Air Filtration Systems • Air Filter Elements • Air Filter Media Exhaust Systems … · 2018. 3....
Transcript of Air Filtration Systems • Air Filter Elements • Air Filter Media Exhaust Systems … · 2018. 3....
Gas Turbine Systems
NORTHERN STATIC FILTERS NorrVee and NorrCel Filters
Air Filtration Systems • Air Filter Elements • Air Filter Media Exhaust Systems • Inlet Cooling Systems • Turbine Auxiliary Equipment
www.filtration-ltd.co.uk
2
STATIC FILTERS - NorrVee and NorrCel
NorrVee Series Grade M6 - E12
Technical and Construction Data
• High efficiency static filter element
• Water and oil resistant media
• High dust holding capacity (DHC)
• Ease of installation
• Durability
• Low initial and operating pressure drop
• Operational under severe environmental conditions
• Long filter life - less filter replacement
• Plastic executionKEY BENEFITS
Standard Version (12”): 592mm x 592mm x 292mm
NV 60 NV 90 NV 95 NV 98 NV 100 NV 110 NV 120
Filter Area 18.2m2 18.2m2 18.2m2 18.2m2 18.2m2 18.2m2 18.2m2
Initial Efficiency 30% @ 0.4µm 50% @ 0.4µm 70% @ 0.4µm 80% @ 0.4µm >85% @ M.P.P.S >95% @ M.P.P.S >99.5% @ M.P.P.S
Avg Efficiency (0.4µm) 60-80% 80-90% 90-95% >95% >99% >99.9% >99.9%
Initial DP
@3400m3/hr 80 Pa 95 Pa 105 Pa 125 Pa 158 Pa 170 Pa 280 Pa
@4250m3/hr 105 Pa 120 Pa 130 Pa 155 Pa 200 Pa 210 Pa 350 Pa
Rec Final DP 635 Pa 635 Pa 635 Pa 635 Pa 635 Pa 635 Pa 635 Pa
Avg Arrestance >98% >99% >99% >99% >99.9% >99.9% >99.9%
Burst DP 3800 Pa 3800 Pa 3800 Pa 3800 Pa 3800 Pa 3800 Pa 3800 Pa
Grade
EN779:2012 M6 F7 F8 F9
EN1822:2009 E10 E11 E12
• Higher Power Output and Increased Turbine Availability
The filter elements optimize power output
by eliminating performance reducing
deposits in your compressor section.
Their outstanding filtration efficiency
reduces power losses while improving fuel
consumption. Machine availability and
reliability are also significantly increased
as off-line compressor washing frequency
is reduced.
• Reduced Fuel and Maintenance Costs
The filter elements significantly reduce
maintenance costs while increasing
compressor and turbine life. Unlike current
air intake filters, they provide increased
efficiency which reduces unexpected
failures and major outages by preventing
fine and corrosive particulate from
reaching the compressor blades.
• Water and Oil Resistant Media
All NorrVee series filters are composed of
media that is water and oil resistant and
can withstand exposure to free moisture
in the air-stream. When wet, the moisture
accumulates over the media and drains
down the vertically pleated packs. The
design ensures no moisture carry-over.
Deep Version (17”): 592mm x 592mm x 440mm
NV H60 NV H90 NV H95 NV H98 NV H100 NV H110 NV H120
Filter Area 33.0m2 33.0m2 33.0m2 33.0m2 33.0m2 33.0m2 33.0m2
Initial Efficiency 30% @ 0.4µm 50% @ 0.4µm 70% @ 0.4µm 80% @ 0.4µm >85% @ M.P.P.S >95% @ M.P.P.S >99.5% @ M.P.P.S
Avg Efficiency (0.4µm) 60-80% 80-90% 90-95% >95% >99% >99.9% >99.9%
Initial DP
@3400m3/hr 62 Pa 70 Pa 80 Pa 95 Pa 120 Pa 126 Pa 225 Pa
@4250m3/hr 80 Pa 90 Pa 100 Pa 117 Pa 150 Pa 160 Pa 280 Pa
Rec Final DP 635 Pa 635 Pa 635 Pa 635 Pa 635 Pa 635 Pa 635 Pa
Avg Arrestance >98% >99% >99% >99% >99.9% >99.9% >99.9%
Burst DP 3800 Pa 3800 Pa 3800 Pa 3800 Pa 3800 Pa 3800 Pa 3800 Pa
Grade
EN779:2012 M6 F7 F8 F9
EN1822:2009 E10 E11 E12
FEATURES
3
DONALDSON FILTRATION SOLUTIONS
Standard Version (12”): 592mm x 592mm x 292mm
NV 60 NV 90 NV 95 NV 98 NV 100 NV 110 NV 120
Filter Area 18.2m2 18.2m2 18.2m2 18.2m2 18.2m2 18.2m2 18.2m2
Initial Efficiency 30%@0.4µm 50%@0.4µm 70%@0.4µm 80%@0.4µm >85%@M.P.P.S >95%@M.P.P.S >99.5%@M.P.P.S
Avg Efficiency (0.4µm) 60-80% 80-90% 90-95% >95% >99% >99.9% >99.9%
Initial DP
@3400m3/hr 80 Pa 95 Pa 105 Pa 125 Pa 158 Pa 170 Pa 280 Pa
@4250m3/hr 105 Pa 120 Pa 130 Pa 155 Pa 200 Pa 210 Pa 350 Pa
Rec Final DP 635 Pa 635 Pa 635 Pa 635 Pa 635 Pa 635 Pa 635 Pa
Avg Arrestance >98% >99% >99% >99% >99.9% >99.9% >99.9%
Burst DP 3800 Pa 3800 Pa 3800 Pa 3800 Pa 3800 Pa 3800 Pa 3800 Pa
Grade
EN779:2012 M6 F7 F8 F9
EN1822:2009 E10 E11 E12
Deep Version (17”): 592mm x 592mm x 440mm
NV H60 NV H90 NV H95 NV H98 NV H100 NV H110 NV H120
Filter Area 33.0m2 33.0m2 33.0m2 33.0m2 33.0m2 33.0m2 33.0m2
Initial Efficiency 30%@0.4µm 50%@0.4µm 70%@0.4µm 80%@0.4µm >85%@M.P.P.S >95%@M.P.P.S >99.5%@M.P.P.S
Avg Efficiency (0.4µm) 60-80% 80-90% 90-95% >95% >99% >99.9% >99.9%
Initial DP
@3400m3/hr 62 Pa 70 Pa 80 Pa 95 Pa 120 Pa 126 Pa 225 Pa
@4250m3/hr 80 Pa 90 Pa 100 Pa 117 Pa 150 Pa 160 Pa 280 Pa
Rec Final DP 635 Pa 635 Pa 635 Pa 635 Pa 635 Pa 635 Pa 635 Pa
Avg Arrestance >98% >99% >99% >99% >99.9% >99.9% >99.9%
Burst DP 3800 Pa 3800 Pa 3800 Pa 3800 Pa 3800 Pa 3800 Pa 3800 Pa
Grade
EN779:2012 M6 F7 F8 F9
EN1822:2009 E10 E11 E12
NorrCel Series Grade F7 - E12
Technical and Construction Data
• High efficiency static filter element
• High dust holding capacity (DHC)
• Ease of installation
• Durability
• Low initial and operating pressure drop
• Operational under severe environmental conditions
• Long filter life - less filter replacement
• Plastic execution as well as metallic execution available
KEY BENEFITS
RM 90 XL 90 RM 95 XL 95 XN 98 XN 120
Filter Area 9.6m2 12.6m2 9.6m2 12.6m2 20.0m2 20.0m2
Initial Efficiency 59% @ 0.4µm 59% @ 0.4µm 71% @ 0.4µm 71% @ 0.4µm 80% @ 0.4µm >99.5% @ M.P.P.S
Avg Efficiency (0.4µm) 80-90% 80-90% 90-95% 90-95% >95% >99.9%
Initial DP
@3400m3/hr 180 Pa 170 Pa 190 Pa 180 Pa 200 Pa 350 Pa
@4250m3/hr 250 Pa 240 Pa 270 Pa 250 Pa 260 Pa 380 Pa
Rec Final DP 635 Pa 635 Pa 635 Pa 635 Pa 635 Pa 635 Pa
Avg Arrestance >99% >99% >99% >99% >99.9% >99.9%
Burst DP 3000 Pa 3000 Pa 3000 Pa 3000 Pa 3000 Pa 3000 Pa
Grade
EN779:2012 F7 F7 F8 F8 F9
EN1822:2009 E12
Nominal Flow Rate 3400m3/hr 3400m3/hr 3400m3/hr 3400m3/hr 3400m3/hr 3400m3/hr
• Higher Power Output and IncreasedTurbine Availability
The filter elements optimize power output
by eliminating performance reducing
deposits in your compressor section.
Their outstanding filtration efficiency
reduces power losses while improving fuel
consumption. Machine availability and
reliability are also significantly increased
as off-line compressor washing frequency
is reduced.
• Reduced Fuel and Maintenance Costs
The filter elements significantly reduce
maintenance costs while increasing
compressor and turbine life. Unlike current
air intake filters, they provide increased
efficiency which reduces unexpected
failures and major outages by preventing
fine and corrosive particulate from
reaching the compressor blades.
FEATURES
Maximum Operating Temperature: 60° C
Header and Side Plates: Galvanized or Polystyrene
Gasket (Optional): Polyurethane
Actual Dimension: 592mm x 592mm x 292mm
Nominal Dimension: 24” x 24” x 12”
Separators: Aluminium or Hot Melt
Media: Fibreglass
Global Support• Facilities in 37 countries• 40 manufacturing plants and 14 distribution centers
Leading Technology• Inlet Filters• Evaporative cooler media• Ancillary parts & equipment• Conversions, modifications, and upgrades
Experience and Service• Retro-fit projects• Filter replacement services• Technical advisory services
Donaldson Gas Turbine Systems is the leading global provider of inlet air systems, replacement parts and technical services.
Brochure No. 14GTS006_Static Filters(11/14)© 2014 Printed in Australia. All rights reserved. Information in this document is subject to change without notice.
Donaldson Australasia Pty LtdPO Box 153, Wyong NSW [email protected]: 1800 345 837
North & South [email protected]
Europe, Middle East, [email protected]
www.donaldson.com www.northern.ae
Filtration Ltd, 303B Dean Road, Avonmouth, Bristol, BS11 8AT