Providing indoor climate comfort
@DNOVA - THX
Application guide
@DNOVA-THX-AGU-0907-E
Application Guide @DNOVA-THX-AGU-0907-E - Page �
Due to LENNOX on going commitment to quality, specifications subject to change without notice and without incurring liability
Our products comply with the European standards.
The manufacturing @DNOVA units answers to ISO 9001 control quality system. A copy of the certificate can be get on request.
APPLICATION GUIDE
TABLE OF CONTENTS
Ref : @DNOVA-THX-AGU-0907-E
Lennox have been providing environmental solutions since 1895, our range of @DNOVA continues to mee the standards that have made LENNOX a household name. Flexible design solutions to meet YOUR needs anduncompromising attention to detail. Engineered to last, simple to maintain and Quality that comes as standard.Information on local contacts at www.lennoxeurope.com.
All the technical and technological information contained in this manual, including any drawing and technical descrip-tions provided by us, remain the property of Lennox and must not be utilised (except in the operation of this product), reproducted, issued to or made available to third parties without the prior written agreement of Lennox.
1. THX : DESIGN AND TECHNOLOGY 02
2. FEATURES AND BENEFITS 03
3. CONFIGURATION DIGIT 04
4. MANUFACTURING SPECIFICATIONS 05 5. CONTROL SOFTWARE AND HARDWARE 09
6. LIST OF MAIN OPTIONS 10
7. TESTS AND REFERENCE STANDARDS 128. TECHNICAL DATA 13 9. DIMENSIONAL DRAWINGS 14
Page � - Application Guide @DNOVA-THX-AGU-0907-E
THX : DESIGN AND TECHNOLOGY
THX = Design & Technology
THX unitTheunitsoftheseriesTHX.LennoxTelecomunitsWallmounted.are tobeusedfor theconditioningofsmallandmediumsizedtelecommunicationstransceiverstationsorswitches.
Wall mountingThemachinesaredesigned foranoutdoorwallmountingwithPlug&Playlogic,toreducetheinstallationtimesandtheneedofspecific professional skills in the installation step.
Direct expansionTheTHX units are single-block conditioners with direct expansion andaircondensation.Theinnovativesystemofaircirculationem-bodies a significant improvement of the performances in different thermalloadconditions.
Reduced noise levelThe use of innovative axial fans with 6-pole backward curved blades, together with a Scroll-type compressor and a cabinetdesign eliminating every source of inner sound reflection and vibrations,makes this equipment suitable especially for city areas.
Minimized pressure dropThewholerecirculatingandFree-Coolingsectionhasbeende-signedtolimitthepressuredrop(airside)andtomaximizetheunitperformance;forthisreason,theTHXunitsarefeaturedbythe exclusive equipment with backward curved blade centrifugal fans(Plugfans),thewidesurfacesoftheevaporatingcoilsandof the intake grilles, in line with the supply standard of the main phonecompanies.
StructureThe unit supporting structure is made of thick galvanized sheet, while theouterpart is inaluminumalloy5005 (standard)or inpaintedgalvanizedsheetmetalRAL9002(optional).Itisfeaturedbyroundedshapeedges,accordingtoinnovativestyletrendsandtheaccidentprevention.Allstructuredetailsareentirelyprodu-cedin-housewithautomaticprocessesintegratingtheCAD-3Ddesigning(solidmodeller)withtheproductionprocess(CAM)=CAD-CAM.
PanellingAllouterpanelsarefastenedusinganti-vandalscrewsTORX®,while the front ones are equipped with handles for an easy removal forinspections.Theunitmaintenancecanbefullymadefromthefront, includingthe innovativeextractabledampersection.Thisenables a unique flexibility, with unit ."On Site Upgrading".and the possibilitytoaccessandcleanthecondensatecollectingtray.
Power suppliesAllunitsareavailablewithdifferentsupplyvoltages,withtheoptionofdoublepowersupply.Inthiscaseit ispossibletohavea48vdcor24Vdcsolutionfortheair-conditioningcontrol,evenincaseofpowerfailure.
European directivesTheTHXunitsaredesignedandmanufacturedaccordingtotheEuropean directives currently in force, and are consequently marked CE.
Application Guide @DNOVA-THX-AGU-0907-E - Page �
FEATURES AND FORTES
Features and fortes
Design vs. Technology?TheTHXunitsintroduceanewplantmodelfeaturedbyapleasantdesignmatchedwitharationalarrangementofthecomponentsandanexcellentassemblycompactness.Thesingle-compressorunit reduceddimensionsenable to install twounitsona2.20-mwall,asforthesheltersincludingtheministationsforwirelesstelephony.ThespecialLennoxconceptofSFT.SideFree-CoolingTechnology.enablestoreacharealoperationunderpartialloadconditionswithpossiblesimultaneousmechanicalcooling,evenwhenthetwounitsoperatetogether.Thetwo-compressorseries.2.matchesthesafetyofthetwomachineswiththeinexpensivenessofthesingleunit,withapowerrangecoveringabout80%oftheinstalled.Allunitsarefactorytestedbyusingautomaticsystemsbasedonobjective.in-out.criteriaandarereadytobeinstalledandstartedbysimplewiringonsite.
Start-UpThe holes arranged on the rear flange enable the machine/s wall-mounting;thecondensatedischargeistobearrangedandthepowersupplyistobeconnected.Incaseofunitswiththree-phasemain supply, check the phase correct sequence (the indicator on the phase sequence relay in the electric board switches on): in case of wrong sequence, themP control records an alarmand doesnotenablethecompressorstart.Thestartingprocedureisoperated by pressing the key .ON. on the control keyboard.
HandlingThe THX units can be handled by fitting belts under the base and paying attention to make them pass through the supplied anti-tilting eyebolts,fastenedintheuppersidepart.
Noise levelsTheTHX unitsincludetheexclusiveuseofventilationsolutions,featured by a low emitted noise level making these conditioners compatiblewithcityinstallations.Thesupportstructure,thepanelsandthefasteningsystemsaredesignedtoreducevibrationsandtheir transmission as low frequency sound emissions as much aspossible.
Energy efficiencyThe highest possible energy efficiency has been the maintargetinthewholethermo-dynamicandaeraulicdesigning.Therefrigerating circuit is featured by the use of .rolling piston. or.Scroll.compressorswithtopreliabilityand(optional)possibilityof replacing the traditional lamination component with anelectronically-controlled electric valve: this brings a reduced energyconsumptionby50%whentheoutertemperaturelowersbelow20¢XCand,aboveall,whenthedirectfree-coolingisnotpossible.Theaerauliccircuit implies theuseofcentrifugal fans
with backward curved blades, featured by a very high reaction degree,itisthuspossibletoremovethescrollandtherelevantenergylossesinthedynamic-staticalconversion;allusedfanscan be equipped with .brushless. motor with permanent magnets andrelevantswitchingelectronics,thatcanbedirectlypoweredbyanemergencymainsat48Vdcor24Vdc.Inthiscase,thedc motor efficiency matches with the fan efficiency, thus reaching outstanding energy results (over 45%). The SFT® conceptdevelopedbyLennoxachieves,aswellasexceptionalaeraulicperformance,atrueexploitationeventogetherwiththemechanicalcycle: this contributes remarkably to reduce energy costs in the rangeofoutertemperaturesbetweentheinnersetpointandTFT(TotalFree-Coolingtemperature).
Emergency situationsAll units can be equipped with dual supply, main supply and "dc" supply.
• Main supply:-Compressor-Heating-Condensingsectionfan
• 24 V dc or 48 V dc supply:-evaporatingsectionfan-Microprocessor-Damperservomotor
In caseofmains failure,a voltagepresence relaysignals thisto the "mP" control that, together with the ventilation and Free-Cooling section, continues to be powered by back-up batteries. Thisensurestheair-conditioningcontrolevenwithpossibleinnertemperaturevariationsfromtheset-pointvalues.ManufacturingfeaturesAllelectric,aeraulicand refrigeratingcomponentsareassembledinsidethemachinecabinetandcannotbeaccessedfrom outside, without removing the panels.All removablefasteningsby.AVAScrews.needspecialtools(optional)fortheirremoval.Themachinehasamin.protectiondegree IP44andtheprotectiongrillesoftherotarypartscomplywiththeaccidentpreventionsectionofthenormsEN60335;asoption,afurtherprotectinggrilleforthecondensingsectionfanfrontisavailable.
UpgradingTheTHX seriesisdevelopedontwodimensional.frames.only,inthesingle-compressorversion,andonasingle.frame.inthetwo-compressorversion.Thisenablestheupgradingofthebasicradiostationsduetotheimplementationofnewtransmissionstandards,andthereforetotheincreasedinnerthermalload.
Page � - Application Guide @DNOVA-THX-AGU-0907-E
THX0 045 1 H123456789
0 230 V / 1 Ph / 50 Hz1 230 V / 1 Ph / 50 Hz + (24 V dc)2 230 V / 1 Ph / 50 Hz + (48 V dc)3 230 V / 1 Ph / 50 Hz + (230 V / 1~ / 50 Hz)4 400 V / 3 Ph + N / 50 Hz5 400 V / 3 Ph + N / 50 Hz + (24 V dc)6 400 V / 3 Ph + N / 50 Hz + (48 V dc)7 400 V / 3 Ph + N / 50 Hz + (230 V / 1~ / 50 Hz)ABC0 R407C12 R2234 R134a5
6DE01FGH012789KLMNPQ125
CONFIGURATION DIGIT
Confiuration DIGITS
Family: Lennox Telecom Wall mounted
Refrigerant capacity"KW x 10"
1 - Supply + (Auxiliary)
2 -Check BASIC(withlocaluserterminal)-[CarelìAC]ADVANCED(withoutterminal-local)-[CarelpCO2]ADVANCED(withbuilt-interminal)[CarelpCO2]
3 -Refrigerating cycle optionsR407C + electronic thermal expansion valve
R22 + electronic thermal expansion valve
R134a + electronic thermal expansion valveOther
4 -Cabinet options AluminumPeralumanAlloy5005Paintedgalvanizedsheet
5 -Electric re-heating Heaters-NOHeaters-YES
6 -Free-Cooling WithoutFree-CoolingModulatingFree-Cooling0-10VFree-Coolingwithspringreturn
7 -Air filtration G2Filter(Std.)G3FilterG4FilterG2 Filter + Clogged filter sensorG3 Filter + Clogged filter sensorG4 Filter + Clogged filter sensorOther
8 -Condensation control WithoutcondensationcontrolOn / OffModulatingwithpressuretransducerModulatingwithtemperatureprobeFlooding-type
9 - Serial communication options SerialcardRS232ModemSerialcardRS485Free"-1-" only for ADVANCED control
Application Guide @DNOVA-THX-AGU-0907-E - Page �
mANUFACTURING SpECIFICATIONS
Recirculation air filtrationThe filter is located upstream the evaporating coil and can be easily extracted by removing the front panel dedicated to the filter/damper section. Thanks to its position, it filters both the recirculation and the fresh air in case of Free-Cooling: in the latter case, on the fresh air ejection section, a metal filterprevents the nesting inside the containerofsmallanimalsorinsects.Thewashablesynthetic-typefiber filter, with efficiency EU2, is installed in a galvanized sheet frameforaneasymaintenance.
Condensing section fanTheaxial-typeusedfans,withwing-shapedblades,arefeaturedbyahighcoveringdegree.Allused6-polemotorslimitthesoundemissions, and are outer rotor type to improve the energy effi-ciencyandreducethemagneticnoisewhentheyareadjustedwithphasedisconnectingdevices(optional).
Condenser with finned packWith dimensions 25x21.65 and a 3/8. pipe it is composed of 0.10-mm thick aluminum fins and copper pipes expanded on the sameforacompletecontact.Thedesigncriteriaprivilegesthefrontsectionwiththeadvantageofreducedlossesontheairside,sothat it ispossibletouse6-polefanswithminimizedemittedsound power. The condensing coil can be equipped with a metal filter that can be easily removed fromone of themachine sides: this doubleaccessenablesthemaintenanceevenincaseofdoubleinstallationonthecontainerwall.
Electric board
Itislocatedinaseparatecabinethidden on the back side by the recirculationairbeforeitiscoo-led by the evaporating coil : this aspectisextremelyimportantforboththecomponentcoolingand,atthesametime,forpreventingthecondensationonthebottomside of the board.All on-board systems comply with the EECDirective "Low tension 73/23" and with the related norms. The accesstotheelectricboardispossiblewithoperatingunitasitis completely separated from the air flow; the protection degree withopenpanelisIP20.
Manufacturing specifications
StructureTheTHX seriesunitsarededicatedtotheoutdoorusewithtem-peratures rangingbetween .20°C(undercondensationcontrol)and +45°C. The entire inner structure is made up of hot electro-galvanized sheet with high thickness, and the outer paneling is in smooth 5005 aluminum alloy or, upon request, in galvanized sheet paintedwithepoxy-polyesterpowdersRALxxxx,oven-curedat180°C.Ifpainted,thecolouroftheunitsdependsonthecustomer.s specifications for re-order batches of more than 20 pieces. The innovativeglobaldesignofthemachineenablesacompletefrontaccessibility whereas the outstanding possibility of extracting/fitting thedamperfromthefrontoffersthedoublechanceofupgradingonsiteofthemachinesoriginallywithouttheFree-Coolingoption,and itoffers theaccessibility to theevaporatingcoilandto thecondensatecollectiontray,too.
Refrigerating circuitTherefrigeratingcircuit isentirelyinhousemanufactured, using welders certified accor-ding to the Directive PED 97/23 on pressuri-zedcontainers,andallrelevantcomponentsare certified according to the same directive. Theexclusiverotaryorscroll-typeusedcom-pressors are available in the version for fluids typeHFC(R407C;R134a);forthenon-EECcountries signing theMontrealProtocol, inthe version with HCFC R22.The machinestandard equipment includes a thermostatic lamination valve and a vacuum start device: thisdeviceisenclosedintheScrollcompressororisoutsideinthe versions with single-phase rotary compressor/s. The circuit is completed with anti-acid dryer filter with molecular sieve, a flow indicator and pressure intakes for the maintenance and/or inspectionoperations.
Evaporating section fan
TheTHX units are fitted with centrifu-gal-type fans, with (tilted) backward curved blades and single intake. These fansare featuredbydivergingbladeducts and by a high outer diameter/in-nerdiameterratio,enablingtoachievean outstanding aeraulic efficiency; fur-ther,ahighoutputspeedandthereforealaunchoversevenmeterscanbereachedthroughtheirpositiontowardsthedeliverygrille.All machines can be equipped with fans powered by brushless motorswithpermanentmagnets,dcsuppliedat48Vor24V,andinthiscase,combinedwiththeADVANCEDmicroprocessor.Therefore,itispossibletopilotdirectlytherotatingspeedsuitingit to the different operating conditions, such as: de-humidification, energysaving,etc.
Finned pack evaporatorWith its dimensions 25x21.65 and a 3/8. pipe it is composed of 0.10-mm thick aluminum fins and copper pipes expanded on the sameforacompletecontact.Thedesigncriteriaprivilegesthefrontsectionwiththeadvantageofreducedlossesontheairside,whilethe exchange surface is sized so as to avoid de-humidification at theprojectratedconditions.Thecondensatecollectiontraycanbeaccessedfromtheunitfrontforcleaning,andcanbeingalvanizedsheetor,asoption,inausteniticstainlesssteelAISI304L.
Page � - Application Guide @DNOVA-THX-AGU-0907-E
RS485
Modbus® RS485
BACnettTM RS485
LonWorks® RS485
Trend RS485
Tcp / Ip RS485
GSM
RS485
Modbus® RS485
BACnetTM RS485
LonWorks® LONRS485
Trend
Tcp / Ip RS485
GSMRS232
mANUFACTURING SpECIFICATIONS
PackingThe THX units are packed on wooden pallet with anti-shock cardboardanglesand upper protection in cardboard/polystyrene. In the end, the whole packing is wrapped with protection transparent polythene film.
InterconnectivityAllunitscanbeconnectedwithremotesupervisionsystemsbytheuseof.Gateway..Whenusingthe.mP.controlofthe.ADVANCED.type,thereisthepossibilityofpilotingdirectlyaGSMmodemabletosendandreceiveSMSmessages.
Application fieldThe machines have been designed to operate with outdoortemperatures "oT" up to +45°C and indoor temperatures "iT" rangingbetween18°C -R.H. 40%and35°C -R.H. 50%.Fortheapplicationswithlowoutdoortemperature,thecondensationcontrol is required: -AbsentforoT>20°C -Modulatingfor-20°C<oT<20°C -Flooding-35°C<oT<-20°CUptomax.6unitscanbeconnectedforthestand-by.rotationcontrol, with mP BASIC, in LAN (Local Area Networking), while uptomax.15unitscanbeconnectedwithADVANCEDtypemP,sharingtheoperatingparametersandenablingthestand-byro-tationandre-startoftheinstalledmachines.Indoortemperaturefrom 21_C (fromR.H. 30% to R.H. 80%) to 32_C (R.H. 40%)withoperatingcompressor.Refer to theperformance table foreachmodel (Tab.4,Page13).The interconnectionpossibilities,accordingtocontroltype,aresummarizedinthetwotablesbelow(Tab.1andTab.2).
PROTOCOL SERIAL CARD GATEWAY NOTES
ProprietaryCarelNotnecessary RS485 network connectionRS485 / RS232 converter (PC485KIT) ConnectionwiththesupervisionPC
GatewayModbus® RS485 network connection
GatewayBACnettTM RS485 network connection
GatewayBACnettTM RS485 network connection
GatewayBACnettTM RS485 network connection
Gateway TCP / IP Ethernet network connectionRS485controllocalnetwork PlantWatch + GSM modem PlantWatchoperatesasconcentrator
Tab.2 - mP BASIC
PROTOCOL SERIAL CARD GATEWAY NOTES
ProprietaryCarelNotnecessary RS485 network connectionRS485 / RS232 converter(PC485KIT)
ConnectionwiththesupervisionPC
Notnecessary RS485 network connection
GatewayBACnettTM RS485 network connection
Notnecessary Forthededicatedprogramming,contactLEN-NOX
Trendserial Notnecessary Forthededicatedprogramming,contactLEN-NOX
Gateway TCP / IP Ethernet network connection
GSMmodem Forthededicatedprogramming,contactLEN-NOX
RS485controllocalnetwork PlantWatch + GSM modem PlantWatchoperatesasconcentrator
Tab.1 - mP ADVANCED
Application Guide @DNOVA-THX-AGU-0907-E - Page 7
12
3
4
5
6
7
8
mANUFACTURING SpECIFICATIONS
Fig.1 - Machine Main Units
Tab.3 - Machine Main Units
RE. DESCRIPTION
1 Compressor
2 Condensingsectionfan
3 Free-Coolingdamper
4 Air filter
5 Electricboard
6 Evaporatingsectionfan
7 Evaporator
8 Condenser
Page � - Application Guide @DNOVA-THX-AGU-0907-E
mACHINE FUNCTIONAL SCHEmES
Machine functional schemes
Fig.2 - MECHANICAL COOLING Fig.3 - FREE COOLING
Fig.4 - MODULATING FREE COOLING Fig.5 - AIR FLOW IN COMBINED OPERATION
Delivery air
Recirculation air
Free cooling-air
Condensation air
Indoor
Outdoor
Indoor
Indoor
Outdoor
Outdoor
Application Guide @DNOVA-THX-AGU-0907-E - Page 9
CONTROL SOFTwARE AND HARDwARE
Control software and hardware
BASIC [Carel ìAC] + ADVANCED [Carel pCO2]The THX units can be sup-pliedwithtwomicroprocessorcontrol levels :
• BASIC with user interface4x20LCD
•ADVANCED : optional confi-guration: with built-in display 4x20LCD
FortheADVANCEDcontrols,aremotedisplayisavailable,too,andcanbepositionedupto200m farwithasimpleplug-inconnectionwithphone-typecable.Allmicroprocessors,BASIC,ADVANCEDandADVANCEDwithbuilt-indisplay4x20LCD,enabletocontrolcompletelytheunits,such as :
•Sensors- room temperature to keep the inner set-point-outertemperaturetopilottheFree-Coolingdamper- delivery temperature to prevent the risks of thermal shocks of the room electronic equipment-condensingpressure(optional)-evaporatingpressure(optional)
•Functions-roomtemperaturemanagement-readingoftherelativehumidity(optional)-controloftheairoutletmin.temperatureintheenvironment- control of the air de-humidification by reducing the fan speed(withoptionalsensorandwithoptionaldcfans)
-heating(optional)- alarm control equipped with clean contacts for the remote connectionsofvisualandsoundsystems-stand-bymanagementoftwounits.TheLANconnectionbytheADVANCEDmicroprocessor,ensuresotherfunctionssuchasSMART,Free-Cooling,modemsharing,etc.-cleancontactsforeveryothertypeofalarm(optional)-fromthemicroprocessoritispossibletoselectthe automatic restart after a voltage lack-min.timebetweentwocompressorstart-ups-remoteinterface,upto200m,directlyconnectedusingaLANconnection(formPADVANCED)-possibilityofconnectingtheunitwithasupervisionsystem(optional)- 2 password levels to access the unit configuration- clock card for recording the even date and time-hour-countertoenableascheduledmaintenanceofthefans, compressors and filters-automaticswitchingbetweentwocompressorsforeachunitwithdoublerefrigeratingcircuit.Thealgorithmcanbeselectedtoachievethe.oneinoperation.oneinstandby.strategyortoachieveabalancedoperating timebetween twocircuits.Thesecondcircuit,too,isstartedwhenexceedingthepresetset-pointtemperature,independentlyfromtheselectedcontrolstrategy.
Note : the ADVANCED control is available for all units with double circuit, only.
mP ADVANCED [Carel pCO2] technical data
• Flash memory: ........... 1MByteexpandableto16MByte• RAM memory: ............ 256 kByte expandable to 1 MByte• Parameter memory: ... 2 kByte• Analog inputs: ............. B4 - B5 = two inputs for NTC probes (-50 ÷ 100°C), PT1000 (-100 ÷ 200°C) / clean inputs B1 - B2 - B3 = three inputs for NTC probes (-50°C ÷ 100°C); voltage 0 ÷ 1 V dc / 0 ÷ 10 V dc current 0 ÷ 20 mA / 4 ÷ 20 mA• Analog outputs: .......... Y1 - Y4 = four opto-insulated outputs 0 ÷ 10 V dc, max. load 10 mA (1 k )• Digital inputs: .............. ID1 - ID8 = eight opto-insulated inputs 24 V ac 50/60 Hz / 24 V dc• Digital outputs:............ No.1÷No.8=electro-mechanicalrelays
mP BASIC [Carel ìAC] technical data
• Analog inputs: ............. B1 - B2 - B4 = three inputs for NTC temperature probes (10 k .a25°C) B3 = one input for humidity/pressure probe (0 ÷ 1 V dc / 4 ÷ 20 mA) + V = probe supply output(14Vdc,30mAmax.)• Analog outputs:........... Y1 = output 0 ÷ 10 V dc, not opto-insulated, referred to the supply potential G0, max. load 10 mA (1 k ).) Y2=phasedisconnectionoutput• Digital inputs:............... ID1-ID10=tennon-optoinsulatedinputsreferredtothesupplypotentialG0,supplied with24Vac,currentabsorbedbyeachinput6.5mAat24Vac• Digital outputs:............ OUT1-5=5SSR,24Vac,1A,withmin.current20mA OUT6-C6=1relay,220Vac OUT7-C7=1relay,220Vac
Page �0 - Application Guide @DNOVA-THX-AGU-0907-E
LIST OF mAIN OpTIONS
1 - ADVANCED microprocessorProgrammablemicroprocessor with 16bit and high performan-ces. 2 - Air differential pressure switch 3 - Double supply
• AC main supply from the mains:- compressor/s- fan/s of the condensing section-heating
• Auxiliary supply 48 V dc (24 V dc, upon request):-microprocessor-evaporatingsectionfan-damperservomotor
Note :it is possible to activate the fan speed control to enable the coil energy saving during its operation.
SFT® "Side Free-Cooling Technology"TheinnovativeFree-Coolingsystemenablestoreachoutstandingefficiency levels, above all when operating simultaneously with the mechanical cooling: this situation, in many central European climateareas,representsover50%oftheyearlytotalhours. 4 - Refrigerant R134aFor extreme outdoor conditions up to +55°C. 5 - Free-Cooling with damperThanks to the unit designing principle, it is possible to carry out the .upgrading on site. on the units not equipped with the Free-Coolingoption
6 - ETV--T “Electronic Thermostatic Valve Technology”ForapplicationswherethedirectFree-Cooling is not possible.This solutionenablestoreducetheenergyconsump-tionupto50%comparedtothestandardunits when the outdoor temperatureis below 20°C.The damper is furtherdesigned to be integrally extracted,thusenablingacompletemaintenancepossibilityaswellastheaccesstothecondensatecollectiontray. 7 - Humidity sensorFortheenthalpiccontrolintheFree-Coolingsituations(combinedwiththemPADVANCEDcontrol). 8 - Condensation control 9 - Interconnectivity
• Serial port:-RS232-RS485
• Communication protocol:-Carel-Modbus©
- LonWorks®
-BACnettTM
-TCP-IP- GSM modem (complete management through SMSServices).
TheTHXdesigningconceptenablestheupgradingonsiteofunitsnot equipped with the Free-Cooling option; this is important in such cases where it is necessary to have a unit stock at disposal.The temperature sensors installed at delivery, intake and fresh air control completely the damper, improving its energy efficiency and avoiding the risk of inlet air at temperatures lower than the limit allowed by the electronic equipment. In case of combination with DUAL supply, mains + dc UPS, the Free-Cooling can enable tocontroltheclimateeveninemergencysituationsand,ifthetwounitsarereciprocallyconnected,itcanimplementallstrategiesforavoidingtolosethecontroloftheinnersetpointofthecontainer(see Fig. 6).
Fig.6 - SFT® operating diagram
Coolingcapacity
Truecontainerthermal requi-rement
Free-cooling : capacity of oneunit
Free-cooling : capacity of twounits
RoomSetpoint
Roomairtem-perature
FFT1 FFT2
Application Guide @DNOVA-THX-AGU-0907-E - Page ��
LIST OF mAIN OpTIONS
Damper servomotor with spring returnItpositions thedamperscompletelyopenorcompletelyclosedat the customer's choice in case of power lack: with an operation signal connected with a fire alarm, the damper is usually positio-nedclosed,toenabletheoperationoftheautomaticswitching-offsystems. This option must be defined at the order.
Clogged filter sensorThis differential pressure sensor detects the filter clogging and generatesanalarmdisplayedbythemicroprocessorcontrol.
HeatingItisperformedbyusingheatersinextrudedaluminum,withhighthermal exchange surface: this aspect enables to match reduced thermalinertiaswithreducedsurfacetemperatures,totheadvan-tageofafullusesafety.Eachheatingelementisprotectedbyasafetythermostatdirectlyactingonthesupply.
Outer panelingThe standard supply includes panels in aluminum-magnesiumalloy5005, representing thebestsolution for the resistance toweather agents and for limiting the unit weight: the weight reduction vs. the version in painted galvanized sheet is averagely 32 kg.Surface treatments on finned coilsAn efficient protection against corrosive agents is guaranteed by thecopper-copperversion,thecataphoresisprotectionandtheuse of hydrophile pre-treated aluminum: the protection grade is reportedinthementionedorder.RefrigerantsAccording to the norm EEC 2037/00, the HTW units can operate with :
•HFCR407Casstandard•HFCR134a(optional)•HCFCR22Exportnon-EEC in thecountriessigning theMontrealprotocol
The unit is supplied: tested and ready to be started up on the site.AlarmsItreportshighandlowpriorityalarmsoncleancontacts.IncaseofADVANCEDmicroprocessor,itispossibletohaveasubdivisionofthealarmtypeintheterminalboardoftheelectricpaneland,generally,itispossibletoarrangeCustomsolutionsaccordingtothedifferentsupplystandardsofthephonecompanies.Air distribution grillesThewall-mountedairdistributionsgrillesaremadeofextrudedaluminum, with single row of adjustable fins and accident-preven-tionprotectionnetonthedelivery.IncaseofFree-Coolingunit,afurthernetisarrangedontheairoutlettopreventtheunwishedentry of small animals and/or insects.
Page �� - Application Guide @DNOVA-THX-AGU-0907-E
TESTS AND REFERENCES STANDARDS
Tests and Reference StandardsSafetyTheTHX unitshavebeendesigned,manufacturedand testedaccording to the directives of the European Union : • 98/37/EC (former 89/392/EEC, 91/368/EEC, 93/68/EEC) • 89/336/EEC • 73/23/EECElectric boardsTheelectricboardscomplywithEN60204-1.Electro--magnetic compatibilityTheTHX unit complies with the following EMC standards:
• EN 50081-1, Emissions (.Generic emission standard,Part 1: residential, commercial and light industrial., January 1992)• EN 50082-2, Electro-magnetic compatibility (.Genericemission standard, Part 2: industrial environment., March 1995)
ConformityEach THX unit is supplied complete with test certificate and conformity certificate according to the Directives of the European Union.The units are .CE. marked.
Application Guide @DNOVA-THX-AGU-0907-E - Page ��
@DNOVA HTX 0451 0561 0731 0901 1051 1201 0902 1102 1302
As-hrae R407C
W 4500 5600 7300 8900 10150 11950 9100 10800 13200
V-n-f 230/1/50 400/3/50
V-n-f - 400/3/50 400/3/50 230/1/50
V-n-f230/1/50
+230/1/50
400/3/50+
230/1/50
V-n-f230/1/50
+VDC
430/3/50+
VDC
230/1/50+
VDC
430/3/50+
VDC
V-n-f -430/3/50
+VDC
430/3/50+
VDC
230/1/50+
VDC
430/3/50+
VDC
230/1/50+
VDC
W 1390 1880 2520 2960 3490 4350 2780 3650 4700
A 6,4 8,8 11,6 15,6 17,2 20,6 13,1 17 10,7
A 13,2 14,5 16,5 21,8 26,7 28 26 28,8 13
A 36 49 63 81 104 117 43 52 41
W 108 108 310 470 470 470 230 230 230
m3/h 1450 1450 2150 3020 3020 3020 2800 2800 2800
m3/h 1320 1320 1980 2810 2810 2810 2650 2650 2650
°C 16,8 14,4 16 17,6 16,9 14.05 16,8 15,1 12,5
EU2 EU2 EU2 EU2 EU2 EU2 EU2 EU2 EU2
dB-A 69 70 70 71 71 71 72 72 72
dB-A 42 43 43 44 44 44 45 45 45
Rotary Scroll Scroll Scroll Scroll Scroll Rotary Scroll Scrol
1 1 1 1 1 1 2 2 2
1 1 1 1 1 1 2 2 2
dm3 0,44 1 1 1,1 1,1 1,1 0,44 1 1
m2 0,3 0,3 0,3 0,38 0,38 0,38 0,37 0,37 0,37
m2 0,36 0,36 0,36 0,56 0,56 0,56 0,55 0,55 0,55
m3/h 3450 3350 3350 5100 5100 4800 5100 5100 4800
1 1 1 1 1 1 2 2 2
mm 1580 1580 1580 1630 1630 1630 1630 1630 1630
mm 804 804 804 999 999 999 1130 1130 1130
mm 498 498 498 596 596 596 596 596 596
kg 93,5 101,5 112,5 142,5 146,5 154,5 160,0 175,0 179,0
TECHNICAL DATA
Cooling mode
Refrigerant
Cooling Capacity @27°/40%, 35°
Standard Power Supply
Power Supply (Option 2)
Power Supply (Option 3)
Power Supply (Option 4)
Power Supply (Option 5)
Electrical dataTotal Absorbed PowerTotal Absorbed CurrentFLALRAIndoor Fan(s) absorbed Power in 230/1/50 executionIndoor Fan(s) absorbed Power in 48 V DC execution (optional)VentilationIndoor Air Flow
Indoor Air Flow during FreeCooling Operations @ 40 Pa
Full Free Cooling TemperatureFiltrationAcousticSound Power LevelSound Pressure Level @10 meters in Free FieldRefrigeration circuit
Type of compressor
Number of refrigerating circuitsNumber of compressorsOil charge per compressorIndoor Coil Front SurfaceOutdoor Coil Front SurfaceCondenser Air FlowNumber of condenser’s fanDimensions and WeightOverall dimensions: height HOverall dimensions: length LOverall dimensions: depth DWeight
Technical data - @DNOVA - HTX
FLA : Max.operating current LRA : Pick-up current
Page �� - Application Guide @DNOVA-THX-AGU-0907-E
DImENSIONAL DRAwINGS
Dimensional drawings : mod. THX 0451 - 0561 - 0731
Side viewFront view
Top view
Application Guide @DNOVA-THX-AGU-0907-E - Page ��
DImENSIONAL DRAwINGS
Dimensional drawings : mod. THX 0901 - 1051 - 1201
Page �� - Application Guide @DNOVA-THX-AGU-0907-E
DImENSIONAL DRAwINGS
Dimensional drawings : mod. THX 0902 - 1102 - 1302
www.lennoxeurope.com
www.lennoxbelgium.com
www.lennoxczech.com
www.lennoxfrance.com
www.lennoxdeutschland.com
www.lennoxnederland.com
www.lennoxpolska.com
www.lennoxportugal.com
www.lennoxrussia.com
www.lennoxdistribution.com
www.lennoxspain.com
www.lennoxukraine.com
www.lennoxuk.com
www.lennoxdistribution.com
@DNOVA-THX-AGU-0907-E
BELGIUM, LUXEMBOURG
CZECH REPUBLIC
FRANCE
GERMANY
NETHERLANDS
POLAND
PORTUGAL
RUSSIA
SLOVAKIA
SPAIN
UKRAINE
UNITED KINGDOM AND IRELAND
OTHER COUNTRIES
Due to Lennox’s ongoing commitment to quality,
the Specifications, Ratings and Dimensions are
subject to change without notice and without
incurring liability.
Improper installation, adjustment, alteration,
service or maintenance can cause property
damage or personal injury.
Installation and service must be performed by a
qualified installer and servicing agency.