Analog Sensors – The Design & Operation
![Page 2: Analog Sensors – The Design & Operation](https://reader033.fdocuments.net/reader033/viewer/2022061502/5681585d550346895dc5b85c/html5/thumbnails/2.jpg)
HVAC Sensors
Sensors measure the controlled medium and provide a controller with information concerning changing conditions in an accurate and
repeatable manner. The common HVAC variables are temperature, pressure, flow rate and relative humidity.
Controller
ControlledElement
Controlled Variable = Space TemperatureControlled Medium = Room Air
Controls Heat/Cool Source
Control Agent
![Page 3: Analog Sensors – The Design & Operation](https://reader033.fdocuments.net/reader033/viewer/2022061502/5681585d550346895dc5b85c/html5/thumbnails/3.jpg)
HVAC Sensors
• The placement of a sensor is critical to achieve good control. In sensing space conditions, the sensing device must not be in the path of direct solar radiation or be located on a surface which would give a false reading such as a poorly insulated external wall.
• In pipework or ductwork, sensors must be arranged so that the active part of the device is immersed fully in the fluid and that the position senses the average condition.
![Page 4: Analog Sensors – The Design & Operation](https://reader033.fdocuments.net/reader033/viewer/2022061502/5681585d550346895dc5b85c/html5/thumbnails/4.jpg)
Types of Inputs
Digital InputTwo position, a simple contact closure from a mechanical switch or
similar device
Pressure • TemperatureEvent • Level • Flow
Analog InputModulating, the signal is proportional and varies with the control variable
![Page 5: Analog Sensors – The Design & Operation](https://reader033.fdocuments.net/reader033/viewer/2022061502/5681585d550346895dc5b85c/html5/thumbnails/5.jpg)
Types of Analog Inputs
Typical sensors used in electronic control systems are:•Resistance sensors are ‘Resistance Temperature Devices (RTD’s) •Voltage sensors could be used for temperature, humidity and pressure. Typical voltage input ranges are 0 to 5 Vdc (Volts direct current), 1 to 11 Vdc, and 0 to 10 Vdc, 2 to 10 Vdc.•Current sensors could be used for temperature, humidity, and pressure. The typical current range is 4 to 20 mA (milliamps) or 0 to 20 mA
![Page 6: Analog Sensors – The Design & Operation](https://reader033.fdocuments.net/reader033/viewer/2022061502/5681585d550346895dc5b85c/html5/thumbnails/6.jpg)
Types of Analog Inputs
ActiveRequire an external source
(voltage or current) of excitation
PassiveAre two-port devices that directly
transform physical energy to electrical energy, generating output
signals without the need for an excitation source.
Thermocouple Photodiode
Thermistors
RTD
Strain Gage
![Page 7: Analog Sensors – The Design & Operation](https://reader033.fdocuments.net/reader033/viewer/2022061502/5681585d550346895dc5b85c/html5/thumbnails/7.jpg)
Thermocouples (Passive)
• Thermocouples have two dissimilar metal wires joined at one end. • Temperature differences at the junctions’ causes a voltage, in the mill
volts (Seebeck Effect)• The output is a voltage proportional to the temperature difference
between the junction and the free ends
![Page 8: Analog Sensors – The Design & Operation](https://reader033.fdocuments.net/reader033/viewer/2022061502/5681585d550346895dc5b85c/html5/thumbnails/8.jpg)
Thermocouples
• By holding one junction at a known temperature (reference junction) and measuring the voltage, the temperature at the sensing junction can be deduced.
• The voltage generated is directly proportional to the temperature difference.
![Page 9: Analog Sensors – The Design & Operation](https://reader033.fdocuments.net/reader033/viewer/2022061502/5681585d550346895dc5b85c/html5/thumbnails/9.jpg)
Thermocouples
• Advantages: Widest operating range, simple, low cost and no external power supply required
• Disadvantages: Non-linear, low stability relative to other types, reference junction temperature compensation required
![Page 10: Analog Sensors – The Design & Operation](https://reader033.fdocuments.net/reader033/viewer/2022061502/5681585d550346895dc5b85c/html5/thumbnails/10.jpg)
Thermocouples – Various Types (Active)
Seebeck Coefficient is Nonlinear
Type K = 41µV/˚C
![Page 11: Analog Sensors – The Design & Operation](https://reader033.fdocuments.net/reader033/viewer/2022061502/5681585d550346895dc5b85c/html5/thumbnails/11.jpg)
Thermistors
• Thermistors are temperature sensitive semiconductors that exhibit a large change in resistance over a relatively small range of temperature.
• There are two main types of thermistors, positive temperature coefficient (PTC) and negative temperature coefficient (NTC).
• NTC thermistors exhibit the characteristic of falling resistance falling with increasing temperature.
![Page 12: Analog Sensors – The Design & Operation](https://reader033.fdocuments.net/reader033/viewer/2022061502/5681585d550346895dc5b85c/html5/thumbnails/12.jpg)
Thermistors
• They are non-linear, and cannot be characterized by a single coefficient. Manufacturers commonly provide resistance-temperature data in curves, tables or polynomial expressions
• Linearizing the resistance-temperature correlation may be accomplished with analog circuitry, or by the application of mathematics using digital computation
![Page 13: Analog Sensors – The Design & Operation](https://reader033.fdocuments.net/reader033/viewer/2022061502/5681585d550346895dc5b85c/html5/thumbnails/13.jpg)
Thermistors
• Advantages: Large resistance change with temperature, rapid response time, good stability, High resistance eliminates difficulties caused by lead resistance, Low cost and interchangeable
• Disadvantages: Non-linear, limited operating temperature range, may be subjected to inaccuracy due to overheating, current source required
![Page 14: Analog Sensors – The Design & Operation](https://reader033.fdocuments.net/reader033/viewer/2022061502/5681585d550346895dc5b85c/html5/thumbnails/14.jpg)
RTD (Resistive Temperature Device)
• RTD (Resistance Temperature Detector) is a temperature sensitive resistor
• It is a positive temperature coefficient device
Common materials used are BALCO wire and Platinum
Advantages Very predictable Stable output over a long period of time Easy to recalibrate Accurate reading over relatively narrow
temperature range
![Page 15: Analog Sensors – The Design & Operation](https://reader033.fdocuments.net/reader033/viewer/2022061502/5681585d550346895dc5b85c/html5/thumbnails/15.jpg)
Balco
• A sensor constructed using a BALCO wire is an annealed resistance alloy with a nominal composition of 70 percent nickel and 30 percent iron.
• A BALCO 500-ohm resistance element provides a relatively linear resistance variation from –40 to 250°F.
• The sensor is a low mass device and responds quickly to changes in temperature.
• When 1000 ohms is measured across the BALCO element, the temperature is approximately 70°F.
• As the temperature increases, the resistance changes 2.2 ohms per 1°F.
![Page 16: Analog Sensors – The Design & Operation](https://reader033.fdocuments.net/reader033/viewer/2022061502/5681585d550346895dc5b85c/html5/thumbnails/16.jpg)
Platinum
• RTD sensors using platinum material exhibit linear response and stable over time.
• In some applications a short length of wire is used to provide a nominal resistance of 100 ohms.
• However, with a low resistance value, element self-heating and sensor lead wire resistance can effect the temperature indication. With a small amount of resistance change of the element, additional amplification must be used to increase the signal level.
![Page 17: Analog Sensors – The Design & Operation](https://reader033.fdocuments.net/reader033/viewer/2022061502/5681585d550346895dc5b85c/html5/thumbnails/17.jpg)
Humidity Sensor - Resistive
• Relative humidity based on a layer of hygroscopic salt, such as lithium chloride or carbon powder deposited between two electrodes
• Both materials absorb and release moisture as a function of the relative humidity, causing a change in resistance of the sensor
• An electronic controller connected to this sensor detects the changes in resistance which it can use to provide control of relative humidity
![Page 18: Analog Sensors – The Design & Operation](https://reader033.fdocuments.net/reader033/viewer/2022061502/5681585d550346895dc5b85c/html5/thumbnails/18.jpg)
Humidity Sensor - Capacitive
• Changes in capacitance can be used to determine relative humidity • This sensor measures the capacitance between two conductive plates
separated by a moisture sensitive material such as polymer plastic• As the material absorbs water, the capacitance between the plates
decreases and the change can be detected by an electronic circuit
Humidity Sensor - Capacitive
![Page 19: Analog Sensors – The Design & Operation](https://reader033.fdocuments.net/reader033/viewer/2022061502/5681585d550346895dc5b85c/html5/thumbnails/19.jpg)
Pressure Sensors
• Diverse electrical principles are applied to pressure measurement. • Those commonly used include capacitance and variable resistance
(piezoelectric and strain gage)
![Page 20: Analog Sensors – The Design & Operation](https://reader033.fdocuments.net/reader033/viewer/2022061502/5681585d550346895dc5b85c/html5/thumbnails/20.jpg)
Pressure Sensors - Resistive
• A method that measures pressure by detecting changes in resistance using a small flexible diaphragm and a strain gage assembly
• The strain gage assembly includes very fine (serpentine) wire or a thin metallic film deposited on a nonconductive base
• The strain gage assembly is stretched or compressed as the diaphragm flexes with pressure variations.
• The stretching or compressing of the strain gage changes the length of its fine wire/thin film metal, which changes the total resistance.
• The resistance can then be detected and amplified.
![Page 21: Analog Sensors – The Design & Operation](https://reader033.fdocuments.net/reader033/viewer/2022061502/5681585d550346895dc5b85c/html5/thumbnails/21.jpg)
Pressure Sensor - Capacitive
• A fixed plate forms one part of the capacitor assembly and a flexible plate is the other part of the capacitor assembly
• As the diaphragm flexes with pressure variations, the flexible plate of the capacitor assembly moves closer to the fixed plate and changes the capacitance.
![Page 22: Analog Sensors – The Design & Operation](https://reader033.fdocuments.net/reader033/viewer/2022061502/5681585d550346895dc5b85c/html5/thumbnails/22.jpg)
Testing an Analog Input – Thermistor
![Page 23: Analog Sensors – The Design & Operation](https://reader033.fdocuments.net/reader033/viewer/2022061502/5681585d550346895dc5b85c/html5/thumbnails/23.jpg)
Testing an Analog Input – Thermistor
• Use an ice bath to test thermistors• Solutions allows a known
temperature for the test• Crushed ice works best• Fill container with as much ice as
possible• Then fill with water (distilled water
if possible)• Let solution stabilize for several
minutes to allow ice an water to stabilize at 32˚F
![Page 24: Analog Sensors – The Design & Operation](https://reader033.fdocuments.net/reader033/viewer/2022061502/5681585d550346895dc5b85c/html5/thumbnails/24.jpg)
Testing an Analog Input – Thermocouple
There are two steps to checking thermocouples. •The first is to check for a short on its terminals •And the second, to make sure that voltage tracks with the temperature.
![Page 25: Analog Sensors – The Design & Operation](https://reader033.fdocuments.net/reader033/viewer/2022061502/5681585d550346895dc5b85c/html5/thumbnails/25.jpg)
Testing an Analog Input – Thermocouple
Put the meter in ohms or continuity mode; on a good thermocouple, you should see a low resistance reading. If you
see more than a few ohms, you probably have a faulty thermocouple
![Page 26: Analog Sensors – The Design & Operation](https://reader033.fdocuments.net/reader033/viewer/2022061502/5681585d550346895dc5b85c/html5/thumbnails/26.jpg)
Testing an Analog Input – Thermocouple
The second test requires a meter that can measure down to tenths of millivolts (0.0001 V). A meter that can measure hundredths of millivolts (0.00001 V) makes it even easier to do this check, because the added resolution shows very small temperature changes.
Connect the meter to the terminals of the thermocouple. Grabbing the end of the thermocouple should cause the voltage to increase slightly, since you're warming it up. As you release the junction, the temperature (and voltage) should drop
![Page 27: Analog Sensors – The Design & Operation](https://reader033.fdocuments.net/reader033/viewer/2022061502/5681585d550346895dc5b85c/html5/thumbnails/27.jpg)
Testing an Analog Input - 4 to 20 mA / 0 to 10 vDC
Manometer
![Page 28: Analog Sensors – The Design & Operation](https://reader033.fdocuments.net/reader033/viewer/2022061502/5681585d550346895dc5b85c/html5/thumbnails/28.jpg)
Check its Wiring Per the Manufacturers Wiring Diagram
Testing an Analog Input - 4 to 20 mA / 0 to 10 vDC
![Page 29: Analog Sensors – The Design & Operation](https://reader033.fdocuments.net/reader033/viewer/2022061502/5681585d550346895dc5b85c/html5/thumbnails/29.jpg)
Check Setting of Sensor, if applicable
• Set PJ3 at L position and PJ5 at N position
• Zero out the sensor by removing any hoses from the two barbs and holding in the zero button for 4-5 seconds
Sensor should be set for 0 to 1“ operation Follow Manufactures Guidelines
![Page 30: Analog Sensors – The Design & Operation](https://reader033.fdocuments.net/reader033/viewer/2022061502/5681585d550346895dc5b85c/html5/thumbnails/30.jpg)
Testing an Analog Input - 4 to 20 mA
mAPP
PPI )
min)(max)(
min)((164
Manometer
![Page 31: Analog Sensors – The Design & Operation](https://reader033.fdocuments.net/reader033/viewer/2022061502/5681585d550346895dc5b85c/html5/thumbnails/31.jpg)
Example
Manometer0.5 in. w.c.
Sensor Range = 0 to 1 in. w.c.
![Page 32: Analog Sensors – The Design & Operation](https://reader033.fdocuments.net/reader033/viewer/2022061502/5681585d550346895dc5b85c/html5/thumbnails/32.jpg)
Example
mAPP
PPI )
min)(max)(
min)((164
mAI
mAI
12
))0()1(
)0(50.0(164
![Page 33: Analog Sensors – The Design & Operation](https://reader033.fdocuments.net/reader033/viewer/2022061502/5681585d550346895dc5b85c/html5/thumbnails/33.jpg)
Example
Manometer0.5 in. w.c.
mAI
mAI
12
))0()1(
)0(50.0(164
![Page 34: Analog Sensors – The Design & Operation](https://reader033.fdocuments.net/reader033/viewer/2022061502/5681585d550346895dc5b85c/html5/thumbnails/34.jpg)
Testing an Analog Input – 0 to 10 vdc
vdcPP
PPV )
min)(max)(
min)((10
![Page 35: Analog Sensors – The Design & Operation](https://reader033.fdocuments.net/reader033/viewer/2022061502/5681585d550346895dc5b85c/html5/thumbnails/35.jpg)
Example
Sensor Range 0 to 100 psig
![Page 36: Analog Sensors – The Design & Operation](https://reader033.fdocuments.net/reader033/viewer/2022061502/5681585d550346895dc5b85c/html5/thumbnails/36.jpg)
Example
vdcV ))0()100(
)0(50(10
vdcV 5
vdcPP
PPV )
min)(max)(
min)((10
![Page 37: Analog Sensors – The Design & Operation](https://reader033.fdocuments.net/reader033/viewer/2022061502/5681585d550346895dc5b85c/html5/thumbnails/37.jpg)
Example
Sensor Range 0 to 100 psig
vdcV ))0()100(
)0(50(10
vdcV 5
![Page 38: Analog Sensors – The Design & Operation](https://reader033.fdocuments.net/reader033/viewer/2022061502/5681585d550346895dc5b85c/html5/thumbnails/38.jpg)
Selecting Replacement Sensors
• Normally best to use an OEM replacement• If resistive based, determine type and characteristics • If current or voltage, determine the required range and
required output signal
![Page 39: Analog Sensors – The Design & Operation](https://reader033.fdocuments.net/reader033/viewer/2022061502/5681585d550346895dc5b85c/html5/thumbnails/39.jpg)
Read the controller’s manual
Getting Help
Call the manufacture
![Page 40: Analog Sensors – The Design & Operation](https://reader033.fdocuments.net/reader033/viewer/2022061502/5681585d550346895dc5b85c/html5/thumbnails/40.jpg)
Product Literature
![Page 41: Analog Sensors – The Design & Operation](https://reader033.fdocuments.net/reader033/viewer/2022061502/5681585d550346895dc5b85c/html5/thumbnails/41.jpg)