API Curriculum Module on Fault Calculations
-
Upload
adrian-tan -
Category
Documents
-
view
192 -
download
5
Transcript of API Curriculum Module on Fault Calculations
COLLABORATIVE POWER ENGINEERING CENTRES OF EXCELLENCE
FAULT CALCULATIONS IN
POWER SYSTEMS
PROF. ARINDAM GHOSH
School of Engineering Systems
Queensland University of Technology
Brisbane, Queensland
Course Notes
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 i
© Queensland University of Technology, 2010
No part of this material may be reproduced without permission. For enquiries and requests to access
resources, contact the API University Representative on the Australian Power Institute website:
www.api.edu.au - Collaborative Power Engineering Centres of Excellence.
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 ii
Table of Contents
Introduction: Setting the Scene 1
Assumed Knowledge 1
Objectives 1
Teaching and Learning Approaches 2
Module Resources 2
Course Notes 2
Presentation Packs 2
Activities 2
Acknowledgment 2
Author/s and Contact Details 3
1. Fault in an AC Circuit 5
2. Synchronous Machine Model 7
2.1 Short Circuit on an Unloaded Synchronous Generator 12
3. Symmetrical Faults in a Power System 15
3.1. Calculation of Fault Current using Impedance Diagram 15
3.2. Calculation of Fault Current using Zbus Matrix 17
4. Symmetrical Components 21
4.1. Symmetrical Component Transformation 21
4.2. Real and Reactive Power 25
4.3. Orthogonal Transformation 26
5. Sequence Circuits for Loads 29
5.1. Sequence Circuit for a Y-Connected Load 29
5.2. Sequence Circuit for a -Connected Load 30
6. Sequence Circuits for Synchronous Generator 35
7. Sequence Circuits for Symmetrical Transmission Line 37
8. Sequence Circuits for Transformers 41
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 iii
8.1. Y-Y Connected Transformer 41
8.2 - Connected Transformer 43
8.3 Y- Connected Transformer 44
9. Sequence Networks 47
10. Unsymmetrical Faults 49
10.1 Single-Line-to-Ground Fault 49
10.2 Line-to-Line Fault 52
10.3 Double-Line-to-Ground Fault 55
10.4 Fault Current Computation using Sequence Networks 59
Conclusions 68
References 68
INTRODUCTION AND OVERVIEW
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 1
INTRODUCTION: SETTING THE SCENE
Short circuits occur in power system due to various reasons like, equipment failure, lightning strikes,
falling of branches or trees on the transmission lines, switching surges, insulation failures and other
electrical or mechanical causes. All these are collectively called faults in power systems. A fault
usually results in high current flowing through the lines and if adequate protection is not taken, may
result in damages in the power apparatus. In this module, we shall discuss the effects of both
symmetrical faults and unsymmetrical on the system. Here the term symmetrical fault refers to those
conditions in which all three phases of a power system are grounded at the same point. For this
reason the symmetrical faults sometimes are also called three-line-to-ground (3LG) faults. The
unsymmetrical faults are of three types. These are:
Single-line-to-ground (1LG) fault
Line-to-line (LL) fault
Double-line-to-ground (2LG) fault
We shall first discuss the behavior of electrical circuits and synchronous generators under faulted
condition. We shall proceed to calculate fault currents in a network under balanced fault condition.
Following this, we shall discuss symmetrical components and how a power network can be modeled
for unbalanced operation. Finally we shall discuss unsymmetrical fault current calculations.
ASSUMED KNOWLEDGE
It is assumed that you will have a basic knowledge of:
Basic three-phase circuits and phasor calculations
Synchronous generators
Power systems representation and impedance diagrams
Ybus formulation
OBJECTIVES
On completion of this module you should be able to:
1. Compute fault currents for symmetrical faults.
2. Compute fault currents for unsymmetrical faults.
3. Compute and analyze circuits in terms of symmetrical components.
4. Use concepts learned in designing protective devices.
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 2
TEACHING AND LEARNING APPROACHES
This module is best taught through a combination of:
Group lectures presented by the instructor using the PowerPoint Slides which are part of the module material,
Group lecture discussions coordinated by the instructor,
Individual study of the notes provided to review lectures and learn details required to perform activities,
Performing individually fault calculations using calculators, and
Performing individually simulation studies to analyze different types of faults.
A set of presentation packs and activities are available in addition to the course notes as a suite of
resources for this module. These are listed below and can be downloaded by visiting www.api.edu.au
– Collaborative Power Engineering Centres of Excellence.
MODULE RESOURCES
COURSE NOTES
Fault Calculations in Power Systems
PRESENTATION PACKS
Symmetrical Faults (2 hrs)
Symmetrical Faults and Symmetrical Components (2 hrs)
Sequences Circuits of Loads, Generator and Line (2 hrs)
Sequence Circuits of Transformers and Sequence Networks (2 hrs)
Unsymmetrical Fault Current Calculations. (2 hrs)
Fault Current Calculation Examples (2 hrs)
ACTIVITIES
Tutorial: Fault Calculations - Problem Set (3 hrs)
Practical: Overcurrent Protection Coordination (1 hr)
Fault Calculations - PSCAD Simulation Exercise (3 hrs)
ACKNOWLEDGMENT
The author wishes to thank Dr. Manjula Dewadasa for his help in preparing the simulation example.
Also, this material has been developed with the support of API.
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 3
AUTHOR/S AND CONTACT DETAILS
Prof. Arindam Ghosh
Professor in Power Engineering
School of Engineering Systems
Queensland University of Technology
Brisbane, Queensland
Email: [email protected]
COURSE NOTES
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 5
1. FAULT IN AN AC CIRCUIT
Consider the single-phase circuit of Fig. 1 where Vs = 240 V (rms), the system frequency is 50 Hz, R =
0.864 , L = 11 mH (L = 3.46 ) and the load is R-L comprising of an 8.64 resistor and a 49.5 mH
inductor (L = 15.55 ). The current phasor when the switch S is open is given by
43.6329.1110.1005.501.19504.9
240j
jI A
This means that the current has a peak value of (11.29×2 =) 15.97 A.
We shall now use the switch S to simulate a short circuit across the load. When the switch is closed,
the fault current is given by
98.7523.672965301646.3864.0
240.j .
jI A
This implies that the fault current has a peak value of (67.23×2 =) 95.17 A. The current (i) waveform
is shown in Fig. 2. Even though the steady state fault current is about 6 times the un-faulted load
current, the peak of the transient current is around 125 A, i.e., over 10 times higher than the nominal
current. The peak current depends on the time of inception of the fault that is unpredictable.
We shall now discuss model of synchronous machine and how it can be represented in fault studies.
Fig. 1. A single-phase circuit in which a source supplies a load through a source impedance.
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 6
Fig. 2. The current waveform of the circuit of Fig. 5 before and after the closing of the switch S.
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 7
2. SYNCHRONOUS MACHINE MODEL
The schematic diagram of a synchronous generator is shown in Fig. 3. This contains three stator
windings that are spatially distributed. It is assumed that the windings are wye-connected. The
winding currents are denoted by ia, ib and ic. The rotor contains the field winding the current through
which is denoted by if. The field winding is aligned with the so-called direct (d) axis. We also define a
quadrature (q) axis that leads the d-axis by 90°. The angle between the d-axis and the a-phase of the
stator winding is denoted by θd.
Fig. 3. Schematic diagram of a synchronous generator.
Let the self-inductance of the stator windings be denoted by Laa, Lbb, Lcc such that
ccbbaas LLLL (1)
and the mutual inductance between the windings be denoted as
cabcabs LLLM (2)
The mutual inductances between the field coil and the stator windings vary as a function of θd and are
given by
dfaf ML cos (3)
120cos dfbf ML (4)
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 8
120cos dfcf ML (5)
The self-inductance of the field coil is denoted by Lff.
The flux linkage equations are then given by
fafcbsasfafccababaaaa iLiiMiLiLiLiLiL (6)
fbfcasbsb iLiiMiL (7)
fafbascsc iLiiMiL (8)
fffccfbbfaaff iLiLiLiL (9)
For balanced operation we have
0 cba iii
Hence, the flux linkage equations for the stator windings (6) to (8) can be modified as
fafassa iLiML (10)
fbfbssb iLiML (11)
fcfcssc iLiML (12)
For steady state operation we can assume
constant ff Ii (13)
Also assuming that the rotor rotates at synchronous speed ωs, we obtain the following two equations
dt
d ds
(14)
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 9
0dsd t (15)
where θd0 is the initial position of the field winding with respect to the phase-a of the stator winding
at time t = 0. The mutual inductance of the field winding with all the three stator windings will vary as
a function of θd, i.e.,
0cos dsfaf tML (16)
120cos 0dsfbf tML (17)
120cos 0dsfcf tML (18)
Substituting (13) and (16) to (18) in (10) to (12) we get
0cos dsffassa tIMiML (19)
120cos 0dsffbssb tIMiML (20)
120cos 0dsffcssc tIMiML (21)
Since we assume balanced operation, we need to treat only one phase. Let the armature resistance of
the generator be R. The generator terminal voltage is given by
dt
dRi a
aa
(22)
where the negative sign is used for generating mode of operation in which the current leaves the
terminal. Substituting (19) in (22) we get
0sin dssffa
ssaa tIMdt
diMLRi
(23)
The last term of (23) is the internal emf ea that is given by
0sin||2 dsia tEe (24)
where the rms magnitude |Ei| is proportional to the field current
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 10
2
ffs
i
IME
(25)
Since θd0 is the position of the d-axis at time t = 0, we define the position of the q-axis at that instant
as
900d (26)
Therefore (15) can be rewritten as
90 tsd (27)
Substituting (26) in (24) we get
tEe sia cos||2 (28)
Replacing the last term of (23) by the internal emf ea, we get
aa
ssaa edt
diMLRi
(29)
The equivalent circuit of a synchronous generator is shown in Fig. 4. Let the current ia lag the internal
emf ea by θa. The stator currents are then
asaa tIi cos||2 (30)
120cos||2 asab tIi (31)
120cos||2 asac tIi (32)
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 11
Fig. 4. Three-phase equivalent circuit of a synchronous generator.
The single-phase equivalent circuit of the generator is shown in Fig. 5. The phase angle θa between ea
and ia is rather difficult to measure under load as ea is the no load voltage. To avoid this, we define
the phase angle between va and ia to be θ. We assume that ea leads va by δ. Therefore we can write
a (33)
Then the voltages and currents shown in Fig. 5 are given as
tV saa cos2 (34)
)cos(2 tEe sia (35)
)cos(2 tIi saa (36)
Equations (34) to (36) imply that
aaiaaa IIEEVV and ,0 (37)
From Fig. 5, we define the synchronous impedance as
sssdd MLjRjXRZ (38)
Then the terminal voltage equation can be written as
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 12
adaa IjXREV (39)
In general, the resistance R is negligible compared to the d-axis reactance. Therefore the machine can
be represented by the classical voltage behind a reactance model. For a cylindrical rotor machine, the
d-axis reactance is equal to the q-axis reactance. This is usually called the synchronous reactance Xs.
Therefore (39) can be modified as
adaasaa IjXEIjXEV (40)
Fig. 5. Single-phase equivalent circuit of a synchronous generator.
2.1 SHORT CIRCUIT ON AN UNLOADED SYNCHRONOUS GENERATOR
Fig. 6 shows a typical response of the armature current when a three-phase symmetrical short circuit
occurs at the terminals of an unloaded synchronous generator. It is assumed that there is no dc offset
in the armature current. From a high initial value, the magnitude of the current decreases
exponentially. This is due to the fact that the machine reactance changes due to the effect of
armature reaction. When a short circuit occurs, the flux linking the stator and the rotor cannot
change instantaneously due to the eddy currents flowing in the rotor and damper circuits. These eddy
currents oppose the change. The reactance due to the armature reaction is small during the initial
phase. The eddy current in the damper circuit decays first, followed by the decay of the eddy current
in the field circuit. Then the armature reaction gets to establish.
Fig. 6. Armature current of a synchronous generator as a short circuit occurs at its terminals.
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 13
The instantaneous expression for the fault current shown in Fig. 6 is given by
t
Xe
XXe
XXVti s
d
Tt
dd
Tt
dd
tfdd sin
111112
(41)
where Vt is the magnitude of the terminal voltage, and
dX is the direct axis subtransient reactance
dX is the direct axis transient reactance
dX is the direct axis synchronous reactance
with ddd XXX . The time constants are
dT is the direct axis subtransient time constant
dT is the direct axis transient time constant
In the expression of (41), we have neglected the effect of the armature resistance. Let us assume that
the fault occurs at time t = 0. Then the rms value of the initial current is
d
tff
X
VII
0
(42)
which is called the subtransient fault current. The duration of the subtransient current is dictated by
the time constant Td. As the time progresses and Td < t < Td, the first exponential term of (41) will
start decaying and will eventually vanish. However since t is still nearly equal to zero, we have the
following rms value of the current
d
tf
X
VI
(43)
This is called the transient fault current. Now as the time progress further and the second exponential
term also decays, we get the following rms value of the current for the sinusoidal steady state
d
tf
X
VI
(44)
In addition to the ac, the fault currents will also contain the dc offset. Note that a symmetrical fault
occurs when three different phases are in three different locations in the ac cycle. Therefore the dc
offsets in the three phases are different. The maximum value of the dc offset is given by
ATt
fdc eIi 2max
(45)
where TA is the armature time constant.
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 15
3. SYMMETRICAL FAULTS IN A POWER SYSTEM
3.1. CALCULATION OF FAULT CURRENT USING IMPEDANCE DIAGRAM
Let us first illustrate the calculation of the fault current using the impedance diagram with the help of
the following examples.
Example 1
Consider the power system of Fig. 7 in which a synchronous generator supplies a
synchronous motor. The motor is operating at rated voltage and rated MVA while
drawing a load current at a power factor of 0.9 (lagging) when a three phase
symmetrical short circuit occurs at its terminals. We shall calculate the fault current
that flow from both the generator and the motor.
We shall choose a base of 50 MVA, 20 kV in the circuit of the generator. Then the
motor synchronous reactance is given by
4.025
502.0 mX per unit
Also the base impedance in the circuit of the transmission line is
12.8750
662
baseZ
Fig.7. A generator supplying a motor load though a transmission line.
Therefore the impedance of the transmission line is
1148.012.87
10jjX line per unit.
The impedance diagram for the circuit is shown in Fig. 8 in which the switch S indicates
the fault.
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 16
Example 1
Fig. 8. Impedance diagram of the circuit of Fig. 7.
Before the fault, when the switch S is open, the motor draws a load at rated voltage
and rated MVA with 0.9 lagging power factor. Therefore
4359.09.09.0cos1 1 jIL per unit
Let us assume the voltage across the terminal A and B is 1.0 per unit when the fault
occurs. Then the subtransient voltages of the motor and the generator are
36.08256.04.00.1 jIjE Lm per unit
4633.02244.15148.00.1 jIjE Lg per unit
Hence, the subtransient fault currents, when the switch S closes, fed by the motor and
the generator are
0641.29.04.0
jj
EI m
m
per unit
3784.29.05148.0
jj
EI
g
g
per unit
and the total current flowing to the fault is
4425.4jIII mgf per unit
Note that the base current in the circuit of the motor is
8.1603183
1050 3
baseI A
Therefore while the load current was 1603.8 A, the fault current is 7124.7 A.
We shall now solve the above problem differently.
Example 2
The Thevenin impedance at the circuit between the terminals A and B of the circuit of
Fig. 8 is the parallel combination of the impedances j0.4 and j0.5148. This is then given
as
2251.05148.04.0
5148.04.0jjZth
per unit
Since voltage at the motor terminals before the fault is 1.0 per unit, the fault current is
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 17
Example 2
4425.40.1
jZ
Ith
f per unit
If we neglect the pre-fault current flowing through the circuit, then fault current fed by
the motor and the generator can be determined using the current divider principle,
i.e.,
5.25148.09148.0
0 jjj
II
f
m
per unit
9425.14.09148.0
0 jjj
II
f
g
per unit
If, on the other hand, the pre-fault current is not neglected, then the fault current
supplied by the motor and the generator are
0641.29.00 jIII Lmm per unit
3784.29.00 jIII Lgg per unit
3.2. CALCULATION OF FAULT CURRENT USING ZBU S MATRIX
Consider the circuit of Fig. 9 (a), the impedance diagram of which is drawn in Fig. 9 (b). We assume
that a symmetrical fault has occurred in bus-4 such that it is now connected to the reference bus. Let
us assume that the pre-fault voltage at this bus is Vf. To denote that bus-4 is short circuit, we add two
voltage sources Vf and Vf together in series between bus-4 and the reference bus. This is shown in
Fig. 9 (c). Also note that the subtransient fault current If flows from bus-4 to the reference bus. This
implies that a current that is equal to If is injected into bus-4. This current, which is due to the
source Vf will flow through the various branches of the network and will cause a change in the bus
voltages. Assuming that the two sources and Vf are short circuited, Vf is the only source left in the
network that injects a current If into bus-4. The voltages of the different nodes that are caused by
the voltage Vf and the current If are then given by
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 18
(a) (b)
(c)
Fig.9. (a) Single-line diagram of a simple power network, (b) its impedance diagram and (c) the equivalent network depicting
a symmetrical fault at bus-4.
f
bus
f I
Z
V
V
V
V
0
0
0
3
2
1
(46)
where the prefix indicates the changes in the bus voltages due to the current If.
From the fourth row of (14) we can write
ff IZV 44 (47)
Combining (46) and (47) we get
3,2,1,44
44 iV
Z
ZIZV f
ifii
(48)
We further assume that the system is unloaded before the fault occurs and that the magnitude and
phase angles of all the generator internal emfs are the same. Then there will be no current circulating
anywhere in the network and the bus voltages of all the nodes before the fault will be same and
equal to Vf. Then the new altered bus voltages due to the fault will be given from (48) by
4,,1,144
4
iV
Z
ZVVV f
iifi
(49)
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 19
Example 3
Let us consider following parameters, in per unit, for the impedance diagram of Fig. 9
(b)
Z11 = Z22 = j0.25, Z12 = j0.2, Z13 = j0.25, Z23 = Z34 = j0.4 and Z24 = j0.5
Then Ybus is then given as
5.45.220
5.295.24
25.25.135
04513
jYbus per unit
Inverting the Ybus matrix, we get the Zbus matrix as
3926019740136701133.0
19740256501236012640
13670123601531009690
0.1133126400969015310
...
....
....
...
jZbus per unit
Let us now assume that the internal voltages of both the generators are equal to
1.00. Then the current injected in both bus-1 and 2 will be given by 1.0/j0.25 = j4.0
per unit. Now the altered bus voltages for a symmetrical fault in bus-4 are given from
(49) as
7114.03926.0
1133.011 V per unit
6518.03926.0
1367.012 V per unit
4972.03926.0
1974.013 V per unit
03926.0
3926.014 V per unit
Also since the Thevenin impedance looking into the network at bus-4 is Z44, the
subtransient fault current flowing from bus-4 is
5471.23926.0
1j
jI f per unit
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 21
4. SYMMETRICAL COMPONENTS
An unbalanced three-phase system can be resolved into three balanced systems in the sinusoidal
steady state. This method of resolving an unbalanced system into three balanced phasor system has
been proposed by C. L. Fortescue. This method is called resolving symmetrical components of the
original phasors or simply symmetrical components. In this section we shall discuss symmetrical
components transformation and then will present how unbalanced components like Y- or -
connected loads, transformers, generators and transmission lines can be resolved into symmetrical
components. We can then combine all these components together to form what are called sequence
networks.
A system of three unbalanced phasors can be resolved in the following three symmetrical
components:
Positive Sequence: A balanced three-phase system with the same phase sequence as the original sequence.
Negative sequence: A balanced three-phase system with the opposite phase sequence as the original sequence.
Zero Sequence: Three phasors that are equal in magnitude and phase.
Fig. 10 depicts a set of three unbalanced phasors that are resolved into the three sequence
components mentioned above. In this the original set of three phasors are denoted by Va, Vb and Vc,
while their positive, negative and zero sequence components are denoted by the subscripts 1, 2 and 0
respectively. This implies that the positive, negative and zero sequence components of phase-a are
denoted by Va1, Va2 and Va0 respectively. Note that just like the voltage phasors given in Fig. 10, we
can also resolve three unbalanced current phasors into three symmetrical components.
Fig. 10. Representation of (a) an unbalanced network, its (b) positive sequence, (c) negative sequence and (d) zero
sequence.
4.1. SYMMETRICAL COMPONENT TRANSFORMATION
Before we discuss the symmetrical component transformation, let us first define the a-operator as
2
3
2
10120 jea j (50)
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 22
Note that for the above operator the following relations hold
on so and
1
2
3
2
1
22403606005
1203604804
3603
2402
000
000
0
0
aeeea
aeeea
ea
ajea
jjj
jjj
j
j
(51)
Also note that we have
02
3
2
1
2
3
2
111 2 jjaa
(52)
Using the a-operator we can write from Fig. 10 (b)
111
2
1 and acab aVVVaV (53)
Similarly from Fig. 10 (c) we get
2
2
222 and acab VaVaVV (54)
Finally from Fig. 10 (d) we get
000 cba VVV (55)
The symmetrical component transformation matrix is given by
c
b
a
a
a
a
V
V
V
aa
aa
V
V
V
2
2
2
1
0
1
1
111
3
1
(56)
Defining the vectors Va012 and Vabc as
c
b
a
abc
a
a
a
a
V
V
V
V
V
V
V
V ,
2
1
0
012
we can write (56) as
abca CVV 012 (57)
where C is the symmetrical component transformation matrix and is given by
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 23
aa
aaC2
2
1
1
111
3
1
(58)
The original phasor components can also be obtained from the inverse symmetrical component
transformation, i.e.,
012
1
aabc VCV (59)
Inverting the matrix C given in (58) and combining with (59) we get
2
1
0
1
2
1
0
2
2
1
1
111
a
a
a
a
a
a
c
b
a
V
V
V
C
V
V
V
aa
aa
V
V
V
(60)
From (60) we can write
210 aaaa VVVV (61)
21021
2
0 bbbaaab VVVaVVaVV (62)
2102
2
10 cccaaac VVVVaaVVV (63)
Finally, if we define a set of unbalanced current phasors as Iabc and their symmetrical components as
Ia012, we can then define
012
1
012
aabc
abca
ICI
CII
(64)
Example 4
Let us consider a set of balanced voltages given in per unit by
1200.1 and 1200.1 ,0.1 cba VVV
These imply
aVaV cb and 2
Then from (56) we get
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 24
Example 4
013
1 2
0 aaVa
pu 0.113
1 33
1 aaVa
013
1 24
2 aaVa
We then see that for a balanced system the zero and negative sequence voltages are
zero. Also the positive sequence voltage is the same as the original system, i.e.,
ccbbaa VVVVVV 111 and ,
All the quantities given in this example are in per unit.
Example 5
Let us now consider the following set of three unbalanced voltages
1209.0 and 1102.1 ,0.1 cba VVV
Resolving those using (56), we have
72.1470873.0
87.30296.1
16.681250.0
0466.00738.0
0695.00273.1
1161.00465.0
1209.0
1102.1
0.1
1
1
111
3
1
2
2
2
1
0
j
j
j
aa
aa
V
V
V
a
a
a
Therefore we have
16.68125.0000 cba VVV
87.1230296.1,13.1160296.1 11 cb VV
72.270973.0,72.2670873.0 22 cb VV
Furthermore note that
0.1210 aaaa VVVV
1102.1210 bbbb VVVV
1209.0210 cccc VVVV
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 25
4.2. REAL AND REACTIVE POWER
The three-phase power in the original unbalanced system is given by
abc
T
abcccbbaaabcabc IVIVIVIVjQP ***
(65)
where I is the complex conjugate of the vector I. Now from (59) and (64) we get
012
1
012 a
TT
aabcabc ICCVjQP (66)
Noting that
100
010
001
31CC T
we can write (66) as
2211003 aaaaaaabcabc IVIVIVjQP (67)
Thus the complex power is three times the summation of the complex power of the three
phase sequences.
Example 6
Let us consider the voltages given in Example 5. Let us further assume that
these voltages are line-to-neutral voltages and they supply a balanced Y-
connected load whose per phase impedance is ZY = 0.2 + j0.8 per unit. Then the
per unit currents in the three phases are
96.752127.1Y
aa
Z
VI pu
04.1744552.1Y
bb
Z
VI pu
04.440914.1Y
cc
Z
VI pu
Then the real and reactive power consumed by the load is given by
pu 9559.0
96.75cos0914.19.04552.12.12127.10.1
abcP
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 26
Example 6
pu 8235.3
96.75sin0914.19.04552.12.12127.10.1
abcQ
Now using the transformation (64) we get
75.711058.0
10.722486.1
12.1441516.0
1005.00331.0
1881.13839.0
0889.01229.0
2
1
0
j
j
j
I
I
I
a
a
a
pu
From the results given in Example 5 and from the above values we can compute
the zero sequence complex power as
0552.00138.03 0000 jIVjQP aa pu
The positive sequence complex power is
7415.39354.03 1111 jIVjQP aa pu
Finally the negative sequence complex power is
0269.00067.03 2222 jIVjQP aa pu
Adding the three complex powers together we get the total complex power
consumed by the load as
8235.39559.0210210 jQQQjPPPjQP abcabc pu
4.3. ORTHOGONAL TRANSFORMATION
Instead of the transformation matrix given in (58), let us instead use the transformation
matrix
aa
aaC2
2
1
1
111
3
1
(68)
The inverse of the above matrix is
2
21
1
1
111
3
1
aa
aaC
(69)
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 27
Note from (68) and (69) that C1 = (CT). We can therefore state C(CT) = I3, where I3 is (33)
identity matrix. Therefore the transformation matrices given in (68) and (69) are orthogonal.
Now since
100
010
0011 CCCC TT
we can write from (66)
221100 aaaaaaabcabc IVIVIVjQP (70)
This implies that real and reactive powers are directly obtained by the polar multiplication
voltage and current of the symmetrical component voltage and conjugate of currents. The
factor 3 is absent using this transformation, unlike that given in (67).
We shall now discuss how different elements of a power system are represented in terms of their
sequence components. In fact we shall show that each element is represented by three equivalent
circuits, one for each symmetrical component sequence.
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 29
5. SEQUENCE CIRCUITS FOR LOADS
In this section we shall construct sequence circuits for both Y and -connected loads separately.
5.1. SEQUENCE CIRCUIT FOR A Y-CONNECTED LOAD
Consider the balanced Y-connected load that is shown in Fig. 11. The neutral point (n) of the windings
are grounded through an impedance Zn. The load in each phase is denoted by ZY. Let us consider
phase-a of the load. The voltage between line and ground is denoted by Va, the line-to-neutral
voltage is denoted by Van and voltage between the neutral and ground is denoted by Vn. The neutral
current is then
02221110 33 acbacbaa
cban
IIIIIIII
IIII
(71)
Therefore there will not be any positive or negative sequence current flowing out of the neutral
point.
Fig. 11. Schematic diagram of a balanced Y-connected load.
The voltage drop between the neutral and ground is
03 ann IZV (72)
Now
03 anannana IZVVVV (73)
We can write similar expression for the other two phases. We can therefore write
1
1
1
3 0an
c
b
a
Y
n
n
n
cn
bn
an
c
b
a
IZ
I
I
I
Z
V
V
V
V
V
V
V
V
V
(74)
Pre-multiplying both sides of the above equation by the matrix C and using (58) we get
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 30
1
1
1
3 0012012 CIZIZV anaYa
(75)
Now since
0
0
1
1
1
1
C
We get from (75)
0
03
0
2
1
0
2
1
0 a
n
a
a
a
Y
a
a
a I
Z
I
I
I
Z
V
V
V
(76)
We then find that the zero, positive and negative sequence voltages only depend on their respective
sequence component currents. The sequence component equivalent circuits are shown in Fig. 12.
While the positive and negative sequence impedances are both equal to ZY, the zero sequence
impedance is equal to
nY ZZZ 30 (77)
If the neutral is grounded directly (i.e., Zn = 0), then Z0 = ZY. On the other hand, if the neutral is kept
floating (i.e., Zn = ), then there will not be any zero sequence current flowing in the circuit at all.
Fig. 12. Sequence circuits of Y-connected load: (a) positive, (b) negative and (c) zero sequence.
5.2. SEQUENCE CIRCUIT FOR A -CONNECTED LOAD
Consider the balanced -connected load shown in Fig. 13 in which the load in each phase is denoted
by Z. The line-to-line voltages are given by
caca
bcbc
abab
IZV
IZV
IZV
(78)
Adding these three voltages we get
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 31
cabcabcabcab IIIZVVV (79)
Denoting the zero sequence component Vab, Vbc and Vca as Vab0 and that of Iab, Ibc and Ica as Iab0 we can
rewrite (79) as
00 abab IZV (80)
Fig. 13. Schematic diagram of a balanced -connected load.
Again since
0 accbbacabcab VVVVVVVVV
we find from (80) that Vab0 = Iab0 = 0. Hence a -connected load with no mutual coupling does not
have any zero sequence circulating current. Note that the positive and negative sequence impedance
for this load will be equal to Z.
Example 7
Consider the circuit shown in Fig. 14 in which a -connected load is connected in
parallel with a Y-connected load. The neutral point of the Y-connected load is
grounded through an impedance. Applying Kirchoff’s current law at the point P in the
circuit we get
Y
ncba
Y
Y
nacabaa
Z
VVV
ZV
ZZ
Z
VV
Z
VV
Z
VVI
112
The above expression can be written in terms of the vector Vabc as
Y
nabca
Y
aZ
VV
ZV
ZZI
111113
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 32
Example 7
Fig. 14. Parallel connection of balanced and Y-connected loads.
Since the load is balanced we can write
1
1
1
111
111
111113
Y
nabcabc
Y
abcZ
VV
ZV
ZZI
Pre-multiplying both sides of the above expression by the transformation matrix C we
get
1
1
1
111
111
111113
012
1
012012 CZ
VVCC
ZV
ZZI
Y
naa
Y
a
Now since
000
000
003
111
111
1111CC
we get
0
0
1313
0012012
Y
naa
Y
aZ
VV
ZV
ZZI
Separating the three components, we can write from the above equation
11
13a
Y
a VZZ
I
22
13a
Y
a VZZ
I
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 33
Example 7
n
Y
a
Y
a VZ
VZ
I11
00
Suppose now if we convert the -connected load into an equivalent Y, then the
composite load will be a parallel combination of two Y-connected circuits one with
an impedance of ZY and the other with an impedance of Z/3. Therefore the positive
and the negative sequence impedances are given by the parallel combination of these
two impedances. The positive and negative sequence impedance is then given by
3
3
ZZ
ZZ
Y
Y
Now refer to Fig. 14. The voltage Vn is given by
03 aYncYbYaYnn IZIIIZV
From Fig. 14 we can also write Ia = Ia + IaY. Therefore
cYbYaYbccaabbccaab
cYbYaYcbacba
IIIIIIIII
IIIIIIIII
This implies that Ia0 = IaY0 and hence Vn = 3ZnIa0. We can then rewrite the zero sequence
current expression as
nY
aa
ZZ
VI
3
00
It can be seen that the Z term is absent from the zero sequence impedance.
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 35
6. SEQUENCE CIRCUITS FOR SYNCHRONOUS GENERATOR
The three-phase equivalent circuit of a synchronous generator is shown in Fig. 15, where the neutral
point grounded through a reactor with impedance Zn. The neutral current is then given by
cban IIII (81)
Fig. 15. Equivalent circuit of a synchronous generator with grounded neutral.
The derivation of Section 1 assumes balanced operation which implies Ia + Ib + Ic = 0. As per (81) this
assumption is not valid any more. Therefore with respect to this figure we can write for phase-a
voltage as
ancbasass
ancbsasan
EIIIMjIMjLjR
EIIMjILjRV
(82)
Similar expressions can also be written for the other two phases. We therefore have
cn
bn
an
c
b
a
s
c
b
a
ss
cn
bn
an
E
E
E
I
I
I
Mj
I
I
I
MLjR
V
V
V
111
111
111
(83)
Pre-multiplying both sides of (83) by the transformation matrix C we get
2
1
0
2
1
0
1
2
1
0
2
1
0
111
111
111
an
an
an
a
a
a
s
a
a
a
ss
an
an
an
E
E
E
I
I
I
CCMj
I
I
I
MLjR
V
V
V
(84)
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 36
Since the synchronous generator is operated to supply only balanced voltages we can assume that
Ean0 = Ean2 = 0 and Ean1 = Ean. We can therefore modify (84) as
0
0
000
000
003
2
1
0
2
1
0
2
1
0
an
a
a
a
s
a
a
a
ss
an
an
an
E
I
I
I
Mj
I
I
I
MLjR
V
V
V
(85)
We can separate the terms of (85) as
0000 2 agassan IZIMLjRV (86)
1111 aananassan IZEEIMLjRV (87)
2222 aassan IZIMLjRV (88)
Furthermore we have seen for a Y-connected load that Va1 = Van1, Va2 = Van2 since the neutral current
does not affect these voltages. However Va0 = Van0 + Vn. Also we know that Vn = 3ZnIa0. We
can therefore rewrite (86) as
00000 3 aanga IZIZZV (89)
The sequence diagrams for a synchronous generator are shown in Fig. 16.
Fig. 16. Sequence circuits of synchronous generator: (a) positive, (b) negative and (c) zero sequence.
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 37
7. SEQUENCE CIRCUITS FOR SYMMETRICAL TRANSMISSION LINE
The schematic diagram of a transmission line is shown in Fig. 17. In this diagram the self impedance of
the three phases are denoted by Zaa, Zbb and Zcc while that of the neutral wire is denoted by Znn. Let us
assume that the self impedances of the conductors to be the same, i.e.,
ccbbaa ZZZ
Since the transmission line is assumed to be symmetric, we further assume that the mutual
inductances between the conductors are the same and so are the mutual inductances between the
conductors and the neutral, i.e.,
cabcab ZZZ
cnbnan ZZZ
The directions of the currents flowing through the lines are indicated in Fig. 17 and the voltages
between the different conductors are as indicated.
Fig. 17. Lumped parameter representation of a symmetrical transmission line.
Applying Kirchoff’s voltage law we get
nnnaaannnaaaan VVVVVVV (90)
Again
nancbabaaaaa IZIIZIZV (91)
cbaanannnn IIIZIZV (92)
Substituting (91) and (02) in (90) we get
nnnancbanabaanaanaan IZZIIZZIZZVV (93)
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 38
Since the neutral provides a return path for the currents Ia, Ib and Ic, we can write
cban IIII (94)
Therefore substituting (94) in (93) we get the following equation for phase-a of the circuit
cbannnabaannnaanaan IIZZZIZZZVV 22 (95)
Denoting
annnabmannnaas ZZZZZZZ 2 Zand 2
(7.46) can be rewritten as
cbmasnaan IIZIZVV (96)
Since (96) does not explicitly include the neutral conductor we can define the voltage drop across the
phase-a conductor as
naanaa VVV (97)
Combining (96) and (97) we get
cbmasaa IIZIZV (98)
Similar expression can also be written for the other two phases. We therefore get
c
b
a
smm
msm
mms
cc
bb
aa
I
I
I
ZZZ
ZZZ
ZZZ
V
V
V
(99)
Pre-multiplying both sides of (99) by the transformation matrix C we get
012
1
012 a
smm
msm
mms
aa IC
ZZZ
ZZZ
ZZZ
CV
(100)
Now
msmsms
msmsms
msmsms
smm
msm
mms
smm
msm
mms
ZaZaZaaZZZ
ZaaZZaZaZZ
ZZZZZZ
aa
aa
ZZZ
ZZZ
ZZZ
C
ZZZ
ZZZ
ZZZ
112
112
2
1
1
111
22
22
2
21
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 39
Hence
ms
ms
ms
msmsms
msmsms
msmsms
smm
msm
mms
ZZ
ZZ
ZZ
ZaZaZaaZZZ
ZaaZZaZaZZ
ZZZZZZ
aa
aaC
ZZZ
ZZZ
ZZZ
C
3300
0330
0063
3
1
112
112
2
1
1
111
3
1
22
22
2
21
Therefore from (100) we get
2
1
0
2
1
0 2
a
a
a
ms
ms
ms
aa
aa
aa
I
I
I
ZZ
ZZ
ZZ
V
V
V
(101)
The positive, negative and zero sequence equivalent circuits of the transmission line are shown in Fig.
18 where the sequence impedances are
abaams ZZZZZZ 21
annnabaams ZZZZZZZ 63220
Fig. 18. Sequence circuits of symmetrical transmission line: (a) positive, (b) negative and (c) zero sequence.
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 41
8. SEQUENCE CIRCUITS FOR TRANSFORMERS
In this section we shall discuss the sequence circuits of transformers. As we have seen earlier that the
sequence circuits are different for Y- and -connected loads, the sequence circuits are also different
for Y and connected transformers. We shall therefore treat different transformer connections
separately.
8.1. Y-Y CONNECTED TRANSFORMER
Fig. 19 shows the schematic diagram of a Y-Y connected transformer in which both the neutrals are
grounded. The primary and secondary side quantities are denoted by subscripts in uppercase letters
and lowercase letters respectively. The turns ratio of the transformer is given by = N1:N2.
The voltage of phase-a of the primary side is
03 ANANNANA IZVVVV
Fig. 19. Schematic diagram of a grounded neutral Y-Y connected transformer.
Expanding VA and VAN in terms of their positive, negative and zero sequence components, the above
equation can be rewritten as
0210210 3 ANANANANAAA IZVVVVVV (102)
Noting that the direction of the neutral current In is opposite to that of IN, we can write an equation
similar to that of (102) for the secondary side as
0210210 3 ananananaaa IZVVVVVV (103)
Now since the turns ratio of the transformer is = N1:N2 we can write
AN
an
an
AN VV
V
V
N
N
2
1
AaaA IIININ 21
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 42
Substituting in (103) we get
0210210 31
AnANANANaaa IZVVVVVV
Multiplying both sides of the above equation by results in
0
2
210210 3 AnANANANaaa IZVVVVVV (104)
Finally combining (102) with (104) we get
0
2
210210 3 AnNAAAaaa IZZVVVVVV (105)
Separating out the positive, negative and zero sequence components we can write
11
2
11 Aaa VV
N
NV
(106)
22
2
12 Aaa VV
N
NV
(107)
0
2
2100
2
10 3 AnNAaa IZNNZVV
N
NV
(108)
From (106) and (107) we see that the positive and negative sequence relations are the same as that
we have used for representing transformer circuits used in impedance diagram of Fig. 9. Hence the
positive and negative sequence impedances are the same as the transformer leakage impedance Z.
The zero sequence equivalent circuit is shown in Fig. 20. The total zero sequence impedance is given
by
nN ZNNZZZ2
210 33 (109)
Fig. 20. Zero sequence equivalent circuit of grounded neutral Y-Y connected transformer.
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 43
The zero sequence diagram of the grounded neutral Y-Y connected transformer is shown in Fig. 21 (a)
in which the impedance Z0 is as given in (109). If both the neutrals are solidly grounded, i.e., Zn = ZN =
0, then Z0 is equal to Z. The single line diagram is still the same as that shown in Fig. 21 (a). If however
one of the two neutrals or both neutrals are ungrounded, then we have either Zn = or ZN = or
both. The zero sequence diagram is then as shown in Fig. 21 (b) where the value of Z0 will depend on
the neutral which is kept ungrounded.
Fig. 21. Zero sequence diagram of (a) grounded neutral and (b) ungrounded neutral Y-Y connected transformer.
8.2 - CONNECTED TRANSFORMER
The schematic diagram of a - connected transformer is shown in Fig. 22. From this circuit we have
21210210 ABABBBBAAA
BAAB
VVVVVVVV
VVV
(110)
Fig. 22. Schematic diagram of a - connected transformer.
Again
ababAB VVN
NV
2
1
Therefore from (110) we get
2121 ababABABAB VVVVV (111)
The sequence components of the line-to-line voltage VAB can be written in terms of the sequence
components of the line-to-neutral voltage as
303 11 ANAB VV (112)
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 44
303 22 ANAB VV (113)
Therefore combining (111)-(113) we get
303303303303 2121 ananANAN VVVV (114)
Hence we get
2211 and anANanAN VVVV (115)
Thus the positive and negative sequence equivalent circuits are represented by a series impedance
that is equal to the leakage impedance of the transformer. Since the -connected winding does not
provide any path for the zero sequence current to flow we have
000 aA II
However the zero sequence current can sometimes circulate within the windings. We can then
draw the zero sequence equivalent circuit as shown in Fig. 23.
Fig. 23. Zero sequence diagram of - connected transformer.
8.3 Y- CONNECTED TRANSFORMER
The schematic diagram of a Y- connected transformer is shown in Fig. 24. It is assumed that the Y-
connected side is grounded with the impedance ZN. Even though the zero sequence current in the
primary Y-connected side has a path to the ground, the zero sequence current flowing in the -
connected secondary winding has no path to flow in the line. Hence we have Ia0 = 0. However the
circulating zero sequence current in the winding magnetically balances the zero sequence current
of the primary winding.
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 45
Fig. 24. Schematic diagram of a Y- connected transformer.
The voltage in phase-a of both sides of the transformer is related by
ababAN VVN
NV
2
1
Also we know that
NANA VVV
We therefore have
0210
0210210
3
3
ANababab
ANANANANAAA
IZVVV
IZVVVVVV
(116)
Separating zero, positive and negative sequence components we can write
03 000 abANA VIZV (117)
303 111 aabA VVV (118)
303 222 aabA VVV (119)
The positive sequence equivalent circuit is shown in Fig. 25 (a). The negative sequence circuit is the
same as that of the positive sequence circuit except for the phase shift in the induced emf. This is
shown in Fig. 25 (b). The zero sequence equivalent circuit is shown in Fig. 25 (c) where Z0 = Z + 3ZN.
Note that the primary and the secondary sides are not connected and hence there is an open circuit
between them. However since the zero sequence current flows through primary windings, a return
path is provided through the ground. If however, the neutral in the primary side is not grounded, i.e.,
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 46
ZN = , then the zero sequence current cannot flow in the primary side as well. The sequence diagram
is then as shown in Fig. 25 (d) where Z0 = Z.
Fig. 25. Sequence diagram of a Y- connected transformer: (a) positive sequence, (b) negative sequence, (c) zero sequence
with grounded Y-connection and (d) zero sequence with ungrounded Y-connection.
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 47
9. SEQUENCE NETWORKS
The sequence circuits developed in the previous sections are combined to form the sequence
networks. The sequence networks for the positive, negative and zero sequences are formed
separately by combining the sequence circuits of all the individual elements. Certain assumptions are
made while forming the sequence networks. These are listed below.
Apart from synchronous machines, the network is made of static elements.
The voltage drop caused by the current in a particular sequence depends only on the impedance of that part of the network.
The positive and negative sequence impedances are equal for all static circuit components, while the zero sequence component need not be the same as them. Furthermore subtransient positive and negative sequence impedances of a synchronous machine are equal.
Voltage sources are connected to the positive sequence circuits of the rotating machines.
No positive or negative sequence current flows between neutral and ground.
Example 8
Let us consider the network shown in Fig 26. The values of the various reactances are
not important here and hence, are not given in this figure. However various points of
the circuit are denoted by the letters A to G. This has been done to identify the
impedances of various circuit elements. For example, the leakage reactance of the
transformer T1 is placed between the points A and B and that of transformer T2 is
placed between D and E.
Fig. 26. Single-line diagram of a 3-machine power system.
The positive sequence network is shown in Fig. 27. The negative sequence diagram,
shown in Fig. 28, is almost identical to the positive sequence diagram except that the
voltage sources are absent in this circuit. The zero sequence network is shown in Fig.
29. The neutral point of generator G1 is grounded. Hence a path from point A to the
ground is provided through the zero sequence reactance of the generator. The primary
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 48
Example 8
side of the transformer T1 is -connected and hence there is discontinuity in the circuit
after point A. Similar connections are also made for generator G2 and transformer T2.
The transmission line impedances are placed between the points BC, CD and CF.
The secondary side of transformer T3 is ungrounded and hence there is a break in the
circuit after the point F. However the primary side of T3 is grounded and so is the
neutral point of generator G3. Hence the zero sequence components of these two
apparatus are connected to the ground.
Fig.27. Positive sequence network of the power system of Fig. 26.
Fig. 28. Negative sequence network of the power system of Fig. 26.
Fig. 29. Zero sequence network of the power system of Fig. 26.
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 49
10. UNSYMMETRICAL FAULTS
The sequence circuits and the sequence networks developed in the previously will now be used for
finding out fault current during unsymmetrical faults. For the calculation of fault currents, we shall
make the following assumptions:
The power system is balanced before the fault occurs such that of the three sequence networks only the positive sequence network is active. Also as the fault occurs, the sequence networks are connected only through the fault location.
The fault current is negligible such that the pre-fault positive sequence voltages are same at all nodes and at the fault location.
All the network resistances and line charging capacitances are negligible.
All loads are passive except the rotating loads which are represented by synchronous machines.
Based on the assumptions stated above, the faulted network will be as shown in Fig. 30 where the
voltage at the faulted point will be denoted by Vf and current in the three faulted phases are Ifa, Ifb
and Ifc. We shall now discuss how the three sequence networks are connected when the three types
of faults discussed above occur.
Fig. 30. Representation of a faulted segment.
10.1 SINGLE-LINE-TO-GROUND FAULT
Let a 1LG fault has occurred at node k of a network. The faulted segment is then as shown in Fig. 31
where it is assumed that phase-a has touched the ground through an impedance Zf. Since the system
is unloaded before the occurrence of the fault we have
Fig. 31. Representation of 1LG fault.
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 50
0 fcfb II (117)
Also the phase-a voltage at the fault point is given by
fafka IZV (118)
From (117) we can write
0
0
1
1
111
3
1
2
2
012
fa
fa
I
aa
aaI
(119)
Solving (119) we get
3210
fa
fafafa
IIII
(120)
This implies that the three sequence currents are in series for the 1LG fault. Let us denote the zero,
positive and negative sequence Thevenin impedance at the faulted point as Zkk0, Zkk1 and Zkk2
respectively. Also since the Thevenin voltage at the faulted phase is Vf we get three sequence circuits
that are similar to the ones shown in Fig. 16. We can then write
222
111
000
fakkka
fakkfka
fakkka
IZV
IZVV
IZV
(121)
Then from (120) and (121) we can write
0210
210
fakkkkkkf
kakakaka
IZZZV
VVVV
(122)
Again since
0210 3 faffafafaffafka IZIIIZIZV
we get from (122)
fkkkkkk
f
faZZZZ
VI
3210
0
(123)
The Thevenin equivalent of the sequence network is shown in Fig. 32.
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 51
Fig. 32. Thevenin equivalent of a 1LG fault.
Example 9
A three-phase Y-connected synchronous generator is running unloaded with rated
voltage when a 1LG fault occurs at its terminals. The generator is rated 20 kV, 220
MVA, with subsynchronous reactance of 0.2 per unit. Assume that the subtransient
mutual reactance between the windings is 0.025 per unit. The neutral of the generator
is grounded through a 0.05 per unit reactance. The equivalent circuit of the generator
is shown in Fig. 33. We have to find out the negative and zero sequence reactances.
Fig. 33. Unloaded generator of Example 9.
Since the generator is unloaded the internal emfs are
1200.11200.10.1 cnbnan EEE
Since no current flows in phases b and c, once the fault occurs, we have from Fig. 33
0.4
05.02.0
1j
jI fa
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 52
Example 9
Then we also have
2.0 fann IXV
From Fig. 33 and (83) we get
72.1240536.1866.06.0025.0
72.1240536.1866.06.0025.0
0
jIjVEV
jIjVEV
V
fancnc
fanbnb
a
Therefore
3.0
7.0
4.0
72.1240536.1
72.1240536.1
0
012 CVa
From (87) we can write Z1 = j(Ls + Ms) = j0.225. Then from Fig. 16 we have
3333.1225.0
7.01
1
11 j
jZ
VEI aan
fa
Also note from (120) that
210 fafafa III
Therefore from Fig. 16 we get
15.015.03.030
00 jjZ
I
VZ n
a
ag
225.02
22 j
I
VZ
a
a
Comparing the above two values with (86) and (88) we find that Z0 indeed is equal to
j(Ls 2Ms) and Z2 is equal to j(Ls + Ms). Note that we can also calculate the fault
current from (123) as
3333.1
05.0315.0225.0225.0
10 j
jI fa
10.2 LINE-TO-LINE FAULT
The faulted segment for an L-L fault is shown in Fig. 34 where it is assumed that the fault has occurred
at node k of the network. In this the phases b and c got shorted through the impedance Zf. Since the
system is unloaded before the occurrence of the fault we have
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 53
0faI (124)
Also since phases b and c are shorted we have
fcfb II (125)
Therefore from (124) and (125) we have
fb
fb
fb
fbfa
Iaa
Iaa
I
ICI2
2
012
0
3
10
(126)
We can then summarize from (126)
21
0 0
fafa
fa
II
I
(127)
Therefore no zero sequence current is injected into the network at bus k and hence the zero
sequence remains a dead network for an L-L fault. The positive and negative sequence currents are
negative of each other.
Fig. 34. Representation of L-L fault.
Now from Fig. 34 we get the following expression for the voltage at the faulted point
fbfkckb IZVV (128)
Again
21
2
2
2
1
2
2211
210210
kakakaka
kckbkckb
kckckckbkbkbkckb
VVaaVaaVaa
VVVV
VVVVVVVV
(129)
Moreover since Ifa0 = Ifb0 = 0 and Ifa1 = Ifb2, we can write
1
2
21
2
21 fafbfafbfbfb IaaaIIaIII (130)
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 54
Therefore combining (128)-(130) we get
121 fafkaka IZVV (131)
Equations (128) and (131) indicate that the positive and negative sequence networks are in parallel.
The sequence network is then as shown in Fig. 35. From this network we get
fkkkk
f
fafaZZZ
VII
21
21
(132)
Fig. 35. Thevenin equivalent of an LL fault.
Example 10
Let us consider the same generator as given in Example 9. Assume that the generator is
unloaded when a bolted (Zf = 0) short circuit occurs between phases b and c. Then we
get from (125) Ifb = Ifc. Also since the generator is unloaded, we have Ifa = 0. Therefore
from (83) we get
0.1 anan EV
fbfbbnbn IjIjEV 225.01201225.0
fbfccncn IjIjEV 225.01201225.0
Also since Vbn = Vcn, we can combine the above two equations to get
849.345.0
12011201
jII fcfb
Then
2222.2
2222.2
0
849.3
849.3
0
012
j
jCI fa
We can also obtain the above equation from (132) as
2222.2225.0225.0
121 j
jjII fafa
Also since the neutral current In is zero, we can write Va = 1.0 and
5.0 bncb VVV
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 55
Example 10
Hence the sequence components of the line voltages are
5.0
5.0
0
5.0
5.0
0.1
012 CVa
Also note that
5.0225.00.1 11 faa IjV
5.0225.0 22 faa IjV
which are the same as obtained before.
10.3 DOUBLE-LINE-TO-GROUND FAULT
The faulted segment for a 2LG fault is shown in Fig. 36 where it is assumed that the fault has occurred
at node k of the network. In this the phases b and c got shorted through the impedance Zf to the
ground. Since the system is unloaded before the occurrence of the fault we have the same condition
as (124) for the phase-a current. Therefore
fcfbfa
fcfbfcfbfafa
III
IIIIII
0
0
3
3
1
3
1
(133)
Also the voltages of phases b and c are given by
03 fafcbfkckb IZIIZVV (134)
Therefore
kbka
kbka
kbka
kb
kb
ka
ka
VaaV
VaaV
VV
V
V
V
CV2
2
012
2
3
1
(135)
We thus get the following two equations from (135)
21 kaka VV (136)
kbkakakakbkaka VVVVVVV 223 2100 (137)
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 56
Substituting (134) and (136) in (137) and rearranging we get
Fig. 36. Representation of 2LG fault.
0021 3 fafkakaka IZVVV (138)
Also since Ifa = 0 we have
0210 fafafa III (139)
The Thevenin equivalent circuit for 2LG fault is shown in Fig. 37. From this figure we get
fkkkk
fkkkk
kk
f
fkk
l
kkkk
f
fa
ZZZ
ZZZZ
V
ZZZZ
VI
3
33
02
02
1
021
1
(140)
The zero and negative sequence currents can be obtained using the current divider principle as
fkkkk
kkfafa
ZZZ
ZII
302
210
(141)
fkkkk
fkk
fafaZZZ
ZZII
3
3
02
0
12
(142)
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 57
Fig. 37. Thevenin equivalent of a 2LG fault.
Example 11
Let us consider the same generator as given in Examples 9 and 10. Let us assume that
the generator is operating without any load when a bolted 2LG fault occurs in phases b
and c. The equivalent circuit for this fault is shown in Fig. 38. From this figure we can
write
fcfbnnbn IjIjVVE 025.02.01201
fbfcnncn IjIjVVE 025.02.01201
fcfbn IIjV 05.0
Combining the above three equations we can write the following vector-matrix form
1201
1201
25.0025.0
025.025.0
fc
fb
I
Ij
Solving the above equation we get
8182.1849.3
8182.1849.3
jI
jI
c
b
Hence
6162.1
8283.2
2121.1
8182.1849.3
8182.1849.3
0
012
j
j
j
j
jCi fa
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 58
Example 11
Fig. 38. Equivalent circuit of the generator in Fig. 8.4 for a 2LG fault in phases b and c.
Note that we can also obtain the above values using (140)-(142). Note from Example 9
that
0 and 3.005.0315.0,225.0 021 fZjjZjZZ
Then
8283.2
525.0
3.0225.0225.0
0.11 j
j
jjj
I fa
6162.1525.0
3.012 j
j
jII fafa
2121.1525.0
225.010 j
j
jII fafa
Now the sequence components of the voltages are
3636.0225.00.1 11 faa IjV
3636.0225.0 22 faa IjV
3636.03.0 00 faa IjV
Also note from Fig. 38 that
0909.10225.0 fcfbnana IIjVEV
and Vb = Vc = 0. Therefore
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 59
Example 11
3636.0
3636.0
3636.0
0
0
0909.1
012 CVa
which are the same as obtained before.
10.4 FAULT CURRENT COMPUTATION USING SEQUENCE NETWORKS
In this section we shall demonstrate the use of sequence networks in the calculation of fault currents
using sequence network through some examples.
Example 12
Consider the network shown in Fig. 39. The system parameters are given below:
Generator G: 50 MVA, 20 kV, X = X1 = X2 = 20%, X0 = 7.5%
Motor M: 40 MVA, 20 kV, X = X1 = X2 = 20%, X0 = 10%, Xn = 5%
Transformer T1: 50 MVA, 20 kV/110 kVY, X = 10%
Transformer T2: 50 MVA, 20 kV/110 kVY, X = 10%
Transmission line: X1 = X2 = 24.2 , X0 = 60.5
We shall find the fault current for when a (a) 1LG, (b) LL and (c) 2LG fault occurs at bus-
2.
Fig. 39. Radial power system of Example 12.
Let us choose a base in the circuit of the generator. Then the per unit impedances of
the generator are:
075.0,2.0 021 GGG XXX
The per unit impedances of the two transformers are
1.021 TT XX
The MVA base of the motor is 40, while the base MVA of the total circuit is 50.
Therefore the per unit impedances of the motor are
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 60
Example 12
0625.040
5005.0,125.0
40
501.0,25.0
40
502.0 021 nMMM XXXX
For the transmission line
24250
1102
baseZ
Therefore
25.0242
5.60,1.0
242
2.24021 LLL XXX
Let us neglect the phase shift associated with the Y/ transformers. Then the positive,
negative and zero sequence networks are as shown in Figs. 40-42.
Fig. 40. Positive sequence network of the power system of Fig. 39.
Fig. 41. Negative sequence network of the power system of Fig. 39.
Fig. 42. Zero sequence network of the power system of Fig. 39.
From Figs. 40 and 41 we get the following Ybus matrix for both positive and negative
sequences
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 61
Example 12
141000
1020100
0102010
001015
21 jYY busbus
Inverting the above matrix we get the following Zbus matrix
1667.01333.01000.00667.0
1333.01867.01400.00933.0
1000.01400.01800.01200.0
0667.00933.01200.01467.0
21 jZZ busbus
Again from Fig. 42 we get the following Ybus matrix for the zero sequence
2.3000
01440
04140
0003333.13
0 jYbus
Inverting the above matrix we get
3125.0000
00778.00222.00
00222.00778.00
000075.0
0 jZbus
Hence for a fault in bus-2, we have the following Thevenin impedances
0778.0,18.0 021 jZjZZ
Alternatively we find from Figs. 40 and 42 that
18.045.03.021 jjjZZl
0778.035.01.00 jjjZl
(a) Single-Line-to-Ground Fault: Let a bolted 1LG fault occurs at bus-2 when the system
is unloaded with bus voltages being 1.0 per unit. Then from (123) we get
2841.2
0778.018.02
1210 j
jIII fafafa
per unit
Also from (120) we get
8524.63 0 jII fafa per unit
Furthermore Ifb = Ifc = 0. From (121) we get the sequence components of the voltages
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 62
Example 12
as
4111.018.0
5889.018.01
1777.00778.0
222
112
002
faa
faa
faa
IjV
IjV
IjV
Therefore the voltages at the faulted bus are
11.1079061.0
11.1079061.0
0
22
12
02
1
a
a
a
c
b
a
V
V
V
C
V
V
V
(b) Line-to-Line Fault: For a bolted LL fault, we can write from (132)
7778.218.02
121 j
jII fafa
per unit
Then the fault currents are
8113.4
8113.4
00
2
1
1
fa
fa
fc
fb
fa
I
IC
I
I
I
Finally the sequence components of bus-2 voltages are
5.018.0
5.018.01
0
222
112
02
faa
faa
a
IjV
IjV
V
Hence faulted bus voltages are
5.0
5.0
0.1
22
12
02
1
a
a
a
c
b
a
V
V
V
C
V
V
V
(c)Double-Line-to-Ground Fault: Let us assumes that a bolted 2LG fault occurs at bus-2.
Then
0543.00778.018.0 jjjZl
eq
Thus from (140) we get the positive sequence current as
2676.418.0
11 j
ZjI
eq
fa
per unit
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 63
Example 12
The zero and negative sequence currents are then computed from (141) and (142) as
9797.2
0778.018.0
18.010 j
j
jII fafa
per unit
2879.1
0778.018.0
0778.012 j
j
jII fafa
per unit
Therefore the fault currents flowing in the line are
89.42657.6
11.137657.6
0
2
1
0
1
fa
fa
fa
fc
fb
fa
I
I
I
C
I
I
I
Furthermore the sequence components of bus-2 voltages are
2318.018.0
2318.018.01
2318.00778.0
222
112
002
faa
faa
faa
IjV
IjV
IjV
Therefore voltages at the faulted bus are
0
0
6954.0
22
12
02
1
a
a
a
c
b
a
V
V
V
C
V
V
V
Example 13
Let us now assume that a 2LG fault has occurred in bus-4 of the system of Example 12
instead of the one in bus-2. Therefore
3125.0,1667.0 021 jXjXX
Also we have
1087.03125.01667.0 jjjZl
eq
Hence
631.31667.0
11 j
ZjI
eq
fa
per unit
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 64
Example 13
Moreover
2631.1
3125.01667.0
1667.010 j
j
jII fafa
per unit
3678.2
3125.01667.0
3125.012 j
j
jII fafa
per unit
Therefore the fault currents flowing in the line are
04.205298.5
96.1595298.5
0
2
1
0
1
fa
fa
fa
fc
fb
fa
I
I
I
C
I
I
I
We shall now compute the currents contributed by the generator and the motor to the
fault. Let us denoted the current flowing to the fault from the generator side by Ig,
while that flowing from the motor by Im. Then from Fig. 40 using the current divider
principle, the positive sequence currents contributed by the two buses are
2103.175.0
25.011 j
j
jII faga per unit
4206.275.0
5.011 j
j
jII fama per unit
Similarly from Fig. 41, the negative sequence currents are given as
7893.075.0
25.022 j
j
jII faga per unit
5786.175.0
5.022 j
j
jII fama per unit
Finally notice from Fig. 42 that the zero sequence current flowing from the generator
to the fault is 0. Then we have
00 gaI
2631.10 jIma per unit
Therefore the fault currents flowing from the generator side are
93.67445.1
07.1737445.1
904210.0
2
1
0
1
ga
ga
ga
gc
gb
ga
I
I
I
C
I
I
I
and those flowing from the motor are
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 65
Example 13
93.258512.3
07.1548512.3
904210.0
2
1
0
1
ma
ma
ma
mc
mb
ma
I
I
I
C
I
I
I
It can be easily verified that adding Ig and Im we get If given above.
In the above two examples we have neglected the phase shifts of the Y/ transformers. However
according to the American standard, the positive sequence components of the high tension side lead
those of the low tension side by 30, while the negative sequence behavior is reverse of the positive
sequence behavior. Usually the high tension side of a Y/ transformer is Y-connected. Therefore as
we have seen in Fig. 25, the positive sequence component of Y side leads the positive sequence
component of the side by 30 while the negative sequence component of Y side lags that of the
side by 30. We shall now use this principle to compute the fault current for an unsymmetrical fault.
Example 14
Let us consider the same system as given in Example 12. Since the phase shift does not
alter the zero sequence, the circuit of Fig. 42 remains unchanged. The positive and the
negative sequence circuits must however include the respective phase shifts. These
circuits are redrawn as shown in Figs. 43 and 44.
Note from Figs. 43 and 44 that we have dropped the 3 vis-à-vis that of Fig. 25. This is
because the per unit impedances remain unchanged when referred to the either high
tension or low tension side of an ideal transformer. Therefore the per unit impedances
will also not be altered.
Fig. 43. Positive sequence network of the power system of Fig. 39 including transformer phase shift.
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 66
Example 14
Fig. 44. Negative sequence network of the power system of Fig. 39 including transformer phase shift.
Since the zero sequence remains unaltered, these currents will not change from those
computed in Example 12. Thus
00 gaI and 2631.10 jIma per unit
Now the positive sequence fault current from the generator Iga1, being on the Y-side of
the Y/ transformer will lead Ima1 by 30. Therefore
602103.13012103.11 jIga per unit
4206.21 jIma per unit
Finally the negative sequence current Iga2 will lag Ima2 by 30. Hence we have
607893.03017893.02 jjIga per unit
5786.12 jIma per unit
Therefore
04.200642.1
1809996.1
04.200642.1
2
1
0
1
ga
ga
ga
gc
gb
ga
I
I
I
C
I
I
I
Also the fault currents flowing from the motor remain unaltered. Also note that the
currents flowing into the fault remain unchanged. This implies that the phase shift of
the Y/ transformers does not affect the fault currents.
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 67
Example 15
Let us consider the same power system as shown in Fig. 26, the sequence diagrams of
which are given in Figs. 27 to 29. With respect to Fig. 26, let us define the system
parameters as:
Generator G1: 200 MVA, 20 kV, X = 20%, X0 = 10%
Generator G2: 300 MVA, 18 kV, X = 20%, X0 = 10%
Generator G3: 300 MVA, 20 kV, X = 25%, X0 = 15%
Transformer T1: 300 MVA, 220Y/22 kV, X = 10%
Transformer T2: Three single-phase units each rated 100 MVA, 130Y/25 kV, X
= 10%
Transformer T3: 300 MVA, 220/22 kV, X = 10%
Line B-C: X1 = X2 = 75 , X0 = 100
Line C-D: X1 = X2 = 75 , X0 = 100
Line C-F: X1 = X2 = 50 , X0 = 75
Let us choose the circuit of Generator 3 as the base, the base MVA for the circuit is
300. The per unit reactances are then computed as shown below.
Generator G1: 3.0200
3002.0 X , X0 = 0.15
Generator G2: 1312.022.22
182.0
2
X , X0 = 0.0656
Generator G3: 2.0X , X0 = 0.15
Transformer T1: 121.0200
2201.0
2
X
Transformer T2: 1266.022.22
251.0
2
X
Transformer T3: 121.020
221.0
2
X
Line B-C: 5625.033.133
7521 XX , 75.0
33.133
1000 X
Line C-D: 5625.033.133
7521 XX , 75.0
33.133
1000 X
Line C-F: 375.033.133
5021 XX , 5625.0
33.133
750 X
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 68
Example 15
Neglecting the phase shifts of Y/ connected transformers and assuming that the
system is unloaded, we shall find the fault current for a 1LG fault at bus-1 (point C of
Fig. 26).
From Figs. 27 and 28, we can obtain the positive and negative sequence Thevenin
impedance at point C as (verify)
X1 = X2 = j0.2723 per unit
Similarly from Fig. 29, the Thevenin equivalent of the zero sequence impedance is
X0 = j0.4369 per unit
Therefore from (123) we get
0188.1
4369.02723.02
10 j
jI fa
per unit
Then the fault current is Ifa = 3Ifa0 = 3.0565 per unit.
CONCLUSIONS
In this module, the fundamentals of fault calculations are discussed. Throughout the course phasor
techniques are employed for fault calculation assuming that a power system is in its sinusoidal steady
state. This implies that if a fault is allowed to persist, the calculated fault currents will flow to the fault
and the various parts of the network. However, before that can happen, the fault will be interrupted
by protective devices. The rms currents, assuming that a fault is allowed to persist, gives us an
indication of what the maximum current that can flow in that part of the circuit. The instantaneous
current can be anywhere between 1.0 to 1.8 times the calculated phasor current. This gives an
indication of what the rating of the circuit breaker that will withstand this current be. We can also
determine the conductor sizes based on this calculations. Furthermore, the fault current levels are
used for coordination of overcurrent relays in power distribution systems. Thus we find that the
application of fault studies is numerous. Moreover, the symmetrical component analysis presented in
this module can be used to analyze any unbalanced circuit.
REFERENCES
For further reading
[1] J. D. Glover and M. S. Sarma, Power System Analysis and Design, 5th Ed., Cengage Learning,
Stamford, CT, 2012.
[2] J. J. Grainger and W. D. Stevenson, Power Stem Analysis, McGraw-Hill, New York, 1994.
COURSE NOTES: FAULT CALCULATIONS IN POWER SYSTEMS Ghosh, A.
2010 UGSP7_Fault Calculations_Course Notes_Final 2010 69
[3] D. P. Kothari and I. J. Nagrath, Modern Power Systems Analysis, McGraw-Hill, Boston, 2008.