SUBMITTAL © 2015 Ingersoll Rand TAG: _________________________________ Upflow/ Horizontal Induced Draft Single Stage Gas Furnace Ameristar M801P040AU24AA M801P040AU24-SUB-1A FURNACE AIRFLOW (CFM) VS. EXTERNAL STATIC PRESSURE (IN. W.C.) MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 M801P040AU24AA 4-HIGH - Black 3-MED - HIGH - Blue 2-MED - LOW - Yellow 1-LOW - Red 1018 847 716 617 1004 832 701 599 982 809 678 575 950 779 648 544 910 742 610 507 860 697 585 463 802 644 512 413 763 585 452 357 660 517 384 294 CFM VS. TEMPERATURE RISE MODEL CFM (CUBIC FEET PER MINUTE) 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 M801P040AU24AA 54 49 42 37 33 30 7/8" DIA. HOLES ELECTRICAL CONNECTION 1-1/2" DIA. HOLE GAS CONNECTION 40" 1/2" 3-3/4" 28-1/4" 5-5/16" 3/8" 2-1/8" 23-1/2" 3-13/16" 3/4" 28-3/8" 19-5/8" 5/8" 4-1/16" 13-1/4" 22-1/2" 28-1/4" 8-1/4" 5/8" 14-1/2" 13" 3/4" 3/4" 3-15/16" 9-5/8" 5/8" 2-1/16" 4" DIAMETER FLUE CONNECT 2-1/16" 1/2" Ø 7/8” HOLE WITH PLUG ELECTRICAL CONNECTION (ALTERNATE) Ø 1-5/8” HOLE WITH PLUG (2)

Transcript of Ameristar · 2019-03-11 · Since the manufacturer has a policy of continuous product and product...

Page 1: Ameristar · 2019-03-11 · Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without

SUBMITTAL

© 2015 Ingersoll Rand

TAG: _________________________________

Upflow/ Horizontal Induced Draft Single Stage Gas Furnace

Ameristar

M801P040AU24AA

M801P040AU24-SUB-1A

FURNACE AIRFLOW (CFM) VS. EXTERNAL STATIC PRESSURE (IN. W.C.)

MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90

M801P040AU24AA

4-HIGH - Black3-MED - HIGH - Blue2-MED - LOW - Yellow1-LOW - Red

1018847716617

1004832701599

982809678575

950779648544

910742610507

860697585463

802644512413

763585452357

660517384294

CFM VS. TEMPERATURE RISE

MODELCFM (CUBIC FEET PER MINUTE)

500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800

M801P040AU24AA 54 49 42 37 33 30

7/8" DIA. HOLESELECTRICALCONNECTION

1-1/2" DIA. HOLEGAS CONNECTION

40"

1/2"

3-3/4"

28-1/4"

5-5/16"

3/8"

2-1/8"

23-1/2"

3-13/16"

3/4"

28-3/8"19-5/8"

5/8"

4-1/16"

13-1/4"

22-1/2"

28-1/4"

8-1/4"

5/8"14-1/2"

13"

3/4"

3/4"

3-15/16"

9-5/8"

5/8"

2-1/16"

4" DIAMETERFLUE CONNECT

2-1/16"

1/2"

Ø 7/8” HOLE WITH PLUGELECTRICAL CONNECTION(ALTERNATE)

Ø 1-5/8” HOLE WITH PLUG (2)

Page 2: Ameristar · 2019-03-11 · Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without

Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.

Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032

Technical Literature - Printed in U.S.A.

LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes

Mechanical Specifications

AmeristarFurnacesFurnaceM801Submittal-05/15M801P040AU24-SUB-1AM801P040AU24-SUB-1

1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.

SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.

QUICK HEATING— Durable, cycle tested, heavy gauge aluminized steel heat exchanger quickly transfers heat to provide warm conditioned air to the struc-ture. Low energy power vent blower, to increase efficiency and provide discharge of gas fumes to the outside, allows com-mon venting with hot water heater.

BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.

INTEGRATED SYSTEM CONTROL - Exclusively designed operational program provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self diagnostics for ease of service.

AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).

STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.

FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter

b. Vent proving pressure switch.

PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)

M801P040AU24AAUpflow / Horizontal

40,00031,00030 - 60Direct10 x 6

14

See Fan Performance Table1/5

1080115/1/60

CentrifugalDirect - 1

1/50 - 3180115/1/60

1.09No

High Velocity1 - 16x25 - 1 in.

4 Round

HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)

Alum. Steel-

20

2 — 452 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

2115/1/60

5.4151/2

H x W x D41-3/4 x 16-1/2 x 30-1/2

119 / 110

Page 3: Ameristar · 2019-03-11 · Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without

SUBMITTAL

© 2015 Ingersoll Rand

TAG: _________________________________

Upflow/ Horizontal Induced Draft Single Stage Gas Furnace

Ameristar

M801P060AU24AA

M801P060AU24-SUB-1A

FURNACE AIRFLOW (CFM) VS. EXTERNAL STATIC PRESSURE (IN. W.C.)

MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90

M801P060AU24AA

4-HIGH - Black3-MED - HIGH - Blue2-MED - LOW - Yellow1-LOW - Red

1018835712611

997821702596

973800683573

941771655543

901734617505

852689571459

796636516406

731575452345

659506379277

CFM VS. TEMPERATURE RISE

MODELCFM (CUBIC FEET PER MINUTE)

500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600

M801P060AU24AA 63 56 49 44

7/8" DIA. HOLESELECTRICALCONNECTION

1-1/2" DIA. HOLEGAS CONNECTION

40"

1/2"

3-3/4"

28-1/4"

5-5/16"

3/8"

2-1/8"

23-1/2"

3-13/16"

3/4"

28-3/8"19-5/8"

5/8"

4-1/16"

13-1/4"

22-1/2"

28-1/4"

8-1/4"

5/8"14-1/2"

13"

3/4"

3/4"

3-15/16"

9-5/8"

5/8"

2-1/16"

4" DIAMETERFLUE CONNECT

2-1/16"

1/2"

Ø 7/8” HOLE WITH PLUGELECTRICAL CONNECTION(ALTERNATE)

Ø 1-5/8” HOLE WITH PLUG (2)

Page 4: Ameristar · 2019-03-11 · Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without

Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.

Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032

Technical Literature - Printed in U.S.A.

LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes

Mechanical Specifications

AmeristarFurnacesFurnaceM801Submittal-05/15M801P060AU24-SUB-1AM801P060AU24-SUB-1

1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.

SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.

QUICK HEATING— Durable, cycle tested, heavy gauge aluminized steel heat exchanger quickly transfers heat to provide warm conditioned air to the struc-ture. Low energy power vent blower, to increase efficiency and provide discharge of gas fumes to the outside, allows com-mon venting with hot water heater.

BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.

INTEGRATED SYSTEM CONTROL - Exclusively designed operational program provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self diagnostics for ease of service.

AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).

STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.

FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter

b. Vent proving pressure switch.

PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)

M801P060AU24AAUpflow / Horizontal

60,00047,00030 - 60Direct

10 x 6**14

See Fan Performance Table1/3

1075115/1/60

CentrifugalDirect - 1

1/50 - 3180115/1/60

1.09No

High Velocity1 - 16x25 - 1 in.

4 Round

HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)

Alum. Steel

20

3 — 453 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

3115/1/60

9.0151/2

H x W x D41-3/4 x 16-1/2 x 30-1/2

127 / 118

Page 5: Ameristar · 2019-03-11 · Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without

SUBMITTAL

© 2015 Ingersoll Rand

TAG: _________________________________

Upflow/ Horizontal Induced Draft Single Stage Gas Furnace

Ameristar

M801P060AU36AA

M801P060AU36-SUB-1A

FURNACE AIRFLOW (CFM) VS. EXTERNAL STATIC PRESSURE (IN. W.C.)

MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90

M801P060AU36AA

4-HIGH - Black3-MED - HIGH - Blue2-MED - LOW - Yellow1-LOW - Red

142612431042900

138912251039903

134511971027895

129811601005877

12361113973848

11711057931809

1099991879760

1020916817700

934831745629

CFM VS. TEMPERATURE RISE

MODELCFM (CUBIC FEET PER MINUTE)

500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700

M801P060AU36AA 56 49 44 40 37 34 32

7/8" DIA. HOLESELECTRICALCONNECTION

1-1/2" DIA. HOLEGAS CONNECTION

40"

1/2"

3-3/4"

28-1/4"

5-5/16"

3/8"

2-1/8"

23-1/2"

3-13/16"

3/4"

28-3/8"19-5/8"

5/8"

4-1/16"

13-1/4"

22-1/2"

28-1/4"

8-1/4"

5/8"14-1/2"

13"

3/4"

3/4"

3-15/16"

9-5/8"

5/8"

2-1/16"

4" DIAMETERFLUE CONNECT

2-1/16"

1/2"

Ø 7/8” HOLE WITH PLUGELECTRICAL CONNECTION(ALTERNATE)

Ø 1-5/8” HOLE WITH PLUG (2)

Page 6: Ameristar · 2019-03-11 · Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without

Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.

Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032

Technical Literature - Printed in U.S.A.

LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes

Mechanical Specifications

AmeristarFurnacesFurnaceM801Submittal-05/15M801P060AU36-SUB-1AM801P060AU36-SUB-1

1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.

SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.

QUICK HEATING— Durable, cycle tested, heavy gauge aluminized steel heat exchanger quickly transfers heat to provide warm conditioned air to the struc-ture. Low energy power vent blower, to increase efficiency and provide discharge of gas fumes to the outside, allows com-mon venting with hot water heater.

BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.

INTEGRATED SYSTEM CONTROL - Exclusively designed operational program provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self diagnostics for ease of service.

AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).

STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.

FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter

b. Vent proving pressure switch.

PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)

M801P060AU36AAUpflow / Horizontal

60,00047,00030 - 60Direct

10 x 6**14

See Fan Performance Table1/3

1075115/1/60

CentrifugalDirect - 1

1/50 - 3180115/1/60

1.09No

High Velocity1 - 16x25 - 1 in.

4 Round

HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)

Alum. Steel

20

3 — 453 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

3115/1/60

9.0151/2

H x W x D41-3/4 x 16-1/2 x 30-1/2

127 / 118

Page 7: Ameristar · 2019-03-11 · Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without

SUBMITTAL

© 2015 Ingersoll Rand

TAG: _________________________________

Upflow/ Horizontal Induced Draft Single Stage Gas Furnace

Ameristar

M801P080BU36AA

M801P080BU36-SUB-1A

FURNACE AIRFLOW (CFM) VS. EXTERNAL STATIC PRESSURE (IN. W.C.)

MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90

M801P080BU36AA

4-HIGH - Black3-MED - HIGH - Blue2-MED - LOW - Yellow1-LOW - Red

1393 1210 1046 900

1384 1209 1052 903

136411981047895

133511771033888

129611471008869

12471107973842

11891058928808

1120999873766

1042930808717

CFM VS. TEMPERATURE RISE

MODELCFM (CUBIC FEET PER MINUTE)

500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600

M801P080BU36AA 59 54 49 46 42

7/8" DIA. HOLESELECTRICALCONNECTION

1-1/2" DIA. HOLEGAS CONNECTION

40"

1/2"

3-3/4"

28-1/4"

5-5/16"

3/8"

2-1/8"

23-1/2"

3-13/16"

3/4"

28-3/8"19-5/8"

5/8"

4-1/16"

16-1/4"

22-1/2"

28-1/4"

8-1/4"

5/8"17-1/2"

16"

3/4"

3/4"

3-15/16"

9-5/8"

5/8"

2-1/16"

4" DIAMETERFLUE CONNECT

2-1/16"

1/2"

Ø 7/8” HOLE WITH PLUGELECTRICAL CONNECTION(ALTERNATE)

Ø 1-5/8” HOLE WITH PLUG (2)

Page 8: Ameristar · 2019-03-11 · Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without

Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.

Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032

Technical Literature - Printed in U.S.A.

LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes

Mechanical Specifications

AmeristarFurnacesFurnaceM801Submittal-05/15M801P080BU36-SUB-1AM801P080BU36-SUB-1

1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.

SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.

QUICK HEATING— Durable, cycle tested, heavy gauge aluminized steel heat exchanger quickly transfers heat to provide warm conditioned air to the struc-ture. Low energy power vent blower, to increase efficiency and provide discharge of gas fumes to the outside, allows com-mon venting with hot water heater.

BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.

INTEGRATED SYSTEM CONTROL - Exclusively designed operational program provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self diagnostics for ease of service.

AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).

STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.

FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter

b. Vent proving pressure switch.

PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)

M801P080BU36AAUpflow / Horizontal

80,00063,00030 - 60Direct10 x 7

14

See Fan Performance Table1/3

1075115/1/60

CentrifugalDirect - 1

1/50 - 3180115/1/60

1.09No

High Velocity1 - 17x25 - 1 in.

4 Round

HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)

Alum. Steel

20

4 — 454 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

4115/1/60

9.0151/2

H x W x D41-3/4 x 19-1/2 x 30-1/2

142 / 132

Page 9: Ameristar · 2019-03-11 · Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without

SUBMITTAL

© 2015 Ingersoll Rand

TAG: _________________________________

Upflow/ Horizontal Induced Draft Single Stage Gas Furnace

Ameristar

M801P080BU48AA

M801P080BU48-SUB-1A

FURNACE AIRFLOW (CFM) VS. EXTERNAL STATIC PRESSURE (IN. W.C.)

MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90

M801P080BU48AA

4-HIGH - Black3-MED - HIGH - Blue2-MED - LOW - Yellow1-LOW - Red

183913231092788

182113251090783

179613291091780

175613191083768

171013081076758

164112751059737

157312461040719

148012011005674

13921165970630

CFM VS. TEMPERATURE RISE

MODELCFM (CUBIC FEET PER MINUTE)

500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800

M801P080BU48AA 67 62 57 53 49

7/8" DIA. HOLESELECTRICALCONNECTION

1-1/2" DIA. HOLEGAS CONNECTION

40"

1/2"

3-3/4"

28-1/4"

5-5/16"

3/8"

2-1/8"

23-1/2"

3-13/16"

3/4"

28-3/8"19-5/8"

5/8"

4-1/16"

16-1/4"

22-1/2"

28-1/4"

8-1/4"

5/8"17-1/2"

16"

3/4"

3/4"

3-15/16"

9-5/8"

5/8"

2-1/16"

4" DIAMETERFLUE CONNECT

2-1/16"

1/2"

Ø 7/8” HOLE WITH PLUGELECTRICAL CONNECTION(ALTERNATE)

Ø 1-5/8” HOLE WITH PLUG (2)

Page 10: Ameristar · 2019-03-11 · Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without

Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.

Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032

Technical Literature - Printed in U.S.A.

LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes

Mechanical Specifications

AmeristarFurnacesFurnaceM801Submittal-05/15M801P080BU48-SUB-1AM801P080BU48-SUB-1

1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.

SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.

QUICK HEATING— Durable, cycle tested, heavy gauge aluminized steel heat exchanger quickly transfers heat to provide warm conditioned air to the struc-ture. Low energy power vent blower, to increase efficiency and provide discharge of gas fumes to the outside, allows com-mon venting with hot water heater.

BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.

INTEGRATED SYSTEM CONTROL - Exclusively designed operational program provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self diagnostics for ease of service.

AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).

STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.

FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter

b. Vent proving pressure switch.

PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)

HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)

M801P080BU48AAUpflow / Horizontal

80,00064,00030 - 60Direct10 x 8

14

See Fan Performance Table1/3

1075115/1/60

CentrifugalDirect - 1

1/50 - 3180115/1/60

1.09No

High Velocity1 - 17x25 - 1 in.

4 Round

Alum. Steel

20

4 — 454 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

4115/1/60

9.8151/2

H x W x D41-3/4 x 19-1/2 x 30-1/2

142 / 132

Page 11: Ameristar · 2019-03-11 · Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without

SUBMITTAL

© 2015 Ingersoll Rand

TAG: _________________________________

Upflow/ Horizontal Induced Draft Single Stage Gas Furnace

Ameristar

M801P100BU36AA

M801P100BU36-SUB-1A

FURNACE AIRFLOW (CFM) VS. EXTERNAL STATIC PRESSURE (IN. W.C.)

MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90

M801P100BU36AA

4-HIGH - Black3-MED - HIGH - Blue2-MED - LOW - Yellow1-LOW - Red

147612491020873

146412571046

887

144112521058

890

140812341050883

136312031028864

13071158990834

12411101936794

11631030866742

1074946780680

CFM VS. TEMPERATURE RISE

MODELCFM (CUBIC FEET PER MINUTE)

500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900

M801P100BU36AA 58 52 49 46 42 40 37 35 33

7/8" DIA. HOLESELECTRICALCONNECTION

1-1/2" DIA. HOLEGAS CONNECTION

40"

1/2"

3-3/4"

28-1/4"

5-5/16"

3/8"

2-1/8"

23-1/2"

3-13/16"

3/4"

28-3/8"19-5/8"

5/8"

4-1/16"

16-1/4"

22-1/2"

28-1/4"

8-1/4"

5/8"17-1/2"

16"

3/4"

3/4"

3-15/16"

9-5/8"

5/8"

2-1/16"

4" DIAMETERFLUE CONNECT

2-1/16"

1/2"

Ø 7/8” HOLE WITH PLUGELECTRICAL CONNECTION(ALTERNATE)

Ø 1-5/8” HOLE WITH PLUG (2)

Page 12: Ameristar · 2019-03-11 · Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without

Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.

Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032

Technical Literature - Printed in U.S.A.

LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes

Mechanical Specifications

AmeristarFurnacesFurnaceM801Submittal-05/15M801P100BU36-SUB-1AM801P100BU36-SUB-1

1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.

SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.

QUICK HEATING— Durable, cycle tested, heavy gauge aluminized steel heat exchanger quickly transfers heat to provide warm conditioned air to the struc-ture. Low energy power vent blower, to increase efficiency and provide discharge of gas fumes to the outside, allows com-mon venting with hot water heater.

BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.

INTEGRATED SYSTEM CONTROL - Exclusively designed operational program provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self diagnostics for ease of service.

AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).

STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.

FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter

b. Vent proving pressure switch.

PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)

HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)

M801P100BU36AAUpflow / Horizontal

100,00079,00040 - 70Direct10 x 7

14

See Fan Performance Table1/3

1075115/1/60

CentrifugalDirect - 1

1/50 - 3180115/1/60

1.09No

High Velocity1 - 17x25 - 1 in.

4 Round

Alum. Steel

20

5 — 455 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

5115/1/60

9.0151/2

H x W x D41-3/4 x 19-1/2 x 30-1/2

151 / 141

Page 13: Ameristar · 2019-03-11 · Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without

SUBMITTAL

© 2015 Ingersoll Rand

TAG: _________________________________

Upflow/ Horizontal Induced Draft Single Stage Gas Furnace

Ameristar

M801P100CU48AA

M801P100CU48-SUB-1A

FURNACE AIRFLOW (CFM) VS. EXTERNAL STATIC PRESSURE (IN. W.C.)

MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90

M801P100CU48AA

4-HIGH - Black3-MED - HIGH - Blue2-MED - LOW - Yellow1-LOW - Red

1880166214281208

1846163514211215

1799159814021210

1740155113701193

1669149313261164

1595142412691124

1489134511991073

1381125611171009

126011571022935

CFM VS. TEMPERATURE RISE

MODELCFM (CUBIC FEET PER MINUTE)

800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100

M801P100CU48AA 67 62 57 53 49 46 44 41 39 37

7/8" DIA. HOLESELECTRICALCONNECTION

1-1/2" DIA. HOLEGAS CONNECTION

40"

1/2"

3-3/4"

28-1/4"

5-5/16"

3/8"

2-1/8"

23-1/2"

3-13/16"

3/4"

28-3/8"19-5/8"

5/8"

4-1/16"

19-3/4"

22-1/2"

28-1/4"

8-1/4"

5/8"21"

19-1/2"

3/4"

3/4"

3-15/16"

13-1/16"

5/8"

2-1/16"

4" DIAMETERFLUE CONNECT

2-1/16"

1/2"

Ø 7/8” HOLE WITH PLUGELECTRICAL CONNECTION(ALTERNATE)

Ø 1-5/8” HOLE WITH PLUG (2)

Page 14: Ameristar · 2019-03-11 · Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without

Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.

Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032

Technical Literature - Printed in U.S.A.

LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes

Mechanical Specifications

AmeristarFurnacesFurnaceM801Submittal-05/15M801P100CU48-SUB-1AM801P100CU48-SUB-1

1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.

SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.

QUICK HEATING— Durable, cycle tested, heavy gauge aluminized steel heat exchanger quickly transfers heat to provide warm conditioned air to the struc-ture. Low energy power vent blower, to increase efficiency and provide discharge of gas fumes to the outside, allows com-mon venting with hot water heater.

BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.

INTEGRATED SYSTEM CONTROL - Exclusively designed operational program provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self diagnostics for ease of service.

AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).

STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.

FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter

b. Vent proving pressure switch.

PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)

HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)

M801P100CU48AAUpflow / Horizontal

100,00079,00035 - 65Direct10 x 8

14

See Fan Performance Table1/2

1075115/1/60

CentrifugalDirect - 1

1/50 - 3180115/1/60

1.09No

High Velocity1 - 20x25 - 1 in.

4 Round

Alum. Steel

20

5 — 455 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

5115/1/60

11.6151/2

H x W x D41-3/4 x 23 x 30-1/2

162 / 151

Page 15: Ameristar · 2019-03-11 · Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without

SUBMITTAL

© 2015 Ingersoll Rand

TAG: _________________________________

Upflow/ Horizontal Induced Draft Single Stage Gas Furnace

Ameristar

M801P100CU60AA

M801P100CU60-SUB-1A

FURNACE AIRFLOW (CFM) VS. EXTERNAL STATIC PRESSURE (IN. W.C.)

MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90

M801P100CU60AA

4-HIGH - Black3-MED - HIGH - Blue2-MED - LOW - Yellow1-LOW - Red

2181190816211443

2143188816091419

2104186815971395

2053183415821381

2001180015671367

1929174515331335

1856169014981302

1766 1631 1438 1256

1676157213771209

CFM VS. TEMPERATURE RISE

MODELCFM (CUBIC FEET PER MINUTE)

1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400

M801P100CU60AA 62 57 53 49 46 44 41 39 37 35 34 32 31

7/8" DIA. HOLESELECTRICALCONNECTION

1-1/2" DIA. HOLEGAS CONNECTION

40"

1/2"

3-3/4"

28-1/4"

5-5/16"

3/8"

2-1/8"

23-1/2"

3-13/16"

3/4"

28-3/8"19-5/8"

5/8"

4-1/16"

19-3/4"

22-1/2"

28-1/4"

8-1/4"

5/8"21"

19-1/2"

3/4"

3/4"

3-15/16"

13-1/16"

5/8"

2-1/16"

4" DIAMETERFLUE CONNECT

2-1/16"

1/2"

Ø 7/8” HOLE WITH PLUGELECTRICAL CONNECTION(ALTERNATE)

Ø 1-5/8” HOLE WITH PLUG (2)

Page 16: Ameristar · 2019-03-11 · Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without

Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.

Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032

Technical Literature - Printed in U.S.A.

LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes

Mechanical Specifications

AmeristarFurnacesFurnaceM801Submittal-05/15M801P100CU60-SUB-1AM801P100CU60-SUB-1

1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.

SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.

QUICK HEATING— Durable, cycle tested, heavy gauge aluminized steel heat exchanger quickly transfers heat to provide warm conditioned air to the struc-ture. Low energy power vent blower, to increase efficiency and provide discharge of gas fumes to the outside, allows com-mon venting with hot water heater.

BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.

INTEGRATED SYSTEM CONTROL - Exclusively designed operational program provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self diagnostics for ease of service.

AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).

STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.

FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter

b. Vent proving pressure switch.

PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)

HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)

M801P100CU60AAUpflow / Horizontal

100,00079,00030 - 60Direct

11 x 1014

See Fan Performance Table1/2

1075115/1/60

CentrifugalDirect - 1

1/50 - 3180115/1/60

1.09No

High Velocity1 - 20x25 - 1 in.

4 Round

Alum. Steel

20

5 — 455 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

5115/1/60

13.4201/2

H x W x D41-3/4 x 23 x 30-1/2

162 / 151

Page 17: Ameristar · 2019-03-11 · Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without

SUBMITTAL

© 2015 Ingersoll Rand

TAG: _________________________________

Upflow/ Horizontal Induced Draft Single Stage Gas Furnace

Ameristar

M801P120DU60AA

M801P120DU60-SUB-1A

FURNACE AIRFLOW (CFM) VS. EXTERNAL STATIC PRESSURE (IN. W.C.)

MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90

M801P120DU60AA

4-HIGH - Black3-MED - HIGH - Blue2-MED - LOW - Yellow1-LOW - Red

2135190616461423

2101188116321415

2066185616171407

2036181715961391

2005177715751375

1923172415351338

1840167114941300

1750160214271246

1659153313601192

CFM VS. TEMPERATURE RISE

MODELCFM (CUBIC FEET PER MINUTE)

1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400

M801P120DU60AA 59 56 52 49 47 44 42 40

7/8" DIA. HOLESELECTRICALCONNECTION

1-1/2" DIA. HOLEGAS CONNECTION

40"

1/2"

3-3/4"

28-1/4"

5-5/16"

3/8"

2-1/8"

23-1/2"

3-13/16"

3/4"

28-3/8"19-5/8"

5/8"

4-1/16"

23-1/4"

22-1/2"

28-1/4"

8-1/4"

5/8"24-1/2"

23"

3/4"

3/4"

3-15/16"

15-5/16"

5/8"

2-1/16"

4" DIAMETERFLUE CONNECT

2-1/16"

1/2"

Ø 7/8” HOLE WITH PLUGELECTRICAL CONNECTION(ALTERNATE)

Ø 1-5/8” HOLE WITH PLUG (2)

Page 18: Ameristar · 2019-03-11 · Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without

Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.

Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032

Technical Literature - Printed in U.S.A.

LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes

Mechanical Specifications

AmeristarFurnacesFurnaceM801Submittal-05/15M801P120DU60-SUB-1AM801P120DU60-SUB-1

1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.

SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.

QUICK HEATING— Durable, cycle tested, heavy gauge aluminized steel heat exchanger quickly transfers heat to provide warm conditioned air to the struc-ture. Low energy power vent blower, to increase efficiency and provide discharge of gas fumes to the outside, allows com-mon venting with hot water heater.

BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.

INTEGRATED SYSTEM CONTROL - Exclusively designed operational program provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self diagnostics for ease of service.

AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).

STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.

FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter

b. Vent proving pressure switch.

PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)

HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)

M801P120DU60AAUpflow / Horizontal

120,00096,00030 - 60Direct

11 x 1014

See Fan Performance Table1/2

1075115/1/60

CentrifugalDirect - 1

1/50 - 3180115/1/60

1.09No

High Velocity1 - 24x25 - 1 in.

4 Round

Alum. Steel

20

6 — 456 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

6115/1/60

13.4201/2

H x W x D41-3/4 x 26-1/2 x 30-1/2

186 / 174

Page 19: Ameristar · 2019-03-11 · Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without

SUBMITTAL

© 2015 Ingersoll Rand

TAG: _________________________________

Upflow/ Horizontal Induced Draft Single Stage Gas Furnace

Ameristar

M801P140DU60AA

M801P140DU60-SUB-1A

FURNACE AIRFLOW (CFM) VS. EXTERNAL STATIC PRESSURE (IN. W.C.)

MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90

M801P140DU60AA

4-HIGH - Black3-MED - HIGH - Blue2-MED - LOW - Yellow1-LOW - Red

2462212817551450

2407211217461446

2351209617361442

2284205417191427

2216201217021411

2143194916561383

2069188716091354

1989179715641298

1908170615181241

CFM VS. TEMPERATURE RISE

MODELCFM (CUBIC FEET PER MINUTE)

1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400

M801P140DU60AA 69 65 61 58 55 52 49 47 45

7/8" DIA. HOLESELECTRICALCONNECTION

1-1/2" DIA. HOLEGAS CONNECTION

40"

1/2"

3-3/4"

28-1/4"

5-5/16"

3/8"

2-1/8"

23-1/2"

3-13/16"

3/4"

28-3/8"19-5/8"

5/8"

4-1/16"

23-1/4"

22-1/2"

28-1/4"

8-1/4"

5/8"24-1/2"

23"

3/4"

3/4"

3-15/16"

15-5/16"

5/8"

2-1/16"

4" DIAMETERFLUE CONNECT

2-1/16"

1/2"

Ø 7/8” HOLE WITH PLUGELECTRICAL CONNECTION(ALTERNATE)

Ø 1-5/8” HOLE WITH PLUG (2)

Page 20: Ameristar · 2019-03-11 · Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without

Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.

Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032

Technical Literature - Printed in U.S.A.

LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes

Mechanical Specifications

AmeristarFurnacesFurnaceM801Submittal-05/15M801P140DU60-SUB-1AM801P140DU60-SUB-1

1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.

SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.

QUICK HEATING— Durable, cycle tested, heavy gauge aluminized steel heat exchanger quickly transfers heat to provide warm conditioned air to the struc-ture. Low energy power vent blower, to increase efficiency and provide discharge of gas fumes to the outside, allows com-mon venting with hot water heater.

BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.

INTEGRATED SYSTEM CONTROL - Exclusively designed operational program provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self diagnostics for ease of service.

AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).

STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.

FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter

b. Vent proving pressure switch.

PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)

HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)

M801P140DU60AAUpflow / Horizontal

140,000111,00040 - 70Direct

11 x 1014

See Fan Performance Table3/4

1075115/1/60

CentrifugalDirect - 1

1/50 - 3180115/1/60

1.09No

High Velocity1 - 24x25 - 1 in.

4 Round

Alum. Steel

20

7 — 457 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

7115/1/60

13.8201/2

H x W x D41-3/4 x 26-1/2 x 30-1/2

193 / 181

Page 21: Ameristar · 2019-03-11 · Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without

SUBMITTAL

© 2012 Ingersoll Rand

TAG: _________________________________

Downflow/ Horizontal Induced Draft Single Stage Gas Furnace

Ameristar

M801P060AD24AA

M801P060AD24-SUB-1A

CFM VS. TEMPERATURE RISE

MODELCFM (CUBIC FEET PER MINUTE)

500 600 700 800 900 1000 1100 1200 1300 1400

M801P060AD24AA 63 56 49 44 40

FURNACE AIRFLOW (CFM) VS. STATIC PRESSURE (ins. w.g.)

MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90

M801P060AD24AA

4-HIGH - Black3-MED - HIGH - Blue2-MED - LOW - Yellow1-LOW - Red

12001025838722

1155988808689

1111951779656

1056905742618

1001859704579

924797646528

848735588478

774646502376

701558415275

7/8" HOLE WITH PLUG

1-1/2" DIA. GASCONNECTION(ALTERNATE)

7/8" DIA. HOLESELECTRICALCONNECTION

1-5/8" DIA. HOLE WITH PLUGGAS CONNECTION (ALT)

40"

20-1/4"

10"

5-5/16"1/2"

3-3/4”

19"

8-1/4"

3/4"

28"

19-5/8"

5/8"

4-1/8"

13-1/4"14-1/2"

13"

3/4"

3/4"

9-5/8"

2-1/8"

2-1/8"

12-3/8"

10"

5/8"

FLUE OPENING

24-1/2"

29-1/2"

5"

7"

SIDE PANEL CUTOUT FORHORIZONTAL VENTINGTHROUGH THE CABINET

1/2"

4" O

3-15/16"

3-3/8

3-1/2

31

5" O SIDE PANEL CUTOUTFOR HORIZONTAL VENTINGTHROUGH THE CABINET

7-3/8"

1-5/8” HOLEWITH PLUG

1-5/8” HOLEWITH PLUG

1-5/8” HOLE WITH PLUG

1-5/8” HOLE WITH PLUG

Page 22: Ameristar · 2019-03-11 · Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without

Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.

Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032

Technical Literature - Printed in U.S.A.

LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes

Mechanical Specifications

AmeristarFurnacesFurnaceM801Submittal-05/15M801P060AD24-SUB-1AM801P060AD24-SUB-1

1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.

SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.

QUICK HEATING— Durable, cycle tested, heavy gauge aluminized steel heat exchanger quickly transfers heat to provide warm conditioned air to the struc-ture. Low energy power vent blower, to increase efficiency and provide discharge of gas fumes to the outside, allows com-mon venting with hot water heater.

BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.

INTEGRATED SYSTEM CONTROL - Exclusively designed operational program provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self diagnostics for ease of service.

AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).

STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.

FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter

b. Vent proving pressure switch.

PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)

HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)

M801P060AD24AADownflow / Horizontal

60,00048,00035 - 65

DIRECT10 x 7

14

See Fan Performance Table1/5

1075115/1/60

CentrifugalDirect - 1

1/50 - 3180115/1/60

1.09No

High Velocity2 - 14x20 - 1in.

4 Round

Alum. Steel

20

3 — 453 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

3115/1/60

5.5151/2

H x W x D41-3/4 x 16-1/2 x 30-1/2

129 / 119

Page 23: Ameristar · 2019-03-11 · Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without

SUBMITTAL

© 2012 Ingersoll Rand

TAG: _________________________________

Downflow/ Horizontal Induced Draft Single Stage Gas Furnace

Ameristar

M801P060AD36AA

M801P060AD36-SUB-1A

CFM VS. TEMPERATURE RISE

MODELCFM (CUBIC FEET PER MINUTE)

500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700

M801P060AD36AA 56 49 44 40 37 34 32

FURNACE AIRFLOW (CFM) VS. STATIC PRESSURE (ins. w.g.)

MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90

M801P060AD36AA

4-HIGH - Black3-MED - HIGH - Blue2-MED - LOW - Yellow1-LOW - Red

148013021115956

142912761100947

137512291070918

131811881035888

128211411000859

11001088965824

11121024918788

1029953859741

959882790682

7/8" HOLE WITH PLUG

1-1/2" DIA. GASCONNECTION(ALTERNATE)

7/8" DIA. HOLESELECTRICALCONNECTION

1-5/8" DIA. HOLE WITH PLUGGAS CONNECTION (ALT)

40"

20-1/4"

10"

5-5/16"1/2"

3-3/4”

19"

8-1/4"

3/4"

28"

19-5/8"

5/8"

4-1/8"

13-1/4"14-1/2"

13"

3/4"

3/4"

9-5/8"

2-1/8"

2-1/8"

12-3/8"

10"

5/8"

FLUE OPENING

24-1/2"

29-1/2"

5"

7"

SIDE PANEL CUTOUT FORHORIZONTAL VENTINGTHROUGH THE CABINET

1/2"

4" O

3-15/16"

3-3/8

3-1/2

31

5" O SIDE PANEL CUTOUTFOR HORIZONTAL VENTINGTHROUGH THE CABINET

7-3/8"

1-5/8” HOLEWITH PLUG

1-5/8” HOLEWITH PLUG

1-5/8” HOLE WITH PLUG

1-5/8” HOLE WITH PLUG

Page 24: Ameristar · 2019-03-11 · Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without

Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.

Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032

Technical Literature - Printed in U.S.A.

LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes

Mechanical Specifications

AmeristarFurnacesFurnaceM801Submittal-05/15M801P060AD36-SUB-1AM801P060AD36-SUB-1

1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.

SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.

QUICK HEATING— Durable, cycle tested, heavy gauge aluminized steel heat exchanger quickly transfers heat to provide warm conditioned air to the struc-ture. Low energy power vent blower, to increase efficiency and provide discharge of gas fumes to the outside, allows com-mon venting with hot water heater.

BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.

INTEGRATED SYSTEM CONTROL - Exclusively designed operational program provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self diagnostics for ease of service.

AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).

STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.

FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter

b. Vent proving pressure switch.

PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)

HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)

M801P060AD36AADownflow / Horizontal

60,00048,00030 - 60

DIRECT11 x 7

14

See Fan Performance Table1/2

1075115/1/60

CentrifugalDirect - 1

1/50 - 3180115/1/60

1.09No

High Velocity2 - 14x20 - 1in.

4 Round

Alum. Steel

20

3 — 453 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

3115/1/60

11.6151/2

H x W x D41-3/4 x 16-1/2 x 30-1/2

129 / 119

Page 25: Ameristar · 2019-03-11 · Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without

SUBMITTAL

© 2012 Ingersoll Rand

TAG: _________________________________

Downflow/ Horizontal Induced Draft Single Stage Gas Furnace

Ameristar

M801P080BD45AA

M801P080BD45-SUB-1A

CFM VS. TEMPERATURE RISE

MODELCFM (CUBIC FEET PER MINUTE)

500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600

M801P080BD45AA 64 57 52 48 44 41

FURNACE AIRFLOW (CFM) VS. STATIC PRESSURE (ins. w.g.)

MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90

M801P080BD45AA

4-HIGH - Black3-MED - HIGH - Blue2-MED - LOW - Yellow1-LOW - Red

1798138412101005

175013671150970

169213331108808

164213001075775

157512751042767

150012331008733

14251192967700

13251142925675

12251083867617

7/8" HOLE WITH PLUG

1-1/2" DIA. GASCONNECTION(ALTERNATE)

7/8" DIA. HOLESELECTRICALCONNECTION

1-5/8" DIA. HOLE WITH PLUGGAS CONNECTION (ALT)

40"

20-1/4"

10"

5-5/16"1/2"

3-3/4”

19"

8-1/4"

3/4"

28"

19-5/8"

5/8"

4-1/8"

16-1/4"17-1/2"

16"

3/4"

3/4"

9-5/8"

2-1/8"

2-1/8"

12-3/8"

10"

5/8"

FLUE OPENING

24-1/2"

29-1/2"

5"

7"

SIDE PANEL CUTOUT FORHORIZONTAL VENTINGTHROUGH THE CABINET

1/2"

4" O

3-15/16"

3-3/8

3-1/2

31

5" O SIDE PANEL CUTOUTFOR HORIZONTAL VENTINGTHROUGH THE CABINET

7-3/8"

1-5/8” HOLEWITH PLUG

1-5/8” HOLEWITH PLUG

1-5/8” HOLE WITH PLUG

1-5/8” HOLE WITH PLUG

Page 26: Ameristar · 2019-03-11 · Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without

Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.

Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032

Technical Literature - Printed in U.S.A.

LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes

Mechanical Specifications

AmeristarFurnacesFurnaceM801Submittal-05/15M801P080BD45-SUB-1AM801P080BD45-SUB-1

1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.

SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.

QUICK HEATING— Durable, cycle tested, heavy gauge aluminized steel heat exchanger quickly transfers heat to provide warm conditioned air to the struc-ture. Low energy power vent blower, to increase efficiency and provide discharge of gas fumes to the outside, allows com-mon venting with hot water heater.

BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.

INTEGRATED SYSTEM CONTROL - Exclusively designed operational program provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self diagnostics for ease of service.

AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).

STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.

FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter

b. Vent proving pressure switch.

PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)

HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)

M801P080BD45AADownflow / Horizontal

80,00064,00035 - 65

DIRECT10 x 8

14

See Fan Performance Table1/3

1075115/1/60

CentrifugalDirect - 1

1/50 - 3180115/1/60

1.09No

High Velocity2 - 14x20 - 1 in.

4 Round

Alum. Steel - Type I

20

4 — 454 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

4115/1/60

9.1151/2

H x W x D41-3/4 x 19-1/2 x 30-1/2

146 / 135

Page 27: Ameristar · 2019-03-11 · Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without

SUBMITTAL

© 2012 Ingersoll Rand

TAG: _________________________________

Downflow/ Horizontal Induced Draft Single Stage Gas Furnace

Ameristar

M801P100CD48AA

M801P100CD48-SUB-1A

CFM VS. TEMPERATURE RISE

MODELCFM (CUBIC FEET PER MINUTE)

800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400

M801P100CD48AA 62 57 53 49 46 44 41 39 37

FURNACE AIRFLOW (CFM) VS. STATIC PRESSURE (ins. w.g.)

MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90

M801P100CD48AA

4-HIGH - Black3-MED - HIGH - Blue2-MED - LOW - Yellow1-LOW - Red

1965164514071202

1915162713981208

1865160513871205

1805157513751195

1740153513471166

1670148213181140

1587142112751105

1500133011901045

137012201095970

7/8" HOLE WITH PLUG

1-1/2" DIA. GASCONNECTION(ALTERNATE)

7/8" DIA. HOLESELECTRICALCONNECTION

1-5/8" DIA. HOLE WITH PLUGGAS CONNECTION (ALT)

40"

20-1/4"

10"

5-5/16"1/2"

3-3/4”

19"

8-1/4"

3/4"

28"

19-5/8"

5/8"

4-1/8"

19-1/4"21"

19-1/2"

3/4"

3/4"

13-1/16"

2-1/8"

2-1/8"

12-3/8"

10"

5/8"

FLUE OPENING

24-1/2"

29-1/2"

5"

7"

SIDE PANEL CUTOUT FORHORIZONTAL VENTINGTHROUGH THE CABINET

1/2"

4" O

3-15/16"

3-3/8

3-1/2

31

5" O SIDE PANEL CUTOUTFOR HORIZONTAL VENTINGTHROUGH THE CABINET

7-3/8"

1-5/8” HOLEWITH PLUG

1-5/8” HOLEWITH PLUG

1-5/8” HOLE WITH PLUG

1-5/8” HOLE WITH PLUG

Page 28: Ameristar · 2019-03-11 · Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without

Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.

Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032

Technical Literature - Printed in U.S.A.

LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes

Mechanical Specifications

AmeristarFurnacesFurnaceM801Submittal-05/15M801P100CD48-SUB-1AM801P100CD48-SUB-1

1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.

SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.

QUICK HEATING— Durable, cycle tested, heavy gauge aluminized steel heat exchanger quickly transfers heat to provide warm conditioned air to the struc-ture. Low energy power vent blower, to increase efficiency and provide discharge of gas fumes to the outside, allows com-mon venting with hot water heater.

BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.

INTEGRATED SYSTEM CONTROL - Exclusively designed operational program provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self diagnostics for ease of service.

AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).

STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.

FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter

b. Vent proving pressure switch.

PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)

HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)

M801P100CD48AADownflow / Horizontal

100,00080,00035 - 65

DIRECT10 x 8

14

See Fan Performance Table1/2

1075115/1/60

CentrifugalDirect - 1

1/50 - 3180115/1/60

1.09No

High Velocity2 - 16x20 - 1in.

4 Round

Alum. Steel

20

5 — 455 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

5115/1/60

11.6151/2

H x W x D41-3/4 x 23 x 30-1/2

166 / 154

Page 29: Ameristar · 2019-03-11 · Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without

SUBMITTAL

© 2012 Ingersoll Rand

TAG: _________________________________

Downflow/ Horizontal Induced Draft Single Stage Gas Furnace

Ameristar

M801P100CD60AA

M801P100CD60-SUB-1A

CFM VS. TEMPERATURE RISE

MODELCFM (CUBIC FEET PER MINUTE)

1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400

M801P100CD60AA 62 57 53 49 46 44 41 39 37 35 34 32 31

FURNACE AIRFLOW (CFM) VS. STATIC PRESSURE (ins. w.g.)

MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90

M801P100CD60AA

4-HIGH - Black3-MED - HIGH - Blue2-MED - LOW - Yellow1-LOW - Red

2165196217051492

2113192716881467

2060189116711442

1995183916361414

1929178616001385

1842172415471346

1755166214921307

1674158114351243

1593150013771179

7/8" HOLE WITH PLUG

1-1/2" DIA. GASCONNECTION(ALTERNATE)

7/8" DIA. HOLESELECTRICALCONNECTION

1-5/8" DIA. HOLE WITH PLUGGAS CONNECTION (ALT)

40"

20-1/4"

10"

5-5/16"1/2"

3-3/4”

19"

8-1/4"

3/4"

28"

19-5/8"

5/8"

4-1/8"

19-1/4"21"

19-1/2"

3/4"

3/4"

13-1/16"

2-1/8"

2-1/8"

12-3/8"

10"

5/8"

FLUE OPENING

24-1/2"

29-1/2"

5"

7"

SIDE PANEL CUTOUT FORHORIZONTAL VENTINGTHROUGH THE CABINET

1/2"

4" O

3-15/16"

3-3/8

3-1/2

31

5" O SIDE PANEL CUTOUTFOR HORIZONTAL VENTINGTHROUGH THE CABINET

7-3/8"

1-5/8” HOLEWITH PLUG

1-5/8” HOLEWITH PLUG

1-5/8” HOLE WITH PLUG

1-5/8” HOLE WITH PLUG

Page 30: Ameristar · 2019-03-11 · Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without

Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.

Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032

Technical Literature - Printed in U.S.A.

LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes

Mechanical Specifications

AmeristarFurnacesFurnaceM801Submittal-05/15M801P100CD60-SUB-1AM801P100CD60-SUB-1

1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.

SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.

QUICK HEATING— Durable, cycle tested, heavy gauge aluminized steel heat exchanger quickly transfers heat to provide warm conditioned air to the struc-ture. Low energy power vent blower, to increase efficiency and provide discharge of gas fumes to the outside, allows com-mon venting with hot water heater.

BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.

INTEGRATED SYSTEM CONTROL - Exclusively designed operational program provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self diagnostics for ease of service.

AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).

STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.

FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter

b. Vent proving pressure switch.

PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)

HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)

M801P100CD60AADownflow / Horizontal

100,00080,00030 - 60

DIRECT11 x 10

14

See Fan Performance Table1/2

1075115/1/60

CentrifugalDirect - 1

1/50 - 3180115/1/60

1.09No

High Velocity2 - 16x20 - 1 in.

4 Round

Alum. Steel - Type I

20

5 — 455 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

5115/1/60

12.8151/2

H x W x D41-3/4 x 23 x 30-1/2

167 / 155

Page 31: Ameristar · 2019-03-11 · Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without

SUBMITTAL

© 2012 Ingersoll Rand

TAG: _________________________________

Downflow/ Horizontal Induced Draft Single Stage Gas Furnace

Ameristar

M801P120DD60AA

M801P120DD60-SUB-1A

CFM VS. TEMPERATURE RISE

MODELCFM (CUBIC FEET PER MINUTE)

1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400

M801P120DD60AA 59 56 52 49 47 44 42 40

FURNACE AIRFLOW (CFM) VS. STATIC PRESSURE (ins. w.g.)

MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90

M801P120DD60AA

4-HIGH - Black3-MED - HIGH - Blue2-MED - LOW - Yellow1-LOW - Red

2241198117211476

2202196217051466

2163194216881456

2106190416711440

2049186616531423

1979180516111392

1908174315691361

1804168015151302

1700161714611243

7/8" HOLE WITH PLUG

1-1/2" DIA. GASCONNECTION(ALTERNATE)

7/8" DIA. HOLESELECTRICALCONNECTION

1-5/8" DIA. HOLE WITH PLUGGAS CONNECTION (ALT)

40"

20-1/4"

10"

5-5/16"1/2"

3-3/4”

19"

8-1/4"

3/4"

28"

19-5/8"

5/8"

4-1/8"

23-1/4"24-1/2"

23"

3/4"

3/4"

15-5/16"

2-1/8"

2-1/8"

12-3/8"

10"

5/8"

FLUE OPENING

24-1/2"

29-1/2"

5"

7"

SIDE PANEL CUTOUT FORHORIZONTAL VENTINGTHROUGH THE CABINET

1/2"

4" O

3-15/16"

3-3/8

3-1/2

31

5" O SIDE PANEL CUTOUTFOR HORIZONTAL VENTINGTHROUGH THE CABINET

7-3/8"

1-5/8” HOLEWITH PLUG

1-5/8” HOLEWITH PLUG

1-5/8” HOLE WITH PLUG

1-5/8” HOLE WITH PLUG

Page 32: Ameristar · 2019-03-11 · Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without

Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.

Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032

Technical Literature - Printed in U.S.A.

LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes

Mechanical Specifications

AmeristarFurnacesFurnaceM801Submittal-05/15M801P120DD60-SUB-1AM801P120DD60-SUB-1

1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.

SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.

QUICK HEATING— Durable, cycle tested, heavy gauge aluminized steel heat exchanger quickly transfers heat to provide warm conditioned air to the struc-ture. Low energy power vent blower, to increase efficiency and provide discharge of gas fumes to the outside, allows com-mon venting with hot water heater.

BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.

INTEGRATED SYSTEM CONTROL - Exclusively designed operational program provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self diagnostics for ease of service.

AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).

STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.

FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter

b. Vent proving pressure switch.

PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)

HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)

M801P120DD60AADownflow / Horizontal

120,00096,00035 - 65

DIRECT11 x 10

14

See Fan Performance Table1/2

1075115/1/60

CentrifugalDirect - 1

1/50 - 3180115/1/60

1.09No

High Velocity2 - 16x20 - 1 in.

4 Round

Alum. Steel - Type I

20

6 — 456 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

6115/1/60

12.8151/2

H x W x D41-3/4 x 26-1/2 x 30-1/2

189 / 176

Page 33: Ameristar · 2019-03-11 · Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without

SUBMITTAL

© 2012 Ingersoll Rand

TAG: _________________________________

Downflow/ Horizontal Induced Draft Single Stage Gas Furnace

Ameristar

M801P140DD60AA

M801P140DD60-SUB-1A

CFM VS. TEMPERATURE RISE

MODELCFM (CUBIC FEET PER MINUTE)

1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400

M801P140DD60AA 69 65 61 58 55 52 49 47 45

FURNACE AIRFLOW (CFM) VS. STATIC PRESSURE (ins. w.g.)

MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90

M801P140DD60AA

4-HIGH - Black3-MED - HIGH - Blue2-MED - LOW - Yellow1-LOW - Red

2377211518061527

2321208117931507

2265204617791486

2199199217381473

2133193816961459

2050187216551422

1967180516141384

1877172715561329

1786164914971273

7/8" HOLE WITH PLUG

1-1/2" DIA. GASCONNECTION(ALTERNATE)

7/8" DIA. HOLESELECTRICALCONNECTION

1-5/8" DIA. HOLE WITH PLUGGAS CONNECTION (ALT)

40"

20-1/4"

10"

5-5/16"1/2"

3-3/4”

19"

8-1/4"

3/4"

28"

19-5/8"

5/8"

4-1/8"

23-1/4"24-1/2"

23"

3/4"

3/4"

15-5/16"

2-1/8"

2-1/8"

12-3/8"

10"

5/8"

FLUE OPENING

24-1/2"

29-1/2"

5"

7"

SIDE PANEL CUTOUT FORHORIZONTAL VENTINGTHROUGH THE CABINET

1/2"

4" O

3-15/16"

3-3/8

3-1/2

31

5" O SIDE PANEL CUTOUTFOR HORIZONTAL VENTINGTHROUGH THE CABINET

7-3/8"

1-5/8” HOLEWITH PLUG

1-5/8” HOLEWITH PLUG

1-5/8” HOLE WITH PLUG

1-5/8” HOLE WITH PLUG

Page 34: Ameristar · 2019-03-11 · Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without

Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change specifications and design without notice.

Ingersoll Rand11819 N. Pennsylvania StreetCarmel, IN 46032

Technical Literature - Printed in U.S.A.

LibraryProduct SectionProductModelLiterature TypeSequenceDateFile No.Supersedes

Mechanical Specifications

AmeristarFurnacesFurnaceM801Submittal-05/15M801P140DD60-SUB-1AM801P140DD60-SUB-1

1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

NATURAL GAS MODELS - Central Heat-ing furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.

SAFE OPERATION - The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heat-ing mode of operation. Slow opening, dual solenoid combination gas valve and regulator provide extra safety and quieter operation.

QUICK HEATING— Durable, cycle tested, heavy gauge aluminized steel heat exchanger quickly transfers heat to provide warm conditioned air to the struc-ture. Low energy power vent blower, to increase efficiency and provide discharge of gas fumes to the outside, allows com-mon venting with hot water heater.

BURNERS - Multiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.

INTEGRATED SYSTEM CONTROL - Exclusively designed operational program provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self diagnostics for ease of service.

AIR DELIVERY - The multispeed, direct drive blower motor, with sufficient air-flow range for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed. (Fan relay and 35VA control transformer is standard).

STYLING - Heavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is com-pletely lined with foil faced fiberglass in-sulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass.

FEATURES AND GENERAL OPERA-TION - The High Efficiency Gas Furnaces employs a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access. a. Low energy power venter

b. Vent proving pressure switch.

PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)

HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)

M801P140DD60AADownflow / Horizontal

140,000113,00045 - 75

DIRECT11 x 10

14

See Fan Performance Table3/4

1075115/1/60

CentrifugalDirect - 1

1/50 - 3180115/1/60

1.09No

High Velocity2 - 16x20 - 1in.

4 Round

Alum. Steel

20

7 — 457 — 56

Redundant - Single Stage

Hot Surface IgnitionMultiport Inshot

7115/1/60

13.8201/2

H x W x D41-3/4 x 26-1/2 x 30-1/2

196 / 183