AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E...

48
AIR COOLED WATER CHILLERS -SCREW TYPE- Maintenance Instructions. Service Manual RCUE40AG1-400AG1 (R407C) Cooling Capacity 108 kW - 1068 kW

Transcript of AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E...

Page 1: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

AIR COOLEDWATER CHILLERS-SCREW TYPE-

Maintenance Instructions.

Service Manual

RCUE40AG1-400AG1 (R407C)Cooling Capacity 108 kW - 1068 kW

Page 2: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual
Page 3: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

0

TABLE OF CONTENTS

1.TROUBLESHOOTING ................................................................................................................. 11.1. OUTLINE OF FAILURE DIAGNOSIS.............................................................................................................21.2. ALARM INDICATION.................................................................................................................................31.3. FAILURE DIAGNOSIS METHOD41.4. ANALYSIS AND COUNTERMEASURE OF ABNORMAL RUNNING.......................................................................21

2. ELECTRICAL WIRING................................................................................................................ 272.1. CUSTOMER WIRING .................................................................................................................................272.2. WIRING DIAGRAM....................................................................................................................................292.3. MAIN CIRCUIT BOARD ..............................................................................................................................41

Page 4: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual
Page 5: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

TROUBLESHOOTING 1/1

1 TROUBLESHOOTING

1.1. OUTLINE OF FAILURE DIAGNOSIS

In the case of abnormality, alarm lamp of remote control and alarm LED on the control panel are ON. And segment indication onthe control panel is flickering. For stopping the unit, put it into stop operation without power OFF.

Alarm occur

Segment Indication:Abnormality Code Flickering.

Alarm Indication: ON(Local Side)

Remote Control Run Indication:ON

Remote Control Alarm Indication: ON(Remote Side)

Stop Operation

Is abnormality code in segment indication

confirmed?

Abnormality code is indicated by indication mode of alarm

Occurence Data.

Abnormality code is indicatedin the segment indication.

Take proper measure according to the alarm position

NOTE:- After the stop operation, alarm indication is turned off and initial status 88 is displayed. And then abnormality code, which

activated before is indicated by “Indication Mode of Alarm Occurrence Data”.- When the power turns off and turns on, the indication is initial status. And then abnormal code, which activated before is

indicated by “Indication Mode of Alarm Occurrence Data”

Yes

No

Page 6: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

1/2 TROUBLESHOOTING

1.2. ALARM INDICATION7-Segment indication shows the following abnormalities

Unit does not run Check the power source

Check the 7-segmentindication

Alarm CodeNo.1~6 cycles Description of abnormality

[]~[] Excessively Low Pressure

[]~[] Low Pressure Protection by Suction Gas Thermistor

[]~[] Excess Low Temperature of Cooler Inlet Refrigerant

[]~[] Freezing Protection Control by Cooler Inlet Refrigerant Temperature and excess low suction pressure (retryoperation)

[] Activation of Freezing Protection Control

[]~[] Activation of High Pressure Switch

[]~[] Activation of Discharge Gas Thermostat

[]~[] Activation of Compressor Internal Thermostat

[]~[] Phase Abnormally

[]~[] Error communication between Ctrl. PCB and Fan Speed Ctrl. PCBs (Low Ambient Fan Speed Ctrl. Option)

[]~[] Failure of Thermistor set before Expansion Valve (Open / Short)

[]~[] Activation of Fan Motor Internal Thermostat

[] Failure of Ambient Temperature Thermistor (Open / Short)

[]~[] Failure of Cooler Inlet Refrigerant Thermistor (Open/Short)

[]~[] Failure of Discharge Gas Thermistor (Open/Short)

[]~[] Failure of water oulet temperature thremistor i cooler siter (Open / Short)

[]~[] Failure of Suction Gas Thermistor (Open / Short)

[]~[] Failure of Discharge Gas Pressure Sensor (Open / Short)

[]~[] Failure of Suction Gas Pressure Sensor (Open / Short)

[] Error communication between Ctrl. PCB (PCBC1, PCBC2)

[] Failure of Water Inlet Temperature (Open / Short)

[] Failure of Water Outlet Temperature Thermistor (Open / Short)

[] Failure of Water Outlet 2 Temperature Thermistor (Open/Short)

[] Failure of Water Outlet 3 Temperature Thermistor (Open/Short)

[] Malfunction

[]~[] Activation of Differential Pressure Control

[]~[] Activation of Thermal Relay for Compressor

[]~[] No Feedback Signal from Water Pump

[]~[] Alarm of Excessively High Water -Temperature

[] Alarm of Water Failure (Differential Water Pressure Switch Option)

[] Activation of Additional Protection Device (Option)" " - " " : Flickering. XX - XX : SEG1-SEG2

With indication

Without indication

Page 7: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

TROUBLESHOOTING 1/3

1.3. FAILURE DIAGNOSIS METHOD

1.3.1. GENERAL CHECK OF FAILURE DIAGNOSIS.In the case of no segment indication, unit cannot operate.

Is 220-240V suppliedto the unit?:

Check the powersource switch

Is 220-240V supplied totransformer primary side? Is fuse broken? Replace fuse

Wiring check and repairIs R phase or S

phase failure?

Wiring check

Is 30V in PIN1~PIN2,16.3V IN PIN3~PIN4,

19.6V IN PIN5~PIN6 of the printed circuit board for CPU

(PCBc) connector CN2A

Is the wiring oftransformer broken? Replace

transformer

Wiring checkConnector check

Is the wiring oftransformer broken?

Replace transformer

Wiring checkConnector check

Is 26.7V in PIN1~PIN2,17.6V in PIN3~PIN4,

17.6V in PIN5~PIN6 of the printed circuit board for CPU

(PCBc) connector CN2B and CN2C

Is voltage in each test PIN of printed circuit boardfor CPU

5 V part VCCO5-GND1V5B-GND1

VCCO5N-GND1VCCR-GND1

+15V part VCC15T-GND1- 15V part VCC15T-GND1 24V part VCC24-GND1

VCC24T-GND1

Power Source CircuitMalfunction

Replace PrintedCircuit Board for

CPU (PCBC)

Are connector FCN1, FCN2on the printed circuit board forCPU (PCBC) and PrintedCircuit Board for Display andOperation (PCBA, PCBB)correctly connected andchecked loose connection?

Connector Repair

Check PrintedCircuit Board for

Display andOperation (PCBA,

PCBB)Check Printed

Circuit Board forCPU (PCBC)

No

Yes

Yes

Yes

YesNo

No

Yes

Yes

Yes

No

Yes

No

No

No

No

No

Yes

Yes

No

Page 8: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

1/4 TROUBLESHOOTING

! [] ~ [] Excessively Low Suction Pressure

In case of the suction pressure is less than 0.31 Mpa during 90 seconds, the unit will stop at once and indicate[]~[]. 3 minuts later, the unit will start again. This Alarm code is indicated when it occurs 3 times during 30minutes (It will retry until 2 times.).

Is connector CN 29Ps on theprinted circuit board for relay(PCBD) correctly connected?

Wiring Check

No

Shortage of Refrigerant Gas Leakage

Clogging of expansion valve

Clogging of strainer

Clogging of low pressure side pipe

Stop Valve malfunction

Shortage of Water

Pump reverse rotation

Air mixed

Deposits on Water Cooler Plates

Clogging of Water Strainer

Yes

Page 9: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

TROUBLESHOOTING 1/5

! [] ~ [] Low Pressure Protection by Suction Gas Thermistor

This alarm code is indicated when the suction temperature is lower than -2°C during 10 seconds.

Is the wiring of connector in thePrinted Circuit Board for Relay

(PCBD) correct?

Plug correctly andrepair wiring

Replace thermistorPull out connector and measure

thermistor resistance. Isresistance correct?

Check Printed Circuit Boardfor Relay (PCBD)

Thermistorresistance

(KΩ)

Temperature (°C)

Thermistor for Suction Gas Temperaturecharacteristics

Clogging of water strainer

Yes

No

YesCheck the water flow rate.(Check temperatureof inlet and outlet.)

Pump reverse rotating check

Check the air mixing

Clogging of expansion valve

Clogging of strainer

No

Check chilled water thermostat setting value(Within the working range)

Shortage of refrigerant Gas Leakage

Clogging of low pressure pipe

Malfunction of Check valve

Yes

Malfunction of Expansion Valve

Page 10: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

1/6 TROUBLESHOOTING

! []~[] Excess Low Temperature of Cooler Inlet Refrigerant

In case of the cooler inlet refrigerant temperature is lower than -3°C during 10 seconds, the unit will stop at once and indicate[]~[]. 3 minutes later, the unit will start again. This alarm code is indicated when it occurs 3 times during 30minutes (It will retry until 2 times)

Is connector CN27Tr2 on theprinted circuit board for Relay(PCBD) correctly connected?

Plug correctly andrepair wiring

Pull out connector and measurethermistor resistance.Is resistance correct?

Replace Thermistor

Check printed circuit board forRelay (PCBD)

No

Yes

Yes

No

Yes

Check water flow rate (Check thetemperature of Inlet and Outlet)

Check pump reverse rotation

Check water strainer clogging

Check air mixing

Check Chilled water thermostatsetting value (It shall be withinthe unit working range)

Shortage of Refrigerant GasLeakage

Clogging of low pressure side pipe

Clogging of expansion valve

Check Valve Malfunction

Expansion Valve Malfunction

Page 11: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

TROUBLESHOOTING 1/7

! [] Activation of Freeze Protection Control

This alarm code is indicated when the water inlet or outlet temperature is lower than 2°C.

Is connectors on the PrintedCircuit Board correctly connected?

PCBC:CN4,CN6,CN7,CN3PCBD:CN23Te2

Plug correctly andrepair wiring

Pull out connector and measurethermistor resistanceIs resistance correct?

Replace Thermistor

Check printed circuit board

Thermistorresistance

(KΩ)

Temperature (°C)

Thermistor for Water Temperaturecharacteristics

No

Yes

Yes

No

Yes

Check water flow rate (Check thetemperature of Inlet and Outlet)

Check pump reverse rotation

Check water strainer clogging

Check air mixing

Check Chilled water thermostatsetting value (It shall be withinthe working range)

Page 12: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

1/8 TROUBLESHOOTING

! ] ~ [] Activation of high pressure switch (PSH1~6)

This alarm code is indicated when the discharge pressure is higher than 2.74 Mpa.

Is alarm activated just afterrunning?

Is 220-240V the voltagebetween connectorPCN203 PIN1 andconnector PCN 203PIN3 on the Printed

Circuit Board for Relay(PCBD1~6)?

PCBD Check

Is alarm activated in 3minutes after running

operation?

Wiring Check(breaking of wire,

wrong wiring)

Is high pressure switch(PSH1~6) activated?

Check clogging in air side heat

exchanger

High PressureCheckIs high pressure

switch (PSH1~6) resetbutton activated?

ResetCycle Check

Is 220-240V the voltagebetween connectorPCN203 PIN1and

connector PCN 203PIN3 on the Printed

Circuit Board for Relay(PCBD1~6)?

Wiring check(breaking of wire,

wrong wiring)

Is 220-240V the voltagebetween connector PCN203

PIN1 and connector PCN 203PIN3 on the Printed Circuit Board

for Relay (PCBD1~6)?

Wiring Check Check PrintedCircuit Board forRelay (PCBD1~6)

Check Printed CircuitBoard for Relay ( PCBD 1~6)

NOTE:To check the nominal value for pressure refer to safety and control device setting table to the technical catalogue

Yes(Activate

immediately)

No (Activateafter a while)

Yes(PCB isnormal)

Yes

No

No

Yes

No

Yes

No

Yes

Yes

No (Activate a whileafter Compressor ON)

No

Page 13: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

TROUBLESHOOTING 1/9

! [] ~ [] Activation of Discharge Gas Thermostat

This alarm code is indiacted when the temperature in discharge pipe is higher than 140ºC

Is connector CN24Td on theprinted circuit board for relay(PCBD) correctly connected

Wiring check (breaking of wire, wrong wiring)

Pull out connector andmeasure thermistor resistance.

Is resistance correct?

Replace Thermistor

Thermistorresistance

(KΩ)

Temperature (°C)

Thermistor for Discharge Gas Temperaturecharacteristics

Yes

No

Yes Shortage of Refrigerant Gas Leakage

Check Valve Malfunction

Clogging of expansion valve

Expansion valve opening check

Clogging of strainer

Check PCBD

Page 14: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

1/10 TROUBLESHOOTING

! [] ~ [] Activation of Compressor Internal Thermostat

This alarm code is indicated when the compressor internal thermostat is higher than 115ºC

Is alarm activated just afterrunning?

Is 220-240V thevoltage between

connector PCN204PIN1 and connectorPCN 204 PIN3 onthe Printed CircuitBoard for Relay

(PCBD) ?

Check PrintedCircuit Board for

Relay (PCBD)

Wiring Check(breaking of wire,

wrong wiring)

Is 220-240V the voltage between connector PCN204 PIN1and connector PCN 204 PIN3 on

the Printed board for Relay(PCBD)?

Wiring Check

! [] ~ [] Phase Abnormality

This alarm code is indicated when the power source phase failure or reverse phase occur.

Is power source phasefailure or reverse phase? Power Supply,

Wiring Check

Is printed circuit board for relay(PCBD) connector R.S.T correctly

connected?Connection repair

Is the power source ofconnector R.S.T part phase

failure or reverse phase?

Repair to correctphase

Check printedcircuit board for relay

(PCBD)

Yes Yes

No

No (Activateafter a while)

Yes

No (Printed CircuitBoard is normal) Excessive or short power source voltage

Interphase of power source voltage is imbalanced.

Compressor motor is locked

Insulation of compressor motor is lowered

Yes (Phase Failure,Reverse Phase)

No

No

Yes

No (Correct Phase)

Yes

Page 15: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

TROUBLESHOOTING 1/11

! []~[] Error comunication between Ctrl. PCB and Fan speed Ctrl. PCB

This alarm code is indicated when the transmission signal is missing more than 5 seconds.

Is connector CN14A on theprinted circuit board for CPU(PCBC) correctly connected?

Plug correctly andrepair wiring

Is connector on the printedcircuit board for Fan speed

control (PCBE) correctlyconnected

Plug correctly andrepair wiring

Check the Printed circuit boardfor Fan speed control (PCBE)

Replace the printedcircuit board for

Fan Speed (PCBE)

Replace the printed circuitboard for CPU (PCBC)

Normal

Yes

Yes

No

No

Abnormal

Page 16: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

1/12 TROUBLESHOOTING

! []~[] Thermistor set before Expansion Valve Abnormality

This alarm code is indicated when the thermistor resistance is out of range (72 Ω ≤ Resistance ≤ 179 kΩ)

Is printed circuit board for relay(PCBD) connector CN22Te1

correctly connected?Plug, Wiring Repair

Disconnect connector andmeasure resistance. Is the

resistance correct? Replace thermistor

Replace printed circuitboard for relay (PCBD)

! []~[] Activation of Fan Motor Internal Thermostat

This alarm code is indicated when the fan motor internal thermostat is higher than 135ºC

Is alarm activated justafter running?

Is 220-240V the voltage between connector PCN206PIN1 and connector PCN206PIN3 on the Printed Circuit Board for Relay (PCBD)?

Check Printed CircuitBoard for Relay (PCBD)

Wiring check (breakingof wire, wrong wiring)

Is 220-240V the voltagebetween connector PCN206

PIN1 and connector PCN206 PIN3on the Printed circuit board for

Relay (PCBD)?

Wiring check

No

Yes

No

Yes

Yes(Activate

immediately)

Yes

No (activateafter a while)

Excessive or short power sourcevoltage

Interphase of power sourcevoltage is imbalanced

Fan Motor is locked

Insulation of Fan Motor is lowered

Yes

No

No (Printed CircuitBoard is normal)

Page 17: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

TROUBLESHOOTING 1/13

! [] [] [] [] [][]~ [] Temperature Thermistor Abnormality

This alarm code is indicated when the thermistor resistance is out of range.(Water Temperature Thermistor: 240 Ω ≤ Resistance ≤ 39 kΩ)(Ambient Temperature Thermistor: 240 Ω ≤ Resistance ≤ 600 kΩ)

[] Inlet Water Temperature Thermistor Abnormality[] [] [] Outlet Water Temperature Thermistor Abnormality[] Ambient Temperature Thermistor Abnormality

Is connector on the printedcircuit board for CPU (PCBc)

correctly connected?Plug, Wiring, Repair

Pull out connector andmeasure thermistor resistance.

Is resistance correct? Replace thermistor

Replace printed circuit boardfor CPU (PCBC)

[] [] [][]~ []

[]

Thermistorresistance

(KΩ)

Thermistor resistance

(KΩ)

Temperature (°C)

Thermistor for Water Temperaturecharacteristics

No

Yes

No

Yes

Page 18: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

1/14 TROUBLESHOOTING

! []~ [] Cooler Inlet Refrigerant Temperature Thermistor Abnormality

This alarm code is indicated when the thermistor resistance is out of range (72 Ω ≤ Resistance ≤ 179 kΩ)

Is printed circuit board for relay(PCBD) connector CN23Te2

correctly connected?Plug, Wiring Repair

Disconnect connector andmeasure resistance. Is the

resistance correct ? Replace thermistor

Replace printed circuitboard for relay (PCBD)

Thermistorresistance

(KΩ)

Temperature (°C)

Thermistor for Cooler Inlet Refrigerantcharacteristics

No

Yes

No

Yes

Page 19: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

TROUBLESHOOTING 1/15

! []~[] Discharge Gas Temperature Thermistor Abnormality

This alarm code is indicated when the thermistor resistance is out of range (Refer below table).

Is connector CN24 Td on thePrinted Circuit Board for Relay(PCBD) correctly connected?

Connect correctly

Pull out connector andmeasure thermistor resistance.

Is resistance correct? Replace thermistor

Check Printed Circuit Board

Thermistorresistance

(KΩ)

Air temperature (°C)

Thermistor for Discharge Gas Temperaturecharacteristics

No

Yes

No

Yes

Page 20: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

1/16 TROUBLESHOOTING

! []~[] Suction Gas Thermister Abnormality

This alarm code is indicated when the thermistor resistance is out of range (72 Ω ≤ Resistance ≤ 179 kΩ)

Is printed circuit board for relay(PCBD) connector CN25Ts

correctly connected?Plug, Wiring Repair

Disconnect connector andmeasure resistance. Is the

resistance correct? Replace thermistor

Replace printed circuitboard for relay (PCBD)

Thermistorresistance

(KΩ)

Temperature (°C)

Thermistor for Suction Gas Temperaturecharacteristics

No

Yes

No

Yes

Page 21: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

TROUBLESHOOTING 1/17

! [] [] Discharge Gas Pressure Sensor Abnormality

Malfunction of pressure sensor

Is connector CN28Pd on theprinted circuit board for relay(PCBD) correctly connected?

Connect correctly

Is DC24V betweenconnector CN28Pd PIN1 and

PIN3 on the printed circuitboard for relay (PCBD)?

Replace theprinted circuit board

for relay (PCBD)

Is less than DC 0.1V or more than DC 4.9V betweenconnector CN28Pd PIN2 and

PIN3 on the printed circuitboard for relay (PCBD) when

discharge gas pressuresensor is connected?

Replace the printedcircuit board for relay (PCBD)

Is discharge gas pressure sensor

connecting pipe clogging?

Remove clogging in the pipe.

Discharge gas PressureSensor Abnormality

Yes

Yes

Yes

Yes

No

No

No

No

Page 22: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

1/18 TROUBLESHOOTING

! [] [] Suction Gas Pressure Sensor Abnormality

Malfunction of pressure sensor

Is connector CN29Ps on theprinted circuit board for relay(PCBD) correctly connected?

Connect correctly

Is DC5V betweenconnector CN29Ps PIN1 and

PIN3 on the printed circuitboard for relay (PCBD)?

Replace theprinted circuit board

for relay (PCBD)

Is less than DC 0.1V or more than DC 4.9V betweenconnector CN29Ps PIN2 and

PIN3 on the printed circuitboard for relay (PCBD) when

suction gas pressuresensor is connected?

Replace the printedcircuit board for relay (PCBD)

Is suction gas pressure sensor

connecting pipe clogging?

Remove clogging in the pipe.

Suction gas PressureSensor Abnormality

! [] Error comunication between Ctrl. PCB

This alarm code is indicated when the transmission signal between Ctrol PCB is missing more than 30 seconds.

Is connector CN12 on thePrinted Circuit Board for CPU (PCBc) correctly

connected?

Plug correctlyand repair wiring

Check the printedcircuit board

for CPU (PCBC)

Yes

Yes

Yes

Yes

No

No

No

No

No

Yes

Page 23: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

TROUBLESHOOTING 1/19

! [] Alarm for Operation Error

Performed incorrect operation.

Is local operation?Is changeover to

local side during remoteoperation?

It is incorrect thatoperation changeover

to local side during remote operation.Do not perform it.

Wiring Check betweenremote control switch

and printed circuit board.

Is 220-240V between PIN1-PIN3of connector PCN16 on the printed

circuit board for CPU (PCBC)?

Check printed circuitboard for CPU (PCBC)

Is optional wiring connected? Is the signal transmitted from option device?

It is incorrect thatremote operation signal

is transmitted fromoption device during

local operation.Do not perform it.

Wiring Check betweenexternal device

and printing board

Is it changed over to remote side during local

operation?

It is incorrect operationthat changeover to

Remote Side duringLocal Operation.Do not perform it.

Check printed circuit board for display (PCBA)

Check printed circuitboard for operation (PCBB)

Check printed circuit board for CPU (PCBC)

! [] ~ [] Activation of Differential Pressure Control

This alarm code is indicated when the pressure difference between discharge and suction pressure is less than 0.3 Mpaduring 3 minutes.

Is connector CN28Pdand CN29Ps on the

Printed Circuit Board forRelay (PCBD) correctly

connected?

Plug correctlyand repair wiring

No

No (Remote)

Yes (Local)

Yes (NormalRunning)

Yes

Yes (NormalRunning)

No

No

Yes(NormalRunning)

No

No

Yes

No

Check Refrigerant oil strainer clogging

Check Refrigerant oil Quantity

Solenoid Valve for Compressor Malfunction

Compressor slide valve Malfunction

Yes

Page 24: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

1/20 TROUBLESHOOTING

! [] ~ [] Activation of Thermal Relay for Compressor

This alarm code is indicated when the compressor running current is more than thermal Relay Setting Value.

Is alarm activated just afterrunning operation?

Is 220-240V thevoltage between

connector PCN207PIN1 and connectorPCN 207 PIN3 onthe Printed CircuitBoard for Relay

(PCBD) ?

Check PrintedCircuit Board for

Relay (PCBD)

Wiring Check(breaking of wire,

wrong wiring)

Is 220-240V the voltage betweenconnector PCN207 PIN1 and

connector PCN 207 PIN3 on thePrinted board for Relay (PCBD)?

Wiring Check

! [] ~ [] No Feedback Signal from Water Pump

CMP pump feed back signal is not coming and Unit stops

Is 220-240V between PIN1 andPIN3 of connector PCN4 on the

printed circuit board for CPU(PCBC)

Is pump thermal relay forpump (TRP) activated?

Check pumplock

Check thermalrelay for pump

Check printed circuit board forCPU (PCBC)

Check wiringaround pump

and thermal relayfor pump

Yes (activatedimmediately) Yes

No

No (Activateafter a while)

Yes

No (Printed CircuitBoard is normal) Excessive or short power source voltage

Interphase of power source voltage is imbalanced.

Compressor motor is locked

Insulation of compressor motor is lowered

Power fuse for compressor motor is broken

Power source terminal screw loosened

Thermal relay for compressor failure

Compressor slide valve malfunction

Yes

No

No (Printed CircuitBoard is normal)

Yes

Page 25: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

TROUBLESHOOTING 1/21

1.4. ANALYSIS AND COUNTERMEASURE OF ABNORMAL RUNNINGChiller unit has various kinds of protection device. When the operation is not correct status due to the activation of someprotection device, refer to the table below and find out the main reason to take a countermeasure.1 failure can affect other different conditions. Thus, do not check only 1 point but analyze it from overall viewpoint in detail.

Phenomenon Cause Check Point Countermeasure

Power Failure Measure voltage by tester. Wait the recovery of power source

Power is OFF Check power switch. Power Switch ON

Wiring Short Circuit Check falling of wiring coating. Eliminate short-circuit and replace fuse.

Wiring Earth Fault Measure insulation resistance. Eliminate the earth fault and replace fuse.

Compressor Motor Failure Replace compressor and fuse.

Fuse forpower

source ismelted

Fan Motor Failure

Measure the interphaseresistance, insulation resistance. Replace fan motor and fuse

Wiring Short-circuit Check falling of wiring device. Eliminate short-circuit and replace fuse..

Earth Fault in Operation Circuit Measure insulation resistance. Eliminate earth fault and replace fuse

Magnetic Contactor forCompressor Motor Failure

Magnetic Contactorfor Fan Motor Failure

Magnetic Contactorfor pump motor Failure

Replace magnetic contactor and fuse.

Auxiliary Relay Coil Failure Replace auxiliary relay and fuse.

Solenoid Valve Coil Failure

Measure the coil resistance.

Replace solenoid coil and fuse.

Printed Circuit Board Short-Circuit Conductive Foreign Particle. Remove the particle and replace fuse

Fuse foroperationcircuit ismelted

Crankcase Heater Failure Measure resistance. Replace oil heater and fuse.

Trans Coil Failure Measure the transformersecondary voltage. Replace transformer.

Remote Control Wiring Incorrect Wiring Change wiring.

R, S, T phase of power source is phase failure or reverse phase. (05 alarm)

Check the connectionof R, S, and T phase Change to the correct phase.

Remote Control Switch Failure. Change-over switchof Printed Circuit Board is Local (40 alarm) Check changeover switch. Replace remote control switch.

Turn changeover switch on Remote

Wiring Connection Failure Repair the wiring connection

Replace the Printed Circuit Board

PrintedCircuitBoardFailure Printed Circuit Board Failure

Check the current by tester.

Breaking of Coil

It does notrun whenoperate

PumpMagneticContactorfor PumpFailure(52P)

Loose Connection

Measure the voltage of contactpoint of magnetic contactor

Replace magnetic contactor for pump

Pump locked Check water freeze, clogging of foreign particle. Remove it.

Pump Over-currentrelay RC Value Wrong

Check the RC value andpump running current.

Change the RC value orreplace magnetic contactor.

Pump stopsbefore

compressorrunning

Pump Over-currentRelay

Activated(TRP) (5P

Alarm)Pump over-current

relay failurePush reset button

and check running current. Replace magnetic contactor.

Page 26: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

1/22 TROUBLESHOOTING

Wiring Connection Failure Check circuit by tester Repair the wiringconnection

Printed Circuit BoardFailure Printed Circuit Board

Failure

Check circuit by tester CheckPrinted Circuit Board by self-

checking function

Replace Printed CircuitBoard

Remote Control Switch Failure Operative by the unit side Replace remotecontrol switch.

Coil Broken Check circuit by tester

Pump runs,but neither

fan norcompressor

run.

Fan Magnetic ContactorFailure (Cooling

Operation) Contact Point FailureMeasure the voltage between

contact points of magneticcontactor.

Replace magneticcontactor.

Fan Motor Failure Measure the interphaseresistance Replace fan motor

Pump andcompressorrun, but fandoes not run

Wiring Connection Failure

Printed Circuit BoardFailure

Check circuit by tester Repair the wiringconnection.Printed Circuit Board

Failure

Thermistor Malfunction Measure the thermistor resistance Replace thermistor

Coil Breaking Check circuit by tester

Compressor MagneticContactor Failure Contact points Failure

Measure the voltage betweencontact points of electromagnetic

contactor

Replace magneticcontactor

Thermostat is activated. (Thermo-Off) Change water temperature orchange the setting temperature. It is not failure

Compressor Motor Failure Measure the interphaseresistance

Pump andfan run butcompressor

does not run.

Compressor Failure Beat noise from compressor

Replace compressor

Voltage at starting up is low. Measure the voltage Consult with electricpower company

Excessive dust in air side heatexchanger

Inlet or outlet of air side heatexchanger is clogged

Remove it.

Shortage of Service Space forChiller Unit

Secure the servicespace

Insufficient air in air sideheat exchanger

Reverse Rotation of Fan Motor Change wiring for fanmotor

Air Short Circuits in Chiller Unit Remove short-circuitsAir temperature through airside heat exchanger is

excessively high Another heat source aroundchiller unit Remove heat source

Refrigerant excessivecharge Check cycle temperature. Charge correct

quantity of refrigerant

Non-condensable gas inthe refrigerant cycle

Turn off the unit and check therelation between water

temperature and pressure.

Charge refrigerantagain after the

evacuation

High pressure pipeclogging

Check clogging

Expansion Valve clogging

Check Valve (Air side heatexchanger side) clogging

Check clogging

Remove clogging, orreplace check valve

Strainer CloggingCheck the difference of

temperature before and after ofstrainer.

Replace or clean thestrainer

Discharge pressure isexcessively high, so that

high pressure switchactivates.

(C1-H1)~ (C6-H6)

Chilled water inlettemperature of Water side

heat exchanger isexcessively high

Confirm if it is within the workingrange

Check the status ofheat load in detail andtake a countermeasure

Unit stopsduringcooling

operation

Discharge gas control isactivated

Suction gas temperature isexcessively high

(Excessively super heat)

Gas leakage or refrigerantshortage

Charge correctquantity of refrigerant

after checking gasleakage

Page 27: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

TROUBLESHOOTING 1/23

Check valve(Air heat exchanger side)

MalfunctionReplace check valve

Expansion Valve Clogging Remove Clogging

Suction gastemperature is

excessively high(excessivesuperheat)

Strainer Clogging Replace or clean the strainer

Discharge gascontrol is activated(- alarm)~(- alarm)

Discharge gasThermistor Failure Check thermistor resistance Replace discharge gas

thermistor

Fan motor bearingfailure Lock Status Replace fan motor

Single PhaseRunning Check magnetic contactor Replace magnetic switch

Motor InsulationDeteriorated Measure insulation resistance Replace fan motor

Power Voltage excessively highor low

Set voltage within workingrange during operation

Power Voltage PhaseImbalance

Measure the voltage in eachinterphase and ask PowerCompany for the advice

Compressor DriveExcessive Current

Discharge pressure isexcessively high Analyze the cause

Power Fuse melted Replace power fuse

Loose Power Terminal Screw Retighten the screwSingle PhaseRunning

Contact point of compressorMotor magnetic Contactor

RoughnessReplace contact points

CompressorBearing Failure Lock Status

Compressor Motorinsulation Failure Measure insulation resistance

Replace compressor

Thermal relay forcompressor is

activated(- alarm)~(- alarm)

Compressor internalthermostat is

activated(- alarm)~(- alarm)

Fan internalthermostat is

activated(- alarm)~(- alarm)

Compressor MotorOver-current relay

Failure

Measure current of compressormotor Replace over-current Relay

Pump locked Check freezing of water,clogging of foreign particle Remove them

Pump Over-currentrelay RC value

Wrong

Check the RC value and pumprunning current

Change the RC value orreplace magnetic contactor

Pump over-currentrelay is activated

( alarm)

Pump Over-currentrelay Failure

Push reset button. Check therunning current Replace magnetic contactor

Shortage of waterFlw

Check the difference oftemperature between inlet and

outlet of chilled waterIncrease water flow

Water Strainer Clogging Clean the strainer

Pump reverserotated Check rotative direction Repair to correct direction

Air mixed Open Air Vent Valve Evacuate Air

Unit stopsduringcooling

operation

Freeze protectioncontrol is activated

( alarm)

Thermistor Failure( alarm)( alarm)( alarm)( alarm)

Check inlet temperature ofchilled water Replace Thermistor

Page 28: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

1/24 TROUBLESHOOTING

The heat load is bigger than cooling capacity Calculate heat load Replace to larger unit

Gas leakage or shortage ofrefrigerant Check super-heat. Charge correct quantity after

checking gas leakage

Expansion Valve Clogging Check clogging Remove clogging

Strainer Clogging

Check to make sure that nodifference of temperature

before and after of the strainerexists.

Replace strainer

Low pressure PipingClogging

Check to make sure that nodifference of temperature

between piping exists.Remove clogging

Check Valve Malfunction

Check to make sure that nodifference of temperature

before and after of check valveexists.

Replace check valve

Shortage of water flowCheck the difference of

temperature between inlet andoutlet of chilled water

Increase water flow

Clogging of Water Strainer Replace or clean the strainer

Pump Reverse Rotation Check the rotation direction Repair to the correct direction

Air Mixed Open the air vent valve Evacuate the air

Low pressure is excessivelylow.

(Low-pressure control isactivated)

( )~( alarm)

Deposits on water coolerplates

Check the scales inside ofwater cooler Clean water cooler

Excessive dust in air-side heatexchanger

Inlet or outlet of air-side heatexchanger is clogged

Remove it.

Shortage of Service Space forchiller unit Secure the service space

Air flow shortage in air-sideheat exchanger

Reverse Rotation of Fan Motor Correct the wiring of fan motor

Air Short-circuits in Chiller Unit Repair short-circuit.Air temperature through air-side heat exchanger is high

Another Heat Source aroundthe Chiller Unit Remove heat source

Refrigerant Excessive charge Check cycle temperature Charge the correct quantity

Non-condensable Gas in theRefrigerant Cycle.

Turn off the unit and check therelation between water

temperature and pressure

Evacuate and chargerefrigerant again

High Pressure Pipe Clogging Check clogging

Expansion Valve Clogging Check cloggingRemove clogging

High pressure is excessivelyhigh

(High-pressure switch isactivated)

( )~( alarm)

Strainer CloggingCheck to make sure that nodifference of temperature

before and after strainer existsReplace strainer.

Check valve mal-function

Check to make sure that nodifference of temperature

before and after check valveexists.

Replace check valve.

Unit is running,but the cooling

capacity isinsufficient

Compressor Failure Check pressure, cycletemperature, and current Replace compressor.

Propeller-fan contacts with shroud Investigate Adjust the position of propellerfan

Installation error or loose bolt Check each bolt if loosen Tighten up.

Liquid Compression Check suction gas temperature,pressure Ensure superheat

Oil hammer Check suction gas temperatureand oil level Replace compressor

No-current to oil heater atcompressor stopping Check the current to oil heater. Replace oil heater.

Noise from compressor

Worn or damaged part in thecompressor

Noise from inside ofcompressor Replace compressor.

Beats of magnetic contactor Check the roughness of contact Replace contact points

Unit is running,and it makes anoise.

Vibration of cabinet Check screws if loosen Tighten up

Page 29: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

ELECTRICAL WIRING 2/25

2. ELECTRICAL WIRING

2.1. CUSTOMER WIRINGIn

cas

e of

rem

ote

cont

rol o

pera

tion

this

wire

sha

ll be

rem

oved

.

R P

hase

R P

hase

Neu

tral

Pum

pIn

terlo

ck

Pum

pop

erat

ion

Rem

ote

cont

rol S

witc

h (R

SW

-A )

(Opt

ion)

In c

ase

of In

divi

dual

with

out R

emot

e co

ntro

l Sw

itch

(6 C

ycle

s)C

usto

mer

Wiri

ng

2,3,

4,5,

6 C

ycle

s

4,5,

6 C

ycle

s

6 C

ycle

s

ON

/OFF

ALA

RM

LAM

P

RU

N/S

TOP

SIG

NA

LA

LAR

MS

IGN

AL

DC

24V

LOW

VO

LTA

GE

RE

MO

TE C

ON

TRO

L

MO

DE

No

Use

Low

Vol

tage

Con

trol)

Dip

Sw

itch

Set

ting

(DS

W1

of M

ain

PC

B)

NO

RM

AL

MO

DE

(No

Low

Vol

tage

Con

trol)

MO

DE

1(H

i / L

o)O

NO

FF

MO

DE

2(P

ulse

)

SE

TTIN

G O

F LO

W V

OLT

AG

E C

ON

TRO

L

NO

TE:

1. A

ll th

e se

tting

sha

ll be

per

form

ed b

efor

e P

ower

ON

.2.

Rem

ote/

Loca

l Cha

nge

over

Sw

itch

on O

pera

tion

Sw

itch

shal

l be

set t

o "R

emot

e".

3. T

erm

inal

s 1

∼ 1

7

are

for A

C22

0-24

0V –

Term

inal

s A

∼ D

a

re fo

r DC

24V

.

CU

STO

ME

R W

IRIN

G

3,4,

5,6

Cyc

les

5,6

Cyc

les

Hi

Lo min

.100

ms

min

.100

ms

Flow

Sw

itch

Diff

eren

tial W

ater

Pre

ssur

e S

witc

h O

ptio

n.

Page 30: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

2/26 ELECTRICAL WIRING

PARTS LIST(n=1~N)

Mark Name Remark Mark Name Remark

MC1-n Compressor Motor THMs1-nSuction Gas TemperatureThermistor

MF11-n4 Condenser Fan Motor THMI1-n Liquid Temperature Thermistor OPTIONMI Main Isolator EF1~3, R,S,T Fuse 6ACMC1-n Contactor for Compressor Motor SV11-n1 Solenoid Valve for Starting

CMCs1-snContactor for Compressor Motor(Start Operation) SV12-n2 Solenoid Valve for Load-down

CMCD1-DnContactor for Compressor Motor(Delta Operation) SV13-n3 Solenoid Valve for Load-up

CMF11-n4Contactor for Condenser FanMotor TM1-n Hour Meter

EFC1-n Fuse for Compressor Motor or optionalCircuit Breaker PCBA

Printed Circuit Board forDisplay

ORC1-nOvercurrent Relay for CompressorMotor PCBB

Printed Circuit Board forOperation

EFF11-n4 Fuse for Condenser Fan Motor or optionalCircuit Breaker PCBC1,C2 Printed Circuit Board for CPU

ITC1-nInternal Thermostat forCompressor PCBD1-Dn Printed Circuit Board for Relay

ITF11-n4 Internal Thermostat for Fan Motor PCBE1-EnPrinted Circuit Board for FanControl OPTION

CH1-n Crankcase Heater WP Water Pressure Switch,Water Flow Switch OPTION

AR1-n,H,R Auxiliary Relay PBSR1Push Button Switch for Starting(REMOTE) OPTION

PSH1-n High Pressure SwitchOFF: 2.74MpaON: ManualReset

PBSR2Push Button Switch forStoppage (REMOTE)

Pd1-n High Pressure Sensor RL Pilot Lamp for RemoteIndication (Unit Operation)

Ps1-n Low Pressure Sensor OL1-nPilot Lamp for RemoteIndication (Alarm)

THMiInlet Water TemperatureThermistor CMP Contactor for Pump

THM01,

02,03

Outlet Water TemperatureThermistor TRP Thermal Relay for Pump

FieldSupplied

THMr2 1-n Cooler Inlet Refrigerant Thermistor SVEn Solenoid Valve for Economizer

THMd 1-n Discharge Gas Thermistor PSWnPressure Switch forEconomizer

PFC1-n Fuse holder for Compresor Motor Or optionalCircuit Breaker EHF1-n Cooler Heater

PFF1-nFuse holder for Compresor FanMotor

Or optionalCircuit Breaker TF1,2,3,4,5 Transformers

THMaAtmosphere TemperatureThermistor

Model NRCUE 40, 50, 60, 70AG1 1RCUE 80, 100, 120,140AG1 2RCUE 150, 180, 200AG1 3RCUE 240, 270AG1 4RCUE 300,330AG1 5RCUE 360,400AG1 6

Page 31: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

ELECTRICAL WIRING 2/27

2.2. WIRING DIAGRAM

2.2.1. POWER CIRCUIT

POWER CIRCUIT FOR RCUE 40AG1, RCUE 50AG1, RCUE 60AG1, RCUE 70AG1

Mod

els

RC

UE

40A

G1

RC

UE

50A

G1

RC

UE

60A

G1

RC

UE

70A

G1

Mai

n S

witc

h

PO

WE

R C

IRC

UIT

(OPT

ION

)

(OPT

ION

)

Page 32: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

2/28 ELECTRICAL WIRING

POWER CIRCUIT FOR RCUE 80AG1, RCUE 100AG1, RCUE 120AG1, RCUE 140AG1

Mai

n S

witc

h

PO

WE

R C

IRC

UIT

Mod

els

RC

UE

80

AG

1

RC

UE

100

AG

1R

CU

E 1

20A

G1

RC

UE

140

AG

1

Page 33: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

ELECTRICAL WIRING 2/29

POWER CIRCUIT FOR RCUE 150AG1, RCUE 180AG1, RCUE 200AG1

Mai

n S

witc

h

PO

WE

R C

IRC

UIT

Mod

els

RC

UE

150

AG

1

RC

UE

180

AG

1R

CU

E 2

00A

G1

Page 34: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

2/30 ELECTRICAL WIRING

POWER CIRCUIT FOR RCUE 240AG1, RCUE 270AG1

Mai

n S

witc

h

PO

WE

R C

IRC

UIT

Mod

els

RC

UE

240

AG

1

RC

UE

270

AG

1

Page 35: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

ELECTRICAL WIRING 2/31

POWER CIRCUIT FOR RCUE 300AG1, RCUE 330AG1

Mod

els

RC

UE

300

AG

1

RC

UE

330

AG

1

Mai

n S

witc

h

PO

WE

R C

IRC

UIT

Page 36: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

2/32 ELECTRICAL WIRING

POWER CIRCUIT FOR RCUE 360AG1, RCUE 400AG1

Mod

els

RC

UE

360

AG

1

RC

UE

400

AG

1

Mai

n S

witc

h

PO

WE

R C

IRC

UIT

Page 37: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

ELECTRICAL WIRING 2/33

2.2.2. CONTROL CIRCUIT

CONTROL CIRCUIT FOR RCUE 40AG1, RCUE 50AG1, RCUE 60AG1, RCUE 70AG1

Mod

els

RC

UE

40A

G1

RC

UE

50A

G1

RC

UE

60A

G1

RC

UIE

70A

G1

CO

NTR

OL

CIR

CU

IT

FAN

SP

EED

CTR

L (O

PTI

ON

)

Page 38: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

2/34 ELECTRICAL WIRING

CONTROL CIRCUIT FOR RCUE 80AG1, RCUE 100AG1, RCUE 120AG1, RCUE 140AG1C

ON

TRO

L C

IRC

UIT

Mod

els

RC

UE

80

AG

1

RC

UE

100

AG

1R

CU

E 1

20A

G1

RC

UE

140

AG

1

FAN

SP

EED

CTR

L. (O

PTI

ON

)

Page 39: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

ELECTRICAL WIRING 2/35

CONTROL CIRCUIT FOR RCUE 150AG1, RCUE 180AG1, RCUE 200AG1C

ON

TRO

L C

IRC

UIT

FAN

SP

EED

CTR

L. (O

PTI

ON

)

Mod

els

RC

UE

150

AG

1

RC

UE

180

AG

1R

CU

E 2

00A

G1

Page 40: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

2/36 ELECTRICAL WIRING

CONTROL CIRCUIT FOR RCUE 240AG1, RCUE 270AG1C

ON

TRO

L C

IRC

UIT

Mod

els

RC

UE

240

AG

1

RC

UE

270

AG

1

FAN

SP

EED

CTR

L. (O

PTI

ON

)

Page 41: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

ELECTRICAL WIRING 2/37

CONTROL CIRCUIT FOR RCUE 300AG1, RCUE 330AG1

FAN

SP

EED

CTR

L. (O

PTI

ON

)

Mod

els

RC

UE

300

AG

1

RC

UE

330

AG

1

CO

NTR

OL

CIR

CU

IT

FAN

SP

EED

CTR

L. (O

PTI

ON

)

Page 42: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

2/38 ELECTRICAL WIRING

CONTROL CIRCUIT FOR RCUE 360AG1, RCUE 400AG1

FAN

SP

EED

CTR

L. (O

PTI

ON

)

CO

NTR

OL

CIR

CU

IT

Mod

els

RC

UE

360

AG

1

RC

UE

400

AG

1

FAN

SP

EED

CTR

L. (O

PTI

ON

)

Page 43: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

ELECTRICAL WIRING 2/39

2.3. MAIN CIRCUIT BOARD

MAIN PRINTED CIRCUIT BOARD (MASTER)R

emot

e co

ntro

l Sw

itch

(RS

W-A

) (op

tion)

MA

IN P

RIN

TED

CIR

CU

IT B

OA

RD

(MA

STE

R)

Diff

eren

tial W

ater

Pre

ssur

e S

witc

h (O

ptio

n)

FAN

SP

EE

DC

TRL.

(OP

TIO

N)

BM

SC

ON

NE

CTI

ON

PO

WE

R

OPE

RAT

ION

OPE

RAT

ION

ALA

RM

(CH

EC

K)

Page 44: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

2/40 ELECTRICAL WIRING

RELAIS PRINTED CIRCUIT BOARD (SUBSIDIARY)

Mod

elR

CU

E 3

00A

G1

RC

UE

330

AG

1R

CU

E 3

60A

G1

RC

UE

400

AG

1

RE

LAY

S P

RIN

TED

CIR

CU

IT B

OA

RD

(SU

BS

IDIA

RY

)

PC

BC -

MA

STE

R(o

nly

RC

UE

300A

G1∼

400A

G1)

Fan

Spe

edC

trl. (

optio

n)(

Page 45: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

ELECTRICAL WIRING 2/41

RELAYS PRINTED CIRCUIT BOARD

Mod

elR

CU

E 4

0,50

,60,

70A

G1

RC

UE

80,

100,

120,

140A

G1

RC

UE

150

,180

,200

AG

1R

CU

E 2

40,2

70A

G1

(OP

TIO

N)

(ON

LY)

RE

LAY

S P

RIN

TED

CIR

CU

IT B

OA

RD

Exc

ept R

CU

E 4

0,80

AG

1

DU

MM

YTH

ERM

I

DM

-1

Page 46: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

2/42 ELECTRICAL WIRING

RELAYS PRINTED CIRCUIT BOARD

(ON

LY)

Mod

elR

CU

E 3

00,3

30A

G1

RC

UE

360

,400

AG

1

RE

LAY

S P

RIN

TED

CIR

CU

IT B

OA

RD

(OP

TIO

N)

No

cabl

es (n

=3,5

for R

CU

E30

0,33

0AG

1N

o ca

bles

(n=

4,6

for R

CU

E36

0.40

0AG

1

No

cabl

es (n

=3,5

for R

CU

E30

0,33

0AG

1N

o ca

bles

(n=

4,6

for R

CU

E36

0.40

0AG

1

Page 47: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual
Page 48: AIR COOLED WATER CHILLERS - HD Kldocumentatie.hdkl.nl/Koudwatermachines/SERVICEMANUAL RCU()E R… · AIR COOLED WATER CHILLERS-SCREW TYPE-Maintenance Instructions. Service Manual

SMGB0002-rev.0 - 07/05 - Printed in Spain

Hitachi Air Conditioning Products (M) Sdn. Bnd.Lot No. 10, Jalan Kemajan Bangi Industrial Estate43650 Bandar Baru BangiSelangor Darul Ehsan, MalaysiaCertification ISO 9001, Malaysia

HitachiAir Conditioning Products Europe, S.A.Ronda Shimizu, 1 - Políg. Ind. Can Torrella08233 Vacarisses (Barcelona) EspañaISO 9002 certified byAENOR, Spain

HITACHI is participating in the EUROVENT Certification Programme.Products are as specified in the EUROVENT Directory of CertifiedProducts.

Products are manufactured according to the ISO certification system.Air Conditioning Systems Operation, Shimizu shi,Shizuoka

--ken, Japan: ISO9001 certified by JQA, Japan