Analytic and experimental evaluation of masonry walls ... · LOPEZ, Sebastián / FE 2015 3 Figure...
Transcript of Analytic and experimental evaluation of masonry walls ... · LOPEZ, Sebastián / FE 2015 3 Figure...
![Page 1: Analytic and experimental evaluation of masonry walls ... · LOPEZ, Sebastián / FE 2015 3 Figure 2. Stretcher and header bond masonry wall. The compression strength of the units](https://reader030.fdocuments.net/reader030/viewer/2022041208/5d66cc1688c993dd5b8b6568/html5/thumbnails/1.jpg)
Bauhaus Summer School in Forecast Engineering: Global Climate change and the challenge for built environment
17-28 August 2015, Weimar, Germany
Analytic and experimental evaluation of masonry walls externally
reinforced with mortar and wire welded mesh applied to
historical building walls
LOPEZ, Sebastián
Escuela Colombiana de Ingeniería, Julio Garavito. ECI
Abstract
Colombian seismic provisions (NSR-10) had recently accepted a new system of externally reinforced
masonry walls with welded wire mesh and mortar (W.W.M). Escuela Colombiana de Ingeniería Julio
Garavito, with the objective of evaluate the response of full scale walls reinforced with this new
reinforcement system for masonry structures like existing houses and historical buildings.
Unreinforced masonry walls and reinforced masonry walls were tested; small specimens were used to
evaluate the material properties; while in plane monotonic and dynamic lateral load were run in full
scale walls. The article shows experimental results and their comparison with the values obtained by
using the equations and recommendations of NSR-10 for walls typical of some historical buildings.
Results demonstrate that calculations are conservative and safe; furthermore, the reinforcement
technique increased the strength to in plane lateral loads between 4 to 8 times when was used by one
or by two sides of the wall respectively.
Introduction
Colombian seismic construction regulations NSR-10 (Ministerio de Ambiente, Vivienda y Desarrollo
Territorial, 2010) allowed the use of externally reinforced masonry walls with mortar and wire welded
mesh (W.W.M) as the main seismic resistant system for structures with limited height (between 12 m
and 18 m) and certain occupancy category (not permitted for government facilities and public
buildings; e.g. hospitals, schools, universities, etc.). In spite of the limitations, approving the use of
this structural system represents an important opportunity to develop different solutions to improve the
behaviour of existing buildings or even to develop new ones.
Since 2011 a research program was developed in the laboratory of the Escuela Colombiana de
Ingeniería, Julio Garavito (ECI, Bogotá. Col) with the general objective of evaluate the behavior of
full scale walls, representative of Colombian housing buildings and historical buildings. This article is
one of a series of articles and a M. Sc. thesis that have been published to show the research program
methodology and experimental results (López S.,2013; López, Quiroga, & Torres Castellanos, 2013
and 2012; López & Torres Castellanos, 2012); nevertheless, this document makes a briefer
presentation of the methodology and the results and focuses mainly in the presentation of new
unreleased analysis comparing between the calculations according to the Colombian seismic code
provisions and the experimental results obtained by the Structural Behavior Research Group from the
ECI, for historical building walls, externally reinforced with mortar and W.W.M. by one or two sides
of the wall.
![Page 2: Analytic and experimental evaluation of masonry walls ... · LOPEZ, Sebastián / FE 2015 3 Figure 2. Stretcher and header bond masonry wall. The compression strength of the units](https://reader030.fdocuments.net/reader030/viewer/2022041208/5d66cc1688c993dd5b8b6568/html5/thumbnails/2.jpg)
LOPEZ, Sebastián / FE 2015 2
Methodology
Tests of compression and diagonal tension were made to masonry assemblages to evaluate the
compression strength of the walls, elastic modulus, shear strength and shear modulus. Full scale walls
were tested under in plane lateral loads, monotonic and pseudo dynamic to determine their stiffness
and strength. Diagonal tension tests and in plane lateral load tests were done also for specimens
unreinforced and reinforced with W.W.M. Table 1 shows a summary with the characteristics of the
tested walls.
Table 1. Tested walls summary
Wall type
Characteristics
Reinforced Reinforced sides
MT2 NO N.A*
MT2R3 YES 1
MT2R4 YES 2
* N.A. Not applicable
Walls representative of the construction techniques used in Colombia during the end of XVIII century
and beginnings of the first half of XIX century, were replicated to evaluate the behaviour of the walls
under compression, diagonal tension and in-plane lateral load. Figure 1 shows a drawing form a
surveyed wall during the study for structural reinforcing of the building of The Instituto Técnico
Central La Salle (built between 1919 and 1930, Bogotá. Col); it can be seen the complex configuration
that can be found in masonry walls in historical masonry buildings.
Figure 1. Basic drawing from a surveyed masonry wall in a historical masonry building.
According to the variety and the difficulty of replicating walls with all the kind of possible
arrangements, it was decided to build walls with solid fired clay units, disposed in a regular
arrangement. Masonry walls in stretcher and header bond were selected. Mortar joints had between 10
and 15 mm thickness. Figure 2 shows a three dimensional view of the construction technique.
![Page 3: Analytic and experimental evaluation of masonry walls ... · LOPEZ, Sebastián / FE 2015 3 Figure 2. Stretcher and header bond masonry wall. The compression strength of the units](https://reader030.fdocuments.net/reader030/viewer/2022041208/5d66cc1688c993dd5b8b6568/html5/thumbnails/3.jpg)
LOPEZ, Sebastián / FE 2015 3
Figure 2. Stretcher and header bond masonry wall.
The compression strength of the units (f’cu) was determined based on the data stored on the database of
the ECI’s Structures and Materials Laboratory. The laboratory data base has information about
compression tests results of masonry units. The data was filtered according to the reported age of the
specimen and there were selected 79 results to determine statistically the average compression
strength. It was found a value of 25 MPa a representative of the compression strength.
To determine the compression strength of joint mortar (f’cp) in existing historical building walls are
required specialized techniques (for example flat jack tests and chemical composition analysis)
considerable out of the scope for general objective of this study. Even though there is not enough local
research about this, a few researchers had found that compression strengths in joint mortars from walls
in historical buildings can be as low as 0.5 MPa (Jaramillo Morilla, Rodríguez Liñán, de Justo
Alpañés, Romero Hernández, & Pérez Gálvez, 2000; Useche, 1993). For the purpose of the research, it
was selected 9.0 MPa for the joint mortar compression strength, mainly to ensure the integrity of the
specimen and diminish the risk of a sudden collapse during tests setup.
Figure 3 shows unreinforced masonry walls during its construction.
Figure 3. Building a full scale masonry wall.
Reinforced walls characteristics.
Reinforced walls were built with the same arrangement of the unreinforced ones but they were
reinforced by one or two sides (front and back planes of the wall). For the reinforcement, a wire
welded mesh was installed on the surface of the wall and then a thin layer of mortar was placed by
hand. Reinforcement details for the walls reinforced by just one side are shown in Figure 4.
![Page 4: Analytic and experimental evaluation of masonry walls ... · LOPEZ, Sebastián / FE 2015 3 Figure 2. Stretcher and header bond masonry wall. The compression strength of the units](https://reader030.fdocuments.net/reader030/viewer/2022041208/5d66cc1688c993dd5b8b6568/html5/thumbnails/4.jpg)
LOPEZ, Sebastián / FE 2015 4
Figure 4. Reinforcement of walls type R3.
To fix the wire welded mesh to the wall, two techniques were used depending on how many sides of
the wall were going to be reinforced. For walls reinforced by one side (walls type MT2.R3), 4 anchors
of 6.35 mm (1/4 in) per m²were fixed over the vertical area of the wall. The anchors were installed in
a 9.53 mm (3/8") drilled hole filled with epoxy resin. For the walls reinforced on the two sides of the
wall (walls type MT2R4), the same amount and diameter of anchors were installed but the anchor rod
passed through the hole; once the anchor was inside the hole, the rod was bent 90° on both sides. The
final anchor had hooks on both sides which were tied to the W.W.M. The longitudinal and transverse
reinforcement was made of welded deformed wire fabric of 6.00 mm spaced each 150 mm in both
directions centre to centre, with a yield strength (fy) of 480 MPa. Once the W.W.M was placed and
tied to the anchors, a 25 mm layer of mortar with a compression strength (f'cre) of 20 MPa was applied
over the reinforcing mesh. Detailed drawings of the anchors for walls reinforced by one side or for
both are shown in Figure 5.
Figure 5. Anchor type B and type C. Details of reinforced walls.
![Page 5: Analytic and experimental evaluation of masonry walls ... · LOPEZ, Sebastián / FE 2015 3 Figure 2. Stretcher and header bond masonry wall. The compression strength of the units](https://reader030.fdocuments.net/reader030/viewer/2022041208/5d66cc1688c993dd5b8b6568/html5/thumbnails/5.jpg)
LOPEZ, Sebastián / FE 2015 5
Figure 5 (Continued). Anchor type B and type C. Details of reinforced walls.
Full scale walls had a foundation beam and a top beam. The reinforced walls had bars of 12.7 mm
(1/2") each 300 mm, anchored to the foundation beam through epoxy adhesive, those bars were used
to tie the mesh to the foundation. The top beam was used to apply lateral loads and it had embedded
bars of 6.35 mm (1/4”) to fix the W.W.M. Construction details of the reinforced walls are shown in
Figure 6.
Figure 6. Construction details of full scale walls.
Tests
Table 2 shows a compilation of the most important tests, including the dimensions of the specimens,
quantity of tests done and if the test included results for reinforced and unreinforced specimens. The
width of the wall shown includes the masonry unit and the thickness of the for reinforcing mortar
Tests set up
A brief description of the test set up and the standards or reference documents used to develop the tests
are shown below for the most important tests.
Diagonal tension in masonry assemblages
Diagonal tension tests were done with reference to ASTM E-519 (ASTM, 2010) and NTC 4925
(ICONTEC, 2001). Figure 7 shows the most important details of the instrumentation and test set up for
the test; test set up and specimen dimensions were slightily different compared to the specifications
from standars.
![Page 6: Analytic and experimental evaluation of masonry walls ... · LOPEZ, Sebastián / FE 2015 3 Figure 2. Stretcher and header bond masonry wall. The compression strength of the units](https://reader030.fdocuments.net/reader030/viewer/2022041208/5d66cc1688c993dd5b8b6568/html5/thumbnails/6.jpg)
LOPEZ, Sebastián / FE 2015 6
Table 2. Summary of specimens and tests quantities
Test
Wall type Dimensions Quantity of
tests Unreinforced Reinforced Height
(mm)
Length
(mm) Width (mm)
Diagonal
tension
X
1100 1100
260 3
X 285 3
X 310 3
Monotonic in
plane lateral
load
X
2000 1320
260 1
X 285 1
X 310 1
Pseudo
dynamic in
plane lateral
load
X 260 1
X 285 1
X 310 1
Figure 7. Diagonal tension test set up.
To apply the force, threaded steel rods mm (1 1/2") were placed parallel to the diagonal direction
of the masonry assemblage between upper and lower loading shoes. For unreinforced and reinforced
masonry walls load was applied using an hydraulic jack with a capacity of 150 kN and a load cell of
1000 kN to register the loads. To measure deformations, dial indicators with a precision of 10-2
mm
were installed in the four diagonals of the specimen (both sides of the wall in parallel and
perpendicular direction to the load applied). The wall specimen was built over a layer of sand to
provide temporary support during the construction. Before the test, the sand was removed and the wall
was finally supported on rolling supports placed previously during construction and imbibed into the
sand layer. Figure 8 shows in detail the load mechanism for diagonal tension tests.
Upper
Loading Shoe
Dial Indicators
(both sides)
Loading Jack
Threaded
Steel Rods
=38mm
Lower
Loading
Shoe
![Page 7: Analytic and experimental evaluation of masonry walls ... · LOPEZ, Sebastián / FE 2015 3 Figure 2. Stretcher and header bond masonry wall. The compression strength of the units](https://reader030.fdocuments.net/reader030/viewer/2022041208/5d66cc1688c993dd5b8b6568/html5/thumbnails/7.jpg)
LOPEZ, Sebastián / FE 2015 7
Figure 8. Loading mechanism for diagonal tension test.
Lateral load in full scale walls
Tests of full scale walls, under lateral monotonic and pseudo dynamic in plane loading were done
according to the appendix A of the Mexican seismic provisions for masonry buildings (GDF, 2002).
This document was developed specifically for masonry structures. Other standars developed for lateral
loading in walls for example ASTM standars for in plane lateral loading have been developed for other
materials. Figure 9 shows a general view of the test set up for monotonic loading test.
Figure 9. Test set up for monotonic in plane lateral load.
To apply the load in pseudo dynamic tests it was used a MTS dynamic actuator with 250 kN of pulling
force capacity and 300 kN of pushing force; the total path length of the actuator’s piston is 500 mm.
The wall was fixed to the actuator with a couple of drilled steel plates, subjected through threaded
steel bars of 15.9 mm (5/8"). On the side of the actuator was placed a steel plate with a rod welded
parallel to the wall thickness to generate a hinged connection between the actuator and the wall.
Displacements were registered through LVDTs (Linear Variable Differential Transducers) and strain
in extreme fibre (left and right side of the wall) on wire welded mesh was measured with
unidirectional strain gauges. A general view of the test set up is shown in Figure 10.
Load
Cell
Hydraulic
Jack
Upper
loading
shoe
Reaction
steel plates
Reinforcing
steel plate in
the piston
Loading
Jack
vertical
LVDT
horizontal
LVDT
horizontal
LVDT
Supports
![Page 8: Analytic and experimental evaluation of masonry walls ... · LOPEZ, Sebastián / FE 2015 3 Figure 2. Stretcher and header bond masonry wall. The compression strength of the units](https://reader030.fdocuments.net/reader030/viewer/2022041208/5d66cc1688c993dd5b8b6568/html5/thumbnails/8.jpg)
LOPEZ, Sebastián / FE 2015 8
Figure 10. Test set up for pseudo dynamic in plane lateral load.
Loading pattern for dynamic tests was according to Mexican seismic provisions for masonry buildings
(GDF, 2002). Loading for the first cycles of the test are a function of the wall’s nominal strength and
from experimental results obtained form monotonic tests; afterwards, the load pattern increses
gradually the drift ratio by adding 0.002 increments until the failure of the specimen. The load pattern
requires to know first the results of the monotonic loading tests. Figure 11 shows the load pattern
(figure adapted from GDF, 2002)
Figure 11. Load Pattern for pseudo dynamic tests.
Dynamic
actuator
Holding
bars
Supports
Unidirectional
strain gauges
horizontal
LVDT
horizontal
LVDT
horizontal
LVDT
43
Lateral load
Controled by
load
Controled by
drift
Cycles
Drift, q
Load 1
Load 2
Load 3
0.002
0.004
0.006
0.008
0.01
Incr
easi
ng b
y 0
.00
2
Load 1: 0.25 times calculated cracking or yielding load
Load 2: 0.50 times calculated cracking or yielding load
Load 3: Cracking load or first yielding (experimental)
![Page 9: Analytic and experimental evaluation of masonry walls ... · LOPEZ, Sebastián / FE 2015 3 Figure 2. Stretcher and header bond masonry wall. The compression strength of the units](https://reader030.fdocuments.net/reader030/viewer/2022041208/5d66cc1688c993dd5b8b6568/html5/thumbnails/9.jpg)
LOPEZ, Sebastián / FE 2015 9
Test results and analysis of results
The results of the most important tests are shown below
Figure 12. Shear stress vs average angular distortion. Unreinforced walls (TD2)and walls reinforced by one side
(TD2.R3).
Figure 13. Shear stress vs average angular distortion. Unreinforced walls (TD2)and walls reinforced by one side
(TD2.R4).
0
100
200
300
400
500
600
0 2 4 6 8 10 12 14 16 18
Ss (kPa)
gprom (10-4 mm/mm)
TD2.1
TD2.3
TD2.R3.1
TD2.R3.2
TD2.R3.3
0
100
200
300
400
500
600
0 2 4 6 8 10 12 14 16 18
Ss (kPa)
gprom (10-4 mm/mm)
TD2.1
TD2.3
TD2.R4.1
TD2.R4.2
TD2.R4.3
![Page 10: Analytic and experimental evaluation of masonry walls ... · LOPEZ, Sebastián / FE 2015 3 Figure 2. Stretcher and header bond masonry wall. The compression strength of the units](https://reader030.fdocuments.net/reader030/viewer/2022041208/5d66cc1688c993dd5b8b6568/html5/thumbnails/10.jpg)
LOPEZ, Sebastián / FE 2015 10
Diagonal tension in masonry assemblages
The apparent shear modulus were obtained from the stress vs average angular distortion (average form
the measurements from front and back plane of the wall) shown below in Figure 12 for walls
reinforced by one side and Figure 13 for walls reinforced by two sides. The angular distortion on each
side of the wall was calculated according to the ASTM E-519 (ASTM, 2010).
Table 3 shows the average of the maximum shear stresses obtained for each test. Table 4 shows the
apparent average shear modulus, which is the average of the slopes of each plot stress vs average
angular distortion under the elastic zone.
Table 3. Tests results diagonal tension. Shear stress.
Wall
type
Statistical values
Type Quantity. S s average
(MPa)
Variation
Coefficient.
TD2 281 5.7% Unreinforced 3
TD2R3 417 16.8% Reinforced 1
side 3
TD2R4 504 5.3% Reinforced 2
sides 3
Table 4. Tests results diagonal tension. Apparent shear modulus.
Wall
type
Statistical values
Type Quantity. G apparent
average
(MPa)
Variation
Coefficient.
TD2 1020 5.7% Unreinforced 3
TD2R3 1596 16.8% Reinforced 1
side 3
TD2R4 1754 5.3% Reinforced 2
sides 3
Results showed that using W.W.M for one side of the wall can increase the diagonal tension strength
1.5 times in comparison to the unreinforced walls and up to 1.8 times when this technique is applied to
both planes of the wall. Failures followed cracking patterns through the diagonal load direction. There
was an important difference between the behaviour observed for unreinforced and reinforced. The
failure in unreinforced walls was brittle. For reinforced walls the failure was gradual and there was
more damaged in the mortar of the walls reinforced for both sides (M2R4) than in the other walls also
reinforced (M2R3). The reinforced walls showed an increase in the shear apparent stiffness according
to the slopes observed in the shear vs. distortion plots.
Below are shown the values of calculated diagonal tension strength according to Colombian
regulations, which are based on ACI530-08 (ACI, 2008), and the comparison between the test results
and the calculated values. The maximum allowable shear force (VALW) is the value of the shear force
that produces the maximum allowable stress on one of the composing materials when the acting force
is distributed in proportion to the stiffness of the transverse section component (López, 2013).
Allowable stresses are named with the letter “F” and the letter “f” is used for the acting ones; for the
stresses in each material. The sub index “v m” is used for the stresses on the masonry, “v cre” for the
mortar and for the reinforcing steel the letter “s”. The allowable shear stress (Ss ALW) is calculated
dividing the force VALLW by the transverse section of the wall including the mortar layer thickness for
the reinforced walls.
![Page 11: Analytic and experimental evaluation of masonry walls ... · LOPEZ, Sebastián / FE 2015 3 Figure 2. Stretcher and header bond masonry wall. The compression strength of the units](https://reader030.fdocuments.net/reader030/viewer/2022041208/5d66cc1688c993dd5b8b6568/html5/thumbnails/11.jpg)
LOPEZ, Sebastián / FE 2015 11
Figure 14. Diagonal tension failures. (a) Unreinforced masonry, (b) reinforced by one side and (c) reinforced by
two sides.
Table 5 shows the value of Ss ALW for unreinforced walls according to the equation 1.5-12 of NSR-10.
Table 6 shows the value of the allowable working stresses for each material according to equations D-
1.5-14 and D-1.5-18 from the same provisions. Table 7 shows the values of VALW and SS ALW for the
reinforced walls. In the tables below the gray colour cells represents the stress governing the
behaviour.
Table 5. Allowable working stress for diagonal tension. Unreinforced walls.
Wall type Shear strength
SS ALW=Fv=√f'm/40<=560
(kPa)
TD2 83.0
Table 6. Allowable working stresses for each material. Reinforced walls.
Wall type M/Vd Shear strength
Fv m=√f'm/12<=0.25 (MPa) Fv cre=√f'cre/12<=0.25 (MPa) Fs=0.5 fy (MPa)
TD2R3 1.0 0.25 0.25 215
TD2R4 1.0 0.25 0.25 215
Table 7. Calculated working stresses for each material. Reinforced walls.
Wall type V ALW (kN) M/Vd Shear stress
SS ALW (kPa) fv m (MPa) fv cre (MPa) fs (MPa)
TD2R3 36.3 1.0 0.11 0.22 215 98
TD2R4 36.3 1.0 0.09 0.17 215 87
Safety factors (S.F) can be estimated as the ratio between the experimental maximum shear stress and
the calculated shear strength. Table 8 shows the safety factors for shear, obtained for allowable stress
design (A.S.D).
For unreinforced masonry assemblages the average safety factor is 3.5 and the minimum is 3.2. For
the specimens reinforced the average safety factor is 5 with a minimum of 3.5. Those values are
consistent with the results obtained by other researchers, developed for different type of walls
subjected to similar tests ( López S. , 2013; Luna y Rojas, 2004).
(a) (b) (c)
![Page 12: Analytic and experimental evaluation of masonry walls ... · LOPEZ, Sebastián / FE 2015 3 Figure 2. Stretcher and header bond masonry wall. The compression strength of the units](https://reader030.fdocuments.net/reader030/viewer/2022041208/5d66cc1688c993dd5b8b6568/html5/thumbnails/12.jpg)
LOPEZ, Sebastián / FE 2015 12
Table 8. Diagonal tension safety factors for unreinforced and reinforced masonry walls. A.S.D.
Wall type SS ALW (kPa) SS exp max (kPa) 𝐹𝑆𝑆𝐻𝐸𝐴𝑅 (𝐴.𝑆.𝐷) =𝑆𝑆 exp𝑚𝑎𝑥
𝑆𝑠 𝐴𝐿𝑊
TD2.1
83
292 3.2
TD2.2 288 3.5
TD2.3 262 4.0
TD2R3.1
98
339 3.5
TD2R3.2 476 4.9
TD2R3.3 434 4.4
TD2R4.1
87
500 5.7
TD2R4.2 480 5.5
TD2R4.3 533 6.1
On the other hand, analysing the shear strength through limit state design (L.S.D), the shear strength
(n) was calculated in a conservative way according to Equation 1 (D.5.1.5, NSR-10) with a strength
reduction factor () of 0.60 and considering only the resistance of the mortar layer.
𝝓𝒗𝒏 = 𝛟(𝟎. 𝟏𝟔√𝒇′𝒄𝒓𝒆) ≤ 𝟎. 𝟐𝟗𝒇′𝒄𝒓𝒆 (1)
Where f'cre is the mortar layer compression strength in MPa. Compression strength for the mortar is
16.9 MPa for TD2R3 walls and 15.3 MPa for TD2R4 test walls. The safety factors for shear, obtained
for limit state design are shown on the Table 9.
Table 9. Diagonal tension safety factors for unreinforced and reinforced masonry walls. L.S.D.
Wall type φn (kPa) SS exp max (kPa) 𝐹𝑆𝑆𝐻𝐸𝐴𝑅 (𝐿.𝑆.𝐷) =𝑆𝑆 exp𝑚𝑎𝑥
∅𝑣𝑛
TD2.R3.1
395
339 0.86
TD2.R3.2 476 1.21
TD2.R3.3 434 1.10
TD2.R4.1
376
500 1.33
TD2.R4.2 480 1.28
TD2.R4.3 533 1.42
For more than 80% of the results the approach adopted predicted adequate strength design values.
Making apart the results of the specimen TD2.R3.1, the average safety factor for limit state design is
1.27 with a minimum of 1.10. Those values are relatively lower than those obtained for other kind of
walls under the same kind of loads (López, Quiroga, & Torres Castellanos, 2013).
Lateral load in full scale walls
Monotonic lateral loads tests were used specially to generate the load pattern for pseudo dynamic load
tests as it was exposed previously in the tests set up. M2 walls were unreinforced walls, M2R3 were
reinforced by one side and M2R4 were reinforced by both sides. Figure 15 shows simultaneously in
plane lateral load tests plots for walls M2R4.1 (monotonic) and M2R4.2 (pseudo dynamic).
![Page 13: Analytic and experimental evaluation of masonry walls ... · LOPEZ, Sebastián / FE 2015 3 Figure 2. Stretcher and header bond masonry wall. The compression strength of the units](https://reader030.fdocuments.net/reader030/viewer/2022041208/5d66cc1688c993dd5b8b6568/html5/thumbnails/13.jpg)
LOPEZ, Sebastián / FE 2015 13
Figure 15. Load vs drift plots for monotonic and pseudo dynamic lateral load test. Wall M2R4.
Table 10 shows a summary of the maximum lateral loads (VMAX) and the shear stress calculated over
the gross section of each wall.
Table 10. Results summary for in plane lateral load tests. Monotonic and dynamic.
Wall type Test type VMAX (kN) MAX (kPa)
M2.1
Monotonic
7.8 22.8
M2.R3.1 29.2 77.7
M2.R4.1 48.1 115.0
M2.2
Dynamic
6.20 30.6
M2.R3.2 32.4 160.0
M2.R4.2 67.1 331.4
Figure 16 shows the envelope plots from the hysteretic curves of unreinforced and reinforced walls.
The plots shows a considerable increment of lateral load strength for the reinforced walls comparing to
the unreinforced. Lateral load strength can be increased, compared to unreinforced walls, 4.8 times
when W.W.M is installed by one side and up to 9 times when it is used in both sides of the wall.
According to the results obtained, the reinforced walls had a lower rate of per cycle stiffness reduction
compared to the reinforced walls. Furthermore, reinforcing both sides of the walls would reduce up to
80% the stiffness reduction for drifts under the allowable values for masonry structures according to
NSR-10 (maximum drift of 0.5%). Failure patterns of unreinforced walls were due to uplift and for
reinforced walls due to foundation anchor failure and mortar failure parallel to the longitudinal
reinforcement. Figure 18 shows failures for unreinforced and reinforced walls.
Table 11 shows a summary of all the parameters required to calculate the energy dissipation
coefficient (R) according to NSR-10 or response modification coefficient according to ASCE 7
(ASCE, 2005). This value was obtained using two different approaches. R1 was calculated according
to the methodology of Newmark and Hall (Newark y Hall, 1973) and R2 was obtained according to
San Bartolomé (San Bartolomé et al, 2007). To calculate R1, was used as drift limit ( m) the drift
obtained for the maximum experimental lateral load from the pseudo dynamic tests. To calculate R2 it
Test: M2.R4.2
Pmax=50838 N/m
-196
-156
-117
-78
-39
0
39
78
117
156
196
-2.0% -1.5% -1.0% -0.5% 0.0% 0.5% 1.0% 1.5% 2.0%
-80000
-64000
-48000
-32000
-16000
0
16000
32000
48000
64000
80000
-40 -30 -20 -10 0 10 20 30 40
Shear stress
(kPa)Load (N)
D (mm)
Dynamic
Monotonic
![Page 14: Analytic and experimental evaluation of masonry walls ... · LOPEZ, Sebastián / FE 2015 3 Figure 2. Stretcher and header bond masonry wall. The compression strength of the units](https://reader030.fdocuments.net/reader030/viewer/2022041208/5d66cc1688c993dd5b8b6568/html5/thumbnails/14.jpg)
LOPEZ, Sebastián / FE 2015 14
was used as drift limit of 0.5%, which is 50% of the design drift allowable for walls with a flexural
failure mode or the allowable drift for any masonry structure according to NSR-10.
Figure 16. Load vs drift envelopes for unreinforced and reinforced walls.
Figure 17 shows the stiffness reduction per cycle curves for unreinforced and reinforced walls.
Figure 17. Per cycle stiffness reduction vs per cycle maximum drift for unreinforced and reinforced walls.
-2.0% -1.5% -1.0% -0.5% 0.0% 0.5% 1.0% 1.5% 2.0%
-204
-153
-102
-51
0
51
102
153
204
-40 -30 -20 -10 0 10 20 30 40
Shear stress
(kPa)
D (mm)
M2.2
M2.R3.2
M2.R4.2
0.0%
10.0%
20.0%
30.0%
40.0%
50.0%
60.0%
70.0%
80.0%
90.0%
100.0%
110.0%
120.0%
0.00% 0.25% 0.50% 0.75% 1.00% 1.25% 1.50% 1.75% 2.00%
Stifness
D(%)
M2.2
M2.R3.2
M2.R4.2
![Page 15: Analytic and experimental evaluation of masonry walls ... · LOPEZ, Sebastián / FE 2015 3 Figure 2. Stretcher and header bond masonry wall. The compression strength of the units](https://reader030.fdocuments.net/reader030/viewer/2022041208/5d66cc1688c993dd5b8b6568/html5/thumbnails/15.jpg)
LOPEZ, Sebastián / FE 2015 15
Figure 18. Failure patterns for lateral load test results. (a) Unreinforced wall uplift. Reinforced wall (b)
compression failure on the edge and (c) mortar failure parallel to longitudinal reinforcement.
Table 11. Calculation of energy dissipation coefficient or response modification coefficient.
Wall Type Δy (mm) μ=Δu/Δy EH (N.mm) VR (N) R1=√(2μ-1) R2=√(2K0EH)/VR
M2R3.2 3.22 1.8 552283 31590 1.6 3.0
M2R4.2 8.08 1.8 1026103 67106 1.6 1.6
The values obtained shows that there is only a really big difference between both approaches for wall
M2.R3.2. Conservatively a value of R=1.6 would be used as energy dissipation coefficient,
independently if one or two sides of the wall is reinforced. This value is close enough to the value
assigned to this structural system by NSR-10, R=1.5. Finally it was found that the walls reinforced can
develop up to 1.8 times greater drifts than the elastic limit drifts.
Below would be shown the strength calculations for allowable stress design and limit state design for
laterally loaded walls. The conventions used were the conventions already shown above for the
calculation of strength in the analysis of the diagonal tension tests. Table 12 shows the results of the
maximum allowable shear force (VALW), the allowable stresses and the stresses calculated according to
the acting force for unreinforced masonry walls.
Table 12. Allowable stresses for bending and shear in laterally loaded walls.
Wall
type
VALW
(kN)
Bending Shear
Ft*
(MPa)
Fb=0.33 f'm
(MPa)
ft
(MPa)
fb
(MPa)
Fv=√f'm/40<=0.56
(MPa)
fv
(MPa)
M2 6.9 0.17 3.83 0.17 0.17 0.09 0.03
Conservatively it was assumed an allowable stress of 0.17 MPa for tension due to bending on the
extreme fibre (minimum allowable stress for M and S mortars with hollow units according to table D-
1.5-1 NSR-10 page. D-71 or table 2.2.3.2 page C-28 ACI 530-05). The safety factor would be
calculated as the ratio between VALW form Table 12 and the minimum ultimate load for pseudo
dynamic and monotonic tests from Table 10. For unreinforced walls the safety factor is 6.9/6.2=1.11.
Table 13. Allowable stresses due to bending for laterally loaded walls.
Wall
type
VALW
(kN)
Bending
x
(mm)
Fb m=0.33 f'm
(MPa)
Fb cre=
0.33 f'cre
(MPa)
Fs=
0.5 fy
(MPa)
fb m
(MPa)
fb cre
(MPa)
fs
(MPa)
M2.R3 13.6 263
3.50 5.58 226 0.714 1.38 226
M2.R4 32.5 3.60 5.05 226 1.426 2.63 226
(a) (b) (c)
![Page 16: Analytic and experimental evaluation of masonry walls ... · LOPEZ, Sebastián / FE 2015 3 Figure 2. Stretcher and header bond masonry wall. The compression strength of the units](https://reader030.fdocuments.net/reader030/viewer/2022041208/5d66cc1688c993dd5b8b6568/html5/thumbnails/16.jpg)
LOPEZ, Sebastián / FE 2015 16
Table 14. Allowable stresses due to shear for laterally loaded walls.
Wall
type
VALW
(kN)
M/V
d
Shear
Fv m=
√f'm/12<=0.25
(MPa)
Fv cre=
√f'cre/12<=0.25
(MPa)
Fs=0.5 fy
(MPa)
fv m
(MPa)
fv cre
(MPa)
fsv
(MPa)
M1.R3 13.6 1.48 0.25 0.25 215 0.04 0.08 76.6
M1.R4 32.5 1.48 0.25 0.25 215 0.08 0.16 183.8
Below are shown the analysis of the results for reinforced walls according to the allowable stress
design method. Table 13 shows the maximum allowable shear force (VALW) and the allowable stresses
as the stresses due to bending. Table 14 shows the allowable and acting stresses due to shear.
The governing stress is tension due to bending in the longitudinal reinforcement bars. Table 15 shows
the calculation of the safety factors for bending and shear for laterally loaded walls according to the
allowable stress design method.
Table 15. Bending and shear safety factors for reinforced masonry walls. L.S.D.
Wall type VALW (kN) Lateral load test results
𝐹𝑆𝐵+𝑆 (𝐴.𝑆.𝐷) =𝑉exp𝑚𝑎𝑥
𝑉𝐴𝐿𝑊
Vexp max MONO (kN) Vexp max DYNA (kN)
M2.R3.1 13.6
29.2 - 2.16
M2.R3.2 - 32.4 2.39
M2.R4.1 32.5
48.6 - 1.49
M2.R4.2 - 67.1 2.06
For reinforced walls the average safety factor is 2.03 with a minimum value of 1.49.
Calculations of the strength of the walls according to the limit strength design were made using
Equation 2 and Equation 3 which correspond to modified equations originally used for concrete walls
designs with uniformly distributed reinforcement. The equations were modified considering the total
thickness of the wall the same as the thickness of the mortar layer (or the sum of the thicknesses in the
case of the walls reinforced into both sides) and the compression strength from the concrete (f’c) was
replaced by the compression strength of the mortar layer (f'cre).
𝑀𝑢 ≤ ∅𝑀𝑛 = ∅0.5𝐴𝑠𝑓𝑦𝐿 �1 +𝑃𝑢∅
𝐴𝑠𝑓𝑦 (1 −
𝑐
𝐿) (2)
𝑐
𝐿=
𝑃𝑢∅
+ 𝜌cre
𝑓𝑦𝑓 ′
𝑐𝑟𝑒
2𝜌𝑓𝑦
𝑓 ′𝑐𝑟𝑒
+ .7225
(3)
Where
=Strength reduction coefficient. For walls under bending without axial force is taken as 0.85.
As=Total area of steel in the transverse section, mm².
fy=Yielding strength of the reinforcing steel, MPa.
L=Length of the wall, mm.
Pu=Ultimate load of the wall, corresponding to the factored ultimate bending moment (Mu), N.
c/L=Ratio between the length of the compressed zone due to bending and the total length of the wall.
Table 16 and
![Page 17: Analytic and experimental evaluation of masonry walls ... · LOPEZ, Sebastián / FE 2015 3 Figure 2. Stretcher and header bond masonry wall. The compression strength of the units](https://reader030.fdocuments.net/reader030/viewer/2022041208/5d66cc1688c993dd5b8b6568/html5/thumbnails/17.jpg)
LOPEZ, Sebastián / FE 2015 17
Table 17 shows the calculation of the strength of the walls for bending and shear according to the limit
state design. Safety factors calculated according to the limit strength design are shown in Table 18.
Table 16. Bending strength for laterally loaded reinforced masonry walls. L.S.D.
Wall type
Boundary
stresses Boundary
Elements
required?
Bending
(MPa) C/L As (mm²) φMn (kN.m) φMn/H (kN)
M2.R3 7.3 SI 0.18 254 53.0 27.6
M2.R4 6.1 SI 0.17 509 107 55.9
Table 17. Shear strength for laterally loaded reinforced masonry walls. L.S.D.
Wall type Shear
Mu/(Vu d)=H/d Vm (kN) Vs (kN) φVn (kN)
M2.R3 1.48 25.7 0 15.4
M2.R4 1.48 57.5 0 34.5
Table 18. Safety factors for lateral loaded reinforced masonry walls. L.S.D.
Wall type VL.S.D (kN) Lateral load test results
𝐹𝑆𝐵+𝑆 (𝐿.𝑆.𝐷) =𝑉exp𝑚𝑎𝑥
𝑉𝐿.𝑆.𝐷
Vexp max MONO (kN) Vexp max DYNA (kN)
M2.R3.1 15.4
29.2 - 1.89
M2.R3.2 - 32.4 2.10
M2.R4.1 34.5
48.6 - 1.41
M2.R4.2 - 67.1 1.94
The minimum safety factor is 1.41 and the average is 1.84.
Compared to the results obtained for the same walls according to the allowable stress design method
where the average was 2.03 and the minimum was 1.49, it was found similarity between the results
and in both cases the calculations would be consider as appropriated because they always showed
safety factors higher than one.
Conclusions
Diagonal tension strength in masonry walls externally reinforced with W.W.M, can be increased
respect to the unreinforced masonry walls, in almost 1.5 times when this technique is applied by one
side of the wall and up to almost 1.9 times when it is applied by both faces of the wall.
Considering the results for monotonic and pseudo dynamic in plane lateral loads, it was observed that
applying W.W.M and mortar by one of the sides of the walls, increases the ultimate strength of the
wall comparing the results with the unreinforced walls, in more than 4 times when W.W.M and mortar
is applied by one side and up to 8 times when is applied on both sides of the wall.
Even if the reinforcement technique is applied just by one side of the wall, this would always improve
the stiffness reduction of the wall when is subjected to pseudo dynamic loads and the strength is being
increased as well for both monotonic and pseudo dynamic loads.
In all the tests done, it was found a critical change between the failure mechanism of the unreinforced
and reinforced masonry walls. All the walls reinforced for one or both sides, had a ductile and gradual
failure mechanism while the unreinforced walls had a sudden and brittle failure mechanism. This
difference would be valuable specially when the structural elements are approaching to the ultimate
limit state, allowing to the users to evacuate before the failure of the element. This feature would be
impossible in structure totally made of unreinforced masonry wall.
![Page 18: Analytic and experimental evaluation of masonry walls ... · LOPEZ, Sebastián / FE 2015 3 Figure 2. Stretcher and header bond masonry wall. The compression strength of the units](https://reader030.fdocuments.net/reader030/viewer/2022041208/5d66cc1688c993dd5b8b6568/html5/thumbnails/18.jpg)
LOPEZ, Sebastián / FE 2015 18
The calculated strength for diagonal tension and lateral load for the methodologies allowed by
Colombian regulations, for reinforced and unreinforced masonry walls, showed that the calculations
developed were safe in comparison to the experimental results
Calculations of the response modification coefficient according to Newmark and Hall, and San
Bartolomé, showed in a conservative way, that reinforcing both sides W.W.M and mortar does not
improve the value of the coefficient for the walls studied. This results are compatible with the results
obtained for this technique in other kind of walls and also confirms that the value of 1.5 adopted for
the response modification coefficient by NSR-10 is adequate.
Special care should be taken during the construction of this kind of walls. It has to be done an strict
quality control during installation of the anchors to the wall, to the foundation beam and top beam.
Before pouring the mortar an inspection should be required
High plasticity mortars are required for this kind of application. All the measurements should be taken
to avoid the lost of humidity and reduce the compression strength of the mortar. Previously to the
installation of the mortar, should be applied directly to the surface of the wall, enough water to
guaranty the saturation of the base surface.
References
ACI. (2008). 530/530.1-08: Building Code Requirements and Specification for Masonry Structures
and Related Commentaries. Farmington Hills, MI: ACI.
ASCE. (2005). ASCE 7-05 Minimum Design Loads for Buildings and Other Structures. Reston, VA:
American Society of Civil Engineers.
ASTM. (2010). Standard Test Method for Diagonal Tension (Shear) in Masonry Assemblages. ASTM
E519 / E519M - 10 Standard Test Method for Diagonal Tension (Shear) in Masonry Assemblages
. West Conshohocken, PA: ASTM International.
GDF. (2002). Normas Técnicas Complementarias para el Ciseño y Construcción de Estructuras de
Mampostería. México, DF.
ICONTEC. (2001, 03 21). Método de ensayo para determinar la resistencia a la tracción diagonal -
cortante - en muretes de mampostería. NTC 4925 - Prefabricados de concreto. Método de ensayo
para determinar la resistencia a la tracción diagonal - cortante - en muretes de mampostería.
Bogotá, Cundinamarca, Colombia: ICONTEC.
Jaramillo Morilla, A., Rodríguez Liñán, C., de Justo Alpañés, J. L., Romero Hernández, R., & Pérez
Gálvez, F. (2000). Características de los muros antiguos de Sevilla. Tercer Congreso Nacional de
Historia de la Construcción, (pp. 527-535). Sevilla.
López, S. (2013). Evaluación del comportamiento de muros de mampostería no reforzada recubiertos
con mortero reforzado. Bogotá: Escuela Colombiana de Ingeniería Julio Garavito.
López, S., & Torres Castellanos, N. (2012). Evaluación del comportamiento de muros de mampostería
no reforzada recubierta con mortero reforzado. XXII CONGRESO NACIONAL, XI CONGRESO
INTERNACIONAL DE ESTUDIANTE DE INGENIERIA CIVIL, (pp. 1-10). Manizales, Col.
López, S., Quiroga, P. N., & Torres Castellanos, N. (2013). Evaluación analítica y experimental de
muros de mampostería no reforzada y reforzada. VI CONGRESO NACIONAL DE INGENIERIA
SISMICA, (pp. 1-20). Bucaramanga, Col.
López, S., Quiroga, P. N., & Torres Castellanos, N. (2012). Evaluation of unreinforced masonry walls
covered with reinforced mortars. xxxv Jornadas Sul Americanas de Engenharia Estrutural, (pp.
1-14). Rio de Janeiro, Bra.
Ministerio de Ambiente, Vivienda y Desarrollo Territorial. (2010). NSR-10. Reglamento Colombiano
de Construcciones Sismorresistentes. Bogotá.
![Page 19: Analytic and experimental evaluation of masonry walls ... · LOPEZ, Sebastián / FE 2015 3 Figure 2. Stretcher and header bond masonry wall. The compression strength of the units](https://reader030.fdocuments.net/reader030/viewer/2022041208/5d66cc1688c993dd5b8b6568/html5/thumbnails/19.jpg)
LOPEZ, Sebastián / FE 2015 19
Newark Nathan M., H. W. (1973). Seismic design criteria for nuclear reactor facilities. Building
Practices for Disaster Mitigation, National Bureau of Standards, U.S., Department of Commerce,
Reporte Nº 46 . Washington.
San Bartolomé, Á. ,. (2007). Comportamiento a fuerza cortante de muretes de concreto reforzados con
malla electrosoldada, acero dúctil y fibra metálica. 1-10.
Useche, L. A. (1993). Estudio de lo morteros y pañetes para la conservación de monumentos
históricos. Bogotá: Universidad Nacional de Colombia.