ADDENDUM TO INVITATION FOR BID (IFB)
Issued By:
Addendum No.
3
Date of this Addendum
April 10, 2015
Number of Pages
6 Plus Attachments
PURCHASING OFFICE
BOARD OF EDUCATION OF
PRINCE GEORGE’S
COUNTY
UPPER MARLBORO,
MARYLAND 20772-9983
IFB No.
041-15
Date IFB Issued
March 19, 2015
Date & Hour of Return of IFB
April 15, 2015 @ 2:00 P.M.
TITLE:
Bowie HS Air Conditioning EEI Project
The above IFB is amended as follows. ALL OTHER TERMS AND CONDITIONS REMAIN THE SAME.
The purpose of this Addendum is to provide changes to PGCPS Prequalified Asbestos Contractors, Revisions to Drawings
and Specifications.
CHANGES TO IFB
Item 1-1: Section IV A. - Bid Form (April 10, 2015)
CHANGES TO DRAWINGS
Item 1-16: Sheet A-001: REVISED: General Note #6 revised
Item 1-17: Sheet A-107 thru A-116: REVISED: Reflected Ceiling Plan Ledged revised
Item 1-18: Sheet C-001: REVISED: Added sheet M-201E, Mechanical New Work First Floor, Condensate Piping, part
plan F.
Item 1-19: Sheet M-001: REVISED: Added sheet M-201E, Mechanical New Work First Floor, Condensate Piping, part
plan F.
Item 1-20: Sheet M-405: REVISED: Sequence of Operation section on the Heat Wheel Operation was removed and note
on Hot Gas Reheat relay output was also removed.
Item 1-21: Sheet M-601: REVISED: CFM's for the Outside Air Units were revised.
Item 1-22: Sheet M-602: REVISED: Energy Recovery Unit schedule was revised.
Item 1-23: Sheet M-201E: NEW: This sheet is a newly created drawing of the refrigerant piping for part plan F.
QUESTIONS:
Q1 Do you have an estimated price range for the above project?
A1 No estimated price range will be provided. Contractor will provide cost proposal for all associated work
Q2 The Technical Specifications on the CD appear to be missing the following sections: 15700 Air-To-Air Energy
Recovery Units, 15738 Packaged Rooftop Air Conditioning Units, 15739 Variable Refrigerant Volume Air
Conditioning, 15840 Ductwork, and 15830 Fans has page 1/3 of a page and then the bottom goes to 15060. Is this
the complete fan specification?
A2 Specifications for Sections 15080, 15700, 15738, 15739, 15840, and 15850 have been submitted.
Q3 There seems to be several sections of the specifications missing, in particular sections 15080, 15700, 15738,
15739, 15840, and 15850 and possibly more.
A3 Specifications for Sections 15080, 15700, 15738, 15739, 15840, and 15850 have been submitted.
Q4 We are going to bid Bowie and want to make sure we are on the bid list. I am setting up subs that will need to
look at the job and will send out and email to coordinate.
A4 A bid walk was previously provided. No additional bid walks will be held.
Q5 I was able to download the documents from the website that was in the ad, but I wasn’t able to find any drawings.
I see that the ad mentioned the plans and specs are currently being processed, is this still the case or are they
available now?
A5 Drawings and specification are available for pick up in accordance with instructions outlined in the solicitation.
Q6 Would it be possible to get lists of contractors who attended the pre-bid meeting, and site visit for this project? Is
a current plan holder list available as well?
A6 Prebid attendee list was posted to PGCPS website.
Q7 Do you have a value “parameter” for this project already set? If so, please can you let me know what it is.
A7 No value “parameter” is set.
Q8 Please advise if a site visit is still possible on this bid.
A8 No additional site visits will be conducted.
Q9 Is there any asbestos present in any of the work locations or the school. If yes where?
A9 Yes, the “Red Book” reviewed during the walk-thru at the site will identify HAZMAT also see revised general
note #6 on sheet A-001.
Q10 Can you provide a copy of the ACM log book on site?
A10 No copies are available. Copy is available for review on site
Q11 Will the project be phased and section turned over to the contractor with students moved out of that area so work
can be completed. If yes, how many sections can/will be turned over to the contractor?
A11 See addendum #2.
Q12 Will PGCPS move furniture so work can be completed?
A12 No, Contractor will be required to move and relocate furniture.
Q13 Will the contractor be allowed to remove ceiling tile and or grid in occupied area to complete work. Ceiling tile
and grid will have to remain removed until all work is completed.
A13 Ceiling will need to be in place while building is occupied.
Q14 What type of control system exist and how is the contractor required to tie into this system.
A14 The units are provided with on-board controllers. The school needs to provide options to the contractor to tie into
the units' on-board controllers.
Q15 Will the school be occupied for summer school? If yes what sections.
A15 Summer school will not be in session.
Q16 Will phasing areas be available during the summer if so which ones.
A16 See addendum #2.
Q17 Unit description under items 1,2,&3 ask for unit prices but do not provide size or type. What size and type of pipe
and valves is to be priced under unit pricing.
A17 Not clear which units are being discussed. Contractor needs to be specific.
Q18 What hours will the contractor be allowed to work during the school year.
A18 Contractor will be allowed to work after school hours and on weekends.
Q19 What hours will the contractor be allowed to work when school is out.
A19 After school hours and weekends.
Q20 What hours will the contractor be allowed to work when school is out for the summer.
A20 After school hours and weekends.
Q21 Specifications note 2 on MD-100A- MD-101B indicates "disconnect/cap and seal outside air" no detail is
provided or specified. Please provide a spec and detailed drawing. Someone could simply cap with galvanized
sheet metal to meet current specifications.
A21 This note is referring to the outside air connection of the unit ventilators which is to be closed off/cut off/sealed so
that the unit is not pulling in outside air through that connection.
Q22 Mechanical drawings do not have a legend and there are symbols on the drawings. Need a legend to clearly
indicate what the symbols are.
A22 Mechanical drawing sheet M-001 has a Mechanical symbols list.
Q23 No specifications provided for the ductwork.
A23 Specifications for DUCTWORK has been provided.
Q24 No specifications provided for the control system.
A24 None is required. The units are packaged units equipped with on-board controllers come supplied with equipment
specifications manual.
Q25 RCP symbol legend on A-107 show existing flat ceiling to remain in the locker room. What type of ceiling is this
and how is it to remain with new ductwork required to be installed above.
A25 See revised legend sheets A-107 thru A-116. Based on field survey Locker room ceiling appeared to be plaster on
lath; only those portions deemed necessary for installation of new ductwork should be removed. If portions or
entire ceiling is removed new ceiling shall be installed to match existing height, texture and finish.
Q26 In the Invitation for Bid, Section XXXII, Paragraph B it states that the Contractor will be responsible for the
removal and abatement of all asbestos and to include the cost in the bid. The prior paragraph states that the
Contractor is not to disturb the asbestos and additionally states that the successful Contractor will be responsible
for making arrangements to review the current abatement plan to ensure that it is not disturbed. The drawings
state all asbestos will be removed by the Owner. As the Contractor will not know what asbestos conditions are
until after they have been awarded the contract there is no way that any such cost could be included in the bid.
Therefore Paragraph B., of Section XXXII should be deleted.
A26 See Q9 this document and revised general note #6 on sheet A-001. Contractor should provide an appropriate
allowance for such abatement.
Q27 Drawing M-101F shows VRF ceiling cassettes; which are scheduled; being installed, however; unlike the other
area drawings; there is no piping, or branch controllers, shown for these units.
A27 See drawings M-101F, M-103F, and M-201E for the scheduled units, branch controllers, refrigerant piping and
drain piping.
Q28 We received the CD that contains all of the contract documents, we are missing various sections of the
specification (too many to list). We would like to confirm that all spec sections are supposed to be on the CD? If
so, what will be the protocol to obtain these missing specifications?
A28 All Specification sections are on the CD that was submitted.
Q29 Please provide a safety/phasing plan of the sequence of work for this project and also the detailed placement of
students while the phased construction is going on.
A29 See addendum #2.
Q30 Is there an existing warranty on the roof, if so, who?
A30 Yes, two years remaining on John Mansfield roof warranty.
Q31 Will all of the work during the school year be done during off hours and weekends? If not, please provide a
placement plan for all of the students for each class and/or room that will be disturbed.
A31 See Addendum #2
Q32 Please provide ceiling types and locations throughout the entire school.
A32 Ceiling types and locations throughout the entire school is not available, see reflected ceiling plan drawings
provided in construction documents as they relate to ceiling types in areas defined for new work. See revised
schedule on sheets A-107 thru A-116.
Q33 Will there be a need for structural steel upgrades under the new rooftop equipment? If so, who will be responsible
for providing the engineering and also the engineered stamped drawings for this scope of work?
A33 If existing field conditions require additional structural steel upgrades, the Design Engineer will provide design
drawings for such upgrade. General Contractor shall be responsible for providing engineered stamped shop
drawing for such design.
Q34 Will we be required to provide professional cleaning after each day/night of work?
A34 A professional cleaning will be required at project turn over, the areas of work will need to be cleaned from
construction items (debris & dust, etc.) prior to student occupancy.
Q35 Will we be able to utilize the existing bathroom facilities or will we be responsible for our own facilities?
A35 Contractor to provide separate toilets.
Q36 Will there be a location(s) set aside for laydown area(s) for all of our construction materials? If so, where?
A36 To be negotiated with PM after award.
Q35 Who will be responsible for moving all classroom furniture and materials?
A37 The Contractor is responsible.
Q37 Drawing M-101F shows VRF ceiling cassettes; which are scheduled; being installed, however; unlike the other
area drawings; there is no piping, or branch controllers, shown for these units.
A38 See drawings M-101F and M-201E for the refrigerant piping and drain piping.
Q39 Drawing M-103F; area F roof plan; shows two (2) condensing units; CU-1-1 and CU-1-2 which are scheduled
though there are no piping trees for these two CU’s, unlike all the other scheduled CU’s. This seems to indicate
that there should be units in the second floor also, however there is no drawing for this second floor area.
The architectural reflected ceiling plan for this area; A-112; also does not show these cassettes.
The condensate piping drawings; M-200 series; also do not include a drawing for this area, whereas there are
drawings for areas A through D, as needed per floor.
A39 See drawings M-101F, M-103F and M201E for the scheduled condensing unit CU-1-1 and piping. CU-1-2 has
been removed from the drawings.
Q40 M101F shows 10 Indoor Air Conditioning Units (ACU F 1-1—1-10), however, no outdoor condensing units are
scheduled, no refrigerant pipe is shown, and no drain piping is shown; please advise.
A41 See drawings M-101F, M-103F, and M-201E for the scheduled condensing units, refrigerant piping and drain
piping.
Q42 The form 7419 for the MBE Program lists several attachments, but the attachments aren’t available on the
website.
A42 The MBE 7419 forms were included with the original solicitation that was posted to PGCPS Purchasing website
and eMarylandMarketplace.
Q43 The Spec Table of Contents lists a number of sections that are not in the specs; are those sections missing or were
they not used? We are missing: 05120, 05210, 05310, 15080, 15700, 15738, 15739, 15840, 15850, and EMS
Temperature Controls.
A43 All listed items on the Specifications Table of Contents have been submitted including Sections 05120, 05210,
05310, 15080, 15700, 15738, 15739, 15840, and 15850.
Q44 Will all of the work during the school year be done during off-hours and weekends? If not, please provide a
placement plan for all of the students for each class and/or room that will be disturbed.
A44 See addendum #2
Q45 There is a conflict between drawings M405 and M602. RTU's and ERU's sequence of operation call for hot gas
reheat and energy recovery wheel. Respective schedules don't show any performance data for those options.
Moreover, there is no cooling capacity for the ERU's. There is no way that an accurate cost could be included in
our bid. Please provide a review.
A43 See revised drawings M-405 and M-602.
Q44 Do you have your own Bid Bond form or can I use the standard AIA Bid Bond form? Please let me know.
A44 Standard AIA Bid Bond Form.
ATTACHMENTS
Revised Bid Form (April 9, 2015)
Reflected Ceiling Plan Ledged revised
Sheet A-001
Sheet A-107 thru A-116
Sheet C-001
Sheet M-001
Sheet M-201E
Sheet M-405
Sheet M-601
Sheet M-602
Sheet M-201E
Bidders must complete, sign, and return two copies of this Addendum on or before bid opening date. Failure to do so
MAY be cause for your offer to be ruled non-responsive and not considered for award.
If your Bid has already been submitted and, because of this Addendum, you desire to modify your offer, you may do so by
letter or email provided such notice makes reference to this Addendum and is received prior to the time specified for
return of Bid.
Donna Parks April 10, 2015 Buyer’s Signature Date
Company Name of Bidder
Signature of Person Authorized to Sign
Address
Type or Print Name and Title
1
SECTION IV
REVISED BID FORM (April 9, 2015) IFB 041-15 Bowie A/C EEI Project
A. BASE BID The total BASE BID, including the cost of all work and the cost of Builder’s All Risk Insurance, which shall be provided separately as informational prices. Please Note: Base bid must include taxes. Vendors are not allowed to submit invoice separately for taxes paid for supplies. Base Bid: (in words) ________________________________________ Total $__________________ BREAKDOWN – Costs for Allowance, Abatement and Phase I-III should be included in base bid as requested below See Cd's and all addenda for phasing plan: ASBESTOS ABATEMENT - DEDUCTIVE ALTERNATE (included in base bid, above): $__________________ PHASE I - [30-May-15 thru 24-Aug-15] (included in base bid, above): $__________________ PHASE II 18-Aug-15 thru 10-Jun-16: (included in base bid, above): $__________________ PHASE III 13-Jun-16 thru 15-Aug-16: (included in base bid, above): $__________________ ALLOWANCE: Allowance (included in base bid, above): $_________250,000.00 TOTAL BASE BID COST $__________________ B. COMPLETION DATE
I/We agree to erect and achieve project completion, no later than August 15, 2016.
2
C. UNIT PRICES - Not applicable D. AFFIDAVIT
______________________________________________ being first duly sworn deposes and says that he is an officer in the building construction organization known as ______________________________________________, and the party making a certain proposal or bid dated ________________________, to the Board of Education of Prince George’s County for the Air Conditioning,EEI at Bowie High School – 15200 Annapolis Road, MD 20715, and that this bid is genuine and not collusive or sham; that said bidder has not colluded, conspired, connived or agreed, directly, or indirectly, with any bidder or person to put in a sham bid or to refrain from bidding, and has not in any manner, directly or indirectly, sought by agreement or collusion, or communication or conference, with any person to fix the bid prices of the affidavit or any other bidder, or to fix any overhead, profit, or cost element of said bid price, or that of any bidder, or to secure any advantage against the Board of Education of Prince George’s County or any other person interested in the proposed contract; and that all statements in said proposal or bid are true. Signature of:
x___________________________________ (Bidder if the bidder is an individual)
x___________________________________
(Bidder if the bidder is a partnership) x___________________________________
(Bidder if the bidder is a corporation) Subscribed and sworn before me this ___day of _______.
x___________________________________ Notary Public
My commission expires: _________________________.
END OF BID FORM
CALLOUT HEAD
DOOR TYPE
KEYNOTE
REVISIONS
WINDOW TYPE
WALL TYPE
101
1
1
SIM
A102 A103
SECTIONS
1t
1
A102A108
ALIGN NOTE
T
R
U
E
N
O
R
T
H
N
1
A102A108
1
A102A108
1
A102A108
BUILDING
SECTIONS
EXTERIOR
ELEVATIONS
1
2
4
2
A-203
INTERIOR
ELEVATIONS
XX
VERT. ELEVATION
VIEW TITLE
GRID SYMBOL
0.00
-
ALIGN
NORTH ARROW
ROOM TITLE
101
ROOM
VOLUME
GRAPHIC SCALE
4 0 4 8
XX
INTERIOR PARTITION
GLAZING
LOW WALL PARTITION
EARTH / COMPACT FILL
POROUS FILL
CONCRETE
CONCRETE MASONRY
UNITS
BRICK
SAND
STONE
STEEL
RIGID INSULATION
BATT INSULATION
GYPSUM WALLBOARD
EXTERIOR SHEATHING /
PLYWOOD
FINISH WOOD
ACOUSTICAL TILE
VINYL TILE
View Name
1/8" = 1'-0"
1
SIM
A102A108
SECTION TITLE
VIEW TITLE
SYMBOLS
GENERAL DEMOLITION FLOOR PLAN NOTES
1. DEMOLITION WORK SHOWN IS BASED ON EXISTING FIELD VERIFIED CONDITIONS.
THE CONTRACTOR SHALL VISUALLY INSPECT ALL EXISTING CONDITIONS AND IS
RESPONSIBLE FOR PERFORMING THE WORK AS INDICATED. IF ACTUAL CONDITIONS
DIFFER FROM CONDITIONS SHOWN ON THE DRAWINGS THE CONTRACTOR SHALL
NOTIFY THE ARCHITECT AND/OR THE OWNERS REPRESENTATIVE.
2. ALL WORK SHOWN IS EXISTING TO REMAIN UNLESS NOTED OR INDICATED AS
DASHED LINES TO BE REMOVED. THE EXTENT OF DEMOLITION SHALL INCLUDE ALL
INCIDENTAL DEMOLITION WORK NECESSARY TO PROVIDE FOR NEW WORK SHOWN
AND SPECIFIED AND SHALL INCLUDE MECHANICAL, ELECTRICAL & PLUMBING ITEMS.
3. ITEMS TO BE DEMOLISHED SHALL BE REMOVED COMPLETELY INCLUDING
ANCHORS, HANGERS, FASTENERS, PIPES, CONDUIT, DUCTS, ETC. uNLESS OTHERWISE
INDICATED TO BE ABANDONED IN PLACE.
4. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR DUST CONTROL AND
MAINTAINING EMERGENCY EGRESS DURING DEMOLITION AND CONSTRUCTION.
5. CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING THE INTEGRITY OF
EXISTING BUILDING ELEMENTS TO REMAIN THROUGHOUT SEQUENCE OF WORK. ANY
DAMAGE TO EXISTING BUILDING CONDITIONS SHOWN TO REMAIN SHALL BE RESTORED
TO NEW CONDITION AT NO ADDITIONAL COST TO THE OWNER.
6. ANY ITEMS NOTED TO BE REMOVED OR DISTRUBED WHICH ARE ASBESTOS
CONTAINING MATERIALS SHALL BE THE RESPONSIBILITY OF THE GENERAL
CONTRACTOR. GENERAL CONTRACTOR SHALL RETAIN AN ABATEMENT CONTRACTOR
FROM THE OWNERS APPROVED ABATEMENT CONTRACTOR LIST . THE GENERAL
CONTRACTOR SHALL NOTIFY THE OWNERS REPRESENTATIVE IF ANY HAZARDOUS
MATERIALS ARE ENCOUNTERED PRIOR TO OR DURING DEMOLITION.
7. GENERAL CONTRACTOR SHALL COORDINATE ALL WORK, LOCATIONS AND DATES
WITH THE OWNERS REPRESENTATIVE PRIOR TO START OF WORK.
8. GENERAL CONTRACTOR SHALL SUPPLY AND COORDINATE LOCATION OF
CONSTRUCTION DUMPSTER WITH OWNER PRIOR TO START OF WORK.
9. THE CONTRACTOR IS DIRECTED TO LOCAL CODES AND BUILDING REGULATIONS
TO FAMILIARIZE THEMSELVES WITH ALL RELATING TO DEMOLITION, INCLUDING, BUT
NOT LIMITED TO THE FOLLOWING: REMOVAL OF DEBRIS RESULTING FROM DEMOLITION,
GENERAL STAGING AND ACCESS TO AND FROM WORK AREA, BUILDING
MANAGEMENT RULES AND REGULATION.
10. REFER TO ALL OTHER DRAWINGS FOR INCIDENTAL DEMOLITION WORK NOT
NOTED ON THE DEMOLITION PLANS.
11. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DEMOLITION AND
REMOVAL OF ALL EXISTING BUILDING COMPONENTS, MATERIALS, EQUIPMENT, AND
APPURTENANCES AS REQUIRED TO BUILD, ERECT, INSTALL, OR ACCOMMODATE ALL
NEW CONSTRUCTION, WITH THE OWNER HAVING FIRST RIGHT OF REFUSAL ON ALL
REMOVED ITEMS.
12 ALL EXISTING SURFACES AND EQUIPMENT TO REMAIN SHALL BE PROTECTED
FROM DAMAGED DURING DEMOLITION AND CONSTRUCTION. THE CONTRACTOR SHALL
BE SOLELY RESPONSIBLE FOR THE REPAIR AND/OR REPLACEMENT OF ANY DAMAGED
DONE BY HIM OR HIS SUB-CONTRACTORS.
13. IF FOUND PROPOSED OR ACTUAL DIMENSIONS, MEASUREMENTS, CEILING
HEIGHTS, ETC. CONFLICT WITH EACH OTHER, THE CONTRACTOR SHALL IMMEDIATELY
CONTACT THE ARCHITECT IN WRITING FOR CLARIFICATION PRIOR TO COMMENCING
WITH THE WORK. THE CONTRACTOR ASSUMES LIABILITY FOR ANY REPAIR OR
RETROFIT CAUSED BY WORK DONE WITHOUT CLARIFICATION.
14. COORDINATE DEMOLITION OF ALL STRUCTURAL ITEMS (COLUMNS, BEAMS,
JOISTS, SLABS, ETC.) WITH STRUCTURAL DRAWINGS. EXTENT OF DEMOLITION SHALL
BE IN ACCORDANCE WITH STRUCTURAL REQUIREMENTS AND COORDINATED WITH ALL
NEW WORK.
16. LINTELS, PORTIONS OF WALLS, ETC., SHALL NOT BE DISTURBED BY DEMOLITION
WORK, UNTIL THEY ARE RE SUPPORTED BY NEW WORK. TEMPORARY STRUCTURAL
SUPPORT INCLUDES SHORING, BRACING AND UNDERPINNING TO EXISTING
STRUCTURE AS REQUIRED.
17. CONC. SLABS TO REMAIN SHALL BE PATCHED, SCRAPED, LEVELED AND
CLEANED TO RECEIVE NEW FLOOR FINISHES. IN AREAS THAT ARE RECEIVING NEW
UNDERGROUND MECHANICAL, PLUMBING, ELECTRICAL OR ADDITIONAL FOUNDATION
WORK, SEE MECHANICAL, PLUMBING, ELECTRICAL AND STRUCTURAL AND
ARCHITECTURAL DRAWINGS TO DETERMINE EXTENT OF REQUIRED CUT AND PATCH OF
EXISTING SLAB. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL
CONC. SLAB DEMOLITION AND REPLACEMENT NECESSARY TO INSTALL THE NEW
WORK. BACK FILL ALL BELOW GRADE DEMOLITION WORK WITH FILL MEETING
STRUCTURAL REQUIREMENTS FOR NEW WORK.
18. CONCRETE SLAB PATCHES SHALL BE FLUSH WITH REMAINING SURFACE AND
MATCH TEXTURE OF EXISTING SURFACE. PATCHES SHALL BE PREPARED TO RECEIVE
NEW FINISHES. FOR PATCH AREAS LARGER THAN (4)FOUR SQUARE FEET PROVIDE
WELDED WIRE MESH.
19. WHERE FINISHES ARE INDICATED TO BE REMOVED, REMOVAL SHALL INCLUDE
GROUT, ADHESIVES, FASTENERS AND OTHER ITEMS USED TO ATTACHED FINISHES
TO THE SURFACES THEY COVER.
GENERAL FLOOR PLAN NOTES:
1. DO NOT SCALE DRAWINGS. IF DIMENSIONS ARE IN QUESTION, THE CONTRACTOR SHALL
BE RESPONSIBLE FOR OBTAINING CLARIFICATION FROM THE ARCHITECT BEFORE
CONTINUING WITH CONSTRUCTION.
2. DIMENSIONS SHOWN ON THE FLOOR PLANS ARE TO FACE OF GYP. BD., MASONRY,
CONCRETE, ETC., UNLESS OTHERWISE INDICATED OR DETAILED AND DO NOT INCLUDE
ANY APPLIED FINISHES. DIMENSIONS TO MASONRY ARE NOMINAL. ROUND OFF FOR WALLS
ARE TO THE NEAREST 1/8" UNLESS NOTED OTHERWISE.
3. FOR FURTHER DIMENSIONING, SEE LARGE SCALE PLANS, SECTIONS, EXTERIOR
ELEVATIONS AND INTERIOR ELEVATIONS.
4. LOCATE ALL DOORS 1'-6" ON THE PULL SIDE OF DOOR AND 1'-0" ON THE PUSH SIDE OF
THE DOOR FROM THE NEAREST PROJECTION. UNLESS OTHERWISE DIMENSIONED ON
PLANS.
5. ALL FIRE-RATED WALLS AND PARTITIONS SHALL EXTEND TO UNDERSIDE OF
CONSTRUCTION ABOVE AND SHALL BE INSTALLED SO AS TO ALLOW 1/2" DEFLECTION IN
STRUCTURE WHILE MAINTAINING THE INTEGRITY OF THE RATING.
6. ITEMS WITH A SURFACE AREA GREATER THAN 16 SQUARE INCHES SHALL NOT BE
RECESSED IN A RATED AND/OR RATED SMOKE WALL.COORDINATE WITH THE OWNERS
VENDORS TO INSURE THAT THERE ARE NO VENDOR FURNISHED ITEMS WITH A SURFACE
AREA GREATER THAN 16 SQUARE INCHES RECESSED IN RATED WALL OR RATED SMOKE
WALL.
7. WHERE A ONE HOUR PARTITION IS SHOWN AS A CONTINUATION OF A TWO-HOUR
PARTITION OR COLUMN ENCASEMENT, THE FACE OF THE GYPSUM BOARD SHALL BE
ALIGNED. STUDS SHALL BE OFFSET AND ADDITIONAL LAYERS OF GYPSUM BOARD SHALL
BE PROVIDED AS REQUIRED TO PROVIDE FACE ALIGNMENT OF GYPSUM.
8. ALL DEVICES INSTALLED IN FIRE-RATED PARTITIONS,FLOORS OR CEILINGS SHALL BE
CONSTRUCTED AS REQUIRED TO MAINTAIN INTEGRITY OF FIRE-RATING.
9. ALL CONCEALED SPACES IN WALLS, COLUMNS ENCLOSURES, BULKHEADS AND SIMILAR
LOCATIONS, NOT COMPLETELY FILLED WITH INSULATION, ARE TO BE FIRE STOPPED AT
THE CEILING LEVEL.
10. REFER TO MISCELLANEOUS DETAILS SHEET FOR TYPICAL DETAILS WHICH MAY APPLY
TO THIS FLOOR PLAN BUT MAY NOT BE SPECIFICALLY KEYED IN ON THIS PLAN OR TO A
SPECIFIC SECTION.
11. ALL GYP. BD. SHALL BE 5/8" THICK. GYPSUM BOARD SHALL EXTEND TO ROOF DECK IN
AREAS OF EXPOSED STRUCTURE. UNLESS NOTED OTHERWISE.
12. SEE REFLECTED CEILING PLAN FOR LOCATIONS OF CEILING FURR DOWNS AND
CEILING MOUNTED ITEMS.
HC.
HOLLOW CORE OR
HANDICAP ACCESSIBLE
WELDED WIRE FABRIC
VINYL COMPOSITION TILE
UNLESS OTHERWISE
NOTED
JANITOR
JANITOR'S CLOSET
HOLLOW METAL
HORIZONTAL
HOUR
HARDWOOD
INCH
HEATING VENTILATING
AND AIR CONDITIONING
INCANDESCENT
IN.
JAN.
JC.
INCAN.
HORIZ.
HDWD.
HR.
HVAC.
H.M.
U.O.N.
W.W.F.
W.
W/O
WT.
W/
WD.
V.C.T.
VERT.
WIDE
WEIGHT
WITHOUT
WOOD
WITH
VERTICAL
PANIC HARDWARE
PROPERTY LINE
PLASTIC LAMINATE
ROUGH OPENING
ELECTRIC WATER COOLER
FIRE EXTINGUISHER CABINET
GYPSUM
GENERAL CONTRACTOR
FLOOR
FLUORESCENT
FIRE HOSE CABINET
GC.
GYP.
F.H.C.
FLUOR.
FLR.
ELECTRICAL
ENCLOSURE
EACH
EXISTING
EXPANSION
EXTERIOR
FINISH FLOOR
EQUAL
EXIST.
F.E.C.
F.F.
EXP.
EXT.
ELEC.
ENC.
E.W.C.
EQ.
EA.
CONCRETE MASONRY UNIT
CORR.
CORRIDOR
DIMENSION
DOOR OPENING
DOWN
DRAWING
DINNING ROOM
D.O.
DWG.
DR
DN.
DIM.
CEILING
COLUMN
CLOSET
CONTINUOUS
CONSTRUCTION
CONCRETE
C.M.U.
CONST.
CONT.
CONC.
CLO.
COL.
CLG.
PLYWD.
REINF.
RESIL.
REQ 'D.
RECEP.
RM
R.O.
R.
R.D.
RAD.
PTD.
RECEPTACLE
REINFORCED
RESILIENT
ROOM
REQUIRED
ROOF DRAIN
RADIUS
RISER
PAINTED
PLYWOOD
P.LAM.
P.L.
PL.
P.H.
PLATE
PNT.PAINT
D
C
E
I
J/K
O
R
W
V
U
JOINTJT.
BLOCK
BOARD
BITUMINOUS
BEAM
BUILDING
BUILT-UP ROOFING
BRICK COURSE
BOTTOM
BLK'G
BC.
B.U.R.
BOT.
BLDG.
BM.
BD.
BIT.
B
ABOVE FINISH FLOOR
ACOUSTICAL CEILING TILE
ADDITIONAL
ALUMINUM
ADJUSTABLE
APPROXIMATELY
AFF
APPX.
ADJ.
ALUM.
ACT.
ADD.
A
CLEARCLR.
COMPRESSIBLECOMP.
CONTROL JOINT
CJ.
CAST-IN-PLACE
CIP.
CAST IRON
C.I.
CHALKBOARD
CBD.
CPT.
CARPET
CRS.
COURSES
CT.
CERAMIC TILE
ELEVATORELEV.
EXPANSION JOINTE.J.
ELEVATIONEL.
EQUIPMENTEQUIP.
FINISHED FLOOR TRANSITIONFFT.
FINISHFIN.
FACE OF CONCRETEFOC.
FACE OF FINISHF.O.F.
GYPSUM WALLBOARD
GLASSG.L.
GWB.
H
HIGH POINT
HEIGHT
HP.
HTG.
HEATERHTR.
INSULATION
INTERIOR
INSUL.
INT.
INCLUDING
INCL.
TOILET PAPER
T.O.C.
T.P.D.
T.O.W.
T.O.B.
TYP.
T.O.S
TR
TEL.
THK.
TH
TOP OF BEAM
TOP OF WALL
TOP OF SLAB
TOP OF CURB
TYPICAL
TELEPHONE
THICK
THRESHOLD
TREAD
TLT.TOILET
T
DISPENSER
ACOUSTICALACOUS.
ARCHITECTURALARCH.
BATHROOM
BA.
BULKHEAD
B.H.
BEDROOM
BR
CATCH BASIN
CB.
CABINET
CAB.
CHANNEL
C
CERAMIC
CER.
CLEARANCECLRE.
D
DEEP
D
DOUBLE
DETAIL
DOWN SPOUT
DRINKING FOUNTAIN
DET .
DBL.
DS.
D.F.
DRAWINGSDWGS
EXISTING
(E)
FINISH FLOOR ELEVATIONF.F.E.
FIXTURE
FLOW LINEF.L.
FIXT.
FACE OF MASONRYFOM.
FT.
FOOT/FEET
FR.
FIRE-RATED
FLOOR UTILITY BOXFUB.
FTG.
FOOTING
KITCHENKIT.
LAVATORYLAV
L
LINEN CLOSETLIN
LOW POINTLP.
LIVING ROOMLR.
MASONRYMAS.
M
MAXIMUMMAX.
GALVANIZED
GAUGE
GALV.
GA.
G
MECHANICALMECH.
MEZZANINEMEZZ.
MANUFACTURERMFR.
MANUFACTURERMFR.
MASONRY OPENING
MOUNTED
MISCELLANEOUS
MIN.
MTD.
M.O.
MISC.
MINIMUM
METAL
MTL.
GALVANIZED
GAUGE
GALV.
GA.
G
NUMBER
NOT IN CONTRACT
N/A
NO.
N.I.C.
NOT APPICABLE
N
OUTSIDE DIAMETER
OWNER FURNISHED
EQUIPMENT
OVERHEAD
ON CENTER
OPG.
O.R.OUTSIDE RADIUS
OPENING
OH.
OA.
OFE
OFF
O.D.
O.C.
OVERALL
OFFICE
P
SHT.
SIM.
SECT.
S.C.
S.D.
SCHED.
SECTION
SHEET
SIMILAR
SOAP DISPENSER
SCHEDULE
SOLID CORE
S
STL.
STOR.
STD.
SPEC.
S.S.
SQ./
STANDARD
STEEL
STORAGE
STAINLESS STEEL
SQUARE
SPECIFICATION
ST.STORIES
FIRE EXTINGUISHERF.E.
F
FLOOR DRAINFD.
FOUNDATIONFDN.
GENERAL DEMOLITION ROOF PLAN NOTES
1. CONTRACTOR IS TO FIELD VERIFY ALL DIMENSIONS.
2. REMOVE GRAVEL, BUILT-UP ROOF MEMBRANE AND FLASHINGS, AND INSULATION
DOWN TO EXISTING METAL DECK.
3. INSPECT METAL DECK FOR AREAS THAT NEED TO BE REPLACED. IN THE EVENT
DAMAGED METAL DECK IS DISCOVERED, PROVIDE A NEW UNIT COST TO OVERLAY
EXISTING METAL DECK WITH NEW DECKING MATCHING EXISTING PROFILE AND
GAUGE
4. REVIEW EXTENT OF DAMAGED DECK WITH OWNER/ ARCHITECT BEFORE
REPLACING
ABBREVIATIONS GENERAL NOTES
GENERAL DEMOLITION REFLECTED CEILING
PLAN NOTES
1. THE CONTRACTOR IS DIRECTED TO LOCAL CODES AND BUILDING REGULATIONS TO
FAMILIARIZE HIMSELF WITH ALL RELATING TO DEMOLITION, BUT NOT LIMITED TO THE
FOLLOWING:
1. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION.
2. USE OF EXISTING CORRIDORS IN OTHER AREAS OF THE BUILDING.
3. GENERAL STAGING AND ACCESS TO AND FROM AREA OF WORK.
4. BUILDING MANAGEMENT RULES AND REGULATIONS.
2. DEMOLISHED AND NON-SALVAGEABLE ITEMS NOT TO BE RE-USED SHALL BE REMOVED
FROM THE THE PREMISES EACH DAY, UNLESS DIRECTED OTHERWISE. REMOVE ITEMS SO
AS TO MINIMIZE DAMAGE TO EXISTING WORK TO REMAIN. REPAIR ALL EXISTING WORK SO
DAMAGED.
2. REMOVE CEILING TILE CAREFULLY. STORE CEILING TILE UNTIL WORK IS COMPLETED,
REINSTALL CAREFULLY. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY TILE THAT IS
DAMAGED BY THIS WORK. IF TILE IS DAMAGED,IT SHALL BE REPLACED BY THE
CONTRACTOR AT NO COST TO THE OWNER. ALL NEW TILE MUST MATCH EXISTING TILE.
3. WHEN CEILING TILE IS REMOVED, TEMPORARILY SUPPORT DEVICES LOCATED IN
CEILING, REINSTALL DEVICES IN REINSTALLED OR NEW CEILING ASSEMBLY.
4. REMOVE CEILING GRID SECTIONS AS NECESSARY TO WORK ABOVE THE CEILING.
REINSTALL.
5. PROVIDE TEMPORARY BARRIERS AS REQUIRED TO ASSURE SAFE CIRCULATION TO
ADJACENT SPACES THAT WILL REMAIN OCCUPIED DURING CONSTRUCTION. FREE AND
CLEAR ACCESS TO EGRESS ELEMENTS MUST BE MAINTAINED THROUGHOUT THE
PROJECT. SEAL ALL HVAC GRILLES AND VAV BOX INTAKES IN AFFECTED WORK AREA AS
REQUIRED. REPLACE ALL AFFECTED HVAC FILTERS AS REQUIRE. COORDINATE WITH
BUILDING MANAGER.
9901 Business Parkway, Suite H
Lanham, Maryland 20706
Ph. No. 301-967-1719 Fax No. 301-967-1766
50155-0005
Project No.
Drawn By:
Checked By:
Scale:
Date:
Sheet Title
Project Name
Sheet Number
Project Adress
Revision
DateDescriptionNo.
SIGN & SEAL“ Professional Certification.: I hereby certify that these documents were prepared or approved by me, and that I am a duly licensed Professional Engineer under the laws of the State of Maryland.License No. 13313, Expiration Date: 2/01/2017."
AS NOTED
PERMIT SET
PERMIT COMMENT
RESPONSES
PEER REVIEW/DGS COMMENTS
BID FINAL
A-001
SYMBOLS, ABBREVIATIONS, AND
GENERAL NOTES
GAH
3
MA
TC
H L
IN
E S
EE
2
/ A
-1
07
DRAFTING # 1
DRAFTING # 2
RE
PR
OD
UC
TIO
N
RM
.
STOR # 2
MATH # 1
TYPING # 1
BUSINESS
ED # 1
BUSINESS
ED # 2
BUSINESS
ED # 3
COST
GIRLS
TOIL.#1
BOYS
TOIL.#1
CO
NF
.
MATH # 2
CO
NF
.
44
49
47
45
43B
41
42
40
43
STOR # 1
DRAFTING # 1B
44B
MA
TC
H L
IN
E S
EE
1
/ A
-1
07
MATH # 5
MATH # 6
COST
GIRLS
TOIL.#1
BOYS
TOIL.#1
CONF.
CONF.
CLASSROOM
# 14
CLASSROOM
# 13
CLASSROOM
# 12
CLASSROOM
# 11
CLASSROOM
# 10
CLASSROOM
# 9
MATH # 7
MATH # 8
CO
NF
.
28-C
CO
NF
.
29-C
29 27 25 23 21
28
26
24
22
20
24-C
22-C
ELEV.
CLG HGHT
8' - 0"
CLG HGHT
9' - 6"
GIR
LS
OU
TS
ID
E
TO
ILE
T
BO
YS
OU
TS
ID
E
TO
ILE
T
GIRLS LOCKER
ROOM
LA
UN
DR
Y
RO
OM
CLOSET
CUST
INSTRUCTORS
OFFICE
SHOWER &
DRESSING ROOM
GIRLS
TOILET
DRYING
ROOM
SHOWER
ROOM
DRESSING
ROOM
STORE
OU
TS
ID
E
ST
OR
AG
E
TOWEL
ROOM
EQ
UIP
ME
NT
ST
OR
AG
E
MECHANICAL
EQUIPMENT
EQ
.E
Q.
EQ
.E
Q.
EQ
.E
Q.
EQ
.E
Q.
EQ
.E
Q.
EQ
.E
Q.
EQ. EQ.
9901 Business Parkway, Suite H
Lanham, Maryland 20706
Ph. No. 301-967-1719 Fax No. 301-967-1766
50155-0005
Project No.
Drawn By:
Checked By:
Scale:
Date:
Sheet Title
Project Name
Sheet Number
Project Adress
Revision
DateDescriptionNo.
SIGN & SEAL“ Professional Certification.: I hereby certify that these documents were prepared or approved by me, and that I am a duly licensed Professional Engineer under the laws of the State of Maryland.License No. 13313, Expiration Date: 2/01/2017."
AS NOTED
PERMIT SET
PERMIT COMMENT
RESPONSES
PEER REVIEW/DGS COMMENTS
BID FINAL
A-107
REFLECTED CEILING PLANS
GROUND FLOOR - PARTS A,B & E
REFLECTED CEILING PLAN - GROUND FLOOR - PART A
REFLECTED CEILING PLAN - GROUND FLOOR - PART B
REFLECTED CEILING PLAN - GROUND FLOOR - PART E
2
2
3
CLG HGHT
9' - 0"
CLG HGHT
9' - 0"
CLG HGHT
9' - 0"
MA
TC
H L
IN
E S
EE
2/ A
-10
8
MATCH LINE SEE 1/ A-109
MATCH LINE SEE1/ A-109
CLG HGHT
9' - 0"
CLG HGHT
9' - 0"
CLG HGHT
9' - 0"
CLG HGHT
9' - 0"
MA
TC
H L
IN
E S
EE
2
/ A
-1
08
MATCH LINE SEE 1/ A-109
MATCH LINE SEE 1/ A-110
9901 Business Parkway, Suite H
Lanham, Maryland 20706
Ph. No. 301-967-1719 Fax No. 301-967-1766
50155-0005
Project No.
Drawn By:
Checked By:
Scale:
Date:
Sheet Title
Project Name
Sheet Number
Project Adress
Revision
DateDescriptionNo.
SIGN & SEAL“ Professional Certification.: I hereby certify that these documents were prepared or approved by me, and that I am a duly licensed Professional Engineer under the laws of the State of Maryland.License No. 13313, Expiration Date: 2/01/2017."
AS NOTED
PERMIT SET
PERMIT COMMENT
RESPONSES
PEER REVIEW/DGS COMMENTS
BID FINAL
A-108
REFLECTED CEILING PLAN - FIRST FLOOR - PART A
REFLECTED CEILING PLAN - FIRST FLOOR - PART B
REFLECTED CEILING PLANS
FIRST FLOOR - PARTS A&B
2
3
CLG HGHT
9' - 0"
CLASS RM.
CLASS RM.
CLASS RM.
BIOLOGY
BIOLOGY
PREP. RM.
PREP. RM.
STORE
STORE
BANK
DARK
RM.
PREP.
RM.
CHEM.
GR
OW
IN
G
RM
.
PHYSICS
DRIVER
TRAINING
DRIVER
TRAINING
BOILER RM.
CA
N W
AS
H
EN
GIN
EE
R
SWBD
KITCHEN
LAUNDRY
REFR.
M.T.
W.T.
OFF.
JAN.
GROWING
RM.
BIOLOGY
PHYSICAL SCI.
132
133
131
130
131S
104
106
105
105-C
CA
N W
AS
H
EN
GIN
EE
R
MA
TC
H LIN
E S
EE
1/ A
-1
10
MATCH LINE
SEE 1/ A-107
MATCH LINE
SEE 3/ A-107
MATCH LINE
SEE 1/ A-107
9901 Business Parkway, Suite H
Lanham, Maryland 20706
Ph. No. 301-967-1719 Fax No. 301-967-1766
50155-0005
Project No.
Drawn By:
Checked By:
Scale:
Date:
Sheet Title
Project Name
Sheet Number
Project Adress
Revision
DateDescriptionNo.
SIGN & SEAL“ Professional Certification.: I hereby certify that these documents were prepared or approved by me, and that I am a duly licensed Professional Engineer under the laws of the State of Maryland.License No. 13313, Expiration Date: 2/01/2017."
AS NOTED
PERMIT SET
PERMIT COMMENT
RESPONSES
PEER REVIEW/DGS COMMENTS
BID FINAL
A-109
REFLECTED CEILING PLAN - FIRST FLOOR (PART C)
REFLECTED CEILING PLAN- FIRST
FLOOR - PART C
2
3
CLG HGHT
11' - 0"
CLG HGHT
9' - 0"
CLG HGHT
9' - 0"
CLG HGHT
9' - 0"
CLG HGHT
11' - 0"
CLG HGHT
9' - 0"
CLASS RM.
CLASS RM.
ST
OR
BUSINESS ED.
TYPING
TYPINGOFFICE
PRACTICE
BANK
BOYS'
TOILET
GIRLS'
TOILET
JAN.
BUSINESS ED.
BOOKKEEPING
HEALTH
WALT.
T. T.
SOUND
VAULT
V.PRIN.
CONF.
CONF.
GUIDANCE
VAULT
PRIN.
STOR.
V.P
RIN
.
T.
GENERAL OFF.
BOYS'
RECOVERY
NURSE
CONF.
GIRLS'
RECOVERY
STUDENT
ACTIVITY
114
112
110
111
113
115
105
103
102
MA
TC
H L
IN
E S
EE
1
/ A
-11
1
MATCH LINE SEE 2/ A-107MA
TC
H L
IN
E S
EE
1
/ A
-1
09
9901 Business Parkway, Suite H
Lanham, Maryland 20706
Ph. No. 301-967-1719 Fax No. 301-967-1766
50155-0005
Project No.
Drawn By:
Checked By:
Scale:
Date:
Sheet Title
Project Name
Sheet Number
Project Adress
Revision
DateDescriptionNo.
SIGN & SEAL“ Professional Certification.: I hereby certify that these documents were prepared or approved by me, and that I am a duly licensed Professional Engineer under the laws of the State of Maryland.License No. 13313, Expiration Date: 2/01/2017."
AS NOTED
PERMIT SET
PERMIT COMMENT
RESPONSES
PEER REVIEW/DGS COMMENTS
BID FINAL
A-110
REFLECTED CEILING PLAN- FIRST
FLOOR - PART D
REFLECTED CEILING PLAN - FIRST FLOOR (PART D)
2
3
CLG HGHT
9' - 0"
CLG HGHT
11' - 0"
CLG HGHT
9' - 0"
CLG HGHT
11' - 0"
CLG HGHT
9' - 0"
EXIST. MECH
EQUIP.
OUT
STORE
STORE
BOYS'
TOIL.
GIRLS'
TOIL.
EXERCISE RMS.
GYM
EQUIP.
TEAM RM.
LOUNDRY
UN
IF
OR
M
DR
YIN
G
UNIFORM
STORE
TO
WE
LS
INSTRUCT
BOYS'
LOCKER
EQUIP.
SHOWERS
DR
YIN
G
T.
T.
GYMNASIUM
MATCH LINE SEE 2/ A-111
MA
TC
H LIN
E S
EE
1/ A
-11
0
EQUIP.
STOR.
GIRLS' GYMNASIUM
MATCH LINE SEE 2/ A-111
MA
TC
H L
IN
E S
EE
1/ A
-11
0
9901 Business Parkway, Suite H
Lanham, Maryland 20706
Ph. No. 301-967-1719 Fax No. 301-967-1766
50155-0005
Project No.
Drawn By:
Checked By:
Scale:
Date:
Sheet Title
Project Name
Sheet Number
Project Adress
Revision
DateDescriptionNo.
SIGN & SEAL“ Professional Certification.: I hereby certify that these documents were prepared or approved by me, and that I am a duly licensed Professional Engineer under the laws of the State of Maryland.License No. 13313, Expiration Date: 2/01/2017."
AS NOTED
PERMIT SET
PERMIT COMMENT
RESPONSES
PEER REVIEW/DGS COMMENTS
BID FINAL
A-111
REFLECTED CEILING PLAN - FIRST FLOOR - PART E (SOUTH)
REFLECTED CEILING PLANS
FIRST FLOOR - PARTS E
REFLECTED CEILING PLAN - FIRST FLOOR - PART E (NORTH)
2
2
2
2
STOR
SERV'G
AREA
DISH
WASH
SERVING
AREA
CAFETERIA
SN
AC
K B
AR
CH
AIR
ST
OR
E
STAGE
FOUNDRY
METAL SHOP
PROJECT
STOR.
TOOL &
STOCK
GRAPHIC ARTS
WOOD SHOP
J.T. T.
TOOL &
SUPPLY
STORAGE
STORAGE
TR
AN
S M
IT
'
ELECTRONICS
SHOP
PRACTICE
(FORMERLY STORAGE)
MU
SIC
C
.R
.
(F
OR
ME
RLY
DR
AF
TIN
G R
M.)
ST
OR
AG
E (F
OR
ME
RLY
RE
PR
OD
UC
TIO
N R
M.)
ST.
MUSIC
MUSIC
LIBR.
BAND
INSTR.
STOR.
PRACTICE
GIRLS TOILET
SNACK BAR
COMMONS AND
LUNCH ROOMS
BOYS TOILET
155
156
154
154S
152A
152B
150
153
151
151S
LO
DIN
G
DO
CK
OFFICE
OFFICE
MATCH LINE SEE 1/ B-108
9901 Business Parkway, Suite H
Lanham, Maryland 20706
Ph. No. 301-967-1719 Fax No. 301-967-1766
50155-0005
Project No.
Drawn By:
Checked By:
Scale:
Date:
Sheet Title
Project Name
Sheet Number
Project Adress
Revision
DateDescriptionNo.
SIGN & SEAL“ Professional Certification.: I hereby certify that these documents were prepared or approved by me, and that I am a duly licensed Professional Engineer under the laws of the State of Maryland.License No. 13313, Expiration Date: 2/01/2017."
AS NOTED
PERMIT SET
PERMIT COMMENT
RESPONSES
PEER REVIEW/DGS COMMENTS
BID FINAL
A-112
REFLECTED CEILING PLANS - FIRST
FLOOR - PART F
REFLECTED CEILING PLAN - FIRST FLOOR - PART F
2
2
3
CLASS RM.
CLASS RM.
READING &
STUDY
SKILLS
BIOLOGY
BIOLOGY
PREP. RM.
ST
OR
AG
E
GIRLS TOIL.BOYS TOIL.
CUST.
CO
NF
.
MATHCLASS RM.
CLASS RM. CLASS RM.
STUDENT
ACTIVITY
CONF.
CONF.
VICE
PRIN.
VICE
PRIN.
CO
NF
.
STUDY RM.
STR.
GUIDANCE
OFF.
OFF.
OFF.
249
247
245243
241
248
246
244
242
247-C
245-C
242S
242-C
240
MA
TC
H L
IN
E S
EE
1
/ A
-1
09
MATCH LINE SEE 1/ A-110MATCH LINE SEE 1/ A-110
CLASS RM.
CLASS RM.
PHYSICS LAB
PR
EP
.
RM
.
STORAGE
CO
NF
.
GIRLS
TOIL.
BOYS
TOIL.
CUST.
HOMES ECONOMICS
LANGUAGE LAB
ADMIN
OFFICE
VIC
E
PR
IN
.
T.
GUIDANCE
OFF.
OFF.
LA
NG
UA
GE
ST
OR
E
PH
YS
IC
AL S
CIE
NC
E
ART
AR
T S
TO
RE
CHEM STORE
FOOD STORE
FURN. STORE
224
225
223
221
222
220
222S
214
CO
NF
.
STAIR #4
MA
TC
H L
IN
E S
EE
1
/ A
-10
9
MATCH LINE SEE 1/ A-110 MATCH LINE SEE 1/ A-110
9901 Business Parkway, Suite H
Lanham, Maryland 20706
Ph. No. 301-967-1719 Fax No. 301-967-1766
50155-0005
Project No.
Drawn By:
Checked By:
Scale:
Date:
Sheet Title
Project Name
Sheet Number
Project Adress
Revision
DateDescriptionNo.
SIGN & SEAL“ Professional Certification.: I hereby certify that these documents were prepared or approved by me, and that I am a duly licensed Professional Engineer under the laws of the State of Maryland.License No. 13313, Expiration Date: 2/01/2017."
AS NOTED
PERMIT SET
PERMIT COMMENT
RESPONSES
PEER REVIEW/DGS COMMENTS
BID FINAL
A-113
REFLECTED CEILING PLANS
SECOND FLOOR - PARTS A&B
REFLECTED CEILING PLAN - SECOND FLOOR - PART A
REFLECTED CEILING PLAN - SECOND FLOOR- PART B
2
3
CLG HGHT
8' - 0"
CLG HGHT
9' - 6"
CLG HGHT
10' - 0"
CLG HGHT
9' - 0"
READING &
CLASS RM.
TOILET
#2
TEACHERS
ART #1
STORAGE #2
STOR
STOR #8
FOODS
ART
STORAGE
STORAGE #1
KIT.
HOME
MANAGEMENT
LANGUAGE LAB
CUST.
WORKTOILET
#1
GIRLS
TOIL.
BOYS
TOIL.
LO
CK
ER
S
#2
LAUNDRY
CLOTHING
233
231
232
232S
230S
230
209
LOCKERS
#1
LAUNDRY
STOR #9
T.
#3
MATCH LINE SEE 1/ A-109
MA
TC
H LIN
E S
EE
1/ A
-1
10
MATCH LINE SEE 1/ A-111
9901 Business Parkway, Suite H
Lanham, Maryland 20706
Ph. No. 301-967-1719 Fax No. 301-967-1766
50155-0005
Project No.
Drawn By:
Checked By:
Scale:
Date:
Sheet Title
Project Name
Sheet Number
Project Adress
Revision
DateDescriptionNo.
SIGN & SEAL“ Professional Certification.: I hereby certify that these documents were prepared or approved by me, and that I am a duly licensed Professional Engineer under the laws of the State of Maryland.License No. 13313, Expiration Date: 2/01/2017."
AS NOTED
PERMIT SET
PERMIT COMMENT
RESPONSES
PEER REVIEW/DGS COMMENTS
BID FINAL
A-114
REFLECTED CEILING PLAN - SECOND FLOOR (PART C)
REFLECTED CEILING PLAN-
SECOND FLOOR - PART C
2
3
CLG HGHT
10' - 0"
CLG HGHT
9' - 0"
CLG HGHT
9' - 0"
CLG HGHT
10' - 0"
CLG HGHT
10' - 0"
STOR.
OF
F.
TEACHERS
LIBRARY
AUDIO VISUAL
MEDIA CENTER
LIBRARY C.R.
250
LOCKERS
#1
STAIR #7
MATCH LINE SEE 2/ A-111
CLG HGHT
9' - 0"
CLASS RM.
STOR
STOR.
MATH
CLASS RM.
MATH
MATH
MATH
LANGUAGE LAB
LANGUAGE STORE
TOILET
#1
WORK
C.R.
C.R.
C.R.
C.R.
STOR.
CONF.
JAN.
GIRLS TOILET
BOYS TOILET
STUDENT
ACTIVITY
C.R.
C.R.
C.R.
AUDIO VISUAL
LIBRARY WORK RM.
214
215
213
211
212
210
209
S-6
201
203
205
207
S-5
200
202
204
206
206-C
LOCKERS
#1
CO
NF
.
STAIR #5
STAIR #3
STAIR #4
MA
TC
H L
IN
E S
EE
1
/ A
-11
2
MATCH LINE SEE 1/ A-111
MATCH LINE SEE 2/ A-209
MA
TC
H L
IN
E S
EE
1
/ A
-1
10
9901 Business Parkway, Suite H
Lanham, Maryland 20706
Ph. No. 301-967-1719 Fax No. 301-967-1766
50155-0005
Project No.
Drawn By:
Checked By:
Scale:
Date:
Sheet Title
Project Name
Sheet Number
Project Adress
Revision
DateDescriptionNo.
SIGN & SEAL“ Professional Certification.: I hereby certify that these documents were prepared or approved by me, and that I am a duly licensed Professional Engineer under the laws of the State of Maryland.License No. 13313, Expiration Date: 2/01/2017."
AS NOTED
PERMIT SET
PERMIT COMMENT
RESPONSES
PEER REVIEW/DGS COMMENTS
BID FINAL
A-115
REFLECTED CEILING PLAN-
SECOND FLOOR - PART D
REFLECTED CEILING PLAN - SECOND FLOOR (NORTH)REFLECTED CEILING PLAN - SECOND FLOOR (SOUTH)
2
3
BOTT. BEAM (TYP.)
22'-9"
RIDGE OF CONC.
BEAM (TYP.)
27 - 5"
BOTT. BEAM (TYP.)
22' - 9"
RIDGE OF CONC.
BEAM (TYP.)
27' - 5"
STORAGE
DRESSING
SHOWERS DRYING
BOY'S LOCKER
TOWELS
INST.
T.
UPPER PART
OF GYM
MATCH LINE SEE 2/ A-112
MA
TC
H L
IN
E S
EE
2
/ A
-11
1
EQ
.E
Q.
EQ
.E
Q.
EQ
.E
Q.
3'-6
"
2'-4"
UPPER PART
OF GIRLS GYM
MATCH LINE SEE 1/ A-112
9901 Business Parkway, Suite H
Lanham, Maryland 20706
Ph. No. 301-967-1719 Fax No. 301-967-1766
50155-0005
Project No.
Drawn By:
Checked By:
Scale:
Date:
Sheet Title
Project Name
Sheet Number
Project Adress
Revision
DateDescriptionNo.
SIGN & SEAL“ Professional Certification.: I hereby certify that these documents were prepared or approved by me, and that I am a duly licensed Professional Engineer under the laws of the State of Maryland.License No. 13313, Expiration Date: 2/01/2017."
AS NOTED
PERMIT SET
PERMIT COMMENT
RESPONSES
PEER REVIEW/DGS COMMENTS
BID FINAL
A-116
REFLECTED CEILING PLAN - SECOND FLOOR - PART E (SOUTH)
REFLECTED CEILING PLANS
SECOND FLOOR - PART E
REFLECTED CEILING PLAN - SECOND FLOOR - PART E (NORTH)
2
3