AirCon Training Manual

download AirCon Training Manual

of 175

Transcript of AirCon Training Manual

  • 8/17/2019 AirCon Training Manual

    1/175

    1

    CONTENTS

    1. General Discription of Air Conditioner ...................................................................2

    2. Refrigerant Cycle....................................................................................................9

    3. Installation .............................................................................................................11

    4. Window Type Room Air Conditioner....................................................................34

    5. Split Type Room Air Conditioner..........................................................................48

    6. Packaged Type Air Conditioner............................................................................90

    7. Control And Electrionics Part .............................................................................100

    8. Method Of Main quality Service.........................................................................123

    9. The Others And References..............................................................................143

    Contents

  • 8/17/2019 AirCon Training Manual

    2/175

    2

    1. GENERAL DISCRIPTION OF AIR CONDITIONER

    1. TYPE OF AIR CONDITIONER

    1-1. Classification according to funciton

    Cooling

    Cooling + Heating (Electric heater)

    Cooling + Heatig (Heat pump)

    1-2. Classification according to installation type

    Window Window

    Skinny

    PTAC

    Split SplitFloor

    Multi

    Ceiling

    Duct

    Convertible

    Multi

  • 8/17/2019 AirCon Training Manual

    3/175

    3

    2. EXPLANATION OF TERMINOLOGY

    1)Air Conditioning:

    Keeping room air in an optimum condition, depending on the use or purpose. (Cooling, heating, humidity regulatiog,air cleaning, etc.)

    2) Cooling (Heating) capacity:

    Calorie which is able to be released (or added) per a unit time in room. It is expressed in Kcal/h, BTU/h, W or RT

    3)Humidity

    (1) Absolute humidity: The amount of vapor contained in the air. Generally it is equal to the amount of vapor by g unitcontained in 1m3 air, and is expressed in g/m3.

    (2) Relative humidity: The ratio between the amount of vapor contained in the air and the maximum amount (theamout of saturated vapor) of vapor capable of containing at that temperature in %.

    *Relative humidity= Actual vapor pressure/Saturated vapor pressure x 100= Actual vapor pressure of dew point temperature/saturated vapor pressure of dry-dulb temp.

    x 100(3) Dew point temperature: The surface temperature which starts dewing on the surface when it is cooled in the air.

    4) Heat

    (1) Latent heat and sensible heat:Heat which causes a change in the state of a substance, with its temperature being constant, is called latent heatwhereas heat which changes the temperature of a substance is called sensible heat. Latent heat is expressed interms of calories needed to cause a change of state of a substance per 1 kg. The following equation shows that QKcal is needed to change state of a substance weight G Kg when the latent heat is L Kcal/kg. (Q=GL)

    (2) Thermal flow1 Radiation : A phenomenon which termal energy as an electro-magnetic wave is transmitted directly from a

    thermal source.2 Conduction : A phenomenon which transmits from high to low temperature when there is a temperature

    difference partially in a substance.3 Convection : When the temperature of a fluid like gas or liquid changes by heat, the high temperature part

    expands and thus the density drops to cause to be light whereas the low themperature part is tobe heavy. It means a phenomenon that heat is transmitted together when floating happens by the

    weight difference of air.

    Three states of a substance

  • 8/17/2019 AirCon Training Manual

    4/175

    4

    5) Quantity of heat

    (1) Kcal: Adding or releasing heat to or from a substance changes its temperature. This change of temperature is inproportion the heat added or released This heat is called calorie which is expressed in Kcal or cal. 1 Kcal isequal to the amount of heat required to raise the 1˚C Temperature of 1kg water 4˚C.

    (2) BTU: 1 BTU is equal to the amount of heat required to raise the 1˚F temperature of 1 lb water.•1 Kcal=3.968 BTU, 1 BTU=0.252 Kcal

    6) Refrigerating Ton (RT):• 1 RT is equal to the capacity which makes 1 Ton water 0˚C into ice 0˚C in 24 hours. It is expressed in calorie

    required to freeze water 1 Ton water 32˚F(200 lb) into ice 32˚F, and when using the solidification latent heat ofwater, 1RT is as follows

    • 1 RT= 144BTU/lb x 200 lb/24hr = 12,000 BTU/lb = 3,024 Kcal/h = 3.517 KW

    7)Pressure:

    Pressure p is the normal (perpendicular) force exerted by a fluid per unit area against which the force is exerted.Absolute pressure is the measure of pressure above zero; gauge pressure is measured above existing atmosphericpressure. the unit used for pressure is newtons per square meter (N/m 2), also called a pascal (Pa). The newton is aunit of force. Standard atmospheric pressure is 101,325 Pa=101.3 kPa.

    8) Specific heat:

    The specific heat of a substance is the quantity of energy required to raise the temperature of a unit mass by 1 K.

    9) Horse Power(Hp)

    • 1 Hp = 0.75 KW = 645 Kcal/h, 1W = 086 Kcal/h

    10) Conversion of unit

    (1) Temperature conversion (˚C ˚F)• ˚F = 9/5˚C + 32, ˚C = 5/9(˚F-32)

    (2) Area or volume conversion

    • 1m

    2

    = 10.764 ft

    2

    , 1m

    3

    = 35.3165ft

    3

    (3) Weight conversion• 1Kg = 2.2 lb, 1 lb = 0.45 Kg

    (4) Unit conversion table

    Classification

    1BTU/h

    1Kcal/h

    1W

    1KJ

    1Hp

    1RT

    BUT/h

    1

    3.968

    3.413

    0.948

    2559

    12000

    Kcal/h

    0.252

    1

    0.86

    0.239

    645

    3024

    W

    0.293

    1.163

    1

    0.278

    750

    3516

    KJ

    1.055

    4.186

    3.601

    1

    2700

    12660

    Hp

    0.00039

    0.00155

    0.00133

    0.00037

    1

    4.68

    RT

    0.000083

    0.000329

    0.000283

    0.000079

    0.212

    1

  • 8/17/2019 AirCon Training Manual

    5/175

    5

    11) Compressor:

    Absorb and compress the low pressure gasified refrigerant in evaporator and let it flow into condenser. At this time,the low pressure is to be kept in evaporator and the refrigerant gas flows into condenser as high pressure condition.The most economical condition of compressor for an proper operating is when the refrigerant gas absorbed intocompressor is in dry-saturated condition. The overly-heated suction gas may cause the mechanical ability ocompressor to be reduced and the cylinder clearance of compressor to be re-expanded, and as a result, therefrigerant may be used without its refrigerating effect. The types of compressor is Recipro. type, Rotary type, Scroll

    type, Screw type, etc. and consists of cylinder, piston, vane, shaft, bearing, case and accumulator for structurereason.

    12) Condenser:

    The high temperature/high pressure refrigerant gas compressed by compressor is sucked into condenser andliquified by cooling. The condenser is cooled by the forced-convection of fan. The calorie emitted from condenser isequal to the sum of the heat absorbed in evaporator and the calorie used for compressor operationg.

    13) Evaporator:

    Absorb the heat from room air by forced-convectionThe liquid refrigerant in evaporator is evaporated by absorbing heat from room air and flowed into compressor as a

    gasified state. The evaporating temperature of refrigerant is decided by pressure, which is decided by thetemperature of suction air and the wind flow, and the pressure in evaporator is normally 5Kg/cm2G and theevaporating temperature is 5~8˚C

    14) Capillary (Expansion Valve):

    Regulate the refrigerant flow into evaporator get, lower the pressure of refrigerant, and lead it into a liquid of lowtemperature and low pressure. The type of capillary is generally a thin and long copper tube of 0.6~2.0mm2 innerdiameter and 1~2m long. The resistance of tube causes to turn into a liquid of low pressure and low temperature.

    15) Dryer:

    Any moisture in refrigerating cycle may cause the compressor motor to be damaged or turn into an ice state it selfin the middle of cycle, which blocks the flow of refrigerant. Dryer is installed in a cycle for the purpose of removing

    such moisture.There are two types of dryer; a liquid line dryer which is connected serially to the condenser outlet and a suction linedryer which is connected serially to the suction line, with a desiccative in dryer.The dryer is designed for uni-directional flowing of the refrigerant.

    16) Strainer:

    Strainer serves to remove foreign substances from refrigerant by a metal net pelt of fine grid or a glass wool beinginserted into metal vessel and refrigerant being passed through between the interval. The mounted position isbetween condenser and capillary expansion valve.

    17) Service valve:

    Service valve is used for vacuum working and refrigerant filling. Front seat is called a state which cap is opened andvalve is completely rotated clockwise and refrigerant stops flowing in that condition, whereas back seat is called astate which valve is totated completely counter-clockwise and refrigerant flows. In case of pressure measurementsor vacuum work form service valve, the back seat condition is changed into some fornt seat condition. Product isreleased in front seat condition, so the back seat by brake-in is not needed.

    18) Motor:

    Generates a rotating force by electric power and supply the driving force to fan and blower in both indoor andoutdoor of air conditioner.

  • 8/17/2019 AirCon Training Manual

    6/175

    6

    19) Fan:

    Generates forced air flow. The forced air passes throngh heat-exchanger and blow out the heat (or give the heat onthe contrary) from heat-exchanger.A Fan can be classified by axial fan and radial fan. Generally we call axial fan (mostly propellar fan) as (Fan).

    20) Blower (Cross Flow Fan: C.F.F):

    A kind of Fan. It also generates forced air flow and air flows cross over axis of FanBlower is placed indoor unit, so a small size, high wind flow and low noise type is used.

    21) Thermostat:

    Sense the temperature of air or heat exchangers and controlls automatically room temperature by switchingcompressor on/off depending on temperature. Thermostat is used for a mechanical type model and thermistor for amicom type control method.

    22) Capacitor:

    Get shift the phase of input electricity for compressor or fan motor, which leads starting direction and torque to thecompressor motor or fan motor for aircon and make the operating efficiency better during operation.

    23) Over load protector (O.L.P):A protective device of automatic retrip type which is placed in the compressor and trip(cut) off the power ofcompressor moto against the overheat and overcurrent of compressor.At this time, compressor stopps operating by power off and only fan is on work. Generally the trip temperature isaround 120°C and the return thmperature is around 90°C.

    24) High pressure switch(H.P.S/W):

    A protective device of automatic return type which protects compressor and the discharge pipes from overload bysensing the discharge pressure of compressor, working at an abnormal high temperature, and shutting off theelectric circuit. Generally the working pressure is around 28kg/cm2G and the return pressure is 23 kg/cm2G.

    25) Accumulator:A kind of liquid refrigerant separator which prevents the liquid refrigerant getting into compressor and is installed inthe suction inlet of compressor.

    26) Reversing valve (4 way valve):

    Convert the flow of refrigerant upon cooling/heating switch-over, electrically power on when heating and off whencooling, be installed in outdoor, and have four connecting valves as shown in the name. The refrigerant passingthrough compressor always flows to a constant direction and is able to reverse-operate completely the refrigeratingcycle of both cooling and heating by a reversing valve. Consist of reversing valve and solenoid valve. The mainvalve in reversing valve uses a nylon resin which is deformed by heat 120˚C or over and thus causes valve not towork, so be cautious while operating or when welding.

    27) Check valve:Prevent refrigerant from reverse flow in refrigerating cycle. It is installed in a place where it is necessary to preventthe reverse flow of refrigerant in a copper pipe. It has a mechanical structure and attached to the opposite of aheating capillary to expand the heating/cooling model by two speeds, and is constructed so as to flow throughcapillary in heating and through the check valve in cooling only.

    28) Solenoid valve

    Regulate the refrigerant flow by refrigerant on/off in cycle which refrigerant flows according as the valve operatesthrough a coil unit being powered on. Mainly it is used when reversing the 4 way valve of a cooling/heating model orconstruction each unit cycle of multi model.

  • 8/17/2019 AirCon Training Manual

    7/175

    7

    3. PRINCIPLE OF OPERATING AIR-CONDITIONER

    1) Four elements of air conditioning

    (1) Temperature:The dry-bulb temperature by cooling or heating room air.

    (2) Humidity:

    A comfortable humidity condition of room air is generally kept by the relative humidity of air, and the room air iscontrolled into a given relative humidity condition.

    (3) The degree of purity:Remove dusts in the air, and keep smoke from exceeding the allowable degree of concentration.

    (4) Air flow:To disperse properly the air regulated in temperature, humidity and the degree of purity into indoor, make anappropriate air flow and keep uniformaly the temperature/humidity condition of room unit.

    •Satandard for feeling comfortable

    2) Principle of cooling Air-Conditioner

    • Sprinkling with water in summer cause to cool surroundings because water absorbs the heat of surroundings• Gasifying a liquid (R-22) which is easier to evaporate than water cooler because water evaporates at 100˚C under

    1 atmosphere but freon gas (R-22) does a very low temperature of -40°C.• It is an Aircon that the principle is used for

    (1) Elements of Aircon

    ClassificationTemperature

    Relative humidity

    Air flow

    Summer21 ~ 28˚C

    30 ~ 30%

    0.2m/s or less

    Winter20 ~ 24˚C

    30 ~ 60%

    0.2m/s or less

    Cooling

    1 Compressor

    2 Condensor

    3 Evaporator

    4 Expansion valve

    Cooling + Heating(Heat pump)

    1 Compressor

    2 Condensor

    3 Evaporator

    4 Expansion valve

    5 4Way valve

  • 8/17/2019 AirCon Training Manual

    8/175

    8

    • Heat pump: Convert the flow of refrigerant (freon

    gas) upon Coooling/ Heating by 4way valve.

    • In colling operation, the flow of freon gas is same

    as above, (4Way valve:electrically power off)

    • The flow of freon gas

    1 2 3 4 5

    • Heat pump: Convert the flow of refrigerant (freon

    gas) upon Coooling/ Heating by 4way valve.

    • In Heating operation, the flow of freon gas is

    reverse-operate completely by 4 way valve.

    (4way valve: electrically power ON)

    • The flow of freon gass

    1 2 3 4 5

    Evaporator4

    Condensor2

    3

    1

    Room AirOutside Air

    Compressor

    Expansionvalve

    Indoor Outdoor

    CooledAir Hot discharged Air

    Heat Exchanger(evaporator)

    Heat Exchanger(Condensor)

    2

    3

    4

    1

    5

    Room Air

    4Way valve

    Cooled Air

    Indoor Outdoor

    Hot discharged Air

    Outside Air

    Compressor

    Expansionvalve

    Compressor

    Heat Exchanger(Condensor)

    Heat Exchanger(evaporator)

    4

    3

    3

    15

    Room Air

    4Way valve

    Hot discharged Air

    Indoor Outdoor

    Cooled Air

    Outside Air

    Compressor

    Expansionvalve

    Compressor

    (2) Principle of operating

    • Cooling

    1 The low pressure freon gas is compressed incompressor and flow into condensor.

    2 In condensor freon gas emits the heat by forced-convection fan and liquified by cooling.

    3 Liquid passed through the expansion valve is spoutedin evaporator.4 Liquid in evaporator absorbs the heat from room air by

    forced-convection fan and flowed into compressor as agasified state.

    5 This circulation repeats (1~4)

  • 8/17/2019 AirCon Training Manual

    9/175

    9

    2. REFRIGERANT CYCLE1. REFRIGERATING CYCLE

    Service valve

    Room Air Conditioner

    (Cycle of refrigeration)

    Service valve

  • 8/17/2019 AirCon Training Manual

    10/175

    10

    2. THE PRINCIPLE OF REFRIGERATING CYCLE

    ¡

    fl

    The role of each cycle

    1) Compression:The gasified refrigerant evaporated is absorbed into compressor through the suction pipe, and the compressed by apiston in cylinder and turned into a gas of high temperature and high pressure which is able to be liquified in a roomtemperature.

    2)Liquification:

    The gas of high temperature and high pressure in compressor is cooled by air in condenser and liquified by acondensing heat.

    3)Expansion:

    With passing through the capillary tube, the high pressure refrigerant liquified in condenser turns into a low pressurecondition, which is easy to evaporate.

    4)Evaporation:

    The liquid refrigerant of low temperature and low pressure passed though the capillary tube absorbs the room air heatin evaporator and evaporates into a gas.

    Low pressGas

    Compression

    (Mid. Temp)

    Compressor

    High PressGas

    Liquification

    (Hi. Temp)

    Emission Cooledd Air

    Hot discharged Air Absorbing

    Condensor

    High PressLiquid

    Expansion

    (Hi. Temp)

    Capillary

    Low pressLiquid

    Evaporation

    (Low. Temp)

    Evaporator

    Low pressGas

    (Mid. Temp)

  • 8/17/2019 AirCon Training Manual

    11/175

    11

    3. INSTALLATION1. INSTALLATION PROCEDURE

    Select the location

    Check and Caution

    OK

    YES

    YES

    YES

    YES

    Set Return

    Refrigerant pipe andDrain pipe connections

    Wiring

    Test running

    Insulation and Final Work

    Check and Caution

    OK

    Check and Caution

    OK

    Check and Caution

    OK

    YES

    Check and Caution

    END

    OK

    1. Check the piping hole2. Select the distance in pipe length3. Vaccum and Air pauge4. Decide the refregerant suplement refill5. Check the leakage

    1. Check the power of Aircon2. Install a leakage braker3. Check the power capacity4. Check the location of earth

    1. Check the power source2. Check the leakage

    3. Check the pressure4. Check the running current

    YES

    Check and Caution

    OK

    1. Check the construction of drain part2. Check the insulation3. Check the operating of set4. Explain to customer

    1. Check the Environment2. Check the capacity of transport

    3. Decide after the customer’s agreement4. Check the power capacity

    1. Caution of damage.2. Keep the minimun space for service.3. Check the accessory and tools

  • 8/17/2019 AirCon Training Manual

    12/175

    12

    2. TOOLS REQUIRED

    2-1 Tools

    Screw driver

    Assembly, disassmbly

    Core drill(diameter 70mm)

    Wall through

    Hand drill

    Indoor istallationPlate fixing

    Monkey spanner(300mm):2EA

    Indoor/Outdoor pipeconnection

    Ruler, knife

    Ruler: Length &distance measurement.

    Knife: Tape cutting

    Torque wrench

    Indoor/outdoorpipe connection

    Gas leak detector& soup water

    Leak inspection

    Hook meter (for currentmeasuremement)

    Current, voltage,resistance measurement

    Thermometer

    Temperaturemeasurement at Indoorsuction inlet/discharge

    outlet.

    Insulation resistancemeter

    Insulation resistancemeasurement (Electric

    shock prevention)

    Hex. wrench (Largeside:4mm, 5mm)

    Service valveoperating

    Flare tool set

    Pipe cutting, Burrremoval

    2.2 Accessory

    Connection cable

    Indoor-Outdoorwire connection

    Refrigerant pipe(forhigh/low pressure)

    Refrigerant circuitconnection to

    Indoor/Outdoor.

    Winter cover

    Outdoor protectionin a unusedseason

    like winter

    Putty

    Chaging of wallthroughhole

    anti-vibration rubber

    Vibration absorptionof outdoor

    Vinyl tape

    Wire & pipe finishing

    Band

    Wire & pipefinishing

    Remocon fixture

    Remocon hanger

    Adhesive

    Finishing

    Fixture clampingscrew

    Remocon fixturefixing

    Drain hose

    Drainage

    Remocon

    Clamp meter

    Clamp meter Thermometer

    Drive torch Mega tester

  • 8/17/2019 AirCon Training Manual

    13/175

    13

    3. INSTALLATION

    3-1. SELECTION OF THE BEST LOCATION

    Decide installation place with the customer’s agreement.

    3-1-1. Indoor unit installation place• Select a place where the circulation of suction air and discharge air will be so good that the room temperature is

    uniform sufficiently considering air arrival distance during cooling.

    • In selecting indoor unit installation place, select a place where can ensure the minimum space indicated by the productspecification for service and cooling efficiency.

    • Avoid following place1) A place where there is a danger of inflammable gas leakage.2) A place where there is a danger of electromagnetic interference.-hospital, etc

    1. Install where a side of electromagnetic wave radiation transmitter does not face the main body of unit directly.2. In order to avoid noise effect, keep more than 3-m minimum distance from the devices of transmitting

    electromagnetic wave.3) A place where there is a lot of oil or steam. (kitchen, cooking place, machine plant)

    If installed in this place, as oil contacts heat exchanger, there is a great possibility of a frost generation in a poorheat exchanger, a deformation and a damage of resin parts, and a corrosion of heat exchanger.

    4) A place where there is a lot of moisture.Be easy to frost a product during cooling.

    5) A place where organic material is used.6) A place where cannot hold the weight of the products.7) A place where is not easy to drain.8) A place where is difficult to acquire service space.

    3-1-2. Outdoor unit installation place• In selecting outdoor unit installation place, select a place where can ensure the minimum space indicated by theproduct specification for service and cooling efficiency.

    • Avoid following place1) A place where discharging air turns toward neighbor’s window.2) A place where operation sound of outdoor unit is transmitted to neighbor.

    Take into consideration that there is no damage to neighbor in the bound of neighbor.3) A place where is difficult to acquire service space.4) A place where is not easy to discharge air.5) A place where there is a heat source near the outdoor unit.6) A place where a strong wind may blow straightly against outdoor unit.7) A place where sunlight shine the unit directly. (If so, an awning must be built separately.)8) A place where the wall of an apartment or a building is not stable. (If not stable, falling outdoor unit can damage

    human life or property.)9) A place where salty air or phosphoricacid chloride gas can be reached.

    3-1-3. Remote controller

    A place where there is no obstacles-curtain, etc-to disturbs a signal transmission of remote controller.A place where there is no direct sunlight or heat source around it.A place where separate more than 1-m from TV, radio, wireless phone, luminescent light, etc.If the neon lamp is near the product, it may not operate for electromagnetic interference.Protect them from neon lamp.

    Caution) Refer the installation manual before the installation, because there can be special articles for theproducts.

  • 8/17/2019 AirCon Training Manual

    14/175

    14

    3-2. SET RETURN

    • Transportation Method1) Please convey indoor and outdoor unit to the installation place in packing state as possible.2) Please take care to convey indoor and outdoor unit with no shock.3) Please do not use service valve with the use of carriage.4) Please do not carry front of the indoor unit on the back.

    Can be damaged and deformed the side of grill.

    3-3. Refrigerant pipe and drain pipe connections

    3-3-1. Refrigerant pipe connections

    • Working procedurePipe design – pipe manufacture – pipe connection – air purge – gas leak check – additional refrigerant charge(In case of exceeding the standard pipe length, 5-m)

    1. Precautions in pipe design

    Refrigerant pipe design affects deeply the efficiency of airconditioner, and wrong pipe constructions can be a cause of

    airconditioner’s failure.Please refer to attached management explanation and service manual in the main body of unit about standard pipespecification of airconditioner product classification, tolerance of pipe length, tolerance of high and low difference, andan amount of additional refrigerant, etc,

    Keep in mind the followings on pipe connections indoor and outdoor unit.1) Please use pre-defined pipe diameter and thickness.2) Additional charge is required according to the excessive length.

    Before the shipment, this airconditioner is filled with the rated amount of refrigerant including additional amountrequired for air purging, subject to 5m-pipe length.

    3) Please select the best short distance in pipe length.4) Please reliably fix pipe support.5) Please install oil trap per 10m to observe gas in case of vertical axis piping.6) Please high and low difference between indoor and outdoor unit is slight as possible in order not to exceed

    tolerance range.7) Please take a special care of pipe management to protect dust, moist, and scales by sealing the end of pipe with

    cap or tape.8) Please seal the end of pipe when go through the passing parts of the wall etc. and work.9) Please take care of the end of the pipe not to touch ground when pipe is placed on the ground directly.10) After pipe manufacturing, Remove burrs in the downward of the pipe.

    Aircon Classification

    Air pauge amount

    Split Type

    50g

    Package Type

    200g

    Band

    CAP or VINYL Band CAP or VINYL

    No touch!

    Burr removal

    Pipe

    Dust and refuse will insert in the pipe Burr will insert in the pipe

  • 8/17/2019 AirCon Training Manual

    15/175

    11) On raining day, please take a special care to pipe-work.12) Please not to install unnecessary trap in order to protect the staying of refrigerating oil, refrigerant inside of inlet

    gas pipe. Avoid the way gloving figure in case of crossing the axis as ceil side. In case of shortage of refrigerantbe a cause of refrigerating oil.

    13) In case of installing gas pipe horizontally, work downward slanted 1/250 (length 5m to 2mm downward) in the flowdirection in order to be easy for refrigerant to flow.

    14) Please keep the temperature of the gas pipe necessarily.If you tie with liquid pipe to keep temperature, compressor efficiency will be low because gas pipe overheating isgreat.

    15) Because outlet operation temperature is over 80˚C, insulate necessarily a place where men, animals, and plantscan contact.In case that water pipe is short, it may not insulate, but as flash phenomenon can be brought to externaltemperature, be desired to keep temperature.

    16) Please work to install the bit necessarily in case that refrigerant pipe is under ground.Please install the copper panel or concrete cover on the bit not to be pressed on upper-side pipe.If bit is not installed, expansion and stress for temperature change may cause to cut or leak it.

    17) Refrigerant pipe through part can be absorbing the change of temperature and vibration in order to preventrefrigerant leakage under the following picture.

    15

    Cover

    FloorTube

    Bit

    (Work to install the bit) (Work to install the hanger)

    Wall

    Wire Vinyl tape

    Gas pipe

    Insulation material

    Liquid pipe

    Protection pin

    Hanger

    Sleeve

    Wall

    Pipe

    axics

    IndoorUnit

    IndoorUnit

  • 8/17/2019 AirCon Training Manual

    16/175

    2. Pipe manufacturingBefore manufacture indoor/outdoor refrigerant pipe, decide method of refrigerant pipe connection. Use the simpleand speedy method of flare connection in case that pipe diameter is less than 3/4”. And connection method in thebelow picture is a method to connect flare nut with flare too set.For pipe diameter more than 3/4”, to be desired to braze cross other copper pipe after enlarge the pipe.

    1) Flare manufacturing

    • Using tool

    a. Please cut thepipe with pipe cutter.

    b. Remove burrs from cut edges of pipes.Caution: If burrs are not removed, they may cause gas leakage.

    If scales enter the pipe, they may cause a freezing malfunction.

    c. Insert the flare nuts, flare the pipe

    16

    Inclined Surface damaged Cracked Uneven thickness

    Pipe cutter Enlarger

    Reamer

    Pipe

    Enlarger bar

    Out Diameter

    ø6.35mm

    ø9.52mm

    ø12.7mm

    A(mm)

    1.3

    1.8

    2.0

    Nominal diameter

    1/4”

    3/8”

    1/2”

    5/8”3/4”

    D

    6.35

    9.52

    12.7

    15.8819.05

    A

    8.3~8.7

    12~12.4

    15.4~15.8

    18.6~1922.9~23.3

    90˚ Slant Burr

  • 8/17/2019 AirCon Training Manual

    17/175

    17

    2) Brazing manufacturing

    3) The methed of banding refrigerant pipe

    • Refrigerant pipe use connection pipe.• Insulate reliably refrigerant pipe 2-pieces as form dew or it may cause a malfunction.

    (Please use polyethylene with insulates plate.)• Hold the tubing with your two hands closely and then bend or stretch it slowly not to make any crack.• Keep in mind that the bending part should not be cracked, and make the radius® as long as possible.

    (Over R 50mm)• In case of unfolding, roll with pressing the end of it. (Refer to the below picture)

    4) Material of refrigerant pipeCopper tube or steel tube can use Freon refrigerant pipe, but at actual place considering work and durability, isusing copper non-connection tube widely.Air-conditioning phosphor deoxidization copper tube (C1220T-OL)

    a

    Capillary

    1/4~3/8”

    1/2~11/8”

    b

    0.05~0.1

    0.1~0.15

    0.15~0.2

    c

    10~15

    6~10

    10~20

    (Units:mm)

    6.35

    0.8

    1/4”

    9.52

    0.8

    1/2”

    12.7

    0.8

    1/2”

    15.86

    1.0

    5/8”

    19.05

    1.2

    3/4”

    22.2

    1.2

    7/8”

    25.4

    1.2

    1”

    28.6

    1.2

    9/8”

    31.8

    1.5

    5/4”

    35

    1.5

    11/8”

    Pipe diameter

    Thickness

    INCH

    (Units:mm)

    More than R50mm Press down

    Rolling

  • 8/17/2019 AirCon Training Manual

    18/175

    18

    3. Pipe connection

    If paste refrigerating oil on the contacting side of flare, there is an effect of protecting gas leakage.Align the center of the pipe, rotate and tighten the flare nut with fingers, and tighten the flare nut with torque wrench inthe below picture.

    Caution) if fastened by excessive force, flare part become destroyed

    Connection torque: using 30Cm-monkey spanner, fasteningwith 10Kg-force, toque is 300KgCm, the number ofmultiplication of distance and forceLiquid Side

    Gas Side

    Pipe Size

    6.35

    9.52

    12.7

    15.88

    Torque(kg.m)

    1.5~2.0

    3.1~3.5

    5.0~5.5

    7.0~7.6

    Liquid side

    PipeUnion

    Nut

    Gas side

  • 8/17/2019 AirCon Training Manual

    19/175

    19

    4. Air purge

    On pipe connection, discharging air in pipe is air purge, do purge air necessarily, because it may cause pressurerising, operating energy loss, compressor overheating, cooling efficiency drop.Before the shipment, our products are filled with the additional refrigerant for air purge. On installation, Air purges theindoor unit and pipe by using refrigerant of the outdoor unit.

    Caution) open the valves coke till it cannot rotate by stopper.Fasten reliably the valve cap with tools of spanner, etc.Use 4mm L-wrench to close or open the valve coke.

    Open the cap of the valve B & A

    Check the leakage of pipe connection portion.

    Open completely the stopper of the valve B & A.

    Close the each valve cap.

    Check the gas leakage.

    Open the stopper of valve B by 45˚C, close the stopperafter 10sec.(At this time, tools using control the pipe,exclusive L-wrench.)

    * Open needle cap of the valve A, by pressing needlevalve during 3 sec, discharge gas, and repeat 3 timesin this order.

    • Close the connection tube portion, If no leakage,proceed *.

    • If it is required to repair for gas leakage, afterdischarge the refrigerant gas and repair the part ofleakage, vacuum again and charge refrigerant.

    Liquid

    Outdoor unitGasside

    flare nut

    Stopper

    Cap

    Needle valve cap

    Indoor Unit

    Liquid side

    Service valveat liquid side

    Service valveat gas side

    Outdoor Unit

    Gas side

  • 8/17/2019 AirCon Training Manual

    20/175

    20

    • Work method of air purge according to pipe length.

    Ref) As air purge amount is different from products, Refer to installation manual of the products.

    1) Air purge-using refrigerant in the unit.Working order is the same as the above mentioned.

    2) Air purge using vacuum pumpWorking order is the same as follows.First. Connect the pipe of indoor and outdoor units. (At this time service valve is all closed in gas side and liquid side.)Second. Vacuum pump operator till the gauge’s pressure is to –76CmHg.Third. after close1, wait during 3-4min and check that pressure gauge is changed.If that is changed, check connections part and prevent refrigerant leakage in advance.Fourth. Open completely gas side and liquid side service valve with hexagonal wrench.

    Method

    Air purge-using Refrigerant in the units

    Air purge using vacuum pump

    Air purge using refrigerant bombe

    Condition

    Length of pipe 10m

    Length of pipe > 10m

    Length of pipe > 10m

    Amount of air pauge

    200g

    200g

    200~500g

    Lowpressure

    Highpressure

    Vaccum Pump

    Outdoor Unit

    Indoor Unit

    Pressure guage

    Open Close

    Gas Side

    Liquid Side

  • 8/17/2019 AirCon Training Manual

    21/175

    21

    3) Air purge using refrigerant bombeWorking order is the same as follows.First. Connect the pipe of indoor and outdoor units. (At this time service valve is all closed in gas side and liquidside.)At this time, connect loosely flare nut4. (Can rotate by fingers)Second. Open 1, 3 and discharge air in the tube. Transparent air comes out and white gas is started todischarge. After 3 seconds at that time, close1,2,3.

    Third. Open completely gas side and liquid side service valve with hexagonal wrench.

    Pressure guage

    CloseOpen

    Outdoor Unit

    Indoor Unit

    Gas Side

    Liquid Side

    Lowpressure

    Highpressure

  • 8/17/2019 AirCon Training Manual

    22/175

    22

    5. Leak Inspection

    Please check the leakage of the connection parts by using leak detector and soup water.

    Indoor Uint connection

    Outdoor Unit Connection

    Leak Detector

  • 8/17/2019 AirCon Training Manual

    23/175

    23

    6. Additional refrigerant charging

    When measure the pressure with lack of the refrigerant, measure the pressure with manifold gauge after connecting tovalve.In case that the pressure is less than the standard, add the refrigerant as the following method.If the refrigerant contains too excessive refrigerant, liquid refrigerant will down the product quality.

    Preparation of manifold gauge• Check that three valves is attached properly.• Check that left side (low pressure), right side (high-

    pressure) handle is closed completely.• Check that there is a pin at the end of low pressure hose.

    (1) Connect the middle hose of the pressure gauge to gascylinder, open the Gas side service valve of the gascylinder. (At this time, do not turn gas cylinder over.)

    In holding state, the low pressure becomes differentaccording to the ambient temperature of the outdoor unit.

    (3) operate airconditioner in cooling mode(fan speed/strong)

    (4) In case of lower pressure than that, turn overrefrigerant gas cylinder.

    (5) Loose the low-pressure valve of the pressure gaugeduring 2-3sec. And close again and wait during 4-5sec.

    (7) After close the refrigerant gas cylinder, remove thehose of the low-pressure side, and close the cap of the

    valves in original state.

    (6) Till the pressure become 4-5kg/cm2 , repeat (5) work.

    In case of proper refrigerant, pressure is about to 0 at first,10min later the pressure is stable in 4-5kg/cm2 .(The pressure can be changed according to the roomtemperature and humidity.)

    (2) Open the low-pressure sided valve of the pressuregauge, discharge air in the hose. After 2-3sec. releasethe low part cap of the Gas side service valve andconnect the low-pressure sided hose(blue) to this place.Close the low-pressure sided valve after full connection.

    Lowpressure

    ClosePin

    Red

    YellowBlueLiquid side

    servicevalve

    Gas Side

    Outdoor unit

    Pipe

    Spindle

    Hose of Low pressure

    Construction of Gas side service valve

    Connect to valve

    Close

    Highpressure

  • 8/17/2019 AirCon Training Manual

    24/175

    24

    Precautions in charging refrigerant

    • Before connect the hose of the pressure gauge to airconditioner, work necessarily (1), (2).• Do not encloses a lot amount of the refrigerant at once.• As the above message is the explanation of additional injection of the refrigerant.

    When charge first after repairing the refrigerant cycle, vacuum sufficiently inside of the airconditioner and then chargerefrigerant.

    • When charge the additional refrigerant, after operate necessarily in cooling mode (strong).

    • In case that that is not a cooling mode, the low-pressure side can be changed.)

    • Charging Additional refrigerant per length

    Model

    DSB-070L

    DSB-091L

    DSB-121L

    DSA-151L

    DSB-181L

    DP-130E

    DP-130H

    DP-150E

    DP-171M

    DP-170H

    DP-200M

    DP-310M

    DH-400M

    Quantity of

    Heat

    [kcal/h]

    1,800

    2,270

    3,000

    3,550

    4,280

    4,500

    4,500

    5,100

    6,100

    6,100

    7,100

    9,600

    12,500

    Reference

    refrigerant

    [g]

    800

    1000

    1200

    1250

    1150

    2000

    2000

    2200

    2200

    2200

    2100

    3600

    3800

    Name

    Gas Pipe

    Liquid Pipe

    Gas Pipe

    Liquid PipeGas Pipe

    Liquid Pipe

    Gas Pipe

    Liquid Pipe

    Gas Pipe

    Liquid Pipe

    Gas Pipe

    Liquid Pipe

    Gas Pipe

    Liquid Pipe

    Gas Pipe

    Liquid Pipe

    Gas Pipe

    Liquid Pipe

    Gas Pipe

    Liquid Pipe

    Gas Pipe

    Liquid Pipe

    Gas Pipe

    Liquid Pipe

    Gas Pipe

    Liquid Pipe

    Pipe

    Diameter

    (D)

    12.7

    6.35

    12.7

    6.3512.7

    6.35

    12.7

    6.35

    12.7

    6.35

    15.88

    9.52

    15.88

    9.52

    15.88

    9.52

    15.88

    9.52

    15.88

    9.52

    15.88

    9.52

    15.88

    9.52

    19.05

    12.7

    Length

    (L)

    5m

    5m

    5m

    5m5m

    5m

    5m

    5m

    5m

    5m

    5m

    5m

    10m

    10m

    8m

    8m

    10m

    10m

    10m

    10m

    10m

    10m

    10m

    10m

    10m

    10m

    Increase

    Decrease

    Increase

    DecreaseIncrease

    Decrease

    Increase

    Decrease

    Increase

    Decrease

    Increase

    Decrease

    Increase

    Decrease

    Increase

    Decrease

    Increase

    Decrease

    Increase

    Decrease

    Increase

    Decrease

    Increase

    Decrease

    Increase

    Decrease

    20g/m

    -17g/m

    20g/m

    -17g/m20g/m

    -17g/m

    20g/m

    -17g/m

    20g/m

    -17g/m

    40g/m

    -37g/m

    40g/m

    -37g/m

    40g/m

    -37g/m

    40g/m

    -37g/m

    40g/m

    -37g/m

    40g/m

    -37g/m

    40g/m

    -37g/m

    80g/m

    -77g/m

       S  p   l   i   t   R  o  o  m    A

       i  r  c  o  n

       P  a  c   k  a  g  e   R  o  o  m    A

       i  r  c  o  n

    Added refrigerant

    per length

  • 8/17/2019 AirCon Training Manual

    25/175

    25

    7. Vacuum Method

    The purpose of vacuum is to remove air and moisture in the refrigerant system.It is important to vacuum in the system. Air and moisture in the system may cause Pressure-rising, operating energyloss, compressor deterioration and freezing.In case that there is no remaining refrigerant in the tube because of leakage and repairs, vacuum by opening the gasside and the liquid side service valve.After the pipe connection of indoor and outdoor, must vacuum the tube after close the liquid side and the gas side

    service valve.If vacuum is made completely, start directly to charge refrigerant in order not to be intruded by open air.And in case that required to discharge refrigerant for after-service, discharge slowly and do vacuum in order not todischarge refrigerating oil of the compressor.

    Low pressure High pressure

    Pressure guage

    Open Open

    Indoor Unit

    Gas Side

    Liquid Sige

    Compressor

    Vaccum pump

    Outdoor Unit

  • 8/17/2019 AirCon Training Manual

    26/175

    26

    8. Pump down

    • In order to prevent discharging refrigerant in moving or repairing, gathering the refrigerant of indoor and pipe insideis pump down.

    Operate airconditioner in cooling mode (compressor mustbe operated.)

    (1) Disclose the caps of the liquid side service valve andthe gas side service valve.

    (2) Rotate the spindle of the gas side service valve right-sided and closes completely by using L-wrench.

    (3) About 2 min. later, rotate right-sided and closecompletely the spindle of the gas side service valve

    (4) Stop the airconditioner

    Do required works.

    Liquid side service valve

    Gas side service valve

    Operation states of the service valve

    1The closing state before the shipment   2the mid-state in suctioning air   3the opening state in normal operation

    A-BA-C

    Close

    B-C Open

    A-B Open

    A-CB-C

    Close

    A-B-C Open

  • 8/17/2019 AirCon Training Manual

    27/175

    3-3-2. Drain pipe (hose) connection

    • Drain hose is necessarily slanted outdoors• Drain hose must be slanted downward in order for good flow of condensing water.

    • Arrangement of the drain hose(Check as the following items about the drain hose.)1. Is drain hose downward of others through the hole?2. Isn’s drain hose higher than drain hole because of loosing the hose?

    3. Does water come out when pour water into condensing water rest?

    Caution) As condensing water can overflow in bad insulation of drain part and drain hose connection of theairconditioner, Make sure to insulate connection part necessarily.

    • In case that extension hose (drain hose) is in the room, please insulate the exterior of the hose.

    27

    Indoor

    Insulation

    Outdoor

    Hose extension pant

    Indoor drain hose extension hose Hose(general purchase)

    Hose is higherthan unit

    The end of hoseis gettinginto water

    The end ofhose is being

    crooked.

    The gab of theground is small

    The end of hoseis being in a water

    spout

    The connectionpant of hose isbeing crooked

    water

    spout

    less than

    5m

    Connection Cable

    Indoor Pipe

    Drain Hose

    Indoor Unit

  • 8/17/2019 AirCon Training Manual

    28/175

    28

    3-4. Power supply and wiring construction

    3-4-1. Precaution before the work

    1) Check that source voltage is rated voltage.2) Check that power capacity is sufficient to operate the airconditioner.3) Have an individual power specialized for airconditioner.4) Equip a suitable leakage braker for power capacity.

    5) Provide a circuit braker switch between power source and units.6) Do not cut and connect the power code, that is a great danger.7) Make sure it is not connected to ac power before wiring to protect from electric cause.

    3-4-2.wiring of indoor and outdoor

    1) On wiring of indoor and outdoor, match the number of terminal block and the terminal number of connection cable.2) Connection cable can be short as possible by using specified cables (components).3) If wiring of indoor and outdoor is not correct, it may cause the trouble.4) Refer to installation manual according to the characteristics of the product about the others.

    3-4-3. Earth work1) method of earth work

    • In case of using already established earth• In case of using exclusive earth terminal

    • In case of using earth of a switch board

    • In case of using extraordinary earth pipe

    Cable using in installingaircon(more than 1.6mm2 ornominal surface area over2mm2)

    Electrical resistance:below 100Ω(past equipment)

    Switch board

    Cable using in installingaircon(more than 1.6mm2 ornominal surface area over2mm2)

    Electrical resistance:below 100Ω(past equipment)

    Terminal for earth

    Carbo pipe or copper pipe

    Nominal surface area over 2mm2 viny/wire(blue) Press terminal (M4 screw)

    copper wire

  • 8/17/2019 AirCon Training Manual

    29/175

    29

    2) Procedure of earth workPlease do earth work completely in orders as the following table.

    Order

    1

    2

    3

    4

    5

    6

    work

    selection of earthlocation

    Burying earth pipe

    Arrange earth line

    Check and examination

    Connection of earthpipe and airconditioner

    Never contact in a greatdanger of connectingthe earth line to thefollowing place

    explanations

    suitable place1.a place where be always moist.

    2.mud is better than sand

    unsuitable place1.a place where be underground

    establishment (gas pipe, water pipe,inlet pipe, underground cable)

    2.keep the space over 2m betweenearth for a lightening conductor andearth wire

    In case of having a burial tools1.Bury the earth pipe on ground surface2.Bury over 20Cm deeper by using the

    burial tools

    in case of having no burial tools1. dig the hole as the figure and bury

    the earth pipe2. bury wholly the earth pipe with clay

    In case of extension of short earth line,adhere the insulation and wrap withtapeFix the earth line unscramble withstemple

    Check that the earth resistance withearth ohmmeter is satisfied to thespecified value after installation work.

    In case that the earth resistance is notthe standard value, can be the standardvalue by burying the earth pipe deeperor adding the earth pipe.

    Connect reliably Earth line and earthterminal of outdoor unit.

    TV antenna, gas pipe, aluminum sassy,flower base, water pipe ( earth usingwater pipe can be use as earth polar incase of less than 3% resistance, buttake an approval of water administer inadvance)

    cautions

    Avoid sand ground, pebble groundfor a high earth resistance

    Do not use publicly the earth forphoneFix completely earth line in case ofburying where passers-by are a lot.

    Use vinyl cable that thickness isdiameter 1.6mm orNominal surface area is over 2mm2 ,blue

    In case of being unable to avoid,take an approval of specialist inadvance and then do it.

    check reliablyconnection part

    check reliably connection part

    earth pipe earth pipe burialtool

  • 8/17/2019 AirCon Training Manual

    30/175

    3-5. Test running

    • Check that source voltage is correct to the rated value.

    • Operate in cooling mode for more than 20min. and then measure the temperature of in/out air in the indoor unit of theroom , check that the difference of the temperature is more than 80˚C.

    • Check that service valve (gas-liquid side) is open before test running.• Do not test run by pressing harshly electronic contacting device.• Check that vibration, leakage and shocking exist.• Check s place where operation is unstable or overheating.• Check whether there is an obstacle in air inlet of indoor and outdoor unit.

    • Check that earth wire is fixed reliably.

    30

    8˚C

    cheoked voltage is within ± 10% of therated voltage

    Measure the difference of the temperature

    Suction part discharging part

  • 8/17/2019 AirCon Training Manual

    31/175

    31

    3-6. Insulation and final construction

    • Finish work correctly so that rain water do not come into the room

    • Wrap the connection part with insulation plate.• Block strongly the hole of the wall.• Wrap from the bottom to the top with finishing tape.

    • Take care that indoor and outdoor connection cable and power cable has not to be contacted gas side service valveand pipe without insulation plate.

    1.Dragin hose has to be installed under the pipe, not to be loose for hose.-Before installation, check if drain hose is separated from the products.(When that is separated, water flow into the room, so fit into the product reliably.

    2. Take care that pipes does not come out in the back of the indoor unit.3. In case there is a pipe (copper pipe) exposed in indoors, make dew and fall into the room, exposed pipe is

    required to insulate sufficiently.4. In case of bending the pipe, bend it not to make any crank for copper pipe as big radius (more than 100mm)

    as possible.

    wrap from the bottom to the top by tape

    drain hose

    connnection pipe

    connnection cable

    band

    insulation vinyl tape

    • Wrap the connection part of the pipe with insulateplate,Tie tightly both ends to have no gap with two bands

  • 8/17/2019 AirCon Training Manual

    32/175

    32

    3-7. Checking and conveyance

    • Check the following items after complete installation

    • Please explain airconditioner function, cleaning the filter to customer.

    Appearance checking items

    There is vibration, noise, trembling, etc. is the indoor unit mounted securely?

    Bad cooling does the gas leak?Are there any obstacles in air inlet of indoor and outdoor unit?

    Water falling insulates the pipe sufficiently?Isn’t there the drain hose higher than the drain hole?Does condensing water flow smoothly?

    Unstable operation are all cables compatible to the standard value?

    Or overheating is the source voltage correct to the rated value?

    Generation of electric leakage does the ground wire earth certainly?

  • 8/17/2019 AirCon Training Manual

    33/175

    33

    4.MOVING METHOD

    • Refer to it on house moving and movement of the installation place.

    1) Do pump down (refer to details of pump down)2) Disconnect the power cord.3) Disconnect connection cable from indoor and outdoor unit.4) Remove the flare nut for pipe connection from indoor unit.

    At this time, wrap the pipe and tube of indoor unit with cap or vinyl envelope, etc so that scales do not enter it.5) Disconnect connection pipe from outdoor unit

    At this time, wrap the pipe and tube of indoor unit with cap or vinyl envelope, etc so that scales do not enter it.6) To prevent middle part of connection tube from bending or cracking, wrap in the proper size, and then preserve

    and move it with cables.7) Move indoor and outdoor unit to specified place.8) Dissolve the indoor plate from the wall, and then move the place to install.

    About pressure of the refrigerant cycle.

    • If an actual temperature is low, the pressure become low.

    • If the amount of refrigerant is insufficient, the pressure become low.• Dust is attached to the filter of indoor unit, the pressure of the low pressure part become low for decreasing amount of

    the wind• By blocking the air suction of outdoor unit, decreasing amount of the wind make an operation of OLP.

    - In case of becoming low in low pressure part:evaporator an suction pipe is freezing.

    - In case that the refrigerant is too much:If aircon operates in a low actual temperature, evaporator and suction pipe is freezing.

    - In case that the refrigerant is too small: overheating compressor operates overload.

  • 8/17/2019 AirCon Training Manual

    34/175

    34

    4. WINDOW ROOM AIRCONDITIONER

    1.GENERAL SPECIFICATIONS

    ITEM

    MODEL

    DWB-070C DWB-091C DWB-121C

    Function Cooling only

    Power source V / Hz AC 220 ~ 240V / 50Hz

    Cooling CapacityBtu/h 7,300 8,600 11,700

    Kcal/h 1,840 2,170 2,950

    Energy Efficiency RatioBtu/hw 9.67 9.30 9.92

    Kcal/hw 2.44 2.35 2.49

    DehumidificationPts/h 2.02 2.49 3.30

    g/h 920 1,130 1,500

    Electrical DataPower Input 755 925 1,180

    Running Current 3.2 4.1 5.2

    Compressor

    Type Rotary

    Model QB134PL12A QK164PN12C QK196PN13A

    Capacitor 25µF/400VAC 30µF/400VAC 35µF/400VAC

    Model A9525TS401 A9525TS602   A2925CA070(DMI)/OBM2501P2(OS)

    Fan MotorCapacitor 2µF/400VAC 3µF/400VAC 5µF/400VAC

    Indoor-Fan Blower-Fan

    Outdoor-Fan Propeller-Fan

    Refrigerant (R-22)Control Capillary

    Charge Amount (g) 380 480 730

    DimensionsUnit(W x H x D)   18.5(W)x14(H)x18.9(D)Inch / 470(W)x358(H)x480(D)mm

    Packing(W x H x D) 21.3(W)x17.9(H)x21.7(D)Inch / 540(W)x455(H)x550(D)mm

    Weight Net Weight (Kg) 63 lbs (28.5Kg) 65 lbs (29.5Kg) 90.2 lbs (39.8Kg)

    Gross Weight (kg) 66 lbs (30Kg) 68 lbs (31Kg) 97.5 lbs (43Kg)

    23.6(W)x14.9(H)x21.0(D)Inch600(W)x380(H)x535(D)mm

    26.1(W)x18.1(H)x22.6(D)Inch663(W)x460(H)x573(D)mm

  • 8/17/2019 AirCon Training Manual

    35/175

    35

    2. MAJOR COMPONENTS

    NO PART NAME

    1 AIR FILTER

    2 GRILL FRONT

    3 CABINET

    4 BLADE VERTICAL

    5 KNOB THERMOSTAT

    6 KNOB SELECTOR

    NO PART NAME

    7 BLADE HORIZENTAL

    8 AIR VENT

    9 FRAME GUIDE TOP

    10 FRAME WINDOW KIT

    11 SHUTTER WINDOW

    • DWB-121C

    • DWB-070C / DWB-091C

    4

    15

    6

    3

    2

    7

    9

    0

    q

    4

    15

    6

    3

    2

    65

    2

    3

    7

    4

    8

    11

    10

    9

    1 65

    2

    3

    7

    4

    8

    1

  • 8/17/2019 AirCon Training Manual

    36/175

    36

    3. WIRING DIAGRAM

    COMP

    F.M

    R

    C

    O.L.P BR

    RD

    OR

    OR

    GY

    GN

    (Lo)

    (Hi)

    WH

    CAPACITOR

    BR

    YW

    BL

    Hi-FAN

    LO-FAN

    LO-COOL

    Hi-COOL

    OFF

    SELECTOR SWITCH

    BK AC115V/60Hz

    21

    4

    87

    THERMOSTAT

    F

    S

    C

    H

    (BL) (BR)

    OFF

    YEL

    RED

    GRY

    BLU

    BLUWHTYEL

    L C

    1 6

    7 2

    4

    8

    HIGHCOOL

    MEDCOOL

    LOWCOOL

    LOWFAN

    MEDFAN

    FANMOTOR

    COMP

    SELECTOR SWITCH

    THERMOSTATSWITCHO.L.P

    CAPACITOR

    H

    GRN(GRN/YEL)

    RED

    BLK

    WHT(BLU)

           D       L       K       (       B       R       N       )

           G       R       N       (       G

           R       N       /       Y       E       L       )

    R

    S

    C

    ORG

    BLK(BRN)

    CF

    • DWB-121C

    • DWB-070C / DWB-091C

  • 8/17/2019 AirCon Training Manual

    37/175

    37

    4. FUNCTION OF MAIN COMPONENTS

    1. ROTARY SWITCH (SELECTOR)

    Please refer to the part of selector in the chapter 9 (Wiring Diagram).The rotary switch (selector) controls the fan motor’s rotation speed, and has five positions.The function of the five position is as follow.

    OFF: This po sition s tops all operations of the airconditioner.

    HIGH COOL: This position provides the maximum airflow for rapid cooling, dehumidifying anddust removing operations.(Use this position on sultry summer days.)

    LOW COOL: This position provides the minimum air flowfor quiet cooling, dehumidifying operations.(Use this position on suitable for night-time.)

    HIGH FAN: This position provides the maximum air fiowalone fan operation without coolingoperation.

    LOW FAN: This position provides the minimum air flowair flow alone fan operation without coolingoperation.

    2. THERMOSTAT (TEMPERATURE CONTROL)

    The Thermostat automatically starts and stops operation in order to keep the roomtemperature at a proper level, and this results in efficient use of power and economical

    cooling.

    Turn clockwise for a cooler room temperature.

    Turn counter-clockwise for a warmer room temperature.

    3. MOTORThe motor is used to rotate the indoor and outdoor fan so that the room air can be recirculated.

    4. FAN

    BLOWER FAN: The Blower draws hot air from the room through the Evaporator and then discharges it back into thecool air. It circulates the room air.

    PROPELLER FAN: The propeller draws outdoor air through louvering and cools Condenser, and then blows the hotair out.

    5. CAPACITORThe Capacitor enlarges the difference of phase between main coil and sub coil so that the Compressor and Fan Motorstarts well.

    6. ACCUMULATORThe Accumulator blocks the unflow of liquid refrigerant and impurities into the Compressor.

    SELECTOR 

    HIGH 

    COOL

    HIGH 

    FAN 

    LOW 

    COOL

    LOW 

    FAN 

    OFF 

    THERMOSTAT 

    COOLER 

    • DWB-070C / DWB-091C • DWB-121C

  • 8/17/2019 AirCon Training Manual

    38/175

    38

    5. TROUBLE SHOOTING GUIDE

    TROUBLE SITUATION ANALYSIS CAUSE REMEDY

    Fan motor and

    compressor do not

    run

    Switch is in “cool”

    position but the

    compressor does not

    run

    1. Power failure

    2.Power is supplied,

    but the equipment

    does not run

    1. Not operating at all

    2. Compressor

    3. Frequent start and

    stop

    1) Power plug

    2) Circuit breaker

    1) receptacle

    2)Operation switch

    3) Cord or lead wire to

    the switch

    1) Compressor

    2) Thermostat

    3) Selector switch

    4) O.L.P

    5) Capacitor

    1) Electricity

    2) Room temperature

    and outside

    temperature

    3) Compressor

    4) O.L.P

    5) Capacitor

    1) Thermostat

    2) Capacitor

    3) O.L.P

    1) Power failure

    2) Circuit breaker is tripped

    3) Power plug is not contacting

    ¡ Disconnection

    ¡ Mechanical failure of switch

    1) Disconnection

    2) Malfunction of contact

    ¡ Disconnection or burned-out

    1) Failure

    2) Malfunction

    3) Knob is not set to the proper

    setting

    ¡ Failure of malfunction of proper

    setting

    1) Disconnection

    2) Malfunction of contact

    ¡ Lack of capacity¡ Disconnection

    1) The voltage exceeded allowed

    range (220V-240V)

    2) Capacity of wire is not

    sufficient

    ¡ Extremely high

    ¡ Burned-out

    ¡ Malfunction

    ¡ Lack of capacity

    ¡ Malfunction

    ¡ Lack of capacity

    ¡ Malfunction

    ¡ Consult your electric company

    ¡ In case of a breaker, turn it on

    and off a few times

    ¡ Replace the power plug

    ¡ Repair or replace the

    receptacle

    ¡ Replace the cord or lead wire

    ¡ Replace the compressor or

    connection wire

    ¡ Replace

    ¡ Repair or replace

    ¡ Turn knob for cooler setting

    ¡ Repair or replace the swtting

    ¡ Repair

    ¡ Repair or replace

    ¡ Replace

    ¡ Repair

    ¡ Consult your electric company

    ¡ Check the capacity of wire

    ¡ Ventilate well and remove the

    heat source

    ¡ Replace

    ¡ Replace

    ¡ Replace

    ¡ Replace

    ¡ Replace

    ¡ Replace

  • 8/17/2019 AirCon Training Manual

    39/175

    39

    TROUBLE SITUATION ANALYSIS CAUSE REMEDY

    The compressor runs

    but the motor doesn’trun

    Both fan motor andcompressor are

    running but cooling isbad

    Vibration & Noise

    Water leakage intoroom

    Electric shock

    (Leakage of current)

    Not cooling at all

    Insufficient cooling

    1) Fan2) Fan motor3) Capacitor4) Fan motor circuit

    Refrigerant system

    1) Refrigerant system

    2) Filter

    3) Heat exchanger ofcondenser

    1) Installation place

    2) Fan

    3) Fixing screws

    4) Electriccomponents

    ¡ Installation condition

    ¡ Insulation of

    components

    ¡ Blocked by others

    ¡ Disconnection or burned-outelectric cord

    ¡ Failure malfunction of contact

    ¡ Disconnection of malfunction ofcontact

    1) Refrigerant system is choked

    2) Compressor failure

    3) Leakage of refrigerant gas

    1) Refrigerant system is choked

    2) Compressor failure

    3) Leakage of refrigerant gas

    4) Refrigerant charge is too high

    ¡ Clogged up with dust

    1) Fin is cogged up with dust

    2) The ventilation is not good

    3) The unit is exposed to thesunlight

    4) Other heat source is added inthe room

    ¡ Installation of the unit isimperfectly done

    1) Fan is contacted withobstacles

    2) Fixing bolt

    ¡ Have a screw loose

    ¡ Electrical noise

    ¡ The front is lower than rearside

    1)Insulation defect of wiring and

    lead wire

    2) Leakgae of current due to thedew or rust

    ¡ Repair

    ¡ Replace the fan motor

    ¡ Replace

    ¡ Check the circuit

    ¡ Repair

    ¡ Repair

    ¡ Recharge refrigerant gas

    ¡ Check and repair refrigerantsystem

    ¡ Replace

    ¡ Check a part of Leakage andrepair

    ¡ Repair and recharge

    ¡ Clean the air fiter

    ¡ Clean the unit

    ¡ Shade the unit from the

    sunlight¡ Remove the added heat

    source

    ¡ Install the unit perfectly

    ¡ Remove obstacles

    ¡ Tighten the bolt

    ¡ Tighten the screw

    ¡ Exchange the components

    ¡ Make rear side of the unit lowerthan the front

    ¡ Check the unit’s Leakage of

    current.

    ¡ Replace the defective parts orcomponents

  • 8/17/2019 AirCon Training Manual

    40/175

    40

    6. HOW TO DISASSEMBLE

    1 Before service of 1. Stop the unit, remove the power cord from the receptacles.any part. 2. Move the unit to the safe location for the suitable work.

    2 Ass’y Fan Motor 1. Remove Front Grill

    - Fan Motor - Remove Filter Pre.

    - Propeller Fan - Remove screw in Front Grill. (DWB-070C/091: 1 point, DWB-121C: 2 point)

    - Blower Fan 2. Remove Cabinet from the unit.

    - Remove screws from the unit’s sides.

    (DWB-070C/091C: 8 point, DWB-121C: 2 point)

    3. Remove holder scroll. (DWB-121C)4. Remove Scroll upper.

    5. Remove Plate Scroll (DWB-070C/091C)

    - Remove screws (3 point) from Plate Scroll’s sides.

    6. Remove Ass’y Control Box

    - Remove screws (DWB-070C/091C: 3point, DWB-121C: 4 point).

    - Remove wires in the each components.

    7. Remove wires in the Panel Housing.

    8. Remove screws from Ass’y Fan Motor’s sides.

    (DWB-070C/091C: 7 point, DWB-121C: 4 point)- Ass’y Fan Motor is assembly of Fan Motor, Propeller and Blower Fan,

    Orifice and Panel Housing.

    9. Lift the Ass’y Fan Motor from the unit.

    10. Remove hex-nut (DWB-070C/091C: hex-nut 2 point, DWB-121C: CI:P Fan

    2 point)from the shaft of Fan Motor.

    11. Remove Propeller Fan from the shaft of Fan Motor.

    12. Remove Blower Fan from the shaft of Fan Motor.

    13. Remove Fan Motor from Panel Housing.

    - Remove screws (4 point).

    3 Ass’y Control Box 1. Same as the procedure 1 to 5 in the Item 2.

    - Rotary Switch (selector)

    - Thermostat

    - Capacitor

    - Power Cord

    4 O.L.P 1. Same as the procedure 1 to 2 in the Item 2.

    2. Remove Terminal Cover from Compressor.- Remove hex-nut (1 point).

    Please refer to the chapter (Exploded diagram and parts list).

  • 8/17/2019 AirCon Training Manual

    41/175

    41

    7. EXPLODED DIAGRAM AND PARTS LIST.

    DWB-070C, DWB-091C PARTS LIST

    NO. CODE COMPONENTS Q’TY SPECIFICATION REMARK

    1 3100300700 PAN BASE 1 PP+T30% or PP+CACL3(40%)

    2 3106002400 COMP BOLT 3 M8XP1.25XL57

    3 3106600400 SCROLL LOWER 1 EPS

    4 2221040001 SEALING PUTTY 0.05 GRAY (PGE000901)JOINT SEALER

    53100049100 COMPRESSOR 1 QB134PL12A, 220V-50HZ DWB-070C

    3100049400 COMPRESSOR 1 QB164PN12C, 220V-50HZ DWB-091C

    6 – GROMMET 3 EPDM 45

    7 7400208411 WASHER PLAIN 3 M8(ID8..4XOD22XT1.6)

    8 7392801211 NUT LOCK 3 M8XP1.25 (RIGHT SCREW)

    9

    3100029400 ASS’Y CONDENSOR 1 2RX1CX17S DWB-070C

    3100049700 ASS’Y CONDENSOR 1 3RX2CX17S DWB-091C

    10 7112401611 SCREW TAPPING 2 T1 TRS 4X16 MFZN

    113104414400 PIPE COND IN 1 C1220T-OL. OD7.94XT0.7 DWB-070C

    3100049800 PIPE COND IN 1 C1220T-OL. OD7.94XT0.7 DWB-091C

    12 3100034310 ASS’Y PIPE CAPILLARY 1 DWB-070C

    133104414610 PIPE CAPILLARY 1 C1220T-0, ID1.6XL1,100 DWB-070C

    3104401400 PIPE CAPILLARY 1 C1220T-0, ID1.0XL400X2 DWB-091C

    143100029300 ASS’Y EVAPORATOR 1 2RX2CX12S DWB-070C

    3100049600 ASS’Y EVAPORATOR 1 3RX2CX13S DWB-091C

    15

    3100034500 ASS’Y PIPE EVA OUT 1 DWC-070C DWB-070C

    310005000 ASS’Y PIPE EVA OUT 1 DWC-091C DWB-091C

    16 3100034400 ASS’Y PIPE EVA IN 1 DWC-070C / DWC-091C

    17 3100034600 ASS’Y PIPE SUCTION 1 DW-070C

    18 7112401611 SCREW TAPPING 2 T1 TRS 4X16 MFZN

    193108003300 MOTOR FAN 1 A9525TS401, 220V-50Hz DWB-070C

    3108003500 MOTOR FAN 1 A9525TS602, 220V-50Hz DWB-091C

    20 3104201500 PANEL HOUSING 1 SGCC Z-27

    21 3101402400 COVER ORIFICE 1 PP

    22 7S432X4081 SCREW TAPTITE 4 TT3 TRS 4X8 SE MFZN

    23 7122401211 SCREW TAPPING 3 T2S TRS 4X12 MFZN

    24 3101801820 FAN BLOWER 1 ABS Ø8

    25 3106000600 WASHER PLAIN 1 M6(ID6.4XOD19.8XT1.6)

    26 3106000500 NUT HEX(R) 1 M6(RIGHT SCREW)

    27 3101801910 FAN PROPELLER 1 ABS+GF20% Ø8

    28 3106000600 WASHER PLAIN 1 M6(ID6.4XOD19.8XT1.6)

    29 3106000400 NUT HEX(L) 1 M6(LEFT SCREW)

    30 3100700600 BUSHING GUIDE 1 NBR(HS 60˚±5˚)

    31 3103800400 LOCK TWIST STANDOFF 3 DASTL-3NA

    32 3100700900 BUSHING HOUSING 1 NBR(HS 60˚±5˚)

    33 3100504000 BOX CONTROL 1 SGCC T0.8X332X270P REGULLAR-SP.

    34 5S10503100 S/W ROTARY 1 DAESUNG SRB 315-4-7D, 5-STEP

    35 7001400611 SCREW MACHINE 4 M/C PAN 4X6 MFZN

    36 5SM0101600 THERMOSTAT AS 1 PFA 602D-06B

  • 8/17/2019 AirCon Training Manual

    42/175

    42

    NO. CODE COMPONENTS Q’TY SPECIFICATION REMARK

    373109502100 CAPACITOR 1 2/25µF, 370/400VAC DWB-070C

    3106900900 CAPACITOR 1 3/30µF, 400VAC DWB-091C

    38 3101201600 CLAMP CAPACITOR 1 SGCC T0.8X113XCOIL REGULLAR-SP.

    39 7S432X4081 SCREW TAPTITE 1 TT3 TRS SE 4X8 MFZN

    40 3101396120 POWER CORD 1 KKP-550A(AUSTRIA, ARGENTINA)

    41 7S432X4081 SCREW TAPTITE 1 TT3 TRS SE 4X8 MFZN

    42 7S432X4081 SCREW TAPTITE 1 TT3 TRS SE 4X8 MFZN

    433103524300 LABEL CIRCUIT 1 P.E T0.05 DWB-070C

    3103524400 LABEL CIRCUIT 1 P.E T0.05 DWB-091C

    44 3100701100 BUSHING COVER 0.4 DACB-008(L=300)

    45 3102702100 HARNESS ROTARY S/W 1 AWG-16UL(BR)

    46 3108502900 SEAL CONTROL BOX 1 F-US, 258X264XT5(D/G)

    47 3102702000 HARNESS COMP ASSY 1 AWG-16, UL(BR/RD/OR)

    48 — OVER LOAD PROTECT 1 MRA12012-12003 DWB-070C

    OVER LOAD PROTECT 1 MRA98776-12026 DWB-091C

    49 — GASKET 1 SILICON

    50 — COVER TERMINAL 1 PC

    51 — NUT(HEXAGON GLANGE) 1 HEXACON FLANGE

    52 3108502700 SEAL EVA TOP 1 F-US, 350X40XT5

    53 3104504800 PLATE SCROLL 1 PP+T30

    54 3108503800 SEAL SCROLL 1 F-US, 115X60XT5(D/G)

    55 7122401211 SCREW TAPPING 3 T2S TRS 4X12 MFZN

    56 3106600300 SCROLL UPPER 1 EPS

    57 3108502800 SEAL COND TOP 1 F-US, 400X30XT10

    58 3100034900 CABINET ASSY 1 DW-070(STOP WELDING)

    59 3100603400 BRACKET CABINET 1 DW-070

    60 3104505600 PLATE WINDOW TOP 1 SECC T1.2X82.5X466.5(GY-258D)

    61 7S432X4081 SCREW TAPTITE 3 TT3 TRS SE 4X8 MFZN

    62 3108503100 SEAL CABINET TOP 1 F-US+F-PE(470X155XT10/2)

    63 3108503200 SEAL CABINET SIDE(L) 1 F-US(310X90XT5)

    64 3108503400 SEAL CABINET SIDE(R) 1 F-US(310X155XT5)

    65 3108503000 SEAL CABINET FLANGE 1 F-US(540X10XT5)

    66 7112401211 SCREW TAPPING 6 T1 TRS M4X12 POLY/WAS MFNI

    67 3102401900 GRILLE FRONT 1 ABS

    68 3108503700 SEAL FRONT(C) 2 F-US(80X20XT30)

    69 3108503500 SEAL FRONT(A) 1 F-US(600X20XT10)

    70 3108503600 SEAL FRONT(B) 1 F-US(420X20XT10)

    71 3106501100 BLADE 2 PP

    72 3101600400 DECO FRONT 1 PC T0.4

    73 7122401211 SCREW TAPPING 1 T2S TRS 4X12 MFZN

    74 3100035200 ASS’Y KNOB 2 DW-070

    75 3101901800 FILTER PRE 1 ABS+MESH#32

  • 8/17/2019 AirCon Training Manual

    43/175

    43

    DWB-070C EXPLODED DIAGRAM

  • 8/17/2019 AirCon Training Manual

    44/175

    44

    DWB-091C EXPLODED DIAGRAM

  • 8/17/2019 AirCon Training Manual

    45/175

    45

    DWB-121C PART LIST

    No. CODE COMPONENTS Q’TY SPECIFICATION REMARK

    1 3102402400 GRILL FRONT 1 HIPS

    2 3103400700 KNOB 2 HIPS

    3 3101600600 DECORATE FRONT 1 PC FILM

    4 3101902100 FILTER PRE 1 HIPS

    5 3106501800 BLADE VERTICAL 1 HIPS

    6 3106501700 BLADE HORIZENTAL 2 PP

    7 3108503600 SEAL GRILLE 1 F–US

    8 3108100900 PAN BASE 1 SGCC T1.0

    9 3107400800 ASS’Y EVAPORATOR 1 350X330.2(ø9.52 2R2C) DWC-121C/CS(ONLY)

    10 3104421100 PIPE EVA IN 1 C1220T–O OD9.52 DWC-121C/CS(ONLY)

    11 3100063600 PIPE EVA OUT AS 1 C1220T–O OD9.52 DWC-121C/CS(ONLY)

    12 3104421700 PIPE EVA OUT 1 1 C1220T–O OD9.52 DWC-121C/CS(ONLY)

    13 3104423100 PIPE SUNCTION 1 C1220T–O OD12.7 DWC-121C/CS(ONLY)

    14 3100061600 PIPE CAPILLARY AS 1 C1220T–O ID1.6 L800 DWC-121C/CS(ONLY)

    3100061610 PIPE CAPILLARY AS 1 C1220T–O DWA-150C/CS(ONLY)

    15 3107101190 COMP AS 1 LG–QK164CN12DWC-121C/CS(ONLY)

     – COMP AS 1 LG–QJ196KC23 DWA-150C/CS(ONLY)

    16 3104425800 PIPE DISCHARGE 1 C1220T–O OD7.94 DWC-121C/CS(ONLY)

    17 3100063500 PIPE COND OUT AS 1 C1220T–O OD7 DWC-121C/CS(ONLY)

    18 3100063400 PIPE COND IN AS 1 C1220T–O OD7 DWC-121C/CS(ONLY)

    19 3106800300 ASS’Y CONDESOR 1 515X341.5 (ø7 3R2C) DWC-121C/CS(ONLY)

    3106800310 ASS’Y CONDESOR 1 515X341.5 (ø7 3R2C) DWA-150C/CS(ONLY)

    19-1 3108504300 SEAL COND TOP 1 F–US DWC-121C/CS(ONLY)

    20 3101202800 CLIP FAN 2 SK-5

    21 3101802600 PAN BLOWER1 ABS

    22 3101404100 COVER MOTOR 1 EPS

    23 3104202000 PANEL HOUSING 1 SGCC T1.024 3102000500 FIXTURE RUBBER 1 NBR

    24-1 3100000010 BUSHING GUIDE 1 NBR

    25 3108005100 MOTOR FAN 1 DAEWOO MOTOR (AM 12DWD11) DWA-150C/CS(ONLY)

    26 7007501211 SCREW HEX 4 SX12MFZN

    27 3101802700 FAN PROPELLER 1 ABS + GF20%

    28 3102201100 WINDOW KIT FRAME(L) 1 HIPS

    29 3102201000 WINDOW KIT FRAME(R) 1 HIPS

    30 3100604200 PLATE WINDOW TOP 1 SGCC T1.2

    31 3100801400 CABINET AS 1 SGCC T0.8

    32 3100604300 BRACKET WINDOW LOWER 2 SGCC T0.8

    33 3100604500 BRACKET SILL 2 SGCC T1.6

  • 8/17/2019 AirCon Training Manual

    46/175

    46

    No. CODE COMPONENTS Q’TY SPECIFICATION REMARK

    34 3106600600 SCROLL LOWER 1 EPS

    35 3103700100 LEVER VENT 1 PP

    36 3103700100 WASHER VENT 1 PP

    37 3104600100 RING VENT 1 NBR

    38 3107000100 CLIP THERMO 1 ABS

    39 5SM0101700 THERMOSTAT AS 1 PFA 602GF

    40 5S10405100 SWITCH ROTARY 1 SR6B41610D

    41 3101300600 POWER CORD 1 MP 231 250V/10A

    42 3109503300 CAPACITOR 1 400VAC 5/35µF

    43 3101201600 CLAMP CAPACITOR 1 SGCC T0.8

    44 3966031000 MOTOR SWING 1 200/220V 50/60Hz

    45 3100508500 BOX CONTROL 1 SGCC T0.8

    46 3106600500 SCROLL UPPER 1 EPS

    47 3103002800 HOLDER SCROLL 2 SGCC

    48 3104409300 PIPE RUBBER BUTYL 1 –  

    49 3102708800 HANESS COMP AS 1 UL1015–16,BLK,RED,WHT

    50 3103200500 CAP DRAIN 1 ABS

  • 8/17/2019 AirCon Training Manual

    47/175

    47

    DWB-121C EXPLODED DIAGRAM

  • 8/17/2019 AirCon Training Manual

    48/175

    48

    5. SPLIT ROOM AIRCON

    MODELDSB-070L DSB-070LH DSB-091L DSB-091LH

    ITEM

    Function Cooling Cooling & Heating Cooling Cooling & Heating

    Class T T T T

    Power AC 220~ 240V/ 50Hz AC 220~ 240V/ 50Hz AC 220~ 240V/ 50Hz AC 220~ 240V/ 50Hz

    CapacityW 2,051 2,051 / 2,051 2,637 2,637 / 2,637

    Btu/h 7,000 7,000 / 7,000 9,000 9,000 / 9,000

    Dehumidification l/h 0.89 0.89 1.15 1.15

    Running Current A 2.9 3 / 3.2 4.2 4.0 / 4.2

    Power Input W 680 676 / 693 920 910 / 940

    Starting Current A 18 18 21 24

    Type Rotary Rotary Rotary Rotary

    Model QB 125PL 12B QB 134PL 12B QBB090A001 QK 164PN12F RBB100A001 QK 185PN13B

    Capacitor 25µF / 370VAC 25µF / 400VAC 25µF / 370VAC 30µF / 370VAC 30µF / 450VAC 35µF / 400VAC

    Indoor Unit Outdoor Unit Indoor Unit Outdoor Unit Indoor Unit Outdoor Unit Indoor Unit Outdoor Unit

    Type Cross flow fan Propeller fan Cross flow fan Propeller fan Cross flow fan Propeller fan Cross flow fan Propeller fan

    Capacitor 1.0µF 400VAC 1.8µF 400V 1.0µF 400VAC 1.8µF 400V 1.0µF 400VAC 1.8µF 400V 1.0µF 400VAC 1.8µF 400V

    Motor Model Number IC-8417DWKF5A IC-9625DWLF5A IC-8417DWKF5A IC-9625DWLF5A IC-8417DWKF5A IC-9630DWLF5A IC-8417DWKF5A IC-9630DWLF5A

    Control Capillary Capillary Capillary Capillary

    Charge Q'ty g 800 900 1,000 1,150

    Type Flare Flare Flare Flare

    OD(Liquid/Suction) in(mm) 1/4 (6.35) 1/2 (12.7) 1/4 (6.35) 1/2 (12.7) 1/4 (6.35) 1/2 (12.7) 1/4 (6.35) 1/2 (12.7)

    Dimensions (W x H x D) mm 750x245x174 654x549x256 750x245x174 654x549x256 750x245x174 654x549x256 750x245x174 654x549x256

    Net Weight kg 7.0 34 7.0 34 7.0 34 7.0 34

    ElectricalData

    Compressor

    FanMotor

    Refrigerant(R-22)

    Connection

    1.GENERAL SPECIFICATIONS

  • 8/17/2019 AirCon Training Manual

    49/175

    49

    MODELDSB-121L DSB-121LH DSA-151L DSA-181L DSB-181L DSB-181LH

    ITEM

    Function Cooling Cooling & Heating Cooling Cooling Heating

    Class T T T

    Power AC 220~ 240V/ 50Hz AC 208~ 230V, 60Hz AC 208~230V, 60Hz AC 220~240V, 50Hz AC 220~ 240V/ 50Hz

    CapacityW 3,507 3,654 / 3,946 4,300 5,100 5,100 5,110 5,400

    Btu/h 12,000 12,500 / 13,500 15,500 17,500 17,500 15,500 18,500

    Dehumidification l/h 1.53 1.6 1.98 2.3 2.3 2.2

    Running Current A 5.7 7.0 / 6.5 6.6 8.3 9.8 10.8 11.5

    Power Input W 1.250 1,500 / 1,410 1,450 1,785 1,950 2,050 2,230

    Starting Current A 34 37 42 44 46

    Type Rotary Rotary Rotary Recipro Rotary

    Model RCB120A001 RCB150A001 RCA150A001 ECB185211A CRDQ-0200-PFJ 2JS350D6BA02

    Capacitor 25µF / 400VAC 35µF / 400VAC 30µF / 400VAC 35µF / 370VAC

    Indoor Unit Outdoor Unit Indoor Unit Outdoor Unit Indoor Unit Outdoor Unit

    Type Cross flow fan Propeller fan Cross flow fan Propeller Fan Cross flow fan Propeller fan

    Capacitor 1.0µF 400VAC 3.5µF 400V 1.2µF 400VAC 1.2µF 450VAC 3µF 370VAC

    Motor Model Number IC-8428DWKG7C IC-9430DWLC5B IC-9425DWKH6A IC-9425DWKH6A IC-9425DWKC5A IC-9425DWKC5A AM12DPD04

    Control Capillary Capillary Capillary

    Charge Q'ty g 1,300 1,060 1,250 1,450 1,150 1,320

    Type Flare Flare Flare

    OD(Liquid/Suction) in(mm) 1/4 (6.35) 1/2 (12.7) 1/4 (6.35) 1/4 (6.35) 1/2 (12.7)

    Dimensions (W x H x D) mm925x285x194 1,035x322x205 (Indoor)

    1,035x322x205 800x615x277

    800x615x277 (Outdoor)

    Net Weight kg 9.7 34 43 44 55.8 12.1 51.9

    ElectricalData

    Compressor

    FanMotor

    Refrigerant(R-22)

    Connection

    666x552x264(Before)

    654x549x256(After)

  • 8/17/2019 AirCon Training Manual

    50/175

    50

    750

    Plate Mounting

    REMOCON

    Connecting Pipe

    Grille Insert

    245

    REMOTE CONTROLLER

    Frame Grille

    Body

    Plate Mounting

    174

    2. STRUCTURE & PARTS OF NAME

    1) OUTLINE DIAGRAM OF INDOOR UNIT

    ¡ DSB-070L/LH, DSB-091L/LH

    REMOCON

    Filter - L Filter - R

    Grille Insert

    Frame Grille

    Body

    Plate Mounting

    Connecting Pipe

    Plate Mounting406

    194

            2        8        5

    925

    R EMO TEC O N TR O LLER

    ¡ DSB-121L/LH

    1035

    205

    322

    453

    ¿‹ Æ˘˜ ˙`

    ”fi `⁄˘̇

    `⁄„«…–‚fi‚ ̃

    ‰˙‡»– ‚Ø– ‚–

    ‰˙‡»– ‚ ˆ…

    ¡ DSA-151L/DSA-181L/DSB-181L

  • 8/17/2019 AirCon Training Manual

    51/175

    51

    256

    549

    654

    2) OUTLINE DIAGRAM OF OUTDOOR UNIT

    ¡ DSB-070L/LH, DSB-091L/LH, DSB-121L/LH

    277

    367

    615

    800

    ¡ DSA-151L/DSA-181L/DSB-181L/DSB-181LH

    Inlet

    Inlet

    Outlet

    Outlet

    Foot

    Foot Cushion

    Handle

    Cabinet Side Panel Top Guide Support

    Service Valve

    Cabinet Front

    InletInlet

    Outlet

    Foot

    Handle

    Panel Top

    Cabinet

    Service Valve

    DischargeGrille

  • 8/17/2019 AirCon Training Manual

    52/175

    52

    REMOTECONTROLLER

    Electrostatic Filter

    Deodorizing Filter

    Air Inlet

    Remote ControllerReceiver

    Power Plug

    Remote Controller

    Fan Direction(Up, Down)

    Air Outlet

    Antibacterial Filter

    Lamp

    3) STRUCTURE & PARTS OF NAME

    (1) INDOOR UNIT

    ¡ DSB-070L/LH, DSB-091L/LH

    Remote Control Signal Receiver

    This place is the part to receive the signal if itreceive the signal, you can hear the signal “beep.“beep. beep.”

    There is a switch panel at inside of FrontPanel. At the time of operating, open theFront Panel.

    Emergency switch can be used when the remotecontroller is lost or Testing.

    Remote switch is usually used by remotecontroller.

    Indoor Unit Display Switch Panel

    Timer (Yellow)Lights during the time

    reservation mode.

    Quick (Red)

    ON (Red)

    Lights when the

    operation is going on.

    Air clean (Green)

    EMR. REMOCON

  • 8/17/2019 AirCon Training Manual

    53/175

    53

    ¡ DSB-121L/LH

    Power Plug

    , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , ,  

    , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , ,  

    , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , ,  

    , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , ,  

    , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , ,  

    , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , ,  

    , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , ,  

    , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , ,  

    , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , ,  

    , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , ,  

    , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , ,  

    , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , , ,  

    Electrostatic Filter Deodorizing FilterAir Inlet

    AntibacterialFilter

    Air Outlet Fan Direction(Up, Down)

    Remote Controller

    RemoteControllerReceiver

    Lamp

    R    E     M     O     T      E     C     O     N     T      R     O     L   L   E     R     

    Remote Control Signal ReceiverThis place is the part to receive the signal if it receive thesignal, you can hear the signal "beep, beep".

    Timer (Yellow)Lights during the timereservation mode.

    ON (Red)Lights when theoperation isgoing on.

    There is a switch panel at inside of FrontPanel. At the time of operating, open theFront Panel.

    Air clean (Green) Quick(Red)

    EMERGENCY REMOTE

    Remote switch is usally used by RemoteController.

    Emergency switch can be used when the remotecontroller is lost or testing.

    Indoor Unit Display Switch Panel

    ON AIR CLEAN QUICK TIMER

  • 8/17/2019 AirCon Training Manual

    54/175

    54

    ¡ DSA-151L, DSA-181L, DSB-181L/LH

    Indoor Cover

    Electrostatic FilterRemoves dust

    particles from the air.

    (Option Filter)

    Deodorizing Filter

    Removes bad

    smells from the air.(Option Filter)

    Emergency/Remote SwitchSlide to select

    the desired position.

    IndicatorsIndicate the

    AC setting.

    Remote Sensor

    Power Plug

    Air CleaningFiltersRemoves dust

    and prohibitsgerms.

    AIR OUT

    Air In

    Sensor Wire

    Fan Direction(Up/Down)

    Fan Direction(Left/Right)

     O  N O  F  F

     E  N  T  E  R C

     A  N C  E  L

      T  I  M  E  R

      R  E S  E  T  F

     A  N  D  I  R

     .

      F A  N S

      P  E  E  D

      M O  D  E

     S  L  E  E

      P

     O  N / O  F

      F

      T  E  M  P

     .

    LCD Remote Controller

    Remote Control Signal Receiver

    This place is the part to receive the signal if it receivethe signal, you can hear the signal “beep. beep”.

    There is a switch panel at inside of Front Panel.

    At the time of operating, open the Front Panel.

    Emergency switch can be used when the remotecontroller is lost or Testing.

    Remote switch is usually used by remote controller.

    Indoor Unit Display Switch Panel

    ON (Red)

    Lights when the

    operation is going on.

    Air clean (Green)

    Timer (Yellow)

    Lights during the time

    reservation mode.

    Quick (Red)Lights during the

    time Quick

    Mode.

    Timer

    Quick

    Airclean

    ON

    EMERGENCY REMOTE

  • 8/17/2019 AirCon Training Manual

    55/175

    55

    Air Inlet (Side Back)

    Connection Wire

    Connecting Pipe

    Drain Hose

    Air Outlet

    ¡ DSA-151L, DSA-181L, DSB-181L/LH

    (2) OUTDOOR UNIT

    ¡ DSB-070L/LH, DSB-091L/LH, DSB-151L/LH

    AIR IN

    AIR OUT

    AC Cover

    Remove cover to access the AC connectionfrom this unit to the indoor unit.

    Connection Wire

    Drain Hose

    COPPER TUBING

    Service ValvesThe indoor and outdoorunits are connected bycopper tubes which areconnected here.

    Grounding ScrewGround the unit here.

    Ground Wire (Not supplied)

  • 8/17/2019 AirCon Training Manual

    56/175

    56

    MODE

    SLEEP

    ON/OFF

    TIMER

    ENTER/  CANCEL

    FAN SPEED

    TURBO/MILD

    Display

    Displays information

    pertaining to unit.

    TURBO/MILD

    Press to be colder the unit.

    TIMER ENTER/CANCEL Button

    Press to enter a timer setting or

    to cancel timer setting

    TIMER ON/OFF Button

    Press to set the unit of or on time.

    (0.5, 1, 1.5, 2, 2.5, 3, 4, 5, 6, 8,

    10, 12, 16, 20, 24hr)

    MODE Button

    Press to cycle through the modes

    (Auto/Quick/Cooling/Fan/Dry)

    SLEEP Button

    Press to set the unit for

    the sleep mode.

    FAN DIR. Button

    Press to select up/down

    direction for fan.

    FAN DIR. Button

    Press to select left/right

    direction for fan.

    ON/OFF Button

    Press to turn the unit

    on or off.

    TEMPERATURE Buttons

    Press to raise or lower

    the desired temperature.FAN SPEED Button

    Press to select the fan speed

    (High " ", Middle " ",

    Low " ").

    COVERSlide down to access most

    of the remote buttons.

    Slide down further to

    access the battery

    compartment.

    AUTO

    FAN DIR.

    FAN DIR.

    (3) EACH BUTTON OF REMOCON

  • 8/17/2019 AirCon Training Manual

    57/175

    57

    MODE Indicators (Auto/Quick/Cool/Fan/Dehumidifier)Lights to indicate the mode selected.

    TIMER Indicators (Include sleep)Lights to indicate the timer function mode.

    TEMPERATURE & RESERVATION TIME lndicatorLights to indicate the temperature or time.

    FAN DIRECTION IndicatorsLights to indicate thefan direction.

    NATURAL IndicatorLights to indicate thespeeds simulating a loreeze.

    FAN IndicatorsLights to indicatethe fan speed.

    AUTO

    MODE Indicators (Auto/Quick/Cool/Fan/Dehumidifier/Heat)Lights to indicate the mode selected.

    TIMER Indicators (Include sleep)Lights to indicate the timer function mode.

    TEMPERATURE & RESERVATION TIME lndicatorLights to indicate the temperature or time.

    FAN DIRECTION IndicatorsLights to indicate thefan direction.

    NATURAL IndicatorLights to indicate thespeeds simulating a loreeze.

    FAN IndicatorsLights to indicatethe fan speed.

    AUTO

    (4) REMOTE CONTROLLER DISPLAY

    ¡ DSB-070L, DSB-091L, DSB-121L

    ¡ DSB-070LH, DSB-091LH, DSB-121LH

    MODE Indicators (Auto/Quick/Cool/Fan/Dehumidifier)Lights to indicate the mode selected.

    TIMER Indicators (Include sleep)Lights to indicate the timer function mode.

    TEMPERATURE & RESERVATION TIME lndicatorsLights to indicate th