404 VENTS. Industrial and commercial ventilation | 01-2019 AIR HANDLING UNITS WITH HEAT RECOVERY AIR HANDLING UNITS WITH HEAT RECOVERY Description The air handling units are the fully featured ventila- tion units with heat recovery for air filtration, fresh air supply and stale air extract. The extract air heat is used for warming up of the supply air stream in the high-efficient plate heat exchanger. The units offer energy-efficient ventilation for cottages and flats and are compatible with round Ø 125 mm air ducts. Casing The casing is made of 15-26 mm thick expanded poly- propylene (EPP) sheets, possessing high heat- and sound-insulating properties. Filter Supply and extract air flows are purified through G4 panel filters. For extra supply air filtration a F8 filter is available as a specially ordered accessory. Fans High-efficient electronically commutated motors with external motor and impeller with backward curved blades. Such motors are the most state-of- the-art energy saving solution. EC motors are fea- tured with high performance and total speed con- trollable range. High efficiency reaching 90 % is the premium advantage of the electronically commutat- ed motors. Heat exchanger The VUT 270 V5(B) EC units are equipped with a counter- flow polystyrene heat exchanger. In the cold season the extract air heat is transferred to the intake air stream which reduces ventilation-gener- ated heat losses. This can lead to formation of condensate that is collect- ed in a special drain pan and discharged into the sew- age system. In the warm season the outside air heat is transferred to the exhaust air stream. This allows for a considerable reduction of the supply air temperature which, in its turn, reduces the air con- ditioning load. The VUE 270 V5(B) EC units are equipped with a coun- ter-flow heat exchanger with an enthalpy at the core. In the cold season the extract air heat and moisture are transferred to the supply air stream through the enthalpy. Heat recovery minimises heat losses from ventilation. In the warm season the outdoor air heat and mois- ture are transferred to the exhaust air stream through the enthalpy. This enables considerable reduction of the supply air temperature and humidity which, in its turn, reduces the air conditioning load. Bypass The VUT/VUE 270 V5B EC units are equipped with a bypass for summer ventilation (cooling of the prem- ise with a cool outside air). Automation The VUT/VUE 270 V5B EC A21 units are equipped with integrated control system. The A21 controller allows integrating the unit into the Smart Home sys- tem or BMS (Building Management Systems). Remote control panel is not included in the delivery set and is available as specially ordered accessory. The unit is controlled via Wi-Fi by means of the VENTS AHU mobile application that must be downloaded. The VUT/VUE 270 V5B EC A14 units are equipped with integrated control system and wall-mounted sen- sor control panel A14 with LED indication. The VUT/VUE 270 V5B EC A2 units are equipped with R-1/010 speed controller. Freeze protection For VUT/VUE 270 V5B EC A14, VUT/VUE 270 V5 EC A2 the freeze protection is realized by means of shutdown the supply fan. For VUT/VUE 270 V5B EC A21 the freeze protection is realized by means of turning the preheater on. Series VENTS VUT/VUE 270 V5(B) EC Heat recovery air handling units in sound- and heat-insulated casings. Air flow up to 300 m 3 /h. Heat recovery efficiency up to 98 % Designation key Series Rated air flow [m 3 /h] Installation type Casing design Bypass Motor type Control VUT: ventilation with heat recovery VUE: ventilation with energy recovery 270 V: vertical 5: expanded polypropylene (EPP) _: no bypass B: integrated bypass EC: synchronous electronically commutated motor A2 A14 A21 motor BUILDING MANAGEMENT SYSTEMS

Transcript of AIR HANDLING UNITS WITH HEAT RECOVERYter-flow heat exchanger with an enthalpy at the core. In the...

  • 404 VENTS. Industrial and commercial ventilation | 01-2019

    AIR HANDLING UNITS WITH HEAT RECOVERYAIR HANDLING UNITS WITH HEAT RECOVERY

    DescriptionThe air handling units are the fully featured ventila-tion units with heat recovery for air filtration, fresh air supply and stale air extract. The extract air heat is used for warming up of the supply air stream in the high-efficient plate heat exchanger. The units offer energy-efficient ventilation for cottages and flats and are compatible with round Ø 125 mm air ducts.

    Casing The casing is made of 15-26 mm thick expanded poly-propylene (EPP) sheets, possessing high heat- and sound-insulating properties.

    FilterSupply and extract air flows are purified through G4 panel filters. For extra supply air filtration a F8 filter is available as a specially ordered accessory.

    FansHigh-efficient electronically commutated motors with external motor and impeller with backward curved blades. Such motors are the most state-of-the-art energy saving solution. EC motors are fea-tured with high performance and total speed con-trollable range. High efficiency reaching 90 % is the premium advantage of the electronically commutat-ed motors.

    Heat exchanger The VUT 270 V5(B) EC units are equipped with a counter- flow polystyrene heat exchanger. In the cold season the extract air heat is transferred to the intake air stream which reduces ventilation-gener-ated heat losses.This can lead to formation of condensate that is collect-ed in a special drain pan and discharged into the sew-age system. In the warm season the outside air heat is transferred to the exhaust air stream. This allows for a considerable reduction of the supply air temperature which, in its turn, reduces the air con-ditioning load.

    The VUE 270 V5(B) EC units are equipped with a coun-ter-flow heat exchanger with an enthalpy at the core. In the cold season the extract air heat and moisture are transferred to the supply air stream through the enthalpy. Heat recovery minimises heat losses from ventilation. In the warm season the outdoor air heat and mois-ture are transferred to the exhaust air stream through the enthalpy. This enables considerable reduction of the supply air temperature and humidity which, in its turn, reduces the air conditioning load.

    BypassThe VUT/VUE 270 V5B EC units are equipped with a bypass for summer ventilation (cooling of the prem-ise with a cool outside air).

    AutomationThe VUT/VUE 270 V5B EC A21 units are equipped with integrated control system. The A21 controller allows integrating the unit into the Smart Home sys-tem or BMS (Building Management Systems). Remote control panel is not included in the delivery set and is available as specially ordered accessory. The unit is controlled via Wi-Fi by means of the VENTS AHU mobile application that must be downloaded.

    The VUT/VUE 270 V5B EC A14 units are equipped with integrated control system and wall-mounted sen-sor control panel A14 with LED indication. The VUT/VUE 270 V5B EC A2 units are equipped with R-1/010 speed controller.

    Freeze protectionFor VUT/VUE 270 V5B EC A14, VUT/VUE 270 V5 EC A2 the freeze protection is realized by means of shutdown the supply fan. For VUT/VUE 270 V5B EC A21 the freeze protection is realized by means of turning the preheater on.

    Series VENTS

    VUT/VUE 270 V5(B) EC

    Heat recovery air handling units in sound- and heat-insulated casings.

    Air flow up to 300 m3/h.Heat recovery efficiency up to 98 %

    Designation key

    Series Rated air flow [m3/h] Installation type Casing design Bypass Motor type Control

    VUT: ventilation with heat recovery

    VUE: ventilation with energy recovery

    270 V: vertical5: expanded

    polypropylene (EPP)

    _: no bypassB: integrated

    bypass

    EC: synchronous electronically commutated

    motor

    A2A14 A21

    motorBUILDING MANAGEMENT SYSTEMS

  • 405

    WWW.VENTILATION-SYSTEM.COM

    VENTS. Industrial and commercial ventilation | 01-2019

    WWW.VENTILATION-SYSTEM.COM

    VENT

    S VU

    T/VU

    E 270

    V5

    (B) E

    C

    AIR

    HAND

    LING

    UNIT

    S WIT

    H HE

    AT R

    ECOV

    ERY

    WWW.VENTILATION-SYSTEM.COM

    ModelDimensions [mm]

    Ø D B H L

    VUT/VUE 270 V5(B) EC 125 590 893 316

    Overall dimensions

    D

    H

    Functions A21 A14 A2

    External wired control panel

    option (A22) A14 speed controllerR-1/010

    Wired remote LCD control panel

    option (А25)

    - -

    External wireless control panel

    option (A22 Wi-Fi)

    - -

    BMSRS-485WI-FI

    EthernetMODBUS (RTU, TCP)

    - -

    Service Vents Cloud Server + - -Wi-Fi control via mobile application + - -Speed selection + + +

    Filter replacement indicationaccording to filter timer according to filter timer -according to pressure

    switch of filter clogging - -

    Alarm indication full alarm description in the mobile application alarm LED indication -

    Week scheduled operation + - -

    Bypass auto - -manual manual -Timer + - -Boost mode + - -Fireplace mode + - -

    Freeze protection cyclic shutdown of

    supply fan cyclic shutdown of

    supply fan cyclic shutdown of

    supply fan preheating (option) - -

    Reheater connection option - -Cooler connection option - -Control of minimum supply air temperature + - -Humidity control option option -CO2 control option option -VOC control option - -PM2.5 control option - -Fire detector option option -*Option. The function is available in case of mounting a respective accessory.

    Control and automation

    Installation The units are designed for wall and floor mounting. The access for unit and filter maintenance is available on the right and left side.

    Spigots

    Cable slots

    Extract fan with EC-motor

    Control unit

    G4 extract filter

    G4 supply filter

    F8 supply filter (Option)

    Heat exchanger

    Supply fan with EC-motor

    Drain pan

    Bypass

    Intake air

    Supply air

    Exhaust air

    Extract air

    Unit design

  • 406 VENTS. Industrial and commercial ventilation | 01-2019

    AIR HANDLING UNITS WITH HEAT RECOVERY

    Technical data

    VUT 270 V5(B) EC VUE 270 V5(B) EC

    Voltage 50 (60) Hz [V] 1~230

    Maximum power [W] 162

    Maximum current [A] 1.2

    Maximum air flow [m3/h] 300

    RPM [min-1] 3200

    Sound pressure level at 3 m distance [dBA] 34

    Transported air temperature [°C] -25…+40

    Casing mater expanded polypropylene (EPP)

    Insulation EPP 15…26 mm

    Extract filter G4

    Supply filter G4 (optional F8)

    Connected air duct diameter [mm] Ø125

    Weight [kg] 13 13.5

    Recovery efficiency [%] 87 up to 98 72 up to 94

    Heat exchanger type counter-flow

    Heat exchanger material polystyrene enthalpy

    SEC class for A14, A21 A+ A

    SEC class for A2 B B

    Accessories for air handling units

    Mod

    el

    G4

    pane

    l filte

    r

    F8 p

    anel

    filte

    r

    LCD

    con

    trol

    pan

    el

    Cont

    rol p

    anel

    Wi-F

    i con

    trol

    labl

    e co

    ntro

    l pa

    nel

    Inte

    rnal

    hum

    idity

    sen

    sor

    CO2 s

    enso

    r with

    indi

    catio

    n

    CO2 s

    enso

    r

    Hum

    idity

    sen

    sor

    VOC

    sens

    or (0

    -10

    V)

    CO2

    sens

    or (0

    -10

    V)

    Hum

    idity

    sen

    sor (

    0-10

    V)

    Rehe

    ater

    Preh

    eate

    r

    Syph

    on k

    it

    Air

    dam

    per

    Elec

    tric

    act

    uato

    r

    VUT 270 V5(B) EC A21

    SF 264x182x18

    G4

    SF 264x182x18

    F8

    A25 A22 A22 Wi-FiHV2 CO2-1 CO2-2 HR-S

    DPWQ 30600

    DPWQ 40200

    DPWC 11200

    NKD 125

    NKP 125

    SH-32

    KRV 125 LF230

    VUE 270 V5(B) EC A21 -

    VUT 270 V5(B) EC A14 - - - - - - - - SH-32

    VUE 270 V5(B) EC A14 - - - - - - - - -

    VUT 270 V5 EC A2 - - - - - - - - - - - - SH-32 - -

    VUE 270 V5 EC A2 - - - - - - - - - - - - - - -

  • 407

    WWW.VENTILATION-SYSTEM.COM

    VENTS. Industrial and commercial ventilation | 01-2019

    VENT

    S VU

    T/VU

    E 270

    V5

    (B) E

    C

    AIR

    HAND

    LING

    UNIT

    S WIT

    H HE

    AT R

    ECOV

    ERY

    0 10 20 30 40 50 60 70 80 90

    0

    100

    200

    300

    400

    500

    600

    700

    0 50 100 150 200 250 300 350

    VUT/VUE 270 V5(B) EC0.6 W/l/s0.8 W/l/s1.0 W/l/s1.2 W/l/s1.4 W/l/s1.6 W/l/s1.8 W/l/s2.0 W/l/s

    0 10 20 30 40 50 60 70 80 90

    80

    85

    90

    95

    100

    0 50 100 150 200 250 300 350

    0 10 20 30 40 50 60 70 80 90

    70

    75

    80

    85

    90

    95

    100

    0 50 100 150 200 250 300 350

    VUE 270 V5(B) EC

    VUT 270 V5(B) EC

    VENTS VUT/VUE 270 V5(B) EC

    Stat

    ic p

    ress

    ure

    ΔP

    [Pa]

    Air flow [l/s]

    Air flow [l/s]

    Air flow [l/s]

    Reco

    very

    effi

    cien

    cy [%

    ]Re

    cove

    ry

    effici

    ency

    [%]

    Air flow [m3/h]

    Air flow [m3/h]

    Air flow [m3/h]

    PointPower, W Sound pressure level at 3 m (1 m) distance [dBA]

    VUT/VUE 270 V5(B) EC VUT/VUE 270 V5(B) EC

    1 153 34 (44)

    2 150 34 (44)

    3 142 33 (43)

    4 62 30 (40)

    5 60 29 (39)

    6 59 28 (38)

    7 17 27 (37)

    8 17 23 (33)

    9 16 23 (33)

    Exhaust air spigot configu-ration Air flow [l/s]

    Specific fan power

    [W/l/s]

    Recovery efficiency

    [%]Kitchen + 1 additional wet

    room 21 0,73 85

    Kitchen + 2 additional wet rooms 29 0,86 84

    Kitchen + 3 additional wet rooms 37 1,08 82

    Kitchen + 4 additional wet rooms 45 1.39 81

    A-weighted sound power levelGen. Octave frequency band, Hz LpA, 3 m

    dBALpA, 1 m

    dBAdBA 63 125 250 500 1000 2000 4000 8000

    LwA to supply inlet dBA 82 65 63 65 80 74 74 68 64

    LwA to supply outlet dBA 66 60 56 55 63 58 49 40 33

    LwA to exhaust inlet dBA 85 64 67 71 81 77 79 75 67

    LwA to exhaust outlet dBA 71 51 64 62 68 60 60 50 42

    LwA environment dBA 55 37 45 44 53 43 43 40 38 34 44

    Calculation of air temperature at heat exchanger outlet:

    t = toutd + khr * (textr - toutd)/100,

    where

    toutd is outdoor air temperature [°C] textr is extract air temperature [°C] khr is heat exchanger efficiency (according to the diagram) [%]

  • 408 VENTS. Industrial and commercial ventilation | 01-2019

    AIR HANDLING UNITS WITH HEAT RECOVERY

    Application options

    Ventilation hood Isovent 150 insulated air ductCeiling connector with a disk valve

    Air handling unitFlexiVent air duct CollectorFloor connector with a grille