EQSL AIR COOLED WATER CHILLER UNITS AXIAL FANS Air Cooled Water Chillers TECHNICAL CATALOGUE Models: 300 V2 F06 │……… │ 1310 V2 F16 Cooling capacity: 299 to 1310 KW 02.16 ref. 207598 Rev.100

Transcript of Air Cooled Water Chillers - Hitecsa.com · Air Cooled Water Chillers E ... usability and practical...

EQSL

AIR COOLED WATER CHILLER UNITS – AXIAL FANS

INVERTER

Air Cooled Water Chillers

TE

CH

NIC

AL

CA

TA

LO

GU

E

Models: 300 V2 F06 │……… │ 1310 V2 F16

Cooling capacity: 299 to 1310 KW

02.16 ref. 207598 Rev.100

AIR COOLED WATER CHILLER UNITS – AXIAL FANS

EQSL

02.16 Ref. 207598 Rev.100

2

Thank you for trusting in Hitecsa Products. Our company has been offering the market an extended range of specialized units for

air conditioning and cooling installations for over 30 years. Our approach is based on efficiency, adaptability, usability and practical

solutions. This has been the hallmark of our product catalogue.

The versatility of our factory allows us to contribute solutions, almost tailored to each project’s specifications, in search of a

solution to every problem that arises in design and implementation of air conditioning installations.

From all of us at Hiplus Aire Acondicionado, once again, thank you very much

GENERAL CHARACTERISTICS ..................................................................................................................................... 4

EQSL SERIES.............................................................................................................................................................. 4

EQSL MODELS .......................................................................................................................................................... 4

OPERATING LIMITS ................................................................................................................................................... 5

TECHNICAL SPECIFICATIONS ..................................................................................................................................... 9

MP.COM – MICROPROCESSOR CONTROL SYSTEM ................................................................................................. 13

OPTIONALS ............................................................................................................................................................ 15

PUMP KITS ............................................................................................................................................................. 15

HYDRONIC PUMPS PERFORMACE CHARTS ............................................................................................................. 18

OTHER OPTIONALS ................................................................................................................................................. 19

KIT "BRINE"................................................................................................................................................................ 19

KIT LNO ...................................................................................................................................................................... 19

KIT XLS ....................................................................................................................................................................... 19

HIGH PRESSURE “EC” AXIAL FANS ............................................................................................................................. 20

TECHNICAL SPECIFICATIONS ..................................................................................................................................... 21

PARTIAL HEAT RECOVERY SYSTEM ........................................................................................................................... 25

PARTIAL HEAT RECOVERY HYDRAULIC CIRCUIT DIAGRAM ...................................................................................... 25

TOTAL HEAT RECOVERY SYSTEM ............................................................................................................................... 26

TOTAL HEAT RECOVERY HYDRAULIC CIRCUIT DIAGRAM .......................................................................................... 26

DIMENSIONS .......................................................................................................................................................... 27

MODELS 300 – 320 – 360 ........................................................................................................................................... 27

MODELS 390 – 430 – 480 – 530 – 540 – 560 ............................................................................................................... 28

MODELS 610 – 650 ..................................................................................................................................................... 29

MODELS 710 – 770 – 850 ........................................................................................................................................... 30

MODEL 910 ................................................................................................................................................................ 31

MODEL 950 ................................................................................................................................................................ 32

MODELS 1060 – 1120 – 1180 – 1310 .......................................................................................................................... 33

EQSL

AIR COOLED WATER CHILLER UNITS – AXIAL FANS

EQSL

02.16 Ref. 207598 Rev.100

4

GENERAL CHARACTERISTICS Packaged air cooled liquid chillers for chilled water production. The machines are made with weather resistant

materials and suitable for outdoor installation. Framework with sections of thick steel for high resistance to the greatest

stress during handling and transport. Machines supply fully assembled with refrigerant charge and control systems.

The installation requires electrical and hydraulic connections only allowing high costs and time reduction. Final

assembly on all machines before shipment including running test, reading and monitoring of operating parameters,

alarms simulation and visual check. Design, assembly and test as per the Company Quality Assurance program in full

compliance with ISO 9001:2008. Environmental Management System Certification according to ISO 14001:2004. The

machines are in full compliance with European Directive 2006/42EC, 2006/95EC, 2004/108EC, 97/23EC and

subsequent amendments.

EQSL SERIES Machines equipped with condensing coils in "W" position, screw compressors, axial fans and shell and tube evaporator. Horizontal air suction and vertical air delivery. Cooling capacity : 299 - 1310 KW.

EQSL MODELS EQSL 520 V2 F10 Cabinet size

2 Number of compressors

520 Cooling capacity in KW under standard conditions

AIR COOLED WATER CHILLER UNITS – AXIAL FANS

EQSL

02.16 Ref. 207598 Rev.100

5

OPERATING LIMITS

Cooling – Production of chilled water

Operating limits diagram for chilled water production according to the ambient temperature and chilled water outlet

temperature.

OPERATING CONDITIONS “A” Operating conditions for which the unit’s cooling capacity can be measured with the electronic selection program.

OPERATING CONDITIONS “B” Operating conditions for which the unit’s cooling capacity has to be measured by our commercial and sales department. These values are indicative. Operating temperatures are influenced by a series of variables, such as: Working conditions. Thermal load. Active power stages. Cleanliness of the heat exchanging coils. Microprocessor regulation.

TOTAL HEAT RECOVERY The system is totally controlled by the microprocessor and the heating capacity which is supplied depends on the microprocessor set. 30÷60 °C hot water outlet temperature range 3÷8 °C Δt range between water inlet/outlet

PARTIAL HEAT RECOVERY The system is not regulated and the heating capacity which is supplied depends on the machine’s working conditions. 40-75 °C Range of hot water outlet temperature. 5-15 °C Δt range between water intake/outlet.

ANTIFREEZE MIXTURES Antifreeze mixtures must be used when the conditions are expected to produce outlet chilled water below 5 °C.

PROPYLENE GLYCOL

ETHYLENE GLYCOL

STORAGE TEMPERATURE If the unit is not installed immediately after reception and is to be stored for an extended period of time, please, make sure that storage temperatures range between -30 and 50ºC and the unit is not subject to condensation or direct sunlight.

Chilled water outlet Temp.

ºC 4 2 1 -2 -4 -6 -9

Percentage of mixture (in weight)

% 5 10 15 20 25 30 35

Chilled water outlet Temp.

ºC 4 2 0 -4 -7 -9 -10

Percentage of mixture (in weight)

% 5 10 15 20 25 30 35

Attention:

These values refer to the machine’s operating temperature. The use of antifreeze mixtures may result in a decrease in the unit’s performance.

Please, use the selection program to obtain the effective performance.

AIR COOLED WATER CHILLER UNITS – AXIAL FANS

EQSL

02.16 Ref. 207598 Rev.100

6

FRAMEWORK Base, self supporting frame and panelling in steel plate with protective surfaces treatment in compliance with UNI ISO 9227/ASTMB117 and ISO 7253, and painted with epoxy powders.

COMPRESSORS - Twin screw semi-hermetic compressors with highly

efficient screw profile and high peripheral speed, optimized for R134a refrigerant.

- Integrated discharge check valve. - Flanged-on oil separator. - Integrated safety relief valve (overpressure inner valve). - Replaceable cartridge oil filter. - Oil flow switch. - Valves for oil filling and discharge. - Oil sight glass. Electronic protection device that includes : - Electric motor thermal protection via internal winding

temperature sensors. - Phase sequence electronic relay. - Sensor on refrigerant discharge for temperature

monitoring. - 2-pole 3-phase electric motor with Part-Winding starting

from model 300 V2 F06 to model 530 V2 F08 included. - 2-pole 3-phase electric motor with Star / Delta starting

from model 540 V2 F08 to model 1310 V2 F16 included. - Stepless capacity control, 50÷100% for each compressor. - Crankcase heater. - Terminal box with IP54 class enclosure. - Rubber supports.

EVAPORATOR - Single pass type shell and tube evaporator, optimized for

R134a refrigerant. - Tubes with a helical rifled internal surface. - Intermediate baffles positioned to ensure optimum speed

of the fluid and low pressure drops. - Single circuit on water side and independent circuits, one

for each compressor, on refrigerant side. - Shell, header, tube sheets, made of carbon steel, tubes in

Cu. - Anticondensate insulation made of polyurethane. - Temperature sensors on water inlet and outlet. - Antifreeze heater. - Hydraulic connections with grooved end arranged for

flexible joint (the flexible joint and the adapter pipe are optional accessories).

CONDENSING COIL Heat exchanger coil with high efficiency aluminum fins, specifically developed to provide high heat transfer and lower pressure drops. The combination of two factors, special tubes and fins, allows to optimally combine the following aspects: - Maximum capacity relative to the size of the exchanger. - Minimum charge of refrigerant. - Reduction of the air flow required for the heat exchange. Frame in galvanized steel.

FAN SECTIONS - Axial fans with sickle-shaped blades, fan guard and

optimized for low noise levels. - External rotor AC type electric motor with stepless

variable speed for condensing pressure control with phase-cut electronic controller.

- IP54 class enclosure.

COOLING CIRCUIT - Electronic expansion valve that allows high performance

and system efficiency thanks to a timely and accurate response to changes in temperature and pressure.

- Energy reserve module for the electronic expansion valve to allow the closure of the valve in the event of lack of power supply.

- Sight glass. - Filter dryer on liquid line. - Service valves on liquid line. - Service valves on compressor gas discharge. - Double safety valve (only one in function) on high and low

pressure side. - The system include two safety valves with manual

changeover system. - Pressure transducers with indication, control and

protection functions, on low and high refrigerant pressure and oil pressure.

- High pressure safety switch with manual reset. - Pressure gauge on high and low pressure. - Refrigerant circuit with copper tubing with anticondensate

insulation of the suction line. - Plastic capillary hoses for pressure sensors connection.

R134a refrigerant charge.

ELECTRICAL PANEL In accordance with EN60204-1 norms, suitable for outdoor installation, IP54 class enclosure, complete with: - Main switch with door lock safety. - Fuses for each compressor. - Magnetothermic switches for fans. - Fuses for water pumps (if scheduled). - Contactors for each load. - Compressor Part-Winding starting system from model

290 V2 F06 to model 570 V2 F10 included. - Compressor Star / Delta starting system from model 620

V2 F10 to model 1510 V2 F24 included. - Transformer for auxiliary circuit and microprocessor

supply. - Panel with machine controls. - Power supply 400/3/50.

CONTROL SYSTEM MP.COM microprocessor system with graphic symbol for

control and monitor of operating and alarms status. The

system includes:

- Voltage free contact slot for remote general alarm. - Service hour meter for main components. - Non-volatile flash memory for data storage. - Menu with password security. - LAN connection.

HYDRAULIC CONNECTIONS - Heat exchangers threaded hydraulic connections ISO

228/1 – G M, available up to a diameter of 3" included. - Pipes threaded hydraulic connections ISO 7/1 – R,

available up to a diameter of 3" included. - The hydraulic connections with flange (FL) are not

supplied with counter flange. - The hydraulic connections with grooved end are not

supplied with flexible joint (optional accessory).

AIR COOLED WATER CHILLER UNITS – AXIAL FANS

EQSL

02.16 Ref. 207598 Rev.100

7

ACCESSORIES - Pump KIT. Includes chilled water flow safety switch. - Kit LNO for reduction of noise emissions. - Kit XLS for extreme reduction of noise emissions. - High pressure axial fans equipped with EC motors. - Partial heat recovery system. (not available for units with double cooling circuits) - Voltage free contact slot for partial heat recovery with pump activation. - Partial Heat Recovery System. - Total Heat Recovery System. - Kit "BRINE A" for chilled water production up to -6ºC. (this accessory is not compatible with the Total Heat

Recovery System). - Kit "BRINE B" for chilled water production below -6ºC. (this accessory is not compatible with the Total Heat

Recovery System). Warning: with the BRINE KIT, it is mandatory to use an antifreeze mixture. Please, refer to the “Antifreeze

Mixture” chapter in this manual.

The use of antifreeze mixtures may result in a decrease in the unit’s performance.

(PLEASE, CONTACT OUR COMMERCIAL DEPARTMENT)

OTHER ACCESSORIES - Chilled water safety flow switch. - Analog flowmeter (0÷1V / 4-20mA) for measurement and display of the evaporator water flow. The optional

accessory stops the machine in case of water flow anomalies. The installation of the analog flowmeter excludes the installation of the water flow switch. The optional accessory involves the installation of the microprocessor expansion module "1" and its driver.

- Hydraulic connections of the evaporator and total heat reclaim heat exchangers with flexible joint with adapter pipe (solder type). Flexible joint with adapter for flange connection (FL). The counterflange is not supplied.

- Anti-freeze kit for hydraulic pipes of the pumping group. - Compressor thermal protection relay. - Power factor capacitor for motor compressor - cosφ 0.9. - Supply network control relay. Measurement and control of the minimum line voltage, over line voltage, phase loss,

phase unbalance and phases sequence of the unit. The system stops the machine in case of operative conditions malfunction.

- Compressor operation signalling through additional voltage free contact. - Demand limit. The optional accessory limits the electrical absorption of the unit according to a set point value with a

reduction of the machine engaged load (activation of the compressor capacity control or, in extreme cases, stop of a compressor). The optional accessory involves the installation of the microprocessor expansion module "2" and its driver.

- Analog set point compensation (0-1V). Available only for machines with single refrigerant circuit. The optional accessory involves the installation of the microprocessor expansion module "1" and its driver. Available compensation systems:

- Compensation according to ambient temperature (the system foresees the installation of the ambient temperature sensor).

- Compensation according to an external analog signal. - Stop valve on compressor suction. - Air/gas heat exchanger protection net. - Air/gas heat exchanger in special execution (please contact our Commercial Dept.). - Spring antivibrating supports for the machine- supplied not installed. - Rubber supports for the machine – supplied not installed. - Electrical panel heating system (suggested in case of operation of the machine with negative ambient temperature). - Ambient temperature sensor. The ambient temperature sensor requires the installation of the microprocessor

expansion module "1" and its driver.

AIR COOLED WATER CHILLER UNITS – AXIAL FANS

EQSL

02.16 Ref. 207598 Rev.100

8

OTHER ACCESSORIES MP.COM microprocessor accessories : - Remote terminal. - Line voltage indication. - Line current indication. - Clock card for alarms date and time displaying and storing. - Serial port RCcom, MBUS/JBUS. - Serial port LON. - Serial port BACnet for Ethernet – SNMP – TCP/IP. - Serial port BACnet for MS/TP. - Serial port for GSM modem. - Data logger for the memorization of the intervened alarms.

Additional module "1" with the following inputs / outputs: INPUTS : - Analog flowmeter / Line voltage indication / Line current indication. - Compensation / Line voltage indication / Line current indication. - Ambient air temperature. - The additional module "1" is already included with Water Pumps and Total heat reclaim optional accessories.

Additional module "2" with the following inputs / outputs: INPUTS : - Demand limit. The accessory requires an additional digital input for enabling. - External alarm 1. - External alarm 2. OUTPUTS : - Programmable alarm 1. - Programmable alarm 2. - Programmable alarm 3. - General alarm 2. - Driver for the additional module. Warning : We reserve the right to accept possible combinations of optional accessories installed on the unit.

AIR COOLED WATER CHILLER UNITS – AXIAL FANS

EQSL

02.16 Ref. 207598 Rev.100

9

MODEL 300 V2 F06 320 V2 F06 360 V2 F08 390 V2 F08 430 V2 F08

CAPACITIES

Cooling capacities (1) KW 299 315 335 391 430

EER KW / KW 2,78 2,77 2,62 2,78 2,77

ESSER 3,06 3,03 3,20 3,18 3,10

REFRIGERANT

Type R-134a

Load Kg 110 146 146 145 145

Gas circuits 2 2 2 2 2

PCA 1430 1430 1430 1430 1430

COMPRESSOR

Type Twin Screw

Number 2 2 2 2 2

Absorbed power KW 96 102 116 125 140

Operating current A 162 163 200 208 237

Starting current A 404 383 469 630 639

Maximum absorbed current A 202 205 236 270 288

Power steps 25 .. 100% 25 .. 100% 25 .. 100% 25 .. 100% 25 .. 100%

EVAPORATOR FAN

Type AXIAL

Nominal air flow m3/h 135498 135498 135498 180664 180664

Number 6 6 6 8 8

Absorbed power (1) KW 11,6 11,7 11,7 15,4 15,4

Maximum absorbed current A 23,4 23,4 23,4 31,2 31,2

EVAPORATOR EXCHANGER

Water load lt 113 113 113 160 160

Water flow m3/h 51,3 54,1 57,5 67,1 73,9

Maximum water flow m3/h 63 63 63 90 90

Pressure drop KPa 47 52 48 59 54

Pollution factor m²*K/KW 0,043 0,043 0,043 0,043 0,043

ELECTRICAL CHARACTERISTICS

Voltage V/ph/Hz 400 / III / 50

NOISE LEVELS

Acoustic pressure 1m (4) dB(A) 73,1 71,7 72,0 71,6 76,0

Acoustic power (5) dB(A) 92,9 91,4 91,8 91,9 96,2

DIMENSIONS AND WEIGHT

Length mm 3520 3520 3520 4490 4490

Width mm 2260 2260 2260 2260 2260

Height mm 2550 2550 2550 2550 2550

Net weight Kg 3992 4258 4411 4544 4753

TECHNICAL SPECIFICATIONS

1. Intake/Outlet chilled water temperature 12/7 °C; Ambient air temperature 35 °C – Eurovent standards. 2. Intake/Outlet chilled water temperature 12/7 °C; Intake/Outlet hot water temperature 40/45°C – Eurovent standards. 3. Gross values - Intake/Outlet chilled water temperature 12/7 °C; Ambient air temperature 35 °C and Intake/Outlet hot water temperature 40/45°C. 4. Avergae sound pressure levels [Lpm] measured 1m away, in accordance to ISO EN 3744. 5. Acoustic power levels [Lw] in accordance to ISO EN 9614 – 2.

AIR COOLED WATER CHILLER UNITS – AXIAL FANS

EQSL

02.16 Ref. 207598 Rev.100

10

MODEL 480 V2 F08 530 V2 F08 540 V2 F08 560 V2 F08 610 V2 F08

CAPACITIES

Cooling capacities (1) KW 476 523 543 563 611

EER KW / KW 2,76 2,76 2,78 2,79 2,78

ESSER 3,13 3,17 3,23 3,21 3,17

REFRIGERANT

Type R-134a

Load Kg 145 145 170 194 194

Gas circuits 2 2 2 2 2

PCA 1430 1430 1430 1430 1430

COMPRESSOR

Type Twin Screw

Number 2 2 2 2 2

Absorbed power KW 157 174 180 186 204

Operating current A 261 286 297 309 332

Starting current A 790 811 526 545 545

Maximum absorbed current A 309 330 347 367 390

Power steps 25 .. 100% 25 .. 100% 25 .. 100% 25 .. 100% 25 .. 100%

EVAPORATOR FAN

Type AXIAL

Nominal air flow m3/h 180664 180664 177924 175184 175184

Number 8 8 8 8 8

Absorbed power (1) KW 15,4 15,4 15,5 15,6 15,6

Maximum absorbed current A 31,2 31,2 31,2 31,2 31,2

EVAPORATOR EXCHANGER

Water load lt 150 150 143 143 256

Water flow m3/h 81,8 89,8 93,3 96,7 105,0

Maximum water flow m3/h 95 95 100 100 127

Pressure drop KPa 38 38 41 45 51

Pollution factor m²*K/KW 0,043 0,043 0,043 0,043 0,043

ELECTRICAL CHARACTERISTICS

Voltage V/ph/Hz 400 / III / 50

NOISE LEVELS

Acoustic pressure 1m (4) dB(A) 76,2 76,4 76,4 76,4 78,0

Acoustic power (5) dB(A) 96,4 96,7 96,7 96,7 98,2

DIMENSIONS AND WEIGHT

Length mm 4490 4490 4490 4490 4490

Width mm 2260 2260 2260 2260 2260

Height mm 2550 2550 2550 2550 2550

Net weight Kg 4890 5012 5117 5221 5321

1. Intake/Outlet chilled water temperature 12/7 °C; Ambient air temperature 35 °C – Eurovent standards. 2. Intake/Outlet chilled water temperature 12/7 °C; Intake/Outlet hot water temperature 40/45°C – Eurovent standards. 3. Gross values - Intake/Outlet chilled water temperature 12/7 °C; Ambient air temperature 35 °C and Intake/Outlet hot water temperature 40/45°C. 4. Avergae sound pressure levels [Lpm] measured 1m away, in accordance to ISO EN 3744. 5. Acoustic power levels [Lw] in accordance to ISO EN 9614 – 2.

AIR COOLED WATER CHILLER UNITS – AXIAL FANS

EQSL

02.16 Ref. 207598 Rev.100

11

MODEL 650 V2 F08 710 V2 F10 770 V2 F10 850 V2 F10 910 V2 F12

CAPACITIES

Cooling capacities (1) KW 645 707 768 853 905

EER KW / KW 2,77 2,78 2,77 2,76 2,77

ESSER 3,24 3,18 3,18 3,19 3,26

REFRIGERANT

Type R-134a

Load Kg 194 241 241 302 289

Gas circuits 2 2 2 2 2

PCA 1430 1430 1430 1430 1430

COMPRESSOR

Type Twin Screw

Number 2 2 2 2 2

Absorbed power KW 217 237 258 289 303

Operating current A 354 377 400 456 479

Starting current A 568 581 611 721 827

Maximum absorbed current A 414 444 474 534 567

Power steps 25 .. 100% 25 .. 100% 25 .. 100% 25 .. 100% 25 .. 100%

EVAPORATOR FAN

Type AXIAL

Nominal air flow m3/h 175184 197082 218980 212690 262776

Number 8 9 10 10 12

Absorbed power (1) KW 15,6 17,6 19,5 20,1 23,4

Maximum absorbed current A 31,2 35,1 39,0 39,0 46,8

EVAPORATOR EXCHANGER

Water load lt 256 256 247 238 223

Water flow m3/h 111 121 132 147 156

Maximum water flow m3/h 127 127 143 154 172

Pressure drop KPa 56 63 73 55 63

Pollution factor m²*K/KW 0,043 0,043 0,043 0,043 0,043

ELECTRICAL CHARACTERISTICS

Voltage V/ph/Hz 400 / III / 50

NOISE LEVELS

Acoustic pressure 1m (4) dB(A) 79,2 79,4 80,0 79,7 78,8

Acoustic power (5) dB(A) 99,4 100,1 100,7 100,4 99,8

DIMENSIONS AND WEIGHT

Length mm 4490 5460 5460 5460 6430

Width mm 2260 2260 2260 2260 2260

Height mm 2550 2550 2550 2550 2550

Net weight Kg 5241 6232 6517 7032 7354

1. Intake/Outlet chilled water temperature 12/7 °C; Ambient air temperature 35 °C – Eurovent standards. 2. Intake/Outlet chilled water temperature 12/7 °C; Intake/Outlet hot water temperature 40/45°C – Eurovent standards. 3. Gross values - Intake/Outlet chilled water temperature 12/7 °C; Ambient air temperature 35 °C and Intake/Outlet hot water temperature 40/45°C. 4. Average sound pressure levels [Lpm] measured 1m away, in accordance to ISO EN 3744. 5. Acoustic power levels [Lw] in accordance to ISO EN 9614 – 2.

AIR COOLED WATER CHILLER UNITS – AXIAL FANS

EQSL

02.16 Ref. 207598 Rev.100

12

MODEL 950 V2 F12 1060 V2 F16 1120 V2 F16 1180 V2 F16 1310 V2 F16

CAPACITIES

Cooling capacities (1) KW 949 1063 1121 1181 1310

EER KW / KW 2,76 2,75 2,76 2,77 2,76

ESSER 3,32 3,29 3,34 3,32 3,30

REFRIGERANT

Type R-134a

Load Kg 289 290 290 290 389

Gas circuits 2 2 2 2 2

PCA 1430 1430 1430 1430 1430

COMPRESSOR

Type Twin Screw

Number 2 2 2 2 2

Absorbed power KW 320 355 375 396 443

Operating current A 515 597 634 680 742

Starting current A 903 1058 1138 1182 1324

Maximum absorbed current A 615 710 754 798 896

Power steps 25 .. 100% 25 .. 100% 25 .. 100% 25 .. 100% 25 .. 100%

EVAPORATOR FAN

Type AXIAL

Nominal air flow m3/h 262776 361328 361328 361328 350368

Number 12 16 16 16 16

Absorbed power (1) KW 23,4 30,9 30,9 30,9 31,2

Maximum absorbed current A 46,8 62,4 62,4 62,4 62,4

EVAPORATOR EXCHANGER

Water load lt 223 382 382 370 359

Water flow m3/h 163 183 193 203 225

Maximum water flow m3/h 172 208 208 220 241

Pressure drop KPa 71 41 45 49 59

Pollution factor m²*K/KW 0,043 0,043 0,043 0,043 0,043

ELECTRICAL CHARACTERISTICS

Voltage V/ph/Hz 400 / III / 50

NOISE LEVELS

Acoustic pressure 1m (4) dB(A) 78,8 81,1 81,1 81,1 81,4

Acoustic power (5) dB(A) 99,8 102,9 102,9 102,9 103,2

DIMENSIONS AND WEIGHT

Length mm 6430 8720 8720 8720 8720

Width mm 2260 2260 2260 2260 2260

Height mm 2550 2550 2550 2550 2550

Net weight Kg 7414 9491 9975 9995 10075

1. Intake/Outlet chilled water temperature 12/7 °C; Ambient air temperature 35 °C – Eurovent standards. 2. Intake/Outlet chilled water temperature 12/7 °C; Intake/Outlet hot water temperature 40/45°C – Eurovent standards. 3. Gross values - Intake/Outlet chilled water temperature 12/7 °C; Ambient air temperature 35 °C and Intake/Outlet hot water temperature 40/45°C. 4. Avergae sound pressure levels [Lpm] measured 1m away, in accordance to ISO EN 3744. 5. Acoustic power levels [Lw] in accordance to ISO EN 9614 – 2.

AIR COOLED WATER CHILLER UNITS – AXIAL FANS

EQSL

02.16 Ref. 207598 Rev.100

13

MP.COM – MICROPROCESSOR CONTROL SYSTEM The MP.COM microprocessor control system is equipped with an 8-key terminal and backlit graphic display on which all information in different languages or easily identifiable symbols are displayed. The system counts with a "flash" memory that preserves the information even in absence of an external power supply.

FUNCTIONS

AIR COOLED WATER CHILLER UNITS – AXIAL FANS

EQSL

02.16 Ref. 207598 Rev.100

14

REMOTE CONTROLS/ALARMS

• Remote Controls/Alarms. •• Voltage free Control/Alarm.

AIR COOLED WATER CHILLER UNITS – AXIAL FANS

CLASS “A” ENERGY EFFICIENCY

EQSLA

01.16 Ref. 207585 Rev.100

15

OPTIONALS

PUMP KITS

Pump KIT. It is possible to install only one of the following options:

Standard version Pump KIT. - One pump. - Two pumps operating simultaneously.

STANDARD VERSION SINGLE PUMP KIT HYDRAULIC DIAGRAM

STANDARD VERSION TWIN PUMP KIT HYDRAULIC DIAGRAM

The pumping group includes:

- Control and working electric equipment contained in the chiller electric board and directly managed by the microprocessor control. - Valve on suction line. - Valve on discharge line. - In-line type water pump. - Safety flow switch (excludes the installation of the water flow switch on the evaporator).

AIR COOLED WATER CHILLER UNITS – AXIAL FANS

EQSL

02.16 Ref. 207598 Rev.100

16

Reserve pump version Pump KIT.

- One operating pump and one reserve pump. - Two operating pumps and one reserve pump. All pump kits are factory installed. This optional does not affect the dimensions of the unit.

RESERVE PUMP VERSION SINGLE OPERATING PUMP HYDRAULIC DIAGRAM

RESERVE PUMP VERSION TWIN OPERATING PUMPS HYDRAULIC DIAGRAM

Pumping group with two centrifugal pumps: - Control and working electric equipment contained in the chiller electric board and directly managed by the microprocessor

control. - Valves on suction line. - Check valves on discharge line. - In-line type water pump. - GP-LN... Centrifugal pump with 4 poles electric motor. - Safety flow switch (excludes the installation of the water flow switch on the evaporator). The reserve pump automatically intervenes in case of failure of one of the main pumps. An automatic changeover system is foreseen in order to equalize the water pump working hours.

AIR COOLED WATER CHILLER UNITS – AXIAL FANS

EQSL

02.16 Ref. 207598 Rev.100

17

TECHNICAL SPECIFICATIONS

STANDARD VERSION PUMP KIT

RESERVE PUMP VERSION PUMP KIT

STANDARD VERSION SINGLE PUMP TWIN MED. PUMPS

WATER FLOW RATE

Minimum water flow rate m3/h 10 20

Maximum water flow rate m3/h 120 240

DISCHARGE HEAD

At minimum water flow rate KPa 160 160

At maximum water flow rate KPa 130 130

WATER PUMPS (1)

Absorbed power KW 5,5 11,0

Absorbed current A 11,4 22,8

POWER SUPPLY

Voltage V/ph/Hz 400 / III / 50

EMPTY WEIGHT

Single pump version (2) Kg 212 318

RESERVE PUMP VERSION

SINGLE PUMP TWIN MED. PUMPS

OPERATING

PUMP RESERVE

PUMP OPERATING

PUMP RESERVE

PUMP

WATER FLOW RATE

Minimum water flow rate m3/h 10 10 20 10

Maximum water flow rate m3/h 120 120 240 120

DISCHARGE HEAD

At minimum water flow rate KPa 160 160 160 160

At maximum water flow rate KPa 130 130 130 130

WATER PUMPS (1)

Absorbed power KW 5,5 5,5 11,0 5,5

Absorbed current A 11,4 11,4 22,8 11,4

POWER SUPPLY

Voltage V/ph/Hz 400 / III / 50

EMPTY WEIGHT

Operating pump (2) Kg 318 477

Reserve pump (2) Kg 318 477

(1) The values shown refer only to the working pump. (2) Add this value to the chiller’s weight.

Note: The noise generated by the pumps does not increase the chillers overall acoustic pressure levels.

AIR COOLED WATER CHILLER UNITS – AXIAL FANS

EQSL

02.16 Ref. 207598 Rev.100

18

HYDRONIC PUMPS PERFORMACE CHARTS

STANDARD VERSION PUMP KIT

TWIN PUMP VERSION PUMP KIT

SINGLE OPERATING PUMP RESERVE PUMP

TWIN MED. OPERATING PUMPS RESERVE PUMP

AIR COOLED WATER CHILLER UNITS – AXIAL FANS

EQSL

02.16 Ref. 207598 Rev.100

19

OTHER OPTIONALS

KIT "BRINE" The accessory allows the production of glycol solution leaving the machine down to a temperature of -12 °C.

This KIT includes:

- Set of the working parameters.

Warning: with the "BRINE" KIT optional, it is mandatory to use antifreeze mixtures. The use of antifreeze mixtures may result in a decrease in the unit’s performance.

KIT LNO This optional is available as an accessory with the purpose of obtaining a reduction in noise emissions.

This KIT includes:

- Set of the working parameters. - A cap made with noise-absorbing material on each compressor.

There are 3 different types of LNO KITS:

KIT LNO 100%

No air flow reduction. Noise reduction is obtained through a different working set of the microprocessor control and an acoustic

insulation of the noise source.

KIT LNO 85%

Noise reduction is obtained through a different working set of the microprocessor control, an acoustic insulation of the noise source

and a reduction of the condenser coil air flow at 85% of the nominal value.

KIT LNO 70%

Noise reduction is obtained through a different working set of the microprocessor control, an acoustic insulation of the noise source

and a reduction of the condenser coil air flow at 70% of the nominal value. Consider that a condenser coil air flow reduction induces a

minor cooling capacity of the machine and a major energy consumption of the compressor.

Warning: To obtain the effective working conditions of cooling capacity and noise reduction for unit equipped with LNO KIT, please

refer to the selection program.

KIT XLS This optional accessory is available to obtain an extreme noise reduction on the machine.

The versions equipped with XLS KIT have the following characteristics : - Set of the working parameters. - Machine frame and panels insulated with soundproofing material. - Soundproof cap on each compressor. - Compressor soundproof box.

Consider that a condenser coil air flow reduction induces a minor cooling capacity of the machine and a major energy consumption of the compressor. Warning : To obtain the effective working conditions of cooling capacity and noise reduction for unit equipped with XLS KIT, please refer to the selection program.

AIR COOLED WATER CHILLER UNITS – AXIAL FANS

EQSL

02.16 Ref. 207598 Rev.100

20

HIGH PRESSURE “EC” AXIAL FANS The "EC" axial fans are equipped with a brushless type synchronous motor with integrated electronic commutated system. The motor rotation control is obtained with the EC system (Electronic Commutation) that manages the motor according to the 0-10V proportional signal coming from the microprocessor control. Characteristics of “EC” motors: - No electromagnetic noise. - Efficiency 83 - 86%. - Minimum power input. The following is a characteristics comparison between an "AC" asynchronous electric motor with phase-cut control (voltage controller) and "EC" brushless type synchronous motor.

Sound pressure level 1 meter far in free field conditions. Warning: The graphs are referred to working condition with null available static pressure (0 Pa).

Po

wer

inpu

t (%

)

So

un

d p

ressu

re (

dB

A)

Electric motor revolutions (RPM)

Electric motor revolutions (%RPM)

Electric motor revolutions (RPM)

AIR COOLED WATER CHILLER UNITS – AXIAL FANS

EQSL

02.16 Ref. 207598 Rev.100

21

TECHNICAL SPECIFICATIONS

**PLEASE, CONSULT WITH OUR COMMERCIAL DEPARTMENT

MODEL 300 V2 F06 320 V2 F06 360 V2 F06 390 V2 F08 430 V2 F08

PARTIAL HEAT RECOVERY

Heating capacity KW 59,5 62,7 66,7 77,8 85,6

Heat recovery water flow m3/h 10,2 10,8 11,5 13,4 14,7

Heat recovery pressure drop KPa 6,6 7,3 8,2 8,9 4,4

TOTAL HEAT RECOVERY

Cooling capacity KW 294 311 333 386 429

Compressor power input KW 100 105 118 129 140

Heating capacity KW 394 417 451 515 570

Heat recovery water flow m3/h 68,5 72,4 78,4 89,5 99,0

Heat recovery pressure drop KPa 62 50 61 63 92

LNO KIT 100%

Fan absorbed power KW 11,6 11,7 11,7 15,4 15,4

Total air flow (1) m3/h 135498 135498 135498 180664 180664

Acoustic power level dBA 90,9 89,4 89,8 89,9 94,2

Acoustic pressure level dBA 71,1 69,7 70,0 69,6 74,0

LNO KIT 85%

Fan absorbed power KW 9,8 9,9 9,9 13,1 13,1

Total air flow (1) m3/h 115173 115173 115173 153564 153564

Acoustic power level dBA 89,9 88,4 88,8 88,9 93,2

Acoustic pressure level dBA 70,1 68,7 69,0 68,6 73,0

LNO KIT 70%

Absorbed power KW 8,1 8,2 8,2 10,8 10,8

Total air flow (1) m3/h 94848 94848 94848 126464 126464

Acoustic power level dBA 86,9 85,4 85,8 85,9 90,2

Acoustic pressure level dBA 67,1 65,7 66,0 65,6 70,0

XLS KIT

Fan absorbed power KW 8,1 8,2 8,2 10,8 10,8

Total air flow (1) m3/h 94848 94848 94848 126464 126464

Acoustic power level dBA 83,9 82,4 82,8 82,9 87,2

Acoustic pressure level dBA 64,1 62,7 63,0 62,6 67,0

AIR COOLED WATER CHILLER UNITS – AXIAL FANS

EQSL

02.16 Ref. 207598 Rev.100

22

**PLEASE, CONSULT WITH OUR COMMERCIAL DEPARTMENT

MODEL 480 V2 F08 530 V2 F08 540 V2 F08 560 V2 F08 610 V2 F08

PARTIAL HEAT RECOVERY

Heating capacity KW 94,7 104,0 108,0 112,0 121,0

Heat recovery water flow m3/h 16,3 17,9 18,6 19,2 20,9

Heat recovery pressure drop KPa 4,1 3,8 3,5 2,6 3,1

TOTAL HEAT RECOVERY

Cooling capacity KW 476 527 551 568 620

Compressor power input KW 157 171 175 183 198

Heating capacity KW 633 699 726 750 818

Heat recovery water flow m3/h 108,0 118,0 126,0 130,0 132,0

Heat recovery pressure drop KPa 94 81 63 69 71

LNO KIT 100%

Fan absorbed power KW 15,4 15,4 15,5 15,6 15,6

Total air flow m3/h 180664 180664 177924 175184 175184

Acoustic power level (1) dBA 94,4 94,7 94,7 94,7 96,2

Acoustic pressure level (2) dBA 74,2 74,4 74,4 74,4 76,0

LNO KIT 85%

Fan absorbed power KW 13,1 13,1 13,2 13,3 13,3

Total air flow m3/h 153564 153564 151235 148906 148906

Acoustic power level (1) dBA 93,4 93,7 93,7 93,7 95,2

Acoustic pressure level (2) dBA 73,2 73,4 73,4 73,4 75,0

LNO KIT 70%

Fan absorbed power KW 10,8 10,8 10,9 10,9 10,9

Total air flow m3/h 126464 126464 124546 122628 122628

Acoustic power level (1) dBA 90,4 90,7 90,7 90,7 92,2

Acoustic pressure level (2) dBA 70,2 70,4 70,4 70,4 72,0

XLS KIT

Fan absorbed power KW 10,8 10,8 10,9 10,9 10,9

Total air flow m3/h 126464 126464 124546 122628 122628

Acoustic power level (1) dBA 87,4 87,7 87,7 87,7 89,2

Acoustic pressure level (2) dBA 67,2 67,4 67,4 67,4 69,0

AIR COOLED WATER CHILLER UNITS – AXIAL FANS

EQSL

02.16 Ref. 207598 Rev.100

23

**PLEASE, CONSULT WITH OUR COMMERCIAL DEPARTMENT

MODEL 650 V2 F08 710 V2 F10 770 V2 F10 850 V2 F10 910 V2 F12

PARTIAL HEAT RECOVERY

Heating capacity KW 128 141 153 170 180

Heat recovery water flow m3/h 22,1 24,2 26,3 29,2 31,0

Heat recovery pressure drop KPa 2,8 2,7 3,2 2,6 2,5

TOTAL HEAT RECOVERY

Cooling capacity KW 668 718 783 878 924

Compressor power input KW 203 230 248 273 290

Heating capacity KW 870 948 1031 1151 1214

Heat recovery water flow m3/h 151 156 179 200 211

Heat recovery pressure drop KPa 69 78 81 86 86

LNO KIT 100%

Fan absorbed power KW 15,6 17,6 19,5 20,1 23,4

Total air flow m3/h 175184 197082 218980 212690 262776

Acoustic power level (1) dBA 97,4 98,1 98,7 98,4 97,8

Acoustic pressure level (2) dBA 77,2 77,4 78,0 77,7 76,8

LNO KIT 85%

Fan absorbed power KW 13,3 14,9 16,6 17,1 19,9

Total air flow m3/h 148906 167519 186133 180786 223359

Acoustic power level (1) dBA 96,4 97,1 97,7 97,4 96,8

Acoustic pressure level (2) dBA 76,2 76,4 77,0 76,7 75,8

LNO KIT 70%

Fan absorbed power KW 10,9 12,3 13,7 14,1 16,4

Total air flow m3/h 122628 137957 153286 148883 183943

Acoustic power level (1) dBA 93,4 94,1 94,7 94,4 93,8

Acoustic pressure level (2) dBA 73,2 73,4 74,0 73,7 72,8

XLS KIT

Fan absorbed power KW 10,9 12,3 13,7 14,1 16,4

Total air flow m3/h 122628 137957 153286 148883 183943

Acoustic power level (1) dBA 90,4 91,1 91,7 91,4 90,8

Acoustic pressure level (2) dBA 70,2 70,4 71,0 70,7 69,8

AIR COOLED WATER CHILLER UNITS – AXIAL FANS

EQSL

02.16 Ref. 207598 Rev.100

24

**PLEASE, CONSULT WITH OUR COMMERCIAL DEPARTMENT

MODEL 950 V2 F12 1060 V2 F16 1120 V2 F16 1180 V2 F16 1310 V2 F16

PARTIAL HEAT RECOVERY

Heating capacity KW 189 212 223 235 261

Heat recovery water flow m3/h 32,5 36,4 38,4 40,5 44,9

Heat recovery pressure drop KPa 3,3 4,1 4,6 5,1 6,2

TOTAL HEAT RECOVERY

Cooling capacity KW 979 1081 1159 1227 1357

Compressor power input KW 298 344 353 368 414

Heating capacity KW 1277 1425 1511 1595 1770

Heat recovery water flow m3/h 222 248 263 277 208

Heat recovery pressure drop KPa 82 105 74 81 86

LNO KIT 100%

Fan absorbed power KW 23,4 30,9 30,9 30,9 31,2

Total air flow (1) m3/h 262776 361328 361328 361328 350368

Acoustic power level dBA 97,8 100,9 100,9 100,9 101,2

Acoustic pressure level dBA 76,8 79,1 79,1 79,1 79,4

LNO KIT 85%

Fan absorbed power KW 19,9 26,2 26,2 26,2 26,5

Total air flow (1) m3/h 223359 307128 307128 307128 297812

Acoustic power level dBA 96,8 99,9 99,9 99,9 100,2

Acoustic pressure level dBA 75,8 78,1 78,1 78,1 78,4

LNO KIT 70%

Absorbed power KW 16,4 21,6 21,6 21,6 21,8

Total air flow (1) m3/h 183943 252929 252929 252929 245257

Acoustic power level dBA 93,8 96,9 96,9 96,9 97,2

Acoustic pressure level dBA 72,8 75,1 75,1 75,1 75,4

XLS KIT

Fan absorbed power KW 16,4 21,6 21,6 21,6 21,8

Total air flow (1) m3/h 183943 252929 252929 252929 245257

Acoustic power level dBA 90,8 93,9 93,9 93,9 94,2

Acoustic pressure level dBA 69,8 72,1 72,1 72,1 72,4

AIR COOLED WATER CHILLER UNITS – AXIAL FANS

EQSL

02.16 Ref. 207598 Rev.100

25

PARTIAL HEAT RECOVERY SYSTEM

**This optional accessory is not compatible with double cooling circuit units.

The partial heat recovery exchanger is installed before the main condenser. The system is not regulated and the control is ON-OFF

type. The heat recovery system’s operation is subject to the supply and demand of cooling capacity.

The system includes:

- Copper brazed plate type heat exchanger with cover plates, plates and connections in AISI 316 stainless steel. - Anticondensate insulation made of polyurethane. - Upon request voltage free contact slot for partial heat recovery water pump activation. The water pump is not supplied.

The heating capacity which is supplied depends on the kind of refrigerant gas which is used and working temperatures. The heat

exchangers can produce hot water up to the maximum temperature of 70-75 °C and according to the working conditions of the unit.

PARTIAL HEAT RECOVERY HYDRAULIC CIRCUIT DIAGRAM

AIR COOLED WATER CHILLER UNITS – AXIAL FANS

EQSL

02.16 Ref. 207598 Rev.100

26

TOTAL HEAT RECOVERY SYSTEM

The total heat recovery exchange is installed in parallel to the main condenser. The system is totally controlled by the microprocessor

and the control is ON-OFF type. The heat recovery system’s operation is subject to the supply demand of cooling capacity.

For each refrigerant circuit the system includes:

- Shell and tube condenser optimized for R134a refrigerant with shell, header, tube sheets made of carbon steel, tubes in Cu. - Anticondensate insulation made of polyurethane. - Antifreeze heater. - Water temperature probe on heat reclaim water inlet. - Diverter valve. - Non return valve. - Liquid receiver. - Safety valve.

**Upon request: voltage free contact for total heat recovery water pump activation. The water pump is not supplied.

The parallel connection of the hydraulic circuit is at Customer care and the water temperature probe is supplied not installed.

TOTAL HEAT RECOVERY HYDRAULIC CIRCUIT DIAGRAM

AIR COOLED WATER CHILLER UNITS – AXIAL FANS

EQSL

02.16 Ref. 207598 Rev.100

27

DIMENSIONS

MODELS 300 – 320 – 360

AIR COOLED WATER CHILLER UNITS – AXIAL FANS

EQSL

02.16 Ref. 207598 Rev.100

28

MODELS 390 – 430 – 480 – 530 – 540 – 560

AIR COOLED WATER CHILLER UNITS – AXIAL FANS

EQSL

02.16 Ref. 207598 Rev.100

29

MODELS 610 – 650

AIR COOLED WATER CHILLER UNITS – AXIAL FANS

EQSL

02.16 Ref. 207598 Rev.100

30

MODELS 710 – 770 – 850

AIR COOLED WATER CHILLER UNITS – AXIAL FANS

EQSL

02.16 Ref. 207598 Rev.100

31

MODEL 910

AIR COOLED WATER CHILLER UNITS – AXIAL FANS

EQSL

02.16 Ref. 207598 Rev.100

32

MODEL 950

AIR COOLED WATER CHILLER UNITS – AXIAL FANS

EQSL

02.16 Ref. 207598 Rev.100

33

MODELS 1060 – 1120 – 1180 – 1310

AIR COOLED WATER CHILLER UNITS – AXIAL FANS

EQSL

02.16 Ref. 207598 Rev.100

34

02.16 Ref. 207598 Rev.100

35

HIPLUS AIRE ACONDICIONADO S.L.

Masia Torrents, 2

Tel. +34 93 893 49 12

Fax. +34 93 893 96 15

08800 Vilanova i la Geltrú

Barcelona, Spain

www.hitecsa.com