AN OVERVIEW ON CONTINUOUS EFFLUENT QUALITY …

30
AN OVERVIEW ON CONTINUOUS EFFLUENT QUALITY MONITORING SYSTEM WORKSHOP ORGANIZED BY MPCB, BHOPAL 04-06 JULY 2017

Transcript of AN OVERVIEW ON CONTINUOUS EFFLUENT QUALITY …

Page 1: AN OVERVIEW ON CONTINUOUS EFFLUENT QUALITY …

AN OVERVIEW ON CONTINUOUS EFFLUENT

QUALITY MONITORING SYSTEM

WORKSHOP ORGANIZED BY MPCB, BHOPAL

04-06 JULY 2017

Page 2: AN OVERVIEW ON CONTINUOUS EFFLUENT QUALITY …
Page 3: AN OVERVIEW ON CONTINUOUS EFFLUENT QUALITY …

3

Goals of Online environmental monitoring system

• Improved control over impacts on theenvironment

• Higher environmental awareness• Increased management responsibility for

regulatory compliance• Self Monitoring mechanism within the industries• Increased cost-effectiveness (minimize

inspection)• Increased public access to information(Public

Domain)

Page 4: AN OVERVIEW ON CONTINUOUS EFFLUENT QUALITY …

Real-time Water Quality Monitoring

Fresh Water and Wastewater

Options In-situ and Extractive

Page 5: AN OVERVIEW ON CONTINUOUS EFFLUENT QUALITY …

Advantages and Disadvantages of Flow Through Extractive System

Page 6: AN OVERVIEW ON CONTINUOUS EFFLUENT QUALITY …

Advantages and Disadvantages of In-situ Monitoring System

Page 7: AN OVERVIEW ON CONTINUOUS EFFLUENT QUALITY …
Page 8: AN OVERVIEW ON CONTINUOUS EFFLUENT QUALITY …
Page 9: AN OVERVIEW ON CONTINUOUS EFFLUENT QUALITY …

Instrumentation of RTEQMS

• Various equipment manufacturers in India and Abroad arecapable to supply, install, commission and operate theRTEQMS.

• Technology providers have analyser as well as sensorbased equipment's to cater to the needs of RTEQMS.

• General guidelines shall not specify the equipments andtechnology to be used for setting up of RTEQMS

• Market based system shall be governed for setting up ofRTEQMS

• Industrial units/associations shall use the equipment andservice providers based on the economics and ruggednessfor RTEQMS to last longer (say at least 5 to 8 years)

Page 10: AN OVERVIEW ON CONTINUOUS EFFLUENT QUALITY …
Page 11: AN OVERVIEW ON CONTINUOUS EFFLUENT QUALITY …
Page 12: AN OVERVIEW ON CONTINUOUS EFFLUENT QUALITY …
Page 13: AN OVERVIEW ON CONTINUOUS EFFLUENT QUALITY …
Page 14: AN OVERVIEW ON CONTINUOUS EFFLUENT QUALITY …
Page 15: AN OVERVIEW ON CONTINUOUS EFFLUENT QUALITY …

Site Selection

• Fixing of site for installation of RTEQMS should berepresentative and in compliance to provisions ofConsent Management (notified effluent outfall withcoordinates-Global Positioning System) to assesstemporal changes in the quality of effluentdischarged from the premises of industrial unit.

• Monitoring site should be accurately displayed withwritten station location.

• Photographic evidence should be obtained in thedocumentation.

Page 16: AN OVERVIEW ON CONTINUOUS EFFLUENT QUALITY …

Data Management and Quality Checks

• RTEQMS generated data should be validated according toWater Quality Criteria/Effluent Discharge Standards usingthe methodologies included in the publication of AmericanPublic Health Association on Water and Waste WaterExamination(20th Edition)

• Sensors/analyzers shall have current US EPA reference orequipment method designation and shall be of the latestdesign.

Page 17: AN OVERVIEW ON CONTINUOUS EFFLUENT QUALITY …

Data Management and Quality Checks(contd.)

• Standard Operating procedure should be providedand must contain

o Operating procedures for all analyzers andsensors

o Calibration procedureso Calibration scheduleso Maintenance procedureso Maintenance scheduleso Data Transmission procedureso Data validation procedures

Page 18: AN OVERVIEW ON CONTINUOUS EFFLUENT QUALITY …

General Specifications -RTEQMS

Equipment's should be capable of operating in aself-powering mode from an internal power supply(using cell batteries/alternative system) with a fullpayload at a defined sampling interval.

Equipment's should have a non-volatile flash diskmemory capable of storing individual readings for aperiod of at least one year.

Loss of power should not cause loss of memory

Page 19: AN OVERVIEW ON CONTINUOUS EFFLUENT QUALITY …

pH (mV)

Parameter Technical Specification

Measuring Range 0.0 to 14 units of pH

Accuracy ≤ 0.01 units of pH

Response Time ≤ 60 seconds

Operating Temperature 0 to 40o C

Operating Humidity 5 to 95% non-condensing

Power 12 VDC Nominal

Cleaning Self-Cleaning ( Automatic )

Page 20: AN OVERVIEW ON CONTINUOUS EFFLUENT QUALITY …

COD (mg/l)

Parameter Technical Specification

Measuring Range 0.0 to 500 mg/L

Accuracy ± 2% + 5 mg/L of certified

reference standard

Resolution ≤ 1 mg/L

Response Time ≤ 60 seconds

Operating Temperature 0 to 40o C

Operating Humidity 5 to 95% non-condensing

Power 12 VDC Nominal

Cleaning Self-Cleaning ( Automatic )

Page 21: AN OVERVIEW ON CONTINUOUS EFFLUENT QUALITY …

BOD (mg/L)

Parameter Technical Specification

Measuring Range 0.0-50 mg/L

Resolution ≤ 1 mg/L

Response Time ≤ 60 seconds

Operating Temperature 0 to 40o C

Operating Humidity 5 to 95% non-condensing

Power 12 VDC Nominal

Cleaning Self-Cleaning ( Automatic )

Page 22: AN OVERVIEW ON CONTINUOUS EFFLUENT QUALITY …

Ammonia (mg/l)

Parameter Technical Specification

Measuring Range 0.0 to 100 mg/L

Accuracy ≤ 3% of full scale

Resolution ≤ 0.1 mg / L

Response Time ≤ 60 seconds

Operating Temperature 0 to 40o C

Operating Humidity 5 to 95% non-condensing

Power 12 VDC Nominal

Cleaning Self-Cleaning ( Automatic )

Page 23: AN OVERVIEW ON CONTINUOUS EFFLUENT QUALITY …

Total Suspended Solids (mg/l)

Parameter Technical Specification

Measuring Range 0.0 to 200 mg/l

Accuracy ≤ 5 mg/l

Response Time ≤ 60 seconds

Operating Temperature 0 to 40o C

Operating Humidity 5 to 95% non-condensing

Power 12 VDC Nominal

Cleaning Self-Cleaning ( Automatic )

Page 24: AN OVERVIEW ON CONTINUOUS EFFLUENT QUALITY …

• Replaces old traditional cabinet

analyzers and UV probes to have

organic analysis without any need of

toxic reagents, consumables , spares

& regular maintenance.

A model online water quality monitoring technologies

Page 25: AN OVERVIEW ON CONTINUOUS EFFLUENT QUALITY …

SpectrometerProbes

ISEProbes

Physical

Probes

i::scan

A model online water quality monitoring technologies

Page 26: AN OVERVIEW ON CONTINUOUS EFFLUENT QUALITY …

Online Water Quality Monitoring & UV/Vis Spectrometry

The Measuring Principle – Fingerprint

Page 27: AN OVERVIEW ON CONTINUOUS EFFLUENT QUALITY …

mo

ni:

:to

ol

Sen

sor

and

sta

tio

n m

anag

em

en

t

vali::toolData Validation

Probes

Op

erat

ion

al D

ata

Raw

Dat

a

Val

idat

edD

ata

Even

t D

ata

ana::toolEvent Detection

Operations

From Raw Data to Event Detection

Page 28: AN OVERVIEW ON CONTINUOUS EFFLUENT QUALITY …

Automatic cleaning of submersed sensors

Efficiency of the automatic cleaning w. pressure air

Page 29: AN OVERVIEW ON CONTINUOUS EFFLUENT QUALITY …

• Measurement

results from Okhla:

• Continuous results

every 10 minutes,

automatic file

transfer of:

• NTU, COD, BOD,

NO3, DO, pH,

NH4-N, EC, Cl-,

Temp

Real Time Continuous Water Quality Monitoring Stations at the Ganga Basin

Page 30: AN OVERVIEW ON CONTINUOUS EFFLUENT QUALITY …

THANK YOU

Abhijit Pathak

[email protected]

43102348, 9971566700