404 VENTS. Industrial and commercial ventilation | 01-2019
AIR HANDLING UNITS WITH HEAT RECOVERYAIR HANDLING UNITS WITH HEAT RECOVERY
DescriptionThe air handling units are the fully featured ventila-tion units with heat recovery for air filtration, fresh air supply and stale air extract. The extract air heat is used for warming up of the supply air stream in the high-efficient plate heat exchanger. The units offer energy-efficient ventilation for cottages and flats and are compatible with round Ø 125 mm air ducts.
Casing The casing is made of 15-26 mm thick expanded poly-propylene (EPP) sheets, possessing high heat- and sound-insulating properties.
FilterSupply and extract air flows are purified through G4 panel filters. For extra supply air filtration a F8 filter is available as a specially ordered accessory.
FansHigh-efficient electronically commutated motors with external motor and impeller with backward curved blades. Such motors are the most state-of-the-art energy saving solution. EC motors are fea-tured with high performance and total speed con-trollable range. High efficiency reaching 90 % is the premium advantage of the electronically commutat-ed motors.
Heat exchanger The VUT 270 V5(B) EC units are equipped with a counter- flow polystyrene heat exchanger. In the cold season the extract air heat is transferred to the intake air stream which reduces ventilation-gener-ated heat losses.This can lead to formation of condensate that is collect-ed in a special drain pan and discharged into the sew-age system. In the warm season the outside air heat is transferred to the exhaust air stream. This allows for a considerable reduction of the supply air temperature which, in its turn, reduces the air con-ditioning load.
The VUE 270 V5(B) EC units are equipped with a coun-ter-flow heat exchanger with an enthalpy at the core. In the cold season the extract air heat and moisture are transferred to the supply air stream through the enthalpy. Heat recovery minimises heat losses from ventilation. In the warm season the outdoor air heat and mois-ture are transferred to the exhaust air stream through the enthalpy. This enables considerable reduction of the supply air temperature and humidity which, in its turn, reduces the air conditioning load.
BypassThe VUT/VUE 270 V5B EC units are equipped with a bypass for summer ventilation (cooling of the prem-ise with a cool outside air).
AutomationThe VUT/VUE 270 V5B EC A21 units are equipped with integrated control system. The A21 controller allows integrating the unit into the Smart Home sys-tem or BMS (Building Management Systems). Remote control panel is not included in the delivery set and is available as specially ordered accessory. The unit is controlled via Wi-Fi by means of the VENTS AHU mobile application that must be downloaded.
The VUT/VUE 270 V5B EC A14 units are equipped with integrated control system and wall-mounted sen-sor control panel A14 with LED indication. The VUT/VUE 270 V5B EC A2 units are equipped with R-1/010 speed controller.
Freeze protectionFor VUT/VUE 270 V5B EC A14, VUT/VUE 270 V5 EC A2 the freeze protection is realized by means of shutdown the supply fan. For VUT/VUE 270 V5B EC A21 the freeze protection is realized by means of turning the preheater on.
Series VENTS
VUT/VUE 270 V5(B) EC
Heat recovery air handling units in sound- and heat-insulated casings.
Air flow up to 300 m3/h.Heat recovery efficiency up to 98 %
Designation key
Series Rated air flow [m3/h] Installation type Casing design Bypass Motor type Control
VUT: ventilation with heat recovery
VUE: ventilation with energy recovery
270 V: vertical5: expanded
polypropylene (EPP)
_: no bypassB: integrated
bypass
EC: synchronous electronically commutated
motor
A2A14 A21
motorBUILDING MANAGEMENT SYSTEMS
-
405
WWW.VENTILATION-SYSTEM.COM
VENTS. Industrial and commercial ventilation | 01-2019
WWW.VENTILATION-SYSTEM.COM
VENT
S VU
T/VU
E 270
V5
(B) E
C
AIR
HAND
LING
UNIT
S WIT
H HE
AT R
ECOV
ERY
WWW.VENTILATION-SYSTEM.COM
ModelDimensions [mm]
Ø D B H L
VUT/VUE 270 V5(B) EC 125 590 893 316
Overall dimensions
D
H
Functions A21 A14 A2
External wired control panel
option (A22) A14 speed controllerR-1/010
Wired remote LCD control panel
option (А25)
- -
External wireless control panel
option (A22 Wi-Fi)
- -
BMSRS-485WI-FI
EthernetMODBUS (RTU, TCP)
- -
Service Vents Cloud Server + - -Wi-Fi control via mobile application + - -Speed selection + + +
Filter replacement indicationaccording to filter timer according to filter timer -according to pressure
switch of filter clogging - -
Alarm indication full alarm description in the mobile application alarm LED indication -
Week scheduled operation + - -
Bypass auto - -manual manual -Timer + - -Boost mode + - -Fireplace mode + - -
Freeze protection cyclic shutdown of
supply fan cyclic shutdown of
supply fan cyclic shutdown of
supply fan preheating (option) - -
Reheater connection option - -Cooler connection option - -Control of minimum supply air temperature + - -Humidity control option option -CO2 control option option -VOC control option - -PM2.5 control option - -Fire detector option option -*Option. The function is available in case of mounting a respective accessory.
Control and automation
Installation The units are designed for wall and floor mounting. The access for unit and filter maintenance is available on the right and left side.
Spigots
Cable slots
Extract fan with EC-motor
Control unit
G4 extract filter
G4 supply filter
F8 supply filter (Option)
Heat exchanger
Supply fan with EC-motor
Drain pan
Bypass
Intake air
Supply air
Exhaust air
Extract air
Unit design
-
406 VENTS. Industrial and commercial ventilation | 01-2019
AIR HANDLING UNITS WITH HEAT RECOVERY
Technical data
VUT 270 V5(B) EC VUE 270 V5(B) EC
Voltage 50 (60) Hz [V] 1~230
Maximum power [W] 162
Maximum current [A] 1.2
Maximum air flow [m3/h] 300
RPM [min-1] 3200
Sound pressure level at 3 m distance [dBA] 34
Transported air temperature [°C] -25…+40
Casing mater expanded polypropylene (EPP)
Insulation EPP 15…26 mm
Extract filter G4
Supply filter G4 (optional F8)
Connected air duct diameter [mm] Ø125
Weight [kg] 13 13.5
Recovery efficiency [%] 87 up to 98 72 up to 94
Heat exchanger type counter-flow
Heat exchanger material polystyrene enthalpy
SEC class for A14, A21 A+ A
SEC class for A2 B B
Accessories for air handling units
Mod
el
G4
pane
l filte
r
F8 p
anel
filte
r
LCD
con
trol
pan
el
Cont
rol p
anel
Wi-F
i con
trol
labl
e co
ntro
l pa
nel
Inte
rnal
hum
idity
sen
sor
CO2 s
enso
r with
indi
catio
n
CO2 s
enso
r
Hum
idity
sen
sor
VOC
sens
or (0
-10
V)
CO2
sens
or (0
-10
V)
Hum
idity
sen
sor (
0-10
V)
Rehe
ater
Preh
eate
r
Syph
on k
it
Air
dam
per
Elec
tric
act
uato
r
VUT 270 V5(B) EC A21
SF 264x182x18
G4
SF 264x182x18
F8
A25 A22 A22 Wi-FiHV2 CO2-1 CO2-2 HR-S
DPWQ 30600
DPWQ 40200
DPWC 11200
NKD 125
NKP 125
SH-32
KRV 125 LF230
VUE 270 V5(B) EC A21 -
VUT 270 V5(B) EC A14 - - - - - - - - SH-32
VUE 270 V5(B) EC A14 - - - - - - - - -
VUT 270 V5 EC A2 - - - - - - - - - - - - SH-32 - -
VUE 270 V5 EC A2 - - - - - - - - - - - - - - -
-
407
WWW.VENTILATION-SYSTEM.COM
VENTS. Industrial and commercial ventilation | 01-2019
VENT
S VU
T/VU
E 270
V5
(B) E
C
AIR
HAND
LING
UNIT
S WIT
H HE
AT R
ECOV
ERY
0 10 20 30 40 50 60 70 80 90
0
100
200
300
400
500
600
700
0 50 100 150 200 250 300 350
VUT/VUE 270 V5(B) EC0.6 W/l/s0.8 W/l/s1.0 W/l/s1.2 W/l/s1.4 W/l/s1.6 W/l/s1.8 W/l/s2.0 W/l/s
0 10 20 30 40 50 60 70 80 90
80
85
90
95
100
0 50 100 150 200 250 300 350
0 10 20 30 40 50 60 70 80 90
70
75
80
85
90
95
100
0 50 100 150 200 250 300 350
VUE 270 V5(B) EC
VUT 270 V5(B) EC
VENTS VUT/VUE 270 V5(B) EC
Stat
ic p
ress
ure
ΔP
[Pa]
Air flow [l/s]
Air flow [l/s]
Air flow [l/s]
Reco
very
effi
cien
cy [%
]Re
cove
ry
effici
ency
[%]
Air flow [m3/h]
Air flow [m3/h]
Air flow [m3/h]
PointPower, W Sound pressure level at 3 m (1 m) distance [dBA]
VUT/VUE 270 V5(B) EC VUT/VUE 270 V5(B) EC
1 153 34 (44)
2 150 34 (44)
3 142 33 (43)
4 62 30 (40)
5 60 29 (39)
6 59 28 (38)
7 17 27 (37)
8 17 23 (33)
9 16 23 (33)
Exhaust air spigot configu-ration Air flow [l/s]
Specific fan power
[W/l/s]
Recovery efficiency
[%]Kitchen + 1 additional wet
room 21 0,73 85
Kitchen + 2 additional wet rooms 29 0,86 84
Kitchen + 3 additional wet rooms 37 1,08 82
Kitchen + 4 additional wet rooms 45 1.39 81
A-weighted sound power levelGen. Octave frequency band, Hz LpA, 3 m
dBALpA, 1 m
dBAdBA 63 125 250 500 1000 2000 4000 8000
LwA to supply inlet dBA 82 65 63 65 80 74 74 68 64
LwA to supply outlet dBA 66 60 56 55 63 58 49 40 33
LwA to exhaust inlet dBA 85 64 67 71 81 77 79 75 67
LwA to exhaust outlet dBA 71 51 64 62 68 60 60 50 42
LwA environment dBA 55 37 45 44 53 43 43 40 38 34 44
Calculation of air temperature at heat exchanger outlet:
t = toutd + khr * (textr - toutd)/100,
where
toutd is outdoor air temperature [°C] textr is extract air temperature [°C] khr is heat exchanger efficiency (according to the diagram) [%]
-
408 VENTS. Industrial and commercial ventilation | 01-2019
AIR HANDLING UNITS WITH HEAT RECOVERY
Application options
Ventilation hood Isovent 150 insulated air ductCeiling connector with a disk valve
Air handling unitFlexiVent air duct CollectorFloor connector with a grille