Appendix E – Room Data Sheets - Home -...

53
ADAMS HOUSE AND TOLLGATE LODGE GP PRACTICE Job Nr 5547 Appendix E – Room Data Sheets

Transcript of Appendix E – Room Data Sheets - Home -...

Page 1: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

ADAMS HOUSE AND TOLLGATE LODGE GP PRACTICE

Job Nr 5547

Appendix E – Room Data Sheets

Page 2: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

1 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

PROJECT:  Adams House Medical Centre          Date: 4th July 2017 

ACTIVITY SPACE DATA SHEET: WAITING AREA 1  

Version: 1          Revision:  

 EQUIPMENT             Group 1  Items to be provided and fixed by the builder e.g. sink, coat hook 

Group 2  Items supplied by Trust and fixed by builder e.g. soap dispenser 

Group 3  Loose equipment taking up significant floor space e.g. bed 

Group 4  Small items of loose equipment e.g. computer, waste bin 

 

                         Group  

1. Anti‐ligature luminaires to CIBSE LG7              1 2. Anti‐ligature luminaires with integral emergency inverter/battery pack. To CIBSE LG7  1 3. Heating via Radiators LTHW                1 4. Fire alarm combined smoke detector/sounder             1 5. 2 No. twin socket outlets at 1800mm. AFFL            1 6. 2 No. data outlet socket at 1800mm. AFFL            1 7. 4 No. twin socket outlets at 450mm. AFFL            1 8. 15 x bench style seating                 3 9. Blinds and tracks                  3 10. anti‐ligature door stops                 3 

   

Page 3: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

2 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

TECHNICAL DATA SHEET  

ENVIRONMENTAL  29ºC db. 50% RH Summer  :   DESIGN  :  NOTES       ‐4ºC sat. Winter     :   DATA    : 

AIR          :      :  Winter Temperature        (degC)  :  18  +/‐ 2c  :  Summer Temperature        (degC)  :   24 +/‐ 2c  : Mechanical Ventilation: Supply      (m3/s)  :       : Mechanical Ventilation: Extract      (m3/s)  :       :  Pressure – Rel. to Adj. Space        :      : Filtration (% Dust Sp Eff & % Arr)      :                    Humidity          (%RH)  :      :  

    LIGHTING        :      : Service Illumination        (Lux)  :  200    : Service Illumination Night      (Lux)  :  200    : Local Illumination        (Lux)  :  NA    : Colour Rendering Required        :  Ra 80    : Uniformity            :  0.4    : Standby Lighting Grade          :  NA    : Lighting Control           :  Manual   : 

    NOISE          :      : Acceptable Sound Level   [ (L10dB (A) ]    :   NR 35    : Speech Privacy Required        :      : Quality which cannot be tolerated      :      : 

    SAFETY          :      : Accessible Hot Surface      Max temp (C)  :  43    : Domestic Hot Water      Max temp (C)  :  41    : 

DESIGN CHARACTER       

Internal Finishes    : Walls (HBN 00‐10 B)         : Floor (HBN 00‐10 A) :   Ceiling (HBN 00‐10 B)         : Heavy duty emulsion               Sheet vinyl             Heavy duty emulsion  

 Windows (HBN 00‐10 D)  : Openable UPVC frame double glazed window with toughened glass (as    

existing).  

  

             

Page 4: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

3 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

PROJECT:  Adams House Medical Centre          Date: 4th July 2017 

ACTIVITY SPACE DATA SHEET: Reception 

 

Version: 1          Revision:  

 EQUIPMENT             Group 1  Items to be provided and fixed by the builder e.g. sink, coat hook 

Group 2  Items supplied by Trust and fixed by builder e.g. soap dispenser 

Group 3  Loose equipment taking up significant floor space e.g. bed 

Group 4  Small items of loose equipment e.g. computer, waste bin 

 

                          Group 1. Luminaires to CIBSE LG7                  1 2. Luminaire with integral emergency inverter/battery pack.          1 3. Heating via Radiators LTHW                  1 4. Fire alarm combined smoke detector/sounder              1 5. Fire alarm repeater panel                  1 6. Entry system intercom                    1 7. Natural fresh air supply system                  1 8. 3 No. single socket outlet at 450mm. AFFL              1 9. 6 no twin socket outlets beneath reception counter worktop          1 10. 3 x receptionist chairs                     3 11. Reception counter, with lowered section for wheelchair users          3 12. Hearing loop                      1 

  

  

Page 5: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

4 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

TECHNICAL DATA SHEET  

ENVIRONMENTAL  29ºC db. 50% RH Summer  :   DESIGN   :  NOTES       ‐4ºC sat. Winter     :   DATA    : 

AIR          :      :  Winter Temperature        (degC)  :   21 +/‐ 2c  :  Summer Temperature        (degC)  :   24 +/‐ 2c  : Mechanical Ventilation: Supply      (m3/s)  :       :              Mechanical Ventilation: Extract      (m3/s)  :      :       Pressure – Rel. to Adj. Space        :       :     Filtration (% Dust Sp Eff & % Arr)      :       : Humidity          (%RH)  :      : 

    LIGHTING        :      : Service Illumination        (Lux)  :  300    : Service Illumination Night      (Lux)  :  200    : Local Illumination        (Lux)  :  NA    : Colour Rendering Required        :  Ra 80    : Uniformity            :  0.6    : Standby Lighting Grade          :  NA    : Lighting Control           :      : 

    NOISE          :      : Acceptable Sound Level   [ (L10dB (A) ]    :   NR35    : Speech Privacy Required        :      : Quality which cannot be tolerated      :      : 

    SAFETY          :      : Accessible Hot Surface      Max temp (C)  :  43    : Domestic Hot Water      Max temp (C)  :  41    : 

DESIGN CHARACTER       

Internal Finishes    : Walls (HBN 00‐10 B)             : Floor (HBN 00‐10 A) : Ceiling (HBN 00‐10 B)         : Heavy duty emulsion             : Sheet vinyl            : Heavy duty emulsion  

Doorsets   Solid core light beech veneer FD30S. 2 x Vision panels. Lever handles and mortice lock with internal thumb turn per door. 2 x kick plates. Overhead door closer 

 

 Windows (HBN 00‐10 D)  : Openable UPVC frame double glazed window with toughened glass (as    

existing). Film applied to window  

   

        

Page 6: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

5 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

PROJECT:  Adams House Medical Centre          Date: 4th July 2017 

ACTIVITY SPACE DATA SHEET:  SERVER  

Version: 1          Revision:  

 EQUIPMENT             Group 1  Items to be provided and fixed by the builder e.g. sink, coathook 

Group 2  Items supplied by Trust and fixed by builder e.g. soap dispenser 

Group 3  Loose equipment taking up significant floor space e.g. bed 

Group 4  Small items of loose equipment e.g. computer, waste bin 

 

                            Group 

1. Luminaires to CIBSE LG7                  1 2. Luminaire to CIBSE LG7 with integral emergency inverter/battery pack.        1 3. Cooling                       1 4. Fire alarm combined smoke detector/sounder              1 5. Natural fresh air supply system                  1 6. 1 No. single socket outlet at 450mm. AFFL              1 7. 9 No. twin socket outlets at 920mm. AFFL mounted in 3 compartment dado trunking    1 

  

  

Page 7: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

6 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

TECHNICAL DATA SHEET  

ENVIRONMENTAL  28ºC d.b. 20ºC w.b. summer  :   DESIGN   :  NOTES       ‐4ºC sat. winter     :   DATA    : 

AIR          :      : Winter Temperature        (degC)  :  22 +/‐ 2c  : Summer Temperature        (degC)  :  22 +/‐ 2c  : Mechanical Ventilation: Supply      (m3/s)  :      : Mechanical Ventilation: Extract      (m3/s)  :      : Pressure – Rel. to Adj. Space        :      : Filtration (% Dust Sp Eff & % Arr)      :      : Humidity          (%RH)  :      : 

    LIGHTING        :      : Service Illumination        (Lux)  :  300    : Service Illumination Night      (Lux)  :  NA    : Local Illumination        (Lux)  :  NA    : Colour Rendering Required        :  Ra 60    : Uniformity            :  0.4    : Standby Lighting Grade          :  NA    : Lighting Control           :      : 

    NOISE          :      : Acceptable Sound Level     [ (L10dB (A) ]  :      : Speech Privacy Required        :      : Quality which cannot be tolerated      :      : 

    SAFETY          :      : Accessible Hot Surface      Max temp (C)  :  43    : Domestic Hot Water      Max temp (C)  :  41    : 

DESIGN CHARACTER       

Internal Finishes    : Walls (HBN 00‐10 B)             : Floor (HBN 00‐10 A) :   Ceiling (HBN 00‐10 B)         : Heavy duty emulsion        Raised anti‐station   Heavy duty emulsion  

Doorsets   : Solid core painted timber door. FD30S. Lever handles and mortice lock with     internal thumb turn. 2 x kick plates. Overhead door closer. 

 

 Windows (HBN 00‐10 D)  : Openable UPVC frame double glazed window with toughened glass (as    

existing). Film applied to window  

  

          

Page 8: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

7 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

PROJECT:  Adams House Medical Centre          Date: 4th July 2017 

ACTIVITY SPACE DATA SHEET:  DISABLED WC 

 

Version: 1          Revision:  

 EQUIPMENT             Group 1  Items to be provided and fixed by the builder e.g. sink, coat hook 

Group 2  Items supplied by Trust and fixed by builder e.g. soap dispenser 

Group 3  Loose equipment taking up significant floor space e.g. bed 

Group 4  Small items of loose equipment e.g. computer, waste bin 

 

                           Group  

1. Patient Call Switch with pull cord and reassurance with local reset (Nurse call) with  infra‐red receiver and external over door indicator.            1 

2. Luminaire                      1 3. Luminaire with integral emergency inverter/battery pack         

  1 4. Heating via Radiators LTHW                  1 5. Doc M Pack comprising wash hand basin with lever mixer tap, close coupled WC pan  

with back rest and grab rails                  1 6. Extract Ventilation system with door transfer grille.               7. Concealed drainage from wash hand basin and W.C.            1 8. 1 x Anti ligature coat hook                  1 9. toilet magazine dispenser                                          2 10. soap dispenser                                                2 11. Unbreakable Mirror 300 x 450                                          1 12. alcohol gel dispenser                               2 13. Paper towel dispenser                    2 14. bin                        4 

  

  

Page 9: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

8 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

TECHNICAL DATA SHEET  

ENVIRONMENTAL  29ºC db. 50% RH summer  :   DESIGN   :  NOTES       ‐4ºC sat. Winter     :   DATA    : 

AIR          :      :   Winter Temperature        (degC)  :   18    : Summer Temperature        (degC)  :   Uncontrolled  : Mechanical Ventilation: Supply      (m3/s)  :      : Mechanical Ventilation: Extract      (m3/s)  :  0.015    :  Pressure – Rel. to Adj. Space        :       : Filtration (% Dust Sp Eff & % Arr)      :      : Humidity          (%RH)  :      : 

    LIGHTING        :      : Service Illumination        (Lux)  :  200    : Service Illumination Night      (Lux)  :  200    : Local Illumination        (Lux)  :  NA    : Colour Rendering Required        :  Ra 80    : Uniformity            :  0.6    : Standby Lighting Grade          :  NA    : Lighting Control           :  N    : 

    NOISE          :      : Acceptable Sound Level     [ (L10dB (A) ]  :      : Speech Privacy Required        :      : Quality which cannot be tolerated      :      : 

    SAFETY          :      :   Accessible Hot Surface      Max temp (C)  :  43    :  Domestic Hot Water      Max temp (C)  :  41    :  

DESIGN CHARACTER       

Internal Finishes    : Walls (HBN 00‐10 B)         : Floor (HBN 00‐10 A) :  Ceiling (HBN 00‐10 B)         : Heavy duty emulsion        Non slip vinyl                    Heavy duty emulsion 

Altro whiterock splasback        

Doorsets   : Solid core light beech veneer double swing door. Lever handles with indicator lock with external emergency access. 2 x kick plates 

 

 Windows (HBN 00‐10 D)  : Openable UPVC frame double glazed window with toughened glass (as    

existing). Film applied to window  

   

        

Page 10: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

9 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

PROJECT:  Adams House Medical Centre          Date: 4th July 2017 

ACTIVITY SPACE DATA SHEET: PATIENT WC 

 

Version: 1          Revision:  

 EQUIPMENT             Group 1  Items to be provided and fixed by the builder e.g. sink, coat hook 

Group 2  Items supplied by Trust and fixed by builder e.g. soap dispenser 

Group 3  Loose equipment taking up significant floor space e.g. bed 

Group 4  Small items of loose equipment e.g. computer, waste bin 

 

                           Group  

1. Patient Call Switch and reassurance with local reset (Nurse call) with  infra‐red receiver and external over door indicator.            1 

2. Luminaire with integral emergency inverter/battery pack.          1 3. Wash hand basin with percussion outlets served from thermostatic mixing  

valve and isolation valves.                  1 4. W.C. with air push button flushing cistern. 5. Natural fresh air supply system                  1 6. Concealed drainage from wash hand basin and W.C.            1 7. 1 x Anti ligature coat hook                  1 8. toilet magazine dispenser                                        2 9. soap dispenser                                              2 10. Unbreakable Mirror 300 x 450                                        1 11. alcohol gel dispenser                               2 12. Paper towel dispenser                    2 13. bin                        4 

  

  

Page 11: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

10 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

TECHNICAL DATA SHEET  

ENVIRONMENTAL  29ºC db. 50% RH summer  :  DESIGN   :  NOTES       ‐4ºC sat. Winter     :   DATA    : 

AIR          :      : Winter Temperature        (degC)  :   18    : Summer Temperature        (degC)  :   Uncontrolled  : Mechanical Ventilation: Supply      (m3/s)  :      : Mechanical Ventilation: Extract      (m3/s)  :  0.015    : Pressure – Rel. to Adj. Space        :      : Filtration (% Dust Sp Eff & % Arr)      :      : Humidity          (%RH)  :      : 

    LIGHTING        :      : Service Illumination        (Lux)  :  200    : Service Illumination Night      (Lux)  :  200    : Local Illumination        (Lux)  :  NA    : Colour Rendering Required        :  Ra 80    : Uniformity            :  0.6    : Standby Lighting Grade          :  NA    : Lighting Control           :   N    : 

    NOISE          :      : Acceptable Sound Level     [ (L10dB (A) ]  : NR 35      : Speech Privacy Required        :      : Quality which cannot be tolerated      :      : 

    SAFETY          :      :  Accessible Hot Surface      Max temp (C)  :  43    :  Domestic Hot Water      Max temp (C)  :  41    :  

DESIGN CHARACTER       

Internal Finishes    : Walls (HBN 00‐10 B)         : Floor (HBN 00‐10 A) :  Ceiling (HBN 00‐10 B)         : Heavy duty emulsion        Non slip vinyl                    Heavy duty emulsion 

Altro whiterock splasback        

Doorsets   : Solid core light beech veneer double swing door. Lever handles with indicator lock with external emergency access. 2 x kick plates 

   

            

Page 12: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

11 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

PROJECT:  Adams House Medical Centre          Date: 4th July 2017 

ACTIVITY SPACE DATA SHEET: PATIENT CORRIDOR   

Version: 1          Revision:  

 EQUIPMENT             Group 1  Items to be provided and fixed by the builder e.g. sink, coat hook 

Group 2  Items supplied by Trust and fixed by builder e.g. soap dispenser 

Group 3  Loose equipment taking up significant floor space e.g. bed 

Group 4  Small items of loose equipment e.g. computer, waste bin 

 

  

                          Group  

1. 3 Staff alarm points (linked to Eddison system)              1 2. Luminaires to CIBSE LG7                  1 3. Luminaire to CIBSE LG7 with integral emergency inverter/battery pack.        1 4. Fire alarm combined smoke detector/sounder              1 5. Fire alarm call point with key switch                1 6. 4 No. single socket outlets at 450mm. AFFL              1 

   

  

Page 13: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

12 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

TECHNICAL DATA SHEET  

ENVIRONMENTAL  29ºC db. 50% RH summer  :   DESIGN   :  NOTES       ‐4ºC sat. Winter     :   DATA    : 

AIR          :      :  Winter Temperature        (degC)  :  15    : Summer Temperature        (degC)  :      : Mechanical Ventilation: Supply      (m3/s)  :       : Mechanical Ventilation: Extract      (m3/s)  :       :               :      : Pressure – Rel. to Adj. Space        :       : Filtration (% Dust Sp Eff & % Arr)      :      : Humidity          (%RH)  :      : 

    LIGHTING        :      : Service Illumination        (Lux)  :  200    : Service Illumination Night      (Lux)  :  200    : Local Illumination        (Lux)  :  NA    : Colour Rendering Required        :  Ra 80    : Uniformity            :  0.4    : Standby Lighting Grade          :  NA    : Lighting Control           :  N    : 

    NOISE          :      : Acceptable Sound Level     [ (L10dB (A) ]  :   NR35    : Speech Privacy Required        :      : Quality which cannot be tolerated      :      : 

    SAFETY          :      : Accessible Hot Surface      Max temp (C)  :  43    : Domestic Hot Water      Max temp (C)  :  41    : 

DESIGN CHARACTER       

Internal Finishes    : Walls (HBN 00‐10 B)             : Floor (HBN 00‐10 A) :  Ceiling (HBN 00‐10 B)         : Heavy duty emulsion        Sheet vinyl  :            Heavy duty emulsion  

Doorsets   Solid core light beech veneer door and a half arrangement. FD30S. Flush bolts to slave leaf. Lever handles and mortice lock with internal thumb turn to master leaf.  2 x vision panels to master leaf. 2 x kick plates to both leaves. Overhead door closer to master leaf. 

 

 Windows (HBN 00‐10 D)  : Openable UPVC frame double glazed window with toughened glass (as    

existing). Film applied to window  

    

     

Page 14: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

13 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

PROJECT:  Adams House Medical Centre          Date: 4th July 2017 

ACTIVITY SPACE DATA SHEET: C/E 1  

Version: 1          Revision:  

 EQUIPMENT             Group 1  Items to be provided and fixed by the builder e.g. sink, coat hook 

Group 2  Items supplied by Trust and fixed by builder e.g. soap dispenser 

Group 3  Loose equipment taking up significant floor space e.g. treatment couch

Group 4  Small items of loose equipment e.g. computer, waste bin 

 

                           Group 

1. Staff alarm point (linked to Eddison system)              1 2. Luminaires to CIBSE LG7                  1 3. Luminaires to CIBSE LG7 with integral emergency inverter/battery pack.        1 4. Heating via Radiators LTHW                  1 5. Fire alarm combined smoke detector/sounder              1 6. 4 No. twin socket outlets at 920mm. AFFL mounted in 3 compartment dado trunking    1 7. 2 No. twin socket outlets at 450mm. AFFL              1 8. 2 No. data outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking      

with Cat 6e data cabling to patch panel.               1 9. 1 No. telephone outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking  1 10. 1 x No. Clinical basin with elbow taps mounted on full height IPS panel        1   11. Lockable wall cupboard                   1 12. Worktop and lockable cupboard and draws underneath            1 13. Natural fresh air supply system                  1 14. Desk                        2 15. 1 x doctor’s chair                    3 16. 1 x patient chair                    3 17. Examination couch                    3 18. 1 x curtain and track                    2 19. 2 x bins                       4 20. 1 x computer                      4 21. Alcohol gel dispenser                    2 22. Paper towel dispenser                     2 23. Soap dispenser                      2 24. Door stops and hook                    1 25. Washable roller blinds to windows                1 

  

  

Page 15: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

14 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

TECHNICAL DATA SHEET  

ENVIRONMENTAL  29ºC d.b.50% RH. Summer  :   DESIGN   :  NOTES       ‐4ºC sat. Winter     :   DATA    : 

AIR          :      : Winter Temperature        (degC)  :   21 +/‐ 2c  :  Summer Temperature        (degC)  :   24 +/‐ 2c  :  Mechanical Ventilation: Supply      (m3/s)  :       : Mechanical Ventilation: Extract      (m3/s)  :      :  Pressure – Rel. to Adj. Space        :       :       Filtration (% Dust Sp Eff & % Arr)      :      :     Humidity          (%RH)  :      : 

    LIGHTING        :      : Service Illumination        (Lux)  :  500    : Service Illumination Night      (Lux)  :  NA    : Local Illumination        (Lux)  :  NA    : Colour Rendering Required        :  Ra 90    : Uniformity            :  0.6    : Standby Lighting Grade          :  NA    : Lighting Control           :  N    : 

    NOISE          :      : Acceptable Sound Level     [ (L10dB (A) ]  :   NR 35    : Speech Privacy Required        :       : Quality which cannot be tolerated      :      : 

    SAFETY          :      :  Accessible Hot Surface      Max temp (C)  :  43    :  Domestic Hot Water      Max temp (C)  :  41    :  

DESIGN CHARACTER       

Internal Finishes    : Walls (HBN 00‐10 B)             : Floor (HBN 00‐10 A) : Ceiling (HBN 00‐10 B)         : Heavy duty emulsion             : Sheet vinyl            : Heavy duty emulsion  

Door sets   : Solid core light beech veneer with lever handles and mortice lock with internal   thumb turn. 2 x kick plates 

 

 Windows (HBN 00‐10 D)  : Openable UPVC frame double glazed window with toughened glass (as    

existing). Film applied to window  

   

  

       

Page 16: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

15 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

PROJECT:  Adams House Medical Centre          Date: 4th July 2017 

ACTIVITY SPACE DATA SHEET: C/E 2  

Version: 1          Revision:  

 EQUIPMENT             Group 1  Items to be provided and fixed by the builder e.g. sink, coat hook 

Group 2  Items supplied by Trust and fixed by builder e.g. soap dispenser 

Group 3  Loose equipment taking up significant floor space e.g. treatment couch

Group 4  Small items of loose equipment e.g. computer, waste bin 

 

                           Group 

1. Staff alarm point (linked to Eddison system)              1 2. Luminaires to CIBSE LG7                  1 3. Luminaires to CIBSE LG7 with integral emergency inverter/battery pack.        1 4. Heating via Radiators LTHW                  1 5. Fire alarm combined smoke detector/sounder              1 6. 4 No. twin socket outlets at 920mm. AFFL mounted in 3 compartment dado trunking    1 7. 2 No. twin socket outlets at 450mm. AFFL              1 8. 2 No. data outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking      

with Cat 6e data cabling to patch panel.               1 9. 1 No. telephone outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking  1 10. 1 x No. Clinical basin with elbow taps mounted on full height IPS panel        1   11. Lockable wall cupboard                   1 12. Worktop and lockable cupboard and draws underneath            1 13. Natural fresh air supply system                  1 14. Desk                        2 15. 1 x doctor’s chair                    3 16. 1 x patient chair                    3 17. Examination couch                    3 18. 1 x curtain and track                    2 19. 2 x bins                       4 20. 1 x computer                      4 21. Alcohol gel dispenser                    2 22. Paper towel dispenser                     2 23. Soap dispenser                      2 24. Door stops and hook                    1 25. Washable roller blinds to windows                1 

  

  

Page 17: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

16 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

TECHNICAL DATA SHEET  

ENVIRONMENTAL  29ºC d.b.50% RH. Summer  :   DESIGN   :  NOTES       ‐4ºC sat. Winter     :   DATA    : 

AIR          :      : Winter Temperature        (degC)  :   21 +/‐ 2c  :  Summer Temperature        (degC)  :   24 +/‐ 2c  :  Mechanical Ventilation: Supply      (m3/s)  :       : Mechanical Ventilation: Extract      (m3/s)  :      :  Pressure – Rel. to Adj. Space        :       :       Filtration (% Dust Sp Eff & % Arr)      :      :     Humidity          (%RH)  :      : 

    LIGHTING        :      : Service Illumination        (Lux)  :  500    : Service Illumination Night      (Lux)  :  NA    : Local Illumination        (Lux)  :  NA    : Colour Rendering Required        :  Ra 90    : Uniformity            :  0.6    : Standby Lighting Grade          :  NA    : Lighting Control           :  N    : 

    NOISE          :      : Acceptable Sound Level     [ (L10dB (A) ]  :   NR 35    : Speech Privacy Required        :       : Quality which cannot be tolerated      :      : 

    SAFETY          :      :  Accessible Hot Surface      Max temp (C)  :  43    :  Domestic Hot Water      Max temp (C)  :  41    :  

DESIGN CHARACTER       

Internal Finishes    : Walls (HBN 00‐10 B)             : Floor (HBN 00‐10 A) : Ceiling (HBN 00‐10 B)         : Heavy duty emulsion             : Sheet vinyl            : Heavy duty emulsion  

Door sets   : Solid core light beech veneer with lever handles and mortice lock with internal   thumb turn. 2 x kick plates 

 

 Windows (HBN 00‐10 D)  : Openable UPVC frame double glazed window with toughened glass (as    

existing). Film applied to window  

   

  

       

Page 18: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

17 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

PROJECT:  Adams House Medical Centre          Date: 4th July 2017 

ACTIVITY SPACE DATA SHEET: C/E 3  

Version: 1          Revision:  

 EQUIPMENT             Group 1  Items to be provided and fixed by the builder e.g. sink, coat hook 

Group 2  Items supplied by Trust and fixed by builder e.g. soap dispenser 

Group 3  Loose equipment taking up significant floor space e.g. treatment couch

Group 4  Small items of loose equipment e.g. computer, waste bin 

 

                           Group 

1. Staff alarm point (linked to Eddison system)              1 2. Luminaires to CIBSE LG7                  1 3. Luminaires to CIBSE LG7 with integral emergency inverter/battery pack.        1 4. Heating via Radiators LTHW                  1 5. Fire alarm combined smoke detector/sounder              1 6. 4 No. twin socket outlets at 920mm. AFFL mounted in 3 compartment dado trunking    1 7. 2 No. twin socket outlets at 450mm. AFFL              1 8. 2 No. data outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking      

with Cat 6e data cabling to patch panel.               1 9. 1 No. telephone outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking  1 10. 1 x No. Clinical basin with elbow taps mounted on full height IPS panel        1   11. Lockable wall cupboard                   1 12. Worktop and lockable cupboard and draws underneath            1 13. Natural fresh air supply system                  1 14. Desk                        2 15. 1 x doctor’s chair                    3 16. 1 x patient chair                    3 17. Examination couch                    3 18. 1 x curtain and track                    2 19. 2 x bins                       4 20. 1 x computer                      4 21. Alcohol gel dispenser                    2 22. Paper towel dispenser                     2 23. Soap dispenser                      2 24. Door stops and hook                    1 25. Washable roller blinds to windows                1 

  

  

Page 19: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

18 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

TECHNICAL DATA SHEET  

ENVIRONMENTAL  29ºC d.b.50% RH. Summer  :   DESIGN   :  NOTES       ‐4ºC sat. Winter     :   DATA    : 

AIR          :      : Winter Temperature        (degC)  :   21 +/‐ 2c  :  Summer Temperature        (degC)  :   24 +/‐ 2c  :  Mechanical Ventilation: Supply      (m3/s)  :       : Mechanical Ventilation: Extract      (m3/s)  :      :  Pressure – Rel. to Adj. Space        :       :       Filtration (% Dust Sp Eff & % Arr)      :      :     Humidity          (%RH)  :      : 

    LIGHTING        :      : Service Illumination        (Lux)  :  500    : Service Illumination Night      (Lux)  :  NA    : Local Illumination        (Lux)  :  NA    : Colour Rendering Required        :  Ra 90    : Uniformity            :  0.6    : Standby Lighting Grade          :  NA    : Lighting Control           :  N    : 

    NOISE          :      : Acceptable Sound Level     [ (L10dB (A) ]  :   NR 35    : Speech Privacy Required        :       : Quality which cannot be tolerated      :      : 

    SAFETY          :      :  Accessible Hot Surface      Max temp (C)  :  43    :  Domestic Hot Water      Max temp (C)  :  41    :  

DESIGN CHARACTER       

Internal Finishes    : Walls (HBN 00‐10 B)             : Floor (HBN 00‐10 A) : Ceiling (HBN 00‐10 B)         : Heavy duty emulsion             : Sheet vinyl            : Heavy duty emulsion  

Door sets   : Solid core light beech veneer with lever handles and mortice lock with internal   thumb turn. 2 x kick plates 

 

 Windows (HBN 00‐10 D)  : Openable UPVC frame double glazed window with toughened glass (as    

existing). Film applied to window  

   

  

       

Page 20: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

19 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

PROJECT:  Adams House Medical Centre          Date: 4th July 2017 

ACTIVITY SPACE DATA SHEET: C/E 4  

Version: 1          Revision:  

 EQUIPMENT             Group 1  Items to be provided and fixed by the builder e.g. sink, coat hook 

Group 2  Items supplied by Trust and fixed by builder e.g. soap dispenser 

Group 3  Loose equipment taking up significant floor space e.g. treatment couch

Group 4  Small items of loose equipment e.g. computer, waste bin 

 

                           Group 

1. Staff alarm point (linked to Eddison system)              1 2. Luminaires to CIBSE LG7                  1 3. Luminaires to CIBSE LG7 with integral emergency inverter/battery pack.        1 4. Heating via Radiators LTHW                  1 5. Fire alarm combined smoke detector/sounder              1 6. 4 No. twin socket outlets at 920mm. AFFL mounted in 3 compartment dado trunking    1 7. 2 No. twin socket outlets at 450mm. AFFL              1 8. 2 No. data outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking      

with Cat 6e data cabling to patch panel.               1 9. 1 No. telephone outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking  1 10. 1 x No. Clinical basin with elbow taps mounted on full height IPS panel        1   11. Lockable wall cupboard                   1 12. Worktop and lockable cupboard and draws underneath            1 13. Natural fresh air supply system                  1 14. Desk                        2 15. 1 x doctor’s chair                    3 16. 1 x patient chair                    3 17. Examination couch                    3 18. 1 x curtain and track                    2 19. 2 x bins                       4 20. 1 x computer                      4 21. Alcohol gel dispenser                    2 22. Paper towel dispenser                     2 23. Soap dispenser                      2 24. Door stops and hook                    1 25. Washable roller blinds to windows                1 

  

  

Page 21: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

20 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

TECHNICAL DATA SHEET  

ENVIRONMENTAL  29ºC d.b.50% RH. Summer  :   DESIGN   :  NOTES       ‐4ºC sat. Winter     :   DATA    : 

AIR          :      : Winter Temperature        (degC)  :   21 +/‐ 2c  :  Summer Temperature        (degC)  :   24 +/‐ 2c  :  Mechanical Ventilation: Supply      (m3/s)  :       : Mechanical Ventilation: Extract      (m3/s)  :      :  Pressure – Rel. to Adj. Space        :       :       Filtration (% Dust Sp Eff & % Arr)      :      :     Humidity          (%RH)  :      : 

    LIGHTING        :      : Service Illumination        (Lux)  :  500    : Service Illumination Night      (Lux)  :  NA    : Local Illumination        (Lux)  :  NA    : Colour Rendering Required        :  Ra 90    : Uniformity            :  0.6    : Standby Lighting Grade          :  NA    : Lighting Control           :  N    : 

    NOISE          :      : Acceptable Sound Level     [ (L10dB (A) ]  :   NR 35    : Speech Privacy Required        :       : Quality which cannot be tolerated      :      : 

    SAFETY          :      :  Accessible Hot Surface      Max temp (C)  :  43    :  Domestic Hot Water      Max temp (C)  :  41    :  

DESIGN CHARACTER       

Internal Finishes    : Walls (HBN 00‐10 B)             : Floor (HBN 00‐10 A) : Ceiling (HBN 00‐10 B)         : Heavy duty emulsion             : Sheet vinyl            : Heavy duty emulsion  

Door sets   : Solid core light beech veneer with lever handles and mortice lock with internal   thumb turn. 2 x kick plates 

 

 Windows (HBN 00‐10 D)  : Openable UPVC frame double glazed window with toughened glass (as    

existing). Film applied to window  

   

  

       

Page 22: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

21 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

PROJECT:  Adams House Medical Centre          Date: 4th July 2017 

ACTIVITY SPACE DATA SHEET:  TREATMENT/ MULTI  

 

Version: 1          Revision:  

 EQUIPMENT             Group 1  Items to be provided and fixed by the builder e.g. sink, coat hook 

Group 2  Items supplied by Trust and fixed by builder e.g. soap dispenser 

Group 3  Loose equipment taking up significant floor space e.g. bed 

Group 4  Small items of loose equipment e.g. computer, waste bin 

 

                           Group 

1. Staff alarm point (linked to Eddison system)              1 2. Luminaires to CIBSE LG7                  1 3. Luminaires to CIBSE LG7 with integral emergency inverter/battery pack.        1 4. Heating via Radiators LTHW                  1 5. Fire alarm combined smoke detector/sounder              1 6. 4 No. twin socket outlets at 920mm. AFFL mounted in 3 compartment dado trunking    1 7. 2 No. twin socket outlets at 450mm. AFFL              1 8. 2 No. data outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking      

with Cat 6e data cabling to patch panel.               1 9. 1 No. telephone outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking  1 10. 1 x No. Clinical basin with elbow taps.served from thermostatic mixing valve and     1 11. lockable wall cupboards                   1 12. worktop and lockable cupboards and draws underneath           1 13. Natural fresh air supply system                  1 14. Alcohol gel dispenser                    2 15. Paper towel dispenser                     2 16. Soap dispenser                      2 17. Door stops and hook                    1 

  

  

Page 23: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

22 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

TECHNICAL DATA SHEET  

ENVIRONMENTAL  29ºC db. 50% RH summer  :   DESIGN   :  NOTES       ‐4ºC sat. Winter     :   DATA    : 

AIR          :      :  Winter Temperature        (degC)  :   21 +/‐ 2c  :   Summer Temperature        (degC)  :   23 +/‐ 2c  :  Mechanical Ventilation: Supply      (m3/s)  :   0.110    : Supply air to 10 ACH Mechanical Ventilation: Extract      (m3/s)  :  0.110    : Pressure – Rel. to Adj. Space        :  Positive to corridor 0.107m3/s & 0.050m3/s                                                                                                Dirty utility.       Filtration (% Dust Sp Eff & % Arr)      :   F7    : Humidity          (%RH)  :      : 

    LIGHTING        :      : Service Illumination        (Lux)  :  500    : Service Illumination Night      (Lux)  :  200    : Local Illumination        (Lux)  :  NA    : Colour Rendering Required        :  Ra 90    : Uniformity            :  0.6    : Standby Lighting Grade          :  NA    : Lighting Control           :  N    : 

    NOISE          :      : Acceptable Sound Level     [ (L10dB (A) ]  :   NR 35    : Speech Privacy Required        :      : Quality which cannot be tolerated      :      : 

    SAFETY          :      :   Accessible Hot Surface      Max temp (C)  :  43    :  Domestic Hot Water      Max temp (C)  :  41    :  

DESIGN CHARACTER       

Internal Finishes    : Walls (HBN 00‐10 B)           : Floor (HBN 00‐10 A) :   Ceiling (HBN 00‐10 B)         : Heavy duty emulsion           : Sheet vinyl            : Heavy duty emulsion 

Altro whiterock splasback        

Doorsets  : 2 x Solid core light beech veneer door and a half arrangement. Flush bolts to slave leaves. Lever handles and mortice lock with internal thumb turn to master leaves.  2 x kick plates to both leaves of both sets of doors. 

 

 Windows (HBN 00‐10 D)  : Openable UPVC frame double glazed window with toughened glass (as    

existing). Film applied to window  

         

Page 24: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

23 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

PROJECT:  Adams House Medical Centre          Date: 4th July 2017 

ACTIVITY SPACE DATA SHEET:  DIRTY UTILITY  

 

Version: 1          Revision:  

 EQUIPMENT             Group 1  Items to be provided and fixed by the builder e.g. sink, coat hook 

Group 2  Items supplied by Trust and fixed by builder e.g. soap dispenser 

Group 3  Loose equipment taking up significant floor space e.g. bed 

Group 4  Small items of loose equipment e.g. computer, waste bin 

 

                           Group  

1. Luminaires to CIBSE LG7                  1 2. Luminaire to CIBSE LG7 with integral emergency inverter/battery pack.        1 3. Fire alarm combined smoke detector/sounder              1 4. Stainless steel sink with drainer at mixer taps with lockable cupboards        1 5. Clinical wash hand basin with elbow taps with thermostatic mixing valve       1 6. Stainless steel slop hopper sink                  1 7. Worktop                      1 8. Lockable cupboards with drawers beneath worktops            1 9. Lockable wall mounted cupboards                1 10. 2 No. twin socket outlets at 450mm. AFFL              1 11. Natural fresh air supply system                  1 12. 2 large waste bins – 1 black and 1 clinical waste (yellow)           4 13. Sharps bin holder                    4 14. Glove and apron dispensers                  2 15. soap dispenser                      2 16. Paper towel dispenser                    2 17. 1500 long adjustable height white melamine shelves 1200 x 1800 high        1 18. Alcohol gel dispenser                    2 19. 4 No. twin socket outlets at 920mm. AFFL mounted in 3 compartment dado trunking    1 20. 2 No. twin socket outlets at 450mm. AFFL              1 21. 2 No. data outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking      

with Cat 6e data cabling to patch panel.               1 22. 1 No. telephone outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking  1 

   

  

Page 25: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

24 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

TECHNICAL DATA SHEET  

ENVIRONMENTAL  29ºC db. 50% RH summer  :  DESIGN   :  NOTES       ‐4ºC sat. Winter     :   DATA    : 

AIR          :      :  Winter Temperature        (degC)  :   15    : Summer Temperature        (degC)  :   Uncontrolled  : Mechanical Ventilation: Supply      (m3/s)  :      :               :      : Mechanical Ventilation: Extract      (m3/s)  :   0.050    : Air transfer from Treatment &               :      : corridor to provide 6 ACH as  Pressure – Rel. to Adj. Space        : Negative pressure    HTM  requirements.   Filtration (% Dust Sp Eff & % Arr)      :      : Humidity          (%RH)  :      : 

    LIGHTING        :      : Service Illumination        (Lux)  :  200    : Service Illumination Night      (Lux)  :  200    : Local Illumination        (Lux)  :  NA    : Colour Rendering Required        :  Ra 80    : Uniformity            :  0.6    : Standby Lighting Grade          :  NA    : Lighting Control           :  N    : 

    NOISE          :      : Acceptable Sound Level     [ (L10dB (A) ]  :   NR35    : Speech Privacy Required        :      : Quality which cannot be tolerated      :      : 

    SAFETY          :      : Accessible Hot Surface      Max temp (C)  :  43    : Domestic Hot Water      Max temp (C)  :  41    : 

DESIGN CHARACTER       

Internal Finishes    : Walls (HBN 00‐10 B)  : Floor (HBN 00‐10 A)  : Ceiling (HBN 00‐10 B)         : Heavy duty emulsion     Non slip vinyl              :Heavy duty emulsion 

Altro whiterock splasback        

Door sets   : 2 x Solid core light beech veneer FD30S with lever handles and mortice lock with internal  thumb turns. 2 x kick plates per door. 2 x overhead door closers. 

 

 Windows (HBN 00‐10 D)  : Openable UPVC frame double glazed window with toughened glass (as    

existing). Film applied to window  

  

       

Page 26: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

25 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

PROJECT:  Adams House Medical Centre          Date: 4th July 2017 

ACTIVITY SPACE DATA SHEET: WAITING AREA 2  

Version: 1          Revision:  

 EQUIPMENT             Group 1  Items to be provided and fixed by the builder e.g. sink, coat hook 

Group 2  Items supplied by Trust and fixed by builder e.g. soap dispenser 

Group 3  Loose equipment taking up significant floor space e.g. bed 

Group 4  Small items of loose equipment e.g. computer, waste bin 

 

                         Group  

1. Anti‐ligature luminaires to CIBSE LG7              1 2. Anti‐ligature luminaires with integral emergency inverter/battery pack. To CIBSE LG7  1 3. Heating via Radiators LTHW                1 4. Fire alarm combined smoke detector/sounder             1 5. 2 No. twin socket outlets at 1800mm. AFFL            1 6. 2 No. data outlet socket at 1800mm. AFFL            1 7. 4 No. twin socket outlets at 450mm. AFFL            1 8. 15 x bench style seating                 3 9. Blinds and tracks                  3 10. anti‐ligature door stops                 3 

   

Page 27: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

26 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

TECHNICAL DATA SHEET  

ENVIRONMENTAL  29ºC db. 50% RH Summer  :   DESIGN   :  NOTES       ‐4ºC sat. Winter     :   DATA    : 

AIR          :      :  Winter Temperature        (degC)  :  18  +/‐ 2c  :  Summer Temperature        (degC)  :   24 +/‐ 2c  : Mechanical Ventilation: Supply      (m3/s)  :       : Mechanical Ventilation: Extract      (m3/s)  :       : Pressure – Rel. to Adj. Space        :       : Filtration (% Dust Sp Eff & % Arr)      :                    : Humidity          (%RH)  :      : 

    LIGHTING        :      : Service Illumination        (Lux)  :  200    : Service Illumination Night      (Lux)  :  200    : Local Illumination        (Lux)  :  NA    : Colour Rendering Required        :  Ra 80    : Uniformity            :  0.4    : Standby Lighting Grade          :  NA    : Lighting Control           :  N    : 

    NOISE          :      : Acceptable Sound Level     [ (L10dB (A) ]  :   NR 35    : Speech Privacy Required        :      : Quality which cannot be tolerated      :      : 

    SAFETY          :      : Accessible Hot Surface      Max temp (C)  :  43    : Domestic Hot Water      Max temp (C)  :  41    : 

DESIGN CHARACTER       

Internal Finishes    : Walls (HBN 00‐10 B)         : Floor (HBN 00‐10 A) :   Ceiling (HBN 00‐10 B)         : Heavy duty emulsion               Sheet vinyl             Heavy duty emulsion  

 Windows (HBN 00‐10 D)  : Openable UPVC frame double glazed window with toughened glass (as    

existing). Film applied to window  

               

Page 28: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

27 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

PROJECT:  Adams House Medical Centre          Date: 4th July 2017 

ACTIVITY SPACE DATA SHEET: STORE  

Version: 1          Revision:  

 EQUIPMENT             Group 1  Items to be provided and fixed by the builder e.g. sink, coat hook 

Group 2  Items supplied by Trust and fixed by builder e.g. soap dispenser 

Group 3  Loose equipment taking up significant floor space e.g. bed 

Group 4  Small items of loose equipment e.g. computer, waste bin 

                                                      Group  

1. Luminaire                      1 2. Luminaire to CIBSE LG7 with integral emergency inverter/battery pack.        1 3. Electric Tube Heating.                                                                                        1 4. Fire alarm combined smoke detector/sounder              1 5. Fresh air supply and Ventilation                 1 6. Full height and width timber slatted shelving at 600mm vertical centers        1 

  

  

Page 29: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

28 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

TECHNICAL DATA SHEET  

ENVIRONMENTAL  29ºC db. 50% RH Summer  :   DESIGN   :  NOTES       ‐4ºC sat. Winter     :   DATA    : 

AIR          :      :  Winter Temperature        (degC)  :  15    :  Summer Temperature        (degC)  :  Uncontrolled  : Mechanical Ventilation: Supply      (m3/s)  :      : Mechanical Ventilation: Extract      (m3/s)  :       : Pressure – Rel. to Adj. Space        :      :  Filtration (% Dust Sp Eff & % Arr)      :      : Humidity          (%RH)  :      : 

    LIGHTING        :      : Service Illumination        (Lux)  :  300    : Service Illumination Night      (Lux)  :  200    : Local Illumination        (Lux)  :  NA    : Colour Rendering Required        :  Ra 80    : Uniformity            :  0.6    : Standby Lighting Grade          :  NA    : Lighting Control           :  N    : 

    NOISE          :      : Acceptable Sound Level     [ (L10dB (A) ]  :   NR35    : Speech Privacy Required        :      : Quality which cannot be tolerated      :      : 

    SAFETY          :      : Accessible Hot Surface      Max temp (C)  :  43    : Domestic Hot Water      Max temp (C)  :  41    : 

DESIGN CHARACTER       

Internal Finishes    : Walls (HBN 00‐10 B)             : Floor (HBN 00‐10 A) : Ceiling (HBN 00‐10 B)         : Heavy duty emulsion             : Sheet vinyl            : Heavy duty emulsion  

Doorsets  : Solid core light beech veneer FD30S. Lever handles and mortice lock with internal thumb turn. 2 x kick plates. Overhead door closer 

 :Windows (HBN 00‐10 D)  : Non‐openable steel frame double glazed window with toughened glass (as 

existing). 

             

Page 30: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

29 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

PROJECT:  Adams House Medical Centre          Date: 4th July 2017 

ACTIVITY SPACE DATA SHEET: PATIENT CORRIDOR  

Version: 1          Revision:  

 EQUIPMENT             Group 1  Items to be provided and fixed by the builder e.g. sink, coat hook 

Group 2  Items supplied by Trust and fixed by builder e.g. soap dispenser 

Group 3  Loose equipment taking up significant floor space e.g. bed 

Group 4  Small items of loose equipment e.g. computer, waste bin 

 

  

                          Group  

1. 3 Staff alarm points (linked to Eddison system)              1 2. Luminaires to CIBSE LG7                  1 3. Luminaire to CIBSE LG7 with integral emergency inverter/battery pack.        1 4. Fire alarm combined smoke detector/sounder              1 5. Fire alarm call point with key switch                1 6. 1 No. single socket outlets at 450mm. AFFL              1 

   

  

Page 31: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

30 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

TECHNICAL DATA SHEET  

ENVIRONMENTAL  29ºC db. 50% RH summer  :   DESIGN   :  NOTES       ‐4ºC sat. Winter     :   DATA    : 

AIR          :      :  Winter Temperature        (degC)  :  15    : Summer Temperature        (degC)  :      : Mechanical Ventilation: Supply      (m3/s)  :       : Mechanical Ventilation: Extract      (m3/s)  :       :               :      : Pressure – Rel. to Adj. Space        :       : Filtration (% Dust Sp Eff & % Arr)      :      : Humidity          (%RH)  :      : 

    LIGHTING        :      : Service Illumination        (Lux)  :  200    : Service Illumination Night      (Lux)  :  200    : Local Illumination        (Lux)  :  NA    : Colour Rendering Required        :  Ra 80    : Uniformity            :  0.4    : Standby Lighting Grade          :  NA    : Lighting Control           :  N    : 

    NOISE          :      : Acceptable Sound Level     [ (L10dB (A) ]  : NR35      : Speech Privacy Required        :      : Quality which cannot be tolerated      :      : 

    SAFETY          :      : Accessible Hot Surface      Max temp (C)  :  43    : Domestic Hot Water      Max temp (C)  :  41    : 

DESIGN CHARACTER       

Internal Finishes    : Walls (HBN 00‐10 B)             : Floor (HBN 00‐10 A) :  Ceiling (HBN 00‐10 B)         : Heavy duty emulsion        Sheet vinyl  :            Heavy duty emulsion  

Doorsets   Solid core light beech veneer door and a half arrangement. FD30S. Flush bolts to slave leaf. Lever handles and mortice lock with internal thumb turn to master leaf.  2 x vision panels to master leaf. 2 x kick plates to both leaves. Overhead door closer to master leaf. 

 

 Windows (HBN 00‐10 D)  : Openable UPVC frame double glazed window with toughened glass (as    

existing). Film applied to window  

   

      

Page 32: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

31 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

PROJECT:  Adams House Medical Centre          Date: 4th July 2017 

ACTIVITY SPACE DATA SHEET: STAFF CORRIDOR   

Version: 1          Revision:  

 EQUIPMENT             Group 1  Items to be provided and fixed by the builder e.g. sink, coat hook 

Group 2  Items supplied by Trust and fixed by builder e.g. soap dispenser 

Group 3  Loose equipment taking up significant floor space e.g. bed 

Group 4  Small items of loose equipment e.g. computer, waste bin 

 

  

                          Group  

1. Luminaires to CIBSE LG7                  1 2. Luminaire to CIBSE LG7 with integral emergency inverter/battery pack.        1 3. Fire alarm combined smoke detector/sounder              1 4. Natural fresh air supply system                  1 5. 1 No. magnetic door locks and proximity sensor readers and associated power supplies                  1 6. 2 No. single socket outlets at 450mm. AFFL              1 

   

  

Page 33: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

32 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

TECHNICAL DATA SHEET  

ENVIRONMENTAL  29ºC db. 50% RH Summer  :  DESIGN   :  NOTES       ‐4ºC sat. Winter     :   DATA    : 

AIR          :      : Winter Temperature        (degC)  :  15    : Summer Temperature        (degC)  :  Uncontrolled  : Mechanical Ventilation: Supply      (m3/s)  :      : Mechanical Ventilation: Extract      (m3/s)  :      : Pressure – Rel. to Adj. Space        :   Balanced  :   Filtration (% Dust Sp Eff & % Arr)      :      : Humidity          (%RH)  :      : 

    LIGHTING        :      : Service Illumination        (Lux)  :  200    : Service Illumination Night      (Lux)  :  200    : Local Illumination        (Lux)  :  NA    : Colour Rendering Required        :  Ra 80    : Uniformity            :  0.4    : Standby Lighting Grade          :  NA    : Lighting Control           :  N    : 

    NOISE          :      : Acceptable Sound Level     [ (L10dB (A) ]  :   NR 35    : Speech Privacy Required        :      : Quality which cannot be tolerated      :      : 

    SAFETY          :      : Accessible Hot Surface      Max temp (C)  :  43    : Domestic Hot Water      Max temp (C)  :  41    : 

DESIGN CHARACTER       

Internal Finishes    : Walls (HBN 00‐10 B)             : Floor (HBN 00‐10 A) :  Ceiling (HBN 00‐10 B)         : Heavy duty emulsion        Sheet vinyl  :            Heavy duty emulsion  

Doorsets   2 x Solid core light beech veneer doors FD30S. Push plates and pull handles. Mortice locks with internal thumb turns.  2 x kick plates to both doors. 2 x vision panels per door. Overhead door closers. 

                

Page 34: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

33 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

PROJECT:  Adams House Medical Centre          Date: 4th July 2017 

ACTIVITY SPACE DATA SHEET:  CLEANERS CUPBOARD 

 

Version: 1          Revision:  

 EQUIPMENT             Group 1  Items to be provided and fixed by the builder e.g. sink, coat hook 

Group 2  Items supplied by Trust and fixed by builder e.g. soap dispenser 

Group 3  Loose equipment taking up significant floor space e.g. bed 

Group 4  Small items of loose equipment e.g. computer, waste bin 

 

                           Group  

1. Luminaire with integral emergency inverter/battery pack          1 2. High back cleaners sink with integral grating              1 3. Natural fresh air supply system                  1 

  

  

Page 35: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

34 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

TECHNICAL DATA SHEET  

ENVIRONMENTAL  29ºC db. 50% RH. Summer  :   DESIGN   :  NOTES       ‐4ºC sat. Winter     :  DATA    : 

AIR          :      : Winter Temperature        (degC)  :  15    : Summer Temperature        (degC)  :  Uncontrolled  : Mechanical Ventilation: Supply      (m3/s)  :      : Mechanical Ventilation: Extract      (m3/s)  :                     :               :      :  Pressure – Rel. to Adj. Space        :       : Filtration (% Dust Sp Eff & % Arr)      :      : Humidity          (%RH)  :      : 

    LIGHTING        :      : Service Illumination        (Lux)  :  300    : Service Illumination Night      (Lux)  :  200    : Local Illumination        (Lux)  :  NA    : Colour Rendering Required        :  Ra 80    : Uniformity            :  0.6    : Standby Lighting Grade          :  NA    : Lighting Control           :  N    : 

    NOISE          :      : Acceptable Sound Level     [ (L10dB (A) ]  :      : Speech Privacy Required        :      : Quality which cannot be tolerated      :      : 

    SAFETY          :      :  Accessible Hot Surface      Max temp (C)  :  43    :  Domestic Hot Water      Max temp (C)  :  41    :  

DESIGN CHARACTER       

Internal Finishes    : Walls (HBN 00‐10 B)         : Floor (HBN 00‐10 A) :  Ceiling (HBN 00‐10 B)         : Heavy duty emulsion        Non slip vinyl                    Heavy duty emulsion       

Door sets   : Solid core light beech veneer door FD30S. Lever handles with mortice lock with internal thumb turn override. 2 x kick plates. Overhead door closer. 

   

            

Page 36: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

35 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

 PROJECT:  Adams House Medical Centre          Date: 4th July 2017 

ACTIVITY SPACE DATA SHEET: PATIENT WC 

 

Version: 1          Revision:  

 EQUIPMENT             Group 1  Items to be provided and fixed by the builder e.g. sink, coat hook 

Group 2  Items supplied by Trust and fixed by builder e.g. soap dispenser 

Group 3  Loose equipment taking up significant floor space e.g. bed 

Group 4  Small items of loose equipment e.g. computer, waste bin 

 

                           Group  

1. Patient Call Switch and reassurance with local reset (Nurse call) with  infra‐red receiver and external over door indicator.            1 

2. Luminaire with integral emergency inverter/battery pack.          1 3. Wash hand basin with percussion outlets served from thermostatic mixing  

valve and isolation valves.                  1 4. W.C. with air push button flushing cistern.              1 5. Natural fresh air supply system                  1 6. Concealed drainage from wash hand basin and W.C.            1 7. 1 x Anti ligature coat hook                  1 8. toilet magazine dispenser                                         2 9. soap dispenser                                               2 10. Unbreakable Mirror 300 x 450                                         1 11. alcohol gel dispenser                               2 12. Paper towel dispenser                    2 13. bin                        4 

  

  

Page 37: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

36 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

TECHNICAL DATA SHEET  

ENVIRONMENTAL  29ºC db. 50% RH summer  :   DESIGN   :  NOTES       ‐4ºC sat. Winter     :  DATA    : 

AIR          :      : Winter Temperature        (degC)  :   18    : Summer Temperature        (degC)  :   Uncontrolled  : Mechanical Ventilation: Supply      (m3/s)  :      : Mechanical Ventilation: Extract      (m3/s)  :   0.015    :                :      : Pressure – Rel. to Adj. Space        :       : Filtration (% Dust Sp Eff & % Arr)      :      : Humidity          (%RH)  :      : 

    LIGHTING        :      : Service Illumination        (Lux)  :  200    : Service Illumination Night      (Lux)  :  200    : Local Illumination        (Lux)  :  NA    : Colour Rendering Required        :  Ra 80    : Uniformity            :  0.6    : Standby Lighting Grade          :  NA    : Lighting Control           :  N    : 

    NOISE          :      : Acceptable Sound Level     [ (L10dB (A) ]  : NR 35      : Speech Privacy Required        :      : Quality which cannot be tolerated      :      : 

    SAFETY          :      :  Accessible Hot Surface      Max temp (C)  :  43    :  Domestic Hot Water      Max temp (C)  :  41    :  

DESIGN CHARACTER       

Internal Finishes    : Walls (HBN 00‐10 B)         : Floor (HBN 00‐10 A) :  Ceiling (HBN 00‐10 B)         : Heavy duty emulsion        Non slip vinyl                    Heavy duty emulsion 

Altro whiterock splasback        

Doorsets   : Solid core light beech veneer double swing door. Lever handles with indicator lock with external emergency access. 2 x kick plates 

 

 Windows (HBN 00‐10 D)  : Openable UPVC frame double glazed window with toughened glass (as    

existing). Film applied to window  

   

       

Page 38: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

37 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

PROJECT:  Adams House Medical Centre          Date: 4th July 2017 

ACTIVITY SPACE DATA SHEET:  PLANT ROOM  

Version: 1          Revision:  

 EQUIPMENT             Group 1  Items to be provided and fixed by the builder e.g. sink, coathook 

Group 2  Items supplied by Trust and fixed by builder e.g. soap dispenser 

Group 3  Loose equipment taking up significant floor space e.g. bed 

Group 4  Small items of loose equipment e.g. computer, waste bin 

 

                            Group 

1. Luminaires to CIBSE LG7                  1 2. Luminaire to CIBSE LG7 with integral emergency inverter/battery pack.        1 3. Heating via Radiators LTHW                  1 4. Fire alarm combined smoke detector/sounder              1 5. Naturally Ventilated                    1 6. 3 No. double socket outlets at 450mm. AFFL              1 

  

   

Page 39: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

38 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

TECHNICAL DATA SHEET  

ENVIRONMENTAL  28ºC d.b. 20ºC w.b. summer  :   DESIGN   :  NOTES       ‐4ºC sat. winter     :   DATA    : 

AIR          :      : Winter Temperature        (degC)  :  Uncontrolled  : Summer Temperature        (degC)  :  Uncontrolled  : Mechanical Ventilation: Supply      (m3/s)  :      : Mechanical Ventilation: Extract      (m3/s)  :      : Pressure – Rel. to Adj. Space        :      : Filtration (% Dust Sp Eff & % Arr)      :      : Humidity          (%RH)  :      : 

    LIGHTING        :      : Service Illumination        (Lux)  :  300    : Service Illumination Night      (Lux)  :  NA    : Local Illumination        (Lux)  :  NA    : Colour Rendering Required        :  Ra 60    : Uniformity            :  0.4    : Standby Lighting Grade          :  NA    : Lighting Control           N    : 

    NOISE          :      : Acceptable Sound Level     [ (L10dB (A) ]  :      : Speech Privacy Required        :      : Quality which cannot be tolerated      :      : 

    SAFETY          :      : Accessible Hot Surface      Max temp (C)  :  43    : Domestic Hot Water      Max temp (C)  :  41    : 

DESIGN CHARACTER       

Internal Finishes    : Walls (HBN 00‐10 B)             : Floor (HBN 00‐10 A) :   Ceiling (HBN 00‐10 B)         : Heavy duty emulsion                Painted resin           Heavy duty emulsion  

Doorsets   : Solid core painted timber door. FD30S. Lever handles and mortice lock with     internal thumb turn. 2 x kick plates. Overhead door closer. 

     

    

         

Page 40: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

39 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

PROJECT:  Adams House Medical Centre          Date: 4th July 2017 

ACTIVITY SPACE DATA SHEET: C/E 5  

Version: 1          Revision:  

 EQUIPMENT             Group 1  Items to be provided and fixed by the builder e.g. sink, coat hook 

Group 2  Items supplied by Trust and fixed by builder e.g. soap dispenser 

Group 3  Loose equipment taking up significant floor space e.g. treatment couch

Group 4  Small items of loose equipment e.g. computer, waste bin 

 

                           Group 

1. Staff alarm point (linked to Eddison system)              1 2. Luminaires to CIBSE LG7                  1 3. Luminaires to CIBSE LG7 with integral emergency inverter/battery pack.        1 4. Heating via Radiators LTHW                  1 5. Fire alarm combined smoke detector/sounder              1 6. 4 No. twin socket outlets at 920mm. AFFL mounted in 3 compartment dado trunking    1 7. 2 No. twin socket outlets at 450mm. AFFL              1 8. 2 No. data outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking      

with Cat 6e data cabling to patch panel.               1 9. 1 No. telephone outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking  1 10. 1 x No. Clinical basin with elbow taps mounted on full height IPS panel        1   11. Lockable wall cupboard                   1 12. Worktop and lockable cupboard and draws underneath            1 13. Natural fresh air supply system                  1 14. Desk                        2 15. 1 x doctor’s chair                    3 16. 1 x patient chair                    3 17. Examination couch                    3 18. 1 x curtain and track                    2 19. 2 x bins                       4 20. 1 x computer                      4 21. Alcohol gel dispenser                    2 22. Paper towel dispenser                     2 23. Soap dispenser                      2 24. Door stops and hook                    1 25. Washable roller blinds to windows                1 

  

  

Page 41: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

40 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

TECHNICAL DATA SHEET  

ENVIRONMENTAL  29ºC d.b.50% RH. Summer  :   DESIGN   :  NOTES       ‐4ºC sat. Winter     :   DATA    : 

AIR          :      : Winter Temperature        (degC)  :   21 +/‐ 2c  :  Summer Temperature        (degC)  :   24 +/‐ 2c  :  Mechanical Ventilation: Supply      (m3/s)  :       : Mechanical Ventilation: Extract      (m3/s)  :      :  Pressure – Rel. to Adj. Space        :       :       Filtration (% Dust Sp Eff & % Arr)      :      :     Humidity          (%RH)  :      : 

    LIGHTING        :      : Service Illumination        (Lux)  :  500    : Service Illumination Night      (Lux)  :  NA    : Local Illumination        (Lux)  :  NA    : Colour Rendering Required        :  Ra 90    : Uniformity            :  0.6    : Standby Lighting Grade          :  NA    : Lighting Control           :  N    : 

    NOISE          :      : Acceptable Sound Level     [ (L10dB (A) ]  :   NR 35    : Speech Privacy Required        :       : Quality which cannot be tolerated      :      : 

    SAFETY          :      :  Accessible Hot Surface      Max temp (C)  :  43    :  Domestic Hot Water      Max temp (C)  :  41    :  

DESIGN CHARACTER       

Internal Finishes    : Walls (HBN 00‐10 B)             : Floor (HBN 00‐10 A) : Ceiling (HBN 00‐10 B)         : Heavy duty emulsion             : Sheet vinyl            : Heavy duty emulsion  

Door sets   : Solid core light beech veneer with lever handles and mortice lock with internal   thumb turn. 2 x kick plates 

 

 Windows (HBN 00‐10 D)  : Openable UPVC frame double glazed window with toughened glass (as    

existing). Film applied to window  

   

  

       

Page 42: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

41 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

PROJECT:  Adams House Medical Centre          Date: 4th July 2017 

ACTIVITY SPACE DATA SHEET: C/E 6  

Version: 1          Revision:  

 EQUIPMENT             Group 1  Items to be provided and fixed by the builder e.g. sink, coat hook 

Group 2  Items supplied by Trust and fixed by builder e.g. soap dispenser 

Group 3  Loose equipment taking up significant floor space e.g. treatment couch

Group 4  Small items of loose equipment e.g. computer, waste bin 

 

                           Group 

1. Staff alarm point (linked to Eddison system)              1 2. Luminaires to CIBSE LG7                  1 3. Luminaires to CIBSE LG7 with integral emergency inverter/battery pack.        1 4. Heating via Radiators LTHW                  1 5. Fire alarm combined smoke detector/sounder              1 6. 4 No. twin socket outlets at 920mm. AFFL mounted in 3 compartment dado trunking    1 7. 2 No. twin socket outlets at 450mm. AFFL              1 8. 2 No. data outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking      

with Cat 6e data cabling to patch panel.               1 9. 1 No. telephone outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking  1 10. 1 x No. Clinical basin with elbow taps mounted on full height IPS panel        1   11. Lockable wall cupboard                   1 12. Worktop and lockable cupboard and draws underneath            1 13. Natural fresh air supply system                  1 14. Desk                        2 15. 1 x doctor’s chair                    3 16. 1 x patient chair                    3 17. Examination couch                    3 18. 1 x curtain and track                    2 19. 2 x bins                       4 20. 1 x computer                      4 21. Alcohol gel dispenser                    2 22. Paper towel dispenser                     2 23. Soap dispenser                      2 24. Door stops and hook                    1 25. Washable roller blinds to windows                1 

  

  

Page 43: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

42 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

TECHNICAL DATA SHEET  

ENVIRONMENTAL  29ºC d.b.50% RH. Summer  :   DESIGN   :  NOTES       ‐4ºC sat. Winter     :   DATA    : 

AIR          :      : Winter Temperature        (degC)  :   21 +/‐ 2c  :  Summer Temperature        (degC)  :   24 +/‐ 2c  :  Mechanical Ventilation: Supply      (m3/s)  :       : Mechanical Ventilation: Extract      (m3/s)  :      :  Pressure – Rel. to Adj. Space        :       :       Filtration (% Dust Sp Eff & % Arr)      :      :     Humidity          (%RH)  :      : 

    LIGHTING        :      : Service Illumination        (Lux)  :  500    : Service Illumination Night      (Lux)  :  NA    : Local Illumination        (Lux)  :  NA    : Colour Rendering Required        :  Ra 90    : Uniformity            :  0.6    : Standby Lighting Grade          :  NA    : Lighting Control           :  N    : 

    NOISE          :      : Acceptable Sound Level     [ (L10dB (A) ]  :   NR 35    : Speech Privacy Required        :       : Quality which cannot be tolerated      :      : 

    SAFETY          :      :  Accessible Hot Surface      Max temp (C)  :  43    :  Domestic Hot Water      Max temp (C)  :  41    :  

DESIGN CHARACTER       

Internal Finishes    : Walls (HBN 00‐10 B)             : Floor (HBN 00‐10 A) : Ceiling (HBN 00‐10 B)         : Heavy duty emulsion             : Sheet vinyl            : Heavy duty emulsion  

Door sets   : Solid core light beech veneer with lever handles and mortice lock with internal   thumb turn. 2 x kick plates 

 

 Windows (HBN 00‐10 D)  : Openable UPVC frame double glazed window with toughened glass (as    

existing). Film applied to window  

   

  

       

Page 44: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

43 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

PROJECT:  Adams House Medical Centre          Date: 4th July 2017 

ACTIVITY SPACE DATA SHEET: C/E 7  

Version: 1          Revision:  

 EQUIPMENT             Group 1  Items to be provided and fixed by the builder e.g. sink, coat hook 

Group 2  Items supplied by Trust and fixed by builder e.g. soap dispenser 

Group 3  Loose equipment taking up significant floor space e.g. treatment couch

Group 4  Small items of loose equipment e.g. computer, waste bin 

 

                           Group 

1. Staff alarm point (linked to Eddison system)              1 2. Luminaires to CIBSE LG7                  1 3. Luminaires to CIBSE LG7 with integral emergency inverter/battery pack.        1 4. Heating via Radiators LTHW                  1 5. Fire alarm combined smoke detector/sounder              1 6. 4 No. twin socket outlets at 920mm. AFFL mounted in 3 compartment dado trunking    1 7. 2 No. twin socket outlets at 450mm. AFFL              1 8. 2 No. data outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking      

with Cat 6e data cabling to patch panel.               1 9. 1 No. telephone outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking  1 10. 1 x No. Clinical basin with elbow taps mounted on full height IPS panel        1   11. Lockable wall cupboard                   1 12. Worktop and lockable cupboard and draws underneath            1 13. Natural fresh air supply system                  1 14. Desk                        2 15. 1 x doctor’s chair                    3 16. 1 x patient chair                    3 17. Examination couch                    3 18. 1 x curtain and track                    2 19. 2 x bins                       4 20. 1 x computer                      4 21. Alcohol gel dispenser                    2 22. Paper towel dispenser                     2 23. Soap dispenser                      2 24. Door stops and hook                    1 25. Washable roller blinds to windows                1 

  

  

Page 45: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

44 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

TECHNICAL DATA SHEET  

ENVIRONMENTAL  29ºC d.b.50% RH. Summer  :   DESIGN   :  NOTES       ‐4ºC sat. Winter     :   DATA    : 

AIR          :      : Winter Temperature        (degC)  :   21 +/‐ 2c  :  Summer Temperature        (degC)  :   24 +/‐ 2c  :  Mechanical Ventilation: Supply      (m3/s)  :       : Mechanical Ventilation: Extract      (m3/s)  :      :  Pressure – Rel. to Adj. Space        :       :       Filtration (% Dust Sp Eff & % Arr)      :      :     Humidity          (%RH)  :      : 

    LIGHTING        :      : Service Illumination        (Lux)  :  500    : Service Illumination Night      (Lux)  :  NA    : Local Illumination        (Lux)  :  NA    : Colour Rendering Required        :  Ra 90    : Uniformity            :  0.6    : Standby Lighting Grade          :  NA    : Lighting Control           :  N    : 

    NOISE          :      : Acceptable Sound Level     [ (L10dB (A) ]  :   NR 35    : Speech Privacy Required        :       : Quality which cannot be tolerated      :      : 

    SAFETY          :      :  Accessible Hot Surface      Max temp (C)  :  43    :  Domestic Hot Water      Max temp (C)  :  41    :  

DESIGN CHARACTER       

Internal Finishes    : Walls (HBN 00‐10 B)             : Floor (HBN 00‐10 A) : Ceiling (HBN 00‐10 B)         : Heavy duty emulsion             : Sheet vinyl            : Heavy duty emulsion  

Door sets   : Solid core light beech veneer with lever handles and mortice lock with internal   thumb turn. 2 x kick plates 

 

 Windows (HBN 00‐10 D)  : Openable UPVC frame double glazed window with toughened glass (as    

existing). Film applied to window  

   

  

       

Page 46: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

45 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

PROJECT:  Adams House Medical Centre          Date: 4th July 2017 

ACTIVITY SPACE DATA SHEET: ADMIN OFFICE 

 

Version: 1          Revision:  

 EQUIPMENT             Group 1  Items to be provided and fixed by the builder e.g. sink, coat hook 

Group 2  Items supplied by Trust and fixed by builder e.g. soap dispenser 

Group 3  Loose equipment taking up significant floor space e.g. bed 

Group 4  Small items of loose equipment e.g. computer, waste bin 

  

                          Group  

1. Luminaires to CIBSE LG7                  1 2. Luminaires to CIBSE LG7 with integral emergency inverter/battery pack.        1 3. Patient alarm control panel.                  1 4. Staff alarm control panel (Eddison system)              1 5. Heating via Radiators LTHW                                                                                       1 6. Fire alarm combined smoke detector/sounder              1 7. 12 No. twin socket outlets at 920mm. AFFL mounted in 3 compartment dado trunking    1 8. 2 No. twin socket outlets at 450mm. AFFL              1 9. 12 No. data outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking with  

Cat 6e data cabling to patch panel.                1 10. 6 No. telephone outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking     1 11. Natural fresh air supply system                  1 12. 1 No. magnetic door lock and proximity sensor reader and associated power supply for the door 

 between admin and waiting area                1 13. 6 x computers                      4 14. 6 x Desks                      1 15. 6 x coat hooks                      1 16. 6 x office chairs                                 3 17. Blinds                        2 18. Blind tracks                      1 19. Full height storage cabinets                  3 

  

  

Page 47: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

46 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

TECHNICAL DATA SHEET  

ENVIRONMENTAL  29ºC d.b. 50% RH summer  :   DESIGN   :  NOTES       ‐4ºC sat. winter     :   DATA    : 

AIR          :      : Winter Temperature        (degC)  :   21 +/‐ 2c  :   Summer Temperature        (degC)  :   24 +/‐ 2c  :    Mechanical Ventilation: Supply      (m3/s)  :      :  Mechanical Ventilation: Extract      (m3/s)  :      : Pressure – Rel. to Adj. Space        :      : Filtration (% Dust Sp Eff & % Arr)      :      :     Humidity          (%RH)  :      : 

    LIGHTING        :      : Service Illumination        (Lux)  :  300 ‐ 500  : Service Illumination Night      (Lux)  :  NA    : Local Illumination        (Lux)  :  NA    : Colour Rendering Required        :  Ra 80    : Uniformity             :  0.6    : Standby Lighting Grade          :  NA    : Lighting Control           :  N    : 

    NOISE          :      : Acceptable Sound Level     [ (L10dB (A) ]  :    NR 35    : Speech Privacy Required        :      : Quality which cannot be tolerated      :      : 

    SAFETY          :      : Accessible Hot Surface      Max temp (C)  :  43    : Domestic Hot Water      Max temp (C)  :  41    : 

DESIGN CHARACTER       

Internal Finishes    : Walls (HBN 00‐10 B)             : Floor (HBN 00‐10 A) : Ceiling (HBN 00‐10 B)         : Heavy duty emulsion             : Sheet vinyl            : Heavy duty emulsion  

Door sets  : 2 x Solid core light beech veneer FD30S. 2 x Vision panel per door. Lever handles and mortice lock with internal thumb turn per door. 2 x kick plates per door. 2 x overhead door closers 

 

 Windows (HBN 00‐10 D)  : Openable UPVC frame double glazed window with toughened glass (as    

existing). Film applied to window  

           

Page 48: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

47 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

PROJECT:  Adams House Medical Centre          Date: 4th July 2017 

ACTIVITY SPACE DATA SHEET: PM OFFICE 

 

Version: 1          Revision:  

 EQUIPMENT             Group 1  Items to be provided and fixed by the builder e.g. sink, coat hook 

Group 2  Items supplied by Trust and fixed by builder e.g. soap dispenser 

Group 3  Loose equipment taking up significant floor space e.g. bed 

Group 4  Small items of loose equipment e.g. computer, waste bin 

  

                          Group  

1. Luminaires to CIBSE LG7                  1 2. Luminaire to CIBSE LG7 with integral emergency inverter/battery pack.        1 3. Heating via Radiators LTHW                                                                                     1 4. Fire alarm combined smoke detector/sounder              1 5. 3 No. twin socket outlets at 920mm. AFFL mounted in 3 compartment dado trunking    1 6. 2 No. twin socket outlets at 450mm. AFFL              1 7. 3 No. data outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking with  

Cat 6e data cabling to patch panel.                1 8. 1 No. telephone outlet socket at 920mm. AFFL mounted in 3 compartment dado trunking     1 9. Natural fresh air supply system                  1 10. 1 x computer                      4 11. 1 x Desk                      1 12. 1 x coat hook                      1 13. 1 x office chair                                  3 14. 2 x visitors chairs                    3 15. 2 x filing cabinets                    3 16. Blind                        2 17. Blind track                      1 18. Bookcase                      3 

  

  

Page 49: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

48 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

TECHNICAL DATA SHEET  

ENVIRONMENTAL  29ºC db. 50% RH Summer  :   DESIGN   :  NOTES       ‐4ºC sat. Winter     :   DATA    : 

AIR          :      :  Winter Temperature        (degC)  :   21 +/‐ 2c  :  Summer Temperature        (degC)  :   24 +/‐ 2c  : Mechanical Ventilation: Supply      (m3/s)  :       : Mechanical Ventilation: Extract      (m3/s)  :       :  Pressure – Rel. to Adj. Space        :      : Filtration (% Dust Sp Eff & % Arr)      :      : Humidity          (%RH)  :      : 

    LIGHTING        :      : Service Illumination        (Lux)  :  300‐ 500  : Service Illumination Night      (Lux)  :  NA    : Local Illumination        (Lux)  :  NA    : Colour Rendering Required        :  Ra 80    : Uniformity            :  0.6    : Standby Lighting Grade          :  NA    : Lighting Control           :  N    : 

    NOISE          :      : Acceptable Sound Level     [ (L10dB (A) ]  :   NR 35    : Speech Privacy Required        :       : Quality which cannot be tolerated      :      :     SAFETY          :      : Accessible Hot Surface      Max temp (C)  :  43    : Domestic Hot Water      Max temp (C)  :  41    : 

DESIGN CHARACTER       

Internal Finishes    : Walls (HBN 00‐10 B)             : Floor (HBN 00‐10 A) : Ceiling (HBN 00‐10 B)         : Heavy duty emulsion             : Sheet vinyl            : Heavy duty emulsion  

Doorsets  : Solid core light beech veneer FD30S. 2 x Vision panels. Lever handles and mortice lock with internal thumb turn. 2 x kick plates. Overhead door closer 

 

 Windows (HBN 00‐10 D)  : Openable UPVC frame double glazed window with toughened glass (as    

existing). Film applied to window  

            

Page 50: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

49 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

PROJECT:  Adams House Medical Centre          Date: 4th July 2017 

ACTIVITY SPACE DATA SHEET: STAFF ROOM 

 

Version: 1          Revision:  

 EQUIPMENT             Group 1  Items to be provided and fixed by the builder e.g. sink, coat hook 

Group 2  Items supplied by Trust and fixed by builder e.g. soap dispenser 

Group 3  Loose equipment taking up significant floor space e.g. bed 

Group 4  Small items of loose equipment e.g. computer, waste bin 

 

                           Group              

1. Luminaires to CIBSE LG7                  1 2. Luminaire with integral emergency inverter/battery pack.          1 3. Heating via Radiators LTHW                  1 4. Stainless steel sink with drainer with mixer tap              1 5. Sink base unit with drawer                  1 6. Kitchen base units with drawers                 1 7. Kitchen worktop                    1 8. Kitchen wall units                    1 9. Fire alarm combined heat detector/sounder              1 10. Natural fresh air supply system                  1 11. 3no twin socket outlets above worktop level              1 12. 2 No. twin socket outlets at 450mm. AFFL              1 13. Microwave                      4 14. Toaster                       4 15. Kettle                        4 16. Fridge Freezer                      1 17. Table                        3 18. 4 x dining chairs                     3 19. Large waste bin                     4  

  

  

Page 51: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

50 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

TECHNICAL DATA SHEET  

ENVIRONMENTAL  29ºC db. 50% RH Summer  :   DESIGN   :  NOTES       ‐4ºC sat. Winter     :   DATA    : 

AIR          :      :   Winter Temperature        (degC)  :   21 +/‐ 2c  :  Summer Temperature        (degC)  :   24 +/‐ 2c  : Mechanical Ventilation: Supply      (m3/s)  :      : Mechanical Ventilation: Extract      (m3/s)  :  0.030    : Pressure – Rel. to Adj. Space        :       : Filtration (% Dust Sp Eff & % Arr)      :       : Humidity          (%RH)  :      : 

    LIGHTING        :      : Service Illumination        (Lux)  :  300    : Service Illumination Night      (Lux)  :  NA    : Local Illumination        (Lux)  :  NA    : Colour Rendering Required        :  Ra 80    : Uniformity            :  0.6    : Standby Lighting Grade          :  NA    : Lighting Control           :  N    : 

    NOISE          :      : Acceptable Sound Level     [ (L10dB (A) ]  :   NR 35    : Speech Privacy Required        :      : Quality which cannot be tolerated      :      : 

    SAFETY          :      :  Accessible Hot Surface      Max temp (C)  :  43    :  Domestic Hot Water      Max temp (C)  :  41    : 

DESIGN CHARACTER       

Internal Finishes    : Walls (HBN 00‐10 B)  : Floor (HBN 00‐10 A)  : Ceiling (HBN 00‐10 B) : Heavy duty emulsion        Non slip vinyl          : Heavy duty emulsion        Altro whiterock splasback       

 

Doorsets   : Solid core light beech veneer FD30S. 2 x Vision panels. Lever handles and mortice lock with internal thumb turn. 2 x kick plates. Overhead door closer 

 

 Windows (HBN 00‐10 D)  : Openable UPVC frame double glazed window with toughened glass (as    

existing). Film applied to window  

           

Page 52: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

51 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

PROJECT:  Adams House Medical Centre          Date: 4th July 2017 

ACTIVITY SPACE DATA SHEET:  STAFF WC 

 

Version: 1          Revision:  

 EQUIPMENT             Group 1  Items to be provided and fixed by the builder e.g. sink, coat hook 

Group 2  Items supplied by Trust and fixed by builder e.g. soap dispenser 

Group 3  Loose equipment taking up significant floor space e.g. bed 

Group 4  Small items of loose equipment e.g. computer, waste bin 

 

  

                          Group  

1. Luminaire to CIBSE LG7 with integral emergency inverter/battery pack.        1 2. Electric Panel heating                    1 3. Wash hand basin with percussion outlets served from thermostatic mixing  

valve and isolation valves.                  1 4. W.C. with air push button flushing cistern.              1 5. Natural fresh air supply system                  1 6. 1 coat hook                                              1 7. toilet magazine dispenser                                         2 8. soap dispenser                                          2 9. Unbreakable Mirror300 x 450                                         1 10. alcohol gel dispenser                               2 11. Paper towel dispenser                    2 12. bin                        4 

  

  

Page 53: Appendix E – Room Data Sheets - Home - …fastracktenders.com/.../2013/02/tm07-Appendix-E-Room-Data-Sheets… · Appendix E – Room Data Sheets ... 1 | Page Adams House – 005547

   

52 | P a g e  A d a m s   H o u s e   –   0 0 5 5 4 7   –   R e v   1  

TECHNICAL DATA SHEET  

ENVIRONMENTAL  29ºC db. 50% RH Summer  :   DESIGN   :  NOTES       ‐4ºC sat. Winter     :   DATA    : 

AIR          :      : Winter Temperature        (degC)  :  18    :  Summer Temperature        (degC)  :  Uncontrolled  : Mechanical Ventilation: Supply      (m3/s)  :      : Mechanical Ventilation: Extract      (m3/s)  :   0.015    : Pressure – Rel. to Adj. Space        :       : Filtration (% Dust Sp Eff & % Arr)      :      : Humidity          (%RH)  :      : 

    LIGHTING        :      : Service Illumination        (Lux)  :  200    : Service Illumination Night      (Lux)  :  200    : Local Illumination        (Lux)  :  NA    : Colour Rendering Required        :  Ra 80    : Uniformity            :  0.6    : Standby Lighting Grade          :  NA    : Lighting Control           :  N    : 

    NOISE          :      : Acceptable Sound Level     [ (L10dB (A) ]  :   NR 35    : Speech Privacy Required        :      : Quality which cannot be tolerated      :      : 

    SAFETY          :      :  Accessible Hot Surface      Max temp (C)  :  43    :  Domestic Hot Water      Max temp (C)  :  41    :  

DESIGN CHARACTER       

Internal Finishes    : Walls (HBN 00‐10 B)         : Floor (HBN 00‐10 A) :  Ceiling (HBN 00‐10 B)         : Heavy duty emulsion          Non slip vinyl                    Heavy duty emulsion 

Altro whiterock splasback        

Doorsets   : Solid core light beech veneer door. Lever handles with indicator lock with external emergency access. 2 x kick plates 

 

 Windows (HBN 00‐10 D)  : Openable UPVC frame double glazed window with toughened glass (as    

existing). Film applied to window