Alat Penukar Kalor Tipe Shell and Tube
Click here to load reader
Transcript of Alat Penukar Kalor Tipe Shell and Tube
8/19/2019 Alat Penukar Kalor Tipe Shell and Tube
http://slidepdf.com/reader/full/alat-penukar-kalor-tipe-shell-and-tube 1/7
1. Saturated process steam at 1 atm is condensed in a shell-and-tube heat exchanger (one
shell, two tube passes). Cooling water enters the tubes at 15◦C with an average velocity of
3.5 m/s. The tubes are thin walled and made of copper with a diameter of 14 mm and
length of 0.5 m. The convective heat transfer coefficient for condensation on the outer
surface of the tubes is 21800 W/m
2
K.a. Find the number of tubes/pass required to condensed 2.3 kg/s of steam
b. Find the outlet water temperature.
c.
Find the maximum possible condensation rate that could be achieved with this heat
exchanger using the same water flow rate and inlet temperature.
Diketahui :
Saturated steam (Uap Saturasi): Water:
Pc = 1 atm
D = 14 mm = 0.014 m
L = 0.5 m
Ditanya : a. N
b.
c.
Penyelesaian :
Analisa Data
Untuk tabel saturated steam, gunakan tabel saturated water pada P = 1atm:Tsat = 100◦C hfg = 2257 KJ/kg
Asumsi :
T V.10 Cp µ.10 λ.10 Pr
295 1.002 4181 959 606 6.62
Tabel 1. Analisa Data
X
Tce
Tcs
Tce
Tfs
Tcs
Tfs
TfeT
fe = 15◦C
ℎ0
T
8/19/2019 Alat Penukar Kalor Tipe Shell and Tube
http://slidepdf.com/reader/full/alat-penukar-kalor-tipe-shell-and-tube 2/7
Mencari laju perpindahan panas :
ℎ
Mencari Tfs dengan metode NTU
1. Mencari koefisien panas menyeluruh (k)
Karena ReD >10000, maka aliran yang terjadi adalah aliran turbulen. Oleh karena itu,
dapat kita gunakan rumus
Nu = 0.023 .ReD
0.8
.Pr
1/3
0
0
Mencari nilai k
Setelah mendapatkan faktor pengotoran menyeluruh maka dicari nilai k :
8/19/2019 Alat Penukar Kalor Tipe Shell and Tube
http://slidepdf.com/reader/full/alat-penukar-kalor-tipe-shell-and-tube 3/7
2. Relasi efektifitas : Dengan Cmin = Cf dan
Maka :
Menghitung nilai NTU
(As = πDLNP)
Dari persamaaan Flow Arrangement: (Cr = 0) , maka :
E = 1 – exp(-NTU)
E = 1 – exp(-0.048)
E = 0.0468
Maka dapat kita hitung jumlah tabung (N) :
Jadi :
8/19/2019 Alat Penukar Kalor Tipe Shell and Tube
http://slidepdf.com/reader/full/alat-penukar-kalor-tipe-shell-and-tube 4/7
Mencari Suhu keluar air :
Kita dapatkan nilai Tfs tidak sama dengan nilai dari asumsi, oleh karena itu, perhitungan
dilanjutkan ke iterasi kedua.
Iterasi II
Analisa Data
Asumsi :
Maka :
T V.10 Cp µ.10 λ.10 Pr
290 Vf Cpf µf λ f Pr f
Tabel 2. Analisa Data Iterasi II
Mencari laju perpindahan panas :
ℎ
Mencari Tfs dengan metode NTU
1. Mencari koefisien panas menyeluruh (k)
00 0 000
Karena ReD >10000, maka aliran yang terjadi adalah aliran turbulen. Oleh karena
itu, dapat kita gunakan rumus:
Nu = 0.023 .ReD0.8
.Pr1/3
8/19/2019 Alat Penukar Kalor Tipe Shell and Tube
http://slidepdf.com/reader/full/alat-penukar-kalor-tipe-shell-and-tube 5/7
0
0
Mencari nilai k
Setelah mendapatkan faktor pengotoran menyeluruh maka dicari nilai k :
Relasi efektifitas : Dengan Cmin = Cf dan
Maka :
8/19/2019 Alat Penukar Kalor Tipe Shell and Tube
http://slidepdf.com/reader/full/alat-penukar-kalor-tipe-shell-and-tube 6/7
Menghitung Nilai NTU
As = πDLNP
2
Dari persamaaan Flow Arrangement: (Cr = 0), maka:
E = 1 – exp(-NTU)
E = 1 – exp(-)
E = 0.046
Sehingga didapatkan jumlah tabung (N)
Jadi :
Mencari Suhu keluar air :
Kita dapatkan suhu Tfs hasil iterasi kedua sama dengan Tfs hasil iterasi pertama, oleh
karena itu asumsi pada iterasi kedua adalah benar.
8/19/2019 Alat Penukar Kalor Tipe Shell and Tube
http://slidepdf.com/reader/full/alat-penukar-kalor-tipe-shell-and-tube 7/7
Dengan itu, dapat kita simpulkan:
a. Jumlah tabung yang diperlukan untuk mengkondensasikan Uap Saturasi dengan laju
aliran massa 2.3kg/s dengan pengaruh faktor pengotoran (Fouling Factor) adalah
sebanyak :
N = 590 tabung
b.
Maka, kita dapatkan suhu keluar fluida dingin sebesar:
c. Maka, kita dapatkan nilai laju aliran massa maksimum uap adalah sebesar:
ℎ
ℎ