SUBMITTAL © 2017 Ingersoll Rand TAG: _________________________________ Upflow/ Horizontal Induced Draft Single Stage Gas Furnace Ameristar M951P040BU24AA M951P040BU24-SUB-1B FURNACE AIRFLOW (CFM) VS. EXTERNAL STATIC PRESSURE (in. w.c.) MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 M951P040BU24AA 4 - 3 - 2 - 1 - HIGH - Black MED.-HIGH - Blue MED.-LOW - Yellow LOW - Red 1043 940 837 729 992 895 798 694 930 841 752 657 885 791 705 600 812 726 649 545 740 650 560 478 647 559 438 376 518 420 305 220 457 390 279 178 CFM VS. TEMPERATURE RISE MODEL Cubic Feet Per Minute (CFM) 600 700 800 900 1000 1100 1200 1300 1400 M951P040BU24AA 59 50 44 39 35 1-5/8" HOLE WITH PLUG 1-5/8" HOLE WITH PLUG 7/8" DIA. HOLES ELECTRICAL CONNECTION 1-1/2" DIA. HOLE GAS CONNECTION 40" 2" DIAMETER FLUE CONNECT 22-1/2" 9-1/2" 1/2" 3-3/4" 19-1/2" 5-5/16" 1/2" 5-1/2" 24" 3-1/4" 3/4" 28-1/2" 19-5/8" 5/8" 4-9/16" 16-1/4" 28-1/4" 5/8" 17-1/2" 16" 3/4" 2-1/16" 7-1/2" 2-1/8" 5/8" 1/2" 2-1/4" 20-1/4" 7/8" HOLE WITH PLUG CONDENSATE DRAIN (RIGHT SIDE HOLES ARE ALTERNATIVES) 2" DIAMETER OUTSIDE AIR 1-3/4" X 2-13/32" CUTOUT HORIZONTAL DRAIN

Transcript of Ameristar · 2020. 1. 15. · Ameristar Furnaces Furnace M951 Submittal-03/17 M951P040BU24-SUB-1B...

Page 1: Ameristar · 2020. 1. 15. · Ameristar Furnaces Furnace M951 Submittal-03/17 M951P040BU24-SUB-1B M951P040BU24-SUB-1A 1 Central Furnace heating designs are certified to ANSI Z21.47

SUBMITTAL

© 2017 Ingersoll Rand

TAG: _________________________________

Upflow/ Horizontal Induced Draft Single Stage Gas Furnace

Ameristar

M951P040BU24AA

M951P040BU24-SUB-1B

FURNACE AIRFLOW (CFM) VS. EXTERNAL STATIC PRESSURE (in. w.c.)

MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90

M951P040BU24AA

4 - 3 -2 -1 -

HIGH - BlackMED.-HIGH - BlueMED.-LOW - YellowLOW - Red

1043940837729

992895798694

930841752657

885791705600

812726649545

740650560478

647559438376

518420305220

457390279178

CFM VS. TEMPERATURE RISE

MODELCubic Feet Per Minute (CFM)

600 700 800 900 1000 1100 1200 1300 1400

M951P040BU24AA 59 50 44 39 35

1-5/8" HOLE WITH PLUG

1-5/8" HOLE WITH PLUG

7/8" DIA. HOLESELECTRICALCONNECTION

1-1/2" DIA. HOLEGAS CONNECTION

40"

2" DIAMETERFLUE CONNECT

22-1/2"

9-1/2"

1/2"

3-3/4"

19-1/2"

5-5/16"

1/2"

5-1/2"24"

3-1/4"

3/4"

28-1/2"19-5/8"

5/8"

4-9/16"

16-1/4"

28-1/4"

5/8"17-1/2"

16"

3/4"

2-1/16"

7-1/2"

2-1/8"

5/8"1/2"

2-1/4"

20-1/4"

7/8" HOLE WITH PLUGCONDENSATE DRAIN(RIGHT SIDE HOLES ARE ALTERNATIVES)

2" DIAMETEROUTSIDE AIR

1-3/4" X 2-13/32" CUTOUTHORIZONTAL DRAIN

Page 2: Ameristar · 2020. 1. 15. · Ameristar Furnaces Furnace M951 Submittal-03/17 M951P040BU24-SUB-1B M951P040BU24-SUB-1A 1 Central Furnace heating designs are certified to ANSI Z21.47

Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.

Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032

Technical Literature - Printed in U.S.A.

LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes

Mechanical Specifications

AmeristarFurnacesFurnaceM951Submittal-03/17M951P040BU24-SUB-1BM951P040BU24-SUB-1A

1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.AFUE (Upflow / Horizontal)BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)

HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)

M951P040BU24AAUpflow / Horizontal

40,00038,00030 - 60

95.0 / 94.2DIRECT

9 x 714

See Fan Performance Table1/5

1075115/1/60

CentrifugalDirect - 1

1/55 - 3000115/1/60

1.0No

High Velocity1 - 17x25 - 1in.

2 Round

Aluminized Steel - Type I

20

2 — 452 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

2115/1/60

5.2151/2

H x W x D41-3/4 x 19-1/2 x 30-1/2

139 / 129

NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.

SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.

QUICK HEATING— Durable, cycle tested,heavy gauge aluminized steel heat ex-changer and stainless steel secondary heat exchanger quickly transfer over 90%of the heat to provide warm conditioned air to the structure. Low energy power vent blower, to increase efficiency and provide a positive discharge of gas fumes to the outside as it draws outdoor air in for sealed combus-tion, which means it uses no in-door air for combustion.

BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.

INTEGRATED SYSTEM CONTROL— Ex-clusively designed operational pro-gram pro-vides total control of furnace limit sensors,blowers, gas valve, flame control and in-cludes self diagnostics for ease of service.The built-in, select-able "Cooling Fan Off"feature provides time-delay capability likea BAY24X045 Time-Delay Kit for coolingoperation. Also contains connection pointsfor E.A.C./hu-midifier.

AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).

STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.

FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter

b. Vent proving pressure switch.

Page 3: Ameristar · 2020. 1. 15. · Ameristar Furnaces Furnace M951 Submittal-03/17 M951P040BU24-SUB-1B M951P040BU24-SUB-1A 1 Central Furnace heating designs are certified to ANSI Z21.47

SUBMITTAL

© 2017 Ingersoll Rand

TAG: _________________________________

Upflow/ Horizontal Induced Draft Single Stage Gas Furnace

Ameristar

M951P060BU36AA

M951P060BU36-SUB-1B

FURNACE AIRFLOW (CFM) VS. EXTERNAL STATIC PRESSURE (in. w.c.)

MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90

M951P060BU36AA

4 - 3 -2 -1 -

HIGH - BlackMED.-HIGH - BlueMED.-LOW - YellowLOW - Red

135912321077926

131311991054913

126411611027895

12041116994871

11441065953836

10791004904792

1004934845733

919852768670

812744666570

CFM VS. TEMPERATURE RISE

MODELCubic Feet Per Minute (CFM)

600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800

M951P060BU36AA 59 53 48 44 41 38

1-5/8" HOLE WITH PLUG

1-5/8" HOLE WITH PLUG

7/8" DIA. HOLESELECTRICALCONNECTION

1-1/2" DIA. HOLEGAS CONNECTION

40"

2" DIAMETERFLUE CONNECT

22-1/2"

9-1/2"

1/2"

3-3/4"

19-1/2"

5-5/16"

1/2"

5-1/2"24"

3-1/4"

3/4"

28-1/2"19-5/8"

5/8"

4-9/16"

16-1/4"

28-1/4"

5/8"17-1/2"

16"

3/4"

2-1/16"

7-1/2"

2-1/8"

5/8"1/2"

2-1/4"

20-1/4"

7/8" HOLE WITH PLUGCONDENSATE DRAIN(RIGHT SIDE HOLES ARE ALTERNATIVES)

2" DIAMETEROUTSIDE AIR

1-3/4" X 2-13/32" CUTOUTHORIZONTAL DRAIN

Page 4: Ameristar · 2020. 1. 15. · Ameristar Furnaces Furnace M951 Submittal-03/17 M951P040BU24-SUB-1B M951P040BU24-SUB-1A 1 Central Furnace heating designs are certified to ANSI Z21.47

Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.

Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032

Technical Literature - Printed in U.S.A.

LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes

Mechanical Specifications

AmeristarFurnacesFurnaceM951Submittal-03/17M951P060BU36-SUB-1BM951P060BU36-SUB-1A

1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.AFUE (Upflow / Horizontal)BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)

HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)

M951P060BU36AAUpflow / Horizontal

60,00057,00030 - 60

95.0 / 94.2DIRECT10 x 7

14

See Fan Performance Table1/3

1075115/1/60

CentrifugalDirect - 1

1/15 - 3450115/1/60

1.75No

High Velocity1 - 17x25 - 1in.

2 Round

Aluminized Steel - Type I

20

3 — 453 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

3115/1/60

9.2151/2

H x W x D41-3/4 x 19-1/2 x 30-1/2

150 / 140

NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.

SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.

QUICK HEATING— Durable, cycle tested,heavy gauge aluminized steel heat ex-changer and stainless steel secondary heat exchanger quickly transfer over 90%of the heat to provide warm conditioned air to the structure. Low energy power vent blower, to increase efficiency and provide a positive discharge of gas fumes to the outside as it draws outdoor air in for sealed combus-tion, which means it uses no in-door air for combustion.

BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.

INTEGRATED SYSTEM CONTROL— Ex-clusively designed operational pro-gram pro-vides total control of furnace limit sensors,blowers, gas valve, flame control and in-cludes self diagnostics for ease of service.The built-in, select-able "Cooling Fan Off"feature provides time-delay capability likea BAY24X045 Time-Delay Kit for coolingoperation. Also contains connection pointsfor E.A.C./hu-midifier.

AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).

STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.

FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter

b. Vent proving pressure switch.

Page 5: Ameristar · 2020. 1. 15. · Ameristar Furnaces Furnace M951 Submittal-03/17 M951P040BU24-SUB-1B M951P040BU24-SUB-1A 1 Central Furnace heating designs are certified to ANSI Z21.47

SUBMITTAL

© 2017 Ingersoll Rand

TAG: _________________________________

Upflow/ Horizontal Induced Draft Single Stage Gas Furnace

Ameristar

M951P080BU42AB

M951P080BU42-SUB-1C

FURNACE AIRFLOW (CFM) VS. EXTERNAL STATIC PRESSURE (in. w.c.)

MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90

M951P080BU42AB

4 - 3 -2 -1 -

HIGH - BlackMED.-HIGH - Blue**MED.-LOW - YellowLOW - Red

1646136611751004

161113561159994

157313371145997

153013111130982

147712801108963

142112431081943

136011971045907

12891139993866

12001060929824

** = Factory Set Heat Speed Tap Setting

CFM VS. TEMPERATURE RISE

MODELCubic Feet Per Minute (CFM)

600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900

M951P080BU42AB 64 59 54 50 47 44 41

1-5/8" HOLE WITH PLUG

1-5/8" HOLE WITH PLUG

7/8" DIA. HOLESELECTRICALCONNECTION

1-1/2" DIA. HOLEGAS CONNECTION

40"

2" DIAMETERFLUE CONNECT

22-1/2"

9-1/2"

1/2"

3-3/4"

19-1/2"

5-5/16"

1/2"

5-1/2"24"

3-1/4"

3/4"

28-1/2"19-5/8"

5/8"

4-9/16"

16-1/4"

28-1/4"

5/8"17-1/2"

16"

3/4"

2-1/16"

7-1/2"

2-1/8"

5/8"1/2"

2-1/4"

20-1/4"

7/8" HOLE WITH PLUGCONDENSATE DRAIN(RIGHT SIDE HOLES ARE ALTERNATIVES)

2" DIAMETEROUTSIDE AIR

1-3/4" X 2-13/32" CUTOUTHORIZONTAL DRAIN

Page 6: Ameristar · 2020. 1. 15. · Ameristar Furnaces Furnace M951 Submittal-03/17 M951P040BU24-SUB-1B M951P040BU24-SUB-1A 1 Central Furnace heating designs are certified to ANSI Z21.47

Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.

Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032

Technical Literature - Printed in U.S.A.

LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes

Mechanical Specifications

AmeristarFurnacesFurnaceM951Submittal-03/17M951P080BU42-SUB-1CM951P080BU42-SUB-1B

1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.AFUE (Upflow / Horizontal)BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)MIN VENT — Size (in.)

HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)

M951P080BU42ABUpflow / Horizontal

77,00073,15035 - 65

95.0 / 94.2DIRECT11 x 8

14

See Fan Performance Table1/2

1075115/1/60

CentrifugalDirect - 1

1/20 - 3450115/1/60

0.71No

High Velocity1 - 17x25 - 1in.

2 Round

Aluminized Steel - Type I

20

4 — 454 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

4115/1/60

10.2151/2

H x W x D41-3/4 x 19-1/2 x 30-1/2

158 / 148

NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.

SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.

QUICK HEATING— Durable, cycle tested,heavy gauge aluminized steel heat ex-changer and stainless steel secondary heat exchanger quickly transfer over 90%of the heat to provide warm conditioned air to the structure. Low energy power vent blower, to increase efficiency and provide a positive discharge of gas fumes to the outside as it draws outdoor air in for sealed combus-tion, which means it uses no in-door air for combustion.

BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.

INTEGRATED SYSTEM CONTROL— Ex-clusively designed operational pro-gram pro-vides total control of furnace limit sensors,blowers, gas valve, flame control and in-cludes self diagnostics for ease of service.The built-in, select-able "Cooling Fan Off"feature provides time-delay capability likea BAY24X045 Time-Delay Kit for coolingoperation. Also contains connection pointsfor E.A.C./hu-midifier.

AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).

STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.

FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter

b. Vent proving pressure switch.

Page 7: Ameristar · 2020. 1. 15. · Ameristar Furnaces Furnace M951 Submittal-03/17 M951P040BU24-SUB-1B M951P040BU24-SUB-1A 1 Central Furnace heating designs are certified to ANSI Z21.47

SUBMITTAL

© 2017 Ingersoll Rand

TAG: _________________________________

Upflow/ Horizontal Induced Draft Single Stage Gas Furnace

Ameristar

M951P100CU48AA

M951P100CU48-SUB-1B

FURNACE AIRFLOW (CFM) VS. EXTERNAL STATIC PRESSURE (in. w.c.)

MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90

M951P100CU48AA

4 - 3 -2 -1 -

HIGH - BlackMED.-HIGH - BlueMED.-LOW - YellowLOW - Red

1982189217591593

1912183217121557

1836176516601521

1761169616041485

1679162115361433

1593153814651370

1496144613831294

1389134212751182

1267120511491068

CFM VS. TEMPERATURE RISE

MODELCubic Feet Per Minute (CFM)

1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400

M951P100CU48AA 68 63 59 55 52 49 46 44

7/8" DIA. HOLESELECTRICALCONNECTION

1-1/2" DIA. HOLEGAS CONNECTION

40"

2" DIAMETERFLUE CONNECT

22-1/2"

9-1/2"

1/2"

3-3/4"

19-1/2"

5-5/16"

1/2"

5-1/2"24"

3-1/4"

3/4"

28-1/2"19-5/8"

5/8"

4-9/16"

19-3/4"

28-1/4"

5/8"21"

19-1/2"

3/4"

2-1/16"

9"

2-1/8"

5/8"1/2"

2-1/2"

20-1/4"

3" DIAMETEROUTSIDE AIR

1-5/8" HOLE WITH PLUG

1-5/8" HOLE WITH PLUG

7/8" HOLE WITH PLUGCONDENSATE DRAIN(RIGHT SIDE HOLES ARE ALTERNATIVES)

1-3/4" X 2-13/32" CUTOUTHORIZONTAL DRAIN

Page 8: Ameristar · 2020. 1. 15. · Ameristar Furnaces Furnace M951 Submittal-03/17 M951P040BU24-SUB-1B M951P040BU24-SUB-1A 1 Central Furnace heating designs are certified to ANSI Z21.47

Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.

Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032

Technical Literature - Printed in U.S.A.

LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes

Mechanical Specifications

AmeristarFurnacesFurnaceM951Submittal-03/17M951P100CU48-SUB-1BM951P100CU48-SUB-1A

1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.AFUE (Upflow / Horizontal)BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)

HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)

M951P100CU48AAUpflow / Horizontal

97,00092,15035 - 65

95.0 / 94.2DIRECT10 x 10

14

See Fan Performance Table1/2

1075115/1/60

CentrifugalDirect - 1

1/20 - 3450115/1/60

0.71No

High Velocity1 - 20x25 - 1in.

3 Round

Aluminized Steel - Type I

20

5 — 455 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

5115/1/60

12.5201/2

H x W x D41-3/4 x 23 x 30-1/2

171 / 160

NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.

SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.

QUICK HEATING— Durable, cycle tested,heavy gauge aluminized steel heat ex-changer and stainless steel secondary heat exchanger quickly transfer over 90%of the heat to provide warm conditioned air to the structure. Low energy power vent blower, to increase efficiency and provide a positive discharge of gas fumes to the outside as it draws outdoor air in for sealed combus-tion, which means it uses no in-door air for combustion.

BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.

INTEGRATED SYSTEM CONTROL— Ex-clusively designed operational pro-gram pro-vides total control of furnace limit sensors,blowers, gas valve, flame control and in-cludes self diagnostics for ease of service.The built-in, select-able "Cooling Fan Off"feature provides time-delay capability likea BAY24X045 Time-Delay Kit for coolingoperation. Also contains connection pointsfor E.A.C./hu-midifier.

AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).

STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.

FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter

b. Vent proving pressure switch.

Page 9: Ameristar · 2020. 1. 15. · Ameristar Furnaces Furnace M951 Submittal-03/17 M951P040BU24-SUB-1B M951P040BU24-SUB-1A 1 Central Furnace heating designs are certified to ANSI Z21.47

SUBMITTAL

© 2017 Ingersoll Rand

TAG: _________________________________

Upflow/ Horizontal Induced Draft Single Stage Gas Furnace

Ameristar

M951P100DU60AA

M951P100DU60-SUB-1B

FURNACE AIRFLOW (CFM) VS. EXTERNAL STATIC PRESSURE (in. w.c.)

MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90

M951P100DU60AA

4 - 3 -2 -1 -

HIGH - BlackMED.-HIGH - BlueMED.-LOW - YellowLOW - Red

2339204517191436

2287202117031430

2235199616931430

2168194716711414

2100189716491398

2021183616071372

1941177415651344

1858170114981287

1773162914311230

CFM VS. TEMPERATURE RISE

MODELCubic Feet Per Minute (CFM)

1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400

M951P100DU60AA 68 63 59 55 52 49 46 44 42 40 38 37

7/8" DIA. HOLESELECTRICALCONNECTION

1-1/2" DIA. HOLEGAS CONNECTION

40"

2" DIAMETERFLUE CONNECT

22-1/2"

9-1/2"

1/2"

3-3/4"

19-1/2"

5-5/16"

1/2"

5-1/2"24"

3-1/4"

3/4"

28-1/2"19-5/8"

5/8"

4-9/16"

23-1/4"

28-1/4"

5/8"24-1/2"

23"

3/4"

2-1/16"

10"

2-1/8"

5/8"1/2"

2-15/16"

20-1/4"

3" DIAMETEROUTSIDE AIR

1-5/8" HOLE WITH PLUG

1-5/8" HOLE WITH PLUG

7/8" HOLE WITH PLUGCONDENSATE DRAIN(RIGHT SIDE HOLES ARE ALTERNATIVES)

1-3/4" X 2-13/32" CUTOUTHORIZONTAL DRAIN

Page 10: Ameristar · 2020. 1. 15. · Ameristar Furnaces Furnace M951 Submittal-03/17 M951P040BU24-SUB-1B M951P040BU24-SUB-1A 1 Central Furnace heating designs are certified to ANSI Z21.47

Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.

Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032

Technical Literature - Printed in U.S.A.

LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes

Mechanical Specifications

AmeristarFurnacesFurnaceM951Submittal-03/17M951P100DU60-SUB-1BM951P100DU60-SUB-1A

1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.AFUE (Upflow / Horizontal)BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)

HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)

M951P100DU60AAUpflow / Horizontal

97,00092,15035 - 65

95.0 / 94.2DIRECT11 x 10

14

See Fan Performance Table3/4

1100115/1/60

CentrifugalDirect - 1

1/20 - 3450115/1/60

0.71No

High Velocity1 - 24x25 - 1in.

3 Round

Aluminized Steel - Type I

20

5 — 455 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

5115/1/60

12.920 1/2

H x W x D41-3/4 x 26-1/2 x 30-1/2

197 / 185

NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.

SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.

QUICK HEATING— Durable, cycle tested,heavy gauge aluminized steel heat ex-changer and stainless steel secondary heat exchanger quickly transfer over 90%of the heat to provide warm conditioned air to the structure. Low energy power vent blower, to increase efficiency and provide a positive discharge of gas fumes to the outside as it draws outdoor air in for sealed combus-tion, which means it uses no in-door air for combustion.

BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.

INTEGRATED SYSTEM CONTROL— Ex-clusively designed operational pro-gram pro-vides total control of furnace limit sensors,blowers, gas valve, flame control and in-cludes self diagnostics for ease of service.The built-in, select-able "Cooling Fan Off"feature provides time-delay capability likea BAY24X045 Time-Delay Kit for coolingoperation. Also contains connection pointsfor E.A.C./hu-midifier.

AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).

STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.

FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter

b. Vent proving pressure switch.

Page 11: Ameristar · 2020. 1. 15. · Ameristar Furnaces Furnace M951 Submittal-03/17 M951P040BU24-SUB-1B M951P040BU24-SUB-1A 1 Central Furnace heating designs are certified to ANSI Z21.47

SUBMITTAL

© 2017 Ingersoll Rand

TAG: _________________________________

Upflow/ Horizontal Induced Draft Single Stage Gas Furnace

Ameristar

M951P120DU60AA

M951P120DU60-SUB-1B

FURNACE AIRFLOW (CFM) VS. EXTERNAL STATIC PRESSURE (in. w.c.)

MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90

M951P120DU60AA

4 - 3 -2 -1 -

HIGH - BlackMED.-HIGH - BlueMED.-LOW - YellowLOW - Red

2380204216951402

2334202916901404

2287201616841406

2241198416681397

2193195216521387

2118189216271358

2043183016011328

1956177115451285

1870171214891242

CFM VS. TEMPERATURE RISE

MODELCubic Feet Per Minute (CFM)

1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400

M951P120DU60AA 70 66 62 59 56 53 50 48 46 44

7/8" DIA. HOLESELECTRICALCONNECTION

1-1/2" DIA. HOLEGAS CONNECTION

40"

2" DIAMETERFLUE CONNECT

22-1/2"

9-1/2"

1/2"

3-3/4"

19-1/2"

5-5/16"

1/2"

5-1/2"24"

3-1/4"

3/4"

28-1/2"19-5/8"

5/8"

4-9/16"

23-1/4"

28-1/4"

5/8"24-1/2"

23"

3/4"

2-1/16"

10"

2-1/8"

5/8"1/2"

2-15/16"

20-1/4"

3" DIAMETEROUTSIDE AIR

1-5/8" HOLE WITH PLUG

1-5/8" HOLE WITH PLUG

7/8" HOLE WITH PLUGCONDENSATE DRAIN(RIGHT SIDE HOLES ARE ALTERNATIVES)

1-3/4" X 2-13/32" CUTOUTHORIZONTAL DRAIN

Page 12: Ameristar · 2020. 1. 15. · Ameristar Furnaces Furnace M951 Submittal-03/17 M951P040BU24-SUB-1B M951P040BU24-SUB-1A 1 Central Furnace heating designs are certified to ANSI Z21.47

Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.

Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032

Technical Literature - Printed in U.S.A.

LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes

Mechanical Specifications

AmeristarFurnacesFurnaceM951Submittal-03/17M951P120DU60-SUB-1BM951P120DU60-SUB-1A

1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.AFUE (Upflow / Horizontal)BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)

HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)

M951P120DU60AAUpflow / Horizontal

110,000104,50040 - 70

95.0 / 94.2DIRECT11 x 10

14

See Fan Performance Table3/4

1100115/1/60

CentrifugalDirect - 1

1/20 - 3450115/1/60

0.71No

High Velocity1 - 24x25 - 1in.

3 Round

Aluminized Steel - Type I

20

6 — 456 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

6115/1/60

12.9201/2

H x W x D41-3/4 x 26-1/2 x 30-1/2

205 / 193

NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.

SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.

QUICK HEATING— Durable, cycle tested,heavy gauge aluminized steel heat ex-changer and stainless steel secondary heat exchanger quickly transfer over 90%of the heat to provide warm conditioned air to the structure. Low energy power vent blower, to increase efficiency and provide a positive discharge of gas fumes to the outside as it draws outdoor air in for sealed combus-tion, which means it uses no in-door air for combustion.

BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.

INTEGRATED SYSTEM CONTROL— Ex-clusively designed operational pro-gram pro-vides total control of furnace limit sensors,blowers, gas valve, flame control and in-cludes self diagnostics for ease of service.The built-in, select-able "Cooling Fan Off"feature provides time-delay capability likea BAY24X045 Time-Delay Kit for coolingoperation. Also contains connection pointsfor E.A.C./hu-midifier.

AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).

STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.

FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter

b. Vent proving pressure switch.

Page 13: Ameristar · 2020. 1. 15. · Ameristar Furnaces Furnace M951 Submittal-03/17 M951P040BU24-SUB-1B M951P040BU24-SUB-1A 1 Central Furnace heating designs are certified to ANSI Z21.47

SUBMITTAL

© 2015 Ingersoll Rand

TAG: _________________________________

Downflow/ Horizontal Induced Draft Single Stage Gas Furnace

Ameristar

M951P040BD24AA

M951P040BD24-SUB-1A

CFM VS. TEMPERATURE RISE

MODELCubic Feet Per Minute (CFM)

600 700 800 900 1000 1100 1200 1300 1400 1500

M951P040BD24AA 59 50 44 39 35

FURNACE AIRFLOW (CFM) VS. EXTERNAL STATIC PRESSURE (in. w.c.)

MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90

M951P040BD24AA

4 - 3 -2 -1 -

HIGH - BlackMED.-HIGH - BlueMED.-LOW - YellowLOW - Red

998856753647

965832728617

922797694581

870751650538

807695596490

735628533435

653550460375

561462378308

459363286235

7/8" DIA. ELECTRICALCONNECTION(ALTERNATE)

1-1/2" DIA. GASCONNECTION(ALTERNATE)

7/8" DIA. HOLESELECTRICALCONNECTION

1-5/8" HOLE WITH PLUG

GAS CONNECTION (ALT)

40"

20-1/4"

10"

3-3/8"

1/2"

19"

3/4"

19-5/8"

5/8"

4-1/8"

16-1/4"

17-1/2"

16" 3/4"

17-1/4"

2-1/8"

2-1/8"

5/8"2" DIAMETERFLUE CONNECT

2-1/4"3" OPENINGAIR INTAKE

3" CONNECTION

AIR INTAKE

4-9/16"

7-3/8"

7-3/8"

2-1/16" 25"

1-5/8” HOLEWITH PLUG

1-5/8" HOLE WITH PLUG

CONDENSATE DRAIN

1/2"

5"

5-1/2"

3-3/8"

5-5/16"

8-1/4"

10"

31"

28"

12-3/8"3-7/8"

1-3/4” X 2-13/32 CUTOUTHORIZONTAL DRAIN

1-5/8" HOLE WITH PLUG

1-5/8” HOLEWITH PLUG

7/8” HOLEWITH PLUG

Page 14: Ameristar · 2020. 1. 15. · Ameristar Furnaces Furnace M951 Submittal-03/17 M951P040BU24-SUB-1B M951P040BU24-SUB-1A 1 Central Furnace heating designs are certified to ANSI Z21.47

Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.

Ingersoll-Rand Company

ameristarac.com

Technical Literature - Printed in U.S.A.

LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes

Mechanical Specifications

AmeristarFurnacesFurnaceM951Submittal-05/15M951P040BD24-SUB-1AM951P040BD24-SUB-1

1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.

SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.

QUICK HEATING— Durable, cycle tested,heavy gauge aluminized steel heat ex-changer and stainless steel secondary heat exchanger quickly transfer over 90%of the heat to provide warm conditioned air to the structure. Low energy power vent blower, to increase efficiency and provide a positive discharge of gas fumes to the outside as it draws outdoor air in for sealed combus-tion, which means it uses no in-door air for combustion.

BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.

INTEGRATED SYSTEM CONTROL— Ex-clusively designed operational pro-gram pro-vides total control of furnace limit sensors,blowers, gas valve, flame control and in-cludes self diagnostics for ease of service.The built-in, select-able "Cooling Fan Off"feature provides time-delay capability likea BAY24X045 Time-Delay Kit for coolingoperation. Also contains connection pointsfor E.A.C./hu-midifier.

AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).

STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.

FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter

b. Vent proving pressure switch.

PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)

HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)

M951P040BD24AADownflow / Horizontal

40,00038,00030 - 60

DIRECT10 x 7

14

See Fan Performance Table1/5

1080115/1/60

CentrifugalDirect - 1

1/55 - 3000115/1/60

1.14No

High Velocity2 - 14x20 - 1in.

2 Round

Aluminized Steel - Type I

20

2 — 452 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

2115/1/60

4.815 1/2

H x W x D41-3/4 x 19-1/2 x 30-1/2

145 / 135

Page 15: Ameristar · 2020. 1. 15. · Ameristar Furnaces Furnace M951 Submittal-03/17 M951P040BU24-SUB-1B M951P040BU24-SUB-1A 1 Central Furnace heating designs are certified to ANSI Z21.47

SUBMITTAL

© 2015 Ingersoll Rand

TAG: _________________________________

Downflow/ Horizontal Induced Draft Single Stage Gas Furnace

Ameristar

M951P065BD42AA

M951P065BD42-SUB-1A

CFM VS. TEMPERATURE RISE

MODELCubic Feet Per Minute (CFM)

600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700

M951P065BD42AA 75 66 59 53 48 44 41 38 35

FURNACE AIRFLOW (CFM) VS. EXTERNAL STATIC PRESSURE (in. w.c.)

MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90

M951P065BD42AA

4 - 3 -2 -1 -

HIGH - BlackMED.-HIGH - BlueMED.-LOW - YellowLOW - Red

1501144213461225

1453139313081197

1402134112631160

1344128512121116

1283122711551062

1216116610921001

114511031024931

10681037950853

986968869766

7/8" DIA. ELECTRICALCONNECTION(ALTERNATE)

1-1/2" DIA. GASCONNECTION(ALTERNATE)

7/8" DIA. HOLESELECTRICALCONNECTION

1-5/8" HOLE WITH PLUG

GAS CONNECTION (ALT)

40"

20-1/4"

10"

3-3/8"

1/2"

19"

3/4"

19-5/8"

5/8"

4-1/8"

16-1/4"

17-1/2"

16" 3/4"

17-1/4"

2-1/8"

2-1/8"

5/8"2" DIAMETERFLUE CONNECT

2-1/4"3" OPENINGAIR INTAKE

3" CONNECTION

AIR INTAKE

4-9/16"

7-3/8"

7-3/8"

2-1/16" 25"

1-5/8” HOLEWITH PLUG

1-5/8" HOLE WITH PLUG

CONDENSATE DRAIN

1/2"

5"

5-1/2"

3-3/8"

5-5/16"

8-1/4"

10"

31"

28"

12-3/8"3-7/8"

1-3/4” X 2-13/32 CUTOUTHORIZONTAL DRAIN

1-5/8" HOLE WITH PLUG

1-5/8” HOLEWITH PLUG

7/8” HOLEWITH PLUG

Page 16: Ameristar · 2020. 1. 15. · Ameristar Furnaces Furnace M951 Submittal-03/17 M951P040BU24-SUB-1B M951P040BU24-SUB-1A 1 Central Furnace heating designs are certified to ANSI Z21.47

Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.

Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032

Technical Literature - Printed in U.S.A.

LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes

Mechanical Specifications

AmeristarFurnacesFurnaceM951Submittal-05/15M951P065BD42-SUB-1AM951P065BD42-SUB-1

1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)

HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)

M951P065BD42AADownflow / Horizontal

60,00057,00025 - 55

DIRECT11 x 8

14

See Fan Performance Table1/2

1075115/1/60

CentrifugalDirect - 1

1/25 - 3200115/1/60

1.35No

High Velocity2 - 14x20 - 1in.

2 Round

Aluminized Steel - Type I

20

4 — 484 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

4115/1/60

11.4151/2

H x W x D41-3/4 x 19-1/2 x 30-1/2

158 / 148

NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.

SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.

QUICK HEATING— Durable, cycle tested,heavy gauge aluminized steel heat ex-changer and stainless steel secondary heat exchanger quickly transfer over 90%of the heat to provide warm conditioned air to the structure. Low energy power vent blower, to increase efficiency and provide a positive discharge of gas fumes to the outside as it draws outdoor air in for sealed combus-tion, which means it uses no in-door air for combustion.

BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.

INTEGRATED SYSTEM CONTROL— Ex-clusively designed operational pro-gram pro-vides total control of furnace limit sensors,blowers, gas valve, flame control and in-cludes self diagnostics for ease of service.The built-in, select-able "Cooling Fan Off"feature provides time-delay capability likea BAY24X045 Time-Delay Kit for coolingoperation. Also contains connection pointsfor E.A.C./hu-midifier.

AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).

STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.

FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter

b. Vent proving pressure switch.

Page 17: Ameristar · 2020. 1. 15. · Ameristar Furnaces Furnace M951 Submittal-03/17 M951P040BU24-SUB-1B M951P040BU24-SUB-1A 1 Central Furnace heating designs are certified to ANSI Z21.47

SUBMITTAL

© 2015 Ingersoll Rand

TAG: _________________________________

Downflow/ Horizontal Induced Draft Single Stage Gas Furnace

Ameristar

M951P085CD48AA

M951P085CD48-SUB-1A

CFM VS. TEMPERATURE RISE

MODELCubic Feet Per Minute (CFM)

900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200

M951P085CD48AA 70 64 59 54 50 47 44 41 39 37

FURNACE AIRFLOW (CFM) VS. EXTERNAL STATIC PRESSURE (in. w.c.)

MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90

M951P085CD48AA

4 - 3 -2 -1 -

HIGH - BlackMED.-HIGH - BlueMED.-LOW - YellowLOW - Red

1835172615811401

1772167415391374

1709162214981346

1637155714401308

1566149213831269

1485141613211209

1405134012581148

1313125211721075

1222116410851001

7/8" DIA. ELECTRICALCONNECTION(ALTERNATE)

1-1/2" DIA. GASCONNECTION(ALTERNATE)

7/8" DIA. HOLESELECTRICALCONNECTION

1-5/8" HOLE WITH PLUG

GAS CONNECTION (ALT)

40"

20-1/4"

10"

3-3/8"

1/2"

19"

3/4"

19-5/8"

5/8"

4-1/8"

19-3/4"

21"

19-1/2" 3/4"

17-1/4"

2-1/8"

2-1/8"

5/8"2" DIAMETERFLUE CONNECT

2-1/2"3" OPENINGAIR INTAKE

3" CONNECTION

AIR INTAKE

4-9/16"

7-3/8"

7-3/8"

2-1/16" 25"

1-5/8” HOLEWITH PLUG

1-5/8" HOLE WITH PLUG

CONDENSATE DRAIN

1/2"

5"

5-1/2"

3-3/8"

5-5/16"

8-1/4"

10"

31"

28"

12-3/8"3-7/8"

1-3/4” X 2-13/32 CUTOUTHORIZONTAL DRAIN

1-5/8" HOLE WITH PLUG

1-5/8” HOLEWITH PLUG

7/8” HOLEWITH PLUG

Page 18: Ameristar · 2020. 1. 15. · Ameristar Furnaces Furnace M951 Submittal-03/17 M951P040BU24-SUB-1B M951P040BU24-SUB-1A 1 Central Furnace heating designs are certified to ANSI Z21.47

Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.

Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032

Technical Literature - Printed in U.S.A.

LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes

Mechanical Specifications

AmeristarFurnacesFurnaceM951Submittal-05/15M951P085CD48-SUB-1AM951P085CD48-SUB-1

1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)

HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)

M951P085CD48AADownflow / Horizontal

80,00076,00030 - 60

DIRECT11 x 10

14

See Fan Performance Table1/2

1075115/1/60

CentrifugalDirect - 1

1/20 - 3450115/1/60

0.71No

High Velocity2 - 16x20 - 1in.

2.5 Round

Aluminized Steel - Type I

20

5 — 485 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

5115/1/60

12.520 1/2

H x W x D41-3/4 x 23 x 30-1/2

171 / 160

NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.

SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.

QUICK HEATING— Durable, cycle tested,heavy gauge aluminized steel heat ex-changer and stainless steel secondary heat exchanger quickly transfer over 90%of the heat to provide warm conditioned air to the structure. Low energy power vent blower, to increase efficiency and provide a positive discharge of gas fumes to the outside as it draws outdoor air in for sealed combus-tion, which means it uses no in-door air for combustion.

BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.

INTEGRATED SYSTEM CONTROL— Ex-clusively designed operational pro-gram pro-vides total control of furnace limit sensors,blowers, gas valve, flame control and in-cludes self diagnostics for ease of service.The built-in, select-able "Cooling Fan Off"feature provides time-delay capability likea BAY24X045 Time-Delay Kit for coolingoperation. Also contains connection pointsfor E.A.C./hu-midifier.

AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).

STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.

FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter

b. Vent proving pressure switch.

Page 19: Ameristar · 2020. 1. 15. · Ameristar Furnaces Furnace M951 Submittal-03/17 M951P040BU24-SUB-1B M951P040BU24-SUB-1A 1 Central Furnace heating designs are certified to ANSI Z21.47

SUBMITTAL

© 2015 Ingersoll Rand

TAG: _________________________________

Downflow/ Horizontal Induced Draft Single Stage Gas Furnace

Ameristar

M951P110DD60AA

M951P110DD60-SUB-1A

CFM VS. TEMPERATURE RISE

MODELCubic Feet Per Minute (CFM)

1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200

M951P110DD60AA 88 81 74 69 65 60 57 54 51 48 46

FURNACE AIRFLOW (CFM) VS. EXTERNAL STATIC PRESSURE (in. w.c.)

MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90

M951P110DD60AA

4 - 3 -2 -1 -

HIGH - BlackMED.-HIGH - BlueMED.-LOW - YellowLOW - Red

2147199517121424

2074194016811408

2000188516491392

1941182716021367

1881176715551341

1807169915051296

1732163114551251

1655154713811188

1576146213071124

7/8" DIA. ELECTRICALCONNECTION(ALTERNATE)

1-1/2" DIA. GASCONNECTION(ALTERNATE)

7/8" DIA. HOLESELECTRICALCONNECTION

1-5/8" HOLE WITH PLUG

GAS CONNECTION (ALT)

40"

20-1/4"

10"

3-3/8"

1/2"

19"

3/4"

19-5/8"

5/8"

4-1/8"

23-1/4"

24-1/2"

23" 3/4"

17-1/4"

2-1/8"

2-1/8"

5/8"2" DIAMETERFLUE CONNECT

2-5/16"

3" OPENINGAIR INTAKE

3" CONNECTION

AIR INTAKE

4-9/16"

7-3/8"

7-3/8"

2-1/16" 25"

1-5/8” HOLEWITH PLUG

1-5/8" HOLE WITH PLUG

CONDENSATE DRAIN

1/2"

5"

5-1/2"

3-3/8"

5-5/16"

8-1/4"

10"

31"

28"

12-3/8"3-7/8"

1-3/4” X 2-13/32 CUTOUTHORIZONTAL DRAIN

1-5/8" HOLE WITH PLUG

1-5/8” HOLEWITH PLUG

7/8” HOLEWITH PLUG

Page 20: Ameristar · 2020. 1. 15. · Ameristar Furnaces Furnace M951 Submittal-03/17 M951P040BU24-SUB-1B M951P040BU24-SUB-1A 1 Central Furnace heating designs are certified to ANSI Z21.47

Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.

Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032

Technical Literature - Printed in U.S.A.

LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes

Mechanical Specifications

AmeristarFurnacesFurnaceM951Submittal-05/15M951P110DD60-SUB-1AM951P110DD60-SUB-1

1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)

HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)

M951P110DD60AADownflow / Horizontal

110,000104,50035 - 65

DIRECT11 x 10

14

See Fan Performance Table3/4

1100115/1/60

CentrifugalDirect - 1

1/20 - 3450115/1/60

0.71No

High Velocity2 - 16x20 - 1in.

2.5 Round

Aluminized Steel - Type I

20

6 — 486 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

6115/1/60

12.9201/2

H x W x D41-3/4 x 26-1/2 x 30-1/2

205 / 193

NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.

SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.

QUICK HEATING— Durable, cycle tested,heavy gauge aluminized steel heat ex-changer and stainless steel secondary heat exchanger quickly transfer over 90%of the heat to provide warm conditioned air to the structure. Low energy power vent blower, to increase efficiency and provide a positive discharge of gas fumes to the outside as it draws outdoor air in for sealed combus-tion, which means it uses no in-door air for combustion.

BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.

INTEGRATED SYSTEM CONTROL— Ex-clusively designed operational pro-gram pro-vides total control of furnace limit sensors,blowers, gas valve, flame control and in-cludes self diagnostics for ease of service.The built-in, select-able "Cooling Fan Off"feature provides time-delay capability likea BAY24X045 Time-Delay Kit for coolingoperation. Also contains connection pointsfor E.A.C./hu-midifier.

AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).

STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.

FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter

b. Vent proving pressure switch.