Asset: I.S. 35 - BROOKLYN, 272 MCDONOUGH STREET, New York, 11233
Inspection Id Inspection Type Time In Last Edited
SA : K035 Architectural - Senior 2019-01-15 7:36 AM 2019-06-04 2:39 PM
AA : K035 Architectural - Associate 2019-01-15 8:50 AM 2019-01-23 5:15 PM
Asset Data
Question Answer
Was the building fully accessible for inspection Yes
Principal(s) Information
Principal Name Alexander Brunner
Organization I.S. 35 - Brooklyn
Did you meet with this Principal? No
Did this Principal provide feedback? Yes
Summary of Principal's Feedback Assistant Principal (Kevin Bond) provided comments on behalf of thePrincipal as follows: 1. Bathrooms in the the Auditorium are acommon area and requires updating. 2. The electrical system requiresan upgrade, the clocks are not functional. 3. The Exterior Doors aredeteriorated.
Principal Name Beatrice Thompson
Organization The Brooklyn Brownstone School - Brooklyn
Did you meet with this Principal? No
Did this Principal provide feedback? No
Principal Name Michele Thornton
Organization P141K - District 75 - Brooklyn
Did you meet with this Principal? No
Did this Principal provide feedback? No
Custodian Thomas Cottone
Fireman Siddiq Khan
Building Square Footage 113000
Comments on the Area None
Comments on the Stories (Floors) plus Basements 4 + B + SB + PH
Comments on the Number of Classrooms 49
Comments on the Year Built 1926
Student Population 635
Staff Population 136
Weather Fair
Facade Photo
Corner of MacDonough Street and LewisAvenue - Southwest View
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 1 of 53
Avenue - Southwest View
Main Entrance Photo
Facade A - MacDonough Street
Roof Photo
Roof 1 - West View
Have any Systems/Major Building Components been upgraded? Yes
Systems: Exterior Modernization Program including Ash HoistVault Slab repairs and Doors replacement; Roofing andFlashing replacement; Parapets and coping replacement;Partial Exteriro Walls Brick Veneer replacement; RoofDrain Strainers replacement; Chimney repointing;Bulkhead repairs; Roof Structure repairs; Partial ExteriorWalls repointing; Foundation Walls Waterproofing; (6)Basement, 2nd and 3rd Floor Student Toilet Roomsupgraded to HC compliant; Cafeteria Flooringreplacement
Year: 2016
Systems: New Science Lab Room 102
Year: 2015
Systems: Partial Foundation repairs
Year: 2013
Systems: Windows and Window Guards replacement
Year: 2010
Systems: Partial Exterior Doors replacement
Year: 2007
Have there been any New Building Additions? Yes
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 2 of 53
Comments on New Building Additions 1947 + 80,000 S.F.
Tandem Schools? No
Leased Space? No
Priority Condition
PriorityCondition ExistLast Year?
PriorityCategory
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
Yes Missing InteriorFire Doors
Missing FireDoor is apotential safetyhazard
INTERIOR |CLASSROOMS/CORRIDORS/ADMINSPACES |Door(s)
Exit 14Vestibule
Siddiq Khan Fireman
Yes Tripping Hazard Deterioratedconcrete stairtreads and risersare a potentialtripping hazard.
EXTERIOR |AREAWAY
Exterior stairs atthe areawayfrom thebasement at thewest side of thebuilding.
Thomas Cottone Custodian
Yes Tripping Hazard SeverelyDamaged Stairis a potentialtripping hazard
INTERIOR |STAIRS/RAMPS: INTERIOR |Stairs andLandings
StairD/Basement
Siddiq Khan Fireman
Structural Engineer Required
StructuralCondition Type
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No condition recorded
Accessibility
Accessibility Status Question Response
Is the primary or secondary entrance on an accessible route? Yes
Is the building a multi-story building? Yes
Are all floors of the building accessible through compliant means? No
Are SOME floors other than the 1st floor and basement accessible through compliantmeans?
No
Do any of the following spaces exist on the First floor? Classroom, Art Room,Auditorium, Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, ScienceLabs
Yes
For the rooms that do exist, are SOME of them accessible on the 1st floor? No
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
FUNCTIONAL ACCESSIBILITY
Exterior Routes
Exterior Entrances & Exits Yes
Exterior H/C Lifts No No
Exterior Ramps and Railings No No
Interior Routes
Corridor and Lobby H/C Lifts No Yes
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 3 of 53
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
Interior Routes
Interior Corridor Doors and Hardware Yes Yes
Interior Corridors and Lobbies Yes
Interior Elevators No
Interior Lobby Doors and Hardware Yes
Interior Ramps No
Rooms & Spaces
Art Rooms Room 119, 216 Yes No Not on Accessible Route
Auditorium Basement Yes Yes No Yes
Cafeteria Basement Yes No Not on Accessible Route Yes Yes
Classrooms None on Accessible Route Yes No Not on Accessible Route
Computer Rooms No
Gymnasium 2nd Floor Yes No Not on Accessible Route Yes Yes
Basement Yes Yes Yes Yes
Library Room 328 Yes No Not on Accessible Route
Main Office Room 115 (I.S. 35); Room 312 (TheBrooklyn Brownstone School): Room325 (P141K)
Yes No Not on Accessible Route
Multi-purpose Room No
Nurse's Room Rooms 230 Yes No Not on Accessible Route
Pool No
Science Lab Rooms 102, 201 Yes No Not on Accessible Route
Toilet Rooms (Boys) None on Accessible Route Yes No Not on Accessible Route
Toilet Rooms (Girls) None on Accessible Route Yes No Not on Accessible Route
Toilet Rooms (Staff) None on Accessible Route Yes No Not on Accessible Route
Building Template
Inspection
Question Response
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 4 of 53
Question Response
Architectural
EXTERIOR Inspected
AREAWAY Inspected
InspectedInstance on AW1 - AW13
Instance Condition 5 - Poor
Instance Quantity 13
Instance Quantity Uom EACH
Deficiency AREAWAY STAIRS: DETERIORATEDTREADS/RISERS/NOSINGS
Roof Plan reference
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
AW10
Violations No violations recorded.
Deficiency AREAWAY SLAB: CRACKS AND SPALLING
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 5 of 53
Question Response
EXTERIOR
AREAWAY
Deficiency Photo1
AW6
Violations No violations recorded.
Deficiency AREAWAY WALLS: CRACKS AND SPALLING
Roof Plan reference
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
AW4
Violations No violations recorded.
Deficiency AREAWAY DRAINS: DETERIORATED
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 6 of 53
Question Response
EXTERIOR
AREAWAY
Roof Plan reference
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
AW8
Violations No violations recorded.
Deficiency AREAWAY DRAINS: CLOGGED
Roof Plan reference
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
Deficiency AREAWAY LADDER: DETERIORATED
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 7 of 53
Question Response
EXTERIOR
AREAWAY
Roof Plan reference
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
AWNINGS AND CANOPIES Does not Exist
CHIMNEY Inspected
Material Type(s) Masonry
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
COPING Inspected
Condition 2 - Between Good and Fair
Deficiency CAST STONE: OPEN TRANSVERSE JOINTS WITH DAMAGEDCAULKING
Roof Plan reference
Deficiency Quantity 10
Quantity Uom L.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
CORNICE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
DOORS Inspected
DOORS AND FRAMES Inspected
Condition 4 - Between Fair and Poor
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 8 of 53
Question Response
EXTERIOR
DOORS
DOORS AND FRAMES
Deficiency METAL CLAD: DETERIORATED DOOR AND FRAME - MINORDETERIORATION
Roof Plan reference
Deficiency Quantity 2
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
Deficiency METAL CLAD: DETERIORATED DOOR - MAJORDETERIORATION
Roof Plan reference
Deficiency Quantity 2
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Exit 13
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 9 of 53
Question Response
EXTERIOR
DOORS
DOORS AND FRAMES
Deficiency METAL CLAD: DETERIORATED DOOR - MINORDETERIORATION
Roof Plan reference
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
Deficiency METAL CLAD: DETERIORATED DOOR AND FRAME - MAJORDETERIORATION
Roof Plan reference
Deficiency Quantity 3
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade C
Violations No violations recorded.
DOOR HARDWARE Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 10 of 53
Question Response
EXTERIOR
DOORS
DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TRANSOM/SIDE LIGHT Inspected
Condition 3 - Fair
Deficiency METAL: BROKEN GLASS
Roof Plan reference
Deficiency Quantity 55
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
EXTERIOR WALLS Inspected
Material Type(s) Masonry
Replacement Quantity 45,000
Replacement Uom S.F.
InspectedInstance on All Facades
Instance Condition 3 - Fair
Instance Quantity 45,000
Instance Quantity Uom S.F.
Deficiency BRICK: OPEN JOINTS
Roof Plan reference
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 11 of 53
Question Response
EXTERIOR
EXTERIOR WALLS
Elevation
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade E
Violations No violations recorded.
Deficiency STONE: CRACKS AT BUILDING CORNERS
Roof Plan reference
Elevation
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action REPLACE
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 12 of 53
Question Response
EXTERIOR
EXTERIOR WALLS
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade E
Violations No violations recorded.
EXTERIOR SOFFITS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LOADING DOCK Does not Exist
LOUVER Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
PARAPETS Inspected
Material Type(s) Masonry
Replacement Quantity 9,200
Replacement Uom C.F.
InspectedInstance on All Facades
Instance Condition 1 - Good
Instance Quantity 9,200
Instance Quantity Uom C.F.
Deficiency No deficiencies recorded
PLAZA DECK Does not Exist
ROOF Inspected
Roofing Inspected
Replacement Quantity 29,000
Replacement Uom S.F.
ROOF HATCH/SMOKE HATCH Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
ROOF BARRIER Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
ROOF CAGE Does not Exist
ROOF FENCE Does not Exist
ROOFING Inspected
InspectedInstance on Modified Bitumen: All Roofs
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 13 of 53
Question Response
EXTERIOR
ROOF
Roofing
ROOFING
Instance Condition 3 - Fair
Instance Quantity 29,000
Instance Quantity Uom S.F.
Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?
No
Installation Year 2016
Source of Installation Custodial Staff
Deficiency MODIFIED BITUMEN: ROOFING: MINOR LEAKAGE
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1 - Stair B/3
Violations No violations recorded.
ROOFING DRAINS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Specialties Inspected
BULKHEAD/PENTHOUSE Inspected
Condition 3 - Fair
Deficiency BULKHEAD/PENTHOUSE WALLS/INTERIOR: BRICK OPENJOINTS
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 14 of 53
Question Response
EXTERIOR
ROOF
Specialties
BULKHEAD/PENTHOUSE
Roof Plan reference
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
BH1
Violations No violations recorded.
CUPOLA/ SPIRES/ TOWERS Does not Exist
DORMER Does not Exist
DUNNAGE STEEL Does not Exist
SKYLIGHT/ROOF VENT Inspected
Material Type(s) Glass
Condition 1 - Good
Deficiency No deficiencies recorded
ROOF/GRAVITY TANK Does not Exist
STAIRS/RAMPS: EXTERIOR Inspected
BUILDING CHEEK/FLANK WALLS Does not Exist
RAILINGS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
STAIRS/RAMPS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
WINDOWS Inspected
Replacement Quantity 13,500
Replacement Uom S.F.
EXTERIOR GUARDS Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 15 of 53
Question Response
EXTERIOR
WINDOWS
EXTERIOR GUARDS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency STEEL: MINOR RUSTING
Roof Plan reference
Elevation
Deficiency Quantity 20
Quantity Uom L.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
WINDOWS Inspected
Material Type(s) Aluminum
InspectedInstance on Aluminum - Double Hung: All Facades
Instance Condition 3 - Fair
Instance Quantity 13,000
Instance Quantity Uom S.F.
Installation Year 2010
Source of Installation Custodial Staff
Deficiency ALUMINUM - DOUBLE HUNG: AIR/WATER INFILTRATION
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 16 of 53
Question Response
EXTERIOR
WINDOWS
WINDOWS
Roof Plan reference
Elevation
Deficiency Quantity 40
Quantity Uom L.F.
Potential Action REPLACE TRIM, SILLS OR WEATHERSTRIPPING
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
Deficiency ALUMINUM - DOUBLE HUNG: BROKEN PANE
Roof Plan reference
Elevation
Deficiency Quantity 10
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 17 of 53
Question Response
EXTERIOR
WINDOWS
WINDOWS
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
InspectedInstance on Aluminum - Other: Facade F
Instance Condition 2 - Between Good and Fair
Instance Quantity 500
Instance Quantity Uom S.F.
Installation Year 2010
Source of Installation Custodial Staff
Deficiency No deficiencies recorded
INTERIOR Inspected
POOLS Does not Exist
STRUCTURAL Inspected
COLUMNS/BEAMS/BEARING WALLS Inspected
Condition 3 - Fair
Deficiency STEEL COLUMNS/BEAMS: DETERIORATED MASONRYFIREPROOFING
Deficiency Location/Instance Under Auditorium
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 5
Deficiency Photo1
Under Auditorium
Violations No violations recorded.
Deficiency STEEL COLUMNS/BEAMS: DETERIORATED CONCRETEFIREPROOFING
Deficiency Location/Instance Boiler Room
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 5
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 18 of 53
Question Response
INTERIOR
STRUCTURAL
COLUMNS/BEAMS/BEARING WALLS
Deficiency Photo1
Oil Pup Room 1926 Building
Violations No violations recorded.
FLOOR STRUCTURE Inspected
Condition 3 - Fair
Deficiency CONCRETE SLAB ON GRADE: MINOR CRACKS
Deficiency Location/Instance Coal Storage Room
Deficiency Quantity 60
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Coal Storage Room
Violations No violations recorded.
FOUNDATION WALLS Inspected
Material Type(s) Concrete
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
ROOF STRUCTURE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
VAULTS-BUNKERS Inspected
Foundation Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Slab Structure Inspected
Condition 3 - Fair
Deficiency CONCRETE SLAB ON GRADE: THRU CRACKS
Deficiency Location/Instance Decatur Street
Deficiency Quantity 25
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 19 of 53
Question Response
INTERIOR
STRUCTURAL
VAULTS-BUNKERS
Slab Structure
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 5
Deficiency Photo1
Vault Decatur Street
Violations No violations recorded.
Vault/Ash Hoist Doors and Framing Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
AUDITORIUM Inspected
InspectedInstance on Basement (480 Seats)
Ceiling
InspectedInstance on Basement (480 Seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on Basement (480 Seats)
Condition 4 - Between Fair and Poor
Deficiency METAL CLAD WOOD: DETERIORATED DOOR AND FRAME
Deficiency Location/Instance Exit 11 Vestibule
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Storage
Violations No violations recorded.
Deficiency METAL: DETERIORATED DOOR
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 20 of 53
Question Response
INTERIOR
AUDITORIUM
Door(s)
Deficiency Location/Instance Projection Room
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Projection Room
Violations No violations recorded.
Fixed H/C Lift
Does not ExistInstance on Basement (480 Seats)
Fixed Seating
InspectedInstance on Basement (480 Seats)
Condition 3 - Fair
Deficiency DAMAGED/BROKEN/INOPERABLE
Deficiency Location/Instance Seats D/5, F/9, M/18, Q/22,26, and others
Deficiency Quantity 26
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Seat Q/22
Violations No violations recorded.
Floor Finish
InspectedInstance on Basement (480 Seats)
Condition 2 - Between Good and Fair
Deficiency TERRAZZO: CRACKS
Deficiency Location/Instance Exit 12 Vestibule
Deficiency Quantity 10
Quantity Uom S.F.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 21 of 53
Question Response
INTERIOR
AUDITORIUM
Floor Finish
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Exit 12 Vestibule
Violations No violations recorded.
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Near Stage
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Stage
Violations No violations recorded.
Sliding-folding Partition
Does not ExistInstance on Basement (480 Seats)
Stage
InspectedInstance on Basement (480 Seats)
Stage Inspected
InspectedInstance on Basement (480 Seats)
Condition 3 - Fair
Deficiency DAMAGED FLOOR
Deficiency Location/Instance Front Side
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 22 of 53
Question Response
INTERIOR
AUDITORIUM
Stage
Stage
Deficiency Photo1
Front Side
Violations No violations recorded.
Deficiency DAMAGED FASCIA
Deficiency Location/Instance Center
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Center
Violations No violations recorded.
Stage Curtain Rigging Inspected
InspectedInstance on Basement (480 Seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stage Curtains Inspected
InspectedInstance on Basement (480 Seats)
Condition 3 - Fair
Deficiency WORN/DETERIORATED
Deficiency Location/Instance Stage Left
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 23 of 53
Question Response
INTERIOR
AUDITORIUM
Stage
Stage Curtains
Deficiency Photo1
Stage Left
Violations No violations recorded.
Walls
InspectedInstance on Basement (480 Seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Window Curtains/Shades/Blinds
InspectedInstance on Basement (480 Seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
CAFETERIA Inspected
InspectedInstance on Basement
Ceiling
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Near Stair A
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Stair A
Violations No violations recorded.
Door(s)
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 24 of 53
Question Response
INTERIOR
CAFETERIA
Fixed Equipment
Does not ExistInstance on Basement
Floor Finish
InspectedInstance on Basement
Condition 1 - Good
Deficiency No deficiencies recorded
Sliding-folding Partition
Does not ExistInstance on Basement
Stage
Does not ExistInstance on Basement
Walls
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Window Curtains/Shades/Blinds
Does not ExistInstance on Basement
CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: DETERIORATED DOOR AND FRAME
Deficiency Location/Instance Rooms 201, 328, 434
Deficiency Quantity 3
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 201
Violations No violations recorded.
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Rooms 107, 111, 201, 301, 306, and others
Deficiency Quantity 7
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 25 of 53
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Door(s)
Deficiency Photo1
Room 306
Violations No violations recorded.
Deficiency METAL: MISSING DOOR
Deficiency Location/Instance Exit 14 Vestibule
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Exit 14 Vestibule
Violations No violations recorded.
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency WOOD: DAMAGED/DETERIORATED
Deficiency Location/Instance Room 312
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Rooms 204, 205, 212, Corridor near Room 326
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 26 of 53
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Floor Finish
Deficiency Photo1
Corridor near Room 326
Violations No violations recorded.
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance Rooms 119, 201, 228, 302, 307, and others
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 307
Violations No violations recorded.
Deficiency TERRAZZO: CRACKS
Deficiency Location/Instance Exit 8 Vestibule
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Exit 8 Vestibule
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 27 of 53
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency MIRRORS: BROKEN/DAMAGED
Deficiency Location/Instance Room 202
Deficiency Quantity 60
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 202
Violations No violations recorded.
Deficiency GLAZED BLOCK: CRACKS/SPALLING
Deficiency Location/Instance Corridor near Rooms B14, 209, Gymnasium Basement, Gymnasium2nd Floor
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Gymnasium 2nd Floor
Violations No violations recorded.
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Corridor near Rooms 207, 326, Corridor near Stair E/2
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 28 of 53
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Walls
Deficiency Photo1
Corridor near Room 326
Violations No violations recorded.
Specialties Does not Exist
GYMNASIUM Inspected
InspectedInstance on 2nd Floor
InspectedInstance on Basement
Ceiling
InspectedInstance on 2nd Floor
Condition 2 - Between Good and Fair
Deficiency TECTUM: DAMAGED/MISSING
Deficiency Location/Instance Near Windows, Center
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Windows
Violations No violations recorded.
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency TECTUM: DAMAGED/MISSING
Deficiency Location/Instance Near Entrance
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 29 of 53
Question Response
INTERIOR
GYMNASIUM
Ceiling
Deficiency Photo1
Near Entrance
Violations No violations recorded.
Door(s)
InspectedInstance on 2nd Floor
Condition 4 - Between Fair and Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Office, Storage
Deficiency Quantity 2
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Office
Violations No violations recorded.
InspectedInstance on Basement
Condition 3 - Fair
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Storage
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 30 of 53
Question Response
INTERIOR
GYMNASIUM
Door(s)
Deficiency Photo1
Storage
Violations No violations recorded.
Fixed Equipment
InspectedInstance on 2nd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on 2nd Floor
Condition 2 - Between Good and Fair
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance Office
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Office
Violations No violations recorded.
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency CONCRETE: CRACKS
Deficiency Location/Instance Storage
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 31 of 53
Question Response
INTERIOR
GYMNASIUM
Floor Finish
Purpose of Action LEVEL 2
Deficiency Photo1
Storage
Violations No violations recorded.
Deficiency RUBBER MATTING: WORN/DETERIORATED
Deficiency Location/Instance Center
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Center
Violations No violations recorded.
Seating
InspectedInstance on 2nd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Sliding-folding Partition
Does not ExistInstance on 2nd Floor
Does not ExistInstance on Basement
Stage
Does not ExistInstance on 2nd Floor
Does not ExistInstance on Basement
Walls
InspectedInstance on 2nd Floor
Condition 2 - Between Good and Fair
Deficiency GLAZED BLOCK: CRACKS/SPALLING
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 32 of 53
Question Response
INTERIOR
GYMNASIUM
Walls
Deficiency Location/Instance Near Windows
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Windows
Violations No violations recorded.
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency GLAZED BLOCK: CRACKS/SPALLING
Deficiency Location/Instance Near Windows
Deficiency Quantity 60
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Windows
Violations No violations recorded.
Window Curtains/Shades/Blinds
Does not ExistInstance on 2nd Floor
Does not ExistInstance on Basement
INTERIOR DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
INTERIOR GUARDS Inspected
Condition 3 - Fair
Deficiency DETERIORATED/TORN-OUT/MISSING
Deficiency Location/Instance Stair F/3,4
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 33 of 53
Question Response
INTERIOR
INTERIOR GUARDS
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair F/3
Violations No violations recorded.
KITCHEN Inspected
InspectedInstance on Basement
Ceiling
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on Basement
Condition 5 - Poor
Deficiency METAL: DETERIORATED DOOR AND FRAME
Deficiency Location/Instance Office, Exit 16 Vestibule, Servery
Deficiency Quantity 3
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Office
Violations No violations recorded.
Floor Finish
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency CONCRETE: CRACKS
Deficiency Location/Instance Storage
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 34 of 53
Question Response
INTERIOR
KITCHEN
Floor Finish
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Storage
Violations No violations recorded.
Deficiency CERAMIC TILE: BROKEN/MISSING TILES
Deficiency Location/Instance Servery
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Servery
Violations No violations recorded.
Walls
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/ MISSING
Deficiency Location/Instance Servery, near Ovens
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 35 of 53
Question Response
INTERIOR
KITCHEN
Walls
Deficiency Photo1
Near Ovens
Violations No violations recorded.
LIBRARY Inspected
InspectedInstance on Room 328
Built-in Furnishing
InspectedInstance on Room 328
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Ceiling
InspectedInstance on Room 328
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on Room 328
Condition 3 - Fair
Deficiency WOOD: DETERIORATED DOOR AND FRAME
Deficiency Location/Instance Entrance
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Entrance
Violations No violations recorded.
Floor Finish
InspectedInstance on Room 328
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 36 of 53
Question Response
INTERIOR
LIBRARY Inspected
Walls
InspectedInstance on Room 328
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LOCKER ROOM Inspected
InspectedInstance on 2nd Floor
Alternative use Yes
InspectedInstance on Basement
Alternative use Yes
Ceiling
InspectedInstance on 2nd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on Basement
Condition 3 - Fair
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Entrance
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Entrance
Violations No violations recorded.
Floor Finish
InspectedInstance on 2nd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Locker Room Lockers
Does not ExistInstance on Basement
Does not ExistInstance on 2nd Floor
Walls
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 37 of 53
Question Response
INTERIOR
LOCKER ROOM Inspected
Walls
InspectedInstance on 2nd Floor
Condition 2 - Between Good and Fair
Deficiency GLAZED BLOCK: CRACKS/SPALLING
Deficiency Location/Instance Near Showers
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Showers
Violations No violations recorded.
MULTI-PURPOSE ROOM Does not Exist
SCIENCE DEMO ROOM Does not Exist
SCIENCE LAB Inspected
InspectedInstance on Room 102
Alternative use No
InspectedInstance on Room 201
Alternative use Yes
Fixed Equipment
InspectedInstance on Room 201
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on Room 102
Condition 1 - Good
Deficiency No deficiencies recorded
SCIENCE PREP ROOM Does not Exist
SHOWER ROOM Inspected
InspectedInstance on 2nd Floor
Alternative use Yes
InspectedInstance on Basement
Alternative use Yes
Ceiling
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 2nd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 38 of 53
Question Response
INTERIOR
SHOWER ROOM
Door(s)
Does not ExistInstance on Basement
InspectedInstance on 2nd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on 2nd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls
InspectedInstance on Basement
Condition 3 - Fair
Deficiency CERAMIC TILE: BROKEN/ MISSING
Deficiency Location/Instance Near Entrance
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Entrance
Violations No violations recorded.
STAIRS/RAMPS: INTERIOR Inspected
Do Letter Stair Signs Exist? Yes
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING - ACTIVE LEAK
Deficiency Location/Instance Stair B/3
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 39 of 53
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Ceiling
Deficiency Photo1
Stair B/3
Violations No violations recorded.
Door(s) Inspected
Condition 3 - Fair
Deficiency METAL: MISSING DOOR
Deficiency Location/Instance Stair F/Basement
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair F/Basement
Violations No violations recorded.
Deficiency WOOD: MISSING DOOR
Deficiency Location/Instance Stair E/Basement
Deficiency Quantity 2
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 40 of 53
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Door(s) Inspected
Stair E/Basement
Violations No violations recorded.
Partition Inspected
Condition 2 - Between Good and Fair
Deficiency GLASS PANEL: DAMAGED/DETERIORATED
Deficiency Location/Instance Stairs A/2,3, C/3
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair A/3
Violations No violations recorded.
Deficiency METAL FRAME: DAMAGED/DETERIORATED
Deficiency Location/Instance Stairs A/1,2, B/2,3, D/Basement
Deficiency Quantity 10
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair B/3
Violations No violations recorded.
Railings Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stairs and Landings Inspected
Condition 2 - Between Good and Fair
Deficiency TERRAZZO: CRACKS
Deficiency Location/Instance Stair D/Basement
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 41 of 53
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Stairs and Landings
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Stair D/Basement
Violations No violations recorded.
Deficiency STONE: BROKEN/MISSING
Deficiency Location/Instance Stair A/1, Stair by Room B25
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair by Room B25
Violations No violations recorded.
Deficiency CONCRETE: CRACKS/SPALLING - MAJOR
Deficiency Location/Instance Stairs E/Basement, F/Basement
Deficiency Quantity 60
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 42 of 53
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Stairs and Landings
Deficiency Photo1
Stair E/Basement
Violations No violations recorded.
Deficiency METAL: RUST - MAJOR
Deficiency Location/Instance Stairs A/1, E/Basement
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair A/1
Violations No violations recorded.
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Stairs A/Basement, D/Basement
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair A/Basement
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 43 of 53
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency GLAZED BLOCK: CRACKS/SPALLING
Deficiency Location/Instance Stair A/1, B/2
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair A/1
Violations No violations recorded.
TOILET ROOMS - STAFF Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance 1st Floor - Women, Room B13
Deficiency Quantity 2
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
1st Floor - Women
Violations No violations recorded.
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stalls Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 44 of 53
Question Response
INTERIOR
TOILET ROOMS - STAFF
Stalls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/ MISSING
Deficiency Location/Instance 1st Floor - Women
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
1st Floor - Women
Violations No violations recorded.
TOILET ROOMS - STUDENTS Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Auditorium - Girls
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Auditorium - Girls
Violations No violations recorded.
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Basement Locker Room, Auditorium - Girls, Auditorium - Boys
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 45 of 53
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Door(s)
Deficiency Quantity 3
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Basement Locker Room
Violations No violations recorded.
Deficiency WOOD: DAMAGED LOUVER
Deficiency Location/Instance Room B18
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room B18
Violations No violations recorded.
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/MISSING TILES
Deficiency Location/Instance Auditorium - Boys
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 46 of 53
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Floor Finish
Deficiency Photo1
Auditorium - Boys
Violations No violations recorded.
Stalls Inspected
Condition 2 - Between Good and Fair
Deficiency RUST - MAJOR
Deficiency Location/Instance Basement Locker Room
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Basement Locker Room
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Auditorium - Boys, Room 318
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 47 of 53
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Walls
Deficiency Photo1
Auditorium - Boys
Violations No violations recorded.
Deficiency CERAMIC TILE: BROKEN/ MISSING
Deficiency Location/Instance Room B12
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room B12
Violations No violations recorded.
LIFE SAFETY Inspected
F.D. HOLDING AREA Does not Exist
STEEL STAIRS Does not Exist
SITE Inspected
CONTAINERIZATION Does not Exist
Drainage System for Asphalt Inspected
Catch Basins/Manhole - Surrounded by asphalt Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Asphalt Covering Does not Exist
Drainage System for Concrete Inspected
Catch Basins/Manhole - Surrounded by concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Concrete Covering Does not Exist
Drainage System for Soil Inspected
Catch Basins/Manhole - Surrounded by Soil Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 48 of 53
Question Response
SITE
Drainage System for Soil Inspected
Catch Basins/Manhole - Surrounded by Soil Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Soil Covering Does not Exist
DRINKING FOUNTAINS Does not Exist
FENCES Inspected
Condition 4 - Between Fair and Poor
Deficiency WROUGHT IRON: MISSING SECTIONS
Deficiency Location/Instance MacDonough Street
Deficiency Quantity 80
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
MacDonough Street
Violations No violations recorded.
Deficiency WROUGHT IRON: RUST - MAJOR
Deficiency Location/Instance Lewis Avenue
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Lewis Avenue
Violations No violations recorded.
Deficiency CONCRETE CURB: DAMAGED/DETERIORATED
Deficiency Location/Instance MacDonough Street, Decatur Street, Schoolyard
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 49 of 53
Question Response
SITE
FENCES
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
MacDonough Street
Violations No violations recorded.
Deficiency WROUGHT IRON: DAMAGED/DETERIORATED
Deficiency Location/Instance MacDonough Street, Decatur Street
Deficiency Quantity 360
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Decatur Street
Violations No violations recorded.
IRRIGATION SYSTEM Does not Exist
PAVING Inspected
Student Non-Use Inspected
Gravel Exists? No
Asphalt Does not Exist
Concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Pavers Does not Exist
Student Use Inspected
Gravel Exists? No
Asphalt Inspected
Condition 4 - Between Fair and Poor
Deficiency CRACKS - MAJOR
Deficiency Location/Instance Schoolyard
Deficiency Quantity 1,000
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 50 of 53
Question Response
SITE
PAVING
Student Use
Asphalt
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Schoolyard
Violations No violations recorded.
Concrete Does not Exist
Pavers Does not Exist
Site Sidewalks & Walkways Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 3 - Fair
Deficiency CRACKS - MAJOR
Deficiency Location/Instance Along Park, by Exit 8
Deficiency Quantity 425
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Along Park
Violations No violations recorded.
Pavers Does not Exist
DOT Sidewalk Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 51 of 53
Question Response
SITE
PAVING Inspected
DOT Sidewalk
Pavers Does not Exist
PLAYGROUNDS Does not Exist
PLAYING SURFACE Does not Exist
RETAINING WALLS Inspected
Are there any Retaining Walls 6' OR higher facing publicstreet/sidewalk?
No
Condition 2 - Between Good and Fair
Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR
Deficiency Location/Instance Schoolyard
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Schoolyard
Violations No violations recorded.
SEATING Inspected
Benches Inspected
Concrete Inspected
Condition 5 - Poor
Deficiency CRACKS/SPALLING - MAJOR
Deficiency Location/Instance Schoolyard
Deficiency Quantity 8
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Schoolyard
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 52 of 53
Question Response
SITE
SEATING Inspected
Benches Inspected
Metal/Wood/Plastic Does not Exist
Bleachers Does not Exist
SITE WALLS (NOT RETAINING WALLS) Does not Exist
STAIRS/RAMPS: EXTERIOR Does not Exist
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K035
PB/A&W Print Date: 6/21/2019Page 53 of 53