2

=

Typical Examples

* Accuracy class is stated at 100% rated current* At 10% rated current, twice the error is allowed (5% for 0.15 class)

(0.15*, 0.15S^) E0.2, E0.04)

^ Accuracy class is stated at 100% to 5% rated current

Page 21: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

21GE Multilin

Instrument Transformers, Inc.

0.30

0.30

0.60

0.60

Rating Factor

Accu

racy

Cla

ss -

%

10% 200% 300%

1.0 2.0 3.0 4.0

IEEE C57.13 Accuracy0.3 @ BX.X; RF 4.0

0.3% Accuracy Region

0.6% Accuracy

Region

IEEE CT Metering Accuracy

100% 400%

No accuracy guaranteed at current levels less than 10%

Page 22: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

22GE Multilin

Instrument Transformers, Inc.

IEEE CT Metering Accuracy

CT Parallelogram – IEEE C57.13

Out of 0.3% Class

0.3 classparallelogram

0.6 classparallelogram

100%10%

Note:Burden must be specified

Page 23: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

23GE Multilin

Instrument Transformers, Inc.

IEEE CT Metering Accuracy

Corrected to 0.3% Class

CT Parallelogram – IEEE C57.130.3 classparallelogram

0.6 classparallelogram

100%

10%

Note:Burden must be specified

Page 24: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

24GE Multilin

Instrument Transformers, Inc.

0.30

0.30

0.60

0.60

Rating Factor

Accu

racy

Cla

ss -

%

5% 100% 200% 300% 400%

1.0 2.0 3.0 4.0

IEEE C57.13.6 Accuracy0.15 @ E0.04, E0.20; 0.15 @ BX.X; RF4.0

0.15% Accuracy Region

0.3% Accuracy

Region

IEEE CT Metering Accuracy

0.15

0.15

No accuracy guaranteed at current levels less than 5%

Page 25: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

25GE Multilin

Instrument Transformers, Inc.

0.30

0.30

0.60

0.60

Rating Factor

Accu

racy

Cla

ss -

%

5% 200% 300%

1.0 2.0 3.0 4.0

IEEE C57.13.6 Accuracy0.15S @ E0.04, E0.20; 0.15S @ BX.X, RF4.0

0.15% Accuracy Region

IEEE CT Metering Accuracy

0.15

0.15

No accuracy guaranteed at current levels less than 5%

400%100%

Page 26: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

26GE Multilin

Instrument Transformers, Inc.

IEEE CT Relay AccuracyProtection CT

Standard Relay Accuracy Classes

C or T100

C or T200

C or T400

C or T800

What do these mean?

Page 27: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

27GE Multilin

Instrument Transformers, Inc.

IEEE CT Relay Accuracy

Relay class (C or T___ ) designates minimum secondary terminal volts…

At 20 times rated current

Without exceeding 10% ratio error

Into a maximum specified burden

Now that everyone is totally confused let’s look at some simple examples …

Page 28: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

28GE Multilin

Instrument Transformers, Inc.

T = Determined by testC = CalculatedK = CalculatedL = Low internal secondary impedanceH = High internal secondary impedance

Format

LetterAccuracy Voltage at 20 times CT

Page 29: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

29GE Multilin

Instrument Transformers, Inc.

Primary current24,000 amps

(20 x 1200)

IEEE CT Relay Accuracy

CT1200:5

C or T100

X1X2

Burden ofDevices ()

Burden ofLeads ()

Secondary current 100 amps (20 x 5)

Total Ext Burden1.0

C or T100 example

Terminal Volts = (20 times rated) (Total external burden)

100 Volts = (100 amps) (1.0 )

Term

inal

Vol

ts =

100

Page 30: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

30GE Multilin

Instrument Transformers, Inc.

Primary current24,000 amps

(20 x 1200)

IEEE CT Relay Accuracy

CT1200:5

C or T200

X1X2

Burden ofDevices ()

Burden ofLeads ()

Secondary current 100 amps (20 x 5)

Total Ext Burden2.0

C or T200 example

Terminal volts = (20 times rated) (Total external burden)

200 Volts = (100 amps) (2.0 )

Term

inal

Vol

ts =

200

Page 31: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

31GE Multilin

Instrument Transformers, Inc.

Standard IEEE CT Burdens (5 Amp) (Per IEEE Std. C57.13-1993)

IEEE CT Relay Accuracy

Application Burden

Designation

Impedance

(Ohms)

VA @

5 amps

Power

Factor

Relaying B1 1 25 0.5

B2 2 50 0.5

B4 4 100 0.5

B8 8 200 0.5

Page 32: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

32GE Multilin

Instrument Transformers, Inc.

IEEE CT Relay AccuracyExcitation curve includesvoltage required to overcome internal resistance (DCR) of CT.Approximately 32 volts.

10% ratio error = (20 x 5) (10%) = (100) (0.10) = 10 amps

How many terminal volts would you estimate this CT can produce?

Page 33: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

33GE Multilin

Instrument Transformers, Inc.

1000:5 CT

1000 Amps 5amps

IE<0.5amps

IB >4.5 amps

With 10% error, IB is anywhere from 4.5 to 5.5 amps

Most Protection CT’s also have a Metering CT accuracy so you could use this value for calculating the error at lower

currents

Page 34: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

34GE Multilin

Instrument Transformers, Inc.

CT Burden Calculation

Primary Current

CT

X1X2

Burden ofDevices ()

Burden ofLeads ()

Secondary current

Total Burden ZT

How do we calculate this?

Page 35: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

35GE Multilin

Instrument Transformers, Inc.

CT Burden Calculation

Assumption: 3 phase CTs are “Y” connected

ZT = RCT + RL + ZB

ZT = Total burden in ohms (vector summation of resistance and inductance components)

RCT = CT secondary resistance in ohms @75 deg C (DCR)

RL = Resistance of leads in ohms (Total loop distance)

ZB = Device impedance in ohms

Page 36: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

36GE Multilin

Instrument Transformers, Inc.

GE Multilin Electronic Relay Burden

VA = VI. V= IR, So 0.2 = I*I*R.

.2/25 = .008 ohms

Page 37: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

37GE Multilin

Instrument Transformers, Inc.

100:5 C.T. Secondary Winding Resistance (DCR) = .062 ohm

Resistance of Cable from C.T. to Relay and back = .1 ohms

Resistance of Relay Coil = .02 ohms

Total Resistance = .182 ohms

If we have a fault of 2,000 amps and the C.T. ratio is 100:5 then the C.T. secondary current is 100 amps. Therefore we will produce a voltage of 100 amps x .182 ohms = 18.2 Volts. To prevent CT saturation, select a CT with a knee point above 18.2 Volts.

.062

.1

.02

Page 38: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

38GE Multilin

Instrument Transformers, Inc.

780-102 is a 1000 to 5 CT, Class C100

1000:5 C.T. Secondary Winding Resistance (DCR) = .32 ohm

Resistance of Cable from C.T. to Relay and back = .1 ohms

Resistance of Relay Coil = .008 ohms

Total Resistance = .428 ohms

If we have a fault of 20,000 amps and the C.T. ratio is 1000:5 then the C.T. secondary current is 100 amps. Therefore we will produce a voltage of 100 amps x .428 ohms = 42.8 Volts. To prevent CT saturation, select a CT with a knee point above 42.8 Volts.

What happens if the fault current is 40,000 amps?

.32

.1

.008

Page 39: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

39GE Multilin

Instrument Transformers, Inc.

Factors Influencing CT Accuracy

Frequency

Current Ratio

Burden

“Low frequency” and “High accuracy” are not friends!!

“Low ratio” and “high accuracy” are not friends!!

“High burden” and “High Accuracy” are not friends!!

Page 40: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

40GE Multilin

Instrument Transformers, Inc.

CT Saturation

What is CT Saturation?

Page 41: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

41GE Multilin

Instrument Transformers, Inc.

Power Systems Relay Committee (PSRC) Saturation Calculator

Page 42: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

42GE Multilin

Instrument Transformers, Inc.

Factors Affecting Degree of Saturation and Time to Saturation

DC Offset

Fault Magnitude (symmetrical current)•100 to 5 CT@20 times= 2000 amps, at 20,000 amps we have 200 times CT

CT Turns Ratio

Secondary Burden

CT Accuracy

Remanence Flux • Can occur if current interrupted when core is saturated• If DC flows in windings during testing• Need a voltage above 60% of knee point to reduce the remanence to

less than 10% of saturation flux density.

Page 43: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

43GE Multilin

Instrument Transformers, Inc.

Tips for Avoiding CT SaturationUse higher ratio CTs

Use separate set of high ratio CTs for high fault current tripping

Reduce secondary burdenSelect low burden relays & metersDistribute single phase burdens among phasesIncrease size of secondary leadsReduce length of secondary leads

Use “step down” auxiliary CTs

Page 44: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

44GE Multilin

Instrument Transformers, Inc.

Potential Transformers

Page 45: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

45GE Multilin

Instrument Transformers, Inc.

DefinitionsVoltage Transformer (VT)

An instrument transformer used to reflect a primary voltage into a secondary voltage through a magnetic medium. Always connected in parallel with primary conductor across a circuit load.

Secondary (measuring) voltage is usually 115 or 120 volts nominally. The secondary voltage level is selected for ease of measurement and safety.Control Power Transformer (CPT)

Designed to provide power for contractors, relays and devices with high inrush currents, Regulation is not as critical.

Page 46: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

46GE Multilin

Instrument Transformers, Inc.

Page 47: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

47GE Multilin

Instrument Transformers, Inc.

Relay

14,400/120 = 120/1

4200/120 = 35/1

2400/120 = 20/1

Page 48: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

48GE Multilin

Instrument Transformers, Inc.

IEEE VT Accuracy ClassMetering Accuracy

Classes (% error)

0.3

0.6

1.2

0.15

Defined by IEEE C57.13

Applicable from 90% to 110% rated voltage

Defined by IEEE C57.13.6

Page 49: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

49GE Multilin

Instrument Transformers, Inc.

IEEE VT Accuracy Class

These standard burden designations have no significance at frequencies other than 60 Hz.

Burden VA PF

W 12.5 0.10X 25 0.70M 35 0.20Y 75 0.85Z 200 0.85

ZZ 400 0.85

Metering Accuracy Class Burdens

Page 50: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

50GE Multilin

Instrument Transformers, Inc.

IEEE VT Accuracy Class

Expressed as:

Accuracy Class + Burden Code

0.3 W,X,Y0.6 Z

1.2 ZZ

These standard designations have no significance at frequencies other than 60 Hz.

Page 51: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

51GE Multilin

Instrument Transformers, Inc.

Page 52: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

52GE Multilin

Instrument Transformers, Inc.

VT Installation Guidelines Caution:

Rated voltage: Do not operate above 110%

Line to ground rated:

Do not connect line to line

Do not use on ungrounded systems w/o consulting factory

Rated Frequency: Do not operate below rated frequency w/o consulting factory

Page 53: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

53GE Multilin

Instrument Transformers, Inc.

IEEE VT Groups VT

GroupNo. of

BushingConnection

Method

Neutral Grounding

Notes

1 2 open

Y-Y possible

Any Withstand 25% over rated voltage on an emergency basis

2 2 open

Y-Y possible

Any Withstand 10% over rated voltage continuously. Primary rated for line to line voltage.

3 1 Y-Y-Y Any Outdoor, two secondary windings. Withstand 10% over rated voltage continuously.

4A 1 Y-Y Effectively Withstand 10% over rated voltage continuously & 25% on an emergency basis. For operation at 100% rated voltage.

4B 1 Y-Y

Y-Broken Corner

Non-effectively

Withstand 10% overvoltage continuously. For operation at 58% rated voltage.

5 1 Y-Y Effectively Outdoor. Withstand 40% over rated voltage for 1 minute and 10% over rated voltage continuously

Page 54: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

54GE Multilin

Instrument Transformers, Inc.

VT Typical Connections

Open Delta Connection(2) Double Bushing VTs

Y – Y Connection(3) Single Bushing VTs

Page 55: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

55GE Multilin

Instrument Transformers, Inc.

FerroresonancePossible with Y connected grounded VTs on ungrounded power systems

A VT is an inductive component

Capacitance to ground exists in the system

When they match ferroresonance may occur

May cause higher VT voltages & saturation

Possible results --High VT currentsOverheatingVT failure

Page 56: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

56GE Multilin

Instrument Transformers, Inc.

Ferroresonance

Recommended reading:

“Ferroresonance of Grounded Potential

Transformers on Ungrounded Power Systems”

AIEE Power Apparatus & Systems,

Aug 1959, pg 607-618, by Karlicek and Taylor

Page 57: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

57GE Multilin

Instrument Transformers, Inc.

Ferroresonance Damping

Y – Broken Corner VT connection

Ferroresonancedamping resistor RFR

Voltage relay to detect ground fault

Non effectively grounded system

0 volts @ normal condition

3 times normal L-N phasevoltage @ ground fault

Preferred method

Page 58: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

58GE Multilin

Instrument Transformers, Inc.

Ferroresonance Damping

Y-Y/Broken Corner Connection

Double secondary VT

(1) Relaying / Metering

(1) Ground fault detectionand ferroresonance damping

Preferred method

Page 59: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

59GE Multilin

Instrument Transformers, Inc.

Ferroresonance Damping

Ferroresonancedamping resistor RFR value

Based on 2 variables:Air core inductance of primary winding (La)VT ratio (N)RFR = 100 La / N2

Power rating (watts) of the resistor is a system related problem.General recommendation is 50% of VA rating of a single VT.

Page 60: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

60GE Multilin

Instrument Transformers, Inc.

Required Information for Specifying CTs & VTs

Page 61: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

61GE Multilin

Instrument Transformers, Inc.

Current Transformer (CT) RFQ Specification Environment: ___Indoor ___Outdoor

System Voltage (kV)0.6

0.723.65.07.28.712152425

34.534.5

Power Frequency (kV)43

10192026283450407070

BIL (kV)10

4060607575

110125125150200

Standard (Check one)IEEE __

IEC __IEC __IEEE __IEC __IEEE __IEC __IEEE __IEC __IEEE __IEEE __IEEE __

CT Application: ___Metering ___Protection

Dimensions: ___ Inches ___ mm

Max. Outside: L ______ x W ______ x D ______

CT Window: Round: ______ Diameter; Rectangular: L ______ x W ______ ; Primary Bar: _____

Current Ratio: _______ : 5 _______ : 1

Continued next slide

Page 62: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

62GE Multilin

Instrument Transformers, Inc.

Current Transformer (CT) RFQ Specification (Continued)Accuracy:

Indication Only: _____ %, _____VA (Skip metering & protection selections)

Metering Class:IEEE: ___0.3 ___0.6 ___1.2 ___2.4 ________OtherIEC: ___0.2 ___0.5 ___1.0 ________Other

Metering Burden:IEEE (Ohms): ___B0.1 ___B0.2 ___B0.5 ___B0.9 ___B1.8 ______OtherIEC (VA): ___2.5 ___5.0 ___10 ___15 ___30 ______Other

Protection Class: C______(IEEE) ___VA, ___P___(IEC)

Operating Frequency: ___60HZ ___50HZ

Rating Factor: ___1.0 ___1.33___1.5___2.0______Other

Secondary Connections: ___Terminals___24 inch leads

Outer Insulation: ___Standard___Cotton tape & varnish___Polyester tape

Insulation Class: ___105 0C (Standard)_____Other

Other Special Requirements (dimensional constraints, mounting requirements, …etc):____________________________________________________________________________________________________________________________________________________________

Page 63: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

63GE Multilin

Instrument Transformers, Inc.

Voltage Transformer (VT) RFQ Specification Environment: ___Indoor ___Outdoor

System Voltage (kV)0.6

0.723.65.07.28.712152425

34.534.5

Power Frequency (kV)43

10192026283450407070

BIL (kV)10

4060607575

110125125150200

Standard (Check one)IEEE __IEC __IEC __IEEE __IEC __IEEE __IEC __IEEE __IEC __IEEE __IEEE __IEEE __

Continued next slide

Operating Frequency: ___60HZ ___50HZ

Accuracy:

IEEE: ___W ___X ___M ___Y ___Z ___ZZ ________Other(Enter 0.3, 0.6, 1.2, or leave blank)

IEC: ___10VA ___25VA ___50VA ___100VA ___200VA ___500VA ______Other(Enter 0.2, 0.5, 1.0, or leave blank)

Page 64: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

64GE Multilin

Instrument Transformers, Inc.

Voltage Transformer (VT) RFQ Specification (Continued)

Thermal Rating: _______VA (Optional)

Primary Voltage: ___1 bushing _________VAC - Phase to neutral

___2 bushing _________VAC - Phase to phase

Secondary Voltage: ___120V ___115V ___110V ___100V___120/3 ___115/3 ___110/3 ___100/3___Other _________________

Rated Voltage Factor (RVF) (1 bushing only): ___1.9 for 30s ___1.9 for 8 hours ___Other____________

Fuses:

___Primary ___Secondary ___None (600 – 720 V)

___Primary ___Live parts only ___Switchgear Style ___Unfused (2.5kV – 15kV)

Note integral fusing not available above 15kV

Page 65: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

65GE Multilin

Instrument Transformers, Inc.

Take Home Rule # 1

CTs are intended to be proportional current devices. Very high voltages can result from open circuiting the secondary circuit of an energized CT. Even very small primary currents can cause damage… Consult the factory if you have questions.

Never open circuit a current transformer secondary while the primary is energized

Page 66: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

66GE Multilin

Instrument Transformers, Inc.

Never short circuit the secondary of an energized VT

Take Home Rule # 2

VTs are intended to be used as proportional voltage

devices. Damaging current will result from short

circuiting the secondary circuit of an energized VT.

Page 67: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

67GE Multilin

Instrument Transformers, Inc.

Take Home Rule # 3

Metering applications do not require a “C” class CT

“C” class ratings are specified for protection purposes only. With some exceptions metering class CTs are typically smaller and less expensive.

Page 68: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

68GE Multilin

Instrument Transformers, Inc.

Take Home Rule # 4

CT secondary leads must be added to the CT burden

Electronic relays usually represent very little burden to the CT secondary circuit. In many cases the major burden is caused by the CT secondary leads.

Page 69: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

69GE Multilin

Instrument Transformers, Inc.

Take Home Rule # 5

Never use a 60 Hz rated VT on a 50 Hz System

60 Hz VTs may saturate at lower frequencies and exceed temperature limitations. VT failure is likely…severe equipment damage is possible.

Page 70: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

70GE Multilin

Instrument Transformers, Inc.

Take Home Rule # 6

Exercise caution when connecting grounded VTs to ungrounded systems

Line to ground voltage on any VT may exceed the primary voltage rating during a fault condition… VT must be designed for application.

Page 71: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

71GE Multilin

Instrument Transformers, Inc.

Take Home Rule # 7

It is common practice to apply 600 Volt CT to systems with higher voltages.

This practice is done by passing fully insulated conductors through the Window.

Page 72: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

72GE Multilin

Instrument Transformers, Inc.

QUESTIONS?

Page 73: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

73GE Multilin

Instrument Transformers, Inc.

Page 74: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

74GE Multilin

Instrument Transformers, Inc.

Page 75: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

75GE Multilin

Instrument Transformers, Inc.

LV SwitchboardsLV Panelboards

5 Series

8SHT19RT

Typical CT Models

Page 76: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

76GE Multilin

Instrument Transformers, Inc.

LV SwitchboardsLV Panelboards

Typical VT Models

460, 467, 475, 2VT460, 3VT460

Page 77: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

77GE Multilin

Instrument Transformers, Inc.

L.V. MCC’s

8SHT

19RT

5 Series

3P85

Typical CT Models

Page 78: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

78GE Multilin

Instrument Transformers, Inc.

L.V. MCC’s

Typical VT Models

460, 467, 475, 2VT460, 3VT460

Page 79: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

79GE Multilin

Instrument Transformers, Inc.

L.V. Switchgear

Page 80: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

80GE Multilin

Instrument Transformers, Inc.

L.V. Switchgear Current TransformersGE 2000 amp frameModel 560 MeteringModel 561 Protection

Page 81: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

81GE Multilin

Instrument Transformers, Inc.

Current TransformersGE 4000 amp frameModel 562 MeteringModel 563 Protection

L.V. Switchgear

Page 82: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

82GE Multilin

Instrument Transformers, Inc.

L.V. Switchgear

No more room in the front? We can recommend a different model CT for the rear bus area.

Page 83: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

83GE Multilin

Instrument Transformers, Inc.

L.V. SwitchgearTypical 3 Phase VTInstallation

3VTL4603 Phase VT

Page 84: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

84GE Multilin

Instrument Transformers, Inc.

M.V. SwitchgearTypical Line Up

Where are the CTs, VTs, and CPTs?

Page 85: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

85GE Multilin

Instrument Transformers, Inc.

Current Transformers778 / 779 680 /780 Series Typical IEEE Metering & Protection

M.V. Switchgear

Page 86: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

86GE Multilin

Instrument Transformers, Inc.

M.V. Switchgear Current TransformersMetering & Protection

Model 780, 778

Model 785

Page 87: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

87GE Multilin

Instrument Transformers, Inc.

M.V. Switchgear

Model 203 CTs mounted in rear bus compartment

Page 88: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

88GE Multilin

Instrument Transformers, Inc.

M.V. Switchgear

Zero Sequence CTModel 593, 594

Is this better than a Residual Connection?

Page 89: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

89GE Multilin

Instrument Transformers, Inc.

M.V. SwitchgearTypical VT Rollout Drawer

Installed in enclosure

Withdrawn from enclosure

(2) PTG5’s in open deltaconfiguration

Page 90: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

90GE Multilin

Instrument Transformers, Inc.

M.V. SwitchgearTypical CPT Rollout Drawer

Installed in enclosureWithdrawn from enclosure

CPT5 & 15 kV5 to 15 kVA

Page 91: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

91GE Multilin

Instrument Transformers, Inc.

MV MCC’s

Let’s open a door and see what’s inside

Page 92: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

92GE Multilin

Instrument Transformers, Inc.

MV MCC’s

Typical CT Models112113114115117

Page 93: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

93GE Multilin

Instrument Transformers, Inc.

Generators

Board Mounted Generator CT

Page 94: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

94GE Multilin

Instrument Transformers, Inc.

Station Class Circuit Breakers

Polyester Taped Bushing CT on Outdoor Circuit Breaker

Page 95: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

95GE Multilin

Instrument Transformers, Inc.

Station Class Circuit Breakers

Outdoor BO7 - Replaces BCT’s in shielded aluminum housing

Ground Shield

Page 96: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

96GE Multilin

Instrument Transformers, Inc.

Outdoor Type BO7 for Retrofit

Power TransformersSlip over current transformer for installation over exterior of outdoor bushing

Page 97: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

97GE Multilin

Instrument Transformers, Inc.

Power TransformersMetering applications for indoor instrument transformerson outdoor power transformers

Air terminal chamber Indoor PT and Bar type CT

Page 98: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

98GE Multilin

Instrument Transformers, Inc.

Page 99: Are you using the right CT's and PT's for your application? · 1 GE Multilin Instrument Transformers, Inc. Are you using the right CT's and PT's for your application? John Levine,

99GE Multilin

Instrument Transformers, Inc.

Questions?