App 27.75 Database

212
Application 27.75 Modbus Database Metric Gas DP/Pulse Meter Modbus Index Description Data Type Hex Value Access Notes Level A,B,C Locked FP Locked Serial Info: This data is accessed using Modbus function code 03 for reads and 16 for writes. Boolean data bit are packed 8 to a byte. 1 Custom Data Packet 1 Cust Pack 0001 R/W R/W, , R R (see indexes 3001 to 3040) 201 Custom Data Packet 2 Cust Pack 00C9 R/W R/W, , R R (see indexes 3041 to 3056) 401 Custom Data Packet 3 Cust Pack 0191 R/W R/W, , R R (see indexes 3057 to 3096) Info: This data is accessed using Modbus function code 03. For Method 2, the register count is the desired record number. 701 Archive 1 Data Record (Method 1) Archive 02BD R R, , R 702 Archive 2 Data Record (Method 1) Archive 02BE R R, , R 703 Archive 3 Data Record (Method 1) Archive 02BF R R, , R 704 Archive 4 Data Record (Method 1) Archive 02C0 R R, , R 705 Archive 5 Data Record (Method 1) Archive 02C1 R R, , R 706 Archive 6 Data Record (Method 1) Archive 02C2 R R, , R 707 Archive 7 Data Record (Method 1) Archive 02C3 R R, , R 708 Archive 8 Data Record (Method 1) Archive 02C4 R R, , R 709 Archive 9 Data Record (Method 1) Archive 02C5 R R, , R 710 Archive 10 Data Record (Method 1) Archive 02C6 R R, , R 711 Alarm Log Data Record (Method 1) Archive 02C7 R R, , R 712 Audit Log Data Record (Method 1) Archive 02C8 R R, , R 721 Archive 1 Data Record (Method 2) Archive 02D1 R R, , R 722 Archive 2 Data Record (Method 2) Archive 02D2 R R, , R 723 Archive 3 Data Record (Method 2) Archive 02D3 R R, , R 724 Archive 4 Data Record (Method 2) Archive 02D4 R R, , R 725 Archive 5 Data Record (Method 2) Archive 02D5 R R, , R 726 Archive 6 Data Record (Method 2) Archive 02D6 R R, , R 727 Archive 7 Data Record (Method 2) Archive 02D7 R R, , R 728 Archive 8 Data Record (Method 2) Archive 02D8 R R, , R 729 Archive 9 Data Record (Method 2) Archive 02D9 R R, , R 730 Archive 10 Data Record (Method 2) Archive 02DA R R, , R 731 Alarm Log Data Record (Method 2) Archive 02DB R R, , R 732 Audit Log Data Record (Method 2) Archive 02DC R R, , R Page1 of 212 2/1/2013

Transcript of App 27.75 Database

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    Info:ThisdataisaccessedusingModbusfunctioncode03forreadsand16forwrites.Booleandatabitarepacked8toabyte.

    1 CustomDataPacket1 CustPack 0001 R/W R/W,,R R(seeindexes3001to3040)

    201 CustomDataPacket2 CustPack 00C9 R/W R/W,,R R(seeindexes3041to3056)

    401 CustomDataPacket3 CustPack 0191 R/W R/W,,R R(seeindexes3057to3096)

    Info:ThisdataisaccessedusingModbusfunctioncode03.ForMethod2,theregistercountisthedesiredrecordnumber.

    701 Archive1DataRecord(Method1) Archive 02BD R R,,R702 Archive2DataRecord(Method1) Archive 02BE R R,,R703 Archive3DataRecord(Method1) Archive 02BF R R,,R704 Archive4DataRecord(Method1) Archive 02C0 R R,,R705 Archive5DataRecord(Method1) Archive 02C1 R R,,R706 Archive6DataRecord(Method1) Archive 02C2 R R,,R707 Archive7DataRecord(Method1) Archive 02C3 R R,,R708 Archive8DataRecord(Method1) Archive 02C4 R R,,R709 Archive9DataRecord(Method1) Archive 02C5 R R,,R710 Archive10DataRecord(Method1) Archive 02C6 R R,,R711 AlarmLogDataRecord(Method1) Archive 02C7 R R,,R712 AuditLogDataRecord(Method1) Archive 02C8 R R,,R

    721 Archive1DataRecord(Method2) Archive 02D1 R R,,R722 Archive2DataRecord(Method2) Archive 02D2 R R,,R723 Archive3DataRecord(Method2) Archive 02D3 R R,,R724 Archive4DataRecord(Method2) Archive 02D4 R R,,R725 Archive5DataRecord(Method2) Archive 02D5 R R,,R726 Archive6DataRecord(Method2) Archive 02D6 R R,,R727 Archive7DataRecord(Method2) Archive 02D7 R R,,R728 Archive8DataRecord(Method2) Archive 02D8 R R,,R729 Archive9DataRecord(Method2) Archive 02D9 R R,,R730 Archive10DataRecord(Method2) Archive 02DA R R,,R731 AlarmLogDataRecord(Method2) Archive 02DB R R,,R732 AuditLogDataRecord(Method2) Archive 02DC R R,,R

    Page1of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    751 Archive1Date/TimeRecord(Method1) ArchDate 02EF R R,,R752 Archive2Date/TimeRecord(Method1) ArchDate 02F0 R R,,R753 Archive3Date/TimeRecord(Method1) ArchDate 02F1 R R,,R754 Archive4Date/TimeRecord(Method1) ArchDate 02F2 R R,,R755 Archive5Date/TimeRecord(Method1) ArchDate 02F3 R R,,R756 Archive6Date/TimeRecord(Method1) ArchDate 02F4 R R,,R757 Archive7Date/TimeRecord(Method1) ArchDate 02F5 R R,,R758 Archive8Date/TimeRecord(Method1) ArchDate 02F6 R R,,R759 Archive9Date/TimeRecord(Method1) ArchDate 02F7 R R,,R760 Archive10Date/TimeRecord(Method1) ArchDate 02F8 R R,,R

    761 AlarmLogDate/TimeRecord(Method1) ArchDate 02F9 R R,,R762 AuditLogDate/TimeRecord(Method1) ArchDate 02FA R R,,R

    771 Archive1Date/TimeRecord(Method2) ArchDate 0303 R R,,R772 Archive2Date/TimeRecord(Method2) ArchDate 0304 R R,,R773 Archive3Date/TimeRecord(Method2) ArchDate 0305 R R,,R774 Archive4Date/TimeRecord(Method2) ArchDate 0306 R R,,R775 Archive5Date/TimeRecord(Method2) ArchDate 0307 R R,,R776 Archive6Date/TimeRecord(Method2) ArchDate 0308 R R,,R777 Archive7Date/TimeRecord(Method2) ArchDate 0309 R R,,R778 Archive8Date/TimeRecord(Method2) ArchDate 030A R R,,R779 Archive9Date/TimeRecord(Method2) ArchDate 030B R R,,R780 Archive10Date/TimeRecord(Method2) ArchDate 030C R R,,R

    781 AlarmLogDate/TimeRecord(Method2) ArchDate 030D R R,,R782 AuditLogDate/TimeRecord(Method2) ArchDate 030E R R,,R

    Indexes1001through1024indicatethestatusoftheflowcomputerphysicaldigitalI/Opoints.

    Info:NeversetaphysicalI/OpointwhichhasbeenassignedasaninputasthiscouldcauseaDCvoltagetoappearontheinputterminalsofthatpointwhichmayconflictwithanyvoltagealreadypresentonthoseterminals.

    1001 1024DigitalI/OPoint124 Boolean 03E9 R/W R/W,,R R

    Indexes1025through1088containtoresultsofprogrammablebooleanstatements25through88.

    Info:BooleandataisaccessedusingModbusfunctioncodes01forreadsand05forsinglepointwritesand15formultiplepointwrites.Page2of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    Booleandataispacked8pointstoabytewhenreading.

    Info:Booleandatapoints10571088areavailableforuseralarms.Example:1030:1088=10021088:HighFilterDP.Make1088followsthestatusofDigitalPoint#2.Whentrue,AlarmmessagewillbeplacedintheAlarmlogandonAlarmscreen.

    1025 1088BooleanPoint2588 Boolean 0401 R/W Youmayreadfromorwritetothesevariables,butanythingthatyouwritemaybeoverwrittenbytheflowcomputerdependinguponthelogicfunctionsprogrammedintothelogicstatement.

    R/W,,R R

    1089 1099ProgrammablePulses Boolean 0441 R Points1089to1099arepairedwithfloatingpointvariables7089to7099.Numericdataplacedin7089canbeoutputaspulsesbyassigningadigitalI/Opointto1089.

    R,,R R

    Info:Registers1n011n04(n=1,2,3,4)&18011804UsedtoassignaccumulatorstofrontpanelcountersordigitalI/Opoint.

    1101 Meter1GrossPulses Boolean 044D R UsedtoassignaccumulatortothefrontpanelcountersordigitalI/Opoints.

    R,,R R

    1102 Meter1Net(GSV)Pulses Boolean 044E R UsedtoassignaccumulatortothefrontpanelcountersordigitalI/Opoints.

    R,,R R

    1103 Meter1MassPulses Boolean 044F R UsedtoassignaccumulatortothefrontpanelcountersordigitalI/Opoints.

    R,,R R

    1104 Meter1EnergyPulses Boolean 0450 R UsedtoassignaccumulatortothefrontpanelcountersordigitalI/Opoints.

    R,,R R

    1105 Meter1ActiveFlag Boolean 0451 R Trueifflowpulsesabovethresholdfrequencyordpabovelowcutoff.

    R,,R R

    1106 Meter1isbeingProved Boolean 0452 R Activatesduringprovingofthismeter. R,,R R

    Page3of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    1107 Meter1NewAlarmFlag Boolean 0453 R Clearsifalarmacknowledged. R,,R R

    1108 Meter1BatchEndAcknowledge(ToggleON/OFF)

    Boolean 0454 R R,,R R

    1109 Meter1GCCommunicationAlarm Boolean 0455 R R,,R R1111 Meter1AppliedAutomationGCProblem Boolean 0457 R R,,R R

    1112 Meter1BatchEndAcknowledge(500mS) Boolean 0458 R R,,R R

    1113 Meter1CalculationOutofRangeAlarm Boolean 0459 R R,,R R1114 Meter1DensityPressureOverrideInUse Boolean 045A R R,,R R

    1115 Meter1DPOverrideInUse Boolean 045B R R,,R R1116 Meter1TemperatureOverrideInUse Boolean 045C R R,,R R1117 Meter1PressureOverrideInUse Boolean 045D R R,,R R1118 Meter1DensityOverrideInUse Boolean 045E R R,,R R1119 Meter1DensityTemperatureOverrideIn

    UseBoolean 045F R R,,R R

    1120 Meter1FlowrateLowLowAlarm Boolean 0460 R Alarmcheckingisbasedontheuserselectednetormassflowrate.

    R,,R R

    1121 Meter1FlowrateLowAlarm Boolean 0461 R Alarmcheckingisbasedontheuserselectednetormassflowrate.

    R,,R R

    1122 Meter1FlowrateHighAlarm Boolean 0462 R Alarmcheckingisbasedontheuserselectednetormassflowrate.

    R,,R R

    1123 Meter1FlowrateHighHighAlarm Boolean 0463 R Alarmcheckingisbasedontheuserselectednetormassflowrate.

    R,,R R

    1124 Meter1TemperatureTransducerFailLow

    Boolean 0464 R R,,R R

    1125 Meter1TemperatureLowAlarm Boolean 0465 R R,,R R1126 Meter1TemperatureHighAlarm Boolean 0466 R R,,R R

    Page4of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    1127 Meter1TemperatureTransducerFailHigh

    Boolean 0467 R R,,R R

    1128 Meter1PressureTransducerFailLow Boolean 0468 R R,,R R1129 Meter1PressureLowAlarm Boolean 0469 R R,,R R1130 Meter1PressureHighAlarm Boolean 046A R R,,R R1131 Meter1PressureTransducerFailHigh Boolean 046B R R,,R R1132 Meter1Gravity/DensityTransducerFail

    LowBoolean 046C R R,,R R

    1133 Meter1Gravity/DensityLowAlarm Boolean 046D R R,,R R1134 Meter1Gravity/DensityHighAlarm Boolean 046E R R,,R R1135 Meter1Gravity/DensityTransducerFail

    HighBoolean 046F R R,,R R

    1136 Meter1Dens.TemperatureTransducerFailLow

    Boolean 0470 R R,,R R

    1137 Meter1Dens.TemperatureLowAlarm Boolean 0471 R R,,R R1138 Meter1Dens.TemperatureHighAlarm Boolean 0472 R R,,R R1139 Meter1Dens.TemperatureTransducer

    FailHighBoolean 0473 R R,,R R

    1140 Meter1DPLowRangeTransducerFailLow

    Boolean 0474 R R,,R R

    1141 Meter1DPLowRangeTransducerFailHigh

    Boolean 0475 R R,,R R

    1142 Meter1DPHighRangeTransducerFailLow

    Boolean 0476 R R,,R R

    1143 Meter1DPHighRangeTransducerFailHigh

    Boolean 0477 R R,,R R

    1144 Meter1Dens.PressureTransducerFailLow

    Boolean 0478 R R,,R R

    Page5of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    1145 Meter1Dens.PressureLowAlarm Boolean 0479 R R,,R R1146 Meter1Dens.PressureHighAlarm Boolean 047A R R,,R R1147 Meter1Dens.PressureTransducerFail

    HighBoolean 047B R R,,R R

    1148 Meter1DualPulsecomparatorAlarm Boolean 047C R R,,R R1149 Meter1DualPulseChannelAFailed Boolean 047D R R,,R R1150 Meter1DualPulseChannelBFailed Boolean 047E R R,,R R1151 Meter1DualPulseChannelAorBFailed Boolean 047F R R,,R R

    1152 Meter1DPLowRangeisSelected Boolean 0480 R R,,R R1153 Meter1DPHighRangeisSelected Boolean 0481 R R,,R R1154 Meter1AnyAlarm(ExistingorNew

    Alarm)Boolean 0482 R R,,R R

    1155 Meter1MeterInactive500mSFlag Boolean 0483 R R,,R R1156 Meter1BatchInProgressFlag Boolean 0484 R R,R,R R1157 Meter1BatchStartAcknowledge Boolean 0485 R Setfor500mSwhen17271730commandisreceived. R,R,R R

    1158 Meter1BatchSuspended Boolean 0486 R Truewhenbatchisinprogressbutmeterisinactive. R,R,R R

    1159 Meter1NMiGrossPulses Boolean 0487 R R,,R R

    1160 Meter1NMiNetPulses Boolean 0488 R R,,R R1161 Meter1NMiGrossErrorPulses Boolean 0489 R R,,R R1162 Meter1NMiNetErrorPulses Boolean 048A R R,,R R1163 Meter1NMiAccountableAlarmStatus Boolean 048B R R,,R R1165 Meter1KonbsbergUsesCalculated

    IncrementFlagBoolean 048D R R,,R R

    1166 Meter1KonbsbergUsesPulseSignalFlag Boolean 048E R R,,R R

    Page6of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    1167 Meter1KrohneValidationOKStatus(1=OK)

    Boolean 048F R R,,R R

    1168 Meter1MidRangeDPFailedLowAlarm Boolean 0490 R R,,R R1169 Meter1MidRangeDPFailedHighAlarm Boolean 0491 R R,,R R

    1170 Meter1DayEndFlag(500mS) Boolean 0492 R R,,R R1171 Meter1DPMidRangeisSelected Boolean 0493 R R,,R R1173 Meter1HARTdevicetypemismatchthe

    LowRangeDPassignmentBoolean 0495 R R,,R R

    1174 Meter1HARTdevicetypemismatchtheTemperatureassignment

    Boolean 0496 R R,,R R

    1175 Meter1HARTdevicetypemismatchthePressureassignment

    Boolean 0497 R R,,R R

    1177 Meter1CorrectableTotalizerErrorOccurrec

    Boolean 0499 R PrimarytotalizerchecksumerrorsecondarytotalizerchecksumOK.

    R,,R R

    1178 Meter1NonCorrectableTotalizerError Boolean 049A R Primaryandsecondarytotalizersresettozerobecausebothchecksumincorrect.

    R,,R R

    1179 Meter1DifferentialPressureInUseLowAlarm

    Boolean 049B R R,,R R

    1180 Meter1DifferentialPressureInUseHighAlarm

    Boolean 049C R R,,R R

    1183 Meter1RosemountMVDPaboveUpperRange+10%

    Boolean 049F R R,,R R

    1184 Meter1RosemountMVDPbelowLowerRange10%

    Boolean 04A0 R R,,R R

    1185 Meter1RosemountMVSPaboveUpperRange+10%

    Boolean 04A1 R R,,R R

    Page7of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    1186 Meter1RosemountMVSPbelowLowerRange10%

    Boolean 04A2 R R,,R R

    1187 Meter1RosemountMVSPsensorshorted

    Boolean 04A3 R R,,R R

    1188 Meter1RosemountMVSPisopenbridge Boolean 04A4 R R,,R R

    1189 Meter1RosemountMVPTaboveUpperRange+10%

    Boolean 04A5 R R,,R R

    1190 Meter1RosemountMVPTbelowLowerRange10%

    Boolean 04A6 R R,,R R

    1191 Meter1RosemountMVRTDisdisconnected

    Boolean 04A7 R R,,R R

    1192 Meter1RosemountMVsensorTaboveUpperLimit

    Boolean 04A8 R R,,R R

    1193 Meter1RosemountMVsensorTbelowLowerLimit

    Boolean 04A9 R R,,R R

    1194 Meter1RosemountMVsensorerror Boolean 04AA R R,,R R1195 Meter1RosemountMVWriteProtect

    StatusBoolean 04AB R R,,R R

    1196 Meter1RosemountMVNoCommunicationFlag

    Boolean 04AC R R,,R R

    1197 Meter1inMaintenanceMode Boolean 04AD R R,,R R1198 Meter1HARTdevicetypemismatchthe

    DensityTempassignmentBoolean 04AE R R,,R R

    1199 Meter1HARTdevicetypemismatchtheDensityPressureassignment

    Boolean 04AF R R,,R R

    Page8of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    1201 1299Meter2Status(Sameas11011199)

    Boolean 04B1 R R,,R R

    1301 1399Meter3Status(Sameas11011199)

    Boolean 0515 R R,,R R

    1401 1499Meter4Status(Sameas11011199)

    Boolean 0579 R R,,R R

    Indexes1501through1699areuncommittedbooleanflagswhichcanbeusedasscratchpadvariablesusedtostoreresultsofbooleanstatementsordatareceivedoveramodbuslink.

    1501 1649ScratchpadBoolean Boolean 05DD R/W R/W,,R R1650 1699ScratchpadOneshot(2Sec) Boolean 0672 R/W Thesebooleanpointsremainactivatedforexactly2

    secondsaftertheyhavebeenwrittento.R/W,,R R

    Thefollowingcommandregistersmostareedgetriggeredandresetautomaticallyaftertheactionoccurs.ie:Yousetthemandforgetaboutthem.

    Info:Registers17001800HardwareInteraction:UnreliableoperationwillresultifacommandwhichhasbeenassignedtoadigitalI/OpointdirectlyalsoneedstobeactivThisisbecausetheON/OffstateofthedigitalI/Opointoverwritesthecommandpointevery100msecandmostcommandpointactionsareonlytriggeredevery500msec

    1702 EndBatchStation Boolean 06A6 R/W R/W,W,R Y R1703 EndBatchMeter1 Boolean 06A7 R/W R/W,W,R Y R1704 EndBatchMeter2 Boolean 06A8 R/W R/W,W,R Y R1705 EndBatchMeter3 Boolean 06A9 R/W R/W,W,R Y R1706 EndBatchMeter4 Boolean 06AA R/W R/W,W,R Y R1708 ProveRequestMeter1 Boolean 06AC R/W R/W,W,R Y R1709 ProveRequestMeter2 Boolean 06AD R/W R/W,W,R Y R1710 ProveRequestMeter3 Boolean 06AE R/W R/W,W,R Y R1711 ProveRequestMeter4 Boolean 06AF R/W R/W,W,R Y R1712 AlarmAcknowledge Boolean 06B0 R/W R/W,,R Y R1713 ResetPowerFail Boolean 06B1 R/W R/W,,R R1714 TrialProveRequestMeter1 Boolean 06B2 R/W R/W,W,R Y R1715 TrialProveRequestMeter2 Boolean 06B3 R/W R/W,W,R Y R1716 TrialProveRequestMeter3 Boolean 06B4 R/W R/W,W,R Y R

    Page9of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    1717 TrialProveRequestMeter4 Boolean 06B5 R/W R/W,W,R Y R1718 ProveAbortRequest Boolean 06B6 R/W R/W,W,R Y R1719 RequestSnapshotReport Boolean 06B7 R/W R/W,,R Y R1720 SendSnapshotReporttoModbusBuffer Boolean 06B8 R/W R/W,,R R1721 SendAlarmReporttoModbusBuffer Boolean 06B9 R/W R/W,,R R1722 PID1Permissive Boolean 06BA R/W R/W,,R R1723 PID2Permissive Boolean 06BB R/W R/W,,R R1724 PID3Permissive Boolean 06BC R/W R/W,,R R1725 PID4Permissive Boolean 06BD R/W R/W,,R R1732 AlarmAcknowledgeMeter1 Boolean 06C4 R/W R/W,,R R1733 AlarmAcknowledgeMeter2 Boolean 06C5 R/W R/W,,R R1734 AlarmAcknowledgeMeter3 Boolean 06C6 R/W R/W,,R R1735 AlarmAcknowledgeMeter4 Boolean 06C7 R/W R/W,,R R1736 DisableMeter1 Boolean 06C8 R/W R/W,,R R1737 DisableMeter2 Boolean 06C9 R/W R/W,,R R1738 DisableMeter3 Boolean 06CA R/W R/W,,R R1739 DisableMeter4 Boolean 06CB R/W R/W,,R R1740 SendTimeandDatetoApplied

    AutomationG.C.Boolean 06CC R/W R/W,,R R

    1741 RemoteUpArrowKey Boolean 06CD R/W R/W,,R R1742 RemoteDownArrowKey Boolean 06CE R/W R/W,,R R1751 FreezeAllAnalogInputs Boolean 06D7 R/W R/W,,R R1752 PID1SecondPermissive Boolean 06D8 R/W R/W,,R R1753 PID2SecondPermissive Boolean 06D9 R/W R/W,,R R1754 PID3SecondPermissive Boolean 06DA R/W R/W,,R R1755 PID4SecondPermissive Boolean 06DB R/W R/W,,R R1756 ChangeOrificePlateMeter1 Boolean 06DC R/W R/W,,R N R1757 ChangeOrificePlateMeter2 Boolean 06DD R/W R/W,,R N R1758 ChangeOrificePlateMeter3 Boolean 06DE R/W R/W,,R N R1759 ChangeOrificePlateMeter4 Boolean 06DF R/W R/W,,R N R1760 FreezeAllTotalizers Boolean 06E0 R/W R/W,,R R1761 DisableStation Boolean 06E1 R/W R/W,,R R1762 RemotePrintPreviousBatchReport1 Boolean 06E2 R/W R/W,,R R1763 RemotePrintPreviousBatchReport2 Boolean 06E3 R/W R/W,,R R1764 RemotePrintPreviousBatchReport3 Boolean 06E4 R/W R/W,,R R1765 RemotePrintPreviousBatchReport4 Boolean 06E5 R/W R/W,,R R1766 RemotePrintPreviousBatchReport5 Boolean 06E6 R/W R/W,,R R

    Page10of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    1767 RemotePrintPreviousBatchReport6 Boolean 06E7 R/W R/W,,R R1768 RemotePrintPreviousBatchReport7 Boolean 06E8 R/W R/W,,R R1769 RemotePrintPreviousBatchReport8 Boolean 06E9 R/W R/W,,R R1770 RemotePrintPreviousDailyReport1 Boolean 06EA R/W R/W,,R R1771 RemotePrintPreviousDailyReport2 Boolean 06EB R/W R/W,,R R1772 RemotePrintPreviousDailyReport3 Boolean 06EC R/W R/W,,R R1773 RemotePrintPreviousDailyReport4 Boolean 06ED R/W R/W,,R R1774 RemotePrintPreviousDailyReport5 Boolean 06EE R/W R/W,,R R1775 RemotePrintPreviousDailyReport6 Boolean 06EF R/W R/W,,R R1776 RemotePrintPreviousDailyReport7 Boolean 06F0 R/W R/W,,R R1777 RemotePrintPreviousDailyReport8 Boolean 06F1 R/W R/W,,R R1778 RemotePrintPreviousProveReport1 Boolean 06F2 R/W R/W,,R R1779 RemotePrintPreviousProveReport2 Boolean 06F3 R/W R/W,,R R1780 RemotePrintPreviousProveReport3 Boolean 06F4 R/W R/W,,R R1781 RemotePrintPreviousProveReport4 Boolean 06F5 R/W R/W,,R R1782 RemotePrintPreviousProveReport5 Boolean 06F6 R/W R/W,,R R1783 RemotePrintPreviousProveReport6 Boolean 06F7 R/W R/W,,R R1784 RemotePrintPreviousProveReport7 Boolean 06F8 R/W R/W,,R R1785 RemotePrintPreviousProveReport8 Boolean 06F9 R/W R/W,,R R1786 RemotePrintAlarmReport Boolean 06FA R/W R/W,,R R1788 PID1ShutdownCommand Boolean 06FC R/W R/W,,R Y R1789 PID2ShutdownCommand Boolean 06FD R/W R/W,,R Y R1790 PID3ShutdownCommand Boolean 06FE R/W R/W,,R Y R1791 PID4ShutdownCommand Boolean 06FF R/W R/W,,R Y R1792 PID1StopCommand Boolean 0700 R/W R/W,,R Y R1793 PID2StopCommand Boolean 0701 R/W R/W,,R Y R1794 PID3StopCommand Boolean 0702 R/W R/W,,R Y R1795 PID4StopCommand Boolean 0703 R/W R/W,,R Y R1796 ArchiveRunCommand Boolean 0704 R/W R/W,,R N R1797 ReconfigureArchiveFileCommand Boolean 0705 R/W R/W,,R N R1801 StationPositiveGrossPulses Boolean 0709 R R,,R R1802 StationPositiveNet(GSV)Pulses Boolean 070A R R,,R R1803 StationPositiveMassPulses Boolean 070B R R,,R R1804 StationPositiveEnergyPulses Boolean 070C R R,,R R1805 StationNegativeGrossVolume Boolean 070D R R,,R R1806 StationNegativeNetVolume(NSV) Boolean 070E R R,,R R1807 StationNegativeMass Boolean 070F R R,,R R1808 StationNegativeEnergy Boolean 0710 R R,,R R

    Page11of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    1809 StationFlowrateLowLowAlarm Boolean 0711 R Alarmcheckingisbasedontheuserselectednetormassflowrate.

    R,,R R

    1810 StationFlowrateLowAlarm Boolean 0712 R Alarmcheckingisbasedontheuserselectednetormassflowrate.

    R,,R R

    1811 StationFlowrateHighAlarm Boolean 0713 R Alarmcheckingisbasedontheuserselectednetormassflowrate.

    R,,R R

    1812 StationFlowrateHighHighAlarm Boolean 0714 R Alarmcheckingisbasedontheuserselectednetormassflowrate.

    R,,R R

    1815 StationAnyAlarm(ExistingorNewAlarm)

    Boolean 0717 R R,,R R

    1816 StationNewAlarmFlag Boolean 0718 R R,,R R1817 StationBatchEndAcknowledge(Toggle

    ON/OFF)Boolean 0719 R R,,R R

    1818 StationFatalAlarmfromGasChromatograph

    Boolean 071A R R,,R R

    1819 G.C.Mole%OverrideinUse Boolean 071B R R,,R R1820 G.C.CommunicationAlarm(Lost

    Communication)Boolean 071C R R,,R R

    1824 RunSwitchingThresholdFlag1 Boolean 0720 R R,,R R1825 RunSwitchingThresholdFlag2 Boolean 0721 R R,,R R1826 RunSwitchingThresholdFlag3 Boolean 0722 R R,,R R1827 LeakDetectionFreezeCommandWas

    ReceivedBoolean 0723 R R,,R R

    1828 ContractDayStartFlag(500mS) Boolean 0724 R R,,R R1829 PowerFailedFlag(Setafterpowerup) Boolean 0725 R R,,R R1830 PrintBufferFullFlag Boolean 0726 R R,,R R1831 HourStartFlag(500mS) Boolean 0727 R R,,R R

    Page12of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    1832 WeekStartFlag(SetatContractDayStartMonday)

    Boolean 0728 R R,,R R

    1833 MonthStartFlag(DayStart1stDayofMonth)

    Boolean 0729 R R,,R R

    1834 YearStartFlag(DayStartJan.1st) Boolean 072A R R,,R R1835 StationBatchEndFlag(500mS) Boolean 072B R R,,R R1836 LocalSnapshotPrinted(500mS) Boolean 072C R R,,R R1837 EPROMErrorDetected Boolean 072D R R,,R R1838 PeertoPeerMasterFlag Boolean 072E R R,,R R

    Info:Registers1841841Thesystemlimitsthemaximumnumberofstatementevaluationsto100toprotectagainstpossiblelockupsduetorecursiveloops.Anyadditionalstatementevaluationsareignored.

    1840 BooleanStatementAlarm Boolean 0730 R Thesystemlimitsthemaximumnumberofstatementevaluationsto100toprotectagainstpossiblelockupsduetorecursiveloops.

    R,,R R

    1841 VariableStatementAlarm Boolean 0731 R Thesystemlimitsthemaximumnumberofstatementevaluationsto100toprotectagainstpossiblelockupsduetorecursiveloops.

    R,,R R

    1842 PeertoPeerTransaction1CommunicationError

    Boolean 0732 R R,,R R

    1843 PeertoPeerTransaction2CommunicationError

    Boolean 0733 R Ifaslaveisinvolvedinmultipletransactionswhichfail,onlythefirstwillbeflagged.

    R,,R R

    1844 PeertoPeerTransaction3CommunicationError

    Boolean 0734 R Ifaslaveisinvolvedinmultipletransactionswhichfail,onlythefirstwillbeflagged.

    R,,R R

    1845 PeertoPeerTransaction4CommunicationError

    Boolean 0735 R Ifaslaveisinvolvedinmultipletransactionswhichfail,onlythefirstwillbeflagged.

    R,,R R

    1846 PeertoPeerTransaction5CommunicationError

    Boolean 0736 R Ifaslaveisinvolvedinmultipletransactionswhichfail,onlythefirstwillbeflagged.

    R,,R R

    Page13of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    1847 PeertoPeerTransaction6CommunicationError

    Boolean 0737 R Ifaslaveisinvolvedinmultipletransactionswhichfail,onlythefirstwillbeflagged.

    R,,R R

    1848 PeertoPeerTransaction7CommunicationError

    Boolean 0738 R Ifaslaveisinvolvedinmultipletransactionswhichfail,onlythefirstwillbeflagged.

    R,,R R

    1849 PeertoPeerTransaction8CommunicationError

    Boolean 0739 R Ifaslaveisinvolvedinmultipletransactionswhichfail,onlythefirstwillbeflagged.

    R,,R R

    1850 PeertoPeerTransaction9CommunicationError

    Boolean 073A R Ifaslaveisinvolvedinmultipletransactionswhichfail,onlythefirstwillbeflagged.

    R,,R R

    1851 PeertoPeerTransaction10CommunicationError

    Boolean 073B R Ifaslaveisinvolvedinmultipletransactionswhichfail,onlythefirstwillbeflagged.

    R,,R R

    1852 PeertoPeerTransaction11CommunicationError

    Boolean 073C R Ifaslaveisinvolvedinmultipletransactionswhichfail,onlythefirstwillbeflagged.

    R,,R R

    1853 PeertoPeerTransaction12CommunicationError

    Boolean 073D R Ifaslaveisinvolvedinmultipletransactionswhichfail,onlythefirstwillbeflagged.

    R,,R R

    1854 PeertoPeerTransaction13CommunicationError

    Boolean 073E R Ifaslaveisinvolvedinmultipletransactionswhichfail,onlythefirstwillbeflagged.

    R,,R R

    1855 PeertoPeerTransaction14CommunicationError

    Boolean 073F R Ifaslaveisinvolvedinmultipletransactionswhichfail,onlythefirstwillbeflagged.

    R,,R R

    1856 PeertoPeerTransaction15CommunicationError

    Boolean 0740 R Ifaslaveisinvolvedinmultipletransactionswhichfail,onlythefirstwillbeflagged.

    R,,R R

    1857 PeertoPeerTransaction16CommunicationError

    Boolean 0741 R Ifaslaveisinvolvedinmultipletransactionswhichfail,onlythefirstwillbeflagged.

    R,,R R

    1858 DayStartFlag(@00:00:00)for500mS Boolean 0742 R R,,R R1859 WeekStartFlag(@00:00:00Monday) Boolean 0743 R R,,R R1860 MonthStartFlag(@00:00:001stDayof

    Month)Boolean 0744 R R,,R R

    Page14of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    1861 YearStartFlag(@00:00:00Jan.1st) Boolean 0745 R R,,R R1862 Ref.SGTransducerFailedtoLow Boolean 0746 R R,,R R1863 Ref.SGLowAlarm Boolean 0747 R R,,R R1864 Ref.SGHighAlarm Boolean 0748 R R,,R R1865 Ref.SGTransducerFailedtoHigh Boolean 0749 R R,,R R1866 Mol%NitrogenTransducerFailedtoLow Boolean 074A R R,,R R

    1867 Mol%NitrogenLowAlarm Boolean 074B R R,,R R1868 Mol%NitrogenHighAlarm Boolean 074C R R,,R R1869 Mol%NitrogenTransducerFailedtoHigh Boolean 074D R R,,R R

    1870 Mol%CO2TransducerFailedtoLow Boolean 074E R R,,R R1871 Mol%CO2LowAlarm Boolean 074F R R,,R R1872 Mol%CO2HighAlarm Boolean 0750 R R,,R R1873 Mol%CO2TransducerFailedtoHigh Boolean 0751 R R,,R R1874 HeatingValueTransducerFailedtoLow Boolean 0752 R R,,R R1875 HeatingValueLowAlarm Boolean 0753 R R,,R R1876 HeatingValueHighAlarm Boolean 0754 R R,,R R1877 HeatingValueTransducerFailedtoHigh Boolean 0755 R R,,R R

    1878 PreviousBatchAlarmOccurredFlag Boolean 0756 R R,,R R1879 PreviousBatchRolloverOccurredFlag Boolean 0757 R R,,R R1880 PreviousDailyRolloverOccurredFlag Boolean 0758 R R,,R R1881 G.C.Mol%outofdeviationalarm Boolean 0759 R R,,R R1882 DayEndFlag(500mS) Boolean 075A R R,,R R1883 AuxiliaryInput1TransducerFailedto

    LowBoolean 075B R R,,R R

    1884 AuxiliaryInput1LowAlarm Boolean 075C R R,,R R1885 AuxiliaryInput1HighAlarm Boolean 075D R R,,R R1886 AuxiliaryInput1TransducerFailedto

    HighBoolean 075E R R,,R R

    1887 AuxiliaryInput2TransducerFailedtoLow

    Boolean 075F R R,,R R

    Page15of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    1888 AuxiliaryInput2LowAlarm Boolean 0760 R R,,R R1889 AuxiliaryInput2HighAlarm Boolean 0761 R R,,R R1890 AuxiliaryInput2TransducerFailedto

    HighBoolean 0762 R R,,R R

    1891 AuxiliaryInput3TransducerFailedtoLow

    Boolean 0763 R R,,R R

    1892 AuxiliaryInput3LowAlarm Boolean 0764 R R,,R R1893 AuxiliaryInput3HighAlarm Boolean 0765 R R,,R R1894 AuxiliaryInput3TransducerFailedto

    LowBoolean 0766 R R,,R R

    1895 AuxiliaryInput4TransducerFailedtoHigh

    Boolean 0767 R R,,R R

    1896 AuxiliaryInput4LowAlarm Boolean 0768 R R,,R R1897 AuxiliaryInput4HighAlarm Boolean 0769 R R,,R R1898 AuxiliaryInput4TransducerFailedto

    HighBoolean 076A R R,,R R

    Proverbooleans(2nddigitofindexis9whichdefinesasprover)

    1909 ProverTemperatureUnstableProveAborted

    Boolean 0775 R R,,R R

    1910 TemperatureDeviationBetweenPv&MeterExceed

    Boolean 0776 R R,,R R

    1911 ProveSequenceCompleted(StayTrueUntilNextPv)

    Boolean 0777 R R,,R R

    1912 ProveSequenceAbortedDidNotComplete

    Boolean 0778 R R,,R R

    1919 RunRepeatabilityDeviationLimitExceeded

    Boolean 077F R R,,R R

    Page16of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    1921 FlowrateWasUnstableProveAborted Boolean 0781 R R,,R R1923 MeterFactorObtainedWasNot

    ImplementedBoolean 0783 R R,,R R

    1924 ProvingMeterWasNotActiveProveAborted

    Boolean 0784 R R,,R R

    1928 ProveSequenceSuccessfullyCompletedFlag(500mS)

    Boolean 0788 R R,,R R

    Theseflagsareusedtocausedatatobecondionallyprintedontheprovereport.

    1933 MassProveFlag(ConditionallyPrintedFlag)

    Boolean 078D R R,,R R

    1934 NetProveFlag(ConditionallyPrintedFlag)

    Boolean 078E R R,,R R

    1935 MasterMeterisaCoriolisMeterFlag Boolean 078F R R,,R R1936 TesterMeterisaCoriolisMeterFlag Boolean 0790 R R,,R R1937 MasterMeterisNotaCoriolisMeterFlag Boolean 0791 R R,,R R

    1938 TesterMeterisNotaCoriolisMeterFlag Boolean 0792 R R,,R R

    1962 Print4DecimalforMeterFactorsonPvReport

    Boolean 07AA R R,,R R

    1963 Print5DecimalforMeterFactorsonPvReport

    Boolean 07AB R R,,R R

    1964 Print6DecimalforMeterFactorsonPvReport

    Boolean 07AC R R,,R R

    1965 Print5DecimalforIntermediateMeterFactors

    Boolean 07AD R R,,R R

    Page17of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    1966 Print6DecimalforIntermediateMeterFactors

    Boolean 07AE R R,,R R

    1967 Print7DecimalforIntermediateMeterFactors

    Boolean 07AF R R,,R R

    2101 Meter1CurrentBatchGrossTotalRolloverFlag

    Boolean 0835 R R,,R R

    2102 Meter1CurrentBatchNetTotalRolloverFlag

    Boolean 0836 R R,,R R

    2103 Meter1CurrentBatchMassTotalRolloverFlag

    Boolean 0837 R R,,R R

    2104 Meter1CurrentBatchEnergyTotalRolloverFlag

    Boolean 0838 R R,,R R

    2105 Meter1CurrentCumulativeGrossRolloverFlag

    Boolean 0839 R R,,R R

    2106 Meter1CurrentCumulativeNetRolloverFlag

    Boolean 083A R R,,R R

    2107 Meter1CurrentCumulativeMassRolloverFlag

    Boolean 083B R R,,R R

    2108 Meter1CurrentCumulativeEnergyRolloverFlag

    Boolean 083C R R,,R R

    2109 Meter1DailyGrossTotalRolloverFlag Boolean 083D R R,,R R

    2110 Meter1DailyNetTotalRolloverFlag Boolean 083E R R,,R R2111 Meter1DailyMassTotalRolloverFlag Boolean 083F R R,,R R2112 Meter1DailyEnergyTotalRolloverFlag Boolean 0840 R R,,R R

    Page18of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    2113 Meter1DailyCumulativeGrossRolloverFlag

    Boolean 0841 R R,,R R

    2114 Meter1DailyCumulativeNetRolloverFlag

    Boolean 0842 R R,,R R

    2115 Meter1DailyCumulativeMassRolloverFlag

    Boolean 0843 R R,,R R

    2116 Meter1DailyCumulativeEnergyRolloverFlag

    Boolean 0844 R R,,R R

    2117 Meter1PreviousBatchGrossRolloverFlag

    Boolean 0845 R R,,R R

    2118 Meter1PreviousBatchNetRolloverFlag Boolean 0846 R R,,R R

    2119 Meter1PreviousBatchMassRolloverFlag

    Boolean 0847 R R,,R R

    2120 Meter1PreviousBatchEnergyRolloverFlag

    Boolean 0848 R R,,R R

    2121 Meter1PrevBatchCumGrossRolloverFlag

    Boolean 0849 R R,,R R

    2122 Meter1PrevBatchCumNetRolloverFlag

    Boolean 084A R R,,R R

    2123 Meter1PrevBatchCumMassRolloverFlag

    Boolean 084B R R,,R R

    2124 Meter1PrevBatchCumEnergyRolloverFlag

    Boolean 084C R R,,R R

    Page19of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    2125 Meter1PrevDailyGrossTotalRolloverFlag

    Boolean 084D R R,,R R

    2126 Meter1PrevDailyNetTotalRolloverFlag Boolean 084E R R,,R R

    2127 Meter1PrevDailyMassTotalRolloverFlag

    Boolean 084F R R,,R R

    2128 Meter1PrevDailyEnergyTotalRolloverFlag

    Boolean 0850 R R,,R R

    2129 Meter1PrevDailyCumGrossRolloverFlag

    Boolean 0851 R R,,R R

    2130 Meter1PrevDailyCumNetRolloverFlag Boolean 0852 R R,,R R

    2131 Meter1PrevDailyCumMassRolloverFlag

    Boolean 0853 R R,,R R

    2132 Meter1PrevDailyCumEnergyRolloverFlag

    Boolean 0854 R R,,R R

    2133 Meter1TemperatureHARTDeviceLostCommunicationAlarm

    Boolean 0855 R R,,R R

    2134 Meter1PressureHARTDeviceLostCommunicationAlarm

    Boolean 0856 R R,,R R

    2135 Meter1LowRangeDPHARTDeviceLostCommunicationAlarm

    Boolean 0857 R R,,R R

    2136 Meter1MidRangeDPHARTDeviceLostCommunicationAlarm

    Boolean 0858 R R,,R R

    Page20of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    2137 Meter1HighRangeDPHARTDeviceLostCommunicationAlarm

    Boolean 0859 R R,,R R

    2138 Meter1DensityTemperatureHARTDeviceLostCommunicationAlarm

    Boolean 085A R R,,R R

    2139 Meter1DensityPressureHARTDeviceLostCommunicationAlarm

    Boolean 085B R R,,R R

    2141 Meter1HourlyArchiveBreakFlag Boolean 085D R R,,R R2142 Meter1SMV3000DPInvalidCorrectsor

    ResetBoolean 085E R R,,R R

    2143 Meter1SMV3000DPisintheInputorOutputMode

    Boolean 085F R R,,R R

    2144 Meter1SMV3000DPSignalisSuspect Boolean 0860 R R,,R R2145 Meter1SMV3000PressInvalidCorrects

    orResetBoolean 0861 R R,,R R

    2146 Meter1SMV3000PressisintheInput/OutputMode

    Boolean 0862 R R,,R R

    2147 Meter1SMV3000PressSignalisSuspect Boolean 0863 R R,,R R

    2148 Meter1SMV3000TempInvalidCorrectsorReset

    Boolean 0864 R R,,R R

    2149 Meter1SMV3000TempisintheInput/OutputMode

    Boolean 0865 R R,,R R

    2150 Meter1SMV3000TempSignalisSuspect Boolean 0866 R R,,R R

    2151 Meter1SMV3000BodyFaultOverTemperature

    Boolean 0867 R R,,R R

    Page21of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    2152 Meter1SMV3000FailureofSMVElectronics

    Boolean 0868 R R,,R R

    2153 Meter1SMV3000NotCommunicating Boolean 0869 R R,,R R2154 Meter1UltrasonicMeterLossof

    CommunicationFlagBoolean 086A R R,,R R

    2155 Meter1UltrasonicMeterPulseSuspectAlarmFlag

    Boolean 086B R R,,R R

    2156 Meter1Qsonic/FMCFlowrateDeltaAlarm

    Boolean 086C R R,,R R

    2157 Meter1QsonicPath1aAGCRatioAlarm Boolean 086D R R,,R R

    Meter1KongsbergFMCGain011HighAlarm

    R R,,R R

    Meter1FLOWSIC600MeterinConfigurationMode

    R R,,R R

    2158 Meter1QsonicPath1bAGCRatioAlarm Boolean 086E R R,,R R

    Meter1KongsbergFMCGain110HighAlarm

    R R,,R R

    Meter1FLOWSIC600MeterinReducedAccuracy

    R R,,R R

    2159 Meter1QsonicPath2aAGCRatioAlarm Boolean 086F R R,,R R

    Meter1KongsbergFMCGain29HighAlarm

    R R,,R R

    Meter1FLOWSIC600MeterPath1Error R R,,R R

    2160 Meter1QsonicPath2bAGCRatioAlarm Boolean 0870 R R,,R R

    Page22of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    Meter1KongsbergFMCGain38HighAlarm

    R R,,R R

    Meter1FLOWSIC600MeterPath2Error R R,,R R

    2161 Meter1QsonicPath3aAGCRatioAlarm Boolean 0871 R R,,R R

    Meter1KongsbergFMCGain47HighAlarm

    R R,,R R

    Meter1FLOWSIC600MeterPath3Error R R,,R R

    2162 Meter1QsonicPath3bAGCRatioAlarm Boolean 0872 R R,,R R

    Meter1KongsbergFMCGain56HighAlarm

    R R,,R R

    Meter1FLOWSIC600MeterPath4Error R R,,R R

    2163 Meter1QsonicPath4aAGCRatioAlarm Boolean 0873 R R,,R R

    Meter1KongsbergFMCGain65HighAlarm

    R R,,R R

    Meter1FLOWSIC600MeterEEPROMError

    R R,,R R

    2164 Meter1QsonicPath4bAGCRatioAlarm Boolean 0874 R R,,R R

    Meter1KongsbergFMCGain74HighAlarm

    R R,,R R

    Meter1FLOWSIC600MeterI/OParametererror

    R R,,R R

    2165 Meter1QsonicPath5aAGCRatioAlarm Boolean 0875 R R,,R R

    Page23of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    Meter1KongsbergFMCGain83HighAlarm

    R R,,R R

    Meter1FLOWSIC600MeterWarnI/ORange

    R R,,R R

    2166 Meter1QsonicPath5bAGCRatioAlarm Boolean 0876 R R,,R R

    Meter1KongsbergFMCGain92HighAlarm

    R R,,R R

    Meter1FLOWSIC600MeterDSPfault R R,,R R2167 Meter1QsonicPath1SampleError

    AlarmBoolean 0877 R R,,R R

    Meter1KongsbergFMCGain101HighAlarm

    R R,,R R

    Meter1FLOWSIC600FlowDirectionStatus

    R R,,R R

    2168 Meter1QsonicPath2SampleErrorAlarm

    Boolean 0878 R R,,R R

    Meter1KongsbergFMCGain110HighAlarm

    R R,,R R

    Meter1FLOWSIC600MeterDSPParameterError

    R R,,R R

    2169 Meter1QsonicPath3SampleErrorAlarm

    Boolean 0879 R R,,R R

    Meter1KongsbergFMCBurstAlarm011 R R,,R R

    Meter1FLOWSIC600MeterPath1AGCDeviationAlarm

    R R,,R R

    Page24of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    2170 Meter1QsonicPath4SampleErrorAlarm

    Boolean 087A R R,,R R

    Meter1KongsbergFMCBurstAlarm110 R R,,R R

    Meter1FLOWSIC600MeterPath2AGCDeviationAlarm

    R R,,R R

    2171 Meter1QsonicPath5SampleErrorAlarm

    Boolean 087B R R,,R R

    Meter1KongsbergFMCBurstAlarm29 R R,,R RMeter1FLOWSIC600MeterPath3AGCDeviationAlarm

    R R,,R R

    2172 Meter1QsonicOverallSampleErrorAlarm

    Boolean 087C R R,,R R

    Meter1KongsbergFMCBurstAlarm38 R R,,R RMeter1FLOWSIC600MeterPath4AGCDeviationAlarm

    R R,,R R

    2173 Meter1QsonicPath1GasVelocityofSoundAlarm

    Boolean 087D R R,,R R

    Meter1KongsbergFMCBurstAlarm47 R R,,R RMeter1FLOWSIC600MeterPath1SOSDeviationWarning

    R R,,R R

    2174 Meter1QsonicPath2GasVelocityofSoundAlarm

    Boolean 087E R R,,R R

    Meter1KongsbergFMCBurstAlarm56 R R,,R RMeter1FLOWSIC600MeterPath2SOSDeviationWarning

    R R,,R R

    Page25of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    2175 Meter1QsonicPath3GasVelocityofSoundAlarm

    Boolean 087F R R,,R R

    Meter1KongsbergFMCBurstAlarm65 R R,,R RMeter1FLOWSIC600MeterPath3SOSDeviationWarning

    R R,,R R

    2176 Meter1QsonicPath4GasVelocityofSoundAlarm

    Boolean 0880 R R,,R R

    Meter1KongsbergFMCBurstAlarm74 R R,,R RMeter1FLOWSIC600MeterPath4SOSDeviationWarning

    R R,,R R

    2177 Meter1QsonicPath5GasVelocityofSoundAlarm

    Boolean 0881 R R,,R R

    Meter1KongsbergFMCBurstAlarm83 R R,,R R2178 Meter1KongsbergFMCBurstAlarm92 Boolean 0882 R R,,R R

    Meter1EquimeterAbnormalWarning R R,,R R2179 Meter1KongsbergFMCBurstAlarm101 Boolean 0883 R R,,R R

    Meter1EquimeterAbnormalAlarm R R,,R R2180 Meter1KongsbergFMCBurstAlarm110 Boolean 0884 R R,,R R

    Meter1EquimeterNonSteadyFlowAlarm

    R R,,R R

    2181 Meter1FMCPath0GasVelocityofSoundAlarm

    Boolean 0885 R R,,R R

    Meter1EquimeterNonSteadyFlowWarning

    R R,,R R

    Meter1FLOWSIC600Path1VOSAlarm R R,,R R2182 Meter1FMCPath1GasVelocityof

    SoundAlarmBoolean 0886 R R,,R R

    Page26of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    Meter1EquimeterNoFloworLossofBothPulses

    R R,,R R

    Meter1FLOWSIC600Path2VOSAlarm R R,,R R2183 Meter1FMCPath2GasVelocityof

    SoundAlarmBoolean 0887 R R,,R R

    Meter1EquimeterLeakageorResonantNoNetFlow

    R R,,R R

    Meter1FLOWSIC600Path3VOSAlarm R R,,R R2184 Meter1FMCPath3GasVelocityof

    SoundAlarmBoolean 0888 R R,,R R

    Meter1EquimeterNoMainRotorPulses R R,,R R

    Meter1FLOWSIC600Path4VOSAlarm R R,,R R2185 Meter1FMCPath4GasVelocityof

    SoundAlarmBoolean 0889 R R,,R R

    Meter1EquimeterNoSensingRotorPulses

    R R,,R R

    2186 Meter1FMCPath5GasVelocityofSoundAlarm

    Boolean 088A R R,,R R

    2187 Meter1FMCMPU1200StatusAlarm Boolean 088B R R,,R R2189 Meter1UltrasonicVOSandAGA10VOS

    Devia.AlarmBoolean 088D R R,,R R

    2190 Meter1NIST14Vapor(Gas)PhaseFlag Boolean 088E R R,,R R2191 Meter1NIST14LiquidPhaseFlag Boolean 088F R R,,R R2192 Meter1GrossIncrementExceedLimits Boolean 0890 R R,,R R2193 Meter1NetIncrementExceedLimits Boolean 0891 R R,,R R2194 Meter1MassIncrementExceedLimits Boolean 0892 R R,,R R2195 Meter1NSVIncrementExceedLimits Boolean 0893 R R,,R R

    Page27of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    2196 Meter1HARTDeviceMismatchtheMidRangeDPassignment

    Boolean 0894 R R,,R R

    2197 Meter1HARTDeviceMismatchtheHighRangeDPassignment

    Boolean 0895 R R,,R R

    2198 Meter1FlowSicDataException Boolean 0896 R R,,R R2199 Reserved

    2201 2299Meter2(Sameas21012199) Boolean 0899 R R,,R R2301 2399Meter3(Sameas21012199) Boolean 08FD R R,,R R2401 2499Meter4(Sameas21012199) Boolean 0961 R R,,R R

    2601 AuxiliaryInput1OverrideinUseFlag Boolean 0A29 R R,,R R2602 AuxiliaryInput2OverrideinUseFlag Boolean 0A2A R R,,R R2603 AuxiliaryInput3OverrideinUseFlag Boolean 0A2B R R,,R R2604 AuxiliaryInput4OverrideinUseFlag Boolean 0A2C R R,,R R2605 ReferenceSGOverrideinUseFlag Boolean 0A2D R R,,R R2606 Mol%NitrogenOverrideinUseFlag Boolean 0A2E R R,,R R2607 Mol%CO2OverrideinUseFlag Boolean 0A2F R R,,R R2608 HeatingValueOverrideinUseFlag Boolean 0A30 R R,,R R2614 Reserved2615 Reserved2616 Reserved2617 Reserved2618 Reserved2619 Reserved2620 CalibrationDataChecksumError Boolean 0A3C R R,,R R2621 SystemInitializedFlag Boolean 0A3D R R,,R R2622 DayLightSavingsTime Boolean 0A3E R R,,R R2623 ArchiveMemoryAlarm(0=OK,1=Alarm) Boolean 0A3F R R,R,R R2630 Reserved2631 Serial1asEthernetPort(0=No,1=Yes) Boolean 0A47 R R,,R R

    2632 Serial2asEthernetPort(0=No,1=Yes) Boolean 0A48 R R,,R R

    2633 Serial3asEthernetPort(0=No,1=Yes) Boolean 0A49 R R,,R R

    Page28of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    2634 Serial4asEthernetPort(0=No,1=Yes) Boolean 0A4A R R,,R R

    2635 Serial5asEthernetPort(0=No,1=Yes) Boolean 0A4B R R,,R R

    2636 Serial6asEthernetPort(0=No,1=Yes) Boolean 0A4C R R,,R R

    2637 SE1EthernetMode(0=V0,1=V2) Boolean 0A4D R R,,R R2638 SE2EthernetMode(0=V0,1=V2) Boolean 0A4E R R,,R R2639 SE3EthernetMode(0=V0,1=V2) Boolean 0A4F R R,,R R2640 SE1EthernetPrinter1Error Boolean 0A50 R R,,R R2641 SE1EthernetPrinter2Error Boolean 0A51 R R,,R R2642 2645Reserved2646 SE2EthernetPrinter1Error Boolean 0A56 R R,,R R2647 SE2EthernetPrinter2Error Boolean 0A57 R R,,R R2648 2651Reserved2652 SE3EthernetPrinter1Error Boolean 0A5C R R,,R R2653 SE3EthernetPrinter2Error Boolean 0A5D R R,,R R2654 2657Reserved2658 SE1EthernetLinkDown Boolean 0A62 R R,,R R2659 SE2EthernetLinkDown Boolean 0A63 R R,,R R2660 SE3EthernetLinkDown Boolean 0A64 R R,,R R2681 2699Reserved

    Thefollowingarecommandbooleanswhichcausesomeactiontooccur.Mostareedgetriggeredandresetautomaticallyaftertheactionoccurs,ie:Yousetthemandforgetaboutthem.

    2701 DataPacket1toSerialPort1 Boolean 0A8D R/W R/W,,R R2702 DataPacket2toSerialPort1 Boolean 0A8E R/W R/W,,R R2703 DataPacket3toSerialPort1 Boolean 0A8F R/W R/W,,R R2704 DataPacket1toSerialPort2 Boolean 0A90 R/W R/W,,R R2705 DataPacket2toSerialPort2 Boolean 0A91 R/W R/W,,R R2706 DataPacket3toSerialPort2 Boolean 0A92 R/W R/W,,R R2707 DataPacket1toSerialPort3 Boolean 0A93 R/W R/W,,R R2708 DataPacket2toSerialPort3 Boolean 0A94 R/W R/W,,R R2709 DataPacket3toSerialPort3 Boolean 0A95 R/W R/W,,R R2710 DataPacket1toSerialPort4 Boolean 0A96 R/W R/W,,R R2711 DataPacket2toSerialPort4 Boolean 0A97 R/W R/W,,R R2712 DataPacket3toSerialPort4 Boolean 0A98 R/W R/W,,R R

    Page29of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    2713 OtherWatchdogStatus(RedundancyMode)

    Boolean 0A99 R/W R/W,,R R

    2714 OtherMasterStatus(RedundancyMode) Boolean 0A9A R/W R/W,,R R

    2715 AssumeMasterStatusCommand(RedundancyMode)

    Boolean 0A9B R/W R/W,,R R

    2716 AssumeSlaveStatusCommand(RedundancyMode)

    Boolean 0A9C R/W R/W,,R R

    2717 MOVOpenStatusMeter1 Boolean 0A9D R/W R/W,,R R2718 MOVClosedStatusMeter1 Boolean 0A9E R/W R/W,,R R2719 MOVInServiceCommandMeter1 Boolean 0A9F R/W R/W,,R R2720 MOVOpenStatusMeter2 Boolean 0AA0 R/W R/W,,R R2721 MOVClosedStatusMeter2 Boolean 0AA1 R/W R/W,,R R2722 MOVInServiceCommandMeter2 Boolean 0AA2 R/W R/W,,R R2723 MOVOpenStatusMeter3 Boolean 0AA3 R/W R/W,,R R2724 MOVClosedStatusMeter3 Boolean 0AA4 R/W R/W,,R R2725 MOVInServiceCommandMeter3 Boolean 0AA5 R/W R/W,,R R2726 MOVOpenStatusMeter4 Boolean 0AA6 R/W R/W,,R R2727 MOVClosedStatusMeter4 Boolean 0AA7 R/W R/W,,R R2728 MOVInServiceCommandMeter4 Boolean 0AA8 R/W R/W,,R R2729 2732Reserved2733 BreakArchiveCommandMeter1 Boolean 0AAD R/W R/W,,R N R2734 BreakArchiveCommandMeter2 Boolean 0AAE R/W R/W,,R N R2735 BreakArchiveCommandMeter3 Boolean 0AAF R/W R/W,,R N R2736 BreakArchiveCommandMeter4 Boolean 0AB0 R/W R/W,,R N R2737 ToggleMaintenanceModeMeter1 Boolean 0AB1 R/W R/W,,R N R2738 ToggleMaintenanceModeMeter2 Boolean 0AB2 R/W R/W,,R N R2739 ToggleMaintenanceModeMeter3 Boolean 0AB3 R/W R/W,,R N R2740 ToggleMaintenanceModeMeter4 Boolean 0AB4 R/W R/W,,R N R2741 ForceDayEndMeter1 Boolean 0AB5 R/W R/W,,R Y R2742 ForceDayEndMeter2 Boolean 0AB6 R/W R/W,,R Y R2743 ForceDayEndMeter3 Boolean 0AB7 R/W R/W,,R Y R2744 ForceDayEndMeter4 Boolean 0AB8 R/W R/W,,R Y R2745 ForceDayEndStation Boolean 0AB9 R/W R/W,,R Y R2746 RemoteRequesttoPrintAuditReport Boolean 0ABA R/W R/W,,R R

    Page30of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    2747 ForceDiscoveryMode(SetFromOmniCom)

    Boolean 0ABB R/W R/W,,R R

    2747 2750Reserved2760 Serial1HasEthernetPrinters(0=No,

    1=Yes)Boolean 0AC8 R/W R/W,,R R

    2761 Reserved2762 Serial2HasEthernetPrinters(0=No,

    1=Yes)Boolean 0ACA R/W R/W,,R R

    2763 Reserved2764 Serial3HasEthernetPrinters(0=No,

    1=Yes)Boolean 0ACC R/W R/W,,R R

    2765 Reserved2766 Serial4HasEthernetPrinters(0=No,

    1=Yes)Boolean 0ACE R/W R/W,,R R

    2767 Reserved2768 Serial5HasEthernetPrinters(0=No,

    1=Yes)Boolean 0AD0 R/W R/W,,R R

    2769 Reserved2770 Serial6HasEthernetPrinters(0=No,

    1=Yes)Boolean 0AD2 R/W R/W,,R R

    2771 2774Reserved2775 SE1EthernetSetConfigurationStatus

    CommandBoolean 0AD7 R/W R/W,,R R

    2776 SE2EthernetSetConfigurationStatusCommand

    Boolean 0AD8 R/W R/W,,R R

    2777 SE3EthernetSetConfigurationStatusCommand

    Boolean 0AD9 R/W R/W,,R R

    2778 2799ReservedPage31of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    2801 StationCurrentBatchGrossTotalRolloverFlag

    Boolean 0AF1 R R,,R R

    2802 StationCurrentBatchNetTotalRolloverFlag

    Boolean 0AF2 R R,,R R

    2803 StationCurrentBatchMassTotalRolloverFlag

    Boolean 0AF3 R R,,R R

    2804 StationCurrentBatchEnergyTotalRolloverFlag

    Boolean 0AF4 R R,,R R

    2805 StationCurrentBatchCumGrossRolloverFlag

    Boolean 0AF5 R R,,R R

    2806 StationCurrentBatchCumNetRolloverFlag

    Boolean 0AF6 R R,,R R

    2807 StationCurrentBatchCumMassRolloverFlag

    Boolean 0AF7 R R,,R R

    2808 StationCurrentBatchCumEnergyRolloverFlag

    Boolean 0AF8 R R,,R R

    2809 StationDailyGrossTotalRolloverFlag Boolean 0AF9 R R,,R R

    2810 StationDailyNetTotalRolloverFlag Boolean 0AFA R R,,R R2811 StationDailyMassTotalRolloverFlag Boolean 0AFB R R,,R R2812 StationDailyEnergyTotalRolloverFlag Boolean 0AFC R R,,R R

    2813 StationDailyCumulativeGrossRolloverFlag

    Boolean 0AFD R R,,R R

    2814 StationDailyCumulativeNetRolloverFlag

    Boolean 0AFE R R,,R R

    Page32of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    2815 StationDailyCumulativeMassRolloverFlag

    Boolean 0AFF R R,,R R

    2816 StationDailyCumulativeEnergyRolloverFlag

    Boolean 0B00 R R,,R R

    2817 StationPreviousBatchGrossRolloverFlag

    Boolean 0B01 R R,,R R

    2818 StationPreviousBatchNetRolloverFlag Boolean 0B02 R R,,R R

    2819 StationPreviousBatchMassRolloverFlag Boolean 0B03 R R,,R R

    2820 StationPreviousBatchEnergyRolloverFlag

    Boolean 0B04 R R,,R R

    2821 StationPreviousBatchCumGrossRolloverFlag

    Boolean 0B05 R R,,R R

    2822 StationPreviousBatchCumNetRolloverFlag

    Boolean 0B06 R R,,R R

    2823 StationPreviousBatchCumMassRolloverFlag

    Boolean 0B07 R R,,R R

    2824 StationPreviousBatchCumEnergyRolloverFlag

    Boolean 0B08 R R,,R R

    2825 StationPreviousDailyGrossRolloverFlag Boolean 0B09 R R,,R R

    2826 StationPreviousDailyNetRolloverFlag Boolean 0B0A R R,,R R

    2827 StationPreviousDailyMassRolloverFlag Boolean 0B0B R R,,R R

    Page33of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    2828 StationPreviousDailyEnergyRolloverFlag

    Boolean 0B0C R R,,R R

    2829 StationPreviousDayCumGrossRolloverFlag

    Boolean 0B0D R R,,R R

    2830 StationPreviousDayCumulativeNetRolloverFlag

    Boolean 0B0E R R,,R R

    2831 StationPreviousDayCumMassRolloverFlag

    Boolean 0B0F R R,,R R

    2832 StationPreviousDayCumEnergyRolloverFlag

    Boolean 0B10 R R,,R R

    2833 PrintReferenceSGonSnapshotReportFlag

    Boolean 0B11 R R,,R R

    2834 PrintMol%NitrogenonSnapshotReportFlag

    Boolean 0B12 R R,,R R

    2835 PrintMol%CO2onSnapshotReportFlag Boolean 0B13 R R,,R R

    2836 PrintHeatingValueonSnapshotReportFlag

    Boolean 0B14 R R,,R R

    2837 GC2FatalAlarm Boolean 0B15 R R,,R R2838 GC2LostCommunicaitonAlarm Boolean 0B16 R R,,R R2839 GC2Mol%outofdeviationalarm Boolean 0B17 R R,,R R2840 FlashJumperinEnablePosition Boolean 0B18 R R,,R R2841 AuxiliaryInput1HARTDeviceLost

    CommunicationAlarmBoolean 0B19 R R,,R R

    2842 AuxiliaryInput2HARTDeviceLostCommunicationAlarm

    Boolean 0B1A R R,,R R

    Page34of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    2843 AuxiliaryInput3HARTDeviceLostCommunicationAlarm

    Boolean 0B1B R R,,R R

    2844 AuxiliaryInput4HARTDeviceLostCommunicationAlarm

    Boolean 0B1C R R,,R R

    2847 DPUnitSelectedinkPa Boolean 0B1F R R,,R R2848 DPUnitSelectedinMilliBar Boolean 0B20 R R,,R R2849 PressureUnitSelectedinkPa Boolean 0B21 R R,,R R2850 PressureUnitSelectedinBar Boolean 0B22 R R,,R R2851 PressureUnitSelectedinkg/cm2 Boolean 0B23 R R,,R R2852 PrintEnergyinGJFlag Boolean 0B24 R R,,R R2853 PrintEnergyinkWhFlag Boolean 0B25 R R,,R R2854 PrintTurbineDataFlag Boolean 0B26 R R,,R R2855 PrintOrificeDataFlag Boolean 0B27 R R,,R R2856 PrintInstrometDataFlag Boolean 0B28 R R,,R R2857 PrintAGA8DataFlag Boolean 0B29 R R,,R R2858 Print0DecimalPlaceforGrossTotalizer Boolean 0B2A R R,,R R

    2859 Print1DecimalPlaceforGrossTotalizer Boolean 0B2B R R,,R R

    2860 Print2DecimalPlacesforGrossTotalizer Boolean 0B2C R R,,R R

    2861 Print3DecimalPlacesforGrossTotalizer Boolean 0B2D R R,,R R

    2862 Reserved2863 WatchdogStatus(RedundancyMode) Boolean 0B2F R R,,R R2864 MasterStatus(RedundancyMode) Boolean 0B30 R R,,R R2865 Print0DecimalPlaceforMassTotalizer Boolean 0B31 R R,,R R

    2866 Print1DecimalPlaceforMassTotalizer Boolean 0B32 R R,,R R

    Page35of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    2867 Print2DecimalPlacesforMassTotalizer Boolean 0B33 R R,,R R

    2868 Print3DecimalPlacesforMassTotalizer Boolean 0B34 R R,,R R

    2869 Print0DecimalPlaceforNetTotalizer Boolean 0B35 R R,,R R

    2870 Print1DecimalPlaceforNetTotalizer Boolean 0B36 R R,,R R

    2871 Print2DecimalPlacesforNetTotalizer Boolean 0B37 R R,,R R

    2872 Print3DecimalPlacesforNetTotalizer Boolean 0B38 R R,,R R

    2873 Print0DecimalPlaceforEnergyTotalizer Boolean 0B39 R R,,R R

    2874 Print1DecimalPlaceforEnergyTotalizer Boolean 0B3A R R,,R R

    2875 Print2DecimalPlacesforEnergyTotalizer

    Boolean 0B3B R R,,R R

    2876 Print3DecimalPlacesforEnergyTotalizer

    Boolean 0B3C R R,,R R

    2877 OpenValveMeter1 Boolean 0B3D R R,,R R2878 CloseValveMeter1 Boolean 0B3E R R,,R R2879 IllegalValvePositionAlarmMeter1 Boolean 0B3F R R,,R R2880 TimeoutAlarmOpeningMeter1MOV Boolean 0B40 R R,,R R2881 TimeoutAlarmClosingMeter1MOV Boolean 0B41 R R,,R R2882 OpenValveMeter2 Boolean 0B42 R R,,R R2883 CloseValveMeter2 Boolean 0B43 R R,,R R2884 IllegalValvePositionAlarmMeter2 Boolean 0B44 R R,,R R2885 TimeoutAlarmOpeningMeter2MOV Boolean 0B45 R R,,R R2886 TimeoutAlarmClosingMeter2MOV Boolean 0B46 R R,,R R2887 OpenValveMeter3 Boolean 0B47 R R,,R R2888 CloseValveMeter3 Boolean 0B48 R R,,R R

    Page36of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    2889 IllegalValvePositionAlarmMeter3 Boolean 0B49 R R,,R R2890 TimeoutAlarmOpeningMeter3MOV Boolean 0B4A R R,,R R2891 TimeoutAlarmClosingMeter3MOV Boolean 0B4B R R,,R R2892 OpenValveMeter4 Boolean 0B4C R R,,R R2893 CloseValveMeter4 Boolean 0B4D R R,,R R2894 IllegalValvePositionAlarmMeter4 Boolean 0B4E R R,,R R2895 TimeoutAlarmOpeningMeter4MOV Boolean 0B4F R R,,R R2896 TimeoutAlarmClosingMeter4MOV Boolean 0B50 R R,,R R2897 2899Reserved

    Theseindexsdefinethe16bitintegercontentsofthe'CustomDataPacket'

    3001 Packet1StartingIndex1 UINT16 0BB9 R/W R/W,,R N R3002 Packet1NumberofIndexPoints1 UINT16 0BBA R/W R/W,,R N R3003 Packet1StartingIndex2 UINT16 0BBB R/W R/W,,R N R3004 Packet1NumberofIndexPoints2 UINT16 0BBC R/W R/W,,R N R3005 Packet1StartingIndex3 UINT16 0BBD R/W R/W,,R N R3006 Packet1NumberofIndexPoints3 UINT16 0BBE R/W R/W,,R N R3007 Packet1StartingIndex4 UINT16 0BBF R/W R/W,,R N R3008 Packet1NumberofIndexPoints4 UINT16 0BC0 R/W R/W,,R N R3009 Packet1StartingIndex5 UINT16 0BC1 R/W R/W,,R N R3010 Packet1NumberofIndexPoints5 UINT16 0BC2 R/W R/W,,R N R3011 Packet1StartingIndex6 UINT16 0BC3 R/W R/W,,R N R3012 Packet1NumberofIndexPoints6 UINT16 0BC4 R/W R/W,,R N R3013 Packet1StartingIndex7 UINT16 0BC5 R/W R/W,,R N R3014 Packet1NumberofIndexPoints7 UINT16 0BC6 R/W R/W,,R N R3015 Packet1StartingIndex8 UINT16 0BC7 R/W R/W,,R N R3016 Packet1NumberofIndexPoints8 UINT16 0BC8 R/W R/W,,R N R3017 Packet1StartingIndex9 UINT16 0BC9 R/W R/W,,R N R3018 Packet1NumberofIndexPoints9 UINT16 0BCA R/W R/W,,R N R3019 Packet1StartingIndex10 UINT16 0BCB R/W R/W,,R N R3020 Packet1NumberofIndexPoints10 UINT16 0BCC R/W R/W,,R N R3021 Packet1StartingIndex11 UINT16 0BCD R/W R/W,,R N R3022 Packet1NumberofIndexPoints11 UINT16 0BCE R/W R/W,,R N R3023 Packet1StartingIndex12 UINT16 0BCF R/W R/W,,R N R3024 Packet1NumberofIndexPoints12 UINT16 0BD0 R/W R/W,,R N R3025 Packet1StartingIndex13 UINT16 0BD1 R/W R/W,,R N R3026 Packet1NumberofIndexPoints13 UINT16 0BD2 R/W R/W,,R N R

    Page37of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    3027 Packet1StartingIndex14 UINT16 0BD3 R/W R/W,,R N R3028 Packet1NumberofIndexPoints14 UINT16 0BD4 R/W R/W,,R N R3029 Packet1StartingIndex15 UINT16 0BD5 R/W R/W,,R N R3030 Packet1NumberofIndexPoints15 UINT16 0BD6 R/W R/W,,R N R3031 Packet1StartingIndex16 UINT16 0BD7 R/W R/W,,R N R3032 Packet1NumberofIndexPoints16 UINT16 0BD8 R/W R/W,,R N R3033 Packet1StartingIndex17 UINT16 0BD9 R/W R/W,,R N R3034 Packet1NumberofIndexPoints17 UINT16 0BDA R/W R/W,,R N R3035 Packet1StartingIndex18 UINT16 0BDB R/W R/W,,R N R3036 Packet1NumberofIndexPoints18 UINT16 0BDC R/W R/W,,R N R3037 Packet1StartingIndex19 UINT16 0BDD R/W R/W,,R N R3038 Packet1NumberofIndexPoints19 UINT16 0BDE R/W R/W,,R N R3039 Packet1StartingIndex20 UINT16 0BDF R/W R/W,,R N R3040 Packet1NumberofIndexPoints20 UINT16 0BE0 R/W R/W,,R N R3041 Packet2StartingIndex1 UINT16 0BE1 R/W R/W,,R N R3042 Packet2NumberofIndexPts UINT16 0BE2 R/W R/W,,R N R3043 Packet2StartingIndex2 UINT16 0BE3 R/W R/W,,R N R3044 Packet2NumberofIndexPts UINT16 0BE4 R/W R/W,,R N R3045 Packet2StartingIndex3 UINT16 0BE5 R/W R/W,,R N R3046 Packet2NumberofIndexPts UINT16 0BE6 R/W R/W,,R N R3047 Packet2StartingIndex4 UINT16 0BE7 R/W R/W,,R N R3048 Packet2NumberofIndexPts UINT16 0BE8 R/W R/W,,R N R3049 Packet2StartingIndex5 UINT16 0BE9 R/W R/W,,R N R3050 Packet2NumberofIndexPts UINT16 0BEA R/W R/W,,R N R3051 Packet2StartingIndex6 UINT16 0BEB R/W R/W,,R N R3052 Packet2NumberofIndexPts UINT16 0BEC R/W R/W,,R N R3053 Packet2StartingIndex7 UINT16 0BED R/W R/W,,R N R3054 Packet2NumberofIndexPts UINT16 0BEE R/W R/W,,R N R3055 Packet2StartingIndex8 UINT16 0BEF R/W R/W,,R N R3056 Packet2NumberofIndexPts UINT16 0BF0 R/W R/W,,R N R3057 Packet3StartingIndex1 UINT16 0BF1 R/W R/W,,R N R3058 Packet3NumberofIndexPts UINT16 0BF2 R/W R/W,,R N R3059 Packet3StartingIndex2 UINT16 0BF3 R/W R/W,,R N R3060 Packet3NumberofIndexPts UINT16 0BF4 R/W R/W,,R N R3061 Packet3StartingIndex3 UINT16 0BF5 R/W R/W,,R N R3062 Packet3NumberofIndexPts UINT16 0BF6 R/W R/W,,R N R3063 Packet3StartingIndex4 UINT16 0BF7 R/W R/W,,R N R3064 Packet3NumberofIndexPts UINT16 0BF8 R/W R/W,,R N R

    Page38of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    3065 Packet3StartingIndex5 UINT16 0BF9 R/W R/W,,R N R3066 Packet3NumberofIndexPts UINT16 0BFA R/W R/W,,R N R3067 Packet3StartingIndex6 UINT16 0BFB R/W R/W,,R N R3068 Packet3NumberofIndexPts UINT16 0BFC R/W R/W,,R N R3069 Packet3StartingIndex7 UINT16 0BFD R/W R/W,,R N R3070 Packet3NumberofIndexPts UINT16 0BFE R/W R/W,,R N R3071 Packet3StartingIndex8 UINT16 0BFF R/W R/W,,R N R3072 Packet3NumberofIndexPts UINT16 0C00 R/W R/W,,R N R3073 Packet3StartingIndex9 UINT16 0C01 R/W R/W,,R N R3074 Packet3NumberofIndexPts UINT16 0C02 R/W R/W,,R N R3075 Packet3StartingIndex10 UINT16 0C03 R/W R/W,,R N R3076 Packet3NumberofIndexPts UINT16 0C04 R/W R/W,,R N R3077 Packet3StartingIndex11 UINT16 0C05 R/W R/W,,R N R3078 Packet3NumberofIndexPts UINT16 0C06 R/W R/W,,R N R3079 Packet3StartingIndex12 UINT16 0C07 R/W R/W,,R N R3080 Packet3NumberofIndexPts UINT16 0C08 R/W R/W,,R N R3081 Packet3StartingIndex13 UINT16 0C09 R/W R/W,,R N R3082 Packet3NumberofIndexPts UINT16 0C0A R/W R/W,,R N R3083 Packet3StartingIndex14 UINT16 0C0B R/W R/W,,R N R3084 Packet3NumberofIndexPts UINT16 0C0C R/W R/W,,R N R3085 Packet3StartingIndex15 UINT16 0C0D R/W R/W,,R N R3086 Packet3NumberofIndexPts UINT16 0C0E R/W R/W,,R N R3087 Packet3StartingIndex16 UINT16 0C0F R/W R/W,,R N R3088 Packet3NumberofIndexPts UINT16 0C10 R/W R/W,,R N R3089 Packet3StartingIndex17 UINT16 0C11 R/W R/W,,R N R3090 Packet3NumberofIndexPts UINT16 0C12 R/W R/W,,R N R3091 Packet3StartingIndex18 UINT16 0C13 R/W R/W,,R N R3092 Packet3NumberofIndexPts UINT16 0C14 R/W R/W,,R N R3093 Packet3StartingIndex19 UINT16 0C15 R/W R/W,,R N R3094 Packet3NumberofIndexPts UINT16 0C16 R/W R/W,,R N R3095 Packet3StartingIndex20 UINT16 0C17 R/W R/W,,R N R3096 Packet3NumberofIndexPts UINT16 0C18 R/W R/W,,R N R3097 AlarmTimer(0128Seconds) UINT16 0C19 R/W R/W,,R Y R3098 DigitsofTotalizer(0=9,1=8) UINT16 0C1A R/W R/W,,R N R

    16BitIntegerData.

    3101 Meter1TemperatureOverrideCode UINT16 0C1D R/W R/W,,R Y R3102 Meter1PressureOverrideCode UINT16 0C1E R/W R/W,,R Y R

    Page39of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    3103 Meter1Gravity/DensityOverrideCode UINT16 0C1F R/W R/W,,R Y R3104 Meter1DensityTemperatureOverride

    CodeUINT16 0C20 R/W R/W,,R Y R

    3105 Meter1DensityPressureOverrideCode UINT16 0C21 R/W R/W,,R Y R3106 Meter1FlowmeterActiveThresholdHz UINT16 0C22 R/W R/W,,R N R3107 Meter1SelectTransDensity

    (0=No,1=Yes)UINT16 0C23 R/W Forrevision27.75.05andlower. R/W,,R N R

    Meter1UpstreamTransducerDensitySelection

    R/W Forrevision27.75.06andhigher:0=NoTransducerDensity1=UpstreamTransducerDensity2=DownstreamTransducerDensity(IsentropicUpstreamDensityCalculation)3=DownstreamTransducerDensity(IsenthalpicUpstreamDensityCalculation)

    R/W,,R N R

    3108 Meter1DeviceType UINT16 0C24 R/W 0=OrificedP1=TurbineMeter2=RosemountSVdp3=HoneywellHVdp4=InstrometQsonic5=Reserved6=FMCMPU12007=EquimeterAAT8=DanielUltrasonic9=CoriolisMeter10=SICKUltrasonic

    R/W,R,R N R

    3109 Meter1DifferentialPressureOverrideCode

    UINT16 0C25 R/W R/W,,R Y R

    3110 Meter1DownstreamPressure.1=Yes0=No

    UINT16 0C26 R/W R/W,,R N R

    3111 Meter1AGA8Method UINT16 0C27 R/W R/W,,R R

    Page40of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    3112 Meter1DpHeadDeviceType UINT16 0C28 R/W 0=OrificeCornerTap1=OrificeD&D/22=OrificeFlangeTap3=ISA1932Nozzle4=LongRadiusNozzle5=Venturi,C=0.9846=Venturi,C=0.9957=Venturi,C=0.9858=VenturiNozzle9=VCone(27.75.03andhigher)

    R/W,,R R

    3113 Meter1UpstreamTemperature UINT16 0C29 R/W R/W,,R N R3114 Meter1SelectProduct(14) UINT16 0C2A R/W R/W,,R N R3115 Meter1G.C.AnalyzerStreamNumber UINT16 0C2B R R,,R3116 Meter1UltrasonicMeterMaxRecovery

    DowntimeUINT16 0C2C R/W R/W,,R N R

    3117 Meter1CurrentHourMeterFlowTime(07200)

    UINT16 0C2D R R,,R

    3118 Meter1PreviousHourMeterFlowTime(07200)

    UINT16 0C2E R R,,R

    3119 Meter1ValveMode.1=Manual0=Auto UINT16 0C2F R/W R/W,,R Y R3120 Meter1SetpointMode1=Local

    0=Remote(ReadOnly)UINT16 0C30 R/W R/W,,R Y R

    3121 Meter1PIDLoopinControl,1=Sec.0=Primary

    UINT16 0C31 R R,,R

    3134 Meter1comparatorErrorThreshold UINT16 0C3E R/W R/W,,R Y R3135 Meter1UltrasonicFlowCompareinterval UINT16 0C3F R/W R/W,,R Y R

    3136 Meter1RunHoursSinceDayStarts UINT16 0C40 R R,,R R3137 Meter1RunMinutesSinceDayStarts UINT16 0C41 R R,,R R3138 Meter1RunHoursPreviousDay UINT16 0C42 R R,,R R3139 Meter1RunMinutesPreviousDay UINT16 0C43 R R,,R R

    Page41of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    Info:Registers3n40,3n42,3n44,4n492scomplementnumberbasedonspanentries1717617189.Valuesexpressaspercentageofspanintenthpercentincrements;i.e.1000represents100%.

    Info:Registers3n41,3n43,3n45,3n50Unsignedintegertotalizercumulativebased.Theyrollat65536.

    Info:Registers3n46,3n47,3n482scomplementnumberbasedonthe420mAspans.Valuesareexpressedaspercentagesofspanintenthpercent;i.e.1000equal100%

    3140 Meter1NetFlowrate%(0999) UINT16 0C44 R R,,R R3141 Meter1NetTotal16Bits UINT16 0C45 R Unsignedintegertotalizercumulativebased.Itrollsat

    65536.R,,R R

    3142 Meter1GrossFlowrate%(0999) UINT16 0C46 R R,,R R3143 Meter1GrossTotal16Bits UINT16 0C47 R Unsignedintegertotalizercumulativebased.Itrollsat

    65536.R,,R R

    3144 Meter1MassFlowrate%(0999) UINT16 0C48 R R,,R R3145 Meter1MassTotal16Bits UINT16 0C49 R Unsignedintegertotalizercumulativebased.Itrollsat

    65536.R,,R R

    3146 Meter1Pressure%(0999) UINT16 0C4A R R,,R R3147 Meter1Temperature%(0999) UINT16 0C4B R R,,R R3148 Meter1Gravity/Density%(0999) UINT16 0C4C R R,,R R3149 Meter1EnergyFlowrate%(0999) UINT16 0C4D R R,,R R3150 Meter1EnergyTotal16Bits UINT16 0C4E R Unsignedintegertotalizercumulativebased.Itrollsat

    65536.R,,R R

    3151 Meter1AppliedAutomationG.C.Status UINT16 0C4F R R,,R R3152 Meter1AppliedAutomationG.C.Alarm

    CodeUINT16 0C50 R R,,R R

    3153 Meter1SVPortSelect(14) UINT16 0C51 R/W R/W,,R N R3154 Meter1SVPortModbusAddress UINT16 0C52 R/W R/W,,R N R

    Meter1KongsbergMPU1200SeriesB(0=No,1=Yes)

    R/W R/W,,R N R

    Page42of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    3155 Meter1UltrasonicMeterFlowDirection(0=Fwd,1=Rev)

    UINT16 0C53 R/W R/W,,R N R

    3156 Meter1EquimeterAutoAdjustSelection UINT16 0C54 R/W R/W,,R N R

    Meter1DFI/UltrasonicMeterRetryTimes

    R/W R/W,,R N R

    3157 Meter1EquimeterUnAdjustedCalculationSelection

    UINT16 0C55 R/W R/W,,R N R

    Meter1UltrasonicMeterPrimaryFlowSelect(0=Serial,1=Pulses)

    R/W R/W,,R N R

    3158 Meter1QsonicPath1Performance(%) UINT16 0C56 R R,,R RMeter1KongsbergFMC%ofBurstUsed011

    R R,,R R

    Meter1EquimeterSystemWord R R,,R RMeter1FLOWSIC600StatusRegisterPath1

    R R,,R R

    3159 Meter1QsonicPath2Performance(%) UINT16 0C57 R R,,R RMeter1KongsbergFMC%ofBurstUsed110

    R R,,R R

    Meter1EquimeterNonSteadyFlowStatusWord

    R R,,R R

    Meter1FLOWSIC600StatusRegisterPath2

    R R,,R R

    3160 Meter1QsonicPath3Performance(%) UINT16 0C58 R R,,R RMeter1KongsbergFMC%ofBurstUsed29

    R R,,R R

    Meter1EquimeterAbnormalWord R R,,R R

    Page43of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    Meter1FLOWSIC600StatusRegisterPath3

    R R,,R R

    3161 Meter1QsonicPath4Performance(%) UINT16 0C59 R R,,R RMeter1KongsbergFMC%ofBurstUsed38

    R R,,R R

    Meter1EquimeterAlarmWord R R,,R RMeter1FLOWSIC600StatusRegisterPath4

    R R,,R R

    3162 Meter1QsonicPath5Performance(%) UINT16 0C5A R R,,R RMeter1KongsbergFMC%ofBurstUsed47

    R R,,R R

    Meter1FLOWSIC600DigitalInput'n'asFlowDirection

    R/W Selectdigitalinputbetween124toconnecttoFLOWSIC600flowdirectionoutputsignal.

    R/W,,R N R

    3163 Meter1QsonicPath1aAGCRatio UINT16 0C5B R R,,R RMeter1KongsbergFMC%ofBurstUsed56

    R R,,R R

    Meter1FLOWSICDigitalInput'n'asMeasurementStatus

    R/W Selectdigitalinputbetween124toconnecttoFLOWSIC600MeasurementStatusoutputsignal.

    R/W,,R N R

    3164 Meter1QsonicPath1bAGCRatio UINT16 0C5C R R,,R RMeter1KongsbergFMC%ofBurstUsed65

    R R,,R R

    3165 Meter1QsonicPath2aAGCRatio UINT16 0C5D R R,,R RMeter1KongsbergFMC%ofBurstUsed74

    R R,,R R

    3166 Meter1QsonicPath2bAGCRatio UINT16 0C5E R R,,R R

    Page44of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    Meter1KongsbergFMC%ofBurstUsed83

    R R,,R R

    3167 Meter1QsonicPath3aAGCRatio UINT16 0C5F R R,,R RMeter1KongsbergFMC%ofBurstUsed92

    R R,,R R

    3168 Meter1QsonicPath3bAGCRatio UINT16 0C60 R R,,R RMeter1KongsbergFMC%ofBurstUsed101

    R R,,R R

    3169 Meter1QsonicPath4aAGCRatio UINT16 0C61 R R,,R RMeter1KongsbergFMC%ofBurstUsed110

    R R,,R R

    3170 Meter1QsonicPath4bAGCRatio UINT16 0C62 R R,,R R3171 Meter1QsonicPath5aAGCRatio UINT16 0C63 R R,,R R

    Meter1FLOWSIC600SystemControlRegister

    R R,,R R

    3172 Meter1QsonicPath5bAGCRatio UINT16 0C64 R R,,R RMeter1FLOWSIC600SystemStatus R R,,R R

    3173 Meter1QsonicNumberofPaths UINT16 0C65 R R,,R RMeter1FLOWSIC600NumberofPath R R,,R R

    3174 Meter1QsonicNumberofSampleTaken UINT16 0C66 R R,,R R

    Meter1FLOWSIC600FlowMeterType R R,,R R3175 Meter1QsonicPath1NumberofValid

    SampleUINT16 0C67 R R,,R R

    Meter1FLOWSIC600ValidSamplesPath1

    R R,,R R

    3176 Meter1QsonicPath2NumberofValidSample

    UINT16 0C68 R R,,R R

    Page45of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    Meter1FLOWSIC600ValidSamplesPath2

    R R,,R R

    3177 Meter1QsonicPath3NumberofValidSample

    UINT16 0C69 R R,,R R

    Meter1FLOWSIC600ValidSamplesPath3

    R R,,R R

    3178 Meter1QsonicPath4NumberofValidSample

    UINT16 0C6A R R,,R R

    Meter1FLOWSIC600ValidSamplesPath4

    R R,,R R

    3179 Meter1QsonicPath5NumberofValidSample

    UINT16 0C6B R R,,R R

    3180 Meter1QsonicPath1aAGCLevel UINT16 0C6C R R,,R RMeter1KongsbergFMCGain011 R R,,R RMeter1FLOWSIC600AGCLevelReceiver1A

    R R,,R R

    3181 Meter1QsonicPath1bAGCLevel UINT16 0C6D R R,,R RMeter1KongsbergFMCGain110 R R,,R RMeter1FLOWSIC600AGCLevelReceiver1B

    R R,,R R

    3182 Meter1QsonicPath2aAGCLevel UINT16 0C6E R R,,R RMeter1KongsbergFMCGain29 R R,,R RMeter1FLOWSIC600AGCLevelReceiver2A

    R R,,R R

    3183 Meter1QsonicPath2bAGCLevel UINT16 0C6F R R,,R RMeter1KongsbergFMCGain38 R R,,R RMeter1FLOWSIC600AGCLevelReceiver2B

    R R,,R R

    Page46of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    3184 Meter1QsonicPath3aAGCLevel UINT16 0C70 R R,,R RMeter1KongsbergFMCGain47 R R,,R RMeter1FLOWSIC600AGCLevelReceiver3A

    R R,,R R

    3185 Meter1QsonicPath3bAGCLevel UINT16 0C71 R R,,R RMeter1KongsbergFMCGain56 R R,,R RMeter1FLOWSIC600AGCLevelReceiver3B

    R R,,R R

    3186 Meter1QsonicPath4aAGCLevel UINT16 0C72 R R,,R RMeter1KongsbergFMCGain65 R R,,R RMeter1FLOWSIC600AGCLevelReceiver4A

    R R,,R R

    3187 Meter1QsonicPath4bAGCLevel UINT16 0C73 R R,,R RMeter1KongsbergFMCGain74 R R,,R RMeter1FLOWSIC600AGCLevelReceiver4B

    R R,,R R

    3188 Meter1QsonicPath5aAGCLevel UINT16 0C74 R R,,R RMeter1KongsbergFMCGain83 R R,,R RMeter1FLOWSIC600VBattLevel R R,,R R

    3189 Meter1QsonicPath5bAGCLevel UINT16 0C75 R R,,R RMeter1KongsbergFMCGain92 R R,,R RMeter1FLOWSIC600FrequencyCurrent R R,,R R

    3190 Meter1QsonicPath1aAGCLimit UINT16 0C76 R R,,R RMeter1KongsbergFMCGain101 R R,,R R

    3191 Meter1QsonicPath1bAGCLimit UINT16 0C77 R R,,R RMeter1KongsbergFMCGain110 R R,,R R

    3192 Meter1QsonicPath2aAGCLimit UINT16 0C78 R R,,R R3193 Meter1QsonicPath2bAGCLimit UINT16 0C79 R R,,R R3194 Meter1QsonicPath3aAGCLimit UINT16 0C7A R R,,R R3195 Meter1QsonicPath3bAGCLimit UINT16 0C7B R R,,R R3196 Meter1QsonicPath4aAGCLimit UINT16 0C7C R R,,R R3197 Meter1QsonicPath4bAGCLimit UINT16 0C7D R R,,R R3198 Meter1QsonicPath5aAGCLimit UINT16 0C7E R R,,R R

    Page47of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    3199 Meter1QsonicPath5bAGCLimit UINT16 0C7F R R,,R R

    3201 3299Meter2(Sameas31013199) UINT16 0C81 R/W R/W,,R R3301 3399Meter3(Sameas31013199) UINT16 0CE5 R/W R/W,,R R3401 3499Meter4(Sameas31013199) UINT16 0D49 R/W R/W,,R R

    16BitIntegerData.(ScratchpadVariables)

    3501 3599ScratchpadVariable UINT16 0DAD R/W R/W,,R R

    16BitIntegerData.(DefinesIndex&DecimalofUserDisplayVariables)

    3601 UserDisplay1Variable1Index UINT16 0E11 R/W R/W,,R N R3602 UserDisplay1Var1DecimalPlaces UINT16 0E12 R/W R/W,,R N R3603 UserDisplay1Variable2Index UINT16 0E13 R/W R/W,,R N R3604 UserDisplay1Var2DecimalPlaces UINT16 0E14 R/W R/W,,R N R3605 UserDisplay1Variable3Index UINT16 0E15 R/W R/W,,R N R3606 UserDisplay1Var3DecimalPlaces UINT16 0E16 R/W R/W,,R N R3607 UserDisplay1Variable4Index UINT16 0E17 R/W R/W,,R N R3608 UserDisplay1Var4DecimalPlaces UINT16 0E18 R/W R/W,,R N R3609 UserDisplay2Variable1Index UINT16 0E19 R/W R/W,,R N R3610 UserDisplay2Var1DecimalPlaces UINT16 0E1A R/W R/W,,R N R3611 UserDisplay2Variable2Index UINT16 0E1B R/W R/W,,R N R3612 UserDisplay2Var2DecimalPlaces UINT16 0E1C R/W R/W,,R N R3613 UserDisplay2Variable3Index UINT16 0E1D R/W R/W,,R N R3614 UserDisplay2Var3DecimalPlaces UINT16 0E1E R/W R/W,,R N R3615 UserDisplay2Variable4Index UINT16 0E1F R/W R/W,,R N R3616 UserDisplay2Var4DecimalPlaces UINT16 0E20 R/W R/W,,R N R3617 UserDisplay3Variable1Index UINT16 0E21 R/W R/W,,R N R3618 UserDisplay3Var1DecimalPlaces UINT16 0E22 R/W R/W,,R N R3619 UserDisplay3Variable2Index UINT16 0E23 R/W R/W,,R N R3620 UserDisplay3Var2DecimalPlaces UINT16 0E24 R/W R/W,,R N R3621 UserDisplay3Variable3Index UINT16 0E25 R/W R/W,,R N R3622 UserDisplay3Var3DecimalPlaces UINT16 0E26 R/W R/W,,R N R3623 UserDisplay3Variable4Index UINT16 0E27 R/W R/W,,R N R3624 UserDisplay3Var4DecimalPlaces UINT16 0E28 R/W R/W,,R N R3625 UserDisplay4Variable1Index UINT16 0E29 R/W R/W,,R N R3626 UserDisplay4Var1DecimalPlaces UINT16 0E2A R/W R/W,,R N R

    Page48of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    3627 UserDisplay4Variable2Index UINT16 0E2B R/W R/W,,R N R3628 UserDisplay4Var2DecimalPlaces UINT16 0E2C R/W R/W,,R N R3629 UserDisplay4Variable3Index UINT16 0E2D R/W R/W,,R N R3630 UserDisplay4Var3DecimalPlaces UINT16 0E2E R/W R/W,,R N R3631 UserDisplay4Variable4Index UINT16 0E2F R/W R/W,,R N R3632 UserDisplay4Var4DecimalPlaces UINT16 0E30 R/W R/W,,R N R3633 UserDisplay5Variable1Index UINT16 0E31 R/W R/W,,R N R3634 UserDisplay5Var1DecimalPlaces UINT16 0E32 R/W R/W,,R N R3635 UserDisplay5Variable2Index UINT16 0E33 R/W R/W,,R N R3636 UserDisplay5Var2DecimalPlaces UINT16 0E34 R/W R/W,,R N R3637 UserDisplay5Variable3Index UINT16 0E35 R/W R/W,,R N R3638 UserDisplay5Var3DecimalPlaces UINT16 0E36 R/W R/W,,R N R3639 UserDisplay5Variable4Index UINT16 0E37 R/W R/W,,R N R3640 UserDisplay5Var4DecimalPlaces UINT16 0E38 R/W R/W,,R N R3641 UserDisplay6Variable1Index UINT16 0E39 R/W R/W,,R N R3642 UserDisplay6Var1DecimalPlaces UINT16 0E3A R/W R/W,,R N R3643 UserDisplay6Variable2Index UINT16 0E3B R/W R/W,,R N R3644 UserDisplay6Var2DecimalPlaces UINT16 0E3C R/W R/W,,R N R3645 UserDisplay6Variable3Index UINT16 0E3D R/W R/W,,R N R3646 UserDisplay6Var3DecimalPlaces UINT16 0E3E R/W R/W,,R N R3647 UserDisplay6Variable4Index UINT16 0E3F R/W R/W,,R N R3648 UserDisplay6Var4DecimalPlaces UINT16 0E40 R/W R/W,,R N R3649 UserDisplay7Variable1Index UINT16 0E41 R/W R/W,,R N R3650 UserDisplay7Var1DecimalPlaces UINT16 0E42 R/W R/W,,R N R3651 UserDisplay7Variable2Index UINT16 0E43 R/W R/W,,R N R3652 UserDisplay7Var2DecimalPlaces UINT16 0E44 R/W R/W,,R N R3653 UserDisplay7Variable3Index UINT16 0E45 R/W R/W,,R N R3654 UserDisplay7Var3DecimalPlaces UINT16 0E46 R/W R/W,,R N R3655 UserDisplay7Variable4Index UINT16 0E47 R/W R/W,,R N R3656 UserDisplay7Var4DecimalPlaces UINT16 0E48 R/W R/W,,R N R3657 UserDisplay8Variable1Index UINT16 0E49 R/W R/W,,R N R3658 UserDisplay8Var1DecimalPlaces UINT16 0E4A R/W R/W,,R N R3659 UserDisplay8Variable2Index UINT16 0E4B R/W R/W,,R N R3660 UserDisplay8Var2DecimalPlaces UINT16 0E4C R/W R/W,,R N R3661 UserDisplay8Variable3Index UINT16 0E4D R/W R/W,,R N R3662 UserDisplay8Var3DecimalPlaces UINT16 0E4E R/W R/W,,R N R3663 UserDisplay8Variable4Index UINT16 0E4F R/W R/W,,R N R3664 UserDisplay8Var4DecimalPlaces UINT16 0E50 R/W R/W,,R N R

    Page49of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    3665 3670Reserved3697 3699Reserved

    16BitIntegerData

    3701 Archive701MaximumRecords UINT16 0E75 R/W R/W,R,R R3702 Archive701CurrentRecordNumber UINT16 0E76 R R,R,R R3703 Archive701RequestRecordNumber UINT16 0E77 R/W R/W,R/W,R/W R3704 Archive702MaximumRecords UINT16 0E78 R/W R/W,R,R R3705 Archive702CurrentRecordNumber UINT16 0E79 R R,R,R R3706 Archive702RequestRecordNumber UINT16 0E7A R/W R/W,R/W,R/W R3707 Archive703MaximumRecords UINT16 0E7B R/W R/W,R,R R3708 Archive703CurrentRecordNumber UINT16 0E7C R R,R,R R3709 Archive703RequestRecordNumber UINT16 0E7D R/W R/W,R/W,R/W R3710 Archive704MaximumRecords UINT16 0E7E R/W R/W,R,R R3711 Archive704CurrentRecordNumber UINT16 0E7F R R,R,R R3712 Archive704RequestRecordNumber UINT16 0E80 R/W R/W,R/W,R/W R3713 Archive705MaximumRecords UINT16 0E81 R/W R/W,R,R R3714 Archive705CurrentRecordNumber UINT16 0E82 R R,R,R R3715 Archive705RequestRecordNumber UINT16 0E83 R/W R/W,R/W,R/W R3716 Archive706MaximumRecords UINT16 0E84 R/W R/W,R,R R3717 Archive706CurrentRecordNumber UINT16 0E85 R R,R,R R3718 Archive706RequestRecordNumber UINT16 0E86 R/W R/W,R/W,R/W R3719 Archive707MaximumRecords UINT16 0E87 R/W R/W,R,R R3720 Archive707CurrentRecordNumber UINT16 0E88 R R,R,R R3721 Archive707RequestRecordNumber UINT16 0E89 R/W R/W,R/W,R/W R3722 Archive708MaximumRecords UINT16 0E8A R/W R/W,R,R R3723 Archive708CurrentRecordNumber UINT16 0E8B R R,R,R R3724 Archive708RequestRecordNumber UINT16 0E8C R/W R/W,R/W,R/W R3725 Archive709MaximumRecords UINT16 0E8D R/W R/W,R,R R3726 Archive709CurrentRecordNumber UINT16 0E8E R R,R,R R3727 Archive709RequestRecordNumber UINT16 0E8F R/W R/W,R/W,R/W R3728 Archive710MaximumRecords UINT16 0E90 R/W R/W,R,R R3729 Archive710CurrentRecordNumber UINT16 0E91 R R,R,R R3730 Archive710RequestRecordNumber UINT16 0E92 R/W R/W,R/W,R/W R3731 Archive711MaximumRecords UINT16 0E93 R/W R/W,R,R R3732 Archive711CurrentRecordNumber UINT16 0E94 R R,R,R R3733 Archive711RequestRecordNumber UINT16 0E95 R/W R/W,R/W,R/W R

    Page50of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    3734 Archive712MaximumRecords UINT16 0E96 R/W R/W,R,R R3735 Archive712CurrentRecordNumber UINT16 0E97 R R,R,R R3736 Archive712RequestRecordNumber UINT16 0E98 R/W R/W,R/W,R/W R3737 ArchiveFileStatus(0=OK,1=Error) UINT16 0E99 R R,,R R3738 TimeTaginMMDDorDDMMFormat UINT16 0E9A R R,,R R3739 TimeTaginYYHHFormat UINT16 0E9B R R,,R R3740 TimeTaginMMSSFormat UINT16 0E9C R R,,R R3741 NewArchiveFileExistsBit(B0=Arc701,

    B9=Arc710)UINT16 0E9D R R,,R R

    3742 3744Reserved3746 StartingIndexofDisplayedDatabase

    RegistersUINT16 0EA2 R/W R/W,,R Y R

    3747 DefaultSnapshotReportTemplate(Y/N) UINT16 0EA3 R/W R/W,,R N R3748 DefaultBatchReportTemplate(Y/N) UINT16 0EA4 R/W R/W,,R N R3749 DefaultDailyReportTemplate(Y/N) UINT16 0EA5 R/W R/W,,R N R3750 DefaultProveReportTemplate(Y/N) UINT16 0EA6 R/W R/W,,R N R3751 RunSwitchInAutoMode(0=No,1=Yes) UINT16 0EA7 R/W R/W,,R N R3752 RunSwitchTimer(Seconds) UINT16 0EA8 R/W R/W,,R N R3753 HV1DetailedStatusBytes1&2 UINT16 0EA9 R R,,R R3754 HV1DetailedStatusBytes3&4 UINT16 0EAA R R,,R R3755 HV1DetailedStatusBytes5&6 UINT16 0EAB R R,,R R3756 HV1DetailedStatusBytes7&8 UINT16 0EAC R R,,R R3757 HV2DetailedStatusBytes1&2 UINT16 0EAD R R,,R R3758 HV2DetailedStatusBytes3&4 UINT16 0EAE R R,,R R3759 HV2DetailedStatusBytes5&6 UINT16 0EAF R R,,R R3760 HV2DetailedStatusBytes7&8 UINT16 0EB0 R R,,R R3761 HV3DetailedStatusBytes1&2 UINT16 0EB1 R R,,R R3762 HV3DetailedStatusBytes3&4 UINT16 0EB2 R R,,R R3763 HV3DetailedStatusBytes5&6 UINT16 0EB3 R R,,R R3764 HV3DetailedStatusBytes7&8 UINT16 0EB4 R R,,R R3765 HV4DetailedStatusBytes1&2 UINT16 0EB5 R R,,R R3766 HV4DetailedStatusBytes3&4 UINT16 0EB6 R R,,R R3767 HV4DetailedStatusBytes5&6 UINT16 0EB7 R R,,R R3768 HV4DetailedStatusBytes7&8 UINT16 0EB8 R R,,R R

    Page51of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    3769 NumberofHistoricalAlarmstoBeRetrieved

    UINT16 0EB9 R/W R/W,R/W,R/W Y R

    3770 Component'n'for%Methane UINT16 0EBA R/W R/W,,R N R3771 Component'n'for%Nitrogen UINT16 0EBB R/W R/W,,R N R3772 Component'n'for%CO2 UINT16 0EBC R/W R/W,,R N R3773 Component'n'for%Ethane UINT16 0EBD R/W R/W,,R N R3774 Component'n'for%Propane UINT16 0EBE R/W R/W,,R N R3775 Component'n'for%Water UINT16 0EBF R/W R/W,,R N R3776 Component'n'for%HydrogenSulfide UINT16 0EC0 R/W R/W,,R N R3777 Component'n'for%Hydrogen UINT16 0EC1 R/W R/W,,R N R3778 Component'n'for%CarbonMonoxide UINT16 0EC2 R/W R/W,,R N R3779 Component'n'for%Oxygen UINT16 0EC3 R/W R/W,,R N R3780 Component'n'for%iButane UINT16 0EC4 R/W R/W,,R N R3781 Component'n'for%nButane UINT16 0EC5 R/W R/W,,R N R3782 Component'n'for%iPentane UINT16 0EC6 R/W R/W,,R N R3783 Component'n'for%nPentane UINT16 0EC7 R/W R/W,,R N R3784 Component'n'for%nHexane UINT16 0EC8 R/W R/W,,R N R3785 Component'n'for%nHeptane UINT16 0EC9 R/W R/W,,R N R3786 Component'n'for%nOctane UINT16 0ECA R/W R/W,,R N R3787 Component'n'for%nNonane UINT16 0ECB R/W R/W,,R N R3788 Component'n'for%nDecane UINT16 0ECC R/W R/W,,R N R3789 Component'n'for%Helium UINT16 0ECD R/W R/W,,R N R3790 Component'n'for%Argon UINT16 0ECE R/W R/W,,R N R3791 Component'n'forHeatingValue UINT16 0ECF R/W R/W,,R N R3792 Component'n'forSpecificGravity UINT16 0ED0 R/W R/W,,R N R3793 Component'n'forNeoPentane UINT16 0ED1 R/W R/W,,R N R3797 3799Reserved

    16BitIntegerData

    Info:Register3800Toavoidflushingtheaudittrail,auditeventsotherthancompletedownloadstotheflowcomputerareusuallynotdocumentedintheaudittrailunlessserialportpasswRigorousauditingofaserialportorgroupofserialportscanbeactivatedbyplacingtheappropriatehexadecimalcodein3800(S=SerialPort).000000AA=AuditS10000AA00=AuditS200AA0000=AuditS3AA000000=AuditS400000005=AuditS500000050=AuditS6Tomonitormulpleports;e.g:A

    Info:Registers3803,3805,3807Unsignedintegertotalizerscumulativebased.Theyrollat65536.

    Page52of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    Info:Registers3802,3804,3806,3808,3809,38102scomplementnumbersbasedonspanentries17176through17189.Valuesexpressedaspercentagesofspanintenthpercentincrements.i.e.1000represents100.0%.Nooverrangeorunderrangecheckingisdone.

    3800 SpecialDiagnosticFunction UINT16 0ED8 R/W R/W,,R RUsedtoenable'AuditTrail'reportingofallserialport

    3802 StationCurrentNet(GSV)Flowrate UINT16 0EDA R R,,R R3803 StationNetTotal16Bits UINT16 0EDB R R,,R R3804 StationCurrentGross(IV)Flowrate%(0

    999)UINT16 0EDC R R,,R R

    3805 StationGross(IV)Total16Bits UINT16 0EDD R R,,R R3806 StationMassFlowrate%(0999) UINT16 0EDE R R,,R R3807 StationMassTotal16Bits UINT16 0EDF R R,,R R3811 StationEnergyFlowrate%(0999) UINT16 0EE3 R R,,R R3812 StationEnergyTotal16Bits UINT16 0EE4 R R,,R R3813 Product1TableSelect UINT16 0EE5 R/W R/W,R,R N R3814 Product2TableSelect UINT16 0EE6 R/W R/W,R,R N R3815 Product3TableSelect UINT16 0EE7 R/W R/W,R,R N R3816 Product4TableSelect UINT16 0EE8 R/W R/W,R,R N R3817 Product1AGA8Method UINT16 0EE9 R/W R/W,R,R N R3818 Product2AGA8Method UINT16 0EEA R/W R/W,R,R N R3819 Product3AGA8Method UINT16 0EEB R/W R/W,R,R N R3820 Product4AGA8Method UINT16 0EEC R/W R/W,R,R N R3821 Product1HeatingValueMethodSelect UINT16 0EED R/W 0=AGA5(1999)

    1=GPA2172(1996)2=ISO697615/15C3=ISO69760/0C4=ISO697615/0C5=ISO697625/0C6=ISO697620/20C7=ISO697625/20C8=AGA5(2009)Revision27.75.06andhigher9=GPA2172(2009)Revision27.75.06andhigher

    R/W,R,R N R

    Page53of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    3822 Product2HeatingValueMethodSelect UINT16 0EEE R/W 0=AGA5(1999)1=GPA2172(1996)2=ISO697615/15C3=ISO69760/0C4=ISO697615/0C5=ISO697625/0C6=ISO697620/20C7=ISO697625/20C8=AGA5(2009)Revision27.75.06andhigher9=GPA2172(2009)Revision27.75.06andhigher

    R/W,R,R N R

    3823 Product3HeatingValueMethodSelect UINT16 0EEF R/W 0=AGA5(1999)1=GPA2172(1996)2=ISO697615/15C3=ISO69760/0C4=ISO697615/0C5=ISO697625/0C6=ISO697620/20C7=ISO697625/20C8=AGA5(2009)Revision27.75.06andhigher9=GPA2172(2009)Revision27.75.06andhigher

    R/W,R,R N R

    3824 Product4HeatingValueMethodSelect UINT16 0EF0 R/W 0=AGA5(1999)1=GPA2172(1996)2=ISO697615/15C3=ISO69760/0C4=ISO697615/0C5=ISO697625/0C6=ISO697620/20C7=ISO697625/20C8=AGA5(2009)Revision27.75.06andhigher9=GPA2172(2009)Revision27.75.06andhigher

    R/W,R,R N R

    3826 DualPulseDelayCycle UINT16 0EF2 R/W R/W,R,R N R3827 Select0=UseActualBTU,1=UseDry

    SuperiorUINT16 0EF3 R/W heGCheatingvalueselectionisaddedfor27.75.01

    andhigher.R/W,R,R N R

    Page54of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    3829 FlowrateAverageFactor UINT16 0EF5 R/W R/W,,R N R3830 PrintPriority UINT16 0EF6 R/W R/W,,R N R3831 NumberofNullsAfterCR UINT16 0EF7 R/W R/W,,R N R3832 PrintIntervalinMinutes UINT16 0EF8 R/W R/W,,R N R3833 WeeklyBatchSelect(17) UINT16 0EF9 R/W R/W,,R N R3834 MonthlyBatchSelect(131) UINT16 0EFA R/W R/W,,R N R3835 HourlyBatchSelect(Y/N) UINT16 0EFB R/W R/W,,R N R3837 GasChromatographAnalyzerType UINT16 0EFD R/W R/W,R,R N R3838 ClearDailyatBatchEnd UINT16 0EFE R/W R/W,,R N R3839 AnalyzerNumber UINT16 0EFF R/W R/W,,R N R3840 ResultsInterval UINT16 0F00 R/W R/W,,R N R3841 ListenOnly UINT16 0F01 R/W R/W,,R N R3842 SelectDate0=dd/mm/yy,1=mm/dd/yy UINT16 0F02 R/W R/W,R,R Y R3843 DanalyzerAlarmWord3046 UINT16 0F03 R R,R,R R3844 DanalyzerAlarmWord3047 UINT16 0F04 R R,R,R R3845 DanalyzerAlarmWord3048 UINT16 0F05 R R,R,R R3846 DanalyzerAlarmWord3049 UINT16 0F06 R R,R,R R3847 DanalyzerAlarmWord3050 UINT16 0F07 R R,R,R R3848 DanalyzerAlarmWord3051 UINT16 0F08 R R,R,R R3849 DanalyzerAlarmWord3052 UINT16 0F09 R R,R,R R3850 DanalyzerAlarmWord3053 UINT16 0F0A R R,R,R R3851 DanalyzerAlarmWord3054 UINT16 0F0B R R,R,R R3852 DanalyzerAlarmWord3055 UINT16 0F0C R R,R,R R3853 DanalyzerAlarmWord3056 UINT16 0F0D R R,R,R R3854 DanalyzerAlarmWord3057 UINT16 0F0E R R,R,R R3855 DanalyzerCycleStartMonth UINT16 0F0F R R,R,R R3856 DanalyzerCycleStartDay UINT16 0F10 R R,R,R R3857 DanalyzerCycleStartYear UINT16 0F11 R R,R,R R3858 DanalyzerCycleStartHour UINT16 0F12 R R,R,R R3859 DanalyzerCycleStartMinute UINT16 0F13 R R,R,R R3860 Danalyzer2CycleStartMonth UINT16 0F14 R R,R,R R3861 Danalyzer2CycleStartDay UINT16 0F15 R R,R,R R3862 Danalyzer2CycleStartYear UINT16 0F16 R R,R,R R3863 Danalyzer2CycleStartHour UINT16 0F17 R R,R,R R3864 Danalyzer2CycleStartMinute UINT16 0F18 R R,R,R R3867 CURRENTHOUR UINT16 0F1B R/W R/W,,R R3868 CURRENTMINUTE UINT16 0F1C R/W R/W,,R R3869 CURRENTSECOND UINT16 0F1D R/W R/W,,R R

    Page55of212 2/1/2013

  • Application27.75ModbusDatabaseMetricGasDP/PulseMeter

    ModbusIndex

    Description DataType HexValue

    Access Notes LevelA,B,C LockedFP

    LockedSerial

    3870 CURRENTMONTH UINT16 0F1E R/W R/W,,R R3871 CURRENTDATE UINT16 0F1F R/W R/W,,R R3872 CURRENTYEAR UINT16 0F20 R/W R/W,,R R3873 DAYOFWEEK UINT16 0F21 R/W R/W,,R R3874 DisableDailyReport(0=No,1=Yes) UINT16 0F22 R/W R/W,,R N R3875 JulianDay(ofdayssincefirstdayof

    January)UINT16 0F23 R R,,R R

    3877 GC2IDNumber UINT16 0F25 R/W R/W,,R N R3879 GC1StreamNumber UINT16 0F27 R R,,R R3880 OverrideCodeRef.S.G. UINT16 0F28 R/W R/W,,R Y R3881 OverrideCodeMol%Nitrogen UINT16 0F29 R/W R/W,,R Y R3882 OverrideCodeMol%CO2 UINT16 0F2A R/W R/W,,R Y R3883 OverrideCodeHeatingValue UINT16 0F2B R/W R/W,,R Y R3884 AnalyzerFailCode UINT16 0F2C R/W R/W,,R N R3885 DanalyzerVersion0=USA,1=UK UINT16 0F2D R/W R/W,,R N R3886 GC2StreamNumber UINT16 0F2E R R,,R R3887 GC'n'InUse(1=GC1,2=GC2) UINT16 0F2F R R,,R R3888 Danalyzer2AlarmWord3046 UINT16 0F30 R R,,R R3889 Danalyzer2AlarmWord3047 UINT16 0F31 R R,,R R3890 Danalyzer2AlarmWord3048 UINT16 0F32 R R,,R R3891 Danalyzer2AlarmWord3049 UINT16 0F33 R R,,R R3892 Danalyzer2AlarmWord3050 UINT16 0F34 R R,,R R3893 Danalyzer2AlarmWord3051 UINT16 0F35 R R,,R R3894 Danalyzer2AlarmWord3052 UINT16 0F36 R R,,R R3895 Danalyzer2AlarmWord3053 UINT16 0F37 R R,,R R3896 Danalyzer2AlarmWord3054 UINT16 0F38 R R,,R R3897 Danalyzer2AlarmWord3055 UINT16 0F39 R R,,R R3898 Danalyzer2AlarmWord3056 UINT16 0F3A R R,,R R3899 Danalyzer2AlarmWord3057 UINT16 0F3B R R,,R R

    16BitIntegerData

    3901 ProveRun UINT16 0F3D R R,R,R R3902 ProvingMeterNumber UINT16 0F3E R R,R,R R3907 ArchiveAllProveReport(0=No,1=Yes) UIN